A77 SNMPv1 SCADA INTERFACE INSTRUCTIONS

Similar documents
A77 SNMPv3 SCADA INTERFACE INSTRUCTIONS

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

A77 Series. Microprocessor Controlled SCR Filtered/Battery Eliminator Filtered Charger. Installation and Operation Manual

La Marche Manufacturing Company A36D. Battery Charger / Power Supply. Installation and Operation Manual

BMS MU Internet Ready 24 Volt Battery Management System With Built-in Remote Monitoring and Control. Owners Guide

BMS MU Internet Ready Battery Management System Owners Guide

Contact Product Manager, with details of the application.

TPSD. Installation and Operation Manual. Filtered Battery Charger Power Supply / Battery Eliminator

Alarm module for leak detection with webserver

FPRA IP20 Flexi Power Rectifier

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

Batt-Safe Battery String Monitoring System

RLP-2048BBSCLVD-MU Internet Ready Heavy Duty AC to DC Power Supply With Built-in Remote Monitoring and Control. Owners Guide

LMHF. Software Manual

Added password for IP setup page : Password must be in IP format!

User Guide UTI-IQCP. Control panel for setting and monitoring of UTI-INV internal temperature regulator. v EN

BROADBAND MODEL WITH REMOTE POWER CONTROL (SERIES 2) ICT180S-12BRC (FOR POSITIVE GROUND SYSTEMS) ICT180S-12BRCP (FOR NEGATIVE GROUND SYSTEMS)

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

DIESEL Engine Fire Pump Controllers Features

READ AND SAVE THESE INSTRUCTIONS

NetSure. ACU+ Controller (Advanced Control Unit Plus) User Manual (UM1M820BNA), Revision R

Millennium Xtra. Millennium ATMA setup and configuration guide. May Millennium Group, Inc.

IndigoVision Alarm Panel. User Guide

RAy SNMP. Application notes.

FCD-wire Contents. List of Figures

NetSure SCU+ Controller (Standard Control Unit Plus)

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax:

OPERATING MANUAL. PCC Controller. (PCC-01 and G) [PCC-01 shown]

THX-DL Data Logger USER & INSTALLATION MANUAL V

Multiple Battery Cabinets Dual-Lite TRN. External Maintenance Switch Configuration Options. External Maintenance Switch Options

P4200W2 Series Air Dryer

Innovative Circuit Technology Ltd.

MAIN MENU/HOME SCREEN OVERVIEW

ICT180S-12I INTELLIGENT MODEL (SERIES 2)

Model 135 Reference Document

entri Series HE1U-XX12-BMS-MU Series

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Innovative Circuit Technology Ltd.

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

P550W Series Air Dryers

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7

OPERATING INSTRUCTIONS. G214 Software - Version 4

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

DC-RMCU1 DC-Powered Remote Monitoring and Control Unit Owners Guide

RESET + Password Enter (During Auto Speed Procedure) Maintenance Timeout or after TEST + RESET + DISABLE (No Need for Device to Initialize)

Control/Communicator Installation Manual

Galaxy Pulsar Plus Controller Family Troubleshooting Table with SMNP Traps

QS941A Controller User Interface

LineGuard 2300 Program User Manual (FloBoss 107)

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

CMC-TC Basic CMC DK

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

HGM1750 Automatic Generator Module OPERATING MANUAL Smartgen Electronics

TM3 monitoring unit. installation and users manual

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

3D_ISS. Integrated Software System. User Guide Manual

PowerRouter application guideline

INSTALLATION & OPERATING MANUAL

Using the QRAE Plus personal multigas monitor

Products no longer available

Room Alert. Room Alert 32E, 12E, 4E & 3E. Temperature & Environment Monitoring... Made Easy! User s Guide & Reference Manual

TV2 Room Pressure Monitor Quick Start Guide

RF SCOUT PLUS INSTRUCTION MANUAL. Dielectric, LLC 22 Tower Rd. Raymond, ME Phone: January 2015, Rev B 1

LORAIN CIP 4890/48120 DC Power System

Service Manual Models: 1.0, 1.3, and 1.5

IT801 Thermostat. User s Manual. The complete guide to the set up and operation of your new smart Wi-Fi thermostat.

Spectron LSN (Life Safety Network) Suggested Specifications

Addendum. HART Communication with the FlexSonic Acoustic Detector. 1.1 Rev: 1/

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

How to use the BTRM in Remote Enclosures

PowerLogic ION Setup Meter Configuration Software Configuration Guide

Peak Partners Web-Programmable Thermostat Homeowner s Manual. Look inside for a complete guide to the setup and operation of your new thermostat.

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL

TS5160. Installation & User Guide. Compatible Equipment. CPA6 0M - Output Module Loudspeaker DC54/58 - Digital Communicators (Stand Alone Only)

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17

Carbon Monoxide Transmitter

Instruction Manual Environmental Monitoring Unit with Output Relay

PERMACONN PM1030 Includes DI300. Installation Manual

Item Number Description Price. Accessories " Diesel/Water/Waste tank sender $ Battery temperature sensor $2.22

ENGINE MONITOR VOTT MODEL: YEAR WARRANTY

Room Alert. Room Alert 32E/W, 12E, 4E & 3E. Temperature & Environment Monitoring... Made Easy! User s Guide & Reference Manual

INSTALLATION INSTRUCTIONS

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

RADview-EMS/TDM. Element Management System for TDM Applications Optimux RAD Data Communications Publication 07/04

EL-USB-1-LCD Temperature Data Logger with LCD

Networked Access Control Panel. Installation Guide

INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3. M336 Rev F. November 21, 2000.

Avigilon Control Center 5 System Integration Guide

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

Instruction Manual. Satellite Switched, Power Monitoring Unit. RS2 Series

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DGC-1000 DIGITAL GENSET CONTROLLER

Browser Manual ProMinent ProMtrac Cooling Tower Water Treatment Controller

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Transcription:

A77 SNMPv1 SCADA INTERFACE OPTION 21X INSTRUCTIONS This manual is only valid for A77 Chargers equipped with the following: S2A-368S card with software version P368S0111 080116 MIB file P389S-21X4-00 S2A-389S card with software version P389S-21X4-00 CPN134727 ECN/DATE ISSUE DATE: ECN 20985-3 -8/16 Page 1 of 6 106 BRADROCK DRIVE DES PLAINES, IL. 60018-1967 (847) 299-1188 FAX: (847) 299-3061 INSTRUCTION DRAWING NUMBER: P25-LOPT21X-A77-368S-2

IP Address: 192.168.0.6 Subnet: 255.25.255.0 Gateway: 192.168.0.1 Traps: Disabled Trap Receiver IP: 0.0.0.0 Default Settings Web Interface All settings are available through a web interface that may be accessed at; http://192.168.0.6 Default Username: admin Default Password: lamarche MIB File The La Marche MIB file for your charger can be downloaded from: http://web.lamarchemfg.com/userfiles/instruction-manuals/p389s-21x4-00.mib.txt Security LaMarche recognizes that not all customers desire to have the ability to remotely change settings. This feature is located in the Settings Menu. Within the Advanced Settings Menu is the Communications Menu. Under the Communications Menu is the Remote Disable selection. The only way to enable/disable this feature is through the front panel of the charger. When Remote Disable is set to YES the communications operate in read only mode. Please note that remote setting changes are always disabled whenever the settings menu is entered. Monitored Data Object ID Description Scale Factor Read/ Write Sends Trap COMMS_STATUS Charger Comms Alarm Status. Failure indicates a communications problem between the charger control board and SNMP Agent Board. Data read back is invalid. (FAIL=1) AC_ALARM_STATUS AC Fail Alarm Status. (FAIL=1) LOW_AC_ALARM_STATUS Low AC Alarm Status. (FAIL=1) LV_ALARM_STATUS Low Voltage Alarm Status. (FAIL=1) HV_ALARM_STATUS High Voltage Alarm Status. (FAIL=1) HVSD_ALARM_STATUS High Voltage Shutdown Alarm Status. (FAIL=1) LC_ALARM_STATUS Low Current Alarm Status. (FAIL=1) GD_ENABLED_STATUS Ground Detection Enabled. (ENABLED=1) PG_ALARM_STATUS Positive Ground Alarm Status. (FAIL=1) NG_ALARM_STATUS Negative Ground Alarm Status. FAIL=1) SUM_ALARM_STATUS Summary Alarm Status. (FAIL=1) EOD_ALARM_STATUS End of Discharge Alarm Status. (FAIL=1) Page 2 of 6

OL_ALARM_STATUS Overload Current Alarm Status. (FAIL=1) CF_ALARM_STATUS Charger Failure Alarm Status. (FAIL=1) OT_ALARM_STATUS Over Temperature Alarm Status. (FAIL=1) SCR_ALARM_STATUS SCR Failure Alarm Status. (FAIL=1) OT_PROBE_STATUS Over Temperature Probe Status. (FAIL=1) TC_PROBE_STATUS Temperature Compensation Probe Status. (FAIL=1) OPTIONAL_417S_GND_ENA Charger is equipped with optional 417s Ground None R No BLED Detection Option. (YES=1) OPTIONAL_417S_GND_DET Optional 417S Ground Detection Board has _FAILURE failed. (FAIL=1) OPTIONAL_411S_BOARD Charger is equipped with optional 411s ACV/ACA None R No Measurement Option. (YES=1) OPTIONAL_411S_FAILED Optional 411S ACV/ACA Measurement Board has failed. (FAIL=1) REMOTE_CHANGE_PROHIB IT When read as 1 remote changes are not allowed. This can occur because the charger is set this way or when a local operator is changing settings. THREE_PHASE_CHARGER Phase of charger. (1 PHASE=0, 3 PHASE=1) None R No BOT_ALARM_STATUS Battery Over Temperature Alarm Status. (FAIL=1) ACBO_ALARM_STATUS Open AC Breaker Alarm Status. (FAIL=1) DCBO_ALARM_STATUS Open DC Breaker Alarm Status. (FAIL=1) LE_ALARM_STATUS Low Electrolyte Alarm Status. (FAIL=1) LVBD_OPTION_ENABLE When read as 1 the charger is equipped with the None R No Low Voltage Battery Disconnect (LVBD) option. LVBD_ALARM_STATUS Low Voltage Battery Disconnect Alarm Status. (FAIL=1) CHARGER_MODE Charger Mode. (FLOAT=0, EQUALIZE=1) None RW Yes AC_IN_SUMMARY AC Alarm in Summary. (YES=1) LC_IN_SUMMARY Low Current Alarm in Summary. (YES=1) OL_IN_SUMMARY Overload Alarm in Summary. (YES=1) GD_IN_SUMMARY Ground Detection Alarms in Summary. (YES=1) LATCH_ALARMS Latch Alarms. (YES=1) LATCH_EOD_ALARM Latch End of Discharge Alarm. (YES=1) LCD_BL_MODE LCD Backlight Automatically turns off after 2 minutes of inactivity. (YES=1) EVENT_LOG_ENABLE Event Logging Enable. (YES=1) BOT_IN_SUMMARY Battery Over Temperature Alarm in Summary. (YES=1) ACBO_IN_SUMMARY Open AC Breaker Alarm in Summary. (YES=1) DCBO_IN_SUMMARY Open DC Breaker Alarm in Summary. (YES=1) BOT_ALARM_DISABLE Battery Over Temperature Alarm Disabled. (DISABLED=1) ACBO_ALARM_DISABLE Open AC Breaker Alarm Disabled. (DISABLED=1) DCBO_ALARM_DISABLE Open DC Breaker Alarm Disabled. (DISABLED=1) H1PCT_IN_SUMMARY Hydrogen Gas at 1 Percent Alarm in Summary. (YES=1) LE_ALARM_DISABLE Low Electrolyte Level Alarm Disabled. (DISABLED=1) LVBD_IN_SUMMARY Low Voltage Battery Disconnect Alarm in Summary. (YES=1) Page 3 of 6

LVBD_ALARM_DISABLE Low Voltage Battery Disconnect Alarm disable. (DISABLED=1) BOARD_NUMBER Control Board Number. (368=368S) None R No SOFTWARE_VERSION Software Version. None R No DCV DC Voltage. Volts. 0.1 R No DCA DC Current. Volts. 0.1 R No EQ_TIMER_HHMM Equalize Cycle Time Remaining, HHMM. Note the None R No first two digits are the hours. The last two digits are the minutes. AUTOEQ_TIMER_DAYS Days to next Auto Equalize. Days. None R No AUTOEQ_TIMER_HHMM Hours, Minutes to next Auto Equalize. Note the None R No first two digits are the hours. The last two digits are the minutes. LC_ALARM_LOW_LIMIT Low DC Current Alarm Low Limit. Note setting 0.1 R No the Low DC Current Alarm below this will result in disabling the Low DC Current Alarm. Amps. OT_PROBE_C Over Temperature Probe Reading. Check None R No OT_PROBE_STATUS to determine if reading is valid. Degrees C. TC_PROBE_C Temperature Compensation Probe Reading. None R No Check TC_PROBE_STATUS to determine if reading is valid. Degrees C. OT_ALARM_C Over Temperature Alarm Threshold. Degrees C. None R No MAX_ALARM_VOLTS The maximum value voltage alarms may be set 0.1 R No to. Volts. MAX_ALARM_AMPS The maximum value current alarms may be set 0.1 R No to. Volts. MAX_FL_VOLTS The maximum allowable Float Voltage. Volts. 0.1 R No MIN_FL_VOLTS The minimum allowable Float Voltage. Volts. 0.1 R No MAX_EQ_VOLTS The maximum allowable Equalize Voltage. Volts. 0.1 R No MIN_EQ_VOLTS The minimum allowable Equalize Voltage. Volts. 0.1 R No MAX_CL_AMPS The maximum allowable Current Limit. Amps. 0.1 R No MIN_CL_AMPS The minimum allowable Current Limit. Amps. 0.1 R No LOG_PCT_USED The percent of the event log file used. 0.01 R No MAX_TEMP_COMP_RATE Maximum Temperature Compensation Rate. 0.001 R No Volts/Cell/C. ACV AC Voltage. Volts. 0.1 R No AC_FREQ AC Frequency. Hz. 0.1 R No BATTERY_TYPE Battery Type. None R No Lead Acid = 0 NiCad = 1 BATTERY_CELLS Battery Cells. None R No ACVP1 AC Phase 1 Voltage. Will read 0 on 1 Phase 0.1 R No ACVP2 AC Phase 2 Voltage. Will read 0 on 1 Phase 0.1 R No ACVP3 AC Phase 3 Voltage. Will read 0 on 1 Phase 0.1 R No Page 4 of 6

ACAP1 AC Phase 1 Amps. Will read 0 on 1 Phase 0.1 R No ACAP2 AC Phase 2 Amps. Will read 0 on 1 Phase 0.1 R No ACAP3 AC Phase 3 Amps. Will read 0 on 1 Phase 0.1 R No POS_GND_MA Milliamps between Positive and Ground. 0.1 R No determine if value NEG_GND_MA Milliamps between Negative and Ground. 0.1 R No determine if value GND_NEG_VOLTS Voltage between Ground and Negative. Volts. 0.1 R No determine if value POS_GND_VOLTS Voltage between Positive and Ground. Volts. 0.1 R No determine if value OT_ALARM_TYPE Over Temperature Alarm Type. OK=0, FAIL=1, DERATE=2, SHUTDOWN=3 H2GAS_READING Hydrogen Gas Sensor Reading. 0 Percent=0, 1 Percent=1, 2 Percent=2, Sensor Failure=3, Option Not Available=4 EQT_MODE Equalize Timer Mode. Valid Range: 0 to 4. EQT_HOURS Equalize Timer Setting. Hours. Valid Range: 0 to 144. LV_ALARM_VOLTS Low Voltage Alarm Threshold. Volts. Valid 0.1 RW No Range: 0 to MAX_ALARM_VOLTS HV_ALARM_VOLTS High Voltage Alarm Threshold. Volts. Valid 0.1 RW No Range: 0 to MAX_ALARM_VOLTS HVSD_ALARM_VOLTS High Voltage Shutdown Alarm Threshold. Volts. 0.1 RW No Valid Range: 0 to MAX_ALARM_VOLTS LC_ALARM_AMPS Low DC Current Alarm Threshold. Amps. Valid Range: 0 to MAX_ALARM_AMPS 0.1 RW No Page 5 of 6

EOD_ALARM_VOLTS End of Discharge Alarm Threshold. Volts. Valid 0.1 RW No Range: 0 to MAX_ALARM_VOLTS FL_VOLTS Float Voltage Setting. Volts. Valid Range: 0.1 RW No MIN_FLOAT_VOLTS to MAX_FLOAT_VOLTS EQ_VOLTS Equalize Voltage Setting. Volts. 0.1 RW No Valid Range: MIN_EQ_VOLTS to MAX_EQ_VOLTS CL_AMPS Current Limit Setting. Amps. Valid Range: 0.1 RW No MIN_CL_AMPS to MAX_CL_AMPS TEMP_COMP_RATE The rate of temperature compensation in use. 0.001 RW No Note: 0=Temperature Compensation OFF Valid Range (Lead Acid): 0,1,2,3,4,5 Valid Range (NiCad): 0,1,2,3 LOG_INTERVAL Logging Interval. Minutes. Valid Range: 1 to 60 AC_ALARM_DELAY AC Alarm Delay. Seconds. Valid Range: 1 to 255 LV_ALARM_DELAY Low Voltage Alarm Delay. Seconds. Valid Range: 1 to 255 EOD_ALARM_DELAY End of Discharge Alarm Delay. Seconds. Valid Range: 1 to 255 EQTM4_ALARM_DELAY Equalize Timer Mode 4 Delay. Seconds. Valid Range: 1 to 255 HV_ALARM_DELAY High Voltage Alarm Delay. Seconds. Valid Range: 1 to 255 HVSD_ALARM_DELAY High Voltage Shutdown Alarm Delay. Seconds. Valid Range: 1 to 255 LC_ALARM_DELAY Low Current Alarm Delay. Seconds. Valid Range: 1 to 255 LV_ALARM_RESET Low Voltage Alarm Reset Threshold. Percent. Valid Range: 0 to 20 EOD_ALARM_RESET End of Discharge Alarm Reset Threshold. Volts. Valid Range: 0 to MAX_ALARM_VOLTS RTC_MONTH Real Time Clock (RTC) Month. Valid Range: 1 to 12 RTC_DAY Real Time Clock (RTC) Day of Month. Valid Range: 1 to 31 RTC_YEAR Real Time Clock (RTC) Year. Valid Range: 2000 to 2200 RTC_HOUR Real Time Clock (RTC) Hours. Valid Range: 0 to 23 RTC_MIN Real Time Clock (RTC) Minutes. Valid Range: 0 to 59 RTC_SEC Real Time Clock (RTC) Seconds. Valid Range: 0 to 59 GD_ALARM_DELAY Ground Detection Alarm Delay. Seconds. Valid Range: 0 to 255 GND_DET_MILLIAMPS Ground Detection Alarm Threshold. 0.1 RW No if option is available. BOT_ALARM_C Battery Over Temperature Alarm. Degrees C. Valid Range: 25 to 100 Page 6 of 6