1 HVCA Heating and Ventilating Contractors Association Guide to Good Practice Mothballing and Re-commissioning of Buildings SFG30
2 Guide to Good Practice Mothballing and Re-commissioning of Buildings ACKNOWLEDGEMENTS The HVCA wishes to record it s sincere thanks to the following members of the Service and Facilities Group Drafting Committee, without whose direct input of knowledge, time and experience this publication would not have been produced. Malcolm Linsley (Chairman) Richard Bostel Paul Carter Graeme Craig SFG30 The HVCA also wishes to acknowledge the input from Hertel (UK) Ltd, Tri-Star Fire Protection Ltd, The Swimming Pool and Allied Trades Association, the Fire Protection Association, the HVCA Technical Committee and other Groups for their time, input and vetting. ISBN X First Edition HVCA HVCA Heating and Ventilating Contractors' Association Esca House 34 Palace Court London W2 4JG Tel: Fax: contact@hvca.org.uk website: 1
3 FOREWORD Until now, there has existed no published expert guidance on the de-commissioning, mothballing and re-commissioning of buildings a circumstance which has prompted the Service and Facilities Group of the HVCA to take this opportunity to come up with a definition of best practice for shutdown procedures for building services plant, covering the safety and security of the property, interim maintenance and eventual re-commissioning to full function. Drawing on expertise from within the Service and Facilities Group, the Guide to Good Practice on the Mothballing and Re-commissioning of Buildings provides a comprehenisive explication of the minimum requirements for mothballing building services within properties. As is usual with publications of this kind, specialist experts have been consulted and industry consultation has been sought. Acknowledgement must therefore be made of all those who gave their time and knowledge to the compilation and production of this guidance. I should also like to express my personal thanks for the long hours and hard work put in by both members and staff of the Association, and for their efforts to improve standards for our industry. Malcolm Linsley Chairman, Service and Facilities Group Heating and Ventilating Contractors Association 3
4 CONTENTS Acknowledgements Page 1 Foreword Page 3 Definitions Page 6 1. Mothballing Page 7 Building Management System (BMS)/controls Page 7 Compressed Air Systems Page 8 Ventilation Page 9 Cooling Page 10 Electrical Page 11 Fire Alarms Page 12 Emergency Lighting Page 13 Water Hygiene Services Page 14 Plumbing Page 16 Heating Page 17 Chilled Water Systems Page 18 Oil Supply Page 21 Gas Supply Page 22 Swimming Pools Page 23 Catering Services Page 24 Refrigerant Gases Page Re-commissioning Page 27 Compressed air systems Page 27 Emergency Lighting Page 28 Cooling Page 29 Electrical Page 30 BMS/Controls Page 31 Fire alarms Page 32 Water Hygiene Services Page 33 Plumbing Page 36 Heating Page 37 Chilled Water Systems Page 38 Catering Services Page 40 Refrigerant Gases Page 41 Swimming Pools Page Bibliography Page 43 5
5 Guide to Good Practice Mothballing and Re-commissioning of Buildings Definitions OBJECTIVE The HVCA believes that the interests of the industry s customers and of it s member contractors can be enhanced and brought together by the publication of a straight-forward technical specification, (complementary to Statutory Requirements, European and/or British Standards) bringing a clear focus to practical and functional matters. This publication is therefore primarily intended to: Provide information for customers who are appointing (by competition or negotiation) a contractor. Provide a minimum standard for de-commissioning, mothballing and re-commissioning buildings. Provide a standard of practice that may be verified by independent assessment. STANDARD OF WORKMANSHIP The standard set by this publication is intended to be appropriate to most normal commercial, industrial buildings and relates to good practice in de-commissioning, mothballing and re-commissioning of properties without unnecessary elaboration. The HVCA intends this to be significant guidance that meets the requirements of relevant legislation that conforms to accepted industry best practice. QUALITY ASSURANCE This standard can be used as one criterion that will assist customers and specifiers in performing their important role of defining the standard of work they require. The HVCA anticipates that this standard will be complementary to existing quality assurance schemes and quality assessment schedules. SCOPE This standard covers de-commissioning, mothballing and re-commissioning of properties. This standard may be applied to projects in the U.K. and the Republic of Ireland. It is not intended for overseas work; however, some of it s provisions will be appropriate or may form a basis for overseas work. Specialist equipment such as passenger transport systems and fire suppression systems are not covered in this document and guidance should be sought from manufacturers operating and maintenance manuals. This publication makes use of terms should, shall and must when prescribing procedures: 1.The term must identifies a requirement by law at the time of publication. 2.The term shall prescribes a procedure which, it is intended to be complied with, in full and without deviation. 3.The term should prescribes a procedure which, it is intended to be complied with unless, after prior consideration, deviation is considered to be acceptable. HAZARDOUS WASTE/REFRIGERANTS Hazardous waste and refrigerant gases found on premises will require a risk assessment to determine whether they can be stored in situ during the shutdown period, or if they require disposal. The Hazardous Waste Regulation (England and Wales) 2005 replaced the Special Waste Regulations and brought some Controlled Wastes into the same regime for handling and disposal. All waste that is listed in the European Waste Catalogue (EWC) must now be handled under the requirements of the new Hazardous Waste Regulations. Under the Environmental Protection Act and the Hazardous Waste Regulations you have a Duty of Care to ensure that the company you select to handle your Hazardous Waste is operating correctly and will handle your waste in an acceptable and approved manner. HAZARDOUS WASTE SCOTLAND: Hazardous Waste produced in Scotland is controlled by the Special Waste Amendment (Scotland) Regulations 2004, even if the waste is to be transferred to England and Wales for recycling, the Scotland Regulations take precedence. The Regulations are managed by the Scottish Environment Protection Agency (SEPA). Any movement of such waste must be pre-notified to SEPA, 3 working days before the waste is moved. HAZARDOUS WASTE NORTHERN IRELAND: Hazardous Waste produced in Northern Ireland is controlled by the Special Waste Regulations (Northern Ireland) The Regulations are managed by The Environment and Heritage Service (EHS). Any movement of such waste must be pre-notified to EHS 3 working days before the waste is moved. PUBLICATION AND REVIEW User feedback on the wording or the requirements of the standard will be welcomed to assist in continued updating. 6
The Legal Obligations of Employers to Maintain all Electrical Installations in a Safe Condition
The Legal Obligations of Employers to Maintain all Electrical Installations in a Safe Condition Issued in the interests of safety by The Legal Obligations of Employers to Maintain all Electrical Installations
More informationCORRECTIONS WITHIN DESIGN MANUAL FOR ROADS AND BRIDGES AUGUST 2009
DESIGN MANUAL FOR ROADS AND BRIDGES CORRECTIONS WITHIN DESIGN MANUAL FOR ROADS AND BRIDGES AUGUST 2009 SUMMARY OF CORRECTION HA 200/08 VOLUME 11, SECTION 1, PART 1 AIMS AND OBJECTIVES OF ENVIRONMENTAL
More informationAustralian/New Zealand Standard
AS/NZS 3760:2003 (Incorporating Amendment No. 1) AS/NZS 3760:2003 Australian/New Zealand Standard In-service safety inspection and testing of electrical equipment AS/NZS 3760:2003 This Joint Australian/New
More informationFIRE RISK ASSESSMENT COMPETENCY COUNCIL
FIRE RISK ASSESSMENT COMPETENCY COUNCIL A Guide to Choosing a Competent Fire Risk Assessor Version 2 Published 29/4/14 The Fire Risk Assessment Competency Council is a workstream consisting of the major
More informationCD/12 Form (Landlord Oil Installation Check)
CD/12 Form (Landlord Oil Installation Check) Diagram 47a 1 2 3 4 5 6 7 8 9 10 2010 Edition Section 7 Page 9 7.5 CD/14 (Warning & Advice Notice) 7.5.1 General This form can be used to formally notify oil
More informationGuided Learning Hours (GLH) 4 Invigilated Assessment (IA) 1 Total Qualification Time (5)
Qualification: Date Completed: 31 Jan 17 Unit: FIA AO Level 2 Environmental for Field Service Technicians Development Group: FD&A Development Group Guided Learning Hours (GLH) 4 Invigilated Assessment
More informationCertificate No: EWS534
Certificate No: EWS534 Plumis Automist Smartscan Hydra Description of Product This is an assessment of the Plumis Automist multiroom Smartscan Hydra targeted fire suppression system. The system utilises
More informationLoss Prevention Standard
Loss Prevention Standard LPS 1500: Issue 2.1 provide compartmentation in buildings This standard defines the requirements for companies installing fire resisting compartment systems approved by LPCB to
More informationElectrical Safety Policy and Management System
TITLE: PAGE: 1 OF 14 Housing Solutions Limited Electrical Safety Policy and Management System Page 1 of 15 TITLE: PAGE: 2 OF 14 FOREWORD This document details the system for the management of electrical
More informationLicensed exclusively to SABS. Copying and network storage prohibited.
ICS 29.240.20 ISBN 0-626-10879-9 SABS 0198-14* *This standard references other standards Edition 2 1996 SOUTH AFRICAN STANDARD Code of practice The selection, handling and installation of electric power
More informationSection 2 - Applications - General. Section 2A - FD30 Strebord 35+, 38+, 44 & Superpan with MDF & Wood Frames
Section 2 - Applications - General Section 2A - FD30 Strebord 35+, 38+, 44 & Superpan with MDF & Wood Frames Section 2B - FD30 Strebord 35+, 38+, 44, Superpan & Strebord 54 with Steel Frames Section 2C
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-22437-0 Any reference to SABS 0114-2 is deemed to be a reference to this standard (Government Notice No. 1373 of 8 November 2002) SOUTH AFRICAN NATIONAL STANDARD Interior lighting Part 2:
More informationvolume 11 environmental assessment section 2 environmental impact assessment Part 7 ha 218/08
DESIGN MANUAL FOR ROADS AND BRIDGES volume 11 environmental assessment section 2 environmental impact assessment Part 7 ha 218/08 glossary of terms Used in DMRB Volume 11, Sections 1 and 2 SUMMARY This
More informationAS/NZS 3820:2009 (Incorporating Amendment 1) Essential safety requirements for electrical equipment
AS/NZS 3820:2009 (Incorporating Amendment 1) Essential safety requirements for electrical equipment AS/NZS 3820:2009 This Joint Australian/New Zealand Standard was prepared by Joint Technical Committee
More informationThe Association for Specialist Fire Protection
The Association for Specialist Fire Protection An Association for Specialist Fire Protection CPD Event Understanding the Disciplines of Passive Fire Protection 17 th June 2015 In association with The Association
More informationvolume 11 environmental assessment section 2 environmental impact assessment Part 2 ha 202/08 environmental impact assessment
DESIGN MANUAL FOR ROADS AND BRIDGES volume 11 environmental section 2 environmental impact Part 2 ha 202/08 environmental impact SUMMARY This Advice Note provides guidance for undertaking statutory and
More informationLoss Prevention Standard
Loss Prevention Standard LPS 1531: Issue 1.1 companies installing or applying passive fire protection This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for
More informationAustralian/New Zealand Standard
AS/NZS 3666.2:2011 AS/NZS 3666.2:2011 Australian/New Zealand Standard Air-handling and water systems of buildings Microbial control Part 2: Operation and maintenance AS/NZS 3666.2:2011 This Joint Australian/New
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-26992-0 SOUTH AFRICAN NATIONAL STANDARD Fire detection and alarm systems for buildings System design, installation and servicing Published by SABS Standards Division 1 Dr Lategan Road Groenkloof
More informationBest Practice Guide. Windows and Doors. Single-axis hinges to BS EN
Windows and Doors Single-axis hinges to BS EN 1935 www.dhfonline.org.uk 01 dhf Best Practice dhf Best Practice : Windows and Doors - Single-axis hinges to BS EN 1935 dhf Best Practice s This publication
More informationSubstations and high voltage installations exceeding 1 kv a.c.
AS 2067:2016 AS 2067:2016 Substations and high voltage installations exceeding 1 kv a.c. This Australian Standard was prepared by Committee EL-043, High Voltage Installations. It was approved on behalf
More informationConsumer unit replacement in domestic and similar premises
Consumer unit replacement in domestic and similar premises 6 Issue 2 The Electrical Safety Council is indebted to the following organisations for their contribution and/or support to the development of
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-30385-3 SOUTH AFRICAN NATIONAL STANDARD The installation, maintenance, repair and replacement of domestic solar water heating systems WARNING This document references other documents normatively.
More informationAustralian Standard. Closed circuit television (CCTV) Part 4: Remote video AS AS
AS 4806.4 2008 AS 4806.4 2008 Australian Standard Closed circuit television (CCTV) Part 4: Remote video This Australian Standard was prepared by Committee EL-051, Non-Broadcast Television. It was approved
More informationAustralian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS
AS 4214 2002 (Incorporating Amendment No. 1) AS 4214 2002 Australian Standard Gaseous fire extinguishing systems This Australian Standard was prepared by Committee FP-011, Gaseous Fire Protection. It was
More informationLakanal House inquest: Statement from the Fire Sector Federation
Lakanal House inquest: Statement from the Fire Sector Federation The Fire Sector Federation (FSF) wishes to express profound sadness for the tragic loss of life that occurred at Lakanal House on the 3
More information6.6.3 Minimum Provision for New Systems in New Dwellings Minimum Provision for New/Replacement Systems in Existing Dwellings
6.6.3 Minimum Provision for New Systems in New Dwellings All oil fired boilers installed on or after 1 st April 2008 shall have a minimum seasonal HARP (Home-heating Appliance Register of Performance)
More informationSummary of changes between PD 6662:2010 and PD 6662:2017 a guide
Summary of changes between PD 6662:2010 and PD 6662:2017 a guide October 2017 For other information please contact: British Security Industry Association t: 01905 342 020 e: info@bsia.co.uk www.bsia.co.uk
More informationBACKGROUND AND INTRODUCTION FRAMEWORK AGREEMENT FOR SELF-CONTAINED BREATHING APPARATUS, ASSOCIATED EQUIPMENT AND SERVICES REF: DS
BACKGROUND AND INTRODUCTION FRAMEWORK AGREEMENT FOR SELF-CONTAINED BREATHING APPARATUS, ASSOCIATED EQUIPMENT AND SERVICES REF: DS 072-11 CONTENTS INTRODUCTION... 1 SCOPE OF FRAMEWORK AGREEMENT... 2 PROCUREMENT
More informationRIBA response to the second phase of the Independent Review of Building Regulations and Fire Safety
RIBA response to the second phase of the Independent Review of Building Regulations and Fire Safety The RIBA is concerned that the current approach of the Independent Review of Building Regulations and
More informationThank you for your letter of 26 June regarding the Committee s scrutiny of building regulations in Scotland.
Minister for Local Government and Housing Kevin Stewart MSP T: 0300 244 4000 E: scottish.ministers@gov.scot Bob Doris MSP Convener Local Government and Communities Committee The Scottish Parliament EDINBURGH
More informationTechnical Specification for Remote Controlled Temporary Traffic Management Signs for use on the Highways Agency Strategic Road Network
Technical Specification for Remote Controlled Temporary Traffic Management Signs for use on the Highways Agency Strategic Road Network First published Printed and published by the Highways Agency Page
More informationBuilding Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems
Building Standards Division Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems Crown Copyright 2015 Produced by the Buildings Standards Division February 2015 Version
More informationFor the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems
BAFE Scheme: SP203-1 Version 7.1: January 2019 FIRE SAFETY REGISTER Fire Protection Industry Scheme, Reference SP203-1 For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire
More informationAustralian/New Zealand Standard
AS/NZS 2243.5 Australian/New Zealand Standard Safety in laboratories Part 5: Non-ionizing radiations Electromagnetic, sound and ultrasound This Joint Australian/New Zealand Standard was prepared by Joint
More informationAS/NZS :2014
(ISO 13857:2008, IDT) Australian/New Zealand Standard Safety of machinery Part 1801: Safety distances to prevent danger zones being reached by upper and lower limbs AS/NZS 4024.1801:2014 This joint Australian/New
More informationFIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017
Date: March 2017 Page 1 of 12 FIRE SAFETY POLICY Approval Approved by: University Court Date: March 28 th 2017 Page 1 of 12 Date: March 2017 Page 2 of 12 UNIVERSITY OF ABERDEEN FIRE SAFETY POLICY Contents
More informationAustralian Standard. Fire protection for mobile and transportable equipment AS AS
AS 5062 2006 AS 5062 2006 Australian Standard Fire protection for mobile and transportable equipment This Australian Standard was prepared by Committee FP-022, Fire Protection of Mobile Transportable Equipment.
More informationSFA Guide to Building Regulations and Solid Fuel Heating
SFA Guide to Building Regulations and Solid Fuel Heating Solid Fuel Association 95 High Street Clay Cross Chesterfield Derbyshire S45 9DZ 01773 835400 www.solidfuel.co.uk Building Regulations and Solid
More informationCARE GUIDANCE. Local Exhaust Ventilation (LEV) Systems for High Temperature Insulation Wool (HTIW) LEVEL 2 RECOMMENDATIONS ON BEST PRACTICE
PUBLICATION: MAY 2012 REVISION: JANUARY 2018 VERSION: 1.2 CARE GUIDANCE RECOMMENDATIONS ON BEST PRACTICE LEVEL 2 Local Exhaust Ventilation (LEV) Systems for High Temperature Insulation Wool (HTIW) 2 LOCAL
More informationFire and Rescue Services Act 2004 Factsheet
Fire and Rescue Services Act 2004 Factsheet Summary of the Act s key provisions The Fire and Rescue Services Act 2004 ( the Act ) received Royal Assent on July 22nd. It replaces the Fire Services Act 1947,
More informationDepartment of the Environment Transport and the Regions Building Regulations Division
BR: CPD (top page) (br12a0.htm) Department of the Environment Transport and the Regions Building Regulations Division Construction Products Directive Introduction These pages explain the background to
More informationDESIGN AND MANAGEMENT OBJECTIVES PART 7 HA 92/01 SCHEME DEVELOPMENT, IMPLEMENTATION & MANAGEMENT SUMMARY
DESIGN MANUAL FOR ROADS AND BRIDGES VOLUME 10 SECTION 0 ENVIRONMENTAL DESIGN AND MANAGEMENT ENVIRONMENTAL OBJECTIVES PART 7 HA 92/01 SCHEME DEVELOPMENT, IMPLEMENTATION & MANAGEMENT SUMMARY This Advice
More informationElected Members School Exeter 2009 A planning refresher for elected members
Elected Members School Exeter 2009 A planning refresher for elected members David Hackforth Head of Planning, Milton Keynes Council President Planning Officers Society Elected Members School Exeter 2009
More informationAustralian Standard. Electroacoustics Sound calibrators AS IEC This is a free 7 page sample. Access the full version online.
AS IEC 60942 2004 IEC 60942:2003 AS IEC 60942 Australian Standard Electroacoustics Sound calibrators This Australian Standard was prepared by Committee AV-002, Acoustics Instrumentation and Measurement
More informationEnvironmental Assessment (Scotland) Act 2005: Clackmannanshire Council Sustainability Strategy Scoping Request
TAYSIDE & CLACKMANNANSHIRE Tel: 01738 458582(direct line) Fax: 01738 458616 e-mail addresses: denise.reed@snh.gov.uk Niall Urquhart Team Leader Sustainability Clackmannanshire Council Kilncraigs Greenside
More informationMULTIKWIK SEWER SYSTEMS MULTIKWIK WC PAN CONNECTORS
DHM Plastics Ltd Dickley Lane Lenham Maidstone Kent ME17 2DE Tel: 01622 858888 Fax: 01622 858725 e-mail: info@multikwik.com website: www.multikwik.com APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL
More informationA GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO)
4 PEEL HOUSE,TAUNTON STREET,SHIPLEY,BN18 3NA TEL: 01274 595015 FAX: 01274 580804 EMAIL:sales@rosse-systems.co.uk A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO) THE PURPOSE OF THIS DOCUMENT
More informationProtocol between Local Housing Authorities and Fire and Rescue Authorities to improve fire safety
Protocol between Local Housing Authorities and Fire and Rescue Authorities to improve fire safety Foreword by Communities and Local Government Ministers It is always a priority to ensure safety from the
More informationFORUM FOG FOOD SERVICE INDUSTRY FATS OILS AND GREASE CODE OF PRACTICE SUPPORTED BY
FOOD SERVICE INDUSTRY FATS OILS AND GREASE CODE OF PRACTICE FOG FORUM SUPPORTED BY 1 DEM FACCUPTDO- TABLE OF CONTENTS Introduction FOG Management Legislation and Regulation Site Evaluation Equipment Solutions
More informationEMERGENCY LIGHTING COMPLETION CERTIFICATE For small installations and verification of existing installations
A DETAILS OF THE CLIENT Client/ B DETAILS OF THE EMERGENCY LIGHTING INSTALLATION Extent of the installation covered by this certificate The Owner 19 Walker Grove, Hatfield, Hertfordshire 19 Walker Grove,
More informationLegal Requirements. There is no general legal requirement to install sprinklers. in places of work
01 A sprinkler system is a pipework distribution system charged with water, with a network of heatsensitive sprinkler heads supplied via a tank/reservoir or a water main. If the temperature rises above
More informationFire Safety Management
Fire Safety Management Procedure () FIRE SAFETY MANAGEMENT PROCEDURE Contents Section 1: Management of Fire Safety Procedure in Operation Section 2 Organisational responsibilities Section 3: Emergency
More informationCOMPRESSION PLUMBING SOLUTIONS CONNECT WITH CONFIDENCE
COMPRESSION PLUMBING SOLUTIONS CONNECT WITH CONFIDENCE CONNECT WITH CONFIDENCE With a wealth of expertise and the broadest range of solutions and systems on the market, Pegler Yorkshire s Connect products
More informationAustralian Standard. Security screen doors and security window grilles AS AS 5039
AS 5039 2003 AS 5039 Australian Standard Security screen doors and security window grilles This Australian Standard was prepared by Committee CS-023, Security Screen Doors and Security Window Grilles.
More informationCERTIFICATE OF APPROVAL No CF 418 PROMAT UK LTD
CERTIFICATE OF APPROVAL No CF 418 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of The Sterling Centre,
More informationFire detection and alarm systems. Part 4: Power supply equipment (ISO :2003, MOD) AS (Incorporating Amendment No.
AS 7240.4 2004 (Incorporating Amendment No. 1) AS 7240.4 2004 Fire detection and alarm systems Part 4: Power supply equipment (ISO 7240-4:2003, MOD) This Australian Standard was prepared by Committee FP-002,
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-22587-2 RSR 001:2009 SOUTH AFRICAN NATIONAL STANDARD Railway safety management Part 1: General Published by SABS Standards Division 1 Dr Lategan Road Groenkloof Private Bag X191 Pretoria
More informationAS/NZS :2009. Performance of household electrical appliances Refrigerating appliances AS/NZS :2009
AS/NZS 4474.2:2009 (Incorporating Amendment Nos 1 and 2) Australian/New Zealand Standard Performance of household electrical appliances Refrigerating appliances Part 2: Energy labelling and minimum energy
More informationHardware for Sliding Doors & Folding Doors
Hardware for Sliding Doors & Folding Doors A Best Practice to BS EN 1527:2013 www.dhfonline.org.uk 01 dhf Best Practice dhf Best Practice : Hardware for Sliding Doors and Folding Doors A Best Practice
More informationFIRE RISK ASSESSMENT AND PROTECTION
Tower Stewardship Committee Guidance Note No. 6 FIRE RISK ASSESSMENT AND PROTECTION This guidance note gives guidance to ringers, parochial church councils and clergy regarding Fire Safety affecting the
More informationvolume 11 environmental assessment section 2 environmental impact assessment Part 4 ha 204/08 scoping of environmental impact assessments
DESIGN MANUAL FOR ROADS AND BRIDGES volume 11 environmental assessment section 2 environmental impact assessment Part 4 ha 204/08 scoping of environmental impact assessments SUMMARY This Advice Note provides
More informationNZS 4517:2010. New Zealand Standard. Fire sprinkler systems for houses. Superseding NZS 4517:2002 NZS 4517:2010
New Zealand Standard Fire sprinkler systems for houses Superseding NZS 4517:2002 NZS 4517:2010 NZS 4517:2010 COMMITTEE REPRESENTATION This Standard was prepared under the supervision of the P 4517 Committee,
More informationNon-domestic gas installations (Edition 2)
Irish Standard I.S. 820:2010 Non-domestic gas installations (Edition 2) NSAI 2010 No copying without NSAI permission except as permitted by copyright law. I.S. xxx: Irish Standard national specification
More informationAustralian/New Zealand Standard
AS/NZS 3004:2002 AS/NZS 3004 Australian/New Zealand Standard Electrical installations Marinas and pleasure craft at low-voltage AS/NZS 3004:2002 This Joint Australian/New Zealand Standard was prepared
More informationIGEM/UP/17 Edition 2 Communication 1826 Shared chimney and flue systems for domestic gas appliances
Communication 1826 Shared chimney and flue systems for domestic gas appliances Founded 1863 Royal Charter 1929 Patron: Her Majesty the Queen Communication 1826 Shared chimney and flue systems for domestic
More informationFixing the Foundations Statement
Fixing the Foundations Statement 13 th August 2015 The Heritage Alliance is the largest coalition of non-government heritage interests in England, bringing together 98 national organisations which are
More informationFor the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems
BAFE Scheme: SP203-1 Version 5: May 2011 Fire Protection Industry Scheme, Reference SP203 Part 1 For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems British
More informationStrebord 35 FD30 Strebord 44 FD30 Strebord 54 FD60
.1 Strebord 35 FD30 Strebord 44 FD30 Strebord 54 FD60 Falcon Panel Products Ltd Clock House Station Approach Shepperton Middlesex TW17 8AN Strebord Technical Manual (Version 9.1) Validation of Data against
More informationAustralian/New Zealand Standard
AS/NZS 2033:2008 AS/NZS 2033:2008 Australian/New Zealand Standard Installation of polyethylene pipe systems AS/NZS 2033:2008 This Joint Australian/New Zealand Standard was prepared by Joint Technical Committee
More informationLANDSCAPE INSTITUTE CORPORATE STRATEGY ISSUED 3RD APRIL Landscape Institute 107 Grays Inn Road London WC1X 8TZ United Kingdom
LANDSCAPE INSTITUTE CORPORATE STRATEGY ISSUED 3RD APRIL 2018 Landscape Institute 107 Grays Inn Road London WC1X 8TZ United Kingdom MISSION The Landscape Institute (LI) aims to lead and inspire the landscape
More informationControlled Door Closing Devices
Controlled Door Closing Devices to BS EN 1154: 1997 + A1:2003 www.dhfonline.org.uk 01 dhf Best Practice dhf Best Practice : Controlled Door Closing Devices to BS EN 1154: 1997 + A1:2003 dhf Best Practice
More informationRRC SAMPLE MATERIAL MANAGING FIRE SAFETY LEARNING OUTCOMES
MANAGING FIRE SAFETY LEARNING OUTCOMES On completion of this element, you should be able to demonstrate understanding of the content by applying what you have learnt to familiar and unfamiliar situations.
More informationStandards and Standardisation. An Overview
Standards and Standardisation An Overview Therese Clarke Standards Development 1 NSAI Technical Committee 58/SCI Published - I.S. 398-1:2013 Reactive pyrite in sub-floor hardcore material Part 1 Testing
More information1 2 3 Licence No:
TRICS 2007(a) 06/05/07 Page 1 of 6 List of TRICS Research Publications TRICS Report 89/1 Traffic Generation Study of Offices & High Tech Sites London Borough of Hillingdon The report contains detailed
More informationAS/NZS :2014
AS/NZS 4024.1601:2014 (EN 953:1997 inc A1:2009, IDT) Australian/New Zealand Standard Safety of machinery Part 1601: Design of controls, interlocks and guarding Guards General requirements for the design
More informationAustralian/New Zealand Standard
AS/NZS 4692.1:2005 (Incorporating Amendment Nos 1 and 2) Reconfirmed 2016 AS/NZS 4692.1:2005 A2 Australian/New Zealand Standard Electric water heaters Part 1: Energy consumption, performance and general
More informationAS/NZS :2014
AS/NZS 4755.3.3:2014 Australian/New Zealand Standard Demand response capabilities and supporting technologies for electrical products Part 3.3: Interaction of demand response enabling devices and electrical
More informationPreventing deaths and injuries in the home in Scotland
Preventing deaths and injuries in the home in Scotland www.electricalsafetyfirst.org.uk Electrical Safety First Preventing deaths and injuries in the home in Scotland 1 2 Electrical Safety First Preventing
More informationAppropriate Assessment in relation to County Donegal Draft Heritage Plan
Appendix 12 - Consultation Response a) Sinead Harkin Central Planning Unit Donegal County Council County House Lifford County Donegal Dear Ms Harkin, Appropriate Assessment in relation to County Donegal
More informationCommercial Waste and Recycling Facilities. Site User Information
Commercial Waste and Recycling Facilities Site User Information Commercial Waste Facilities Site User Information This leaflet is designed as a guide for businesses wishing to use the waste transfer station
More informationTudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website:
Fact File No 0055 Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0)20 3166 5002 Website: www.fia.uk.com Watermist Systems 1. INTRODUCTION Over the past twenty
More informationAustralian/New Zealand Standard
AS/NZS 1338.1:2012 AS/NZS 1338.1:2012 Australian/New Zealand Standard Filters for eye protectors Part 1: Filters for protection against radiation generated in welding and allied operations AS/NZS 1338.1:2012
More informationAustralian/New Zealand Standard
AS/NZS 4692.1:2005 AS/NZS 4692.1:2005 Australian/New Zealand Standard Electric water heaters Part 1: Energy consumption, performance and general requirements AS/NZS 4692.1:2005 This Joint Australian/New
More informationThe Association for Specialist Fire Protection. Understanding Best Practice in passive fire protection
The Association for Specialist Fire Protection Understanding Best Practice in passive fire protection Niall Rowan, Technical Officer Association for Specialist Fire Protection The Association for Specialist
More informationFire prevention and protection
Fire prevention and protection The Fire Service College With over 40 years experience, the Fire Service College is a leading organisation for fire prevention, protection and response, providing assessed,
More informationBritish Columbia Landscape Standard. Published by:
British Columbia Landscape Standard Published by: British Columbia Society of Landscape Architects British Columbia Landscape and Nursery Association BC Landscape Standard 2012 The British Columbia Landscape
More informationCompilation of regulatory approaches used in various countries. Information received by the Secretariat through a survey in 2009
Compilation of regulatory approaches used in various countries Information received by the Secretariat through a survey in 2009 At its seventeenth session, the Working Party mandated the Sectoral Initiative
More informationWE ARE LOWE. EST. 1977
WE ARE LOWE. EST. 1977 LOWE S JOURNEY Lowe developed strong presence in global exhibition market Expansion period commences - entered new markets including events and retail New board appointed. Opened
More informationLink-Up. Solid Fuel Association Guide to Central Heating.
Solid Fuel Association Guide to Central Heating Link-Up Combining solid fuel with other central heating technologies using various methods ranging from a simple link-up to a fully integrated thermal store
More informationISO INTERNATIONAL STANDARD. Safety identification Escape and evacuation plan signs. Identification de sécurité Plans d'évacuation et de secours
INTERNATIONAL STANDARD ISO 23601 First edition 2009-02-15 Safety identification Escape and evacuation plan signs Identification de sécurité Plans d'évacuation et de secours Reference number ISO 23601:2009(E)
More informationGuidance Note. Visual Alarm Devices: Conflict between BS 5839 and EN 54-23
Guidance Note Visual Alarm Devices: Conflict between BS 5839 and EN 54-23 Visual Alarm Devices: Conflict between BS 5839 and EN 54-23 INTRODUCTION... 3 EXTENSION OF THE COEXISTENCE PERIOD FOR EN 54-23...
More informationPanic and Emergency Exit Devices
Panic and Emergency Exit Devices BS EN 1125: 2008 & BS EN 179: 2008 www.dhfonline.org.uk 01 dhf Best Practice dhf Best Practice : Panic and Emergency Exit Devices BS EN 1125: 2008 & BS EN 179: 2008 dhf
More informationCERTIFICATE OF APPROVAL No CF 5507 CONSORT ARCHITECTURAL HARDWARE LTD
1 CERTIFICATE OF APPROVAL No CF 5507 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 29-31 Lower Loveday
More informationImplementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -
TF N 687rev1 2015-06-02 CONSTRUCTION SECTOR STANDARDIZATION GUIDANCE DOCUMENT Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - 1 I - Drafting
More informationCONTRACTOR WHS HAZARD STANDARD LASER SAFETY EXTERNAL USE ONLY
CONTRACTOR WHS HAZARD STANDARD LASER SAFETY EXTERNAL USE ONLY Principles in the Optus Contractor WHS management process CONTRACTOR MANAGEMENT STAGES PRINCIPLES THIS STANDARD REQUISITION Requisition WHS
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-30262-7 SOUTH AFRICAN NATIONAL STANDARD The installation, inspection and maintenance of equipment used in explosive atmospheres Part 1: Installations including surface installations on mines
More informationAS/NZS 4821:2014. Protective footwear for firefighters Requirements and test methods AS/NZS 4821:2014. Australian/New Zealand Standard
Australian/New Zealand Standard AS/NZS 4821:2014 (EN 15090:2012, MOD) Protective footwear for firefighters Requirements and test methods Superseding AS/NZS 4821:2006 AS/NZS 4821:2014 This standard, is
More informationAustralian/New Zealand Standard
AS/NZS 61779.6:2000 (Incorporating Amendment No. 1) AS/NZS 61779.6:2000 Australian/New Zealand Standard Electrical apparatus for the detection and measurement of flammable gases Part 6: Guide for the selection,
More informationPROFESSIONAL KITCHEN CLEANING. New Kitchen Ventilation Systems supplied and fitted at competitive rates
New Kitchen Ventilation Systems supplied and fitted at competitive rates About Us As a restaurant owner for over 25 years, I became aware of the difficulties of obtaining the services of a professional
More information