Emergency Lighting: what, when & how? Richard Caple MSc MSLL Lighting Applications Manager
|
|
- Ralf Wiggins
- 5 years ago
- Views:
Transcription
1 Emergency Lighting: what, when & how? Richard Caple MSc MSLL Lighting Applications Manager
2 What is emergency lighting? Legislation and standards Emergency lighting design Emergency lighting testing requirements Technology to the rescue!
3 What is emergency lighting? Legislation and standards Emergency lighting design Emergency lighting testing requirements Technology to the rescue!
4 What is Emergency lighting?
5 What is Emergency lighting?
6 What is Emergency lighting? To facilitate safe exit from the building when the normal lighting fails To allow potentially dangerous equipment/processes to be made safe before evacuation To enable Fire Wardens & Fire and Rescue Service to search the building & locate missing people
7 What is Emergency lighting? To allow people to remain in the building if:- There is no risk Greater harm evacuating (terrorism)
8 What is emergency lighting? Legislation and standards Emergency lighting design Emergency lighting testing requirements Technology to the rescue!
9 Legislation and standards Fire precautions act 1971 Fire precautions (WP) Regulations 1997 Building Regulations Part B 2006 Regulatory Reform Fire Order 2005 BS 5266:2016 BS EN1838:2013 BS EN50172:2004 BS EN12193:1999 BS 5499:2000 BS EN :2014 BS EN62034:2012 BS ISO7010:2011 CIBSE/SLL LG12:2015
10 Legislation and standards Pre 2005: Local Fire Authority Fire certificate Post 2005: Responsible Person Risk assessment! The Responsible Person maybe the Employer, the Building Owner or the Occupier It is an offence not to comply! Fire Brigades are the enforcing Authority. They can Enforce, Prohibit and order alterations. Failure to comply can result in a fine or imprisonment.
11 Legislation and standards Retail store, Oxford Street No Risk Assessment Inadequate staff training No Fire Alarm response procedure Fire door release mechanisms fitted to the wrong side of the exit doors Fine - 400, ,000 costs
12 Legislation and standards Risk Assessment Asses and manage risks Provide appropriate protection systems (such as fire alarms and emergency lighting) Develop a policy Implement procedures Provide training Conduct drills Cary out regular maintenance
13 Legislation and standards Basic Factors How many occupants? Where are the escape routes? Immediate evacuation Policies Procedures For how long? Consultation Strategies Stay Put Strategy Who makes the decision to evacuate? Standby Generation Is Escape Lighting also needed? Risk Assessment What are the risks? How are they mitigated? Test procedures? Manual or automatic
14 Legislation and standards Consultation / Risk Assessments vital inputs in ensuring the emergency lighting is suitable and fit for purpose
15 What is emergency lighting? Legislation and standards Emergency lighting design Emergency lighting testing requirements Technology to the rescue!
16 Emergency Lighting Power Failure Emergency Situation Power Failure Non-Emergency
17 Power Failure Emergency Situation Escape Lighting Escape Route Open Area High Risk Area
18 Escape Route Lighting Applies to corridors, lobbies and staircases or open areas where escape routes have been defined via risk assessment Illumination level: 1 lux minimum along center line of route Uniformity (max:min)= 40:1 Risk asses, maybe more than 1 lux is required?
19 Open Area Lighting >60m 2 open area anti panic lighting Illumination Level: 0.5 lux minimum (excluding 0.5m border) Uniformity (max:min) = 40:1 Areas less the 60m² may need emergency lighting is deemed by the risk assessment.
20 High Risk Lighting Safe termination of hazardous activity Safe passage / rescue access Illumination level: 10% of normal mains lighting, or 15Lux, which ever is greater
21 Disability glare
22 BS5266-1:2016 Minimum of two luminaires per compartment of the escape route and each open plan area or one luminaire & Exit Sign
23 Power Failure Non-Emergency Safety Lighting (Stay Put) Standby Lighting
24 Safety Lighting Must be Risk Assessed What is the risk to people? What task are you asking them to do? Open areas 1lx Escape routes 1lx Low difficulty task 5lx Medium difficulty task 15lx High difficulty task 50lx System duration? If 3 hours, evacuate the building after 2 hours Rest mode?
25 Standby Lighting Providing full output if mains fails via UPS/generator
26 Points of Emphasis Stairs so that each flight receives direct light Changes in level Changes of escape route direction Corridor intersections First aid posts Fire alarm call points or pieces of fire fighting equipment External areas in the immediate vicinity of final exits Moving stairways and walkways Motor generator, control and plant rooms Lift cars Covered car parks Areas of refuge Toilet facilities exceeding 8m² or any multiple closet facility without borrowed light All other areas as deemed by the Risk Assessment
27 BSEN 1838
28 Illuminance for specific locations BS5266-1
29 Place of safety
30 Building Regulations Part B/Technical Handbook
31 Building Regulations Part B/Technical Handbook Be aware of diffusers that form part of the ceiling!
32 Building Regulations Part B/Technical Handbook Thermoplastic lighting diffusers can categorised as either:- TP(a) rigid 3mm thick polycarbonate, or other material a sample of which meets the requirements of the TP(a) test method described in BS Polycarbonate diffusers TP(a) flexible seldom used in luminaires TP(b) polycarbonate less than 3mm thick, or other material a sample of which meets the requirements of the TP(b) test method described in BS Most Acrylic s and PMMA diffusers
33 Why is this important? Depending on material type, there are restrictions on how much material can be used!
34 TP(a) requirements When using TP(a) classified material, there are no limits or restrictions on use, except within protected zones or stairways where no thermoplastic material of any type should be used.
35 TP(b) requirements for circulation spaces The total area of diffuser panels must not exceed 15% of the total floor space. The maximum area of one diffuser must not exceed 5m². Where a number of smaller panels are used (most types of luminaire) then a 5m x 5m group of panels must have a 3m gap between the next group, as shown in below.
36 TP(b) requirements for Rooms The total area of diffuser panels must not exceed 50% of the total floor space. The maximum area of one diffuser must not exceed 5m². Where a number of smaller panels are used (most types of luminaire) then a 5m x 5m group of panels must have a 3m gap between the next group, or in England, Wales and Scotland, the below diagram defines an alternative spacing method where the distance between luminaires must be equal to or greater than the longest dimension of the thermoplastic diffuser.
37
38 Exit Signage
39 Exit Signage Required to ensure ESCAPE ROUTES are apparent from any location MAINTAINED where occupants may be unfamiliar with building Should be conspicuous Consider smoke accumulation
40 Exit Signage At all normal exits At all emergency exists Along escape routes Anywhere else if the route to the nearest exit is not clear
41 Clear and unambiguous instructions! Which way?
42 Clear and unambiguous instructions! Sign types should not be mixed within a building Older types of sign formats may still be used for existing buildings New buildings should use ISO7010 format as referenced in BS5266 ISO7010 sign format Which way?
43 ILLEGAL since 1999 BS EN :2013 European Signs Directive 1996 HTM 65 NHS Hospitals (Withdrawn) ISO 7010 specified in BS EN :2016
44 Sign viewing distances Externally lit Externally lit = 100 x Sign Height = 15m (150mm tall sign) Internally lit Internally illuminated = 200 x Sign Height = 30m (150mm tall sign) Which way?
45 Up or down arrow?
46 What is emergency lighting? Legislation and standards Emergency lighting design Emergency lighting testing requirements Technology to the rescue!
47 Emergency Lighting Testing Requirements Inspection & testing Regular testing & servicing is essential Competent Person should have authority to ensure correct testing, maintenance & logging
48 Emergency Lighting Testing Requirements Commissioning! Full rated duration test (after 24 hours of charging)
49 Emergency Lighting Testing Requirements Inspection & testing Daily Central battery cabinets only Visual inspection to ensure the system is in a ready condition Monthly Short duration test To ensure that all emergency luminaires illuminate correctly (lamps and batteries are working) Annually Full duration test To ensure that all emergency luminaires illuminate correctly and fully achieve duration required (3 hours)
50 Record keeping Competent Person signs regular Test Certificates
51 Emergency Lighting Testing Requirements Record keeping All testing records must be kept off site!
52 What is emergency lighting? Legislation and standards Emergency lighting design Emergency lighting testing requirements Technology to the rescue!
53 Technology to the rescue! LED Technology Good light output Long life Low power consumption Controlled with lenses Greater spacing = fewer points
54 Technology to the rescue! 100,000 hr 4w LED strip vs. 4,000 hr T5 8w fluorescent
55 Technology to the rescue! Automatic testing systems
56 Technology to the rescue! Option 1 : Manual testing Pros : Easy to specify and install equipment, attractive capital costs Cons: Time consuming testing, high labour costs, un-proactive Option 2 : Autotest Pros : Reliable testing, reduced labour costs Cons: Higher capital costs, still requires visual inspection, partly proactive Option 3 : Autotest + networked system Pros : Reliable testing, minimal labour costs, proactive, off site record keeping Cons: High capital costs, potentially high installations costs
57 Technology to the rescue! Option 1 : Manual test Labour intensive testing regime, high maintenance costs plpa (Inclusive of labour for testing and maintenance) Option 2 : Autotest Reduced testing labour, high maintenance costs plpa (Inclusive of labour for testing and maintenance) Option 3 : Autotest + Networked system No manual testing, reduced maintenance costs plpa (Inclusive of labour for testing and maintenance)
58 Technology to the rescue! Wireless automatic testing systems
59 Technology to the rescue! Possibility for full, off site, record keeping
60 Final thoughts Impact of the Grenfell Tower disaster Greater importance of Fire Risk Assessments Risk assessments, safety lighting + new risks (such as threat of terrorism) will drive the use of automated intelligent systems Communication between emergency lighting system and fire alarm system?
61
Technical reference Reference & design
The requirement for emergency lighting originates from the Fire Precautions Act 1971 and was further enforced by the Fire Precautions (Workplace) Regulations 1997 (Amended 1999). The Regulatory Reform
More informationFIRE SAFETY LOG BOOK
FIRE SAFETY LOG BOOK Regulatory Reform (Fire Safety) Order 2005 If you own, manage or operate a business, you will need to comply with fire safety law. The main law is the Regulatory Reform (Fire Safety)
More informationHandout Notes Major changes in BS : 2016
Handout Notes Major changes in BS 5266-1: 2016 The contents section now includes Introduction 1 Scope 2 Normative references 3 Terms and definitions 4 Consultation and records 5 Illumination for emergency
More informationEmergency Lighting Design
SECTION 3: 9: page 1 Section 9: Emergency Lighting Design SECTION 9: page 3 Introduction When the electricity supply fails and the lights go out, it is essential that emergency lighting is automatically
More informationNew Fire Safety Order
Voltimum Technical seminar New Fire Safety Order Implications for the Emergency Lighting Systems Presented by Chris Watts Cooper Lighting and Security Chairman of - British Standards CPL 34/9 Code of Practice
More informationGuidance Note. Guidance Document for Testing and Maintaining Self-Contained Emergency Lighting and Luminaires
Guidance Note Guidance Document for Testing and Maintaining Self-Contained Emergency Lighting and Luminaires Guidance Document for testing and maintaining self-contained Emergency Lighting and Luminaires
More informationCharlotte Building, 17 Gresse Street, London W1T 1QL
Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of
More information161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures
161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means
More informationA Guide To BS Understanding the selection, spacing & siting of detectors
World Class Leaders in Fire Detection Since 1918 A Guide To BS5266-12016 Understanding the selection, spacing & siting of detectors Extra Low Voltage LED Technology Low Maintenance Intelligent Simple Installation
More informationFP-PGN-14 Part of NTW(O)41 Fire Policy
Fire Policy Practice Guidance Note Fire Evacuation in Trust Owned and Occupied Premises V02 Date Issued Issue 1 Aug 2017 Planned Review Aug - 2020 Responsible Officer Head of Estates & Facilities (NTW
More informationEmergency light. Safe solutions
Emergency light Safe solutions Experience and know-how For more than two generations Glamox has developed, produced and distributed lighting solutions for the professional market. Emergency lighting has
More informationFire Risk Assessment Safety Checklist
Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory
More informationEMERGENCY LIGHT SERIES
ASENWARE EMERGENCY LIGHT SERIES 1 / 38 EMERGENCY LIGHT SERIES 1 About ASENWARE was set up at 2005 in UK. After over 10 years very fast developing, we keep the high investment for R&D and international
More informationFire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures
Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting Fire 5. 0 Discovering
More informationFire Safety Protocol
CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents
More informationFIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)
FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT
OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible
More informationSafety Lighting. Safe also without electricity. Standards SIST EN 1838: 2011 ISO (2007) CIE S 020 (2007)
Safety Lighting Prof. Grega Bizjak, PhD Laboratory of Lighting and Photometry Faculty of Electrical Engineering University of Ljubljana Safe also without electricity Since it is practically impossible
More informationFIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre
FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job
More informationDublin airport - Dublin, Ireland
Dublin airport - Dublin, Ireland 604 Route LED 607 Route LED II 608 SYL Safe EMERGENCY 601 Emergency 80 Hammersmith Road - London, England Control Gear: Electronic Integral Sensor: Not applicable Emergency:
More informationFire Risk Management Policy. UK September 2017
UK September 2017 5 & 7 Diamond Court, Opal Drive, Eastlake Park, Fox Milne, Milton Keynes MK15 0DU, T: 01908 396250, F: 01908 396251, www.cognitaschools.co.uk Registered in England Cognita Limited No
More informationFIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS
A GUIDE ON FIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS INTRODUCTION Fire safety in blocks of flats is something that must be taken very seriously. The Local Government Group (LGG) was commissioned to
More informationPREMISES FIRE SAFETY LOGBOOK
0844 740 3473 PREMISES FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: AN INTRODUCTION TO YOUR LOG BOOK. The Regulatory Reform (Fire Safety) Order 2005 (FSO) requires that the
More informationKRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer
KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY Last Review Date 30 June 2015 Policy endorsed by Policy is maintained by ISI reference Trustees Co-Principals/Directors A9, B6, B9 Next review date 30 August
More informationElement C3.5 Means of Escape
.5 Means of Escape RRFSO Article 14 Legal Factors Responsible person must ensure routes to emergency exits and exits themselves are kept clear at all times Exits must directly lead to place of safety Safe
More informationEmergency Lighting User's Guide
Emergency Lighting User's Guide Emergency Lighting System Emergency Lighting System Emergency lighting systems are the systems that become automatically active and provide adequate lighting when the main
More informationFIRE SAFETY POLICY. A. Policy Statement
Overall responsibility for Fire Safety: Delegated responsibility for Fire Safety: Mr J Crocker (Principal) Ms C Lepeck (Student Services Manager) A. Policy Statement This policy has been prepared to help
More informationA basic guide to... Fire Safety for Scout Premises
A basic guide to... Fire Safety for Scout Premises A basic guide to Fire Safety for Scout Premises This Guide has been designed and produced by Chubb Fire to assist persons responsible for fire safety
More informationCOSINE DEVELOPMENTS Reg. No. IT 1637/97
COSINE DEVELOPMENTS Reg. No. IT 1637/97 LEADERS IN LIGHTING TECHNOLOGY P O Box 10177 Tel. : +27 (31) 5793090/4 24 Ashfield Avenue Marine Parade Int. Fax. : +27 (31) 5793021 Springfield Park 4056 Local
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS
FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the
More informationEXIT ROUTES, EMERGENCY ACTION PLANS, AND. FIRE PREVENTION PLANS. PART 1: INTRODUCTION
EXIT ROUTES, EMERGENCY ACTION PLANS, AND FIRE PREVENTION PLANS PART 1: INTRODUCTION Applicability of This Module Use the following General Applicability Checklist to determine whether a rulebook and its
More informationNOT PROTECTIVELY MARKED. Fire Legislation
Fire Legislation Contents Policy Statement... 2 Legislation... 2 Fire Extinguisher Usage... 2 Fire Evacuation Procedure... 3... 4 Line Managers/Supervisors... 4 Business Support Officer... 5 Driver/Handy
More informationEMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be
EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety
More informationFIRE POLICY ST.GEORGES AND OUR LADY QUEEN OF PEACE PARISHES OF WORCESTER INTRODUCTION. Fire is one of the most common workplace hazards.
FIRE POLICY ST.GEORGES AND OUR LADY QUEEN OF PEACE PARISHES OF WORCESTER INTRODUCTION Fire is one of the most common workplace hazards. The RR (Fire Safety) Order 2005 requires responsible persons to carry
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE
FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the
More informationSlight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk
Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action
More informationWellsprings Primary School. Fire Emergency Evacuation Plan
Wellsprings Primary School Fire Emergency Evacuation Plan This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the plan is: To ensure the safety
More informationFire safety procedure
Fire safety procedure Review date: October 2020 Responsible (s): Health and Safety Applicable to Staff: Accessible to Students: Accessible to general public: (including clients) Yes Yes Yes 1 Contents
More informationFire precautions in dwellings
NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types
More informationLow Location Lighting
Low Location Lighting system The spreading of smoke is one of the most dangerous consequences of a fire rendering evacuation difficult and in some cases impossible. Under these conditions, visibility is
More informationAllfire Site No. a division of Allsaved Ltd. Fire Safety Log Book. Premises Address: Responsible Person:
Site No. a division of Allsaved Ltd. Fire Safety Log Book Premises Address: Responsible Person: Introduction An Introduction to Your Fire Safety Log Book The Regulatory Reform (Fire Safety) Order 2005
More informationPREMISES FIRE SAFETY HANDBOOK
UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 188 TOTTENHAM COURT ROAD University College London 188 TOTTENHAM COURT ROAD, LONDON,
More informationFire Safety. A TUC guide for trade union activists
Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the
More informationFire Safety Register
Fire Safety Register Introduction 1.1 Section 18(2) of the Fire Services Acts, 1981 and 2003 generally applies to all premises other than a dwelling house occupied as a single private dwelling. This section
More informationFIRE RISK ASSESSMENT Self Assessment
FIRE RISK ASSESSMENT Self Assessment Important! This fire risk assessment form is to be filled in by the responsible person within a business or organisation. As this is a free download for the use of
More information(Fire) Emergency Evacuation Plan
LAZARI INVESTMENTS LIMITED (Fire) Emergency Evacuation Plan Lazari Investments Maple House 149 Tottenham Court Road London W1T 7BN Version: September 2016 MKDS (Services) Ltd Fire Safety Services & Solutions
More informationExit Routes. Introduction/Overview. OSHA Regulations. Exit Route
Exit Routes Introduction/Overview Knowing how to evacuate your workplace is very important for your safety. An evacuation may be required for a number of different emergencies, including: Fire or smoke
More informationArbour House. Fire Policy and Procedures
Arbour House Fire Policy and Procedures Policy Review Date: May 2017 Introduction Arbour House School endeavours to ensure that risks from fire are identified and that arrangements are in place to control
More informationHealth and Safety Services. Safety Guide 5. Fire drills
Health and Safety Services Safety Guide 5 Fire drills Fire drills Contents Summary...iii 1. Scope...1 2. Responsibilities...1 2.1. Duties on managers... 1 2.2. Duties of all building occupants... 1 2.3.
More informationEMERGI-LITE An authoritative guide to emergency lighting & central power systems
GUIDE EMERGI-LITE An authoritative guide to emergency lighting & central power systems Emergency lighting is a vital and effective life safety tool, providing reassurance and guidance to people at critical
More informationAMBASSADOR HOUSE. A guide on. Fire Safety in Purpose Built Blocks of Flats
AMBASSADOR HOUSE A guide on Fire Safety in Purpose Built Blocks of Flats INTRODUCTION Fire safety in blocks of flats is something that must be taken very seriously. The Local Government Group (LGG) was
More informationISLE OF WIGHT FIRE & RESCUE SERVICE
ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More informationLighting applications - Emergency lighting. EATON Life Safety Eaton Corporation. All rights reserved.
Lighting applications - Emergency lighting EATON Life Safety 2012 Eaton Corporation. All rights reserved. Emergency Lighting Regulation overview The Power of Innovation! - Transforming Tomorrow Alexios
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)
FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE
FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification
More informationFire Safety Policy 2018/19
Fire Safety Policy 2018/19 Reviewed: March 2016 Next Review: March 2019 1. Policy Statement The School is committed to ensuring, so far as is reasonably practicable, the health, safety and welfare of all
More informationDEF Fire Evacuation and Emergency Planning Criteria
DEF Fire Evacuation and Emergency Planning Criteria This criteria should be used to devise individual DEF specific fire evacuation and emergency plans. It is the responsibility of the Clinic Team Leader
More informationFire Safety Awareness Workbook
Fire Safety Awareness Workbook For All Staff Please ensure you read the workbook thoroughly and complete the assessment at the end Version 2. Introduction Fire safety training is a mandatory element of
More informationFIRE SAFETY LOGBOOK ADDRESS OF PREMISES NOMINATED RESPONSIBLE PERSON
FIRE SAFETY LOGBOOK ADDRESS OF PREMISES NOMINATED RESPONSIBLE PERSON SURESITE LTD. All rights reserved. Not to be reproduced without prior permission 23 AN INTRODUCTION TO YOUR LOG BOOK This fire safety
More informationFIRE RISK ASSESSMENT
FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter
More informationFire Safety Policy Date: 0
Fire Safety Policy Date: 0 Policy Preparation & Introduction This document format has been produced by Firesafe Solutions (UK) Ltd to aid managers, tenants and others responsible for fire safety in their
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the
More informationFire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002
a guide to Fire Alarm Systems Design BS5839 Part1:2002 incorporating Amendment No.2 The Regulatory Reform (Fire Safety) Order (RRO) became law on 1 October 2006 Legally you must comply! What is the RRO?
More informationFire Procedures. April 2016
Estates Department Fire Procedures April 2016 Author Robert Hardman Estates Manager Last Policy Review Date 1/04/16 Next policy Review Date 1/04/17 Reviewed by The Laurus Trust School Fire Procedures Contents
More informationincorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications
incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications Smoke shafts - an overview Scope of this guide Smoke shaft is the common term for
More informationTYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)
TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May
More informationFire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD
Fire Safety Policy Somerville College Woodstock Road Oxford OX2 6HD Table of Contents 1.0 Introduction... 2 2.0 Legislative Requirements... 2 3.0 Fire Risk Assessment... 3 4.0 Management of Fire Safety...
More informationGuidance for writing a Personal Emergency Evacuation Plan (PEEP)
Guidance for writing a Personal Emergency Evacuation Plan (PEEP) If assistance with escape is required, the extent of such assistance should be identified in the PEEP i.e. the number of assistants and
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford
More informationFIRE RISK ASSESSMENT
FIRE RISK ASSESSMENT Fire Precautions (Workplace) Regulations Before beginning the risk assessment, check to see if your workplace has a Fire Certificate. If the workplace does have a Fire Certificate,
More informationAVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard
Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!
More informationFire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /)
Fire resistance (A copy of this is available on www.routledge.com/books/details/ 9780415809696/).1 Fire resistance The overall aim of fire safety precautions is to ensure that: all corridor doors shall
More informationFire Risk Assessment Guidance
Fire Risk Assessment Guidance This document is a guidance note to accompany the example fire risk assessment template. The example fire risk assessment template has been designed with small to medium domestic
More informationFire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan
Fire Risk Assessment Worksafe Solutions Consultancy Ltd 67 Flitwick Road Maulden Bedfordshire, MK45 2BJ Tel: 01525 406787 email enquiries@worksafesoultions.co.uk Index Part 1 Introduction Part 2 The Fire
More informationEmergency Lighting Guide. An authoritative guide to emergency lighting systems and design techniques
Emergency Lighting Guide An authoritative guide to emergency lighting systems and design techniques The Emergi-Lite brand from Thomas & Betts delivers highly versatile emergency lighting solutions to a
More informationThe Social Accountability International (SAI) Fire Safety Checklist
The Social Accountability International (SAI) Fire Safety Checklist Introduction The Social Accountability International (SAI) Fire Safety Checklist is a guidance tool prepared for SA8000 & BSCI Auditors
More informationSpecified Systems List
Specified Systems List Index: SS 1 Automatic systems for fire suppression SS 2 Automatic or manual emergency warning systems for fire or other dangers SS 3 Electromagnetic or automatic doors or windows
More informationSELF PRESERVATION SOCIETY By Jim Creak
SELF PRESERVATION SOCIETY By Editor of the Means of Escape Magazine and Chairman of The Health & Safety Signs Association. w w w. m e a n s - of- e s c a p e. c o m Agenda Regulatory Reform Fire Safety
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationPolicy for Safe Evacuation of Persons with Disabilities
Policy for Safe Evacuation of Persons with Disabilities 1. Policy Statement The London School of Economics is committed to promoting access for people who have a disability or long-term medical condition.
More informationFire Safety Risk Assessment for Treowen, Wonastow, Monmouth, NP25 4DL
Fire Safety Risk Assessment for Treowen, Wonastow, Monmouth, NP25 4DL Record of significant findings Scope of Risk Assessment This fire safety risk assessment covers the use of Treowen as a venue for Civil
More informationMaintenance of Fire Systems
Maintenance of Fire Systems Duty Holder Facilities Manager Responsible Person By John Briggs All Fire Facilities, equipment, systems and devices are required by law to be subject to a suitable system of
More informationHAWAII ADMINISTRATIVE RULES DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS DIVISION OF OCCUPATIONAL SAFETY AND HEALTH GENERAL INDUSTRY STANDARDS
HAWAII ADMINISTRATIVE RULES TITLE 12 DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS SUBTITLE 8 DIVISION OF OCCUPATIONAL SAFETY AND HEALTH PART 2 GENERAL INDUSTRY STANDARDS CHAPTER 71.1 EXIT ROUTES, EMERGENCY
More informationAustralian Standard. Emergency escape lighting and exit signs for buildings. Part 1: System design, installation and operation AS 2293.
AS 2293.1 2005 AS 2293.1 2005 Australian Standard Emergency escape lighting and exit signs for buildings Part 1: System design, installation and operation This Australian Standard was prepared by Committee
More information5 Key Stages to Risk Assessment
5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking
More informationUCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES
Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments
More informationCHILD CARE CENTER INSPECTION CHECKLIST 06C
CHILD CARE CENTER INSPECTION CHECKLIST 06C OCCUPANCY-SPECIFIC FIRE S November 2006: Kansas State Fire Marshal Page: 29 November 2006: Kansas State Fire Marshal Page: 30 CHILD CARE CENTERS & PRESCHOOLS
More informationLYHA Fire Safety Policy
LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with
More informationHEALTH AND SAFETY FIRE SAFETY POLICY Putnoe Primary School
HEALTH AND SAFETY FIRE SAFETY POLICY Putnoe Primary School OBJECTIVE This Fire Safety Policy is designed to help Putnoe Primary School comply with their duties under the Regulatory Reform (Fire Safety
More informationUniversity of London
University of London Senate House and Stewart House Fire safety arrangements Contents 1. Introduction p.2 2. Fire Risk Assessment documentation p.2 3. Action to be taken by a person discovering a fire
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationDesign Guidelines Fire Safety in New and Refurbished Buildings
Design Guidelines Fire Safety in New and Refurbished Buildings Introduction All major new or refurbishment projects must comply with the Technical Standards (Scotland) Regulations as a matter of course.
More informationFire Safety Log Book. Safety through knowledge East Coast Safety Training. Kevin James (Proprietor) 99 Johnson Estate Wheatley Hill Durham DH6 3LH
Safety through knowledge East Coast Safety Training Fire Safety Log Book Kevin James (Proprietor) 99 Johnson Estate Wheatley Hill Durham DH6 3LH Tel: 07904163350 Website: Safety through knowledge East
More informationFIRE EVACUATION PLAN
FIRE EVACUATION PLAN LATTA PAVILION CONDOMINIUMS 1320 FILLMORE AVE. CHARLOTTE, NORTH CAROLINA NOVEMBER 2002 PURPOSE The purpose of this plan is to establish procedures for the systematic, safe, and orderly
More informationFIRE SAFETY POLICY. This policy refers to both Wellington Senior School and Wellington Prep School
FIRE SAFETY POLICY This policy refers to both Wellington Senior School and Wellington Prep School Headmaster Henry Price Author Bursar Date Reviewed 27.06.2017 for implementation on 25.07.2017 Date of
More information