RTP Technical Bulletin

Size: px
Start display at page:

Download "RTP Technical Bulletin"

Transcription

1 RTP Technical Bulletin Category: RETROFITTING REGISTERED TECHNICIANS PROGRAM Volume 1 Bulletin 1 this information is presented to clarify some misconceptions that occur, in c h a r g i n g retrofitted systems. it does not contain s p e c i f i c recommendatio ns regarding component changes but gives guidelines for analysing s y s t e m s correctly to e n s u r e performance is maintained for all ambient conditions. a significant amount of retrofits are conducted with charge rates insufficient for high ambient conditions causing poor performance under high heat loads and can also lead to compressor failure. System Charging In Retrofit With the changeover to R134a most technicians have either attended formal training or have simply learnt by experience what is required in an average retrofit. The very early change almost everything except for the air conditioning switch mentality has largely been scaled down to a more realistic level. There are two key factors that have generated this scaling down of retrofit requirements: 1 Overstated initial guidelines 2 Price driven market/industry forces. The early recommendations were in many cases overstated due to a shorter than ideal time for testing. With the recognition of the depletion of the ozone layer, and the severity of the depletion, alternative refrigerants were introduced into the industry without a suitable trial/test period for accurately identifying the absolute requirements of a retrofit. This scenario was unavoidable in the interest of ozone protection but it did leave the manufacturers of systems and components in an awkward situation where they had no choice but to overstate the requirements of retrofit in order to protect their systems and components. An example of this is: given the 20% higher flow rate of R134a how did they know that under certain operating conditions there would not be a liquid flood back to the compressor if the existing R12 valve was left in circuit? The answer was to recommend a TX Valve replacement (R134a type) to ensure a perfect matching to the system which would give absolute protection against liquid flood back. Only after substantial field testing have we determined that in most cases the existing TX will shut down to compensate for the excessive flow rate, but if the system is identified as one that will/may be prone to liquid migration then TX replacement is still recommended. The key point from the manufacturers perspective is not that the system or component will get out of warranty but rather that it must maintain its original life expectancy. If the life expectancy of components, particularly compressors, is noticeably shortened then the supplier of that componentry will, in the long term, become non competitive. 1

2 Given this there was no option but to be overprotective until suitable field testing and reliability trials were completed. The second key point is that we are operating in a price competitive market. What has therefore happened is that the price driven market forces are controlling the service and repair sector to a point where in many cases the level of service and repair (ie the procedures and replacement of components in retrofit) is principally a dollar driven decision. This is in fact a key point in charge determination of any system. Ideally any retrofitted system that has not been fitted with alternative componentry (ie parallel flow condensers, smaller receiver driers, alternative hose runs etc) should accept 90% of original R12 weight (see next). In reality if the componentry does not have the capability to happily accept R134a (particularly the condenser) then we are in an area of compromise. An area where we are charging a system within the limitations of that system. This is where the sub 90% charging rules originate. Many VASA technicians will have heard of 60, 70 and 80% charge ratios, and possibly practice these charging procedures. In some systems and operating environments this is fine - in others it is highly undesirable. This article will address the issues to consider when practicing sub 90% charging. In a price driven market many retrofits are conducted with componentry that is inadequate and the charge rate tailored accordingly. The 90% Charge Rule When a system is charged with refrigerant we have characteristically used the weight charging method. This has led us to the belief that it is the weight of refrigerant that enters the system that is important. In fact it is the LIQUID VOLUME that is the critical factor. When comparing R134a and R12 there is approximately a 10% weight differential to liquid volume (density differential). In simple terms 1kg of R134a will occupy a 10% larger volume than did 1kg of R12. Now ask yourself the question - where is the 10% extra liquid going to fit in the system? The answer is nowhere - you will be in the overcharge band with excessive head pressures. liquid flood back etc a distinct possibility. The answer is to reduce the WEIGHT charge by 10%. This will ensure the liquid volume in the system is equal to what is was designed for. The system should operate correctly if component compatibility is acceptable. If however problems start to arise before the 90% charge ratio is achieved then there is either a limitation in a component design/size with respect to its ability to handle R134a or there is a component malfunction which is limiting its ability. These limitations are usually related to condensing capability. Low charge rates are undesirable in retrofit for 4 reasons 1 Inadequate performance under high heat loads, 2 Excessive superheat ing under high heat loads, 3 Reduced oil circulation, 4 No safety margin when minor leakage occurs. 2

3 R134a - Sight Glass Charging It is imperative the technician identify the cause of a foaming sight glass. It must be proved it is not an undercharge or lack of condensing in retrofitted systems. Lack of performance under high heat loads will result from both conditions. Most technicians by now realise the limitations of sight glass observation of R134a systems. It must be identified however that the sight glass (if fitted) may still, in many systems, by an indicator of charge rates. It is just that it cannot be used as an absolute indicator - because in many cases it will bubble or even foam severely. Our role is to identify charge rates by all of the indicators that the system under test shows. WHY DOES THE SIGHT GLASS FOAM/BUBBLE ON R134a WHERE IT DIDN T ON R12? Basically there are 4 reasons for a bubbling/foaming sight glass: 1 Oil foaming 2 Turbidity of R134a 3 Lack of Condensing 4 Undercharge 3

4 OIL FOAMING Basically a problem of retrofitting. If mineral oil is left in the system excessive foaming and agitation with the R134a compatible synthetic oils may/will occur. This renders the sight glass useless. NOTE: Genuine R134a systems with known oil types do not have oil foaming problems - there are of course no oil mixing problems in these systems. However the sight glass may still foam for one of the following reasons. A case for flushing - it removes the variable of oil foaming in the receiver drier due to oil types being mixed. TURBIDITY R134a exhibits turbid characteristics in some systems in the drier. This will cause unwanted bubbling or foaming of the sight glass even though the eductor tube (stand pipe) is covered with liquid. Foaming or bubbling due to turbidity can be ignored if it is the identified cause of the bubbling/foaming. With R12 there were basically 4 stages of sight glass indication whilst charging: 1 Clear sight glass - oil smearing - pure vapour in the system- very low charge rates. 2 Heavy foaming of sight glass - a small amount of liquid in the base of the drier mixed with a high vapour content - under flow conditions this caused an agitated foamy mixture. 3 Bubbling sight glass - the stand pipe/educator tube was covered but some bubbling, due to agitation under flow, was still picked up. 4 Clear sight glass - there was a sufficient quantity of R12 in the system to cover the bottom of the stand pipe to a degree that no bubbles were picked up. This was our correct charge where a solid liquid stream (liquid head) to the TX valve was guaranteed. This ensured maximum system performance under all operating conditions/heat loads. With the knowledge that the sight glass may foam due to one of the above conditions, it is important that we establish some critical guidelines for charging of systems and the analysis of condensing action. These main points are the subject of the rest of this Bulletin. A clear pool of liquid refrigerant must be present in the base of the receiver/drier - this ensures liquid feed for the TX and gives a reserve quantity of refrigerant for leakages/weeping. If a reserve is not present there is an increased possibility the customer will return within the season complaining of lack of performance - particularly if their system is serviced early in summer (seasonal locations) 4

5 Charging Options There are four options of charging: 1 Weight charging 2 Sight Glass charging 3 Pressure charging 4 Monitoring of Condenser Subcooling. The 90% charge rule in retrofit allows for the density differential between R12 and R134a. R134a is 10% lighter so charging to 90% ensures an equal liquid volume enters the system. CAUTION: None of the above methods of charging should be used in isolation. In all cases pressures must be analysed and in retrofitted systems subcooling checks are recommended to verify correct charge rates and/or satisfactory condenser performance. WEIGHT CHARGING The simplest of all methods of charging is to weigh in a specified quantity of refrigerant as specified by the manufacturer. As previously mentioned the recommendation is for 90% charge ratios to be used in retrofit to ensure the equal liquid volume is maintained. (Accounts for the R12 to R134a density differential.) Before weight charging a system ensure the following factors are taken into account. A thorough inspection must be carried out to ensure the system is unaltered from manufacture. Pulling hoses dry with the high side depressor backed off is a dangerous practice - unless some pretesting verifies there is no danger of runaway head pressures. To accurately weight charge a system the hoses must be pulled dry or an allowance made for the quantity of the refrigerant that is retained in the hoses at the completion of charging. Note: A 2 metre set of service hoses will contain approximately 100 grams of refrigerant unless they are pulled dry. CAUTION: When weight charging retrofitted systems DO NOT pull the hoses dry or balance off the gauges unless some pre-testing has been done on an identical system to ensure that the extra quantity pulled into the system will not drive head pressures up to an unacceptable level. When pulling hoses dry once the high side valve depressor is backed off the high side pressure can no longer be assessed. The extra quantity (up to 100 grams) can be a massive overcharge to a retrofitted or small capacity system. It is for this reason it is strongly recommended the hoses are left full on completion of charging UNLESS prior verification testing is performed. 5

6 SIGHT GLASS CHARGING Contrary to popular opinion the sight glass may still clear at correct charge rates in a correctly operating system. Whilst weight charging or pressure/ subcooling charging keep an eye on the sight glass. If it happens to clear then it still remains a valid indicator. The important thing to realise is it may not clear and this is where the other indicators are critical. PRESSURE CHARGING Clear sight glass indicates a liquid supply to the TX valve - If the sight glass does clear it is still a valid indicator of charge rates. In reality pressure charging should never be done in isolation. It should be married with weight charging, sight glass indication and liquid line subcooling as required. Pressure dynamics will vary significantly dependent on the heat loads placed on the system. However there are some rules that can be used for basic pressure analysis of both genuine and retrofitted R134a systems. In a correctly operating, correctly charged system the evaporator and the condenser will Balance Off. In simple terms this means the condenser will dissipate the heat that the evaporator absorbs - in fact it has to also dissipate suction line superheat and compressor superheat. For this reason the condensers heat radiation capacity is above that of an evaporator. Critically an evaporator will absorb approximately 25 to 30ºC out of the cabin air. On humid days this temperature absorption factor will drop because it has the dehumidification heat loads to contend with (to be discussed later). If the evaporator is absorbing 30ºC out of the cabin then it stands to reason the condenser will need to dump off heat at a differential of 30ºC. Due to the frontal surface area of a condenser being considerably larger than an evaporator its efficiency as a heat exchanger is higher - Given this, well designed systems will balance off when the refrigerant in the condenser is approximately 25ºC hotter than the air surrounding the condenser. In general terms the condenser heat radiation capacity needs to be 1.5 times that of the evaporator in a modern system. This allows for suction line superheating and compressor superheating. Using this +25ºC rule will arm the technician with a basic guideline of establishing what the condensing pressure should be for normal heat loads of 20 to 35ºC (moderate to low humidities). 6

7 Example: Most technicians are familiar with monitoring high side presures - But in both retrofit and genuine 134a systems there are significant advantages in using condensing temperatures as the benchmark for system analysis. Sample the air temperature the condenser is working with - ie the temperature of the air 50mm in front of the condenser with no air flow. Let s use the example of 28ºC. Condenser air on = 28ºC Air to Refrigerant Differential required for = 25ºC adequate condensing = Ideal condensing temperature 53º C = (Refer to P/T chart) Approximately 1320kPa (190PSI) Therefore this system operating and charged correctly will operate with a head pressure of 1320 kpa (190 PSI) to give a condensing temperature of 53ºC. Of course this is in an ideal world with everything working perfectly - but the reality is we must make an allowance to the condensing temperature of + 10% for low humidities and + 20% for high humidities (above 60% Relative Humidity) In the real world a condensing temperature of 60ºC (1580 kpa) (230PSI) would be acceptable for low humidities and up to 66º C (1800 kpa) (265PSI) for high humidity conditions. Using these guidelines establishes a basic pressure/temperature rule for ascertaining head pressures but there are limitations to this clinical approach. For low ambient conditions the doubling rule should be used due to low evaporator heat loads. Low Ambient Conditions Under low ambient conditions (below 25ºC) especially when humidities are also low the +25ºC rule is limited. Going back to the basic system operation why would the condenser establish a 25º differential when the evaporator is only absorbing 18ºof heat (18º day)? The answer is it wouldn t. It would only establish a differential to balance off the system which will only be 18ºC (possibly only 15º to 16º given the efficiency ratio condenser to evaporator). For low ambient conditions it is therefore recommended the doubling rule be used. The doubling rule is simply - sample the ambient temperature and double it. ie: 18ºC day + 18ºC differential = 36º condensing temperature = 810 kpa (118 PSI) 7

8 Once again an allowance of 10% must be made for low to moderate humidities and 20% for high humidities (above 60%). High Ambient Conditions At above 35ºC, especially with high humidities, the evaporator is working at peak capability, the TX valve will be open for a considerable percentage of time causing high flow rates and dense suction vapours to the compressor and the flow rate through the condenser to be higher. These factors load the condenser to a point where it will need to operate at approximately 30ºC higher above its sourcing air (air on) in order for it to dump heat effectively. DETERMINING CHARGE RATES BY PRESSURES A 30º differential will be established at high ambients due to high TX flow rates and dense suction vapours loading the condenser. In addition underbonnet heat leadings will be higher. Things are not as simple here as what they might seem - and those technicians who have been in the trade a while will know this. The relationship between charge rates and condensing pressures/ condensing temperature is not linear. That is we do not have 75% of ideal pressures at 75% charge rates and correct pressures at 100% charge rates. This is not to say we can t use pressures for system evaluation but rather that we need to identify the system dynamics when charging. Let s Go Back To Basics The condenser has to dissipate the heat that the evaporator absorbs. Whilst charging at approximately ½ charge on a 25º day there is a considerable amount of vapour being fed to the TX valve (the receiver drier stand pipe is not covered in liquid). With excess vapour feed to the TX excess superheating will occur across the evaporator (ie reduced volume of refrigerant entering the evaporator = excess superheat). In this case the TX valve will open up to compensate for the vapour feed. At 25º (nominal) the TX will fully open to fill the evaporator coil. In this scenario the evaporator can therefore absorb cabin heat relatively effectively. If we are absorbing cabin heat then the head pressures will already be at recommended levels (ambient +25º) = 50ºC. Past this point we are increasing liquid feed rates to the TX which will effectively cause the TX valve to shut down. The amount of heat absorbed by the evaporator will however remain relatively stable. At moderate heat loads (eg 25ºC) the evaporator can be filled at relatively low charge rates - due to the TX opening up. Once the evaporator is filled and absorbing heat the head pressures will be at or near recommended levels. 8

9 Therefore the head pressures will not rise significantly. This is the formation of the high side Plateau. The high side stabilises off at 50ºC (1220 kpa) (180 PSI) as charging continues up to a point of overcharge. When entering the overcharge band the head pressures kick or begin to wander off the prestabilised plateau. NORMAL PRESSURE CURVE CORRECTLY OPERATING SYSTEM The system should hold the plateau up to 90% charge rates (for retrofitted systems). The correct procedure when charging is to watch the high side gauge carefully for the establishment of the plateau. Past this point the high side should stabilize off or only increase marginally (due to a marginal efficiency rise in the evaporator due to liquid feed.) With continued charging the pressures should remain stable until the system has either: been charged with the correct weight/volume of refrigerant (90% of R12 weight) OR the sight glass clears. 9

10 If the high side kicks or wanders before a 90% charge rate is achieved or before the sight glass clears it clearly indicates a condensing deficiency. The high side kick indicates the condenser is no longer handling the evaporator heat loads at full charge rates when the evaporator is working at peak efficiency and absorbing maximum heat. CAUTION: Below 30ºC (dry air) or 25ºC (humid air) the evaporator is not operating at maximum heat load and therefore a pressure kick may not be indicated. Overcharging is common on cooler days because of the reduced load on the condenser. At these reduced heat loads the system can hold the plateau past the maximum recommended charge point. The problem is on hot days the head pressure runs away. This is where the additional subcooling check (see next) is recommended. A kick off the plateau clearly indicates the condenser is no longer dissipating the heat that the evaporator is absorbing. NORMAL PRESSURE CURVE MARGINAL CONDENSING LIMITATION 10

11 NORMAL PRESSURE CURVE POOR CONDENSING LIQUID LINE SUBCOOLING Liquid line subcooling is a check of condensing efficiency and charge rates. It is a vital check to systems that: Liquid Line subcooling is an additional check that can be used to verify condensing efficiencies or limitations. Do not hold the plateau ( or exhibit rising head pressures) at lower than recommended charge rates Are lacking performance on hot days Fail to clear a sight glass The concept of liquid line subcooling is simple. With reference to Refrigeration Bulletins 1, 2 and 3 we know that: NO LIQUID LINE SUBCOOLING CAN OCCUR UNLESS THE CHANGE OF STATE IS COMPLETED BACK IN THE CONDENSER. 11

12 Once the vapour has condensed it will cool in the last portion of the condenser. It is this subcooling that is the key indicator of adequate condensing. There are however various reasons for lack of condensing. Most of them are obvious and have been our basis for evaluation for years: blocked condenser (external) blocked radiator (external) restricted airflow (coolers, insect screens etc) undersized condensers inoperative electric fans loose drive belts (mechanical fans) faulty viscous drive hubs. Any one or more of the above factors may lead to lack of condensing. There are two additions to this list which are largely a product of the retrofit era: contaminated refrigerants (mixtures) higher latent heat capacity of R134a. Many technicians fail to realise that R134a from a purely technical stand point is approximately 20% harder on condensing. If the R12 condenser fitted to the vehicle was easily handling R12 then it will probably have adequate capacity to handle R134a. Limited condensing performance may not dictate a new high performance condenser be fitted. Fans, shrouding or radiator to condenser sealing are all viable options in certain cases. These methods are widely practiced in America. NOTE: Recent documentation from USA published by a large vehicle manufacturer gives guidelines of retrofitting for all their vehicles 1980 to Reviewing the list over 80% of their vehicles had a condenser change or modification stipulated. Most vehicles retrofitted in Australia do not have a condenser change because it is a price driven not a performance driven market. The common practice is to tailor charge rates to compensate for the lack of condensing. There are problems with this procedure in high heat load environments (see next section undercharging). Subcooling is the method used to identify condensing is in fact adequate. The liquid line should be 5 to 16º cooler than the condensing temperature. How do you do a subcooling test? Check the condensing temperature on the gauge (ie 1220 kpa = 50ºC condensing) Measure the liquid line with a good quality thermocouple/thermistor probe It should read 34 to 45ºC This verifies the liquid has subcooled in the bottom of the condenser. 12

13 LACK OF SUBCOOLING What if in the previous example the liquid line was at 50ºC (equal to condensing temperature). This means there is no subcooling with a distinct possibility of incomplete condensation. This could be the reason for bubbles or foaming in the sight glass (it probably is!!!) A liquid line at the same temperature as the condensing temperature indicates a lack of subcooling. The vehicle must not be sent out with no subcooling - The cause must be identified. When there is a lack of, or no subcooling, there are two possibilities: insufficient condenser capacity low charge rates To differentiate between them we need to go back to the head pressure analysis. If the head pressure is on the plateau or below the recommended level then it is likely a low charge rate. If however the head pressure is creeping then it is clearly lack of condensing. IF THE HIGH SIDE IS NOT STABLE AT RECOMMENDED LEVELS AND SUBCOOLING LEVELS ARE LOW THE PROBLEM WITH THE CONDENSER MUST BE RECTIFIED. SUBCOOLING MUST BE PRESENT WHILST WE ARE STILL ON THE PLATEAU. Do not compare inlet and outlet temperatures of the condenser. THIS IS AN INVALID TEST as it merely compares a superheated pipe temperature with a subcooled pipe temperature - a totally useless test. USING SUBCOOLING TO DETERMINE CHARGE RATES Subcooling levels are dependent on charge rates providing condensing is adequate. Subcooling is the overcooling of the liquid in the last portion of the condenser below its ideal condensing temperature. If the high side gauge is creeping or climbing to above normal condensing pressures and temperatures due to poor condensing action subcool testing is an invalid testing method. Pressures and temperatures must still be on the plateau. With ideal condensing pressures/temperatures present in the system the subcooling level can be checked to verify charge rates. At low charge rates subcooling levels will be low due to a low condensing efficiency (poor refrigerant to condenser wall contact). At correct charge rates subcooling levels will be optimised due to condensing efficiency being at a maximum (refrigerant to condenser wall contact is maximised. In an overcharge condition testing becomes invalid when condensing temperatures rise to above normal levels (kick off the plateau). 13

14 Using this knowledge together with the guidelines of 5ºC to 16ºC being an ideal subcooling range we can monitor subcooling until it is in the ideal range. If we can t promote any subcooling before the head pressure creeps or climbs condensing is inadequate. If we can achieve +5ºC subcooling whilst maintaining head pressure then we are in the normal charge band at moderate to high heat loads. On cooler days (low heat loads) 10ºC subcooling is normal due to the ease of promoting a subcooling run. Subcooling in excess of 16ºC indicates a possible overcharge. On cool days the high side may be stable with 18 to 20ºC of subcooling but on a hot day the head pressure is likely to run away. If a system is checked on a cool day with high subcooling levels it is suggested some refrigerant is removed until the normal subcooling level is reached unless the technician can guarantee against an overcharge on a hot day. (Pre-tested an equivalent system for charge rates.) The subcooling charts included here graph the correct charge and for a property condensed system. These are included as Technical Data Sheets 6 and 7 for future easy reference. PSI SUBCOOLING REFERENCE 14

15 kpa SUBCOOLING REFERENCE Use the subcooling charts to analyse charge rates (providing condensing is adequate). Comparing the high side pressure (condensing temperature) with liquid line temperature will indicate which band you are in (overcharge, undercharge or correct). As little as 20 grams overcharge may present problems in marginally condensed systems with low capacity. OVERCHARGING Most problems of an overcharge need no introduction to a majority of VASA technicians. Likewise the appreciation that R134a is much more charge critical than R12, with +20 grams being a tolerance for many small charge systems. Some items of overcharge however may need some clarification. When head pressures rise above normal levels the temperature of the condenser rises with the refrigerant temperature. This causes the formation of flash gas which may be the bubbling we see in the sight glass with an overcharge. This flash gas, which is really vapour, when entering the TX will cause a decrease in evaporator efficiency and can lead to failure to fill the evaporator on hot/humid days with the subsequent generation of superheat. Subcooling levels checks become invalid with any rise in pressure/ temperature above the normal levels. 15

16 If existing TX valves are retained the flow rate is 20% higher than with R12. The TX valve normally shuts down to compensate but during the stabilisation phase, whilst the TX is shutting down there is an increased risk of liquid flood back to the compressor. This of course means our charge rates are more critical. given we are already working close to the danger zone with normal charge rates. UNDERCHARGING The problems with undercharging are not as well documented and in fact have largely not been a problem with charge tolerant R12 systems. Interconnected with this is the belief that annual servicing is finished. The reality is late model systems are far more critical to charge rates and system integrity and an annual service check (as opposed to a full service - which would be done as necessary) is probably more critical than ever before. Let s look at the problems with undercharging: First and foremost is the inability to fill the evaporator coil under high heat load conditions. Many technicians fail to realize the evaporator can easily be filled on a 25º day (with the TX fully open to compensate for the low charge) but on a 35º day (examples only) there is no way the evaporator can be filled for maximum efficiency. Further to point 1, if the evaporator is not filled the long superheat run, plus suction line superheating that will result may generate excessive discharge line superheat with subsequent thermal switch activation or compressor failure (lack of compressor cooling). It is important to realise this may only occur on hot days (high heat loads). No superheat testing on cooler days will indicate the problems that will arise under high heat loads. Our role as professional service technicians is to ensure a 90% charge rate (or close to it) during service. We then know the evaporator will be capable of being filled under all heat loads. Thirdly is the question of oil return that will be addressed in the next RTP. At this point it is important to realise the amount of refrigerant circulating directly controls the oil circulation rate, with oil return back to the compressor being critical especially under highway conditions. At lower charge rates oil circulation rates reach critically low levels. Excessive flow rates through the TX valve may exist before the TX shuts down if it is oversized- which is technically the case when an R12 valve is used in an R134a Most people do not appreciate the inability to fill the evaporator coil at high heat loads, resulting in lost This Retrofit Bulletin has covered some basics and some advanced concepts of charging in retrofit. We would encourage all VASA technicians not to immediately go into worry mode over this information but rather to think more carefully when charging systems, and to relate this information in simple terms to the customer to encourage professional service as our agenda. 16

RTP Technical Bulletin

RTP Technical Bulletin RTP Technical Bulletin Category: REFRIGERATION REGISTERED TECHNICIANS PROGRAM Volume 1 Bulletin 2 the information contained in this bulletin contains some important c o n c e p t s regarding pressure/

More information

The Saturation process

The Saturation process SOUTH METROPOLITAN TAFE WA The Saturation process Dennis Kenworthy 8/5/2016 A student study guide to measuring and interpreting the saturation process of refrigeration and air-conditioning equipment System

More information

The Essentials Of Working With R-410A

The Essentials Of Working With R-410A The Essentials Of Working With R-410A By Norm Christopherson Several major manufacturers are producing comfort air conditioning equipment using refrigerant 410A. The trend towards the use of 410A continues

More information

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

Checking the Charge on a Heat Pump in the Winter

Checking the Charge on a Heat Pump in the Winter Checking the Charge on a Heat Pump in the Winter When you ask many people nowadays how to check the charge on a heat pump during low outdoor temps they will say that you need to weigh in and weigh out

More information

Otherwise, you can continue reading the file on the following pages.

Otherwise, you can continue reading the file on the following pages. If you d like to be able to print this file out to study off-line or use on the job, a printable version is available for an administrative fee of $3.97 USD. To download the unlocked file, click here.

More information

AIR TO AIR HEAT PUMP SYSTEM DESIGN

AIR TO AIR HEAT PUMP SYSTEM DESIGN 17-1243 Application Engineering Bulletin AE-1243-R5 Revised March 1, 1983 AIR TO AIR HEAT PUMP SYSTEM DESIGN In a world growing increasingly short of natural energy sources, the pressure for more efficient

More information

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system. Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs the unwanted heat, this raises the refrigerant

More information

USING THE P-T CARD AS A SERVICE TOOL

USING THE P-T CARD AS A SERVICE TOOL Service Application Manual SAM Chapter 620-115 Section 2 USING THE P-T CARD AS A SERVICE TOOL Reprinted with permission from Sporlan Division, Parker Hannifin Corporation INTRODUCTION Manufacturers of

More information

Everything You. NEED to KNOW. TXV does this by keeping the coil supplied

Everything You. NEED to KNOW. TXV does this by keeping the coil supplied Everything You NEED to KNOW About TXVs } With the higher SEER air conditioners, technicians need to reacquaint themselves with thermostatic expansion valves B Y A L M A I E R Before the 13 SEER minimum

More information

Negative Superheat? Time to Check Your Tools

Negative Superheat? Time to Check Your Tools Negative Superheat? Time to Check Your Tools I was fresh out of school working as an apprentice at my first real HVAC job and I was listening in on a shop conversation between a few techs. They were talking

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

A Treatise on Liquid Subcooling

A Treatise on Liquid Subcooling A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance

More information

REFRIGERANT CHANGEOVER

REFRIGERANT CHANGEOVER Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants

More information

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications. TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there

More information

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS 22-1182 Application Engineering Bulletin AE-1182-R24 Revised April 1, 1993 LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS One of the major causes of compressor failure is damage

More information

Refrigeration Systems and Accessories

Refrigeration Systems and Accessories As with the Chapter Review Tests and the Final Exam, the tests your understanding of the materials underlying the learning objectives. After you ve reviewed your answers to the Chapter Review Tests, try

More information

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin B40-THERM-PDI-14 1069132 ThermoSaver TM Hot Gas Defrost System For use on select

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

Air Conditioning & Duracool Emery Stora

Air Conditioning & Duracool Emery Stora Air Conditioning & Duracool Emery Stora X Low refrigerant Clutch cut off switch * *Leaves compressor as High pressure gas **Leaves condenser as High pressure liquid ** Changes from a high Pressure liquid

More information

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved. GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant

More information

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a Air-Cooled Variable Speed Drive Screw Chillers Super Efficient Super Quiet Cooling Capacity Range 540-1405 kw R134a World s first low sound Air-Cooled variable speed drive screw chiller The recognition

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

Motor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle

Motor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle Motor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle At Sea level water boils at 212⁰ F R 134a boils at 15⁰ F At Sea level R 134a boils at 15⁰ F At 30 psig R 134a boils at 35⁰

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Determining Real Time Performance of Residential AC Systems. Presented at the RESNET Conference San Antonio, TX February 28, 2006

Determining Real Time Performance of Residential AC Systems. Presented at the RESNET Conference San Antonio, TX February 28, 2006 Determining Real Time Performance of Residential AC Systems Presented at the RESNET Conference San Antonio, TX February 28, 2006 Bill Spohn testo, Inc. testo Worldwide 100 90 80 70 60 50 40 30 20 10 0

More information

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications: TECHNICAL DATA SHEET Features and uses of is a non-azeotropic blend of HFC with zero Ozone Depletion Potential et low Global Warming Potential (GWP), formulated to meet the requirements of the F-Gas Regulation

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Refrigerant Glide and Effect on Performances Declaration

Refrigerant Glide and Effect on Performances Declaration Refrigerant Glide and Effect on Performances Declaration Scope and Purpose As a consequence of the EU regulation 517/2014 (F-gas), the future synthetic refrigerants with a low global warming potential

More information

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014 Class 1: Basic Refrigera0on Cycle October 7 & 9, 2014 Refrigeration Cycle 4 key components needed in a basic refrigera0on cycle: 1. Compressor 2. Condenser 3. Evaporator 4. Metering Device Compressor Compressor

More information

SERVICE ASSISTANT OVERVIEW FDSI Online Training

SERVICE ASSISTANT OVERVIEW FDSI Online Training Author: Dale T. Rossi Online Editor: Zachary Williams SERVICE ASSISTANT OVERVIEW FDSI Online Training May 5, 2009 Table Service Assistant Description... 2 Installing the Main Unit... 3 Ambient Temperature...

More information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient

More information

Superheat charging curves for technicians

Superheat charging curves for technicians This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block.

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin K40-THERM-PDI-15 Part # 1069130 PRODUCT SUPPORT web: k-rp.com/ts email: mdcu-lgcu@k-rp.com

More information

R410a Installation and fault finding training

R410a Installation and fault finding training R410a Installation and fault finding training Contents: General introduction Disassembly and reassembly Installation guide Trouble shooting General introduction: 1. Product Introduction Development Specification

More information

B. A. T. Basic Appliance Training

B. A. T. Basic Appliance Training B. A. T. Basic Appliance Training BASIC REFRIGERATION presented by Phil Whitehead Program Objective The objective of this program is to give you some of the basic elements that are essential to understanding

More information

Refrigerant Transfer and Compressor Damage

Refrigerant Transfer and Compressor Damage Refrigerant Transfer and Compressor Damage While a piston or scroll compressor refrigeration system with a low-side oil sump is shut down, all is not at rest in the refrigerant circuit. Cutaway views of

More information

Fundamentals of Refrigeration Part 2 Refrigeration 1

Fundamentals of Refrigeration Part 2 Refrigeration 1 Fundamentals of Refrigeration Part 2 Refrigeration 1 We have established in the first part of this training session that cooling in a DX coil is the result of the latent heat of vapourisation which is

More information

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems 12 In Row Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents Table of Contents... 3 Site

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office

More information

Efficient Steam System Design

Efficient Steam System Design Efficient Steam System Design The word Efficient is often used to describe the general performance of a system. However it is important to distinguish between efficiency and effectiveness. Efficiency is

More information

HVAC/R Refrigerant Cycle Basics

HVAC/R Refrigerant Cycle Basics HVAC/R Refrigerant Cycle Basics This is a basic overview of the refrigeration circuit and how it works. It isn t a COMPLETE description by any means, but it is designed to assist a new technician or HVAC/R

More information

Use this Construction/HVAC Glossary to answer the questions below.

Use this Construction/HVAC Glossary to answer the questions below. www.garyklinka.com Page 1 of 21 Instructions: 1. Print these pages. 2. Circle the correct answers and transfer to the answer sheet on the second last page. 3. Page down to the last page for the verification

More information

Air Conditioning Components

Air Conditioning Components Air Conditioning Components Agenda AC Components Compressor & Clutch Condenser Receiver-drier or Accumulator Expansion Valve or Orifice Tube Evaporator Compressor 2 primary purposes Increase pressure &

More information

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC. Fig. 2: Blower & Evaporator Unit Specifications 2004 HVAC SYSTEMS Manual HVAC System - Sorento GENERAL SPECIFICATIONS AIR CONDITIONER Fig. 1: Air Conditioner Specifications BLOWER AND EVAPORATOR UNIT HEATER

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE Master Rack Compressor Sequencer 7/21/2017 1 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PARALLEL RACK NOMENCLATURE...

More information

Before I start on this one At HVAC School we focus on a wide range of topics, many of them are very basic. My experience as a trainer for over 16

Before I start on this one At HVAC School we focus on a wide range of topics, many of them are very basic. My experience as a trainer for over 16 Refrigerant Charging Basics For Air Conditioning & Heat Pump Systems Before I start on this one At HVAC School we focus on a wide range of topics, many of them are very basic. My experience as a trainer

More information

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS English Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Instruction Manual

More information

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING Sample Questions and Answers CHAPTER 5 EVAPORATORS 1. What is Evaporator? Classify the various types of evaporator. Evaporator

More information

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration Calhoon MEBA Engineering School Study Guide for Proficiency Testing Refrigeration 1. To prevent an injury when working with refrigerants, what safety precautions are necessary? 2. When halogens are in

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

R07. Answer any FIVE Questions All Questions carry equal marks *****

R07. Answer any FIVE Questions All Questions carry equal marks ***** Set No: 1 III B.Tech. II Semester Supplementary Examinations, April/May 2013 REFRIGERATION AND AIR CONDITIONING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions

More information

Ammonia. Background on ammonia as a refrigerant

Ammonia. Background on ammonia as a refrigerant Ammonia Danfoss Industrial refrigeration has written a technical paper on things to consider when changing from HFC/HCFC s to ammonia. It outlines some of the main differences between the different plant

More information

How to Diagnose a TXV Failurek

How to Diagnose a TXV Failurek How to Diagnose a TXV Failurek There has been much written and many jokes made about the misdiagnosis of TXV (Thermostatic expansion valves) and rightly so. This article will cut straight to the point

More information

Comparative Performance of HFO Blends in a Condenser

Comparative Performance of HFO Blends in a Condenser The knowledge hub for refrigeration, air conditioning and heat pumps Nick Atkins MInstR Simon Jones MInstR Gary Bell Comparative Performance of HFO Blends in a Condenser Paper 2 research laboratory tests

More information

Boiler Manager Technical Report

Boiler Manager Technical Report Boiler Manager Technical Report Boiler Manager Technical Report Process Description The Boiler Manager works by controlling the boiler firing cycle. What is the Boiler Firing cycle? When the central heating

More information

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL BY DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL In the September/October 2005 issue of HPAC Magazine, the case was made for reducing head pressure to increase compressor efficiency, thereby lowering its

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things

More information

Refrigerant changeover guidelines

Refrigerant changeover guidelines Refrigerant changeover guidelines HCFC R-22 to HFC R-407A/F, R-448A or R-449A for medium and low temperature applications HCFC R-22 to HFC R-407C for high, medium and low temperature applications HCFC

More information

THERMOSTATIC EXPANSION VALVES Part 2

THERMOSTATIC EXPANSION VALVES Part 2 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 THERMOSTATIC EXPANSION VALVES Part 2 Revised by Loren Shuck, CMS INTRODUCTION The previous chapter dealt briefly with

More information

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.

More information

Harold Ag & Mobile Products

Harold Ag & Mobile Products TM Harold Ag & Mobile Products Your Ag A/C Parts Specialist 1-800-541-8910 www.heco.net R E F R I G E R A N T S 6-18-13 FR-12 COMPARED TO OTHER BLENDS UL Classified A1/A1 (non-flammable!) ASHRAE Listed

More information

VAPOUR RECOVERY DURING FUEL LOADING. Ben Adamson Principal Engineer Refrigeration Engineering Pty Ltd, NSW Australia

VAPOUR RECOVERY DURING FUEL LOADING. Ben Adamson Principal Engineer Refrigeration Engineering Pty Ltd, NSW Australia VAPOUR RECOVERY DURING FUEL LOADING Ben Adamson Principal Engineer Refrigeration Engineering Pty Ltd, NSW Australia ben_adamson@refeng.com.au ABSTRACT Volatile fuels such as gasoline and naphtha, and to

More information

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA242H WA36H NOTE: Electrical data presented in this manualsupersedes any other data for the above listed models. Bard Manufacturing

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation Form 30-217 / January 2007 Heat Reclaim Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation While the vapor-compression cycle has

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit

More information

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the MYSTICOOL Max Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

How Ground Source Heat Pumps Work

How Ground Source Heat Pumps Work How Ground Source Heat Pumps Work How Ground Source Heat Pumps Work A heat pump is a mechanically simple system that is conceptually difficult to relate to. The boiler plate answer for how geo works is...

More information

If you have any questions, please feel free to contact me at (405) or via at

If you have any questions, please feel free to contact me at (405) or via  at Marketing News M-183-2007 Date: August 7, 2007 To: All Branch Managers, Branch Sales and Service Managers, Distributor Principals, Distributor Sales and Service Managers, Regional Sales Managers and Regional

More information

TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY

TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY A steam trap, which is a fully automated condensate drainage device, generally does not require routine maintenance. Steam

More information

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the XSTREAM Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager INTRODUCTION The science of creating vacuum is often misunderstood and when the desired vacuum condition is not being achieved in a manufacturing setting this usually means production comes to a halt and

More information

Often fellow technicians, co-workers and field personnel CHARGE REFRIGERANT DETERMINING PROPER SYSTEM

Often fellow technicians, co-workers and field personnel CHARGE REFRIGERANT DETERMINING PROPER SYSTEM Image courtesy of Mastercool. DETERMINING PROPER SYSTEM REFRIGERANT CHARGE Troubleshooting refrigerant system issues is one of the toughest jobs HVACR technicians will ever face. BY RICH PERROTTA A wireless

More information

BRA FACT FINDER Number 19

BRA FACT FINDER Number 19 BRA FACT FINDER Number 19 Issue: 1 Date: March 2017 A practical guide to using refrigerants with a temperature glide This document is the second in a series of bulletins produced by the BRA following the

More information

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold LOW VAC INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold REF HIGH SPECIAL FEATURES Low battery indicator Displays 63 refrigerants Displays corresponding saturation, dew or bubble point temperature

More information

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Executive Summary. Number of Low Number of High Number of Faults , Number of OK Unit Lower limit Upper limit Air on Model no evap. F Air off evap. F dt air evap. F Executive Summary Evapo. F This is a summary chart for quick reference and view of all the systems tested. Red boxes

More information

Public Services Building 155 N First Avenue Hillsboro, OR March 2012

Public Services Building 155 N First Avenue Hillsboro, OR March 2012 Public Services Building 155 N First Avenue Hillsboro, OR 97124 March 2012 Tests and report done by: Joel Klobas Emerging Energy Solutions Technical Director joelk@eeswest.com Contents Introduction...

More information

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1 Technical Training Associates Presents Commercial Refrigeration Equipment Servicing Part 1 By Jim Johnson A Practical Approach To The Fundamentals Of Walk-Ins, Reach-In and, Display Cases: Restaurant,

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison Emerging Technologies: VFDs for Condensers Douglas T. Reindl Director, IRC University of Wisconsin-Madison University of Wisconsin-Madison 1 We ve looked at VFDs on Evaporators and compressors, what is

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

AQUASNAP AIR CONDITIONING MADE SIMPLE 30RA/30RH AQUASNAP LIQUID CHILLERS HEAT PUMPS

AQUASNAP AIR CONDITIONING MADE SIMPLE 30RA/30RH AQUASNAP LIQUID CHILLERS HEAT PUMPS AQUASNAP TM AQUASNAP LIQUID CHILLERS HEAT PUMPS 30RA/30RH AIR CONDITIONING MADE SIMPLE BOLT DOWN, PLUG IN... READY THE IDEAL ALL-IN-ONE SOLUTION With the Aquasnap everything is included to reduce the complexity

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

ASSIGNMENT OBJECTIVES

ASSIGNMENT OBJECTIVES LESSON 2 HVAC DIAGNOSIS covers the diagnosis, or troubleshooting, of the HVAC system and the tools used to perform that diagnosis. The lesson contains one reading assignment. ASSIGNMENT 1 HEATING AND AIR-CONDITIONING

More information

CHAMELEON. Flexible thermal unit with sophisticated control options.

CHAMELEON. Flexible thermal unit with sophisticated control options. CHAMELEON Flexible thermal unit with sophisticated control options www.tcmach.cz CHAMELEONCham You can t see it. But you can feel it s present. In each single room of your home. Yesterday impossible, today

More information

Press Release. How can the efficiency of the dryer section be increased? Dryer Section All Paper Grades. Heimbach wherever paper is made.

Press Release. How can the efficiency of the dryer section be increased? Dryer Section All Paper Grades. Heimbach wherever paper is made. Dryer Section All Paper Grades Press Release How can the efficiency of the T. Bock (Dipl.-Ing.), Manager Application & Technical Service, Heimbach GmbH & Co. KG, thomas.bock@heimbach.com I. Durniok (Dipl.-Ing.),

More information

BS En 285:2006+a2:2009 Description: Sterilization.

BS En 285:2006+a2:2009 Description: Sterilization. BS En 285:2006+a2:2009 Description: Sterilization. Steam sterilizers. Large sterilizers Steam sterilizers, Sterilizers, Large, Sterilization (hygiene), Medical equipment, Equipment safety, Safety measures,

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc Important Considerations When Selecting a Fan for Forced Air Cooling By: Jeff Smoot, CUI Inc Designing an appropriate thermal management solution requires a systemic approach; each component on a circuit

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 1 Contents INTRODUCTION... 3 WARNING LABELS AND SAFETY INSTRUCTIONS... 4 PARALLEL RACK NOMENCLATURE... 5 GENERAL RACK DESCRIPTION...

More information