1 K18 PLANT MANUAL Heating and DHW 0 - INTRODUCTION This document provides the guidelines on how the Gas Absorption Heat Pump GAHP K18 operates, how to use it and how a designer or a qualified installer should focus on specific topics in order to design and build a plant working with a GAHP K18. The contents in this manual are an integration of the Instruction Manuals of the GAHP and the OQLT017 System Controller (if present). 1 INDEX Chapter 1 Selection criteria Chapter 2 GAHP K18 Technical Data Chapter 3 Plant design, P&I schematics Pagina1

2 CHAPTER 1 SELECTION CRITERIA Q: Which is the building right size for a typical K18 installation? A: You should consider the actual thermal load and the additional functions instead of the size of the building. For instance, you can always provide DHW while a 120sqm building not well insulated may require the same thermal load of a well-insulated 300sqm one. Q: Which kinds of building are suitable for the K18 heat pump? A: Considering the right thermal load, we can consider one and two-family dwellings, even if already built. Q: Can the K18 be installed in an existing building with high temperature radiators (70/80 C)? A: Yes. The K18 can deliver hot water up to 65 C, a temperature enough for heating even during the coldest seasons, in fact: 1. The radiators dimensions are commonly oversized. 2. The heating power peak is typically calculated on the few coldest hours during night time for only a few days per year and doesn t consider the thermal inertia of the building itself that can compensate the temporary deficit of power. 3. Very often old buildings have been improved with thermal insulation actions (e.g. new window frames). With the K18 the old boiler replacement or integration becomes easier and faster. Q: Which are the advantages of a K18 in comparison with an Electric Heat Pump? A: Mainly but not only: The K18 electrical power need is really low: less than half a kw against more than 5 kw required by the electric technology; The K18 is able to perform well even when the external air temperature drops a lot; as a consequence of this, there is no need of power integration with an electric resistance. Due to this, extra energy savings are guaranteed also; The K18 technology is not involved in the F-Gas regulation; in fact it uses a natural refrigerant without any restriction or any specific maintenance. Pagina2

3 Q: May the K18 be managed by an already installed BMS? A: Yes. You can turn on the unit with a voltage-free contact or through the MODBUS protocol (normally with a BMS). Q: Can you manage the K18 together with an existing boiler? A: Yes, you can manage a third party boiler with the optional System Controller. The boiler will be used only if the K18 power will need to be integrated. Q: How will you manage exhaust piping? A: With 40 Pa of residual head, you can easily bring exhaust pipes up to the roof. Depending on the local normative, you can also manage flue gas exhaust on the wall. Q: K18 is for outdoor installation. Which is the best positioning strategy for the unit looking at the relative building? A: In order to avoid the most possible any unnecessary thermal dispersion due to connection pipes, the closer to the building, the better. You must only guarantee enough air circulation for the finned coil and the fan, and avoid any trouble with people or pets. Q: Is always the existing pipe system to be cleaned before installing the K18? A: Yes, it is. Dust and residual metal powder may reduce the K18 heat exchanger efficiency. Please, follow the pipe cleaning procedure that you can find in the K18 installation manual. Q: which is the optimal design temperature for an air source heat pump? Heat Pumps performances are strongly depending on the water delivery temperature. A variable set point that follows the actual external air temperature is recommended (e.g. 55/60 C when the outdoor temperature is around -5 C; 45/55 C when outdoor temperature is above 0 C). The K18 is ready to work with a variable set point without any further component. With this approach you will slightly improve the seasonal efficiency. Pagina3

4 CHAPTER 2 GAHP K18 TECHNICAL DATA In the table below, the available thermal power, depending on the external air and the water delivery temperature: DESIGN POWER DEMAND Design ambient Temp [ C] High Temperature System - 55 C Low Temperature System - 35 C ,0 13, ,0 14, ,5 15, ,0 16,0-5 14,0 17,0 0 15,0 18,0 5 16,0 18, ,0 19,0 DATI UTILI ALLA COMPILAZIONE DELLA CERTIFICAZIONE ENERGETICA Temperture range θ tol -25 C Generator Temperature θ gen,in 90 C Electrical Power Absorption 0,28 kw Heating Capacity ϕ gahp,in 11,2 kw Modulation range (min) 60 % GUE - K 18 θ f - C θ c - C Further technical data are available in the K18 Instruction Manual. Thermal Power ϕ gahp,out - K 18 θ f - C θ c - C ,5 15,4 13,3 2 18,4 17,4 15,3 7 18,9 18,0 16, ,8 18,3 16,8 Pagina4

5 Q: Does the K18 has its own water circulation pump? A: The K18 is available with or without onboard circulation pump. Q: Does the onboard water pump need a secondary pump towards the plant or is it ready to be used alone? A: An additional secondary water pump can be installed, depending on the existing plant features. The K18 water pump has a residual head of 40 l/h Q: Can the external circulation pump be directly managed by the K18? A: Yes, and it is the best option. This way the K18 will be able to manage the water pump according to the Heat Pump operating mode. Moreover also the active anti-icing cycle will be managed, i.e. the water pump will be connected to the electronic board of the unit and turned on in case of too-low water temperature Q: Is a buffer tank needed for the heating water circuit? A: After several tests, it has been proved that even a small buffer tank (100 liters) will dramatically improve the system seasonal efficiency, especially during partial-load operating mode (the most common working condition during the heating season). The bigger the buffer volume, the most the efficiency gain. Q: How the DHW production is managed with the K18? A: The K18 will work on a serpentine in the DHW production tank. Its volume will depend on the characteristics of the end user needs (number of people, number of bathrooms, et cetera) liters are usually enough. The serpentine must have a wide surface, enough for the power exchange that must be guaranteed between the K18 and the DHW in the tank (3-4 sqm for the liter tank). The System Controller (optional) will manage the right water delivery temperature and the 3-way valve. Q: What about the legionella cycle? A: The GAHP K18 can produce hot water up to 70 C (return temperature up to 60 C). With this temperature range you can eventually manage a thermal legionella cycle. Anyway other options are available, like UV rays, micro-filters and chemical treatments with chlorine dioxide or hydrogen peroxide. Pagina5

6 AVAILABLE MODELS Residual head of the high efficiency circulator pump: Electrical power need: 75 W STANDARD EQUIPMENT Ambient temperature probe Climatic curve available without any optional accessory Remote water delivery temperature probe Modulating fan Pagina 6 GAHP K 18 PLANT MANUAL

7 OPTIONALS In order to optimize the performance and to the overall the management of the K18, the following optional have been made available. The standard components not in the list can be sourced on the market. SYSTEM CONTROLLER (O-QLT017) The System Controller is very important to guarantee energy savings and an optimal efficiency in HVAC solutions. Therefore, also the secondary components, like circulators, room thermostats, valves, auxiliary boiler, et cetera, are to be managed. The K18 Controller has been fine tuned to guarantee all the above. Pagina7

8 Ability of the System Controller: - it manages the room temperatures; - it manages the DHW production; - it manages the K18 and, if needed, an auxiliary boiler. The System Controller is composed of: - Control Box, with the electronic board, some relays and electric plugs. - Room Unit, a remote controller to set and adjust the k18 and all the appliances connected to the Control Box, which acts also as an enhanced Chronothermostat. In fact it is always a good option installing the indoor Room Unit in the same room where you need the comfort temperature, replacing the existing one. This way the controller will force the water setpoint according the actual power needed by the building; in case the climatic curve based on the external air temperature will be adjusted and the ON/OFFs reduced. - External air probe for the climatic curve managing In the following chapter you will find some plant layouts, with and without the System Controller, that were designed in order to simplify the installer operation with some preconfigured parameter settings, and the user experience with a selection of user-friendly parameters. Pagina8

9 PART 3 PLANT DESIGN, HYDRAULIC AND ELECTRICAL SCHEMES BASIC HYDRAULIC PLANT The following components must be installed on the hydraulic plant: NOTES Expansion tank: it must be sized according to the water content of the plant, considering also water content of the unit and pipes (approximately 4 liters of tank per 100 liters of water content). Separator filter: must be installed when the plant already exists, because of possible impurities contained in it. It may be replaced by a simple Y filter in case of new plants. Control valve: required when a modulating pump is not used. Buffer tank: required to ensure a minimum load to the unit during periods of medium/low thermal load of the building. The size of the tank can be increased. In the minimum volume (100 liters) can be included also the volume of pipes between unit and buffer tank. Do not use glycol, if possible. The unit is equipped with anti freeze system, in order to keep water temperature above zero: for this reason the unit must be always connected to gas and power supply. Pagina9

10 ONLY HEATING PLANT ONE HYDRAULIC CIRCUIT (SCHEME 1) Heating plant for the production of hot water up to 65 C (without DHW production), no hydraulic separation. NOTES chronothermostat Water circulation: verify that there is always water circulation in the system. In case of using, for example, thermostatic valves, don t install them on one or two radiators. Is also possible to avoid installation or remove valves in the room where is located chronothermostat. Always install buffer tank to ensure a minimum load to the unit during periods of medium/low thermal load of the building. The control of the unit is made by an external consense from a device, such as a room thermostat, a chronothermostat or some thermostats in parallel that close a contact. The unit is equipped with external temperature probe in order to control climatic curve to optimize performance during periods of medium/low heating load. Is possible to change parameters of the climatic curve from the electronic board of the unit. SCHEME 1 Pagina10

11 OPTIONALS AND ELECTRICAL WIRING BETWEEN GAHP K18 AND PLANT For further details about wiring of GAHP K18 refer to Installation Manual. SCHEME 1 COMPONENTS REQUIRED FOR THE INSTALLATION of K18 version: with circulating pump without circulating pump OCDS005 Ambient chronothermostat OQLT017 System controller OSRB liters DHW tank (3 sq.m. coil surface) OSRB liters DHW tank (4 sq.m. coil surface) OVLV007 Three way diverting valve to switch heating/dhw OSND003 External air temperature probe OSND004 Immersion temperature probe: n. probes OPMP009 Modulating pump 7,5 m head OPMP004 Modulating pump 10 m head ONTV014 Anti vibration supports Pagina11

12 ONLY HEATING PLANT - TWO HYDRAULIC CIRCUITS WITH ONE CIRCULATING PUMP (SCHEME 2) Heating plant for the production of hot water up to 65 C (without DHW production) with two heating circuits and one pump. SCHEME 2 NOTES: Water circulation: verify that there is always water circulation in the system. When using, for example, 2-way valves for each circuit, connect the chronothermostats and 2-way valves to the system controller, in order to turn off the unit and the circulator when both thermostats are OFF. Insert between delivery and return to the plant an overpressure valve, to ensure water circulation when 2-way valves are closed and K18 activates antifreeze function. The control of the unit is ensured by System controller, to which chronothermostats are connected. System controller manages climatic curves (one curve for each zone) to optimize performance during periods of medium/low heating load. Is possible to change parameters of the climatic curve on the Plant controller. Pagina12

13 OPTIONALS AND ELECTRICAL WIRING BETWEEN GAHP K18 AND SYSTEM CONTROLLER For further details about wiring of GAHP K18, System Controller and other devices (thermostats, pumps, etc.) refer to related Manuals. SCHEME 2 COMPONENTS REQUIRED FOR THE INSTALLATION of K18 version: with circulating pump without circulating pump OCDS005 Ambient chronothermostat OQLT017 System controller OSRB liters DHW tank (3 sq.m. coil surface) OSRB liters DHW tank (4 sq.m. coil surface) OVLV007 Three way diverting valve to switch heating/dhw OSND003 External air temperature probe OSND004 Immersion temperature probe: n. probes OPMP009 Modulating pump 7,5 m head OPMP004 Modulating pump 10 m head ONTV014 Anti vibration supports Pagina13

14 ONLY HEATING PLANT - TWO HYDRAULIC CIRCUITS, ONLY ONE CIRCUIT MIXED (SCHEME 3) Heating plant for the production of hot water up to 65 C (without DHW production) with two heating circuits, the first is direct (radiators) and the second with mixing valve (radiant floor). Components required for the installation - System controller (mandatory optional) - Immersion temperature probe (optional) - Circulating pump for direct circuit (optional) - Circulating pump for mixed circuit (optional) - mixing valve and actuator (optional) - Anti vibration supports (optional) NOTES : refer to scheme 2. About electrical wiring, refer to scheme 2. SCHEME 3 Pagina14

15 SCHEME 3 COMPONENTS REQUIRED FOR THE INSTALLATION of K18 version: with circulating pump without circulating pump OCDS005 Ambient chronothermostat OQLT017 System controller OSRB liters DHW tank (3 sq.m. coil surface) OSRB liters DHW tank (4 sq.m. coil surface) OVLV007 Three way diverting valve to switch heating/dhw OSND003 External air temperature probe OSND004 Immersion temperature probe: n. _1_ probes OPMP009 Modulating pump 7,5 m head (the alternative is OPMP004) OPMP004 Modulating pump 10 m head ONTV014 Anti vibration supports Pagina15

16 ONLY HEATING PLANT WITH AUXILIARY BOILER (SCHEME 4) Heating plant for the production of hot water up to 65 C (without DHW production) with one or two heating circuits (refer to scheme 1, 2 or 3), the boiler is new or already existing. NOTES : refer to scheme 2. The boiler must be connected to the System controller in order to activate it when GAHP K18 unit cannot satisfy the heating request of the building (this situation may happen for few days per year when external temperatures are close to design temperature). About electrical wirings, refer to scheme 2. SCHEME 4 Pagina16

17 SCHEME 4 COMPONENTS REQUIRED FOR THE INSTALLATION of K18 version: with circulating pump without circulating pump OCDS005 Ambient chronothermostat OQLT017 System controller OSRB liters DHW tank (3 sq.m. coil surface) OSRB liters DHW tank (4 sq.m. coil surface) OVLV007 Three way diverting valve to switch heating/dhw OSND003 External air temperature probe OSND004 Immersion temperature probe: n. _2_ probes OPMP009 Modulating pump 7,5 m head (the alternative is OPMP004) OPMP004 Modulating pump 10 m head ONTV014 Anti vibration supports Pagina17

18 HEATING PLANT AND DHW PRODUCTION (SCHEME 5) It is possible to produce domestic hot water using a tank with internal coil which must be sized according with maximum delivery temperature of the heat pump. In the scheme below is represented heating plant and DHW production provided with auxiliary boiler and heat pump. There are two heating circuits, the first is direct and the second mixed. NOTES: refer to scheme 2. Diverting valve (optional) and temperature probe in DHW tank must be connected to System controller in order to manage DHW production. About electrical wirings, refer to scheme 2. SCHEME 5 SCHEME 5 Pagina18

19 COMPONENTS REQUIRED FOR THE INSTALLATION of K18 version: with circulating pump without circulating pump OCDS005 Ambient chronothermostat OQLT017 System controller OSRB liters DHW tank (3 sq.m. coil surface) OSRB liters DHW tank (4 sq.m. coil surface) OVLV007 Three way diverting valve to switch heating/dhw OSND003 External air temperature probe OSND004 Immersion temperature probe: n. _4_ probes OPMP009 Modulating pump 7,5 m head (the alternative is OPMP004) OPMP004 Modulating pump 10 m head ONTV014 Anti vibration supports REQUIRED CONNECTIONS Pagina19

20 The unit needs the following connections: - gas supply (maximum consumption is 1,2 m 3 /h). - power supply at 230 V (maximum power consumption is 280 W, water circulating pump is excluded). - electrical wirings for the control of the unit, to be connected to devices inside the building. - hydraulic connections to water inlet and outlet. Water charge can be realized on water pipes of the plant inside the building. - exhaust flue gas from the burner (for a correct discharge refer to local regulations). - Flue gas condense drain and defrosting water drainage (from the finned coil). The details about position and diameters of these connections are explained in the Installation manual of GAHP K18 unit. Pagina20

21 To prepare hydraulic, electrical and discharge connections refer to the scheme below. Hydraulic connections diameter: ¾ M Gas connection diameter: 3/8 M Exhaust flue gas diameter: 60 mm Maximum gas consumption: 1,2 m 3 /h Maximum power consumption GAHP unit: 280 W Pump power consumption (if included): 75 W Pagina21

22

23

24 D-MNL049 rev.a 15MEDSDC005 12/09/2015 Con l obiettivo di migliorare la qualità dei prodotti, Robur si riserva di variare e aggiornare i dati e le informazioni riportate in questo documento. PRONTUARIO GAHP K

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS Energy saving thanks to a total recovery p Cooling Heating/DHW h Galletti multi-purpose heat pumps are total recovery units used for a simultaneous hot and

More information

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw COMFORT HEAT PUMPS AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw climaveneta.com COMFORT HEAT PUMPS PERFECT COMFORT AND MAXIMUM EFFICIENCY Air to water heat pump for outdoor installation,

More information

Design Manual. Pre-assembled unit (LINK) Heating and Cooling/Heating modular groups. Platform PRO

Design Manual. Pre-assembled unit (LINK) Heating and Cooling/Heating modular groups. Platform PRO Design Manual Pre-assembled unit (LINK) Heating and Cooling/Heating modular groups Platform PRO Revision: A Code: D-MNL033 This manual has been drawn up and printed by Robur S.p.A.; whole or partial reproduction

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

Planning guide. (2010/09) en

Planning guide. (2010/09) en Planning guide (2010/09) en 1 Planning guide for Greenline HE E 21, 28 and HE D 36, 43 Page Contents 3 Documentation and VPW2100 4 Technical data of heatpump 5 Dimensioning of DHW systems 6 Symbol explanations

More information

CRIMSON & CRIMSON MAX

CRIMSON & CRIMSON MAX High efficiency water/water and geothermal heat pumps 5 114 General High efficiency water/water and geothermal heat pumps. Ideal for heating, cooling and production of domestic hotwater with total or partial

More information

Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production

Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production THE SIMPLEST SOLUTION FOR A CONDENSING BOILER DIVACONDENS D PLUS is the generator of condensation

More information

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories > HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION Available range Unit type IP Reversible heat pump (reversible on the refrigerant side) ECO-FRIENDLY REFRIGERANT GAS Versions (heat recovery) VB Base

More information

1

1 ST www.coldinnovation.it 1 INDEX Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R410A...pag. 5 Scroll compressors...pag. 6 Condenser

More information

UK arotherm Schematics and installation guide

UK arotherm Schematics and installation guide UK arotherm Schematics and installation guide Air to Water Heat Pumps (AWHP) Controls: VRC 700, VR 70, VR 91 The Vaillant heat pump booklet contains documentation to assist in the design, installation

More information

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS Total heat recovery multi-purpose units LCP Outdoor monobloc air-water unit LCP - kw Heating, cooling, domestic hot water one single system to meet all kinds of needs. Total heat recovery multi-purpose

More information

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

RVL471 Heating and Domestic Hot Water Controller Basic Documentation RVL471 Heating and Domestic Hot Water Controller Basic Documentation Edition: 2.2 Controller series: C CE1P2524E 23.10.2002 Siemens Building Technologies HVAC Products 2/118 HVAC Products 23.10.2002 Contents

More information

Control Application. Supplement - ACVMax

Control Application. Supplement - ACVMax prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

Advance Split

Advance Split Engineering Data Manual Aqu@Scop Advance Split Air-to-Water DC Inverter Split Heat Pumps Models 005, 008, 012 & 014 2 to 16 kw Strength Points Most efficient heating technology with variable speed compressor.

More information

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors infolinia: +48 691 262 691-15 C +63 C +43 C E.V.I. HP The series of high efficiency heat pumps has been specifically designed for use with

More information

Frequently Asked Questions

Frequently Asked Questions Air Source Heat Pumps Frequently Asked Questions Heating that doesn t cost the earth What are the benefits of Air Source Heat Pumps over Ground Source Heat Pumps? There are a number of benefits when using

More information

80HMA. Comfort Module Range for Monobloc Heat Pumps. Compact comfort module. DHW management possibility. Multi zone option control.

80HMA. Comfort Module Range for Monobloc Heat Pumps. Compact comfort module. DHW management possibility. Multi zone option control. product selection data Compact comfort module DHW management possibility Multi zone option control Easy installation Comfort module with two-zone kit Single-zone comfort module Comfort Module Range for

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 1402 C O K AIR R-407C Series RAE... C K Cooling capacity from 81 to 250 kw - 2 circuits The air cooled chillers of RAE C K series, with centrifugal fans, are designed for indoor installation and are

More information

Qualifies for up to $ 1500 Energy Tax Credit! CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ALL NEW, ADVANCED USER FEATURES

Qualifies for up to $ 1500 Energy Tax Credit! CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ALL NEW, ADVANCED USER FEATURES CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ALL NEW, ADVANCED USER FEATURES 5 FLOOR-STANDING AND 5 WALL-MOUNT MODELS FROM 50,000 TO 285,000 BTU/HR FIRING RATE MODULATION TO 5:1 LESS THAN 20 ppm NOx

More information

prestige Control Application Supplement - ACVMax

prestige Control Application Supplement - ACVMax 2015-10 Prestige ACVMax Control Sup 12-14-15_ACVMax_Control 12/15/15 7:36 AM Page 1 prestige Control Application Supplement - ACVMax L I S T E D WARNING This document is intended to be used by a factory

More information

AWR MTD2 XE. Versions

AWR MTD2 XE. Versions Versions ETING COOLING OT WTER ETING COOLING OT WTER ir/water reversible heat pump for water heating up to 58 C and operating limits down to -15 C external air temperature and domestic hot water production.

More information

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS RAH 602 Ka + CF + GP 62 Above picture is only indicative and is not binding.

More information

Better Design, Better Control, Better Systems.

Better Design, Better Control, Better Systems. Product Catalog Better Design, Better Control, Better Systems. At tekmar Control Systems, we believe the indoor comfort of a building depends on the performance of its heating, ventilating & air conditioning

More information

Hydronic & HVAC Control Systems

Hydronic & HVAC Control Systems tekmar 218 Full Line Catalog Hydronic & HVAC Control Systems HVAC Multi-Staging Alternative Energy Zoning Snow Melting Setpoint tekmarcontrols.com tekmarcontrols.com Better Design, Better Control, Better

More information

GHP AWO 38 Technical overview

GHP AWO 38 Technical overview Gas absorption heat pump 9 Technical overview single unit G&' &(')*ption heat pump components. 1 7 2 8 9 3 4 10 8 5 6 1 +),-.&/012 &0* ')-*34 5&1 2 G414*&/)* 3 G&' (-*ner 4 6)1,41'4* 5 6)7(-'/0)1 38&7(4*

More information

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw COMFORT CHILLERS AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw climaveneta.com COMFORT CHILLERS PERFECT COMFORT AND MAXIMUM EFFICIENCY Air-cooled liquid chiller for outside installation

More information

HEAT INTERFACE UNITS (Sanitary Hot Water Only)

HEAT INTERFACE UNITS (Sanitary Hot Water Only) HEAT INTERFACE UNITS (Sanitary Hot Water Only) T-FAST i20 (Sanitary Hot Water Only) 20 The T-Fast i20 is an instantaneous domestic hot water production module that produces a flow rate of 20L per/min at

More information

LZT High efficiency air to water heat pumps with E.V.I. compressors

LZT High efficiency air to water heat pumps with E.V.I. compressors High efficiency air to water heat pumps with E.V.I. compressors -20 C +43 C +65 C E.V.I. C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating

More information

Blue Box Epsilon Echos +

Blue Box Epsilon Echos + Blue Box Epsilon Echos + 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Packaged version in 5 sizes Nominal cooling capacity (A35;W7): 6 26 kw Nominal heating

More information

SHERPA. Air-water split heat pump. COP > 4 ACS a 60 C

SHERPA. Air-water split heat pump. COP > 4 ACS a 60 C Air-water split heat pump. COP > 4 ACS a 60 C Energy class: 35 55 RENEWALE TECHNOLOGIES Sherpa uses the heat in the air, and transfers it to system terminals in an efficient manner. For each kw of electricity

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

prestige Control Application Supplement - TriMax

prestige Control Application Supplement - TriMax prestige Control Application Supplement - TriMax L I S T E D WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions

More information

LZA High efficiency air to water heat pumps with HP compressor

LZA High efficiency air to water heat pumps with HP compressor High efficiency air to water heat pumps with HP compressor -10 C +43 C +60 C HP C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems

More information

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features Comfort Module Range for Monobloc Heat Pumps Quality Management Systems Comfort module with two-zone kit Single-zone comfort module 8HMA Nominal heating capacity 4- kw Nominal cooling capacity 4- kw The

More information

BHSAPPMAN 08/00 USA. Applications Manual. Ecomatic / Logamatic Controls. Save These Instructions!

BHSAPPMAN 08/00 USA. Applications Manual. Ecomatic / Logamatic Controls. Save These Instructions! BHSAPPMAN 08/00 USA Applications Manual Ecomatic / Logamatic Controls Save These Instructions! TABLE OF CONTENTS 1 2 3 4 5 6 7 8 Introduction 1 Terms 2-4 Description of Wiring Terminals 5-7 Application

More information

Mynute Green k. Condensing Wall-Hung Boilers. Residential Heating

Mynute Green k. Condensing Wall-Hung Boilers. Residential Heating Mynute Green k Condensing Wall-Hung Boilers Residential Heating Mynute Green k The right choice for any installation requirements The high flexibility of installation makes MYNUTE GREEN K the condensing

More information

Exclusive Green E Condensing Wall-Hung Boilers

Exclusive Green E Condensing Wall-Hung Boilers Exclusive Green E Condensing Wall-Hung Boilers BERETTA HIGH-EFFICIENCY Residential Heating compliant XL Exclusive Green E Energy efficiency at its best EXCLUSIVE GREEN E is Beretta top of the range condensing

More information

ENERGY TOP. Condensing boiler solutions

ENERGY TOP. Condensing boiler solutions ENERGY TOP Condensing boiler solutions 1 ENERGY TOP > ENERGY TOP RANGE A wide array of flexible solutions both for centralised residential application and big commercial plants The increasing need for

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 201 C K RAE 482 C K AIR R-407C Series RAE... C K from 19 to 83 kw - 1 and 2 circuits The air cooled chillers of RAE... C K series, with centrifugal fans, are designed for indoor installation and are

More information

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR 5:1 FIRING RATE MODULATION LESS THAN 20 ppm NOx DIRECT VENT FLEXIBILITY TO 100 FEET 96% AFUE

More information

SA 1 INDEX Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R410A...pag. 5 Scroll compressors...pag. 6 Condenser coils...pag. 6 Brazed

More information

SHERPA DHW 75. Th e multifunctional air-water split heat pump. COP > 4 DHW 75 C

SHERPA DHW 75. Th e multifunctional air-water split heat pump. COP > 4 DHW 75 C SHERPA Th e multifunctional air-water split heat pump. PATENTED TECHNOLOGY The combination of an inverter air-water heat pump together with a water-water heat pump allows heating/ and high temperature

More information

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES COOLING CAPACITY FROM 76 TO 612 Kw 1 AND 2 COOLING CIRCUITS RAE 1702 F Kc + P2 28 Above picture is only indicative

More information

Heating and D.h.w. Controller RVL482 Basic Documentation

Heating and D.h.w. Controller RVL482 Basic Documentation Heating and D.h.w. Controller RVL482 Basic Documentation Edition: 1.0 Controller series: A CE1P2542en 20.05.2008 Building Technologies Siemens Switzerland Ltd Building Technologies Group International

More information

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application 1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw PROCESS CHILLERS AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw climaveneta.com PROCESS CHILLERS MAXIMUM EFFICIENCY IN EVERY TYPE OF PROCESS APPLICATION Air cooled liquid chiller for outdoor

More information

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS RAE 1352 F.K + MV AIR R-407C FC Series RAE... F.K Cooling capacity from 77 to 289 kw - 2 circuits The air cooled chillers of RAE... F.K series, are designed for outdoor installation and are particularly

More information

Technical description. Atec.

Technical description. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation AIR-TO-WATER HEAT PUMPS 30RQV 017-021 NEW Nominal cooling capacity 15-18 kw Nominal heating capacity 17-21 kw greenspeed Easy and fast installation Hydronic module available Inverter technology compressor

More information

OLIMPIA SPLENDID S INVERTER DC TECHNOLOGY 100% 80% 70% DC INVERTER AC INVERTER NON INVERTER

OLIMPIA SPLENDID S INVERTER DC TECHNOLOGY 100% 80% 70% DC INVERTER AC INVERTER NON INVERTER SHERP ir-water heat pump COP > 4 DHW 60 C Energy class ErP (1) : RENEWLE TECHNOLOGIES Sherpa uses the heat in the air, and transfers it to system terminals in an efficient manner. For each kw of electricity

More information

High efficiency air to water Heat pumps LZT series

High efficiency air to water Heat pumps LZT series High efficiency air to water Heat pumps LZT series 01/2009 THE COMPANY HIDROS was born in 1993 as a trading company involved in the market of dehumidification and humidification of the air. Quite soon

More information

PRODUCT RANGE HEAT PUMPS 2012

PRODUCT RANGE HEAT PUMPS 2012 PRODUCT RANGE HEAT PUMPS 2012 TABLE OF CONTENTS Product range...4 Heat pump system benefits...6 Is the heat pump considered as a "RENEWABLE SOURCE"?...8 ENERGETIC advantage of the heat pump...10 ECONOMIC

More information

USERS MANUAL FOR GAS BOILERS

USERS MANUAL FOR GAS BOILERS USERS MANUAL FOR GAS BOILERS PLEASE READ THE MANUAL CAREFULLY: IT CONTAINS IMPORTANT INFORMATION REGARDING SAFETY, INSTALLATION, USE AND MAINTENANCE OF THE APPLIANCE MODELS: NOVADENS 24 NOVADENS 24C NOVADENS

More information

BLUEWAY DC INVERTER AIR TO WATER HEAT PUMP

BLUEWAY DC INVERTER AIR TO WATER HEAT PUMP BLUEWAY DC INVERTER AIR TO WATER HEAT PUMP 1 Enjoy comfortable life with BLUEWAY DC Inverter Air to Water Heat Pump is an innovative system of house heating, domestic hot water and even space cooling,

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual Suggestions for the hydraulic integration of chillers and heat pumps Table of Contents From practical experience, for your practical needs...

More information

SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS

SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS INDEX Ed. 20150422 GENERAL INFORMATION... 2 Before installing... 2 Materials and PED (97/23/CE) Standards... 3 SKID-TYPE DISTRICT HEATING

More information

95% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS REMOTE CONNECT CAPABLE CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR

95% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS REMOTE CONNECT CAPABLE CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR CONDENSING RESIDENTIAL GAS BOILERS REMOTE CONNECT CAPABLE CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR 5:1 TURNDOWN RATIO LESS THAN 20 ppm NOx 95% AFUE Efficiency DIRECT VENT

More information

- Data Brochure Universal Reset Module 422

- Data Brochure Universal Reset Module 422 - Data Brochure Universal Reset Module 422 D 422 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler

Bosch. Gas Condensing Boiler. Applications Manual. 100, 151 Combi Boiler 57, 100, 131, 151 Heating Boiler WARNING: Improper installation, setup, modification, operation or maintenance of the heating system can cause personal injury and property damage. Follow each appliances' instructions precisely. For assistance

More information

Mynute Green Condensing Wall-Hung Boilers

Mynute Green Condensing Wall-Hung Boilers Mynute Green Condensing Wall-Hung Boilers Residential Heating Mynute Green The right choice for any installation requirements WIDE RANGE Mynute is available in a wide range of models and outputs, to meet

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE)

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE) INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE) Thank you for choosing a DOMUSA TEKNIK heating boiler. Within the product range offered by DOMUSA TEKNIK you have chosen BioClass

More information

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return Single Zone System One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return Multi Zone System Used in small to medium sized buildings

More information

Process glycol chillers

Process glycol chillers Process glycol chillers The most advanced solutions in refrigeration technology. According to normative EN378 y F-Gas Compact chillers for outdoor installation Natural refrigerant Integrated hydraulic

More information

- Data Brochure Boiler Control 274

- Data Brochure Boiler Control 274 - Data Brochure Boiler Control 274 274_D 03/17 The Boiler Control 274 operates up to four on/off boilers to provide outdoor reset operation, domestic hot water and setpoint operation with priority. When

More information

Power X High Power Condensing Wall-Hung Boilers

Power X High Power Condensing Wall-Hung Boilers Power X High Power Condensing Wall-Hung Boilers NEW Residential Heating/Light Commercial compliant POWER X / High Power Condensing Condensing Wall-Hung Wall-Hung Boilers Boilers Power X: the new high power

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation Edition 1.0 Controller series A CE1P2546en 15.03.2011 Building Technologies Siemens Switzerland Ltd Industry

More information

Parameter guide 95M-200 GAS-FIRED DIRECT VENT MODULATING HOT WATER BOILER WARNING WARNING

Parameter guide 95M-200 GAS-FIRED DIRECT VENT MODULATING HOT WATER BOILER WARNING WARNING 95M-200 GAS-FIRED DIRECT VENT MODULATING HOT WATER BOILER! WARNING Revise boiler control parameters only if you fully understand the purpose and result of the changes and on the advice of ECR Technical

More information

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors -15 C +63 C E.V.I. The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems or

More information

Applications and Piping Strategies for Condensing Boilers - Introduction

Applications and Piping Strategies for Condensing Boilers - Introduction Applications and Piping Strategies for Condensing Boilers - Introduction Foil 2, 10/2015 Viessmann Manufacturing Applications and Piping Strategies for Condensing Boilers Webinar Objectives: 1. Control

More information

PCH Heating Condensing Module for Air Handling and Roof Top Units

PCH Heating Condensing Module for Air Handling and Roof Top Units 40 Years Caring for Environment PCH Heating Condensing Module for Air Handling and Roof Top Units Efficiency as high as 105% Saving Up to 50% on Consumptions Environmentally friendly Efficiency as high

More information

Modular Air-cooled Chillers

Modular Air-cooled Chillers Modular Air-cooled Chillers High Seasonal Efficiency (HSE) version Cooling capacity 48-232 kw Trane Flex Series Modular air/water chillers with axial EC fans, inverter driven scroll compressors and microchannel

More information

GAS ABSORPTION HEAT PUMP

GAS ABSORPTION HEAT PUMP G A H P VV GAS ABSORPTION HEAT PUMP Water Cooled Gas Fired Absorption Heat Pump > Make a choice to build up the future G A H P VV GAS ABSORPTION HEAT PUMP WATER COOLED GAS FIRED ABSORPTION HEAT T PUMP

More information

Chiller units and air-water heat pumps RANGE OPERATING LIMITS

Chiller units and air-water heat pumps RANGE OPERATING LIMITS Chiller units and air-water heat pumps Cooling capacity: Heating capacity: 6, to 6,6 kw 8, to 69,4 kw ENVIRONMENTALLY FRIENDLY HFC R407C PROTECTION DE L'ENVIRONNEMENT Silent and compact design Air-conditioning

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

FREQUENTLY ASKED QUESTIONS

FREQUENTLY ASKED QUESTIONS HEAT PUMP INVERTER R-410A All-in-one, all year round heating, cooling and domestic hot water supply solution FREQUENTLY ASKED QUESTIONS WANT TO KNOW MORE? AVERAGE ANNUAL CO 2 EMISSIONS Daikin Altherma

More information

Elegance and design for your residential comfort

Elegance and design for your residential comfort Elegance and design for your residential comfort between elegance, comfort and energy savings Conceived to make every kind of residential environment more comfortable, the new i-life Slim fan coil integrates

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

Enhance the performance of every system

Enhance the performance of every system professional controls for underfloor heating Enhance the performance of every system FLOOR HEATING HYDRONIC FLOOR HEATING ELECTRIC HVAC CONTROLS & POWER OJ Waterline 3 RD GENERATION WATERBASED UNDERFLOOR

More information

PAC BT LOW TEMPERATURE HEAT PUMP WITH DHW TANK INCLUDED

PAC BT LOW TEMPERATURE HEAT PUMP WITH DHW TANK INCLUDED PAC BT LOW TEMPERATURE HEAT PUMP WITH DHW TANK INCLUDED Just feel well Renewable Energy MADE IN EUROPE A ++ + PRODUCTS High efficiency: ηs %. High flexibily due to DC Inverter compressor: operation optimised

More information

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING

More information

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

1 DOCUMENT REVISION CONTROL ELEMENTS... 9 CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11

More information

Also available with the new i-life R-Slim inverter and radiant panel version. Perfect comfort. Silent operation. Real energy savings

Also available with the new i-life R-Slim inverter and radiant panel version. Perfect comfort. Silent operation. Real energy savings The new i-life Slim fan coil, with inverter technology for heating, cooling and dehumidifying. Its elegant design with only 13 cm depth makes i-life Slim the perfect solution for residential applications.

More information

NABILATON PRO. The Nabilaton Pro heat pumps consist of MDV brand outdoor units and suitable hydraulic modules from Nabilaton.

NABILATON PRO. The Nabilaton Pro heat pumps consist of MDV brand outdoor units and suitable hydraulic modules from Nabilaton. NABILATON PRO NABILATON PRO KIT The Nabilaton Pro heat pumps consist of MDV brand outdoor units and suitable hydraulic modules from Nabilaton. INVERTER TECHNOLOGY Increasing the compressor motor rotation

More information

- Data Brochure Universal Reset Module 423

- Data Brochure Universal Reset Module 423 - Data Brochure Universal Reset Module 423 D 423 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT DOC1066 GB STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 08707 707 747 FAX: 08707 707 767 E-MAIL:info@stokvisboilers.com

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM Thank you for choosing a DOMUSA TEKNIK heating boiler. Within the product range offered by DOMUSA TEKNIK you have chosen BioClass HM model. With a suitable

More information

solar thermic system Solar thermic systems are devices that allow you to capture and store solar energy for later use in various utilization.

solar thermic system Solar thermic systems are devices that allow you to capture and store solar energy for later use in various utilization. Solar thermic systems are devices that allow you to capture and store solar energy for later use in various utilization. If you are using the Sun's heat to produce electricity it comes to solar photovoltaic.

More information

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall. Chapter 4 Variable-speed pumps. A variable-speed pump varies the flow rate by maintaining a constant pressure differential as zone valves open and close. A sensor measures the difference in pressure between

More information

Outdoor Reset Control Theory FULL versus PARTIAL reset

Outdoor Reset Control Theory FULL versus PARTIAL reset Outdoor Reset Control Theory FULL versus PARTIAL reset Conventional boilers must be protected against sustained operation at low temperatures. If not, they will be damaged by sustained flue gas condensation.

More information

96.2% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS CON X US REMOTE CONNECT. MODBUS AND BACnet MSTP PROTOCOL

96.2% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS CON X US REMOTE CONNECT. MODBUS AND BACnet MSTP PROTOCOL HIGH EFFICIENCY COMMERCIAL BOILERS CON X US REMOTE CONNECT MODBUS AND BACnet MSTP PROTOCOL CASCADING SEQUENCER WITH CASCADE REDUNDANCY 6 INPUTS FROM 750,000 TO 2.0 MILLION BTU/HR UP TO 25:1 TURNDOWN RATIO

More information

Heat Pump Technology. Air Source, Water Source and Ground Source. Optimised heat pumps for residential and commercial applications

Heat Pump Technology. Air Source, Water Source and Ground Source. Optimised heat pumps for residential and commercial applications Heat Pump Technology Air Source, Water Source and Ground Source Optimised heat pumps for residential and commercial applications ICS Cool Energy Limited has nearly 25 years experience in supplying and

More information

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS David Grassl PE Mechanical Engineer Principal Similar to traditional boiler systems, condensing boiler systems have many designs they can operate

More information

LZT High efficiency air to water heat pumps with E.V.I. compressors

LZT High efficiency air to water heat pumps with E.V.I. compressors High efficiency air to water heat pumps with E.V.I. compressors -20 +43 +65 E.V.I..O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems

More information

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS Indoor motor-driven evaporating units LER 0-0 kw Compact and silent machines with remote dissipation into the air Scroll compressor PLUS R-0A R-0A refrigerant Cooling only Split version Electronic expansion

More information

SYSTEM DESIGN REQUIREMENTS

SYSTEM DESIGN REQUIREMENTS P a g e 1 SYSTEM DESIGN REQUIREMENTS WFC-S SERIES WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLERS / CHILLER-HEATERS Yazaki WFC-S Series water-fired chillers and chiller-heaters are available with nominal

More information

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602* User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled

More information