1 The Space Congress Proceedings 1969 (6th) Vol. 2 - Space, Technology, and Society Apr 1st, 8:00 AM The Design, Testing, and Implementation of a Halon 1301 Fire Extinguishment System for Use in the Service Lunar Adapter at KSC Launch Complex 39 J. T. Myers Catalytic-Dow D. C. Weaver Catalytic-Dow Follow this and additional works at: Scholarly Commons Citation Myers, J. T. and Weaver, D. C., "The Design, Testing, and Implementation of a Halon 1301 Fire Extinguishment System for Use in the Service Lunar Adapter at KSC Launch Complex 39" (1969). The Space Congress Proceedings This Event is brought to you for free and open access by the Conferences at Scholarly Commons. It has been accepted for inclusion in The Space Congress Proceedings by an authorized administrator of Scholarly Commons. For more information, please contact commons@erau.edu.

2 THE DESIGN, TESTING AND IMPLEMENTATIN F A HALN 1301 FIRE.EXTINGUISHMENT SYSTEM FR USE IN THE APLL/SATURN LUNAR MDULE ADAPTER AT KENNEDY SPACE CENTER LAUNCH CMPLEX 39 David C. Weaver Catalytic-Dow Titusville, Florida INTRDUCTIN Since the advent of hypergolic fuels usage at the Kennedy Space Center and the Kennedy Air Force Station, personnel safety during fueling opera tions has been provided by limiting the number of persons having access to hazardous areas to those who were essential to the operation, and by providing these people with protective clothing. With the Apollo Program, a new problem has introduced itself; the Lunar Module (LM) (Fig. 1) is actually two launch vehicles which leave the launch pad as part of the Apollo payload. Fueling of these launch vehicles takes place approximately two weeks before the launch of the Apollo/Saturn V. Personnel are required to continue servicing the LM after fueling; this requires them to be enclosed within the Saturn/ Lunar Module Adapter (SLA). Special egress equipment has been installed but will not be discussed in this presentation. To minimize the hazard of a flash fire resulting from the ignition of a spilled hypergol, a Halon 1301 (bromotriflouromethane) protection system has been designed and has been available during the launches of AS-204 and AS-504. Since im provements over the original system which was installed at Launch Complex 37 were incorporated into the design of the system for Launch Complex 39, our discussion will deal only with the Launch Complex 39 system. DESIGN The responsibility for the design of the Halon 1301 Fire Extinguishment Systems was given to the Kennedy Space Center, Design Engineering, Facilities Branch (DE-FAC). Catalytic-Dow, the facilities support contractor for NASA Kennedy Space Center perations supported DE-FAC in this assignment. Utilizing studies performed by the Explosive Research Center, in the United States Bureau of Mines, it was determined that any atmosphere will be relatively inert to an energy ignition of a spilled hypergol, if the atmosphere contains 10% by volume of Halon To extinguish a burning hypergol which had been ignited by an energy source, 20% by volume of Halon 1301 was found to be required.1 (Research by others in this field has revealed that the extinguishment of less exotic materials can be achieved by concentration no greater than 6%). Research performed by toxicologists has indicated that short-time human exposure to concentration in this range will not cause a high degree of risk to humans. A system was to be designed, therefore, that would permit occupants of the SLA to egress in relative safety in the advent of a spill, and would sustain a 20% by volume Halon 1301 atmos phere until the problem causing the spill could be corrected. Due to the precise nature of work performed within the SLA, highly conditioned air is introduced in large quantities (3,200 standard cubic feet per minute into a volume of 6,000 cubic feet). Because the Halon 1301 system was to be installed on the work platforms of the Mobile Service Structure, care was taken to utilize the lightest available material compatible with its usage. The extinguishing agent is injected as a liquid and vaporizes on leaving the delivery nozzles; therefore, further consideration was given to minimize the possibility that the low temperature discharge would directly impinge upon occupants of the SLA or damage the SLA or LM. This con sideration was required because a change of temperature of as much as 140 Fahrenheit could be experienced in the immediate vicinity of the discharge nozzles. SYSTEM DESCRIPTIN The system is made up of three basic subsystems, two of which are Halon 1301 Storage and Delivery Subsystems; the third is the Control Subsystem. Since Halon 1301 breaks down into toxic by-pro ducts when exposed to temperatures in excess of 800 centigrade, it was determined that the initial application of the agent must be rapid. Extinguishment will occur within milliseconds of achieving the required concentrations. This requirement is achieved by the first subsystem which consists of six 85-pound containers and their associated valves and piping which have been placed in groups of two, at three different locations (Figures 2 and 3). Each group enters the SLA from a different access point. The access points were selected to provide as close a uniform dispersement as possible in accordance with operational demands. The second subsystem consists of three 1-ton cylinders of the extinguishing agent, manifolded in such a way that the discharge from these cylinders enters the SLA through a common piping system which utilizes the same entrance ports as the first system. The Halon 1301 stored in the containers is pressurized with nitrogen to 600 psi, which remains constant throughout discharge (Figures 2 and 3). The piping system is so designed, a sustained rate of flow of either 2.3 or 4.6 pounds per minute can be introduced into the SLA. 8-5

3 The Control Subsystem is so designed that by actuating one switch, the operator can release half (255 pounds) of the rapid discharge system into the SLA and activate a flow rate of 2.3 pounds per minute from the sustaining system. The actuation of another switch can simultan eously release the total contents of the rapid discharge system, and activate the flow rate of 4.6 pounds per minute from the sustaining system. PERATINAL CNCEPTS The Halon 1301 system has been designed to have two modes of operation. The first mode (Inert Mode) is to be used if a hypergol spill is de-. tected within the SLA. After the system has been armed, by throwing a single toggle switch, the 10% switch is thrown, causing the immediate release of a 10% concentration of the halon, and a sustaining flow of approximately 2.3 pounds per second. The second mode of.operation (Extinguish Mode) will be used if a fire is detected within the SLA. After arming as de scribed previously, the Extinguish switch is thrown, releasing a 20% concentration which will extinguish the fire and initiate a flow of 4.3 pounds per second which will prevent re- ignition. Concentration versus time curves are provided in Figures 4 and 5. BIBLIGRAPHY 1. Van Dolan, R. W.: Prevention and Extinguish ment of Fires Involving Hyperbolic Propel- lants. Explosive Research Center, Bureau of Mines, Pittsburgh, Pennsylvania. July 31, Hine, C. H.: Clinical Toxicologic Studies on "Freon" FE The Hine Laboratories, Inc., San Francisco, California. January TESTING In the fall of 1968, tests were conducted utilizing full scale mockups for a major portion of the test program. Test results indicated that concentration of Halon 1301 which would inert or extinguish would be obtained within 2 seconds of activation, and that the sustaining system would prevent combustion for a period of not less than 20 minutes. The rapid introduction of this quantity of Halon 1301 into the SLA did not cause critical overpressures because of the associated cooling. Sound pressure levels reached 120 decibels for periods not exceeding 20 milliseconds. While this approaches the threshold of pain, the short duration minimizes the probability of permanent ear damage. While the Halon 1301 gas is colorless and odor less, its rapid discharge causes cooling which condenses the moisture within the air and does cause limited visibility within the SLA. Visual acquisition was recorded with a high speed camera. In general, it has been determined that the present configuration of the system installed at the Kennedy Space Center Launch Complex 39 will provide a significant level of safety not heretofore possible for those personnel re quired to work in what could be an extremely hazardous environment. 8-6

4 SATURN V SPACE VEHICLE CMMAND MDULE SERVICE MDULE SLA LUNAR MDULE FIG. 1 SLA FREN FRM GN 2 SUPPLY i -^ -^ QtFKE K)7o 2,000 LR. SUSTAINING FKEN B-TTLES ^ 1 2 or. SM SLED

5 oo 00 2 I IJ n c % CNCENTRATIN F FREN ± C z o o C co 2- ^ > 70 ^j m 2 z CJ 09 o*> yo m > 73 m zc C o

6 25 LC-39 SLA FREN EXTINGUISHING SYSTEM (20%) o o 0 H» UJ o u TIME/SECNDS TIME/MINUTES FIG. 5 <b 00

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING Chapter 30 FIRE-FIGHTING This Chapter discusses events which may follow cargo spillage and the procedures which can be adopted to protect life and property in such circumstances. It also describes the

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE Application of BS 8489 to the Protection of Generator Enclosures IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE Agenda Generator Enclosure Characteristics Generator Fire Characteristics Machinery

More information

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle.

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle. MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle. 2 MistMax Low pressure WaterMist fire suppression skid Our modular fire skid is customised to suit your specific

More information

Explosion Venting and Suppression of Bucket Elevator Legs, G90-990

Explosion Venting and Suppression of Bucket Elevator Legs, G90-990 Page 1 of 6 G90-990 Explosion Venting and Suppression of Bucket Elevator Legs Explosion vents and explosion suppression devices limit the danger and damage associated with grain dust explosions. This NebGuide

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities

More information

SPECIAL HAZARDS THE MOST ADVANCED TECHNOLOGY FOR PROTECTING

SPECIAL HAZARDS THE MOST ADVANCED TECHNOLOGY FOR PROTECTING THE MOST ADVANCED TECHNOLOGY FOR PROTECTING SPECIAL HAZARDS There are numerous hazards where the use of dry chemical is the best option for firefighting, and where the use of portable fire extinguishers

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

Large Family Daycare Guideline

Large Family Daycare Guideline Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose

More information

HOT WORK SAFETY PROGRAM:

HOT WORK SAFETY PROGRAM: HOT WORK SAFETY PROGRAM: 1.0 Purpose. To establish safe procedure for open flame or hot work process at Oklahoma City Community College (OCCC) to avoid loss of property and injury to personnel. 2.0 Scope.

More information

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Combustible Dust Symposium Detroit, MI September 20, 2011 1 Objectives

More information

Fixed Fire Extinguishing Equipment and Systems

Fixed Fire Extinguishing Equipment and Systems Fixed Fire Extinguishing Equipment and Systems Sea Term 2016 Massachusetts Maritime Academy January 2016 DESIGN AND INSTALLATION OF FTXED SYSTEMS Fire extinguishing systems are designed and installed

More information

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e 5.07 Air Replenishment Systems (2016) Reference: SFFC, Section 511.2. Purpose: The purpose of this bulletin is to describe the requirements for air replenishment systems intended to be used to fill firefighters'

More information

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows: Technical Bulletin #18-002 February 2018 / 2017 OFC Mobile Food Units Referenced Codes and Standards: OAC 1301:7-7-3(T); OFC 320 OAC 1301:7-7-2(B); OFC 202 OAC 1301:7-7-9(F); OFC 906 NFPA 58 (2014) NFPA

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS (By authority conferred on the director of the department of licensing and regulatory affairs by sections

More information

Paper Session II-C - Laser Ordnance Ignition Capability at KSC

Paper Session II-C - Laser Ordnance Ignition Capability at KSC The Space Congress Proceedings 2000 (37th) Space Means Business in the 21st Century May 3rd, 2:00 PM Paper Session II-C - Laser Ordnance Ignition Capability at KSC F. Lorenzo-Luaces Dynacs Engineering

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Managing Extreme Risk by preventing flammable gas explosions. Michael van Niekerk

Managing Extreme Risk by preventing flammable gas explosions. Michael van Niekerk Managing Extreme Risk by preventing flammable gas explosions Michael van Niekerk Eliminating methane explosion risk ExploSpot eliminates the risk of methane explosions by stopping the explosion before

More information

Amerex Fire Suppression Systems. Because Operators and the Environment are NOT Disposable Quality is Behind the Diamond.

Amerex Fire Suppression Systems. Because Operators and the Environment are NOT Disposable Quality is Behind the Diamond. Amerex Fire Suppression Systems Because Operators and the Environment are NOT Disposable Quality is Behind the Diamond. Quality is Behind the Diamond. Diamonds have long been a symbol for quality. At Amerex

More information

(h) Pesticide Application.

(h) Pesticide Application. Fire Code Cannabis Amendment Section 13.20.066 is added to the Marysville Municipal Code to read in its entirety as follows: 13.20.066 Cannabis Growing, Processing, or Extraction Facilities (a) Application.

More information

Welcome to Argonite fire protection from Ginge-Kerr

Welcome to Argonite fire protection from Ginge-Kerr Welcome to Argonite fire protection from Ginge-Kerr Looking for fire protection of high value areas? Then you've come to the right place. As Halon systems go out, the Argonite system is coming in. All

More information

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials Fire Preven4on Officers Associa4on of Bri4sh Columbia 2013 Annual Seminar Kelowna, Bri4sh Columbia May 9, 2013 NFPA 33 Scope

More information

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist Andrew Kim and George Crampton Fire Research Program, National Research Council of Canada 1200 Montreal Road, Ottawa, Ontario,

More information

5.07 Air Replenishment Systems

5.07 Air Replenishment Systems 5.07 Air Replenishment Systems Reference: 2010 SFFC, Section 511.2 Definitions: CERTIFIED COMPRESSOR. A compressor used by a contractor for maintenance and testing of air replenishment systems that is

More information

FIRE SUPPRESSION SYSTEM

FIRE SUPPRESSION SYSTEM FIRE SUPPRESSION SYSTEM An effective fire suppression systems work fundamentally in three ways; The corner stone has to be an efficient means of early warning/detection. Followed by either an Oxygen reduction

More information

1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.

1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed. REQUIREMENT 2. HOT WORK OPERATIONS 1.0 PURPOSE 1.1 To establish a requirement with responsibilities for any hot work operations during all phases of construction, renovation and routine maintenance work

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

Carbon Dioxide Fire Suppression Systems

Carbon Dioxide Fire Suppression Systems Carbon Dioxide Fire Suppression Systems The original "clean agent," carbon dioxide suppresses fire without leaving behind water, foam or dry chemical to damage sensitive equipment. And because there is

More information

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009 (II) 23, 25 June and 7, 9 July 2009 Organization by Co-organized by the Association of Registered Fire Service Installation contractors of Hong Kong Ltd (FSICA) Gas and Foam Suppression Systems Peter Bressington

More information

Module 5: Combustion Technology. Lecture 38: Combustion Burners

Module 5: Combustion Technology. Lecture 38: Combustion Burners 1 P age Module 5: Combustion Technology Lecture 38: Combustion Burners 2 P age Keywords : Atmospheric burner, atomizer, rotating cup burner, swirl type burner, nozzle design 5.7 Combustion Burners Types

More information

Bombardier Challenger Fire Protection

Bombardier Challenger Fire Protection GENERAL The fire protection system is divided into two separate subsystems: Fire and overheat detection system; and Fire extinguishing system. The fire and overheat detection system includes components

More information

Chapter 12 HOT WORK OPERATIONS. Purpose:

Chapter 12 HOT WORK OPERATIONS. Purpose: Chapter 12 Hot Work Operations Chapter 12 HOT WORK OPERATIONS Purpose: To provide written procedures to prevent the outbreak of fire, fire alarm activations, and smoke and odor migration in buildings resulting

More information

Industrial Explosion Suppression Technology

Industrial Explosion Suppression Technology 88 th Annual Michigan Safety Conference 2018 Tuesday April 17 th 2018-10:45 AM Industrial Division Lansing Center, Lansing, MI Industrial Explosion Suppression Technology Presenter: Rob Markle Phone: (309)

More information

Flammable Liquid Storage

Flammable Liquid Storage Published on UC Davis Safety Services (https://safetyservices.ucdavis.edu) Flammable Liquid Storage SafetyNet #: 523 Properties, Classification, Quantities, Cabinets, Containers and Refrigerators A. Summary

More information

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J.

American Society of Safety Engineers Professional Development Conference June 9-12, Fire Protection. Stephen J. American Society of Safety Engineers Professional Development Conference June 9-12, 2008 Session No. 101F Fire Protection Stephen J. Musur CSP, CFPS Chubb Group of Insurance Companies June 12, 2008 1 Fundamentals

More information

The Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE

The Combustion Process THE FIRE TETRAHEDRON FUEL TEMPERATURE Worldwide Safety Services Fire Extinguisher Training D 1 Objectives Understand the combustion process and different fire classes. Understand d fire extinguisher i types, operating procedures, capabilities,

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8.h.3 TITLE: SCOPE: PURPOSE: HOT-WORK OPERATIONS PERMIT/PLAN SUBMITTAL

More information

WATER MIST CONVENTION AND EXHIBITION

WATER MIST CONVENTION AND EXHIBITION INTERNATIONAL WATER MIST ASSOCIATION IWMA SEMINARS S ON WATER MIST TECHNOLOGY DUBAI INTERNATIONAL CONVENTION AND EXHIBITION CENTRE Water mist fire protection: The most innovative fire fighting technology

More information

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS Town of Brighton Office of the Fire Marshal October 2018 Carbon Dioxide Systems for Beverage Dispensing Requirements Scope The intent

More information

AUTOMATIC FIRE & EXPLOSION SUPPRESSION SYSTEM.

AUTOMATIC FIRE & EXPLOSION SUPPRESSION SYSTEM. AUTOMATIC FIRE & EXPLOSION SUPPRESSION SYSTEM www.abdesign.org AFSS SYSTEM INACTIVE ACTIVE 12 ms 24 ms 60 ms 96 ms 120 ms 156 ms 200 ms As a result of their mission, military vehicles are exposed to hydrocarbon

More information

The Next Generation of Foam Fire Suppression. Automatic CAF Fire hose reel system FEATURES

The Next Generation of Foam Fire Suppression. Automatic CAF Fire hose reel system FEATURES Fire hose reel system The first automatic CAF, fire hose reel system FEATURES The Automatic CAF Fire Hose Systems are ideal for firefighting needs in locations that require foam as a fire fighting agent.

More information

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications National Aeronautics and Space Administration Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications SUPDET 2012 Phoenix, AZ Thierry Carriere (thierryc@adatech.com),

More information

Adv. 8.4 Guidelines for Biosafety Cabinets Rev

Adv. 8.4 Guidelines for Biosafety Cabinets Rev UNIVERSITY OF CINCINNATI Environmental University Health Services 556-4968 Health and Safety ADVISORY NO. 8.4: GUIDELINES FOR THE SELECTION, INSTALLATION AND USE OF BIOSAFETY CABINETS (INCLUDING ISSUES

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Ls Vegas, NV (702) FAX (702)

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Ls Vegas, NV (702) FAX (702) CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Ls Vegas, NV 89119 (702) 455 7316 FAX (702) 455 7347 105.8.h.3 2 TITLE: HOT WORK OPERATIONS PERMIT/PLAN SUBMITTAL RENEWABLE

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

MB05. RESPOND TO EMERGENCIES BASIC KNOWLEDGE OF EMERGENCY PROCEDURES, INCLUDING EMERGENCY SHUTDOWN

MB05. RESPOND TO EMERGENCIES BASIC KNOWLEDGE OF EMERGENCY PROCEDURES, INCLUDING EMERGENCY SHUTDOWN MB05. RESPOND TO EMERGENCIES BASIC KNOWLEDGE OF EMERGENCY PROCEDURES, INCLUDING EMERGENCY SHUTDOWN Content of the lecture 1. DRILLS AND EMERGENCY EXERCISES (general requirements) 2. Emergency procedures

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

SPACE SHUTTLE EXTERNAL TANK GASEOUS OXYGEN VENT SYSTEM William G. Franklin NASA/John F. Kennedy Space Center, Florida

SPACE SHUTTLE EXTERNAL TANK GASEOUS OXYGEN VENT SYSTEM William G. Franklin NASA/John F. Kennedy Space Center, Florida J SPACE SHUTTLE EXTERNAL TANK GASEOUS OXYGEN VENT SYSTEM William G. Franklin NASA/John F. Kennedy Space Center, Florida In the summer of 1979, NASA program management was faced with the problem of ice

More information

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007

More information

Water Mist Fire Suppression

Water Mist Fire Suppression Water Mist Fire Suppression How less water has a big impact. HELPING PROTECT YOUR BUSINESS AND VALUED ASSETS WITH WATER MIST FIRE PROTECTION SYSTEM INTRODUCTION Many buildings have specific areas that

More information

Hot Work Program & Operational Guidelines. Environmental Health, Safety and Emergency Management (828)

Hot Work Program & Operational Guidelines. Environmental Health, Safety and Emergency Management (828) Hot Work Program & Operational Guidelines Environmental Health, Safety and Emergency Management (828) 262-4008 HOT WORK INTRODUCTION Purpose: This program is designed to recognize potential fire and explosion

More information

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle. TM TM

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle. TM TM MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle. TM TM 2 MistMax Low pressure water mist fire suppression skid Our modular fire skid is customised to suit your

More information

WATERFRONT FACILITY COMPLIANCE BOOKLET

WATERFRONT FACILITY COMPLIANCE BOOKLET U. S. COAST GUARD WATERFRONT FACILITY COMPLIANCE BOOKLET NAME: FIN: MOBILE UNIT # COTP: DATE: CG TEAM LEADER: DEPARTMENT OF TRANSPORTATION, U.S. COAST GUARD, CG-5562A (Rev 6-04) INSTRUCTIONS 1. Initial

More information

Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers. 8th March 2016 Dr Tim Nichols CPhys MIFireE

Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers. 8th March 2016 Dr Tim Nichols CPhys MIFireE Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers 8th March 2016 Dr Tim Nichols CPhys MIFireE Industrial Oil Cookers 2 What are Industrial Oil Cookers Large cooker of food

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET Stain Extinguisher - Aerosol Page 1 MATERIAL SAFETY DATA SHEET 1. CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Product Identification Product Name: Stain Extinguisher - Aerosol Product Number: C190, C190-AUS,

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

JAMES MOODY IM FLASH LIFE SAFETY AHJ

JAMES MOODY IM FLASH LIFE SAFETY AHJ TOXIC GAS MONITORING JAMES MOODY IM FLASH LIFE SAFETY AHJ AGENDA 2 Toxic Gas Primary Gas Hazards SemiConductor Industry Code Requirements Large Toxic Gas Monitoring Systems Block Diagram TGM Detection

More information

Inert Gas Fire Extinguishing System

Inert Gas Fire Extinguishing System s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact s & Equipment Manufact

More information

Emergency shutdown systems. Procedures for bypassing ESD s

Emergency shutdown systems. Procedures for bypassing ESD s HYDROCARBON PROCESS SAFETY 2 - ELEMENT 3 - UNIT IOG1 Emergency shutdown systems Emergency shutdown systems (ESD s) are intended to minimise the consequences of emergency situations, for example, the uncontrolled

More information

BOC FS125 The Fire Extinguishing Solution

BOC FS125 The Fire Extinguishing Solution BOC FS125 The Fire Extinguishing Solution Background - Montreal Protocol With the introduction of the Montreal Protocol in 1987, Halon is no longer available in most countries and alternatives must be

More information

Fire suppression systems for server rooms and data centres

Fire suppression systems for server rooms and data centres Fire suppression systems for server rooms and data centres Fire suppression systems for server rooms and data centres Fire suppression systems for server rooms and data centres are essential to the server

More information

With CV Technology products and care, you ll be better protected from dust explosions.

With CV Technology products and care, you ll be better protected from dust explosions. Shield your manufacturing process and people from dust explosions with CV Technology. Let CV Technology offer peace of mind to your company and employees. www.cvtechnology.com Global Leader In Explosion

More information

An Overview of Extinguishing Systems for Computer Equipment

An Overview of Extinguishing Systems for Computer Equipment Risk Solutions An Overview of Extinguishing Systems for Computer Equipment Various types of automatic suppression systems are available for protecting computer equipment. This report discusses the uses

More information

Effective, efficient response for emergency situations Risk Management

Effective, efficient response for emergency situations Risk Management Effective, efficient response for emergency situations Risk Management The network-based Risk Management System Information at a glance Effective, efficient response for emergency situations For each particular

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-31263-3 SOUTH AFRICAN NATIONAL STANDARD Disposable portable condensed aerosol fire extinguishers WARNING This document references other documents normatively. Published by SABS Standards

More information

Fig. 1 - Unit PGD4, PGS4, WPG4

Fig. 1 - Unit PGD4, PGS4, WPG4 OWNER S MANUAL 14 SEER Single -Package Air Conditioner and Gas Furnace System with R -410A Refrigerant Single Phase 2 to 5 Nominal Tons Three Phase 3 to 5 Nominal Tons PGD4andPGS4SeriesE,WPG4SeriesB Fig.

More information

This policy is applicable to all DMS-owned, -leased and -managed facilities.

This policy is applicable to all DMS-owned, -leased and -managed facilities. DEPARTMENT OF MANAGEMENT SERVICES Real Estate Development and Management TITLE: Open Flames & Flammable Materials in DMS Owned, -Leased and -Managed Facilities EFFECTIVE: March 9, 2009 REVISED: June 17,

More information

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO Combustion Safety RESNET Conference San Antonio, TX February 27, 2006 Presented by Rich Moore Lightly Treading Energy & Design Denver, CO Goals of this session Recognize the need for combustion safety

More information

A comprehensive systems-level approach in cabin design minimizes fire potential and helps ensure passenger safety. aero quarterly qtr_04 11

A comprehensive systems-level approach in cabin design minimizes fire potential and helps ensure passenger safety. aero quarterly qtr_04 11 A comprehensive systems-level approach in cabin design minimizes fire potential and helps ensure passenger safety. 18 aero quarterly qtr_04 11 Fire Protection: Passenger cabin the cabins on all boeing

More information

Superior by Design The Kidde ADS TM FM-200 System

Superior by Design The Kidde ADS TM FM-200 System A UTC Fire & Security Company Superior by Design The Kidde ADS TM FM-200 System Engineered to Provide Exceptional Performance The Kidde ADS FM-200 System is an innovative system developed by Kidde engineers

More information

Xavier Field Office Fire Prevention Plan. for. Xavier Field Office Dana Avenue

Xavier Field Office Fire Prevention Plan. for. Xavier Field Office Dana Avenue Xavier Field Office for Xavier Field Office 1601 Dana Avenue Xavier University January 30, 2012 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

The element is closed at one end and open at the other, and it s bolted onto the explosion vent opening on the equipment so that its open end overlaps

The element is closed at one end and open at the other, and it s bolted onto the explosion vent opening on the equipment so that its open end overlaps Meeting explosion safety requirements with flameless venting Jef Snoeys Fike Corp. Flameless venting is a recently developed technology for protecting indoor equipment from dust explosions. This technology

More information

TRAINING BULLETIN September 1, 2010 PURPLE K DRY CHEMICAL EXTINGUISHER 1. INTRODUCTION

TRAINING BULLETIN September 1, 2010 PURPLE K DRY CHEMICAL EXTINGUISHER 1. INTRODUCTION TRAINING BULLETIN September 1, 2010 1. INTRODUCTION Purple K dry chemical extinguishers have been issued to various units of the department. Purple K is a potassium bicarbonate base dry chemical. While

More information

READING: ECLSS (Environmental Control and Life Support System)

READING: ECLSS (Environmental Control and Life Support System) READING: ECLSS (Environmental Control and Life Support System) The ECLSS is responsible for maintaining a comfortable environment for the astronauts while they are out of their space suits and in the orbiter's

More information

***DRAFT - NOT FOR FILING***

***DRAFT - NOT FOR FILING*** ACTION: Original ***DRAFT - NOT FOR FILING*** DATE: 09/29/2017 1:14 PM 1301:7-7-27 Semiconductor fabrication facilities. (A) Section 2701 General (1) 2701.1 Scope. Semiconductor fabrication facilities

More information

NJSP HMRU. Module 5 B HM Operations 1

NJSP HMRU. Module 5 B HM Operations 1 THE MATERIAL PRESENTED IN THIS MODULE IS INTENDED AS AN OVERVIEW. SPECIFIC INFORMATION ON CALIBRATION, OPERATION, AND INTERPRETATION OF RESULTS SHOULD BE OBTAINED FROM EQUIPMENT MANUFACTURERS. IDENTIFYING

More information

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to

More information

AUTOMATIC FIRE SUPPRESSION SYSTEMS

AUTOMATIC FIRE SUPPRESSION SYSTEMS AUTOMATIC FIRE SUPPRESSION SYSTEMS Effective automatic fire suppression systems are essential for the fire protection of mechanical equipment and special technologies. CONTENTS RSBP FIRE PROTECTION OF

More information

Crosswalk: Weight-Based Rating versus Performance-Based Rating

Crosswalk: Weight-Based Rating versus Performance-Based Rating 46 CFR 25.30 (Subchapter C) Motorboats Motorboat size Old New With no fixed fire With a fixed fire extinguishing System extinguishing system Motorboats under 16ft B-I 5-B 1 0 Motorboats 16ft-26ft B-I 5-B

More information

FIRE PROTECTION PROGRAM

FIRE PROTECTION PROGRAM Fire Protection Program Page 1 of 13 FIRE PROTECTION PROGRAM 1.0 Objective The objective of this performance assessment is to evaluate the effectiveness of the laboratory's fire protection program as implemented

More information

EMERGENCY PREPAREDNESS: EVACUATIONS

EMERGENCY PREPAREDNESS: EVACUATIONS GUIDELINE I. EMERGENCY PREPAREDNESS: EVACUATIONS 1.0 PURPOSE 1.1 To provide guidance for the safe and orderly evacuation of faculty, staff, students and visitors to the University of Pennsylvania campus

More information

Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts

Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Pellet Fuels Institute Conference Asheville, NC July 20, 2010 1 Objectives

More information

Fire Extinguishing System

Fire Extinguishing System Fire Extinguishing System Fire Protection CAUTION CAUTION 1 EXTINGUISHER PUSH L ENGINE FIRE R FW VALVE CLOSED TO TEST R ENGINE FIRE R FW VALVE CLOSED EXTINGUISHER PUSH 2 TEST SWITCH 1 ANNUNCIATOR PANEL

More information

Chapter 18 Welding Table of Contents

Chapter 18 Welding Table of Contents Chapter 18 Welding Table of Contents 18.1 Foreword 18.2 Introduction 18.3 Applicability of Standard 18.4 Other Policies that Might Apply 18.5 Approved Areas for Welding and Cutting 18.6 Other Areas 18.7

More information

BETACURE 100 CO-REACTANT

BETACURE 100 CO-REACTANT BETACURE 100 CO-REACTANT Technical Data Sheet BETACURE 100 is a volatile flammable liquid used as a co-reactant in the patented BETASET Cold Box core and mold making process. Chemically, BETACURE 100 consists

More information

Creating a safer world!

Creating a safer world! 03 A leader in next generation of the fire extinguishing system The Fire Prevention industry is expected to have great growth potential and a huge impact on the national economy since nowadays the need

More information

Owner s Information Manual

Owner s Information Manual 48ES---A and 48VL---A Comfort and Performance 13 and 14 SEER Single Packaged Air Conditioner and Gas Furnace System With Puron (R---410A) Refrigerant Single and Three Phase 2---5 Nominal Tons (Sizes 24---60)

More information

APPENDIX A FEES SECTION FC A01 CERTIFICATES A01.1

APPENDIX A FEES SECTION FC A01 CERTIFICATES A01.1 FEES SECTION FC A01 CERTIFICATES A01.1 Certificate fees. Applicants for certificates required pursuant to the provisions of this code or the rules shall pay the fees specified in this section. Fees for

More information

Certificate of Compliance Section 1 - PRODUCT AND COMPANY IDENTIFICATION

Certificate of Compliance Section 1 - PRODUCT AND COMPANY IDENTIFICATION Page 1 of 5 Certificate of Compliance & Material Safety Data Sheet For Health Emergencies: CALL A POISON CONTROL CENTER For Transportation Emergencies ONLY: Call Chem-Tel USA, Canada, Puerto Rico, US Virgin

More information

FIXED PROTECTION FOR OIL AND CHEMICAL PLANTS

FIXED PROTECTION FOR OIL AND CHEMICAL PLANTS GAP.12.2.1.2 A Publication of Global Asset Protection Services LLC FIXED PROTECTION FOR OIL AND CHEMICAL PLANTS INTRODUCTION Fixed water spray, deluge, foam-water and sprinkler systems are essential parts

More information

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES Last Updated: July 18, 2013 1 TABLE OF CONTENTS A. PURPOSE 3 B. SCOPE 3 C. POLICIES AND PROCEDURES 3 1. Facility Hot Work

More information

Laboratories and Hazardous Materials. Company Overview

Laboratories and Hazardous Materials. Company Overview Laboratories and Hazardous Materials Don E. Contois, P.E. Sam Sinapi Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees. RWS is a full service engineering

More information

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER The 2016 Denver Building and Fire Code includes the following codes except as amendment herein. 2015 IBC (Building) 2015 IFC (Fire)

More information

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety

More information

Fire Prevention Plan

Fire Prevention Plan Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........

More information