ARENA-SAFETY & OPPORTUNITIES MAULIK SHAH, MSC, PENG

Size: px
Start display at page:

Download "ARENA-SAFETY & OPPORTUNITIES MAULIK SHAH, MSC, PENG"

Transcription

1 ARENA-SAFETY & OPPORTUNITIES MAULIK SHAH, MSC, PENG

2 SAFETY 2

3 Exit Door Signage Name & address of the installer Refrigerant type and total weight in the system Field test pressures applied Refrigeration capacity Total kw, HP, full load amp., and volt rating of all prime movers 3

4 Leak Detector Remote sensor(s) in room(s) where leaks are likely to occur Panel alarms at 25ppm audible enough to be heard by rink attendant when inside the building Below 300ppm, ventilation system ramps up and compressors shut down 4

5 5

6 Leak Detector Types Five types of sensors available for leak directors (varies in price & features- pros and cons) 1. Chemical -detector tubes 2. Solid state 3. Electrochemical 4. Infrared 5. Ionmobility spectrometers 6

7 Relief Valves & Relief Line 7

8 Relief Valves & Relief Line Pressure-relief valves shall be replaced at intervals no longer than five years. Sized as per the latest code 8

9 Ventilation Single Fan has (2) speeds or multiple Fans At low speed, provides for normal air change of 0.5cfm per ft2 of mechanical room At high speed, is meant to remove ammonia from the machinery room High speed triggered by manual shutdown or high Refrigerant(NH3) alarm Can only be shut down inside the room High speed is calculated based on mass of refrigerant 9

10 Exit Door Exterior doors must also be self-closing and self-locking There must be enough door space to permit escape opportunity for the maximum number of people who may be in the room They should not open to any corridor, or public rooms where people may be assembled 10

11 Vestibule Self-closing, crash bar style, tight-fitting doors, opening outwards from machinery room Refrigerant Alarm Emergency shut-down Eyewash station General arrangement drawing 11

12 P & Id Drawing in vestibule (preferably) Shows all major valves, and power disconnects 12

13 Log Book & Log Sheets Log book should include who is in charge, the date, and the time of all events taking place outside normal activities Log book should indicate any maintenance performed on the system Log sheets should be used to check key equipment readings, positions, operation, ambient temperatures, and any other items important to the operation 13

14 Instructions Emergency instructions Shutdown procedures First responder contacts ABSA contacts Management contact Equipment repair contact Job safety procedures for routine tasks 14

15 PPE(Personal Protective Equipment) The owner of any refrigeration system shall supply and maintain for its employees the Personal Protective Equipment required by the jurisdiction where the system is located 15

16 MACHINE ROOM Access restricted to authorized people Large enough to provide access for operations, maintenance, and service Equipment not floor mounted must be accessible by fixed ladder or portable device(s) meant to legally allow access, and kept on site at all times Any roof equipment must be set back at least 3m from roof edges or railings, and fall arrest equipment to be provided to all trained employees All equipment must meet Occupational Health & Safety requirements, including guarding Labelling of all Pipes and valves with paint Minimum temperature for room is 5 C and may require supplemental heating and equipment Other than lighters, atmospheric testing equipment, or matches, no open flame, or equipment with a temperature exceeding 427 C is permitted Room must meet the National Building Code of Canada, and have a 1 Hr Fire Rating 16

17 PIPING Piping should be guarded from impact by moving equipment Piping, Equipment, Valves should be labelled/tagged Ammonia Piping Color Scheme Recommendations as per IIAR bulletin 114 Piping cannot pass through enclosed hallways, landings, stairways, or elevator/dumb waiter shafts Piping cannot go through floors other than basement to main floor, or top floor to refrigeration room Piping crossing walkways shall be located at least 2.3m from the ground, or against the ceiling Provisions must be made for safety relief valve piping discharge 17

18 Labelling-IIAR Bulletin

19 OPPORTUNITIES 19

20 Grants Community Facility Enhancement Program (CFEP) funding provides financial assistance to acquire, build, purchase, repair, renovate, upgrade or expand sports, recreational, cultural or other related public-use community facilities. Community Initiatives Program (CIP) funds initiatives that enhance and enrich communities throughout Alberta. The program: Reinvests revenues generated from provincial lotteries to communities Empowers local citizens and community organizations to work together Responds to local needs Heat Recovery/Saving Projects VFDs Desuperheater Process water Heating 20

21 CFEP 21

22 CIP 22

23 THANK YOU!!

Todd Jekel, Assistant Director, IRC Feb. 8, Standard Definition. What is a machinery room?

Todd Jekel, Assistant Director, IRC Feb. 8, Standard Definition. What is a machinery room? Machinery Room Requirements & Best Practices Design Todd Jekel, Assistant Director, IRC Feb. 8, 2007 Standard Definition What is a machinery room? ASHRAE 15-2004 3 states: a space, meeting the requirements

More information

RAGAGEP UPDATE. Douglas Reindl, Director, IRC 2016 IRC R&T Forum

RAGAGEP UPDATE. Douglas Reindl, Director, IRC 2016 IRC R&T Forum RAGAGEP UPDATE Douglas Reindl, Director, IRC 2016 IRC R&T Forum What s the point? Process safety information (d)(3)(ii) The employer shall document that equipment complies with recognized and generally

More information

Safety Standard for Refrigeration Systems

Safety Standard for Refrigeration Systems BSR/ASHRAE Addendum a ANSI/ASHRAE Standard 15-2016 First Public Review Draft Safety Standard for Refrigeration Systems First Public Review (April 2017) (Draft shows Proposed Changes to Current Standard)

More information

Ammonia Refrigeration RAGAGEP

Ammonia Refrigeration RAGAGEP Providing Solutions. Simplifying Regulation. Ammonia Refrigeration RAGAGEP Peter Thomas, P.E., CSP Resource Compliance, Inc. Introduction Providing Solutions. Simplifying Regulation. Providing Solutions.

More information

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata) [F]TABLE 903.2.11.6 ADDITIONAL REQUIRED SUPPRESSION SYSTEMS SECTION SUBJECT 402.10 402.5 Covered and open mall buildings (Portions of table not show remain unchanged) 2012 International Building Code SEVENTH

More information

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC

More information

GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS

GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS [Second Revised Edition] April, 2003 Issued by: Mechanical and Engineering Branch Room 500, Norquay Building

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications January 15, 2018 Revision 6 Ammonia detection system codes and design specifications Following is a discussion of ammonia detection system design

More information

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963) INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-

More information

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS SUMMARY Ammonia odours were reported in the community close to the time of the incident (Appendix D) and firefighters reported

More information

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly. SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

Fire/General Safety Review Program Key Performance Indicators Environmental Health and Safety

Fire/General Safety Review Program Key Performance Indicators Environmental Health and Safety Fire/General Safety Review Program Key Performance Indicators Environmental Health and Safety Fire and CO Detection Systems Fire alarm pull station obstructed. Annunciation panel obstructed. Lack of approved

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

REPLACEMENT OF HCFC-22 REFRIGERANTS WITH AMMONIA: A CHALLENGE FOR HOCKEY ARENAS IN QUEBEC

REPLACEMENT OF HCFC-22 REFRIGERANTS WITH AMMONIA: A CHALLENGE FOR HOCKEY ARENAS IN QUEBEC REPLACEMENT OF HCFC-22 REFRIGERANTS WITH AMMONIA: A CHALLENGE FOR HOCKEY ARENAS IN QUEBEC Jean-Paul Lacoursière, P.E. University of Sherbrooke jpla@sympatico.ca Claude Dumas, P.E. Ville de Montréal cdumas@ville.montreal.qc.ca

More information

Residential Care Facilities Requirements

Residential Care Facilities Requirements Development Services Department Building Division 311 Vernon Street Roseville, California 95678-2649 Residential Care Facilities Requirements SUBMITTAL REQUIREMENTS: Note: These requirements are in addition

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Chapter Nursing Homes

Chapter Nursing Homes Chapter 16.01 Nursing Homes Section 1. Licensing. No nursing, convalescent or old age home, as defined in Section 2 of this ordinance, shall be operated except under a license from the City Council of

More information

ALABAMA. Downloaded

ALABAMA. Downloaded Housekeeping/Laundry/Maintenance ALABAMA Downloaded 01.15.11 (e) Maintain an effective pest control program so that the facility is free of pests and rodents. In the laundry, provision shall be made to

More information

Flammable Liquid: A liquid whose flashpoint is greaterless than 100 F when tested by closed-cup test methods.

Flammable Liquid: A liquid whose flashpoint is greaterless than 100 F when tested by closed-cup test methods. ANSI/IIAR 2-2014 Addendum A Standard for Safe Design of Closed-Circuit Ammonia Refrigeration Systems Public Review Draft #3 Reviewers of Addendum A are welcome to comment on the changes in the standard,

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

Exit Routes. Introduction/Overview. OSHA Regulations. Exit Route

Exit Routes. Introduction/Overview. OSHA Regulations. Exit Route Exit Routes Introduction/Overview Knowing how to evacuate your workplace is very important for your safety. An evacuation may be required for a number of different emergencies, including: Fire or smoke

More information

Short Term Accommodations Fire Code Requirements

Short Term Accommodations Fire Code Requirements Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to

More information

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Name & Address of the Society IDENTIFY PEOPLE AT RISK 01 Have you identified who is at risk? 02 Have you identified

More information

Ammonia Refrigeration RAGAGEP

Ammonia Refrigeration RAGAGEP Ammonia Refrigeration RAGAGEP Recognized and Generally Accepted Good Engineering Practice Peter Thomas, P.E., CSP Resource Compliance, Inc. Introduction Where does the term RAGAGEP come from? CalARP RAGAGEP

More information

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL Page 2 of 16 EXPLANATORY MATERIAL In November 1996, the Fire Technical Council introduced a guideline entitled "Approved Fire Safety Guidelines for Apartment Buildings". The guideline was established under

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Washoe County Department of Social Services

Washoe County Department of Social Services SECTION 30 FIRE AND LIFE SAFETY REQUIREMENTS 30.1 Authority to inspect. The facility shall meet all fire and life safety standards. Fire department inspectors shall have authority to enter, for purposes

More information

Selecting And Applying Emergency Lighting Systems

Selecting And Applying Emergency Lighting Systems bodine Selecting And Applying Emergency Lighting Systems A revision of an article originally published in Electrical Construction & Maintenance by David Crippen, CEO & Marketing Manager Contains updated

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

IIAR Minimum Safety Criteria for a Safe Ammonia Refrigeration System

IIAR Minimum Safety Criteria for a Safe Ammonia Refrigeration System Bulletin No. 109 10/97 Guidelines for: IIAR Minimum Safety Criteria for a Safe Ammonia Refrigeration System International Institute of Ammonia Refrigeration NOTICE The information contained in these guidelines

More information

FIRE PREVENTION EXHIBIT GUIDELINES

FIRE PREVENTION EXHIBIT GUIDELINES FIRE PREVENTION EXHIBIT GUIDELINES Exhibit booth construction shall meet all building requirements. All means of entrance and exit must be clear and free from obstruction at all times. No storage of any

More information

August 15, 2013 Page 1 of 19

August 15, 2013 Page 1 of 19 Section C401 Application Compliance with C402, C403, C404 and C405 AND (either C406.2, C406.3 or C406.4) Compliance with C402, C403, C404 or C405 Section C402 Building Envelope (Climate Zone 5A) Space-Conditioning

More information

Large Family Daycare Guideline

Large Family Daycare Guideline Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose

More information

2017 Annual Fire Safety Report

2017 Annual Fire Safety Report 2017 Annual Fire Safety Report King University Security Department Parks Hall 1350 King College Road Bristol, Tennessee 37620 Telephone 423-652-4333 Fax 423-652-6338 Page 1 of 5 Fire Safety The King University

More information

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor;

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor; ACTION: Original DATE: 09/30/2005 1:17 PM 5123:2-3-11 Fire safety and emergency response plans. (A) Purpose The purpose of this rule is to ensure the safety of individuals residing in residential facilities

More information

Description of the European standard EN 378: Refrigerating systems and heat pumps Safety and environmental requirements

Description of the European standard EN 378: Refrigerating systems and heat pumps Safety and environmental requirements : Refrigerating systems and heat pumps Safety and environmental requirements Prof. Dr. Risto Ciconkov, dipl. ing. Faculty of Mechanical Engineering, University Ss. Cyril & Methodius Skopje, R. Macedonia

More information

a) Establishment of emergency procedures to be followed at the time of an emergency;

a) Establishment of emergency procedures to be followed at the time of an emergency; 5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

Motion Controlled Apartment Building Corridor Lighting

Motion Controlled Apartment Building Corridor Lighting STAFF REPORT ACTION REQUIRED Motion Controlled Apartment Building Corridor Lighting Date: October 19, 2009 To: From: Wards: Reference Number: Licensing and Standard Committee Executive Director, Municipal

More information

FIRE PREVENTION STANDARDS

FIRE PREVENTION STANDARDS DATE: 04/11/02 APPROVED: NUMBER: FP0-010 REVISED: FIRE PREVENTION STANDARDS TITLE: Large Family Day Cares (9-14 kids) PURPOSE: The purpose of this standard is to acquaint the applicant with the applicable

More information

FIRE INCIDENT REPORTING

FIRE INCIDENT REPORTING FIRE SAFETY REPORT - 2017 The Higher Education Opportunity Act enacted in August 2008 requires institutions that main on-campus student housing facilities to publish an Annual Fire Safety Report that contains

More information

FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe

FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe FIRE SAFETY PLAN Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA May / 2017 Prepared by: Chris Pancoe TABLE OF CONTENTS Contents A. BUILDING AUDIT:... 3 BUILDING DESCRIPTION... 3 1. Level

More information

Residential Fire Protection

Residential Fire Protection Chapter 13: Residential/Farm Fires Residential fires have become a significant problem throughout the United States. The National Fire Protection Association (NFPA) estimates that residential fires in

More information

Statutory Compliance Checklist

Statutory Compliance Checklist Date of Issue: April 2017 Statutory Compliance Checklist This document is for clergy and churchwardens to help them in the maintenance of their Churches. Refer to supplementary notes for further guidance.

More information

Smoke Management in High-Rise Structures

Smoke Management in High-Rise Structures Smoke Management in High-Rise Structures Most modern building codes define a high-rise structure as a building greater than 75 feet in height from the lowest level of fire department vehicle access to

More information

Secondary Suites. Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August

Secondary Suites. Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August Secondary Suites Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August 2015 PLANNING & DEVELOPMENT SERVICES Building Permits & Licences 1st Floor, 32315 South Fraser

More information

GENERAL AREAS OF INSPECTION

GENERAL AREAS OF INSPECTION This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that

More information

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: Manitoba Regulation 221/2015 and Manitoba Regulation 222/2015 DATE: MARCH 17, 2016 1. INTRODUCTION On April 1, 2016, new building and

More information

Short-Term & Accessory Short-Term Rental Safety Certification

Short-Term & Accessory Short-Term Rental Safety Certification Short-Term & Accessory Short-Term Rental Safety Certification Permit Application Center (City Hall) 555 Liberty St. SE, Room 320 Salem, OR 97301 503-588-6213 (For office use only) License #: If you need

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop Gas Heating/Electric Cooling Unit Two Stage Cooling Capacity Control with Puronr (R---410A) Refrigerant Sizes: 17, 20, 24, 28, 30 Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION

More information

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:. 2012 B.C. Building Code Checklist (Division B Part 3) This checklist is provided as a reference only. The submission of this checklist with a Building Permit application should not be considered as a substitute

More information

Department Of Public Works: Internal Operations

Department Of Public Works: Internal Operations Department Of Public Works: Internal Operations A Checklist There are over 800 municipalities in the Michigan Municipal League s Pool and Fund Programs. Most perform public works functions of one type

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

rpsa FIRE PROTECTION ENGINEERS

rpsa FIRE PROTECTION ENGINEERS FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57295/Page 1/July 21, 2017 HVAC SYSTEMS NARRATIVE REPORT The following is the HVAC system narrative, which defines the scope of work and capacities of the HVAC system as well as the Basis of Design.

More information

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector

More information

Portable Vertical Air-Conditioning and Heating Systems

Portable Vertical Air-Conditioning and Heating Systems Portable Vertical Air-Conditioning and Heating Systems Specifications for 10 Ton Units 208 230 volt 7 1 77 77 77 33 Front Side Back 77 71 / 77 Front 33 Side 2 Cabinet Features: Heating and Cooling Data:

More information

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15 N/A N/A 2015 International Fire Code 2015 International Building Code Codes Jurisdictions for Fire and Building Codes Source of Information Building Fire Plumbing Mechanical Electrical Energy Code Accessibility

More information

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Interfacing Fire Alarm, Sprinkler and Elevator Systems 1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22

More information

BSR/ASHRAE Addendum b to ANSI/ASHRAE Standard FORWORD

BSR/ASHRAE Addendum b to ANSI/ASHRAE Standard FORWORD (This foreword is for information only and is not part of this addendum) FORWORD Changes in this addendum to ANSI/ASHRAE 15-1994 are made to add water as a refrigerant, include absorption refrigeration

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the

More information

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS Town of Brighton Office of the Fire Marshal October 2018 Carbon Dioxide Systems for Beverage Dispensing Requirements Scope The intent

More information

Renovation Program. Renovation Program GENERAL

Renovation Program. Renovation Program GENERAL Renovation Program GENERAL This program provides guidance and protocols for renovation projects in occupied, operational acute hospitals. Team building is essential to quality control and HFD Services

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

ICC CODE CORNER 2015 International Fire Code

ICC CODE CORNER 2015 International Fire Code SECTION 606 MECHANICAL REFRIGERATION [M] 606.1 Scope. Refrigeration systems shall be installed in Code. [M] 606.2 Refrigerants. The use and purity of new, recovered and reclaimed refrigerants shall be

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015

More information

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat SINGLE PACKAGE ROOFTOP, GAS HEATING/ELECTRIC COOLING UNIT WITH PURON R (R-410A) REFRIGERANT ONE STAGE COOLING CAPACITY CONTROL: SIZES 08-12 TWO STAGE COOLING CAPACITY CONTROL: SIZES 08, 12 & 14 Submittal

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-002 EFFECTIVE 05-27-2009 PURPOSE: To define the requirements for a License. To facilitate the quick application and review of new or changed

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop Gas Heating/Electric Cooling Unit Two Stage Cooling Capacity Control with NOVATIONt Coil Sizes 08, 12, 14 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED

More information

DGS - Danfoss Gas Sensor Check / Calibration Procedure

DGS - Danfoss Gas Sensor Check / Calibration Procedure User Guide DGS - Danfoss Gas Sensor Check / Calibration Procedure ADAP-KOOL Refrigeration Control System Content 1 - Introduction... 2 2 - Bump Test... 4 3 - Calibration... 5 4 - Additional recommendations...

More information

Forest Hills Facilities Plan

Forest Hills Facilities Plan Forest Hills Facilities Plan Extensive updates to 8 of our 9 schools Replace Wilson Elementary Enhance learning environments across the district Build additional classrooms to accommodate gradual implementation

More information

BC Building Code Checklist Part 3 Planning and Development Department

BC Building Code Checklist Part 3 Planning and Development Department BC Building Code Checklist Part 3 Planning and Development Department Project: Civic address: Permit No.: CRP: Certified Professional: Date: 1 Value of Construction: $ Developed Site Area: m2 2 BUILDING

More information

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard SOCIAL ACCOUNTABILITY ACCREDITATION SERVICES To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard Background: After an

More information

Compressed Air Products

Compressed Air Products German Quality and Innovation Compressed Air Products Compressed Air Products Glenco Air & Power Pty Ltd I ABN 21101370085 I 21 Resource Street, Parkinson QLD 4115 I Australia tel 07 3386 9999 I fax 07

More information

Rental Housing Initial Inspection Checklist Community Development Department 208 NW 1 st Ave., Faribault, MN

Rental Housing Initial Inspection Checklist Community Development Department 208 NW 1 st Ave., Faribault, MN Rental Housing Initial Inspection Checklist Community Development Department 208 NW 1 st Ave., Faribault, MN 55021 www.faribault.org (507) 333-0359 Property Address: Number of Units Building Type Name

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS AutoZone R Model Single Package Rooftop Gas Heating/Electric Cooling Unit Size 07 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

RAGAGEP: Codes, Standards, and Good Engineering Practice PETER THOMAS, P.E. PRESIDENT AND ENGINEER RESOURCE COMPLIANCE

RAGAGEP: Codes, Standards, and Good Engineering Practice PETER THOMAS, P.E. PRESIDENT AND ENGINEER RESOURCE COMPLIANCE RAGAGEP: Codes, Standards, and Good Engineering Practice PETER THOMAS, P.E. PRESIDENT AND ENGINEER RESOURCE COMPLIANCE PTHOMAS@RESOURCECOMPLIANCE.COM Introduction PSM RAGAGEP References Title 29 1910.119(d)(3)(ii)

More information

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1. EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD STANDARD #F-003 EFFECTIVE 06-03-2009 PURPOSE To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified

More information

Case Study: SUPERMARKET APPLICATION

Case Study: SUPERMARKET APPLICATION Case Study: SUPERMARKET APPLICATION Supermarket Sees Overall Energy Savings and Solutions to Problems of Sweating Doors, Hot/Cold Areas, Severe Energy Loss, and Customer Safety The following is a complete

More information

SAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM

SAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM SAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM COURSE Fire Detection Standards Training 10139 ORIGINATOR K Norgate DATE 2nd November 2012 Amendment 1 October 5th 2013 1st Committee review Amendment

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

Board Policy 6819 Fire Safety and Prevention Plan

Board Policy 6819 Fire Safety and Prevention Plan Board Policy 6819 Fire Safety and Prevention Plan The West Hills Community College District is committed to the safety of faculty, staff, students and visitors. The Fire Safety and Prevention Plan is designed

More information

COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF HEALTH

COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF HEALTH COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF HEALTH ANNEX A, TITLE 28. HEALTH AND SAFETY PART V. DRUG AND ALCOHOL FACILITIES AND SERVICES CHAPTER 701. GENERAL PROVISIONS, SUBCHAPTER A. DEFINITIONS 701.1.

More information

APPLICATION FOR Large Family Day Care Permit

APPLICATION FOR Large Family Day Care Permit PLANNING SERVICES DEPARTMENT 411 Main Street (530) 879-6800 P.O. Box 3420 Chico, CA 95927 Application No. APPLICATION FOR Large Family Day Care Permit Applicant Information Applicant Daytime Phone Street

More information

ACKNOWLEDGEMENT. IIAR expresses its deepest appreciation to these authors for their contributions for the betterment of the industry.

ACKNOWLEDGEMENT. IIAR expresses its deepest appreciation to these authors for their contributions for the betterment of the industry. t ACKNOWLEDGEMENT The success of the 15th Annual Meeting of the International Institute of Ammonia Refrigeration is due to the work of the authors whose technical papers appear in this book. IIAR expresses

More information

Facility Risk Assessment Questionnaire

Facility Risk Assessment Questionnaire Facility Risk Assessment Questionnaire ServiceMaster anytime provides this safety information free of charge. These materials are provided as a service to our clients and 866 Recover enrollees and is for

More information

Consumer Product Safety Commission Smoke Alarms Why, Where, and Which CPSC Document #559

Consumer Product Safety Commission Smoke Alarms Why, Where, and Which CPSC Document #559 Consumer Product Safety Commission Smoke Alarms Why, Where, and Which CPSC Document #559 A smoke alarm is critical for the early detection of a fire in your home and could mean the difference between life

More information