A77 SNMPv1 SCADA INTERFACE OPTION 21X INSTRUCTIONS This manual is only valid for A77 Chargers equipped with the following: S2A-368S card with software version P368S0111 080116 MIB file P389S-21X4-00 S2A-389S card with software version P389S-21X4-00 CPN134727 ECN/DATE ISSUE DATE: ECN 20985-3 -8/16 Page 1 of 6 106 BRADROCK DRIVE DES PLAINES, IL. 60018-1967 (847) 299-1188 FAX: (847) 299-3061 INSTRUCTION DRAWING NUMBER: P25-LOPT21X-A77-368S-2
IP Address: 192.168.0.6 Subnet: 255.25.255.0 Gateway: 192.168.0.1 Traps: Disabled Trap Receiver IP: 0.0.0.0 Default Settings Web Interface All settings are available through a web interface that may be accessed at; http://192.168.0.6 Default Username: admin Default Password: lamarche MIB File The La Marche MIB file for your charger can be downloaded from: http://web.lamarchemfg.com/userfiles/instruction-manuals/p389s-21x4-00.mib.txt Security LaMarche recognizes that not all customers desire to have the ability to remotely change settings. This feature is located in the Settings Menu. Within the Advanced Settings Menu is the Communications Menu. Under the Communications Menu is the Remote Disable selection. The only way to enable/disable this feature is through the front panel of the charger. When Remote Disable is set to YES the communications operate in read only mode. Please note that remote setting changes are always disabled whenever the settings menu is entered. Monitored Data Object ID Description Scale Factor Read/ Write Sends Trap COMMS_STATUS Charger Comms Alarm Status. Failure indicates a communications problem between the charger control board and SNMP Agent Board. Data read back is invalid. (FAIL=1) AC_ALARM_STATUS AC Fail Alarm Status. (FAIL=1) LOW_AC_ALARM_STATUS Low AC Alarm Status. (FAIL=1) LV_ALARM_STATUS Low Voltage Alarm Status. (FAIL=1) HV_ALARM_STATUS High Voltage Alarm Status. (FAIL=1) HVSD_ALARM_STATUS High Voltage Shutdown Alarm Status. (FAIL=1) LC_ALARM_STATUS Low Current Alarm Status. (FAIL=1) GD_ENABLED_STATUS Ground Detection Enabled. (ENABLED=1) PG_ALARM_STATUS Positive Ground Alarm Status. (FAIL=1) NG_ALARM_STATUS Negative Ground Alarm Status. FAIL=1) SUM_ALARM_STATUS Summary Alarm Status. (FAIL=1) EOD_ALARM_STATUS End of Discharge Alarm Status. (FAIL=1) Page 2 of 6
OL_ALARM_STATUS Overload Current Alarm Status. (FAIL=1) CF_ALARM_STATUS Charger Failure Alarm Status. (FAIL=1) OT_ALARM_STATUS Over Temperature Alarm Status. (FAIL=1) SCR_ALARM_STATUS SCR Failure Alarm Status. (FAIL=1) OT_PROBE_STATUS Over Temperature Probe Status. (FAIL=1) TC_PROBE_STATUS Temperature Compensation Probe Status. (FAIL=1) OPTIONAL_417S_GND_ENA Charger is equipped with optional 417s Ground None R No BLED Detection Option. (YES=1) OPTIONAL_417S_GND_DET Optional 417S Ground Detection Board has _FAILURE failed. (FAIL=1) OPTIONAL_411S_BOARD Charger is equipped with optional 411s ACV/ACA None R No Measurement Option. (YES=1) OPTIONAL_411S_FAILED Optional 411S ACV/ACA Measurement Board has failed. (FAIL=1) REMOTE_CHANGE_PROHIB IT When read as 1 remote changes are not allowed. This can occur because the charger is set this way or when a local operator is changing settings. THREE_PHASE_CHARGER Phase of charger. (1 PHASE=0, 3 PHASE=1) None R No BOT_ALARM_STATUS Battery Over Temperature Alarm Status. (FAIL=1) ACBO_ALARM_STATUS Open AC Breaker Alarm Status. (FAIL=1) DCBO_ALARM_STATUS Open DC Breaker Alarm Status. (FAIL=1) LE_ALARM_STATUS Low Electrolyte Alarm Status. (FAIL=1) LVBD_OPTION_ENABLE When read as 1 the charger is equipped with the None R No Low Voltage Battery Disconnect (LVBD) option. LVBD_ALARM_STATUS Low Voltage Battery Disconnect Alarm Status. (FAIL=1) CHARGER_MODE Charger Mode. (FLOAT=0, EQUALIZE=1) None RW Yes AC_IN_SUMMARY AC Alarm in Summary. (YES=1) LC_IN_SUMMARY Low Current Alarm in Summary. (YES=1) OL_IN_SUMMARY Overload Alarm in Summary. (YES=1) GD_IN_SUMMARY Ground Detection Alarms in Summary. (YES=1) LATCH_ALARMS Latch Alarms. (YES=1) LATCH_EOD_ALARM Latch End of Discharge Alarm. (YES=1) LCD_BL_MODE LCD Backlight Automatically turns off after 2 minutes of inactivity. (YES=1) EVENT_LOG_ENABLE Event Logging Enable. (YES=1) BOT_IN_SUMMARY Battery Over Temperature Alarm in Summary. (YES=1) ACBO_IN_SUMMARY Open AC Breaker Alarm in Summary. (YES=1) DCBO_IN_SUMMARY Open DC Breaker Alarm in Summary. (YES=1) BOT_ALARM_DISABLE Battery Over Temperature Alarm Disabled. (DISABLED=1) ACBO_ALARM_DISABLE Open AC Breaker Alarm Disabled. (DISABLED=1) DCBO_ALARM_DISABLE Open DC Breaker Alarm Disabled. (DISABLED=1) H1PCT_IN_SUMMARY Hydrogen Gas at 1 Percent Alarm in Summary. (YES=1) LE_ALARM_DISABLE Low Electrolyte Level Alarm Disabled. (DISABLED=1) LVBD_IN_SUMMARY Low Voltage Battery Disconnect Alarm in Summary. (YES=1) Page 3 of 6
LVBD_ALARM_DISABLE Low Voltage Battery Disconnect Alarm disable. (DISABLED=1) BOARD_NUMBER Control Board Number. (368=368S) None R No SOFTWARE_VERSION Software Version. None R No DCV DC Voltage. Volts. 0.1 R No DCA DC Current. Volts. 0.1 R No EQ_TIMER_HHMM Equalize Cycle Time Remaining, HHMM. Note the None R No first two digits are the hours. The last two digits are the minutes. AUTOEQ_TIMER_DAYS Days to next Auto Equalize. Days. None R No AUTOEQ_TIMER_HHMM Hours, Minutes to next Auto Equalize. Note the None R No first two digits are the hours. The last two digits are the minutes. LC_ALARM_LOW_LIMIT Low DC Current Alarm Low Limit. Note setting 0.1 R No the Low DC Current Alarm below this will result in disabling the Low DC Current Alarm. Amps. OT_PROBE_C Over Temperature Probe Reading. Check None R No OT_PROBE_STATUS to determine if reading is valid. Degrees C. TC_PROBE_C Temperature Compensation Probe Reading. None R No Check TC_PROBE_STATUS to determine if reading is valid. Degrees C. OT_ALARM_C Over Temperature Alarm Threshold. Degrees C. None R No MAX_ALARM_VOLTS The maximum value voltage alarms may be set 0.1 R No to. Volts. MAX_ALARM_AMPS The maximum value current alarms may be set 0.1 R No to. Volts. MAX_FL_VOLTS The maximum allowable Float Voltage. Volts. 0.1 R No MIN_FL_VOLTS The minimum allowable Float Voltage. Volts. 0.1 R No MAX_EQ_VOLTS The maximum allowable Equalize Voltage. Volts. 0.1 R No MIN_EQ_VOLTS The minimum allowable Equalize Voltage. Volts. 0.1 R No MAX_CL_AMPS The maximum allowable Current Limit. Amps. 0.1 R No MIN_CL_AMPS The minimum allowable Current Limit. Amps. 0.1 R No LOG_PCT_USED The percent of the event log file used. 0.01 R No MAX_TEMP_COMP_RATE Maximum Temperature Compensation Rate. 0.001 R No Volts/Cell/C. ACV AC Voltage. Volts. 0.1 R No AC_FREQ AC Frequency. Hz. 0.1 R No BATTERY_TYPE Battery Type. None R No Lead Acid = 0 NiCad = 1 BATTERY_CELLS Battery Cells. None R No ACVP1 AC Phase 1 Voltage. Will read 0 on 1 Phase 0.1 R No ACVP2 AC Phase 2 Voltage. Will read 0 on 1 Phase 0.1 R No ACVP3 AC Phase 3 Voltage. Will read 0 on 1 Phase 0.1 R No Page 4 of 6
ACAP1 AC Phase 1 Amps. Will read 0 on 1 Phase 0.1 R No ACAP2 AC Phase 2 Amps. Will read 0 on 1 Phase 0.1 R No ACAP3 AC Phase 3 Amps. Will read 0 on 1 Phase 0.1 R No POS_GND_MA Milliamps between Positive and Ground. 0.1 R No determine if value NEG_GND_MA Milliamps between Negative and Ground. 0.1 R No determine if value GND_NEG_VOLTS Voltage between Ground and Negative. Volts. 0.1 R No determine if value POS_GND_VOLTS Voltage between Positive and Ground. Volts. 0.1 R No determine if value OT_ALARM_TYPE Over Temperature Alarm Type. OK=0, FAIL=1, DERATE=2, SHUTDOWN=3 H2GAS_READING Hydrogen Gas Sensor Reading. 0 Percent=0, 1 Percent=1, 2 Percent=2, Sensor Failure=3, Option Not Available=4 EQT_MODE Equalize Timer Mode. Valid Range: 0 to 4. EQT_HOURS Equalize Timer Setting. Hours. Valid Range: 0 to 144. LV_ALARM_VOLTS Low Voltage Alarm Threshold. Volts. Valid 0.1 RW No Range: 0 to MAX_ALARM_VOLTS HV_ALARM_VOLTS High Voltage Alarm Threshold. Volts. Valid 0.1 RW No Range: 0 to MAX_ALARM_VOLTS HVSD_ALARM_VOLTS High Voltage Shutdown Alarm Threshold. Volts. 0.1 RW No Valid Range: 0 to MAX_ALARM_VOLTS LC_ALARM_AMPS Low DC Current Alarm Threshold. Amps. Valid Range: 0 to MAX_ALARM_AMPS 0.1 RW No Page 5 of 6
EOD_ALARM_VOLTS End of Discharge Alarm Threshold. Volts. Valid 0.1 RW No Range: 0 to MAX_ALARM_VOLTS FL_VOLTS Float Voltage Setting. Volts. Valid Range: 0.1 RW No MIN_FLOAT_VOLTS to MAX_FLOAT_VOLTS EQ_VOLTS Equalize Voltage Setting. Volts. 0.1 RW No Valid Range: MIN_EQ_VOLTS to MAX_EQ_VOLTS CL_AMPS Current Limit Setting. Amps. Valid Range: 0.1 RW No MIN_CL_AMPS to MAX_CL_AMPS TEMP_COMP_RATE The rate of temperature compensation in use. 0.001 RW No Note: 0=Temperature Compensation OFF Valid Range (Lead Acid): 0,1,2,3,4,5 Valid Range (NiCad): 0,1,2,3 LOG_INTERVAL Logging Interval. Minutes. Valid Range: 1 to 60 AC_ALARM_DELAY AC Alarm Delay. Seconds. Valid Range: 1 to 255 LV_ALARM_DELAY Low Voltage Alarm Delay. Seconds. Valid Range: 1 to 255 EOD_ALARM_DELAY End of Discharge Alarm Delay. Seconds. Valid Range: 1 to 255 EQTM4_ALARM_DELAY Equalize Timer Mode 4 Delay. Seconds. Valid Range: 1 to 255 HV_ALARM_DELAY High Voltage Alarm Delay. Seconds. Valid Range: 1 to 255 HVSD_ALARM_DELAY High Voltage Shutdown Alarm Delay. Seconds. Valid Range: 1 to 255 LC_ALARM_DELAY Low Current Alarm Delay. Seconds. Valid Range: 1 to 255 LV_ALARM_RESET Low Voltage Alarm Reset Threshold. Percent. Valid Range: 0 to 20 EOD_ALARM_RESET End of Discharge Alarm Reset Threshold. Volts. Valid Range: 0 to MAX_ALARM_VOLTS RTC_MONTH Real Time Clock (RTC) Month. Valid Range: 1 to 12 RTC_DAY Real Time Clock (RTC) Day of Month. Valid Range: 1 to 31 RTC_YEAR Real Time Clock (RTC) Year. Valid Range: 2000 to 2200 RTC_HOUR Real Time Clock (RTC) Hours. Valid Range: 0 to 23 RTC_MIN Real Time Clock (RTC) Minutes. Valid Range: 0 to 59 RTC_SEC Real Time Clock (RTC) Seconds. Valid Range: 0 to 59 GD_ALARM_DELAY Ground Detection Alarm Delay. Seconds. Valid Range: 0 to 255 GND_DET_MILLIAMPS Ground Detection Alarm Threshold. 0.1 RW No if option is available. BOT_ALARM_C Battery Over Temperature Alarm. Degrees C. Valid Range: 25 to 100 Page 6 of 6