ALICE TRD AND TPC THERMAL SCREEN COOLING SYSTEM

Size: px
Start display at page:

Download "ALICE TRD AND TPC THERMAL SCREEN COOLING SYSTEM"

Transcription

1 ORGANISATION EUROPEENNE POUR LA RECHERCHE NUCLEAIRE EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH CERN-ST/CV-2003-????? February 2003 ALICE TRD AND TPC THERMAL SCREEN COOLING SYSTEM M. Pimenta dos Santos Abstract This document outlines a design proposal for the external cooling system of the Transition Radiation Detector and the TPC thermal screen. For p-p collisions the total power dissipated by the TRD is approximately 55kW. A residual percentage of this heat needs to be removed by a thermal screen in order to ensure an uniform temperature map on the TPC side. The overall design of the cooling system, including piping to and from the detector, plant operation, controls and leak detection are examined. A complete list of components, costs and required manpower is also presented.

2 Index 1.Introduction 3 2.Cooling Circuits Design 3 3.Cooling Plant Design 3.1 Plant description The leakless or sub-atmospheric mode Temperature regulation Cooling System Operation and communication with ECR and TCR Cooling plant layout drawings 10 4.Responsibilities and resources 4.1 Responsibilities Cost estimation 11 Appendix I: Estimation of pressure drop along one MCM cooling circuit 13 TPC Cooling System Page 2 of 13

3 1. Introduction The ALICE Transition Radiation Detector (TRD) aims at providing electron identification at momenta above 1 GeV/c. The segmentation of the TRD follows that of other ALICE detectors, leading to 18 super-modules, each covering 20 degrees in azimuth and aligned along the z direction. Within each super-module, heat is dissipated by a variety of components, the main heat source being the multi-chip modules (MCM). An estimated 55 kw is dissipated for the whole TRD when running with p-p collisions. The interface with the TPC is of particular interest as the temperature map there must be kept as uniform as possible around 20ºC. An actively cooled thermal screen is introduced between the two detectors aiming at removing any residual heat not taken away by the TRD cooling and smoothing out temperature differences at the TPC boundary. The cooling system described herein comprises a water cooling and de-ionization plant, its controls and all the piping to the detector. Figure 1 Cross section of TRD detector within the ALICE space frame 2. Cooling Circuits Design Cooling is provided to each individual super-module as shown in Fig.2 with inlets on RB26 side and outlets on the opposite side. The thermal screen follows the same segmentation as the TRD, i.e. one screen per super-module. Each screen is made of 5 panels cooled in parallel, as shown in Fig.3. The nominal flow rate is 1.5m3/h per super-module and 300L/h per thermal screen. This value was calculated in order to limit the pressure drop within a super-module and enable the so called leakless operation mode (further details in Appendix I). Water temperature at the super-module inlet can be adjusted to any value between 16ºC and 18ºC. The expected water temperature rise (assuming ~3kW heat dissipation per super-module cooled with full efficiency) is less than 2ºC. The thermal screens are meant to remove just the residual heat from the super-modules and smooth out the temperature map on the TPC side. Consequently, the water temperature at the screen inlet should be just under 20ºC, i.e. the temperature aimed for the TPC volume. Assuming a residual heat of 10% from the super-modules, the power to be removed by one screen is approximately 300W. This would lead to a water temperature increase of 0.8ºC. TPC Cooling System Page 3 of 13

4 Figure 2 TRD super-modules cooling circuits. Left: Supply pipes layout around the TRD right: Cooling of one TRD super-module. Figure 3 Thermal screen cooling circuits. Left: Supply pipes layout around the TPC end-cap right: Cooling of one screen 3. Cooling Plant Design 3.1. Plant description A diagram representing the cooling plant as well as some of the piping to the detector is shown in Figure 4 and some components are identified in table 1. The plant consists of a reservoir large enough to contain all the water in the installation (27), a pump (9), one supply manifold for the thermal screen, one supply manifold for the TRD and one common return manifold for both. Given the difference in water temperature required for the super-modules (~16ºC) and the thermal screen (~20ºC), each supply manifold will have its own heat exchanger connected to the ST/CV mixed water network (12 and 13). All 36 circuits can be temperature and flow adjusted. Temperature regulation is done via individual heaters (17 and 18) on the supply manifolds. These heaters are PID controlled using a temperature sensor (14f) immediately downstream as a feedback signal (see section 3.3 for details). Flow adjustment is done manually on balancing valves (21 and 22) during the commissioning of the system, in order to ensure that all circuits get the right flow despite of varying pipe length between the plant and the super-modules or screens. A PID controller adjusts the pump speed via a frequency inverter in order to keep a constant pressure in the supply manifold despite of the number of circuits in service at any given moment. Another PID controller adjusts the flow of mixed water via the 3-way valves (15 and 16) in order to maintain a constant temperature (14d and 14e) at the heat exchangers outlets. All regulation loops and the plant control is done by a Programmable Logical Controller (PLC). A fraction of the total flow (~5%) is by-passed through a mixed bed de-ionizer (11) and its conductivity measured (35). TPC Cooling System Page 4 of 13

5 Flow rate: TRD: m 3 /h Thermal Screen: m 3 /h 16~20 o C TRD supermodule Total flow: 32.4 m 3 /h +5% by-passed demin. Unit. 34m 3 /h Total heat to be removed: ~ 55 kw 18~20 o C Total Volume of water in the installation: ~2000L RB26 side Thermal screen RB24 side Installed Electrical Power: Pump: 11kVA Heaters TRD: 18 x 700VA Heaters Screen: 18 x 3.5kVA Compressed air 30 29b Total Power: 76kVA 28 Range of available water temperature at the Heaters outlet: Super-modules: 16~18ºC Screen: 18~20ºC Mixed Water Consumption: TRD Heat exchanger : ~32..5m 3 /h Screen Heat exchanger: ~4.5m 3 /h 23a f TRD Supply manifold 18 outlets Thermal screen Supply manifold 18 outlets 23b Return manifold 36 inlets a 2a 3a Total consumption: 37m 3 /h 14d 17 25a 18 14e 13 Mixed water 14c b 11 C Figure 4 TRD and Thermal Screen Cooling System 14b a 34 2b 3b 10 29a 1b item Description item Description 1a, 1b Pressure relief valve 14a,b,c,d,e,f Temperature Sensors 2a, 2b Manometer 15, 16 Mixed water Regulation Valve 3a, 3b Pressure transmitters 17, 18 Heaters 4 Ultra sound Level transmitter 19,20,24, 25a,b Pneumatic shut off valves 5 Vacuum pump 21, 22, 31 Balancing Valves 6 3-way Electro-valve 23 a,b Schrader valves 7 Drain valve 26 Visual Level 8 Butterfly Valve 27 Reservoir 9 Circulator Pump 28 Pneumatic distribution array 10 Strainer 29a,b Pressure switch 11 Mixed bed de-ionizer 32,33,34 Flowmeters 12, 13 Heat Exchangers 35 Conductivity transmitter Table 1 Identification of some components in Figure 4 TPC Cooling System Page 5 of 13

6 3.2. The Leakless Operation Mode 1 Consequences of a leak occurring inside the detector are obviously adverse. The risk of such an event can be eliminated if the hydraulics of the system is such that water pressure within the detector is below atmospheric, i.e.p DETECTOR-INLET P ATMOSPHERIC. This is done by keeping the reservoir (22) below atmospheric pressure by means of a vacuum pump (5), but still at a pressure high enough to avoid cavitation in the pump (9). Pressure drops inside the detector and in the return lines are carefully minimized to obey the following condition: 1 2 PDETECTOR + PRETURN _ LINE PATMOSPHERIC PRESERVOIR + ρ U + ρgh (a) 2 Where 1 ρ U 2 (U, flow speed; ρ density) is the dynamic pressure at the detector inlet 2 And ρgh (h, difference in height; g gravitational acceleration) is the hydrostatic pressure difference between the reservoir free surface and the detector inlet. Leak Detection Should a leak occur inside the detector or anywhere downstream to the cooling plant, no water will be spilled out. Instead, air will infiltrate into the system and be flushed down the return line, accumulating inside the reservoir. The pressure sensor in the reservoir (3a) will detect the consequent pressure build up and as soon as a pre-established threshold P 1 is exceeded, the PLC will immediately switch on the vacuum pump (5) and produce a WARNING message. The vacuum pump will run for a maximum period of 10 minutes. If the vacuum pump is able to restore the pressure back to the normal operation pressure P N in less than 10 minutes, it will stop pumping, yet the WARNING message will persist, informing the operator that a small air infiltration has been detected. As long as the air infiltration remains small, the pump is always able to restore the normal operation pressure in less than 10 minutes and the system can run ad infinitum with the pressure in the reservoir swinging between P N and P 1. In these circumstances the user may decide to engage the leak identification procedure to identify the exact leaky circuit, even though this procedure implies stopping the cooling for a while. If the vacuum pump is not able to restore the pressure in less than 10 min or if the pressure in the reservoir rises above a second threshold P 2, then the air infiltration rate into the system is considered to be important. In this case, not a warning but an ALARM message will be generated by the PLC and the cooling will stop. The PLC will also stop the circulator pump (9) and open the by-pass valves (25a and 25b) in order to start recovering all the water back into the reservoir both through supply and return lines. During this whole process, the vacuum pump stays on. Once most of the water has been recovered back into the reservoir, the user may also decide to engage the leak identification procedure. A significant part of the installation, from the pump outlet up to the immediate upstream vicinity of the detector inlet, will be above atmospheric pressure. Water spill out will occur if a leak develops anywhere between these two points. In this case, the ultra-sound level transmitter (4) will detect the loss of water in the reservoir and the PLC will produce an ALARM message and switch off the circulator pump, i.e., the cooling will stop. With the circulator pump switched off, the pressure throughout the installation falls to sub-atmospheric and the water spillage will stop. The by-pass valve (25a and 25b) opens and water recovery can then precede both through supply and return sides. The vacuum pump stays on during the process. Once most of the water has been recovered back into the reservoir, the user may decide to engage the leak identification procedure. Leak identification procedure This is an automatic procedure to identify and isolate the leaky circuit with the intent to restart the installation without intervention. With all supply and return valves closed and the reservoir at subatmospheric pressure, the leaky circuit is identified by successively opening one circuit at a time and monitoring the pressure in the reservoir. Once the leaky circuit has been identified the installation may 1 Leakless systems were developed by Michel Bosteels, CERN ST/CV TPC Cooling System Page 6 of 13

7 resume the cooling for all remaining circuits. The whole procedure is triggered by the Experiment Control Room (ECR) Temperature Regulation The heat dissipated inside a super-module may vary with time, thus some sort of adjustment needs to be undertaken on the cooling if the temperature field at the TPC boundaries is to be preserved. The adjustment suggested here is to modify the temperature of the water at the inlet of the super-modules in order to cope with different heat dissipations. Prior to any physics data taking, the thermal behaviour of a super-module needs to be established experimentally in the form of an empirical relationship between heat dissipation and required water temperature so that in normal running conditions, the ECR will know what water temperature to request from the cooling plant for each individual super-module. The request is communicated from the ECR to the cooling plant PLC where all the PID controllers are implemented. The PID uses as feedback signal the temperature sensor located at the heater outlet and acts on a Solid State Relay which in turns adjusts the heating power. There is of course a long pipe length between the heater outlet and the Super-modules inlet so these pipes are insulated in order to eliminate any thermal disturbance from the surroundings. Heaters are protected with a thermal switch, to prevent damage caused by accidentally overheating when there is little or no flow. The outgoing water temperature acquisition is made using a CERN developed card, the ELMB- Embedded local monitor Board connected to the PLC via CAN fieldbus. Figure 5 depicts the control loop in block diagram language. Water temperature at the heater inlet Water temperature requested by ECR PID controller Triac heater Water temperature at the heater outlet Travel time along supply line Twater at Supermodule inlet PLC Canbus EMLB Pt100 Figure 5 Control loop for water temperature regulation 3.4. Cooling System Operation and communication with ECR and TCR Plant Status The cooling plant can exist in 4 different statuses: stop, test, stand-by and run. In order to transit from one status to another, an input is required and/or certain conditions must be verified. Stop status: All power is off. Maintenance or repair operations can be carried out Test status: Testing the plant s performance and readiness. Filling, emptying and leak testing operations can be carried out. Mixed water may or may not be flowing The plant may or may not contain water The pressure in the reservoir may or may not be sub-atmospheric TPC Cooling System Page 7 of 13

8 Pressure and liquid level readings are available Pneumatic pressure is available so that individual circuits can be shut off for eventual leak testing. Stand-by status: The plant is water filled and waiting for a RUN order from the ECR Return and supply valves are all open (except any previously identified leaky circuit that may remain not repaired). Pressure and liquid level in the reservoir is correct. Circulator Pump is OFF. Temperature Regulation is OFF. Liquid level and Pressure monitoring is ON. Mixed water is flowing at the right temperature and rate. Compressed air is available and at the right pressure Emergency by-pass valve is closed Run status - Cooling is ON Supply and return valves are all open Emergency by-pass valve is closed Pump is running and outlet pressure regulation loop is ON Leak surveillance (reservoir pressure and liquid level monitoring) and is ON Temperature regulation is ON The detector is being cooled. The experiment may switch the detector on Transition between status Test Stand-by: only the local ST/CV SCADA supervisor can order this transition Stand-by Test: only the local ST/CV SCADA supervisor can order this transition. Stand-by Run: only ECR (experiment control room) can order this transition. However, if the stand-by status was the result of an alarm driven transition from run status, the alarms need to be acknowledged and reset first by the ST/CV supervisory SCADA. Upon ordering this transition, the ECR will have the possibility to set the following parameters: 1. Open/Close the water flow for a particular circuit (as long as the circuit hasn t been declared out of order). 2. Temperature set-point for each and every circuit Run Stand-by: this transition can take place as a result of the ECR deciding to stop the cooling to all circuits. The transition may also originate from the PLC as the result of an ALARM and in this case the ECR will promptly receive an alarm message informing of the imminent stopping of the cooling Warnings and Alarms Warnings and Alarms are issued by the cooling plant PLC and transmitted to the Experiment Control Room (ECR) and to the Technical Control Room (TCR). A warning is issued when a parameter is outside its normal range, but the deviation is not significant enough to stop the cooling. If the deviation becomes significant then an alarm is produced and the cooling plant or part of the cooling plant stops. A warning does not necessarily give rise to an alarm. An alarm always implies ceasing of cooling. TPC Cooling System Page 8 of 13

9 List of Warnings: W1) The pressure in the reservoir is above threshold P 1. W2) PID deviation error greater than 0.1 C (set point outlet temperature>0.1 C) for circuit #N W3) PID deviation error greater than 0.5 C (set point outlet temperature>0.5 C) at heat exchanger W4) PID deviation error greater than 100mbar (set point outlet pressure) at pump outlet W5) Circulator pump motor temperature above limit T PM 1 W6) Mixed water temperature is above limit T MW 1 List of Alarms: A1) Pressure in the reservoir is above threshold P 2 or vacuum pump has been running for more that 10 min. A2) Temperature switch has cut off power to heater #N A3) Compressed air failure (pressure insufficient) A4) Liquid pump failure (pressure insufficient at outlet). A5) Circulator pump motor temperature above limit T PM 2> T PM 1 A6) Mixed water failure (temperature either too high or insufficient flow). A7) Drop of water level in the reservoir Communication with ECR and TCR The role of the TCR, regarding this cooling system is assumed to be to receive alarms and to call the appropriate intervention piquet when required. The piquet is the only entitled entity to reset alarms and allow the system to transit back to run status, upon request from the ECR. This is done through the local ST/CV SCADA supervisor. The commands to switch on/off the cooling circuits as well as to modify set points go directly from the ECR supervisory SCADA (PVSS) to the cooling plant PLC (see Figure6). The ECR does not have access to low level commands to act on individual pieces of equipment in the cooling system (valves, pumps, etc.). TCR Cooling plant Status (Stop, Test, Stand-by, Run) Circuits status (Open, Closed) Warnings, Alarms PLC Transition orders Stand-by <=> Run Status Temperature set point for every circuit Open/Close circuits Cooling plant Status (Stop, Test, Stand-by, Run) Circuits status (Open, Closed) Warnings, Alarms Temperature at the heater outlets ECR Transition orders Stand-by <=> Test Status Alarms Reset Definition of Set Points for mixed water and pump outlet pressure PID regulation Definition of warning and alarm thresholds Cooling plant Data Storage Figure 6-Communication with ECR and TCR Local ST/CV Scada Supervisor (Wizcon) TPC Cooling System Page 9 of 13

10 3.5 Cooling plant layout drawings Figure 7 represents a preliminary sketch of the cooling plant physical layout. For transportation purposes, the plant is divided in 6 main volumes: TCR supply manifold, thermal screen supply manifold, return manifold, reservoir, rack containing pump + heat exchanger + filter and finally a rack with control (PLC), electrical equipment (triacs, circuit-brakers, frequency inverters etc ) and pneumatic equipment (electro-valves, etc..). Figure 8 shows a more detailed drawing of one temperature regulated outlet. Figure 7 Layout of the TRD and thermal screen cooling plant Temperature sensor Ball valve Balancing valve To detector From supply manifold Heater Figure 8 Detail of a temperature regulated outlet TPC Cooling System Page 10 of 13

11 4. Responsibilities and resources 4.1. Responsibilities The cooling plant described in this paper will be assembled, tested and first commissioned by ST/CV at the point 2 surface building by December Later on, the plant will be installed in the ALICE Experimental Area, connected to the mixed water network and again commissioned by ST/CV. Cables from the rack to neighbouring control equipment (PLC, etc.) are included, cables to other areas should be laid to ST/CV specifications by the experiment. Documentation (schematics, description, user instruction manuals) and the associated controls will be delivered with the cooling system. The PLC hardware is included in the work package. However, the PC's for the PVSS control are to be supplied by the experimental group. ST/CV will assume responsibility for the maintenance of the cooling plant during the LHC lifetime. A sub-detector expert from the experiment must participate during the commissioning of the cooling system both at the surface building and ALICE cavern Cost Estimation Table 3 Components and Materials Cost breakdown Item Description Manufacturer Quantity Unit cost (CHF) Total (see Fig 4) /model (CHF) 1a,b Pressure Relief valves CERN stores a,b Manometers CERN stores a,b Pressure transmitter Huba Control Ultra sound level transmitter Burkert Vacuum Pump KNF way electrovalve Parker Drain valve Legris Butterfly valve Zuercher/LUG Circulator Pump Grundfos/CRN Filter TECOFI Demineralisation Unit 50L Degremont ,13 Nickel brazed Heat Exchanger Swep ,16 Mixed water regulation valve Sauter Heater 6000W Dimeca Heater 1000W Dimeca Pneumatic Ball valvesdn20 Zuercher/Meca-Inox Pneumatic Ball valvesdn15 Zuercher/Meca-Inox Balancing valve DN20 Ribat/TA hydronics Balancing valve DN15 Ribat/TA hydronics Schrader valves M Paulus Pneumatic Ball valvesdn25 Zuercher/Meca-Inox Pneumatic Ball valvesdn15 Zuercher/Meca-Inox Visual Level CERN stores Reservoir 2000L Depositos Coballes Pneumatic EV array DIMAT Pressure switch Huba control TPC Cooling System Page 11 of 13

12 30 Electrovalve Lucifer Balancing Valve Rohr Flowmeter Aquadis Qmax=50m3/h Actaris Flowmeter Aquadis Qmax=10m3/h Actaris Flowmeter Aquadis Qmax=7m3/h Actaris Conductivity Meter Burkert Supply manifold TRD Tecnodelta Supply manifold thermal screen Tecnodelta Return manifold Tecnodelta rack for pump CERN stores piping, fittings, etc CERN stores 3000 PLC and related add-ons Schneider/TSX Circuit breakers, cabling etc CERN stores 4000 Frequency inverter Omron 3000 Cabling and accessories CERN stores 4000 Triacs for heaters Radiospares Pt100 sensors ELMB acquisition cards Total cost of material and components: CHF Manpower: duration (days) cost/hour (CHF) total cost Mechanical Assembly Electrical/control design Electrical assembly and cabling PLC programming Preliminary tests at CERN Commissioning at surface building point SCADA Wizcon Programming Commissioning in the cavern (including connection to networks, leaktesting, connection to pipes), Total cost of manpower: CHF TPC Cooling System Page 12 of 13

13 Appendix I Estimation of pressure drop along one MCM cooling circuit Pressure drop vs Flow rate for a 2mm ID pipe Pdrop (mbar) Laminar Re<2000 Transition 2000<Re<4000 Turbulent Re> Length=5.6m 200 Length=1.0m Flow rate (L/h) TPC Cooling System Page 13 of 13

ATLAS INNER DETECTOR COOLING FULL SCALE TEST PHASE 2 MONOPHASE COOLING UNIT -20 C

ATLAS INNER DETECTOR COOLING FULL SCALE TEST PHASE 2 MONOPHASE COOLING UNIT -20 C CH-1211 Geneva 23 Switzerland EDMS No. ST/CV - Cooling of Electronics & Detectors Technical specifications ATLAS INNER DETECTOR COOLING FULL SCALE TEST PHASE 2 MONOPHASE COOLING UNIT -20 C Objectives This

More information

THE THERMOSIPHON COOLING SYSTEM OF THE ATLAS EXPERIMENT AT THE CERN LARGE HADRON COLLIDER

THE THERMOSIPHON COOLING SYSTEM OF THE ATLAS EXPERIMENT AT THE CERN LARGE HADRON COLLIDER THE THERMOSIPHON COOLING SYSTEM OF THE ATLAS EXPERIMENT AT THE CERN LARGE HADRON COLLIDER M. Battistin, S. Berry, A. Bitadze, P. Bonneau, J. Botelho-Direito, G. Boyd, F.Corbaz, O. Crespo-Lopez, E.Da Riva,

More information

ECOPlus SERIES OF HIGH-PRESSURE METERING MACHINES

ECOPlus SERIES OF HIGH-PRESSURE METERING MACHINES ECOPlus SEIES OF HIGH-PESSUE METEING MACHINES The OMS ECOPlus series of high-pressure metering units provides the ideal solution for every PU application. eliability, ease of operation and attractive price-performance

More information

LHCb Rich Detectors Control and High Voltage Systems

LHCb Rich Detectors Control and High Voltage Systems LHCb Rich Detectors Control and High Voltage Systems Mario Sannino On behalf of LHCb RICH Group Rich 2007 Trieste 19.10.2007 1 Rich 2007 Trieste 19.10.2007 LHCb Rich Detectors Control and High Voltage

More information

SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS

SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS SOTTOSTAZIONI PER TELERISCALDAMENTO DISTRICT HEATING SUBSTATIONS INDEX Ed. 20150422 GENERAL INFORMATION... 2 Before installing... 2 Materials and PED (97/23/CE) Standards... 3 SKID-TYPE DISTRICT HEATING

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

Alarms Manual. ver.1 rev.06/'07. Enclosures to Service Manuals of: McbNET Digital TM Magnum400 TM MiniMagnum400 TM. 6) Speeder One

Alarms Manual. ver.1 rev.06/'07. Enclosures to Service Manuals of: McbNET Digital TM Magnum400 TM MiniMagnum400 TM. 6) Speeder One 6) Speeder One VIALE STAZIONE 5-36054 MONTEBELLO VIC. - VI - ITALY Phone (+39) 0444 440441 - Fax (+39) 04444 440418 www.axorindustries.com - INFO@AXORINDUSTRIES.COM Alarms Manual Enclosures to Service

More information

Towards a Detector Control System for the ATLAS Pixeldetector

Towards a Detector Control System for the ATLAS Pixeldetector Towards a Detector Control System for the ATLAS Pixeldetector Pixel2002, Carmel September 2002 Overview of the Detector Control System The Front End System The Back End System Experience with the Testbeam

More information

Frequently asked questions: Intelligent Transmitter Series

Frequently asked questions: Intelligent Transmitter Series Frequently asked questions: Intelligent Transmitter Series The Wilcoxon family of Intelligent Transmitters, relay alarms, and communication modules can be used to implement low-cost online vibration monitoring

More information

RAMSES: THE LHC RADIATION MONITORING SYSTEM FOR THE ENVIRONMENT AND SAFETY

RAMSES: THE LHC RADIATION MONITORING SYSTEM FOR THE ENVIRONMENT AND SAFETY 10th ICALEPCS Int. Conf. on Accelerator & Large Expt. Physics Control Systems. Geneva, 10-14 Oct 2005, TH3B.1-3O (2005) RAMSES: THE LHC RADIATION MONITORING SYSTEM FOR THE ENVIRONMENT AND SAFETY G. Segura

More information

REFRESH, UPGRADE, PERFORM. Revamping Kits and Digital Solutions for quality improvement and energy savings

REFRESH, UPGRADE, PERFORM. Revamping Kits and Digital Solutions for quality improvement and energy savings Revamping Kits and Digital Solutions for quality improvement and energy savings Burners Sacmi for energy savings Complete range of burners for all fuel types. Heads specially designed for different capacities

More information

Design specifications and test of the HMPID s control system prototype in the ALICE experiment

Design specifications and test of the HMPID s control system prototype in the ALICE experiment Design specifications and test of the HMPID s control system prototype in the ALICE experiment Enzo CARRONE Enzo.Carrone@cern.ch HMPID Control System Design Implementation and tests Conclusions HMPID,

More information

ACCESS AND ALARM SAFETY SYSTEMS ACTIVITIES FOR THE 2012/2013 LONG SHUTDOWN*

ACCESS AND ALARM SAFETY SYSTEMS ACTIVITIES FOR THE 2012/2013 LONG SHUTDOWN* ACCESS AND ALARM SAFETY SYSTEMS ACTIVITIES FOR THE 2012/2013 LONG SHUTDOWN* S.Grau, C.Delamare, T.Ladzinski, P.Ninin, R. Nunes, CERN, Geneva, Switzerland. Abstract This paper presents the 2012/2013 long

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert)

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert) Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert) P.N. 7876C (export) February 12, 2015 For Spas equipped with BP2100, BP6013 controllers and Spa Touch panel. Spa

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

INDUSTRIAL RANGE ACCESSORIES AND COMPONENTS

INDUSTRIAL RANGE ACCESSORIES AND COMPONENTS AND COMPONENTS 199 INDUSTRIAL AUTOMATIC PURGING SYSTEMO FOR BX RANGE GENERATORS The automatic bottom blow down unit prevents unnecessary purging duplication or verifiable omission with the manual system.

More information

ENERGY TOP. Condensing boiler solutions

ENERGY TOP. Condensing boiler solutions ENERGY TOP Condensing boiler solutions 1 ENERGY TOP > ENERGY TOP RANGE A wide array of flexible solutions both for centralised residential application and big commercial plants The increasing need for

More information

Additional Cooling Stage (FT174-43) Adds the location points and plumbing for a fourth heat exchanger.

Additional Cooling Stage (FT174-43) Adds the location points and plumbing for a fourth heat exchanger. Modules, Options and Accessories Options (to be defined at time of order) Flowmeter Option (FT174-40) The standard unit displays an estimated flow rate calculated from the feed pump speed. This is accurate

More information

DESIGN, MANUFACTURE AND TEST RESULTS OF THE VTCS CO 2 EVAPORATOR FOR THE LHCB EXPERIMENT AT CERN.

DESIGN, MANUFACTURE AND TEST RESULTS OF THE VTCS CO 2 EVAPORATOR FOR THE LHCB EXPERIMENT AT CERN. HEFAT2010 7 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 19-21 July 2010 Antalya, Turkey DESIGN, MANUFACTURE AND TEST RESULTS OF THE VTCS CO 2 EVAPORATOR FOR THE LHCB

More information

AVAILABILITY AND RELIABILITY OF CERN CRYOPLANTS

AVAILABILITY AND RELIABILITY OF CERN CRYOPLANTS AVAILABILITY AND RELIABILITY OF CERN CRYOPLANTS on behalf of the Cryogenics for Accelerator Group Accelerator Technology Department CERN, Geneva, Switzerland Outline Introduction Cryogenic systems layout

More information

EasiHeat Mechanical Installation and Commissioning Instructions

EasiHeat Mechanical Installation and Commissioning Instructions 2230050/2 IM-S27-05 CH Issue 2 EasiHeat Mechanical Installation and Commissioning Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation 6 Maintenance

More information

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller Mounting and Operating Instructions Electronics from SAMSON EB 5610 EN Firmware version 1.40 Edition December 2014 Controller

More information

DIGITAL MODULATING BOILERS

DIGITAL MODULATING BOILERS DIGITAL MODULATING BOILERS FOR HEATING AND SANITARY HOT WATER CMX15 CMX18 CM15 CM18 INSTALLATI INSTRUCTIS AND USER GUIDE Please read these instructions before installing or using this appliance for the

More information

CO 2 COOLING FOR THE LHCB-VELO EXPERIMENT AT CERN.

CO 2 COOLING FOR THE LHCB-VELO EXPERIMENT AT CERN. GL2008 8 th IIF/IIR Gustav Lorentzen Conference on Natural Working Fluids 7-10 September 2008 Copenhagen, Denmark Paper number: xxx CO 2 COOLING FOR THE LHCB-VELO EXPERIMENT AT CERN. B. Verlaat*, A. Van

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control.

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control. Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA 02717 The first totally integrated multiple boiler management control. USING THIS MANUAL USING THIS MANUAL A. INSTALLATION SEQUENCE Follow

More information

Development of a measurement and control system for a 10 K refrigerator based on Siemens PLC S7-300

Development of a measurement and control system for a 10 K refrigerator based on Siemens PLC S7-300 Development of a measurement and control system for a 0 kw@0 K refrigerator based on Siemens PLC S7-300 J Li,, L Q Liu, T Liu 3, X D Xu, B Dong, W H Lu, W Pan, J H Wu and L Y Xiong Key Laboratory of Cryogenics,

More information

SX65 and SX75. Electronic process controllers

SX65 and SX75. Electronic process controllers SX65 and SX75 Electronic process controllers A combination of simplicity and sophistication... The SX range of process controllers from Spirax Sarco has been designed after carefully considering both technical

More information

Spa Touch Control Panel with 2000, 2100 controllers. (Spa Owner s Manual insert)

Spa Touch Control Panel with 2000, 2100 controllers. (Spa Owner s Manual insert) Spa Touch Control Panel with 2000, 2100 controllers (Spa Owner s Manual insert) P.N. 7876B February 11, 2015 For Spas equipped with BP2000, BP2100 controllers and Spa Touch panel. Spa Touch Control Panel

More information

CERN SUMMER STUDENT REPORT. Gas Environment Recoverable Detection (GERD) HMI

CERN SUMMER STUDENT REPORT. Gas Environment Recoverable Detection (GERD) HMI CERN SUMMER STUDENT REPORT Gas Environment Recoverable Detection (GERD) HMI Mari-Liis Sillat National Institute of Chemical Physics and Biophysics (EE) Supervisor: Andromachi Tsirou CERN 2016 Introduction

More information

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way 1 CHAPTER I INTRODUCTION In the modern life, electronic equipments have made their way in to practically every part, which is from electronic gadgets to high power computers. Electronic components have

More information

Connections, displays and operating elements C D E G H. Installing the control unit

Connections, displays and operating elements C D E G H. Installing the control unit 1 2 3 GB Control unit 0-10 V REG-K/3-gang with manual mode Operating instructions Art. no. MTN646991 ¼ DANGER Risk of fatal injury from electrical current. All work on the device should only be carried

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU Moduflex Dry Air System Desiccant Air P3TJA13A1AN - P3TJA13A7AN EN USER GUIDE (Original Language) NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU LV LT RU SL TR MT CONTENTS 1 Safety Information...2 1.1

More information

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc Important Considerations When Selecting a Fan for Forced Air Cooling By: Jeff Smoot, CUI Inc Designing an appropriate thermal management solution requires a systemic approach; each component on a circuit

More information

Temperature Control of Heat Exchanger Using Fuzzy Logic Controller

Temperature Control of Heat Exchanger Using Fuzzy Logic Controller Vo1ume 1, No. 04, December 2014 999 Temperature Control of Heat Exchanger Using Fuzzy Logic Controller Aravind R. Varma and Dr.V.O. Rejini Abstract--- Fuzzy logic controllers are useful in chemical processes

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL Air curtains ROTOWIND, INVISAIR Please, read these instructions carefully before attempting installation SECURITY ADVISE SYMBOLS Attention, Danger, Safety

More information

CU 300 GRUNDFOS INSTRUCTIONS. Installation and operating instructions

CU 300 GRUNDFOS INSTRUCTIONS. Installation and operating instructions GRUNDFOS STRUCTIONS CU 300 Installation and operating instructions No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm Declaration of Conformity We Grundfos

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic and Seconscrew ranges Manufacturer Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg

More information

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator TECHNICAL GUIDE Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator The XPlorer Range XPlorer is a new range of analogue addressable detectors and interfaces developed for all who

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

OPERATION MANUAL. Daikin Altherma indoor unit EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1

OPERATION MANUAL. Daikin Altherma indoor unit EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1 OPERATION MANUAL EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1 EKHVMRD50+80ABV1 EKHVMYD50+80ABV1 CONTENTS Page 1. Definitions... 1 2. Introduction... 2 2.1. General information... 2 2.2. Scope

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section CHLORINE GAS LEAK DETECTOR

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section CHLORINE GAS LEAK DETECTOR Section 11263 PART 1 GENERAL 1.01 SUMMARY This Section includes the furnishing and installation of chlorine leak detectors as shown on Plans and specified herein. 1.02 MEASUREMENT AND PAYMENT No separate

More information

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

Microgrid Fault Protection Based on Symmetrical and Differential Current Components Microgrid Fault Protection Based on Symmetrical and Differential Current Components Prepared for Public Interest Energy Research California Energy Commission Prepared by Hassan Nikkhajoei and Robert H.

More information

SYNERGY IN LEAK DETECTION: COMBINING LEAK DETECTION TECHNOLOGIES THAT USE DIFFERENT PHYSICAL PRINCIPLES

SYNERGY IN LEAK DETECTION: COMBINING LEAK DETECTION TECHNOLOGIES THAT USE DIFFERENT PHYSICAL PRINCIPLES Proceedings of the 2014 10 th International Pipeline Conference IPC2014 September 29-October 3, 2014, Calgary, Alberta, Canada IPC2014-33387 SYNERGY IN LEAK DETECTION: COMBINING LEAK DETECTION TECHNOLOGIES

More information

SERVICE MANUAL New Electronic Cold Platform 2005.

SERVICE MANUAL New Electronic Cold Platform 2005. SERVICE MANUAL New Electronic Cold Platform 2005. All the parts included in this document are the property of Indesit Company S.p.A. All rights reserved. This document and the information it contains are

More information

TECHNICAL NOTICE GH/GHO/GAE V

TECHNICAL NOTICE GH/GHO/GAE V TECHNICAL NOTICE GH/GHO/GAE V1.0-02.14 INDUSTRIAL COOLING UNITS Identification Marksa SA Industrial cooling 39, avenue du Technicum CH-2400 Le Locle Version Date Modifications 1.0 14.02.14 First edition

More information

CU 300. Installation and operating instructions GRUNDFOS INSTRUCTIONS

CU 300. Installation and operating instructions GRUNDFOS INSTRUCTIONS GRUNDFOS STRUCTIONS CU 300 Installation and operating instructions No contact Overvoltage Undervoltage Dry running Speed reduction Overtemperature Overload Sensor alarm Other languages www.grundfos.com/cu300-manual

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Air curtain SMART

INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Air curtain SMART INSTALLATION, OPERATION AND MAINTENANCE MANUAL Air curtain SMART Read instructions carefully before attempting installation. Deliver this manual to end user. SECURITY ADVISE SYMBOLS Attention, Danger,

More information

FPIAA - Find Persons Inside Atlas Areas A system for finding and rescuing persons in a very large physics experiment

FPIAA - Find Persons Inside Atlas Areas A system for finding and rescuing persons in a very large physics experiment FPIAA - Find Persons Inside Atlas Areas A system for finding and rescuing persons in a very large physics experiment Gianpaolo Benincasa, CERN-Geneva-Switzerland Carlos Cardeira, David Claudino, IDMEC/IST,

More information

2 Overview of the Pixel Detector Control System

2 Overview of the Pixel Detector Control System Towards a Detector Control System for the ATLAS Pixel Detector S. Kersten, K.H. Becks, M. Imhäuser, P. Kind, P. Mättig, J. Schultes Fachbereich Physik Bergische Universität D-4097 Wuppertal 1 Abstract

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

APC BC300 Series 40kW 208/450/480V User Guide

APC BC300 Series 40kW 208/450/480V User Guide APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank

More information

EUROPEAN LABORATORY FOR PARTICLE PHYSICS LABORATOIRE EUROPEEN POUR LA PHYSIQUE DES PARTICULES

EUROPEAN LABORATORY FOR PARTICLE PHYSICS LABORATOIRE EUROPEEN POUR LA PHYSIQUE DES PARTICULES EUROPEAN LABORATORY FOR PARTICLE PHYSICS LABORATOIRE EUROPEEN POUR LA PHYSIQUE DES PARTICULES CERN-ST-99-035 February, 1999 SAFETY ALARMS AND EUROPEAN STANDARDS R. Nunes Abstract This paper describes the

More information

Energy Commander Paralleling Switchgear

Energy Commander Paralleling Switchgear GE Consumer & Industrial Power Quality Energy Commander Paralleling Switchgear Paralleling Switchgear Paralleling is an operation in which multiple power sources, usually two or more generator sets, are

More information

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION Generals Caccialanza & C. developed in the last years some technologically very innovative products, aimed to provide a very

More information

Real Time Pipeline Leak Detection on Shell s North Western Ethylene Pipeline

Real Time Pipeline Leak Detection on Shell s North Western Ethylene Pipeline Real Time Pipeline Leak Detection on Shell s North Western Ethylene Pipeline Dr Jun Zhang & Dr Ling Xu* REL Instrumentation Limited ABSTRACT In the past ten years, a number of pipeline leak detection systems

More information

CRIMSON & CRIMSON MAX

CRIMSON & CRIMSON MAX High efficiency water/water and geothermal heat pumps 5 114 General High efficiency water/water and geothermal heat pumps. Ideal for heating, cooling and production of domestic hotwater with total or partial

More information

Installer Manual KNX Touchscreen Thermostat

Installer Manual KNX Touchscreen Thermostat Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY

More information

Bench Model of Electrical Control System for Inflatable Hemi- Spherical Structure

Bench Model of Electrical Control System for Inflatable Hemi- Spherical Structure Bench Model of Electrical Control System for Inflatable Hemi- Spherical Structure Sunil Kumar *, R. Shyam **, Amitabha Pal, P.Bala Subramaniam,,Narendra Singh Aerial Delivery Research & Development Establishment,

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

AmpLight group management

AmpLight group management AmpLight System Guide AmpLight group management Table of Contents System description.... 3 Benefits...4 Features....4 Central dimming....5 Benefits....5 Features....5 AmpLight Modules...6 Coded mains...8

More information

Wood Boiler Plumbing Schematics

Wood Boiler Plumbing Schematics Wood Boiler Plumbing Schematics Solo Plus Froling FHG Solo Innova Excel Multi-Fuel 2 TABLE OF CONTENTS Section Page 1.0 Introduction..4 2.0 Plumbing Diagrams....5 2.1 Plumbing Example-Solo/Excel 1........5

More information

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

CBU144. Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717. Product specification sheet

CBU144. Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717. Product specification sheet CBU144 Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717 Product specification sheet Version The Compact Booster Unit consists of the following modules, that

More information

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY AUTOMATIC BURNER CONTROL SYSTEM The burner control unit Quad400 is suitable for the control of direct ignition burners up to 350 kw, pursuant to EN 746-2. Flame control by means of UV scanner or ionization

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

Substation Monitoring System

Substation Monitoring System Substation Monitoring System SF6 Gas Density Monitoring System Description Introduction As a result of recent European legislation on the control of greenhouse gasses, utilities and manufacturers alike

More information

PASSIVE HEAT EXCHANGER ANTI-FOULING FOR SOLAR DHW SYSTEMS

PASSIVE HEAT EXCHANGER ANTI-FOULING FOR SOLAR DHW SYSTEMS Proceedings of ISEC 2005 2005 International Solar Energy Conference August 6-12, 2005, Orlando, Florida, USA ISEC2005-76232 PASSIVE HEAT EXCHANGER ANTI-FOULING FOR SOLAR DHW SYSTEMS Stephen J. Harrison

More information

Procedure for the Approval of New Fire Detection and Alarm Technologies

Procedure for the Approval of New Fire Detection and Alarm Technologies VdS Guidelines for Automatic Fire Detection and Fire Alarm Systems VdS 3469en Procedure for the Approval of New Fire Detection and Alarm Technologies VdS 3469en : 2016-01 (01) Publisher and publishing

More information

DELOMATIC 400, DM-400 HYDRO

DELOMATIC 400, DM-400 HYDRO Delomatic 400 HYDRO controller OPERATOR S MANUAL DELOMATIC 400, DM-400 HYDRO Functional description User interface Log books Alarm handling Document no.: 4189340880A SW version 1.0 or later Table of contents

More information

Burner control units BCU 560, 565

Burner control units BCU 560, 565 Burner control units BCU 560, 565 roduct brochure GB 6 Edition 05.15 For monitoring and controlling modulating or staged burners for multiple burner applications with a central air supply For directly

More information

Performance Analysis of the AD Detector Control System in the ALICE Experiment

Performance Analysis of the AD Detector Control System in the ALICE Experiment Performance Analysis of the AD Detector Control System in the ALICE Experiment XXXI Annual Meeting Division of Particles and Fields of the Mexican Physical Society Juan Carlos Cabanillas Noris For the

More information

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS.

CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS. CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS Table of Contents 2.A.1 SCADA Standards 2.5-2 2.A.1.1 Generators 2.5-2 2.A.1.2 Building

More information

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch. Training Title ADVANCED GC PROCESS Training Duration 5 days Training Venue and Dates Advanced GC Process 5 17 21 February, 2019 $4,000 Dubai, UAE Trainings will be conducted in any of the 5 star hotels.

More information

Metering systems 0548EN April 2014

Metering systems 0548EN April 2014 08EN April 0 0U8 GEY - Y - Y (GE- series) 900 000/ 00 00A/ 800 00L/ Versions and product codes Product code Type Heat exchanger nominal power GEY, - GEY and production GEY and production Table - Product

More information

REVO JOB INSTALLATION AREA. REVO Job SELECTION TABLE MAIN FEATURES OF THE PRODUCT PROFESSIONAL. CE marking. Automatic filter cleaning

REVO JOB INSTALLATION AREA. REVO Job SELECTION TABLE MAIN FEATURES OF THE PRODUCT PROFESSIONAL. CE marking. Automatic filter cleaning REVO JOB Revo Job is the new Sistem Air vacuum unit designed for intensive use in tertiary and professional areas. The main features of this product are simplicity, reliability and a great vacuum power.

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

Laboratory Freeze Dryer CRYODOS

Laboratory Freeze Dryer CRYODOS MAINTENANCE MANUAL Laboratory Freeze Dryer CRYODOS CRYODOS_I_rev005MA Telstar Industrial, S.L. Josep Tapiolas, 0 086 TERRASSA (Spain) Tel. +34 937 36 6 00 Fax: +34 937 85 93 4 telstar@etelstar.com www.etelstar.com

More information

Effective Alarm Management for Dynamic and Vessel Control Systems

Effective Alarm Management for Dynamic and Vessel Control Systems DYNAMIC POSITIONING CONFERENCE October 12-13, 2010 OPERATIONS SESSION Effective Alarm Management for Dynamic and Vessel Control Systems By Steve Savoy Ensco Offshore Company 1. Introduction Marine control

More information

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS CONTENTS 1. System Overview 2. User responsibilities 3. First Line controls and indications 3.1 Logging on to the fire alarm system 3.2 Checking system status

More information

Manual No: Revision: G. Sensor Products. Application Guide

Manual No: Revision: G. Sensor Products. Application Guide Manual No: 577013-750 Revision: G Sensor Products Application Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

1U ULTRA Compact System

1U ULTRA Compact System en atel Supervisory Module SM32 Load 60 00 A IE C60947-2 G B140 4 8.2 CHNT NB1-63 C32 23 0/40 0 V e NaT el OK enatel RM 1848 enatel RM 1848 Battery 60 00A IE C60947-2 G B1 4 04 8.2 CHNT NB 1-63 C32 23

More information

Speed and Frequency Seite 1 von 7

Speed and Frequency Seite 1 von 7 Speed and Frequency Seite 1 von 7 E16 Systems for High Safety Speed ing, all with Triple Modular Redundancy. A choice of versions to meet various demands. Compliant with SIL3 / IEC 61508 and/or API 670.

More information

Compact Muon Solenoid Detector (CMS) & The Token Bit Manager (TBM) Alex Armstrong & Wyatt Behn Mentor: Dr. Andrew Ivanov

Compact Muon Solenoid Detector (CMS) & The Token Bit Manager (TBM) Alex Armstrong & Wyatt Behn Mentor: Dr. Andrew Ivanov Compact Muon Solenoid Detector (CMS) & The Token Bit Manager (TBM) Alex Armstrong & Wyatt Behn Mentor: Dr. Andrew Ivanov CERN Conseil Européen pour la Recherche Nucléaire (European Council for Nuclear

More information

DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override

DHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override Date Code - Data rochure oiler Control 265 D 265 10/03 The tekmar oiler Control 265 can control the supply water temperature on up to three modulating boilers based on outdoor temperature or setpoint requirements.

More information

Technical description. Atec.

Technical description. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

Simplex Panel Interface Guide

Simplex Panel Interface Guide Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.

More information

CTT8 TEMPERATURE MONITOR DEVICE

CTT8 TEMPERATURE MONITOR DEVICE INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible

More information

Fire Control Panel FS4000

Fire Control Panel FS4000 Fire Control Panel FS4000 INSTRUCTION MANUAL Revision 4/02.11 Contents 1. Introduction... 4 2. Terminology... 4 3. Function... 5 4. Technical features... 5 4.1 Fire alarm lines... 5 4.2. Current thresholds

More information

Refrigerant Recovery Machine. Model No Operating Manual

Refrigerant Recovery Machine. Model No Operating Manual Refrigerant Recovery Machine Model No. 25700 Operating Manual Safety Precautions WARNING : TO PREVENT PERSONAL INJURY AND / OR EQUIPMENT DAMAGE, CAUTION - Risk of injury. This equipment should only be

More information

ALARMING NEWS FROM INVENSYS PROCESS SYSTEMS, INC.

ALARMING NEWS FROM INVENSYS PROCESS SYSTEMS, INC. ALARMING NEWS FROM INVENSYS PROCESS SYSTEMS, INC. The Foxboro I/A Series and the newly developed and highly versatile I/A Series System Message Manager working in combination to meet all of your plant

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL Air Curtains MAX Please, read these instructions carefully before attempting installation SECURITY ADVISE SYMBOLS Attention, Danger, Safety Advice! Danger

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Fireye Flame Sensor Module CE Flameswitch, model MBCE-110/230FR Company: Fireye Derry, NH USA Contract Number: Q09/10-26 Report No.: FIR 09/10-26

More information

AUTOMATIC VACUUM UNIT

AUTOMATIC VACUUM UNIT USER MANUAL (REV. D) AUTOMATIC VACUUM UNIT Part No. / Art. Nr. / Réf.: 29726, 29736 1 1.INTRODUCTION A SAFETY REGULATIONS manual is delivered with this manual. MEANING OF THE PICTOGRAMS USED IN THIS MANUAL

More information

AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO)

AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO) AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO) Generals Innovating fire extinguishing system for tunnel fires, for fully automatic intervention

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL Air Curtains RUND Please, read these instructions carefully before attempting installation SECURITY ADVISE SYMBOLS Attention, Danger, Safety Advice! Danger

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information