USER S MANUAL. IntelliPack Series 812A/811A Alarms Process Current/Voltage Input

Size: px
Start display at page:

Download "USER S MANUAL. IntelliPack Series 812A/811A Alarms Process Current/Voltage Input"

Transcription

1 IntelliPack Series 812A/811A Alarms Process Current/Voltage Input USER S MANUAL ACROMAG INCORPORATED South Wixom Road P.O. BOX 437 Wixom, MI U.S.A. Tel: (248) Fax: (248) Copyright 1997, Acromag, Inc., Printed in the USA. Data and specifications are subject to change without notice L13F014

2 IntelliPack Series 812A/811A Alarm User s Manual Safety Summary - Symbols on equipment:! Means Caution, refer to this manual for additional information. The information contained in this manual is subject to change without notice. Acromag, Inc., makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Further, Acromag, Inc., assumes no responsibility for any errors that may appear in this manual and makes no commitment to update, or keep current, the information contained in this manual. No part of this manual may be copied or reproduced in any form, without the prior written consent of Acromag, Inc. Table of Contents Page 1.0 INTRODUCTION DESCRIPTION Key IntelliPack 811A/812A Features 3 ACCESSORY ITEMS IntelliPack Configuration Software... 3 IntelliPack Serial Port Adapter.. 4 IntelliPack Cable... 4 IntelliPack Interface Package Optional AC Current Sensor PREPARATION FOR USE... 4 UNPACKING AND INSPECTION 4 INSTALLATION.. 4 Mounting 5 Electrical Connections MODULE CONFIGURATION.. 6 FIELD CONFIGURATION THEORY OF OPERATION SERVICE AND REPAIR... 7 SERVICE AND REPAIR ASSISTANCE. 7 PRELIMINARY SERVICE PROCEDURE SPECIFICATIONS. 7 MODEL NUMBER DEFINITION 7 INPUT SPECIFICATIONS.. 7 RELAY OUTPUT SPECIFICATIONS... 8 DPDT Alarm Relay Specifications 8 SPDT Alarm Relay Specifications 8 ENCLOSURE/PHYSICAL SPECIFICATIONS APPROVALS... 9 ENVIRONMENTAL SPECIFICATIONS... 9 FIELD CONFIGURATION & CONTROLS 9 HOST COMPUTER COMMUNICATION.. 10 SOFTWARE CONFIGURATION List of Drawings Page Simplified Schematic & Contact Protection ( ) Functional Block Diagram ( ). 13 Computer to IntelliPack Connections ( ).. 14 Electrical Connections ( ) AC Sensor Connections ( ) Interposing Relay Connections ( ). 17 Enclosure Dimensions ( ) Windows 95 & NT are registered trademarks of Microsoft Corp. IMPORTANT SAFETY CONSIDERATIONS It is very important for the user to consider the possible adverse effects of power, wiring, component, sensor, or software failures in designing any type of control or monitoring system. This is especially important where economic property loss or human life is involved. It is important that the user employ satisfactory overall system design. It is agreed between the Buyer and Acromag, that this is the Buyer's responsibility. 1.0 INTRODUCTION These instructions cover hardware functionality of the alarm models listed in Table 1. Supplementary sheets are attached for units with special options or features. Table 1: Models Covered in This Manual Series/ Input/Type -Options/Output/ Enclosure/Approvals 1 -Factory Configuration 2 812A C 811A C 811A C Notes (Table 1): 1. Agency approvals include CE, UL Listed, and cul Listed. 2. Include the -C suffix for optional factory configuration. See Factory Configuration Order Form for this model. Otherwise, no suffix is required for standard configuration. Module programming, alarm operation, and use of the Configuration Software is covered in the IntelliPack Alarm Configuration Manual ( ). DESCRIPTION Series 811A/812A Alarms are members of the popular Acromag IntelliPack Alarm & Transmitter family and these models accept DC current, DC voltage, and AC current (using an external sensor) inputs. Output options are two Single-Pole Double-Throw (SPDT) electro-mechanical relays, or one Double-Pole Double-Throw (DPDT) electro-mechanical relay. All units contain an advanced technology microcontroller with integrated downloadable flash memory and EEPROM for non-volatile program, configuration, calibration, and parameter data storage. Units are fully configurable via our user-friendly Windows 95 or NT configuration program. In-field reconfiguration is also possible with module push buttons and status LED s. Once configured, these modules may operate independent of the host computer for true embedded monitoring and control. Modules may be field connected for either DC Voltage or process current input signals. Wide range bipolar DC voltage inputs to 100VDC are possible. The 811A has a single input, while the 812A provides two inputs. On-board excitation is provided at each input to facilitate two-wire transmitter hookup. Each relay has a yellow LED at the front of the module that provides a visual indication of the high or low alarm condition. Additionally, a green Run and yellow Status LED provide local feedback of operating mode, field configuration status, and system diagnostics. Front panel push buttons are available to reset latching alarms and to facilitate field configuration

3 IntelliPack Series 812A/811A Alarm User's Manual The module uses a high-resolution, low-noise, Sigma-Delta Analog-to-Digital Converter (- ADC) to accurately convert the input signal into a digitized value. User-defined alarm setpoints are compared to this value and used to control the built-in alarm relay(s). Each relay may have high or low setpoints plus deadband. Alarm setpoints may be adjusted over the full input range of the unit. Deadband settings for bipolar input ranges should be limited to 50% or less of the range selected. Unipolar input ranges support deadband settings up to 100% of the range selected. Relay actuation is user-selected for failsafe or non-failsafe operation. Relays may be configured as latching, in which case a push button reset is required to reset the latch (this may also be accomplished via software control). Additionally, a programmed relay time delay may be applied to filter transients and minimize nuisance alarms. Wide alarm functionality and convenient reprogrammability makes these alarms extremely powerful and flexible over a broad range of applications. These models may be configured as limit alarms, window alarms, on/off controllers, deviation alarms (dual input models), peak detect alarms, or rate-of-change alarms. Other functions are possible--please consult the factory. An optional AC current sensor (Acromag Model ) is used in conjunction with the DC current input circuit of the 811/812A to implement an AC current alarm for inputs up to 20A rms. The optional AC current sensor is itself an isolated, accurate, toroidal instrument transformer, that outputs a safe, low-level DC milliamp signal to the input of the alarm. As an isolated device, it may also be used to facilitate input-to-input isolation on dual input models. See AC Current Sensor section for more information. All IntelliPack modules are designed to withstand harsh industrial environments. They feature RFI, EMI, ESD, EFT and surge protection, low temperature drift, wide ambient temperature operation, and isolation from input, to power and relay contacts. As a wide-range DC-powered device, the unit may be powered from DC power networks incorporating battery back up. Additionally, the input power terminal is diode-coupled, providing reverse polarity protection. This allows the unit to be connected to redundant power supplies, or several units to safely share a single DC supply. Units are DIN rail mounted and removable terminal blocks facilitate ease of installation and replacement, without having to remove wiring. Alarm relay and power wiring are inserted at one side of the unit, while input wiring is inserted at the other side. Connectors are industry standard screw clamp type and accept a wide range of wire sizes. The safe, compact, rugged, reconfigurable, and reliable design of this alarm makes it an ideal choice for control room and field applications. Custom alarm configurations are also available (please consult the factory). Key IntelliPack 811A/812A Features Agency Approvals - CE, UL Listed, & cul Listed. Windows Configuration - Fully reconfigurable via our user friendly Windows 95 or NT Configuration Program. Nonvolatile Reprogrammable Memory - This module has an advanced technology microcontroller with integrated, nonvolatile, downloadable flash memory and EEPROM. Convenient Field Reprogrammability - The unit includes push-button reconfiguration of key alarm functions in combination with LED indicators to facilitate in-field changes without having to connect a host computer. Key IntelliPack 811A/812A Features continued Wide Alarm Functionality - The unit may be programmed for a wide range of alarm types including limit, window, on/off controller, deviation (dual input models), peak detection, and rate-of-change alarms. Other functions are possible (please consult the factory). Flexible DC Current or Voltage Inputs - Accepts process current (0-24mA), or wide range voltage inputs to 100VDC. Optional AC Current Input - An optional AC current sensor can be purchased separately to support AC current inputs. Wide Ambient Operation - The unit is designed for operation over wide ambient temperatures. Convenient Input Excitation Supply - Each input includes an excitation supply for operation with two-wire transmitters. High-Power SPDT or DPDT Relays - The module includes either one Double-Pole-Double-Throw (DPDT) electromechanical relay, or two Single-Pole-Double-Throw (SPDT) electromechanical relays, for switching voltages to 230VAC at currents to 5A. Fully Isolated - Input(s), power, and relay contacts are all isolated from each other. Dual input units share a common and do not provide input-to-input isolation. Self-Diagnostics - Built-in routines operate upon power-up for reliable service, easy maintenance, and troubleshooting. LED Indicators - A green LED indicates power. A yellow status LED will flash ON/OFF when an over/under range limit of the A/D converter is reached. A yellow alarm LED indicates when a relay is in alarm. These LED s have other functions in field program mode. Wide-Range DC-Powered - This device receives power over a wide DC supply range and the power terminal is diode-coupled. This makes the alarm useful for systems with redundant supplies, and/or battery backup power. Hardened For Harsh Environments - The unit will operate reliably in harsh industrial environments and includes protection from RFI, EMI, ESD, Surges, and EFT. Convenient Mounting, Removal, & Replacement - DIN-Rail mounting and plug-in type terminal blocks for input, power, and relay contact wiring makes replacement and removal easy. High-Resolution Precise A/D Conversion - Alarms include an advanced, high-resolution, low noise, Sigma-Delta Analog to Digital Converter (- ADC) for high accuracy and reliability. Individual Relay Functionality - Each relay of dual relay units may be programmed for different functions. Failsafe or Non-Failsafe Relay Operation - The unit may be configured for failsafe or non-failsafe relay operation. Upon power up, relay may cycle states during diagnostic operation. Configurable Setpoint With Deadband - Programmable deadband is associated with each setpoint to eliminate relay chatter and prolong contact life. Configurable Latching or Momentary Alarms - These alarms may be configured for automatic alarm reset, or latching alarm with manual push-button or software reset. Configurable Relay Time Delay Filters Transients - Useful for increased noise immunity and to filter transients. ACCESSORY ITEMS The following IntelliPack accessories are available from Acromag. Acromag also offers other standard and custom alarm and transmitter types to serve a wide range of applications (please consult the factory)

4 IntelliPack Series 812A/811A Alarm User's Manual IntelliPack Configuration Software (Model ) IntelliPack alarms and transmitters are configured using this user-friendly Windows 95 or NT Configuration Program. This software also includes the IntelliPack Alarm Configuration Manual ( ) and IntelliPack Transmitter Configuration Manual ( ). These manuals describe software operation and various alarm and transmitter functions in detail. All alarm functions are programmable and downloadable to the alarm modules via this software. Non-volatile memory provides program, configuration, and data storage within the IntelliPack. IntelliPack Serial Port Adapter (Model ) This adapter serves as an isolated interface converter between the EIA232 serial port of the host computer and the Serial Peripheral Interface (SPI) port of the IntelliPack module. It is used in conjunction with the Acromag IntelliPack Configuration Software to program and configure the modules. This adapter requires no user adjustment, no external power, and operates transparent to the user. It receives its power from the IntelliPack module. The adapter has a DB9S connector that mates to the common DB9P serial port connector of a host computer. The adapter also has a 6-wire RJ11 phone jack to connect to the IntelliPack alarm module via a separate interconnecting cable (described below). Refer to Drawing for computer to IntelliPack connection details. IntelliPack Cable (Model ) This 6-wire cable is used to connect the SPI port of the IntelliPack Serial Port Adapter to the IntelliPack. This cable carries the SPI data and clock signals, reset signal, and 5V power and ground signals. The cable is 7 feet long and has a 6-wire RJ11 plug at both ends which snap into jacks on the Serial Port Adapter and the IntelliPack module. IntelliPack Software Interface Package (Model 800C-SIP) The IntelliPack Interface Package combines the Configuration Software ( ), Alarm Configuration Manual ( ), Transmitter Configuration Manual ( ), Serial Port Adapter ( ), and Cable ( ), into a complete kit for interfacing with IntelliPack Alarms and Transmitters. AC Current Sensor (Model ) This optional sensor is an accurate toroidal instrument transformer used to convert a sinusoidal 50-60Hz AC current signal into a low level DC milliampere signal of 0 to 11.17mA. The input AC current range is a simple function of the number of turns placed through the toroid as shown in Table 2. This sensor is isolated and requires no calibration or adjustment. When used with an IntelliPack module, it provides redundant input isolation and may facilitate inputto-input isolation on dual input units. Table 2: AC Current Sensor Turns & Range AC Current Input Range Primary Turns Sensor Output (Red/Black Wires) 0 to 20A AC 1 0 to 11.17mA DC 0 to 10A AC 2 0 to 5A AC 4 0 to 2A AC 10 0 to 1A AC 20 The output wires of this sensor are polarized with red as () plus and black as (-) minus. Normally these output wires are attached to one end of a user supplied cable while the other end connects to the IntelliPack s process current input terminals. Input Burden: A function of the wire gauge resistance used for primary turns (the current carrying wire being monitored). AC Current Sensor to Transmitter Wiring Distance: 400 feet maximum for 18 gauge wire. Other wire gauges can be used as long as the resistance of both wires is less than 5. Input Overload: The AC current sensor will withstand overload conditions as follows: 20 times full scale for 0.01 seconds. 10 times full scale for 0.1 seconds. 5 times full scale for 1.0 second. 2.0 PREPARATION FOR USE UNPACKING AND INSPECTION Upon receipt of this product, inspect the shipping carton for evidence of mishandling during transit. If the shipping carton is badly damaged or water stained, request that the carrier's agent be present when the carton is opened. If the carrier's agent is absent when the carton is opened and the contents of the carton are damaged, keep the carton and packing material for the agent's inspection. For repairs to a product damaged in shipment, refer to the Acromag Service Policy to obtain return instructions. It is suggested that salvageable shipping cartons and packing material be saved for future use in the event the product must be shipped. This module is physically protected with packing material and electrically protected with an anti-static bag during shipment. However, it is recommended that the module be visually inspected for evidence of mishandling prior to applying power. This circuit utilizes static sensitive components and should only be handled at a static-safe workstation. INSTALLATION The alarm module is packaged in a general purpose plastic enclosure. Use an auxiliary enclosure to protect the unit in unfavorable environments or vulnerable locations, or to maintain conformance to applicable safety standards. Stay within the specified operating temperature range for best performance. As shipped from the factory, the unit is factory calibrated for all valid input ranges and has the default configuration shown in Table 3: WARNING: Applicable IEC Safety Standards may require that this device be mounted within an approved metal enclosure or subsystem, particularly for applications with voltages greater than or equal to 75VDC or 50VAC

5 IntelliPack Series 812A/811A Alarm User's Manual Table 3: 811A/812A Default Factory Configuration CONFIGURATION PARAMETER INPUT 1 INPUT 2 Input Range 0-22mA 0-22mA Alarm Type Limit Limit ALARM 1 ALARM 2 Mode High Limit Low limit Setpoint 20mA 4mA Deadband 1% (0.16mA) 1% (0.16mA) RELAY 1 RELAY 2 Time Delay 100ms 100ms Operating Mode Failsafe Failsafe Reset Auto (Momentary) Auto (Momentary) Notes (Table 3): Shaded entries do not apply to Model 811A-0100 units. Your application may differ from the default configuration and will require the alarm to be reconfigured to suit your needs. This is accomplished with Acromag s user-friendly Windows 95 /NT Configuration Program & Serial Port Adapter. Configuration is normally done prior to field installation since field configurability via the module s push-buttons is generally limited to setpoint and deadband adjustments where applicable. See the Alarm Configuration Manual for instructions. Mounting: Refer to the Enclosure Dimensions Drawing for alarm mounting and clearance dimensions. DIN Rail Mounting: This module can be mounted on "T" type DIN rails. Use suitable fastening hardware to secure the DIN rail to the mounting surface. Units may be mounted side-byside on 1-inch centers for limited space applications. "T" Rail (35mm), Type EN50022: To attach a module to this style of DIN rail, angle the top of the unit towards the rail and locate the top groove of the adapter over the upper lip of the rail. Firmly push the unit towards the rail until it snaps solidly into place. To remove a module, first separate the input terminal block(s) from the bottom side of the module to create clearance to the DIN mounting area. Next, insert a screwdriver into the lower arm of the DIN rail connector and use it as a lever to force the connector down until the unit disengages from the rail. Electrical Connections Terminals can accommodate wire from AWG (stranded or solid copper). Strip back wire insulation 1/4-inch on each lead before installing into the terminal block. Input wiring may be shielded or unshielded twisted pair. Since common mode voltages can exist on signal wiring, adequate wire insulation should be used and proper wiring practices followed. It is recommended that alarm contacts and power wiring be separated from input signal wiring for safety and low noise pickup. Input, power, and relay terminals are plug-in type and can be easily removed to facilitate module removal or replacement without removing individual wires. Be sure to remove power and/or disable the load before unplugging the terminals to uninstall the module, or before attempting service. All connections must be made with power removed. CAUTION: Risk of Electric Shock - More than one disconnect switch may be required to de-energize the equipment before servicing. 1. Power: Refer to Electrical Connections Drawing Variations in power supply voltage within rated limits has negligible effect on module accuracy. For supply connections, use No. 14 AWG wires rated for at least 75C. The power terminal is diode-coupled for reverse polarity protection. 2. DC Voltage/Current Inputs (Without AC Current Sensor): Connect input(s) per Drawing Observe proper polarity (see label for input type). An excitation supply is provided at the input terminals for two-wire transmitters. Dual input models do not provide input-to-input isolation. 3. AC Current Input (Optional): Refer to Drawing to connect the optional AC current sensor. This sensor is typically mounted near the AC current measured and will transmit a low level DC milliampere signal to the module. This allows the module to be mounted remote from the AC signal and sensor, and connected using small gauge wire. The sensor output (Red/Black) wires can be shorted, open-circuited, or removed from the alarm input terminals, without hazard to personnel or to the sensor. As an isolated device, this sensor may be used to facilitate input-to-input isolation on dual input units. AC Current Sensor: Per Table 2 on Page 4, loop the required number of turns through the toroid for the full-scale current range required by your application. Use the cable tie provided with the sensor to mechanically secure it. DANGER: If the AC current sensor is used with an AC Current Transformer (C.T.), disconnect power from the C.T., or short the output of the C.T., before removing the wire going through the AC current sensor. If this is not done, an open circuited C.T. will generate hazardous high voltages and possible C.T. damage. 4. Output Contacts: Wire relay contacts as shown in Electrical Connections Drawing See the Alarm Relay Specifications for power capacity. If necessary, an interposing relay can be used to switch higher currents as shown in Interposing Relay Connection Drawing Electromechanical Relay Contact Protection: To maximize relay life with inductive loads, external protection is required. For DC inductive loads, place a diode across the load (1N4006 or equivalent) with cathode to () and anode to (-). For AC inductive loads, place a Metal Oxide Varistor (MOV) across the load. See Relay Contact Protection Drawing for details. IMPORTANT: Noise and/or jitter on the input signal has the effect of reducing (narrowing) the instrument s deadband and may produce contact chatter. The long term effect of this will reduce the life of mechanical relays. To reduce this undesired effect, you should increase the effective deadband

6 IntelliPack Series 812A/811A Alarm User's Manual 5. Grounding: See Electrical Connections Drawing The module housing is plastic and does not require an earth ground connection. However, there are mounting positions on the input terminals to connect a cable shield, plus earth ground. These connections are isolated from the input circuit and are recommended to minimize noise and help protect the unit from damaging input transients. WARNING: For compliance to applicable safety and performance standards, the use of shielded cable is recommended as shown in Drawing Further, the application of earth ground must be in place as shown in Drawing Failure to adhere to sound wiring and grounding practices may compromise safety & performance. 3.0 MODULE CONFIGURATION The alarm module needs to be configured for your application. Alarm configuration is done using Acromag s Windows 95 or NT Configuration Program and the IntelliPack Serial Port Adapter. Configuration details are covered in Alarm Configuration Manual Limited field configuration via the module s push-buttons and LED s is covered below. FIELD CONFIGURATION This program mode allows adjustment to key alarm parameters in the field, without having to connect a host computer. Field reconfigurability is accomplished via the alarm module s MODE & SET push buttons and the alarm LED s (see Drawing ). Field reconfiguration via these controls will vary depending on the alarm function (see Table 6). Equipment Required An accurate input source (voltage or current) adjustable over the range required for alarm setpoint and dropout/deadband. Two input sources are required for deviation alarms. Note: For best results, the input source(s) must be accurate beyond the required specifications. For voltage inputs, use a voltage source with an output impedance of 100 or less. General Field Programming Procedure The following procedure uses the corresponding relay LED indicators (constant ON or FLASHING) to indicate which relay parameters (relay 1 or 2) are being modified (see Table 6). CAUTION: To avoid damage to the unit, do not insert sharp or oversized objects into the push-button switch openings. When depressing the push-buttons, use a blunt tipped object and apply pressure gradually until you feel or hear the tactile response. 1. Connect a precision voltage or current source to the input, as required (refer to Electrical Connections Drawing ). For deviation alarms, two input sources are required. 2. Apply power and wait for the module s green Run LED to light (continuous ON). 3. Press and hold the MODE push button until the Run LED goes out, and the relay 1 LED lights (see Table 6). In this mode, the unit is ready to accept an input for parameter 1 of relay 1 per Table 4 below. If you do not wish to change this parameter, skip to step Adjust the input source(s) to the relay parameter 1 level shown in Table 4 according to your alarm function (deviation alarms require an adjustment at both inputs). General Field Programming Procedure continued Table 4: Relay Config Parameter 1 Per Alarm Function ALARM FUNCTION PARAMETER 1 Limit Alarm High or Low Setpoint Value Window Alarm High Setpoint Value On/Off Controller Controller On Setpoint Value Deviation Alarm (Both Inputs Required) Set the Deviation Amount (Use Proper Polarity between inputs) Peak/Valley Detector Peak/Valley Detect Start Value Rate-of-Change Alarm Rate-Of-Change Threshold 5. Press the SET push button to accept the relay 1 parameter indicated in Table 4. Note that every time the SET button is pressed, the yellow Status LED will flash once and the value at the input(s) will be captured. 6. Press the MODE push button once. The relay 1 LED should start flashing (see Table 6). The unit is ready to accept the second parameter for the relay shown in Table 5: 7. Adjust the input source(s) to the desired level. 8. Press the SET button to accept the parameter noted in Table 5 for your alarm function. The module will use the difference between the two programmed parameter values to calculate deadband where applicable. Caution should be taken to avoid creating a Dropout Value outside of the input range. Table 5: Relay Config Parameter 2 Per Alarm Function ALARM FUNCTION PARAMETER 2 Limit Alarm Setpoint Dropout Value Window Alarm Low Setpoint Value On/Off Controller Controller Off Setpoint Value Deviation Alarm (Both Deviation Dropout Value Inputs Required) Peak/Valley Detector Peak or Valley Dropout Value Rate-of-Change Dropout Rate for Rate-of-Change 9. If two relays are being programmed, Press the MODE push button again to complete the first relay program cycle and repeat the above procedure (steps 4-8) to configure parameters for relay 2 (relay 2 LED will light, Run LED will still be off). You may skip relay 2 by pressing MODE again as in step After configuring relay 1, and relay 2 (where applicable), press the MODE push button again to complete the program sequence and return to run mode. The green Run LED will turn ON. This indicates that the unit has returned to the operating mode and the yellow relay LED s will now reflect actual alarm status per your application. Notes (Field Program Procedure): 1. During field configuration of dual relay models, the relay LED will be ON or FLASHING, corresponding to the relay being programmed and the parameter being adjusted as in Table 6: Table 6: Field Configuration Relay LED Mode Indication ALARM RELAY 1 or 2 LED FUNCTION ON FLASHING Limit HI/LO Setpoint HI/LO Dropout Window High Setpoint Low Setpoint ON/OFF Controller ON Setpoint OFF Setpoint Deviation Deviation Dropout Peak/Valley Detect P/V Detect Start P/V Dropout Rate-Of-Change ROC Threshold ROC Dropout - 6 -

7 IntelliPack Series 812A/811A Alarm User's Manual Notes (Field Program Procedure) continued: 2. If the alarm is in configuration mode and no push buttons are pressed after 2 minutes, then the alarm will return to normal operating mode, the green Run LED will light, and no changes will be made to the previously configured values. 3. Latching alarms require a push button reset to exit the alarm state (this may also be accomplished under software control). 4. Deadband and latching relays have no application with respect to on/off controller functionality. 5. Rate-of-change units (volts/second) are software configured only and not configured via the module s push-buttons. 6. Note that alarm operating functions may be selected on a per relay basis. For example, relay 1 could function as a limit alarm monitoring input 1, while relay 2 (if present) functions as an on/off controller monitoring input 2. Note that some functions require the use of both inputs of dual input models. 4.0 THEORY OF OPERATION Refer to Drawing to gain a better understanding of the circuit. These alarms will pre-filter a signal and convert the signal to a scaled voltage--either through a voltage divider circuit (voltage inputs), or a current sink resistor (current inputs). An A/D converter stage then applies appropriate gain to the signal, digitally filters it, and performs analog-to-digital conversion. The digital signal is then transmitted serially to a microcontroller. The microcontroller compares the signal value to the limit value according to the alarm type, and completes all necessary alarm functions per its embedded program. Configuration and calibration parameters are stored in non-volatile memory within the microprocessor. A wide input switching regulator (isolated flyback mode) provides isolated 5V power to the circuit, plus a 15V excitation supply. 5.0 SERVICE AND REPAIR CAUTION: Risk of Electric Shock - More than one disconnect switch may be required to de-energize the equipment before servicing. SERVICE AND REPAIR ASSISTANCE This module contains solid-state components and requires no maintenance, except for periodic cleaning and configuration parameter verification (setpoint, deadband, etc). Since Surface Mount Technology (SMT) boards are generally difficult to repair, it is highly recommended that a non-functioning module be returned to Acromag for repair. The board may be damaged unless special SMT repair and service tools are used. Further, Acromag has automated test equipment that thoroughly checks and calibrates the performance of each module. Please refer to Acromag s Service Policy Bulletin or contact Acromag for complete details on how to obtain service parts and repair. PRELIMINARY SERVICE PROCEDURE Before beginning repair, be sure that all installation and configuration procedures have been followed. The unit routinely performs internal diagnostics following power-up or reset. During this period, all LED s will turn ON momentarily, and the green Run LED flashes. If the diagnostics complete successfully, the Run LED will stop flashing after two seconds and then remain ON. This indicates that the unit is operating normally. If the Run LED continues to flash, then this is indicative of a problem. In this case, use the Acromag IntelliPack Configuration Software to reconfigure the module and this will usually cure the problem. If the diagnostics indicate a problem via a continuously flashing green LED, or if other evidence points to a problem with the unit, an effective and convenient fault diagnosis method is to exchange the questionable module with a known good unit. The IntelliPack Serial Port Adapter also contains a red LED visible at the small opening in the enclosure to the right of the RJ11 receptacle. If this LED is OFF or Flashing, then a communication interface problem exists. Note that the adapter receives its power from the IntelliPack module. A constant ON LED indicates a properly working and powered serial interface adapter. Acromag s Application Engineers can provide further technical assistance if required. When needed, complete repair services are available from Acromag. 6.0 SPECIFICATIONS 812A-0200, Dual I/V Input, Dual SPDT Relay 811A-0200, Single I/V Input, Dual SPDT Relay 811A-0100, Single I/V Input, Single DPDT Relay General: The IntelliPack 811A and 812A are DC-powered alarms which condition DC current, DC voltage, and AC current (using an external sensor), and provide either two Single-Pole Double-Throw (SPDT) electromechanical alarm relays, or one Double-Pole Double-Throw (DPDT) electro-mechanical alarm relay. Isolation is supplied between the sensor input, the relay contacts, and power. This alarm is DIN-rail mounted. The unit is configured and calibrated using our user-friendly Window 95 or NT IntelliPack Configuration Program. Pushbuttons on the module allow field adjustment of setpoint and deadband (where applicable). All calibration and configuration information is stored in non-volatile reprogrammable memory in the module. MODEL NUMBER DEFINITION Alarms are color coded with a yellow label. The prefix 8 denotes the IntelliPack Series 800, while the A suffix specifies that outputs are alarm contacts. 812A: Monitors two DC voltage or current inputs, or AC current inputs (using an external sensor). 811A: Monitors a single DC voltage or current input, or AC current input (using external sensor). -0x00: Numbers in this model suffix represent the following options, respectively: Options = 0: None (reserved for future use); Output = 1: One DPDT relay (described subsequently); Output = 2: Two SPDT relays (described subsequently); Enclosure = 0: DIN rail mount (described subsequently); Approvals = 0: Pending (please consult the factory)

8 IntelliPack Series 812A/811A Alarm User's Manual INPUT SPECIFICATIONS Unit must be wired and configured for the intended input type and range (see Installation Section for details). The following paragraphs summarize this model s input types, ranges, and applicable specifications. DC (Process) Current: 0 to 22mA DC & 0-5mA DC. A precision 24.9 current sink resistor converts the input current to a voltage that is processed by the A/D converter. An optional external sensor is required to monitor AC current signals (Acromag Model ). This sensor generates a DC milliampere signal of 0 to 11.17mA for the module (see Table 2 for scaling to AC current). This module also provides one excitation supply per input for use with 2-wire transmitters. Current Input Reference Test Conditions: 4 to 20mA current input using the on-board excitation supply; Ambient = 25 C; Power Supply = 24V DC; Relay Time Delay = 100ms. Input Overvoltage Protection: Bipolar Transient Voltage Suppressers (TVS), 7.6V clamp level typical. DC Voltage (100:1 Input Divider): User-configurable for the following bipolar voltage ranges: 50 to 100V; 25 to 50V; 12 to 25V; 6 to 12V; 3 to 6V; & 1 to 3V. Input Impedance: 500K. Voltage Input Reference Test Conditions: -10 to 10V DC Input; Ambient = 25 C; Power Supply = 24VDC; Relay Alarm Delay = 100ms. Input Overvoltage Protection: Bipolar Transient Voltage Suppressers (TVS), 135V clamp level typical. General Specifications Accuracy: Better than 0.05% of input span, typical. Accuracy Versus Temperature: Better than ±0.005% of input span per C or 1uV, whichever is greater. Resolution: See Table 7. Table 7: A/D Resolution Per Nominal Input Range Gain Range A/D Resolution mA, 0-24mA Typ 757nA/LSB 2 0-5mA, 0-6mA Typ 757nA/LSB 1 50 to 100V 3770uV/LSB 2 25 to 50V 1880uV/LSB 4 12 to 25V 942uV/LSB 8 6 to 12V 471uV/LSB 16 3 to 6V 236uV/LSB 32 1 to 3V 118uV/LSB 64, 128 Not Used NA Response Time: Less than 100ms typical to 98% of final value for a step change in input. Note a software configurable delay can be implemented for filtering transients and this will increase the response time. Input Filter: Normal mode filtering, plus digital filtering optimized and fixed per input range within the A/D. Input Bandwidth: Alarm contacts will track an input square wave to approximately 3.5Hz. A relay time delay can be implemented for filtering transients and this will lower the relative bandwidth. Noise Rejection (Normal Mode): Better than 60Hz, typical with 100 input unbalance (24.9 for process currents). Noise Rejection (Common Mode): Better than 60Hz, typical with 100 input unbalance (24.9 for process currents). Analog to Digital Converter (A/D): A 16-bit - converter, Analog Devices AD7714AR-5. Input Conversion Rate: 10 conversions per channel per second (dual input models); 20 conversions per second (single input models). Input bias current: ±10nA maximum, excluding excitation current of process current inputs. Input Excitation Supply: 15V DC typical, current limited to approximately 24mA, one per input. For use with two-wire process current transmitters. RELAY OUTPUT SPECIFICATIONS DPDT ALARM OUTPUT (-x1xx): This model contains a single DPDT electromechanical relay comprised of two, high reliability, Form C (Normally Open and Normally Closed) contacts. The DPDT relay option is only available on single input models (811A). DPDT Alarm Relay Specifications: Electrical Life - CSA Ratings: 25VDC, 5A, 10 5 operations, resistive. 48VDC, 0.8A, 10 5 operations, resistive. 240VDC, 0.1A, 10 5 operations, resistive. 120/240VAC, 5A, 3x10 4 operations, resistive. Note: To control a higher amperage device, such as a pump, an interposing relay may be used (see Interposing Relay Connections Drawing ). Contact Material: Silver-Nickel (AgNi 90/10). Initial Dielectric Strength: Between open contacts: 1000VAC rms (1 minute). Expected Mechanical Life: 30 million operations. Note: External relay contact protection is required for use with inductive loads (see Relay Contact Protection Drawing ). Failure to use adequate protection may reduce contact life or damage the unit. Relay Response (No Relay Time Delay): Relay contacts will switch within 150ms for an input step change from 10% of span on one side of an alarm point to 5% of span on the other side of the alarm point. SPDT ALARM OUTPUT (-x2xx): This model contains two independent electromechanical relays. Each relay contains high reliability, Form C (Normally Open and Normally Closed) SPDT contacts. One relay is assigned to each input of dual input models (812A); or both relays to the same input on single input models (811A). Each relay may have any alarm operating function assigned to it. SPDT Alarm Relay Specifications: Electrical Life - CSA Ratings: 25VDC, 5A, 10 5 operations, resistive. 48VDC, 0.8A, 10 5 operations, resistive. 240VDC, 0.1A, 10 5 operations, resistive. 120VAC/240VAC, 5A, 3x10 4 operations, resistive. Note: To control a higher amperage device, such as a pump, an interposing relay may be used (see Interposing Relay Connections Drawing ). Contact Material: Silver-cadmium oxide (AgCdO). Initial Dielectric Strength: Between open contacts: 1000VAC rms

9 IntelliPack Series 812A/811A Alarm User's Manual Expected Mechanical Life: 20 million operations. Note: External contact protection is required for use with inductive loads (see Contact Protection Drawing ). Failure to use adequate protection may reduce contact life or damage the unit. Relay Response (No Relay Time Delay): Relay contacts will switch within 150ms for an input step change from 10% of span on one side of an alarm point to 5% of span on the other side of the alarm point. ENCLOSURE/PHYSICAL SPECIFICATIONS See Enclosure Dimensions Drawing for details. Units are packaged in a general purpose plastic enclosure with an integrated DIN rail mount for high density mounting (approximately 1 wide per unit). Dimensions: 1.05 wide x 4.68 high x 4.35 deep. DIN Rail Mounting (-xx0x): DIN rail mount, Type EN50022; T rail (35mm). Connectors: Removable plug-in type terminal blocks; Current/ Voltage Ratings: 15A / 300V; Wire Range: AWG #14-24 (stranded or solid copper); Separate terminal blocks provided for power, input(s), & relay contacts. For supply connections, use No. 14 AWG wires rated for at least 75C. Case Material: Self-extinguishing NYLON type 6.6 polyamide thermoplastic UL94 V-2, color beige; general purpose NEMA Type 1 enclosure. Printed Circuit Boards: Military grade FR-4 epoxy glass. Shipping Weight: 1 pound (0.45 Kg) packed. APPROVALS (-xxx0) 0: Agency Approvals - CE, UL Listed, and cul Listed. UL3121 First Edition, CSA C22.2 No , Low Voltage Directive (72/23/EEC), EMC (89/336/EEC) Directives. Product approval is limited to the general safety requirements of the above standards. Warning: This product is not approved for hazardous location applications. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: -25C to 70C (-13F to 158F). Storage Temperature: -40C to 85C (-40F to 185F). Relative Humidity: 5 to 95%, non-condensing. Power Requirements: 10V Minimum to 36V DC Maximum. Current draw is a function of the supply voltage and model number (see Table 8). Currents given assume the input excitation supplies are delivering full-scale currents, all relays are energized, and the Serial Port Adapter is connected. An internal diode provides reverse polarity protection. CAUTION: Do not exceed 36VDC peak, to avoid damage to the module. Table 8: Supply Current Versus Voltage Supply Maximum Supply Current Voltage 812A A A V 250mA 170mA 160mA 12V 195mA 140mA 130mA 15V 155mA 110mA 100mA 24V 110mA 70mA 65mA 36V 100mA 55mA 55mA Note: Disconnecting the Serial Port Adapter and/or unloading the optional excitation supplies will reduce the supply current consumption considerably. IMPORTANT External Fuse: If unit is powered from a supply capable of delivering more than 1A to the unit, it is recommended that this current be limited via a high surge tolerant fuse rated for a maximum current of 1A or less (for example, see Bel Fuse MJS1). Power Supply Effect: DC Volts: Less than 0.001% of input span change per volt DC, for rated power supply variations. 60/120 Hz Ripple: Less than 0.01% of input span per volt peak-to-peak of power supply ripple. Isolation: Input, relay contacts, and power are isolated from each other for common-mode voltages up to 250VAC, or 354V DC off DC power ground, on a continuous basis (will withstand 1500VAC dielectric strength test for one minute without breakdown). This complies with test requirements outlined in ANSI/ISA for the voltage rating specified. Dual input units share common and isolation does not apply from input-to-input. Input-to-Input Isolation: None - dual input units share a circuit common and are not isolated from each other. Installation Category: Designed to operate in an Installation Category (Overvoltage Category) II environment per IEC (1990). Radiated Field Immunity (RFI): Complies with IEC Level 3 (10V/m, 80 to 1000MHz AM & 900MHz keyed) 27 to 500MHz) and European Norm EN Electromagnetic Interference Immunity (EMI): No relay trips will occur beyond 0.25% of input span from setpoint under the influence of EMI from switching solenoids, commutator motors, and drill motors. Electrical Fast Transient Immunity (EFT): Complies with IEC Level 3 (2KV power; 1KV signal lines) and European Norm EN Electrostatic Discharge (ESD) Immunity: Complies with IEC Level 3 (8KV/4KV air/direct discharge) to the enclosure port and European Norm EN Surge Immunity: Complies with IEC Level 3 (2.0KV) and European Norm EN Radiated Emissions: Meets or exceeds European Norm EN for class B equipment. FIELD CONFIGURATION AND CONTROLS Field programmability of key alarm functions (e.g. setpoint and deadband) is accomplished with module push buttons and LED indicators in the absence of a host computer. However, the unit must be configured initially using the IntelliPack Configuration Software before alarm setpoint or deadband can be changed in the field. Module Push Buttons (See Dwg for Location): - 9 -

10 IntelliPack Series 812A/811A Alarm User's Manual Mode - Used to change mode of field configuration. Set - Used to accept input data during field calibration. Reset 1 - Used to reset a latched alarm for relay 1. Reset 2 - Used to reset a latched alarm for relay 2. LED Indicators (See Dwg for Location): Operating Mode Run (Green) - Constant ON indicates power is applied and unit is operating normally. Upon power up, the module may take up to 20 seconds to perform internal diagnostics, during diagnostics, the relay may cycle states before the module becomes operational. Flashing ON/OFF indicates that unit is performing diagnostics (first second following power-up) or has failed diagnostics (after a few seconds). Status (Yellow) - Flashing ON/OFF indicates an over/under range limit of the A/D converter is reached. Relay 1 Alarm (Yellow) - Constant ON indicates alarm condition for relay 1. During field configuration, this LED has a different function (see below). Relay 2 Alarm (Yellow) - Constant ON indicates alarm condition for relay 2. During field configuration, this LED has a different function (see below). Field Configuration Mode Run (Green) - Turned OFF in field configuration mode. Status (Yellow) - Blinks each time the SET push-button is pressed to capture an input signal during field configuration mode. Relay 1 Alarm (Yellow) - Constant ON or flashing ON/OFF indicates whether configuration parameter 1 or 2, respectively, of relay 1 is being programmed in field configuration mode (see Table 6). Relay 2 Alarm (Yellow) - Constant ON or flashing ON/OFF indicates whether configuration parameter 1 or 2, respectively, of relay 2 is being programmed in field configuration mode (see Table 6). HOST COMPUTER COMMUNICATION Host Communication Port (SPI): The IntelliPack Serial Peripheral Interface (SPI) port utilizes a standard RJ11, 6-wire phone jack. Configuration information is downloaded from the host computer through one of its EIA232 serial ports. The serial port must be connected to the module through an IntelliPack Serial Port Adapter, which serves as an isolated interface converter between EIA232 and the IntelliPack module s SPI port (standard RJ11 phone jack). Baud Rate (EIA232): 19.2K baud. SOFTWARE CONFIGURATION Units are fully reprogrammable via the user-friendly Windows 95 or NT IntelliPack Configuration Program (Model ). A cable ( ) and converter ( ) are required to complete the interface (Software Interface Package 800C-SIP). See Drawing The following attributes are selectable via the Configuration Software. Applicable attributes and their functions may vary with respect to the alarm model and operating function. Refer to the IntelliPack Alarm Configuration Manual ( ) for a more detailed explanation of these attributes and their application. Input 1 & Input 2 Configuration Input - Range: The alarm input can be configured to accept any of the input ranges described in the Input Specifications using the IntelliPack Configuration Software. Input Calibration: The configuration software can be used to calibrate the input conditioning circuit of this module. Alarm 1 & Alarm 2 Configuration Each input of this model may be configured for one of six different alarm types/operating functions: Alarm Operating Functions: The following gives a brief description of current available alarm functions for this model. Other modes are possible (please consult the factory). Limit Alarm:. Limit alarms have only a single high or low setpoint applied to an input at a time. The relay will enter the alarm state when either the user-defined high or low setpoint is exceeded for the specified amount of time. Relay remains in alarm until the input has retreated past the setpoint, plus any deadband, for the specified amount of time Window: Window alarms have both high and low setpoints on an input at a time. The relay will enter the alarm state when either the user-defined high or low setpoint is exceeded for the specified amount of time. Relay remains in alarm until the input signal has retreated past the defined setpoint, plus any deadband, for the specified amount of time. On/Off Controller: The relay will enter the alarm state when the on setpoint has been exceeded for the specified amount of time. Relay remains in alarm until the input signal has retreated past the off setpoint (deadband does not apply) for the specified amount of time. Note that latching relays are not applicable to On/Off Controllers. Deviation (Dual Input Models Only): The deviation alarm (positive, negative, or absolute) uses the difference between inputs to generate the alarm condition. One input is selected to serve as the reference and the deviation of the other input is measured from this. Positive deviation is determined via (input1-input2), negative deviation via (input2-input1), and absolute deviation is determined via the absolute value of [input1-input2]. The relay will enter the alarm state when the deviation limit has been exceeded for the specified amount of time. The relay remains in the alarm state until the signal has retreated to within the deviation limit, plus any deadband, for the specified amount of time. Peak/Valley Detection: An alarm condition is produced for a user defined peak (max) or valley (min) condition of the desired input signal. The peak/valley detection function will not activate until the input signal has exceeded the userspecified peak or valley start sensing level for the userspecified amount of time delay. Once the peak/valley function has been activated, the input is monitored to detect a retreat in the input by an amount specified as the deadband value. When this occurs, the relay will enter the alarm state (no delay applies). The relay remains in the alarm state until the signal has further retreated beyond a user specified deactivate value (no delay applies). Note that if the start value is greater than the deactivate value, then a peak condition will be detected. Otherwise, a valley detection will be made

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm Table of Contents Page Introduction 1 Description 1 Specifications 2 Installation 3 Calibration 4 General Maintenance 5 List of

More information

IntelliPack : 800 Series

IntelliPack : 800 Series 800 Series Models by Function Guide 800T Intelligent Transmitters 800A Intelligent Alarms 890M Math/Computation IntelliPack transmitter units convert sensor inputs to isolated process current or voltage

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

C-Bus Four Channel Analogue Output Unit Installation Instructions

C-Bus Four Channel Analogue Output Unit Installation Instructions C-Bus Four Channel Analogue Output Unit Installation Instructions 5504AMP Series REGISTERED PATENT Table of Contents Section... Page 1.0 Product Range...3 2.0 Description...3 3.0 Capabilities...3 4.0 Wiring

More information

4 & 8-POINT ANNUNCIATORS Instruction Manual

4 & 8-POINT ANNUNCIATORS Instruction Manual 4 & 8-POINT ANNUNCIATORS Instruction Manual 8 Field Selectable Sequences All Common ISA Sequences 4 or 8-Point (Channel) Monitoring Free Replaceable Message Labels Type 4X, NEMA 4X, IP65 Front Universal

More information

Software Version 2.01 LEVEL MONITOR MODEL 220

Software Version 2.01 LEVEL MONITOR MODEL 220 Software Version 2.01 LEVEL MONITOR MODEL 220 19 April 2000 CONTENTS 1. Introduction 1 1.1 Model Number Designation 2 1.2 Intrinsic Safety Considerations 3 2. Specification 4 3. Operation 6 3.1 Display

More information

C-Bus Four Channel General Input Unit Installation Instructions

C-Bus Four Channel General Input Unit Installation Instructions C-Bus Four Channel General Input Unit Installation Instructions 5504GI Series REGISTERED DESIGN REGISTERED PATENT Table of Contents Section...Page 1.0 Product Range... 3 2.0 Description... 3 3.0 Capabilities...

More information

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 4/01 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1000 and UDC1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers

More information

Instruction Manual August sitrans CU 02

Instruction Manual August sitrans CU 02 Instruction Manual August 2005 sitrans CU 02 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment.

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Speed and Frequency Seite 1 von 7

Speed and Frequency Seite 1 von 7 Speed and Frequency Seite 1 von 7 E16 Systems for High Safety Speed ing, all with Triple Modular Redundancy. A choice of versions to meet various demands. Compliant with SIL3 / IEC 61508 and/or API 670.

More information

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual PD154 & PD158 VIGILANTE II ANNUNCIATORS 8 Field Selectable Sequences All Common ISA Sequences 4 or 8-Point (Channel) Monitoring Free Replaceable Message Labels Type 4X, NEMA 4X, IP65 Front Universal Power

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

UDC100 Universal Digital Controller Specifications

UDC100 Universal Digital Controller Specifications UDC100 Universal Digital Controller Specifications 51-52-03-29 November 1999 Overview The UDC100 Universal Digital Controller is a microprocessor-based 1/4 DIN low cost temperature controller. It combines

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

Nov 08 PRODUCT SPECIFICATION SHEET

Nov 08 PRODUCT SPECIFICATION SHEET Honeywell UDC1200 and UDC1700 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS 51-52-03-35 Nov 08 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1200 & UDC1700 are microprocessor-based 1/16 DIN and 1/8 DIN

More information

LC2200 Level Controller Installation and Maintenance Instructions

LC2200 Level Controller Installation and Maintenance Instructions 4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%

More information

Table of Contents. Protective Relays

Table of Contents. Protective Relays Table of Contents KILOVAC WD Series, DIN Rail or Screw Mounted Introduction..........................................................11-2 KILOVAC WD25 Paralleling Relays........................................11-3

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new

More information

Module Features are-configurable, no module jumpers to set

Module Features are-configurable, no module jumpers to set December 2011 PACSystems* RX3i Isolated Thermocouple Input Module, 6 Channels, IC695ALG306 Isolated Thermocouple Input Module, 12 Channels, IC695ALG312 Isolated Thermocouple Input module IC695ALG306 provides

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

Instruction Manual Model A

Instruction Manual Model A 706 Bostwick Avenue, Bridgeport, CT 06605 TEL: 203-368-6751 FAX: 203-368-3747 1-800-566-6822 www.devarinc.com Instruction Manual Model 18-232A LOOP POWERED ALARM MANUAL NO. 990029 MODEL 18-232A LOOP POWERED

More information

Instruction Manual December 2001 ENACOCU02

Instruction Manual December 2001 ENACOCU02 SENACOCU02 Instruction Manual December 2001 ENACOCU02 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected

More information

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL 95 Methodist Hill Drive Rochester, NY 14623 Phone: US +1.585.321.5800 Fax: US +1.585.321.5219 www.spectracomcorp.com Part Number 8143-5000-0050

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/

Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/ Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/08 Table Of Contents Section I Installation and Startup.................. 1 INSTALLATION............................................

More information

CU-02 with Senaco Plus

CU-02 with Senaco Plus CU-02 with Senaco Plus Instruction Manual PL-509 July 2001 U-02 SENACO 33455090 Rev. 1.1 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

Temperature Controllers

Temperature Controllers Model TEC-4100 1/4 DIN Model TEC-4100 1/4 DIN Temperature Controller Ordering Code: Power Input BOX 1 4 = 90-250 VAC 5 = 11-26 VAC / VDC TEC-4100- Configurable for 4 Programmable Outputs and NEMA 4X/IP65

More information

Greentrol Automation, Inc.

Greentrol Automation, Inc. Model GA-100 Technical Manual GreenAlert 100 Series Greentrol Automation, Inc. Installation, Operation and Maintenance Technical Manual GA-100 Document Name: TM_GA-100_R1C TM_GA-100_R1C Part Number: 960--0000

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

ESSEX ENGINEERING CORPORATION

ESSEX ENGINEERING CORPORATION WATER/WASTEWATER TREATMENT CONTROL SYSTEMS AND SUBSYSTEMS 2000 SERIES CONTROL SYSTEMS: 2000 series are for surface mounting inside a control cabinet Model 2024 Electronic Alternator Duplex (two pump) pump

More information

7EF/7HF/7EC/7ES Temperature Controllers

7EF/7HF/7EC/7ES Temperature Controllers 7EF/7HF/7E/7ES Temperature ontrollers Dual 4 Digit LED Display Universal Input (6 T/, RTD, mv, V, ma) Autotuning NEMA 4X 100 to 240 Vac Switching Power Supply Algorithms for Heat or Heat/ool ontrol 2 Independent

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009 STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009 Introduction Honeywell s STT 3000 family of microprocessor based transmitters covers the full

More information

vibration switch

vibration switch user manual 440-450 vibration switch INSTALLATION - OPERATION - MAINTENANCE Z0592822_A ISSUED 06/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. contents Section 1 -

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

TraceNet ECM Series Control System

TraceNet ECM Series Control System TraceNet ECM Series Control System ECM Operating Guide Thermon Manufacturing Company TraceNet is a registered trademark of Thermon Manufacturing Company. ECM Operating Guide 2014, 2015 Thermon Manufacturing

More information

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions Bulletin E-97DC Thank you for purchasing the Dwyer DCT1000DC Dust Collector Timer Controller. You

More information

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required. TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.

More information

Sierra Series 900 Single & Dual Channel System. Instruction Manual

Sierra Series 900 Single & Dual Channel System. Instruction Manual Series 240/24 Instruction Manual Table of Contents Sierra Series 900 Single & Dual Channel System Instruction Manual Part Number IM-90-07/05 Revision D. 5 Harris Court, Building L Monterey, CA 93940 (83)

More information

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information: RDM LOCK G-1 1400 Series Electromagnetic Lock The patented 1400 Series Electromagnetic Lock is universal for all types of applications, including outdoor use. The innovative design will reduce installation

More information

LC3000 Level Controller Installation and Maintenance Instructions

LC3000 Level Controller Installation and Maintenance Instructions 4025550/12 IM-P402-36 AB Issue 12 LC3000 Level Controller Installation and Maintenance Instructions 1. General safety information LC3000 NORM ALARM TEST 2. General product information 3. Installation 4.

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011 October 2011 PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412 The PACSystems * Thermocouple Input module IC695ALG412 provides twelve isolated differential thermocouple input channels.

More information

Mark 25 Ultrapure Water Conductivity Analyzer

Mark 25 Ultrapure Water Conductivity Analyzer Martek Instruments, Inc. Mark 25 Ultrapure Water Conductivity Analyzer Instruction Manual WARRANTY POLICY Unless otherwise stated, MARTEK INSTRUMENTS, INC. warrants this equipment to be free from defects

More information

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed)

Programmable Output Dual Relay Quad Relay. (Trip Points, High Alarm, Low Alarm, Failsafe, Non-Failsafe, Normally Open, Normally Closed) June 2004 Description The universal SPA 2 Programmable Limit Alarm Trips provide on/off control, warn of unwanted process conditions, alarm on rate-of-change and provide emergency shutdown. Very versatile,

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

Datasheet: K-22 LO Sensor

Datasheet: K-22 LO Sensor Datasheet: K-22 LO Sensor The K- 22 LO is a CO2 sensor module designed to be built- in into stationary ventilation equipment, such as window vent or duct exhaust actuators, serving as a linear transmitter

More information

Analog Input Module IC670ALG630

Analog Input Module IC670ALG630 1 IC670ALG630 The Thermocouple (IC670ALG630) accepts 8 independent thermocouple or millivolt inputs. Module features include: Self calibration Two data acquisition rates based on 50 Hz and 60 Hz line frequencies

More information

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system INSTRUCTION MANUAL 1MN0110 REV. 0 operates with ISO9001 certified quality system TECSYSTEM S.r.l. 20094 Corsico (MI) Tel.: +39-024581861 Fax: +39-0248600783 http://www.tecsystem.it R. 1.1 25/08/16 ENGLISH

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Operating Instructions. For. Alarm Control Module. Model SSR 500

Operating Instructions. For. Alarm Control Module. Model SSR 500 SSR 500 LEVEL CONTROL RELAY MODULE Operating Instructions For Alarm Control Module Model SSR 500 SSR Operation Instructions Rev. 1 Jan 01 Page 1/7 1. Note Please read and take note of these operating instructions

More information

AO Annunciator Module

AO Annunciator Module General Specifications GS48C43Z01-00E-N AO-543-01 Annunciator Module GENERAL Figure 1 This module has two independent annunciator circuits. The circuits handle fault signals and operator actions (acknowledge,

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description DPB52 True RMS 3-Phase, Multifunction monitoring relay Description Benefits Measuring Voltage Range. Very wide input voltage range: from 125 to 624V ( 208V 40% to 480 + 30% ). Adjustable Voltage Ranges

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

Engineering Guideline. pac- Carriers Type Universal

Engineering Guideline. pac- Carriers Type Universal Engineering Guideline pac- Carriers Type 9195 Universal Integration of conventional process automation interfaces pac- Carrier The pac- Carrier reflects the intention of R. STAHL to provide state-of-the-art

More information

DGC-500 DIGITAL GENSET CONTROLLER

DGC-500 DIGITAL GENSET CONTROLLER DGC-500 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-500) offers a low cost microprocessor based integrated alternative for the control and monitoring of small to medium sized

More information

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE DSGH Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE Revision History Revision History Version of manual Description Date 1.0 Initial release 051025 1.1

More information

LORAIN CIP 4890/48120 DC Power System

LORAIN CIP 4890/48120 DC Power System DC Power for Business-Critical Continuity Key Features Compact flexibility provides rectifiers, distribution, and controller in one shelf Constant power delivers more current at lower voltages to meet

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

EOTec 2C32 Installation Guide

EOTec 2C32 Installation Guide ControlNet Dual Ring Modules For the EOTec 2000 Series November 2008 Weed Instrument Company, Inc. 707 Jeffrey Way, P.O. Box 300 Round Rock, TX 78680-0300 USA Tel: 512-434-2850 Fax: 512-434-2851 E-mail:

More information

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing applications which range from freeze protecting water lines to

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER MODEL AL3 7 5 - AL3000 series conforming to CE, UL and CSA are 100mm multi-point type hybrid recorders with a simultaneous display of multi-channel

More information

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

DEB71. Earth Leakage Monitoring Relay. Benefits. Description Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

DIGITAL METERS Large Display Temperature Meters Instruction Manual

DIGITAL METERS Large Display Temperature Meters Instruction Manual DIGITAL METERS Large Display Temperature Meters PD755 PD756 PD757 Handles Thermocouple & RTD Inputs with Simplicity J, K, T, E, R, & S Thermocouples 100 Ω Platinum RTD (0.00385 or 0.00392 curve) Large

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

Frequently asked questions: Intelligent Transmitter Series

Frequently asked questions: Intelligent Transmitter Series Frequently asked questions: Intelligent Transmitter Series The Wilcoxon family of Intelligent Transmitters, relay alarms, and communication modules can be used to implement low-cost online vibration monitoring

More information

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1 VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1. INTRODUCTION This manual contains information for the installation and operation and tuning of our Vertex VT10 series self-tuning

More information

Process Alarm Module RTA 421

Process Alarm Module RTA 421 Technical Information TI 074R/24/ae Process Alarm Module RTA 421 Alarm module and power supply for monitoring current or voltage signals Application Areas Plant and machine construction Panel builders

More information

CT398 Heaterstat TM Temperature Controller. Technical User Guide

CT398 Heaterstat TM Temperature Controller. Technical User Guide CT398 Heaterstat TM Temperature Controller Technical User Guide CT398 HeaterStat Controller Contents CT398 HeaterStat Controller... 2 Contents... 2 Document Overview... 2 For More Information... 2 Introduction...

More information

Audible warning devices for external alarm

Audible warning devices for external alarm VdS SCHADENVERHÜTUNG VdS Publisher: Gesamtverband der Deutschen Versicherungswirtschaft e.v. (GDV) Büro Schadenverhütung Publishing house: VdS Schadenverhütung Rules for Intruder Alarm Systems Audible

More information

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd. F-2000 PC and AO OUTPUT BOARDS INSTRUCTION MANUAL Blue-White R Industries, Ltd. 500 Business Drive Huntington Beach, CA 92649 USA Phone: 714-89-8529 FAX: 714-894-9492 E mail: sales@blue-white.com or techsupport@blue-white.com

More information

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description Three phase AC pumps and ventilators soft starter Description Benefits Easy to use. The is equipped with a self-learning algorithm that automatically adjusts the start parameters to optimise the motor

More information

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS

Engineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS Engineering Guideline pac-carriers Type 9195 for Yokogawa ProSafe-RS 2 Engineering Guideline / Yokogawa ProSafe-RS 06.06.2017 Integrated solutions for Yokogawa R. STAHL offers a wide range of customized

More information

Fisher LCP100 Local Control Panel

Fisher LCP100 Local Control Panel Instruction Manual LCP100 Local Control Panel Fisher LCP100 Local Control Panel Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications... 2 Installation... 3 Hazardous Area Classifications

More information

DGC-1000 DIGITAL GENSET CONTROLLER

DGC-1000 DIGITAL GENSET CONTROLLER DGC-1000 DIGITAL GENSET CONTROLLER Basler Electric s Digital Genset Controller (DGC-1000) offers a low cost microprocessor based integrated alternative for small to medium sized genset control and monitoring.

More information

LC1350 Level Controller

LC1350 Level Controller LC1350 Controller Description The Spirax Sarco LC1350 has two alarm channels that can be independently configured high or low to control the water level of a boiler, tank or vessel by operating a pump,

More information

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl enproteko.com Temperature Monitoring Relay K8AB-TH Compact and Slim Relay Ideal for Temperature Alarms and Monitoring Excessive increases can be prevented and abnormal s can be monitored. Temperature monitoring

More information

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1- DPR-45 User Manual V-2.0 (2..206) DPR-45 TEMPERATURE PROTECTION RELAY PT00 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT 9-50VDC SUPPLY DESCRIPTION DPR-45 is a precision unit designed for the temperature

More information

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

GG-EM ENTRANCE MONITOR. Installation and Operation Manual GG-EM ENTRANCE MONITOR Installation and Operation Manual 2 GG-EM Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified by Calibration

More information

APC BC300 Series 40kW 208/450/480V User Guide

APC BC300 Series 40kW 208/450/480V User Guide APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank

More information

E340 BOILER CONTROL INSTALLATION MANUAL

E340 BOILER CONTROL INSTALLATION MANUAL E-3451 JUNE 1999 E340 BOILER CONTROL INSTALLATION MANUAL DESCRIPTION The E340 Boiler Room Control is a microprocessor-based Boiler Management System designed to interface with existing Fireye D Series

More information

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing applications which range from freeze protecting water lines to

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control Document Number 13I00-5 November, 1997 CONTENTS

More information