Performance Evaluation Of A Vapour Compression Refrigeration System For Simultaneous Cooling And Heating By Using R22 And Alternative Refrigerants
|
|
- Jocelin Hopkins
- 5 years ago
- Views:
Transcription
1 Performance Evaluation Of A Vapour Compression Refrigeration System For Simultaneous Cooling And Heating By Using R22 And Alternative Refrigerants Rahul P Patel (PG student, SVM Institute of technology Bharuch, Gujarat) Dr. R. G. Kapadia (Principal, SVM Institute of technology Bharuch, Gujarat ) Abstract This research paper presents a vapour compression refrigeration (VCR) system for simultaneous heating and cooling utilities for different purpose in industries, hotels. The main advantage of the simultaneous is to carry out heating and cooling in dual mode, by which fossil fuel can be saved by minimize the use of the energy due to simultaneous operation. And even due to simultaneous operation the requirement individual equipment is no more so it saved the first cost of equipment. For research work water cooled condenser and evaporator is used. In which water flow rate is varied and test was conducted in three different modes by using R22 and its alternative refrigerants like R134a, R407C, R410A in existing system without replacing any parts of the system. Experimental results show that R134a has good performance than R22 and performance of R407 is in same manner as R Introduction In today s era, refrigeration industry is passing through evolutionary changes. Emphasis is given to save energy and to protect the environment. Refrigeration technology is expected to develop technologies which are cheap and using refrigerant other than CFC. Many food industries, textiles industries, hotels require both refrigeration and water heating. In case of textile mill, it requires central air conditioning plant which requires chilled water and hot water for steam generation and heating purpose, while in food industries, refrigeration required for product preservation and hot water required for cleaning, sterilization or process heating. It is common for the refrigeration and water heating systems to be separate and unconnected, and both consuming purchased energy. This approach wastes considerable energy, contributing to the depletion of fossil fuel reserves and the release of greenhouse gases. Even in large size VCR system required condenser and cooling tower for condensation process, while by simultaneous heating and cooling requirement of cooling tower is no more. So by the simultaneous heating and cooling by VCR system save the fossil fuel, energy and first cost of system/equipment by serving the both function of heating and cooling simultaneously. In addition, many refrigeration systems employ ozone depleting refrigerants. There are strong international moves to use naturally occurring and ecologically safe working fluids rather than harmful chemicals, in order to minimize the impact on the environment. Alternative technologies are required to limit the economic cost and environmental impact of these applications.[11] According to the Montreal Protocol and its subsequent amendments and regional regulations, CFCs (chlorofluorocarbons) are banned since 1996 and the phase-out deadlines for HCFCs (hydro chlorofluorocarbons) are approaching (2030). Consequently, new fluids with zero ozone depleting potential (ODP), such as HFCs (hydro fluorocarbons) and natural refrigerants are being tested as substitutes for the ODSs. HCFC-22 has been widely used as working fluid in air conditioning and in medium and low-temperature applications within the commercial and industrial refrigeration. Nowadays, the replacement of HCFC-22 in existing and new systems without significant changes in equipment or lubricants constitutes a crucial challenge for the refrigeration industry. [19] The first objective of the VCR system is to produce cooling effect, with the simultaneous mode heating and cooling energies can produce using the same electric energy input at the compressor. Hoon Kang [2] evocate a significant reduction in carbon footprint using improved heat pumps for heating and cooling. Many authors work on such systems for simultaneous production in various applications. Liu and Hong [3] compare ground source heat pumps to variable refrigerant flow systems, both able to provide heating and cooling effect to four perimeter zones and one core zone of a simulated small office building. White SD. [1] expose the advantageous performance of a transcritical CO 2 heat pump for simultaneous refrigeration and water heating. Past studies indicate that carbon dioxide based systems have great potential in two sectors in mobile air conditioning and in heat pumps for simultaneous 1809
2 cooling and heating. Several authors deal with the R22 replacement issues. R.Cabello et al.[10] tested 134a,R407C as alternative of R22 in a VCR system and W. Chen [6] has also replaced R22 with R410A in a heat pump. Tun-Ping et al. [15] compares the performance of R22 with R290 as a alternative of R22 in window air conditioner. Nomenclature (Ẇ, kw), refrigerating effect (Q k, kw) and Coefficient of Performance (COP). Fig. 2 shows a schematic diagram of a vapour compression refrigerator, which consists essentially of a hermetic reciprocating compressor, an evaporator, a condenser and a capillary tube. These components are connected by pipelines in which a refrigerant with suitable thermodynamic properties circulates. COP coefficient of performance Cp specific heat at constant pressure (kj/kg K) h enthalpy (kj/kg) ṁ mass flow rate (kg/s) Ẇ compressor electrical power consumption (kw) P pressure (bar) Q k heat absorbed (kw) Q o heat rejected (kw) s entropy (kj/kg K) T temperature ( C) Subscripts 0 evaporator k condenser wi water inlet wo water outlet ci condenser inlet co condenser outlet ei evaporator inlet eo evaporator outlet In this paper, attention has been focused on studying, from an experimental point of view, utilize the waste heat from the condenser by simultaneous mode and how operating variables affect the performance of a refrigeration plant when using R134a, R407C, R410A and R22 as working fluids. The rest of the paper is organized as follows. In section 2, the theoretical analysis is described. In Section 3, the refrigeration test facility used to obtain the experimental data is described.. In Section 4, the experimental results are presented and discussed via heating and cooling effect and the COP analysis. Finally, in Section 5, the main conclusions of the paper are summarized. Fig. 1 Vapour compression refrigeration system on p-h diagram Fig.2 Schematic diagram of VCR system The rate of heat absorbed by evaporator is given by Q k = ṁ(h 1 h 4 ) 2. Theoretical analysis The overall performance of the plant is determined by evaluating its COP, calculated as the ratio between refrigerating capacity and electrical power supplied to the compressor. The p-h diagram shown in Fig. 1 is frequently used in the analysis of vapour compression refrigeration cycle. In the refrigeration system, the representative performance characteristics are compressor power The rate of heat rejected by condenser is given by Q 0 = ṁ(h 2 h 3 ) Compressor power consumption is given by Ẇ = ṁ(h 2 h 1 ) 1810
3 Coefficient of performance for cooling COP cooling = Q k Ẇ COP cooling = h 1 h 4 h 2 h 1 Coefficient of performance for heating COP heating = Q o Ẇ COP heating = h 2 h 3 h 2 h 1 Second law efficiency of vapour compression cycle η II = Minimum available energy required for the cycle Actual available energy consumed in the cycle η II = COP COP Carnot COP carnot = T o T k T o 4) Evaporator outlet temperature ( C) 5) Condenser inlet pressure (bar) 6) Evaporator inlet pressure (bar) 7) Evaporator outlet pressure (bar) After it in existing system without any replacement or modification of any parts in system R22 is replaced by R134 after it with R407C and R410A. Compressor used in system is fabricated by Kirloskar(KCJ513HAE) for R22 only. So to replace it with other refrigerant the amount of refrigerant was changed. Approximately charged amount of refrigerant are R gm, R134a 600gm, R407C-400gm, R410A-300gm. 3. Experimental Study 3.1 Experimental setup The experiment was carried out in fabricated test rig in which tube-tube heat exchanger is used for evaporation and condensation process. Reciprocating compressor of 1 ton capacity is used in test rig. with the capillary tube as a expansion device. The system was instrumented with three pressure gauges at the inlet and outlet of the evaporator and inlet of compressor for measuring the suction and discharge pressures. The temperature of the refrigerant at eight different points as indicated in Fig. 3 was measured with copper-constantan thermocouples. 3.2 Data analysis Test was conducted by varying the water flow rate through water cooled condenser and evaporator in three different modes. In first mode, water flow rate through evaporator is kept constant (2 LPM) while flow rate through condenser is varied from 2 LPM to 10 LPM, in second mode condenser water flow rate is kept constant (2 LPM) and evaporator water flow rate is varied from 2 LPM to 10 LPM, in third mode water flow rate through both condenser and evaporator are varied from 2 LPM to 10 LPM. The thermodynamic properties of refrigerants are evaluated using COOL PACK. The heating effect and cooling effect produced by VCR system is calculated as follows; heating effect = ṁ C p (T wo T wi ) cooling effect = ṁ C p (T wi T wo ) Following parameters are measured during the test 1) Condenser inlet temperature ( C) 2) Condenser outlet temperature ( C) 3) Evaporator inlet temperature ( C) Fig. 3 Schematic diagram of test rig. Of VCR system 4. Results and discussion The variation of the actual coefficient of performance with the condenser water flow rate changing from 2 LPM to 10 LPM and evaporator water flow rate is at constant (2 LPM) is as described in Fig.2. As water flow rate is increase the COP of the VCR system is increase. At 10 LPM condenser water flow rate system performance is maximum. This is due to an increase of the heat exchanger overall heat transfer coefficient that resulting too high for the evaporation power fixed, determines an increase of the evaporation pressure, a decrease of the compression ratio and of the compression work and so an increase of the COP. 1811
4 Fig. 2 Effect of water flow rate on COP (evaporator water flow rate constant) While the effect on COP by keeping the condenser water flow rate constant and by varying evaporator water flow rate is depicted in Fig.3 As the water flow rate change from 2 LPM to 10 LPM, COP of system is increase. This is due to as the water flow rate is decrease it decrease the refrigerating effect and power required to run the compressor is increase. The performance of VCR system varies considerably with both vaporizing and condensing temperature. As the condenser water flow rate is increase, the condensing temperature decrease and COP of the system is improved as described in Fig.3. Fig. 5 Effect of water flow rate on heating effect (kw) (evaporator water flow rate constant) Fig. 6 Effect of water flow rate on heating effect (kw) (condenser water flow rate constant) Fig. 3 Effect of water flow rate on COP (condenser water flow rate constant) Fig. 4 Effect of water flow rate on COP (both water flow rate varying) Fig. 7 Effect of water rate on heating effect (kw) (both water flow rate varying) It is seen that the capacity and performance of the refrigerating system improve as the vaporising temperature increase and the condensing temperature decrease. And the performance of R134a is better than R22 in existing system during all three mode, while performance of R407C and R410A is better but less than R22 as depicted in Fig.2, 3,
5 For experimental work tube-tube heat exchanger is used in which three tube is used which one is in contact with each tube by thermal bonding material (tin). In it middle tube is carried refrigerant while remaining two tube carried water. Fig. 11 Effect of water flow rate on second law efficiency (evaporator water flow rate constant) Fig. 8 Effect of rate on cooling effect (kw) (evaporator water flow rate constant) Fig. 9 Effect of water flow rate on cooling effect (condenser water flow rate constant) Fig. 12 Effect of water flow rate on second law efficiency (condenser water flow rate constant) Fig. 13 Effect of water flow rate on second law efficiency (both water flow rate varying) Fig. 10 Effect of water flow rate on cooling effect (both water flow rate varying) During the minimum water flow rate through condenser maximum heating effect and during the minimum water flow rate through evaporator maximum cooling effect can be achieved. As shown in fig. 6, 8. And by utilising waste heat from the condenser overall performance of VCR system is increasing. The ideal Carnot cycle is completely reversible, it does not involve any irreversibilities. The vapour compression cycle involves internal irreversibilities due to the throttling process and also due to the superheat horn. Hence, the value of second law efficiency (η II ) is less than 1. Second law efficiency is indication of closeness of actual cycle to Carnot cycle. The actual vapour compression cycle would have the external irreversibilities of condensation and evaporation process due to finite temperature differences required for heat transfer.[20] As water flow rate is increase it decrease the condenser pressure and due to which Carnot COP and actual 1813
6 COP is increase due to which as water flow rate increase second law efficiency also increase, as depicted in fig.11, 12, Conclusion Due to simultaneous heating and cooling energy can be saved and also first cost of equipment. As water flow rate increase in evaporator (condenser water flow rate at minimum level) 26 % heating effect is increase while as condenser water flow rate increase (evaporator water flow rate at minimum level) 20 % cooling effect is increased by R407C. Replacement of R22 in existing system with R134a, R407C, R410A shows that R22 has higher heating and cooling effect than other refrigerant. Performance of R134a is better in system as compare remaining three refrigerant. COP of the system is increase 20% by replacing R22 with R134a and decreasing 10% with R407C and R410A with 18% so R134a is most promisible alternative refrigerant. References [1] S D White, D J Cleland, S D Cotter, R A Stephenson, R D S Kallu, A K Fleming, A heat pump for simultaneous refrigeration and water heating IPENZ Transactions,1997; 24: [2] Hoon Kang, Youngju Joo, Hyunjoon Chung, Yongchan Kim, Jongmin Choi Experimental study on the performance of a simultaneous heating and cooling multi-heat pump with the variation of operation mode international journal of refrigeration, 2009; article in press:1-8. [3] Liu, Hong Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Energy and Buildings, 2010; 42 : [4] J. Sarkar, Souvik Bhattacharyya, M. Ram Gopal, Optimization of a transcritical CO2 heat pump cycle for simultaneous cooling and heating applications International Journal of Refrigeration, 2004; 27: [5] A.M. Foster, T. Brown, A.J. Gigiel, A. Alford, J.A. Evans, Air cycle combined heating and cooling for the food industry International Journal of Refrigeration, 2011; 34: [6] Paul Byrne, Jacques Miriel, Yves Lenat, Design and simulation of a heat pump for simultaneous heating and cooling using HFC or CO2 as a working fluid International Journal of Refrigeration, 2009; 32: [7] W. Chen, A comparative study on the performance and environmental characteristics of R410A and R22 residential air conditioners Applied Thermal Engineering, 2008; 28: 17. [8] M.Ashok Chakravarthy, M.L.S.Deva Kumar, Experimental investigation of an alternate refrigeration for R22 in window air conditioning system international journal of scientific and research publication, 2012; 2: [9] Mark W. Spatz, Samuel F. Yana Motta, An evaluation of options for replacing HCFC-22 in medium temperature refrigeration systems International Journal of Refrigeration, 2004; 27: [10] R.Cabello, E.Torrella, J.Navarro-Esbr, Experimental evaluation of a vapour compression plant performance using R134a, R407C and R22 as working fluids Applied Thermal Engineering, 2004; 24 : [11] Vincenzo La Rocca, Giuseppe Panno, Experimental performance evaluation of a vapour compression refrigerating plant when replacing R22 with alternative refrigerants Applied Energy, 2011; 88: [12] M. Fatouh, Talaat A. Ibrahim, A. Mostafa, Performance assessment of a direct expansion air conditioner working with R407C as an R22 alternative Applied Thermal Engineering, 2010; 30: [13] Jianyong Chen, Jianlin Yu, Performance of a new refrigeration cycle using refrigerant mixture R32/R134a for residential airconditioner applications Energy and Buildings 2008; 40: [14] S. Karagoz, M. Yilmaz, O. Comakli, O. Ozyurt, R134a and various mixtures of R22/R134a as an alternative to R22 in vapour compression heat pumps Energy Conversion and Management, 2004; 45: [15] Tun-Ping Teng, Huai-En Mo, Hung Lin, Yuan-Hong Tseng, Ren-Hao Liu, Yu-Fan Long, Retrofit assessment of window air conditioner Applied Thermal Engineering 2012; 32:
7 [16] Anderson johansson Replacement of R22 in existing system International Journal of Refrigeration, 2011; 34: [17] B. Hadya, P. Usha Sri and Suresh Akella, Comparative Study of Eco-friendly Refrigerants in a Lower Capacity Air- Conditioning System International Conference on Mechanical and Automotive Engineering, 2012: [18] Milind V. Rane, Madhukar S. Tandale, Water-to-water heat transfer in tube tube heat exchanger: Experimental and analytical study Applied Thermal Engineering, 2005; 25: [19] Ozone cell,ministry of environment and forests, Roadmap for phase out of HCFCs in india, Government of india. [20] A text book on Refrigeration and air conditioning by C P Arora. [21] A text book on Refrigeration and air conditioning by R K Rajput. [22] A text book on Heat exchangers by Sadik Kakac, Hongtan Liu. [23] IPU and Department of Mechanical Engineering Technical University of Denmark CoolPack
Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures
Experimental Study on Performance Parameters for Refrigerants, R41a and R44a at Various Air Outlet Temperatures P. Nagaraju P. G. Student Sanketika Institute of Technology and Management Ch. Kiran Kumar
More informationExperimental investigation on the performance of air conditioner using R32 Refrigerant
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 12, Issue 4 Ver. V (Jul. - Aug. 2015), PP 139-144 www.iosrjournals.org Experimental investigation
More informationIJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December
Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser
More informationNUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A
ISSN: 2250-0138 (Online) NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A RANENDRA ROY a1, MADHU SRUTHI EMANI b AND BIJAN KUMAR MANDAL c abc Department
More informationInternational Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:
Comparison of Second Law Efficiency and Exergy Analysis of Refrigerants R-12, R-22, R-407C Influenced by Evaporator Temperature for Vapour Compression Refrigeration System Md Ozair Arshad Guest Faculty,
More informationVolume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation
Methods for Improving Thermodynamic Energy and Exergy Performance of Vapour Compression Refrigeration Systems using Thirteen Ecofriendly Refrigerants in Primary Circuit and TIO 2 Nano Particles Mixed with
More informationThermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23
Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23 A. D. Parekh, P. R. Tailor Abstract The Montreal protocol and Kyoto protocol underlined the need of substitution
More informationRole of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview
International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationIR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT
Proceedings of the International Conference on Mechanical Engineering and Renewable Energy 217 (ICMERE217) 18 2 December, 217, Chittagong, Bangladesh ICMERE217-PI-48 IR-REVERSIBILITY ANALYSIS OF A SPLIT
More informationEffect of capillary diameter on the power consumption of VCRS using different refrigerants
Effect of capillary diameter on the power consumption of VCRS using different refrigerants Dr. A. G. Matani 1, Mukesh K. Agrawal 2 1 Asso. Professor, Mechanical Engineering Department, Govt. College of
More informationNUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A
NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A [1] Ranendra Roy, [2] Madhu Sruthi Emani, [3] Bijan Kumar Mandal [1], [2],[3] Department of Mechanical
More informationPerformance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants
Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants CHENNUCHETTY CHINNARAJ * Associate Professor in Mechanical Engineering, Government College of
More informationSubscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid
Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance
More informationEXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM
EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Prof. S.V.Rao 1, Hitesh Sharma 2, Pankaj Kumar Gound 3, Tukaram Walgude 4, Shekhar Gavas 5 1 Prof.
More informationA Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant
International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article A Review
More informationStudy of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants
International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Study
More informationPerformance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS
Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS Lalit Narayan, Abhishek Arya 2,2 M. Tech. Scholar, Associate Professor,,2 Scope College of Engineering, Bhopal, India Abstract: The
More informationAN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS
AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore
More informationVolume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation
Volume 6, Issue 3(201)199-204 ISSN 2347-325 Comparative Performance Evaluation of Vapor Compression Refrigeration System for drop-in Replacement of R22 Vaibhav Jain *, Dhruva Gupta, Himank Gupta, Anirudh
More informationComparative Exergy Analysis of Vapor Compression Refrigeration System Using Alternative Refrigerants
Comparative Exergy Analysis of Vapor Compression Refrigeration System Using Alternative Refrigerants Gulshan Sachdeva, Vaibhav Jain Abstract In present paper, the performance of various alternative refrigerants
More informationη second law = Second law efficiency
EXERGY ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION CYCLE BASED AUTOMOTIVE AIR CONDITIONER USING ECO FRIENDLY REFRIGERANTS Vijender Singh Saini 1, Balvinder 2, Pardeep Kumar 3 1 M.Tech Scholar, 2,3 Assistant
More informationASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER
University of Maiduguri Faculty of Engineering Seminar Series Volume 6, december 5 ASSESSMENT OF REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R34A REFRIGERANT IN LARGE CAPACITY FREEZER S. Shodiya*, M.B. Oumarou
More informationChapter 10. Refrigeration and Heat Pump Systems
Chapter 10 Refrigeration and Heat Pump Systems Learning Outcomes Demonstrate understanding of basic vaporcompression refrigeration and heat pump systems. Develop and analyze thermodynamic models of vapor-compression
More informationExperimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 14, Issue 1 Ver. V (Jan. - Feb. 2017), PP 75-82 www.iosrjournals.org Experimental Evaluation of
More informationEXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)
EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) Abstract- With the recent government regulations, of banning the ozone depleting substances and Kyoto protocol
More informationEXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE
Karthikeyan, K. et al.: Experimental Investigations on Automobile Air S515 EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE by Karthikeyan
More informationWORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM
WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM Sachin Kumar 1, Vicky Ranga 2 1Assistant Professor, Department of Mechanical Engineering, Jagan Nath University Jhajjar, Haryana, India. 2Scholar.
More informationDEEPAK PALIWAL, S.P.S.RAJPUT
International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-15 623 EXPERIMENTAL ANALYSIS OF HYDROCARBON MIXTURES AS THE NEW REFRIGERANT IN DOMESTIC REFRIGERATION SYSTEM DEEPAK PALIWAL,
More informationVolume 2, Issue 1 (2014) ISSN International Journal of Advance Research and Innovation
Methods for Improving First and Second Law Efficiencies of Vapour Compression Refrigeration Systems Using Flash-Intercooler with Ecofriendly Refrigerants Kapil Chopra *, V. Sahni, R. S. Mishra Department
More informationAvailable online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 109 (2017 ) 56 63 International Conference on Recent Advancement in Air Conditioning and Refrigeration, RAAR 2016, 10-12 November
More informationImproving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a
ISSN (e): 0 00 Vol, 0 Issue, 8 August 0 International Journal of Computational Engineering Research (IJCER) Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants
More informationInternational Journal of Advance Engineering and Research Development
Scientific Journal of Impact Factor(SJIF): 3.134 e-issn(o): 2348-4470 p-issn(p): 2348-6406 International Journal of Advance Engineering and Research Development Volume 02,Issue 06, JUNE -2015 COMPARATIVE
More informationPERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS
RIO 3 - World Climate & Energy Event, 1-5 December 23, Rio de Janeiro, Brazil 275 PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS G. Venkatarathnam, V. Ravindranatha
More informationEVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22
EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22 Ameya P. Shrivastava 1, Choudhari Chandrakishor S. 2 1,2 Mechanical Department, AISSMS College of Engineering, Pune 411001, (India) ABSTRACT HCFC
More informationA COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A
,, IJAET International Journal of Application of Engineering and Technology ISSN: 33 Vol No. A COMPARATIVE STUDY FOR RETROFITTING OF R VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO FRIENDLY REFRIGERANTS
More informationU.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India
DESIGN OF HYBRID AIR COOLER USING VAPOUR COMPRESSION REFRIGERATION SYSTEM Vimalkirti Shende 1, Sushil Borkar 2, Touseef Iqbal Qureshi 3 Asst. Prof. Nikhil Bhende 1 1,2,3 U.G. Student, Department of Mechanical
More informationExperimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator
Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Dr. R. A. Kathar 1, S. D. Surushe 2 1 Associate Professor, Mechanical
More informationThermodynamics I. Refrigeration and Heat Pump Cycles
Thermodynamics I Refrigeration and Heat Pump Cycles Dr.-Eng. Zayed Al-Hamamre 1 Content Introduction The Reversed Carnot Cycle The Ideal Compression Refrigeration Systems Deviation from the ICRS Selection
More informationPERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS
Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK
More informationPerformance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant
International Journal of Scientific and Research Publications, Volume 4, Issue 7, July 2014 1 Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170
More informationTYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP
TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP Paul Maina and Zhongjie Huan mainap@tut.ac.za and huanz@tut.ac.za Department of Mechanical Engineering, Tshwane University of Technology P.O Box Private Bag X680
More informationExperimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering
IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Experimental performance evaluation of heat pump by using CO 2 as a refrigerant To cite this article: V K Venkatesh et al 2016
More informationStudy of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator
Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator Mr. Subodh S. Deshpande Department of Mechanical Engineering M.G.M.s College of Engineering
More informationPart load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants
454 Journal of Scientific & Industrial Research Vol. 72, July 2013, pp. 454-460 Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants P. Thangavel 1* and
More informationEvaluation of Vapour Compression Refrigeration System Using Different Refrigerants
Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Mukesh K. Agrawal, Dr. Ashok G. Matani Abstract- The performance of heat transfer is one of the most important research
More informationDesign of LPG Refrigeration System
Design of LPG Refrigeration System Sethu Sathayan 1, Gopakumar M G 2, Jaya Krishnan S 3, Nanda Gopan 4, Nithin S 6 Assistant Professor, Department of Mechanical Engineering, SNIT Adoor, Kerala, India 1
More informationThermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate
International Journal of Research in Engineering and Innovation (IJREI) Vol-1, Issue-2, (2017), 49-53 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationCHAPTER 1 INTRODUCTION
CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties
More informationThermodynamic Cycle Analysis of Mobile Air Conditioning System Using HFO-1234yf as an Alternative Replacement of HFC-134a
Thermodynamic Cycle Analysis of Mobile Air Conditioning System Using HFO-1234yf as an Alternative Replacement of HFC-134a Jignesh Gohel, Dr. Ragesh Kapadia 1 Head, Mechanical Engineering Department, Aditya
More informationExperimental Investigation of Hot water Fired R134A-DMAC VARS System at Various Heat Source Temperatures
Journal of Energy Research and Environmental Technology pp. 20-25 Krishi Sanskriti Publications http://www.krishisanskriti.org/jeret.html Experimental Investigation of Hot water Fired R134A-DMAC VARS System
More informationAnalysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant
Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET
More informationLow GWP Refrigerants for Air Conditioning Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta
More informationA Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration
ANALELE UNIVERSITĂłII EFTIMIE MURGU REŞIłA ANUL XXI, NR. 1, 2014, ISSN 1453-7397 Feiza Memet A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration
More informationEXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER
EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional
More informationA Review on selecting an Eco-friendly Refrigerant alternate to R134a in Domestic Refrigerators
A Review on selecting an Eco-friendly Refrigerant alternate to in Domestic Refrigerators V. Manoj 1, V. Balamurugan 2, B. Senthil Kumar 3 1 PG Scholar (Thermal Engineering), 2, 3 Assistant Professor 1,
More informationEXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS
International Journal of Scientific & Engineering Research Volume 3, Issue 7, July-2012 1 EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS Rahul ukey, Sharad chaudhary Abstract Electricity
More informationInternational Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]
Experimental Investigation To Develop The Refrigeration System With Two Phases Condensing Ejector Along With Energy Saving Anjani Kumar 1, Kuldip Kumar 2, Ujjwal Kumar Nayak 3 123 Department of mechanical
More informationPERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT
PERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT Binit Kumar Jha 1, Neelam Khandelwal 2, Prateek Singh 3, Nishtha Chaudhary 4, Hasan Ali 5 1 Professor and Head, 2 Assistant Professor, 3,4, Student
More informationTheoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator
Theoretical performance evaluation of R34a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator Chintankumar B. Lad, 2 Dr. Ragesh G. Kapadia M.E. Student, 2 Principal Thermal Engineering,
More informationCHAPTER 1 INTRODUCTION
1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,
More informationPerformance investigation of Air-conditioning system using ejector as expansion device
International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Performance
More informationCapillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning
Journal of Physics: Conference Series PAPER OPEN ACCESS Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning To cite this article: Putu Wijaya Sunu et
More informationKeywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.
Comparative performance analysis of Refrigeration Test RIG for R-12 & R-134a Parmesh 1, Mr. Amit Sharma 2 1 M.Tech. Scholar, Department of Mechanical Engineering, 2 Assistant Professor, Department of Mechanical
More informationPerformance Assessment of Three Eco-Friendly Hydro-Fluorocarbon and Hydrocarbon Refrigerant Mixtures as R22 Alternatives in Refrigeration Systems
Middle-East Journal of Scientific Research 23 (8): 1677-1684, 2015 ISSN 1990-9233 IDOSI Publications, 2015 DOI: 10.5829/idosi.mejsr.2015.23.08.22299 Performance Assessment of Three Eco-Friendly Hydro-Fluorocarbon
More informationOptimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf
Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf Gaurav #1, Raj Kumar* 2 1# Research Scholar, Department of Mechanical Engineering,
More informationInternational Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (www.rdmodernresearch.
COMPARATIVE STUDY OF R600a AND BLENDS OF (R600a /R1270) AS DOMESTIC REFRIGERANTS M. Ramesh Kumar*, S. Siva Subramanian**, R. Arun Kumar*** & A. Sankara Narayana Murthy**** Department of Mechanical Engineering,
More informationA Comparison Between Refrigerants Used In Air Conditioning
A Comparison Between Refrigerants Used In Air Conditioning Derya Özkan, Özden Agra and Özlem Çetin University of Yildiz Technical University, Turkey Corresponding email: tumer@yildiz.edu.tr SUMMARY It
More informationADVANCES in NATURAL and APPLIED SCIENCES
ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-0772 Published BY AENSI Publication EISSN: 1998-1090 http://www.aensiweb.com/anas 2016 Special10(7): pages 112-122 Open Access Journal The Effect Of
More informationEnhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System
Enhancement of COP by Using Spiral and Microchannel instead of conventional of VCR System 1 P.G. Lohote, 2 Dr.K.P. Kolhe. 1 P.G. Student, 2 Professor. 1,2 Department of Mechanical Engineering, JSPM s,
More informationISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015
Page77 Page78 COMPARATIVE ANALYSIS OF PERFORMANCE OF OZONE-FRIENDLY AND LOW GWP HFC REFRIGERANT IN A VAPOUR COMPRESSION REFRIGERATION CYCLE Kashid Hari T. 1,Khatpe Akshay R 1,Khile Parshuram N 1,Ligade
More informationPressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C
drop analysis of evaporator using refrigerants R-22, R-404A and R-407C #1 Pallavi Sawkar, #2 Dr. Pradeep Patil #12 Department of Mechanical Engineering, JSPM s JSCOE, Savitribai Phule Pune University,
More informationA study of Transient Performance of A Cascade Heat Pump System
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 79 (2015 ) 131 136 2015 International Conference on Alternative Energy in Developing Countries and Emerging Economies A study of
More informationEnvironment Protection Engineering
Environment Protection Engineering Vol. 38 212 No. 4 DOI: 1.5277/EPE1244 BUKOLA OLALEKAN BOLAJI*, ZHONGJIE HUAN* COMPUTATIONAL ANALYSIS OF THE PERFORMANCE OF OZONE-FRIENDLY ALTERNATIVE REFRIGERANTS IN
More informationAssessment of LPG as a possible alternative to R-12 in domestic refrigerators
Energy Conversion and Management 44 (2003) 381 388 www.elsevier.com/locate/enconman Assessment of LPG as a possible alternative to R-12 in domestic refrigerators Bilal A. Akash a, *, Salem A. Said b a
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical
More informationInternational Journal of Informative & Futuristic Research ISSN (Online):
Reviewed Paper Volume 2 Issue 9 May 2015 International Journal of Informative & Futuristic Research ISSN (Online): 2347-1697 Performance Comparison of R22 and R290 Refrigerants Using Smaller Paper ID IJIFR/
More informationEffects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling
ISSN 2395-1621 Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling #1 Mr. Sachin Das, #2 Prof. M. V. Khot #1 Student, Mechanical
More informationRefrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology
Refrigeration Cycles MOHAMMAD FAISAL HAIDER LECTURER Department of Mechanical Engineering Department of Mechanical Engineering Bangladesh University of Engineering and Technology Objectives Introduce the
More informationDesign & Fabrication of Hybrid Cooler
IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 11 April 2016 ISSN (online): 2349-6010 Design & Fabrication of Hybrid Cooler Shashank Chauragade Mukul Kshirsagar
More informationIJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY PERFORMANCE ANALYSIS OF AIR COOLED WATER COOLER BY USING ECO- FRIENDLY REFRIGERANTS AS A POSSIBLE SUBSTITUTE OF R134A Gaurav Gupta*,
More informationStudy of R161 Refrigerant for Residential Airconditioning
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen
More informationA Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes
ISSN 2395-1621 A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes #1 N. Dhekale, #2 Dr. P. A. Patil 1 amardhekale@gmail.com #12 Research Laboratory, Department
More informationUse of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion
International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018), 201-208 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationAustralian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator
ISSN:1991-8178 Australian Journal of Basic and Applied Sciences Journal home page: www.ajbasweb.com Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator 1
More informationOyelami S., Bolaji B. O.
International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-2015 1158 Experimental Investigation of the Performance of Liquefied Petroleum Gas (LPG) Refrigerant in A Vapour Compression
More informationWeek 9. Refrigeration Cycles I. GENESYS Laboratory
Week 9. Refrigeration Cycles I Objectives 1. Introduce the concepts of refrigerators and heat pumps and the measure of their performance. 2. Analyze the ideal vapor-compression refrigeration cycle. 3.
More informationPerformance improvement of vapour compression refrigeration systems
International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 48-56 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationPerformance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.
Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a. Raja Kumar Gond 1, Ravindra Pratap Chaudhary 2, Mohammad Amir Khan 3, Gaurav Jain 4 1Student,
More information*Corresponding author;
PERFORMANCE ANALYSIS OF AUTOMOTIVE AIR CONDITIONING SYSTEM WITH AN INTERNAL HEAT EXCHANGER USING R1234YF UNDER DIFFERENT EVAPORATION AND CONDENSATION TEMPERATURES by Mehmet DIREK a *and Alper KELESOGLU
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,
More informationExperimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Experimental Investigation on the Performance of Ground-source Heat Pump
More informationTHEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM
Journal of Science and Technology, Vol. 30, No. 3 (2010), pp 101 2010 Kwame Nkrumah University of Science and Technology (KNUST) THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY
More informationAn Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters
An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters #1 Harshad D Kopurwar, #2 Pravin T Nitnaware, #3 Tapobrata Dey 1 harshvardhan1590@gmail.com #1 Mechanical
More informationWaste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System
Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System 1 Avnish Chandra Pandey, 2 M. Akash Rao, 3 Sabyasachi Sahoo, 4 Narendra Kumar Students, Department of Mechanical
More informationHFCs or the Old Refrigerants - what is the best Choice?
HFCs or the Old Refrigerants - what is the best Choice? Hermann Halozan Institute of Thermal Engineering, Graz University of Technology Inffeldgasse 25 / B, A-8010 Graz, Austria, Phone: +43 316 873-7303
More informationISSN Vol.08,Issue.21, November-2016, Pages:
ISSN 2348 2370 Vol.08,Issue.21, November-2016, Pages:4164-4170 www.ijatir.org Thermal Analysis of Vapour Compression Cycle for Different Refrigerants ALI MOHAMMED ABDOULHA MASSOUD 1, DR. MOHAMMAD TARIQ
More informationA RECENT REVIEW OF REFRIGERANT R-1234YF AND R-1234ZE (E)
A RECENT REVIEW OF REFRIGERANT R-1234YF AND R-1234ZE (E) 1 Prof.Pragnesh D. Kandoliya, 2 Prof.Nirajkumar C Mehta 1 A.P.M.E., 2 A.P.M.E. 1 Mechanical Engineering, 1 Vadodara Institute of Engineering, Vadodara,
More informationJJMIE Jordan Journal of Mechanical and Industrial Engineering
JJMIE Jordan Journal of Mechanical and Industrial Engineering Volume 9 Number 4, August.21 ISSN 199-666 Pages 289-296 Thermodynamic Analysis of R12a and Dimethylether Refrigerant Mixtures in Refrigeration
More informationComparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants
[VOLUME 5 I ISSUE 3 I JULY SEPT 2018] e ISSN 2348 1269, Print ISSN 2349-5138 http://ijrar.com/ Cosmos Impact Factor 5.75 Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a
More informationPerformance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile
Available online at www.pelagiaresearchlibrary.com Advances in Applied Science Research, 2013, 4(5):232-237 ISSN: 0976-8610 CODEN (USA): AASRFC Performance analysis of ejector refrigeration system with
More information