Templifier Heat Recovery Water Heaters

Size: px
Start display at page:

Download "Templifier Heat Recovery Water Heaters"

Transcription

1 Catalog Cat Templifier-1 Templifier Heat Recovery Water Heaters Model TSC, Centrifugal, 3,000 to 24,000 MBH (880 to 7,000 kw) 1996 McQuay International

2 Table of Contents Introduction...3 Templifier Description...5 Model TSC Centrifugal...5 Application...10 General...10 Waste Heat Side...10 Water Heating Side...11 Controls...14 Environmental Impact...15 Economic Evaluation...16 Selection Procedure...17 Performance Data...18 Electrical Data...20 Physical Data...21 Dimensional Data...22 Sound Data...23 Options...23 Guide Specifications...25 Document Catalog Templifier-1 Issue Date November 2006 Replaces PM Templifier Manufactured in an ISO Certified Facility Initial Issue April 2000 "McQuay" is registered trademark of McQuay International 1996 McQuay International "Illustrations and information covers McQuay International products at the time of publication and we reserve the right to make changes in design and construction at anytime without notice" 2 Cat Templifier-1

3 Introduction What Is It? The Templifier Heat Pump Water Heaters are designed to economically turn waste heat into useful heat. They are nonreversible, water-to-water, Carnot cycle heat pumps utilizing centrifugal compressors and shell and tube heat exchangers. Waste heat is extracted from a fluid stream by cooling it in the evaporator, the compressor amplifies the temperature of the heat and the condenser delivers the heat to heating loads such as space heating and domestic hot water. Model TSC Templifiers are equipped with centrifugal compressors and are available in six different sizes, each with optional pass arrangements. Heating capacities range from 3,000 MBH to 24,000 MBH (880 to 7,000 kw) with hot water temperatures up to 140 F (60 C). How Does It Work? Commercial and institutional buildings throw away untold millions of BTUs of rejected heat from the air conditioning load to the atmosphere through their cooling towers. To obtain maximum efficiency from the chillers, the tower water temperature is maintained as low as possible (within certain operational limitations). The tower water temperature range of about 60 F to 95 F (15 C to 35 C) precludes the use of this warm water for other purposes such as domestic water and space heating. However, this heat can be recovered by cooling the stream of cooling tower waste heat in the Templifier evaporator. The waste heat is transferred to the refrigerant. The compressor increases the temperature and pressure of the refrigerant. This higher temperature heat is then transferred from the refrigerant to water flowing through the condenser and delivered to the heating load. Figure 1, Typical Templifier Flow Diagram COOLING TOWER HEATING LOAD SUPPLE- MENTAL HEATER 125 F (52 C) 135 F (57 C) CONDENSER 85 F (29 C) CONDENSER 95 F (35 C) EVAPORATOR 90 F (32 ) TEMPLIFIER 45 F (7 C) EVAPORATOR 55 F (13 C) CHILLER COOLING LOAD Cat Templifier-1 3

4 Where to Use Templifiers Building Types Applications Hotels/Motels Schools Space Heating Service Hot Water Health Care Food Service Outside Air Heating Laundries Athletic Facilities Nursing Homes Reheat Kitchens Resorts COP and the Multiplying Effect Coefficient of Performance (COP) is defined as the useful energy output of a Templifier divided by electric energy input, all expressed in the same units of measure. Put another way, 4 units of waste heat in, plus 1 unit of purchased electrical energy input equals 5 units of useful heat out - a COP of 5. Electric resistance heat has a COP of 1, buy 1 unit of electricity and you get one unit of heat out. In this example, the Templifier is 5 times more efficient. Why Consider a Templifier? The primary purpose of a Templifier is to heat water more economically than fossil fired boilers or electric resistance heaters. A secondary benefit is that a Templifier can off-load overloaded boilers and/or cooling towers thereby delaying or eliminating a capital expenditure required to increase their capacity. The Templifier is nothing more than an electric water heater with an attractive, higher COP than resistance heat, but it must be able to pay its own way by providing an acceptable Return On Investment (ROI) for the owner. Advantageous Job Conditions Certain job conditions will contribute to the economic viability of a Templifier: Relatively high fossil fuel costs and low electrical demand and energy costs. High heating and cooling load factors-a high number of hours of use. When recovering rejected heat from an air conditioning system, this means a long cooling season or high cooling internal loads. Heating requirements coincident with cooling load to minimize or eliminate storage requirements. Warm source water temperatures to maximize COP. 4 Cat Templifier-1

5 Templifier Description Model TSC Centrifugal The McQuay Centrifugal Compressor Templifier is based on the McQuay Distinction Series of water chillers in use around the world for over 40 years. Continuous research and development over this life span have produced one of the most efficient and reliable refrigeration machines available in the market today. Compressor Centrifugal compressor efficiency is a function of impeller design and application to the refrigeration system. McQuay gear drive centrifugal Templifiers provide a variety of tip speed ratios to permit selection of impellers for maximum efficiency over their entire part load to full load range and are ideal for 50 Hz application. Mechanical gear losses are limited by design standards to less than one-half of 1%. The variety of impeller speeds obtained by alternate gear selections make the McQuay compressor uniquely suited to the wide range of operating conditions encountered in heat pump water heating duty. The compressor can be specifically designed for job site conditions. A motor draws locked rotor current until it reaches approximately 80% of its running speed. While drawing locked rotor current the stresses on the motor are over six times that of full load. The McQuay compressors minimize this stress through the unique gear drive and light weight drive train that allows most compressors to reach running speed in less than six seconds. The motors are cooled by liquid refrigerant, a technique particularly well suited to heat pump duty. Lubrication System A separately driven electric oil pump assembly supplies lubrication at controlled temperature and pressure to all bearing surfaces and is the source of hydraulic pressure for the capacity control system. Figure 2, Lubrication System The control system will not allow the compressor to start until oil pressure at the proper temperature is established, and also allows the oil pump to operate after compressor shutdown to assure lubrication during coast down. Lubricant from the pump is supplied to the compressor through an external brazed-plate heat exchanger and internal 5 micron oil filter. All bearing surfaces are pressure lubricated. Drive gears are operated in a controlled lubricated mist atmosphere that efficiently cools and lubricates them. Lubricant is made available under pressure from the compressor oil filter to the unit capacity control system and is used to position the inlet guide vanes in response to changes in leaving condenser water temperature. If a power failure occurs, an emergency oil reservoir provides lubrication flow under pressure and prevents damage that could occur during the spin down period with the oil pump stopped. Cat Templifier-1 5

6 Shell-and-Tube Heat Exchangers McQuay Templifiers are equipped with new high performance heat exchangers. The unique design greatly increases heat transfer and reduces unit footprint and refrigerant charge compared to previous designs. In many cases vessel length has been reduced by 40 percent. Templifiers are designed, constructed and tested in accordance with ASME Section VIII and ASHRAE Standard 15 requirements. The replaceable water tubes are internally and externally enhanced copper and are mechanically bonded to steel tube sheets. Standard tubes are inch wall copper in the evaporator and condenser. Optional tubes include inch and inch in either vessels and 90/10 cupro-nickel, 304 stainless steel or titanium material. Clad tube sheets and epoxy coated heads are included when other than copper tubes are specified. Both vessels are available for 1, 2 or 3 pass water flow. A 3/4" thick vinyl/nitrate polymer condenser insulation is standard. All seams are glued to form an effective vapor barrier. Pumpdown Pumpout systems provide a means to collect and contain the refrigerant charge with minimum loss, when the access to internal components is required for service. McQuay condensers are sized to hold the entire unit refrigerant charge when not more than 90% full at 90 F (32 C) ambient temperature. They are equipped with a tight-seating check valve at the hot gas inlet and a manual shutoff valve in the liquid outlet. These valves, coupled with the condenser design, satisfy the stringent requirements of the U.S. Department of Transportation for refrigerant shipping containers, as well as ASME vessel codes. When service is required, the refrigerant charge may be pumped down into the condenser by compressor operation and use of a refrigerant transfer unit. Elimination of the cost and space requirements of an external pumpout system is a major McQuay advantage. Templifiers Feature MicroTech II Controls McQuay has incorporated the latest microprocessor technology into the MicroTech II control system to give you the ultimate in unit control. The control includes many energy-saving features to keep your unit running efficiently. day in, day out, for years to come. Figure 3, Unit Controller and Operator Interface Touch Screen The unit controller and operator interface touchscreen mounted on a Templifier unit are shown to the right. The 12-inch VGA touch screen is on an adjustable arm so that it can be positioned comfortably for each operator. The unit control panel contains a USB port from which trend data and manuals can be conveniently downloaded. All-important unit operating data is easily accessed and viewed. Password protected unit setpoints, complete with description and setting range, are available at the touch of a screen. 6 Cat Templifier-1

7 Figure 4, Compressor Controller A major feature of the MicroTech II controller, as applied to water heaters, is the distributive control scheme. The picture to the right shows the compressor control panel (with cover removed) mounted at the rear of the unit, adjacent to the compressor itself. This panel also contains the oil pump contactor and overload. Also on the plan (control network) is the unit controller and operator interface touch screen. If the interface touch screen and/or unit controller is out of service, the uinit can continue to operate on the compressor controller alone. This feature provides unprecedented reliability in a control system. MicroTech II Features and Benefits FEATURE Easy integration into a building management system via McQuay s exclusive Protocol Selectability feature. Easy to read, adjustable, 12-inch, Super VGA color touchscreen operator interface Historic trend data-can be downloaded from a USB port Precise ± 0.2 F chilled water control Proactive pre-shutdown correction of unusual conditions allows unit to stay online Automatic control of hot water and source water pumps, if desired Twenty-five previous alarm descriptions are stored in memory Multiple language capability Metric or in-lb units of measure BENEFIT Designer can to select any BAS supplier using industry standard protocols and know the MicroTech II control will easily interface directly with it. Operators can observe chiller operation at a glance, easily select various detail screens and change setpoints Water temperatures, refrigerant pressures, and motor load plots can provide valuable unit operation data Provides stability in chilled water system Activates alarm and modifies chiller operation to provide maximum possible cooling Integrated lead/lag and automatic engagement of backup pump Invaluable asset in troubleshooting Great asset for world-wide applications Designed with the System Operator in Mind Reliable, economic use of any unit depends largely on an easy operator interface. That s why operation simplicity was one of the main considerations in the development of the MicroTech II controller. The operator interface with the unit is a 12-inch, Super VGA color touch-screen. The operator can clearly see the entire unit graphically displayed, with key operating parameters viewable on the screen. Other screens, such as alarm history and set points, are easily accessed through touch screen buttons. Cat Templifier-1 7

8 We have even gone as far as installing the unit operating and maintenance manual, as well as the parts list, in the chiller s microprocessor memory, so that they are viewable on the touchscreen or can be downloaded to a computer through the onboard USB port. Proactive Control By constantly monitoring unit status, the MicroTech II controller will automatically take proactive measures to relieve abnormal conditions or shut the unit down if a fault occurs. For example, if a problem occurs in the source water and suction pressure starts to rise, the controller will automatically hold the load point and activate an alarm signal. A further drop in pressure will initiate compressor unloading in an effort to maintain the setpoint pressure. If the pressure continues to drop, the unit will shut off at the cutout pressure setting. Alarm History for Easy Troubleshooting The MicroTech II controller's memory retains a record of faults and a time/date stamp. The controller's memory (no batteries required) can retain and display the cause of the current fault and the last twenty-five fault conditions. This method for retaining the fault is extremely useful for troubleshooting and maintaining an accurate record of unit performance and history. The MicroTech II controller features a three-level password security system to provide protection against unauthorized use. Figure 5, MicroTech II Controller Home Screen The Home Screen shown above is the primary viewing screen. It gives real time data on unit status, water temperatures, chilled water setpoint and motor amp draw. This display answers the vital question-is the chiller doing what it is supposed to be doing? 8 Cat Templifier-1

9 If an alarm occurs, a red button appears on the screen (a remote signal is also available). Pressing this button accesses the Active Fault Screen that gives complete fault information. The fault can be quickly and easily cleared at this point. Changing Setpoints Changing setpoints is easy with the McQuay MicroTech II control. For example, to change the hot water set point, press SET from any screen, then press the WATER button and this screen appears, press button #1, Leaving Water Temperature, and you are ready to input a password and then a new value. Trend Logging Ever wonder how your unit performed last week? Were you holding the correct hot water temperature? What kind of heating load did the chiller have? The McQuay MicroTech II controller can provide the answers, thanks to its huge memory, and plot water temperatures, refrigerant pressures, and motor load data. These values can also be downloaded through a convenient USB port, located in the unit control panel, and pasted into a spreadsheet for archiving or further detailed evaluation. MicroTech II Controller Increases Chiller Operating Economy Many standard features have been incorporated into MicroTech II control in order to maintain the operating economy of McQuay Templifiers. In addition to replacing normal relay logic circuits, we ve enhanced the controller's energy saving capabilities with the following features: User-programmable compressor soft loading. Prevents excessive power draw during pull down from high chilled water temperature conditions. Demand limit control. Maximum motor current draw can be set on the panel, or can be adjusted from a remote 4-20ma or 1-5 VDC BAS signal. This feature controls maximum demand charges during high usage periods. Plotting Historic Trends. Past operation of the chiller can be plotted as trend lines and even downloaded to spread sheets for evaluation - a valuable tool for optimizing efficiency. Cat Templifier-1 9

10 Application General A Templifier unit is controlled by the heating load as sensed at either the entering or leaving hot (condenser) water temperature. The amount of cooling done in the evaporator is uncontrolled and is a result of the amount of cooling required to meet the heating load. If there is insufficient waste heat for the unit to meet the heating load, the Templifier will begin to pull down the waste heat temperature, i.e. the evaporator water temperature will drop. Templifiers are equipped with a low source water temperature over-ride control feature. The control unloads the unit to prevent the leaving evaporator temperature from falling below a predetermined setpoint. This occurrence basically means that there is insufficient waste heat to support the heat load requirements. Consequently the hot water temperature will fall since the heating load is larger than the Templifier's reduced output. Supplementary heat is activated at this point to make up the heat difference. This is an important concept. The heating load requirements over time, the concurrent availability of waste heat, and the size and control of a supplementary heat must be coordinated. Waste Heat Side Cooling Tower Water Most commercial and institutional heat pump applications use condenser outlet water for a heat source. Some points to remember: The condenser water from the air conditioning system (waste heat source) is from an open system using treated water. This water flows through the tube side of the evaporator of a centrifugal Templifier (Model TSC) and is subject to the same fouling (and attendant required maintenance) as a chiller condenser. The Templifier will often utilize only a portion of the entire tower water flow and require a bypass during normal operation. It is recommended that all installations have a tower water bypass around the Templifier evaporator so that the chiller plant can remain operational in the event of Templifier evaporator servicing. (See Figure 1.) Cooling tower systems are usually designed with 95 F (35 C) entering to 85 F (29.4 C) leaving water temperatures. These temperatures will vary somewhat in areas with unusually high or low wet bulb temperatures. Air conditioning chillers are then designed to operate in this environment as the worst or most severe condition. The cooling tower water temperature is allowed to drop as lower wet bulb temperatures become available. This is good practice since chiller efficiency improves. Important Note: These lower than design condenser water temperatures must be accounted for when selecting a Templifier. The Templifier must be selected to operate at the lowest expected water temperature leaving the air conditioning condenser during Templifier operation. However, the COP used for economic evaluations should be based on a weighted average source water temperature. 10 Cat Templifier-1

11 Geothermal, Warm Ground Water Sufficient quantities of warm ground water are available in some locations to act a heat source. To maximize COP, use as high a quantity of ground water as possible considering the following: Flow capability of the Templifier evaporator. Quantity of water available and disposal considerations. Pump power Ground water may contain: Particulate matter (sand, mud) that should be filtered out Corrosive elements that may require special evaporator materials or an intermediate heat exchanger High mineral content that can cause scaling. This will require a de-scaling maintenance program or an intermediate heat exchanger as shown in Figure 6. Figure 6, Intermediate Heat Exchanger Solar Collectors Templifiers can be mated with solar collector arrays to great advantage. The collectors do not have to be designed to provide the required use temperature. Instead, the collectors provide heat to the Templifier evaporator and the Templifier amplifies the solar heat to the use temperature. This allows utilizing solar heat as low 50 F (10 C) to provide hot water output up to 140 F (60 C) for TSC units. This temperature amplification reduces the number of expensive collectors required and/or allows more BTUs to be collected from an existing array. Water Heating Side General recommendations for the hot water side of the Templifier system: The lowest possible hot water temperature should be selected in order to maximize the unit COP. Booster heaters should be employed for open systems such as laundry or dishwashing water that have temperature requirements higher than the Templifier's capability. Supplementary heaters are usually required in case the heat pump is unavailable or there is insufficient waste heat available. Templifiers can be controlled by either the entering or leaving hot water temperature. Higher COPs and better unloading can be achieved when the entering water temperature is controlled. This method is especially recommended for space heating where it essentially provides hot water reset since the hot water temperature to the heating load decreases as the load decreases. Cat Templifier-1 11

12 Service Hot Water Service hot water system will invariably use a storage tank due to the large variation in demand. Large buildings will use a recirculating hot water system to provide instant hot water at the point of use. The Templifier can be incorporated into the system as shown in Figure 7. Temperature control should be on the leaving water temperature in order to maintain tank temperature. The tank temperature should be as low as possible, usually 120 F (49 C) for lavatory, tub, and shower use and 140 F (60 C) for kitchen use. Supplementary/standby heat should be provided in case the Templifier is off-line or there is insufficient source heat to maintain the setpoint temperature. A Templifier used for both service water heating and space heating should employ an intermediate heat exchanger between the service water system and the unit. Some local codes may require an additional heat transfer surface (heat exchanger) between the refrigerant and potable water. Figure 7, Service Hot Water T-C 140 F (60 C) HEAT SOURCE CONDENSER EVAPORATOR TEMPLIFIER OUTPUT 140 F (60 C) STORAGE TANK 140 F (60 C) RETURN / MAKEUP STANDBY / AUXILIARY HEAT Space Heating/Reheat A key consideration on space heating applications is the simultaneous occurrence of a heating load and the availability of waste heat presumably from the air conditioning system. This condition usually occurs in buildings with a large core zone and buildings using reheat or multizone air handlers. Water source heat pumps can provide an excellent Templifier environment and are treated in a separate section. Return water control is usually used on space heating applications. By holding the condenser entering temperature constant, the leaving water temperature going to the load will decrease with decreasing heating load. Care must be exercised in placement of the supplemental heater temperature sensor so that the heater does not override the Templifier. See Figure 8. Figure 8, Return Water Control 12 Cat Templifier-1

13 Outside Air Heating Templifiers are well suited to heating outside air because of the relatively low air temperature requirements. It is imperative that precautions be taken to prevent freezing the coil. Even though mixed air temperatures can be above freezing or even at setpoint shutting off water flow, cold air can stratify at the bottom of the heating coil and freeze the coil. Figure 9, Outside Air Heating Figure 9 illustrates a method of using a continuously running small circulating pump and three-way valve (twoway valve can also be used) to provide full water flow to the coil at all times. The flow switch overrides normal control and throws the control valve to full open preventing freeze-up. Overheating of the air will result. Power failure or operator error can defeat this protective arrangement. Water-Loop Heat Pump Systems Unitary water-source heat pumps (WSHP) in closed water loops have proven to be a flexible and efficient system for many buildings, especially offices, schools, health care facilities and hotels. These systems should be balanced in regard to the disposition of heat, i.e. not throwing away any heat that can be recovered and used somewhere, somehow in the building. Furthermore, when there is truly excess heat, thought should be given to storing it for later use. Typically, excess heat can be generated during the day and used at night when the net building load requires heat input. The Templifier can be used to advantage in WSHP systems by recovering low grade heat that would otherwise be rejected and increasing its temperature to a useful level. This high grade heat can be: Stored up to 140 F (60 C) for TSC units during periods of excess heat, usually daytime hours, and used as a heat source when heat input into the system is required, usually at night. A conventional storage tank in the main loop has to be excessively large since it is limited to the min/max loop temperature, usually 60 F to 90 F (15 C to 32 C). Used instantaneously for other building heating loads such as domestic hot water, reheat, and make-up air heating. Figure 10 illustrates how to place the Templifier Heat Pump in the WSHP system. Controls are usually set so that: The water heater will come on to control a minimum of 60 F (15 C) loop temperature. The heat rejection device will come on to control a maximum of 90 F (32 C) loop temperature. The Templifier will cycle and load in response to its heating load but also have an evaporator leaving water temperature override to prevent cooling the loop below 63 F (17 C). This eliminates the possibility of the Templifier subcooling the loop below the minimum loop temperature. Cat Templifier-1 13

14 Figure 10, Water Source Heat Pump System Controls Templifiers are controlled by the heating load as sensed by changes in the entering or leaving condenser water temperature. Usually on space heating applications and anywhere else possible, the sensor should be in the entering condenser water. The entering temperature is held constant and the leaving temperature floats with the load. Thus at low loads the leaving condenser water temperature is low and the head imposed on the compressor is minimized. This maximizes the unit COP and provides a more stable environment for centrifugal compressor operation. Templifiers provide heat to a heating load by extracting heat from a waste heat stream by cooling it. If there is insufficient waste heat with respect to the heating load, the temperature of the waste stream will be driven down, perhaps to unacceptable levels. For example, cooling tower water could be lowered to a point where the chillers will not operate properly and the air conditioning compromised. This is not acceptable. To avoid this, Templifiers are equipped with a source water temperature override control feature. The MicroTech control senses the leaving evaporator water temperature and unloads the Templifier when the override setpoint is reached. This decreases the unit's heating capability, the hot water loop temperature will start to drop, and the auxiliary heater will come on to make up the capacity difference. The Templifier is saying, "there is insufficient source heat for me to meet the heating load. I'm doing all I can but will need help from the auxiliary heater". 14 Cat Templifier-1

15 Environmental Impact The environmental impact of any process or equipment is vitally important today and will continue to be in the future. Templifier Heat Pump Water Heaters have some distinct advantages when it comes to their effect on our environment. Environmental impact is measured in several ways: ODP-Ozone Depletion Potential; measures the impact of a substance on the depletion of the ozone layer in the upper atmosphere. With refrigerants, this action is caused by chlorine. HFC-134a contains no chlorine and has a zero ODP. GWP-Global Warming Potential; measures the contribution of a substance to the greenhouse gas effect which causes global warming. This is a pound to pound comparison, discounting the application of the substance and any other effects caused by its use. The number, relative to CO 2 for a 100 year integration time horizon is HFC- 134a=1300. TEWI-Total Equivalent Warming Impact; is a combination of the refrigerant GWP, unit refrigerant emissions rate, and the refrigeration system s energy efficiency. Science has agreed that a systems approach is necessary to evaluate the real effect of a substance on global warming. This is TEWI. In a Templifier, the contribution of the refrigerant GWP is insignificant when compared to the effect of a unit s power needs translated to power plant CO 2 emissions. The percentages shown on the right will vary slightly depending on unit refrigerant loss and on the efficiency of local power generation. Equipment operators should keep equipment leak free (minimize the 2% segment) and operate as efficiently as possible (minimize the 98% segment). The significant influence in establishing the TEWI of a hot water plant is the system used to produce the heat, as illustrated in the following examples. Compare the fuel burned (products of combustion) to produce one million BTUs of hot water at 120 F. Electrical Resistance Heater 6 6 Heater 293 kw T & D 308 kw Power 3 x 10 BTU 100% Eff. 10 BTU Hot Water Network 95% Eff. Plant 35% Eff. Fuel Use On-Site Fossil-Fired Boiler 6 6 Boiler 1.25 x 10 BTU 10 BTU Hot Water 80% Annual Eff. Fuel Use Templifier 6 Templifier T & D Power 6 42 kw 44 kw.43 x 10 BTU COP = 7 10 BTU Hot Water Waste Heat 6.78 x 10 BTU Network 95% Eff. Plant 35% Eff. Fuel Use Compared to a Templifier, a resistance heater burns seven times the fuel quantity and an on-site boiler consumes three times the amount. The Templifier is a clear winner when it comes to keeping the planet green. Cat Templifier-1 15

16 Economic Evaluation Introduction Since Templifiers are often purchased on the basis of their economic viability, economic evaluations should be as accurate as possible. The annual heat output of the Templifier depends on the heating load profile and the coincident availability of waste heat, usually from the chilled water plant condenser water. Evaluation Data The following information will assist in making a reliable evaluation: The daily heating load profile. The cooling load profile as far as the availability of waste heat from the air conditioning system's condenser water. The temperature of the condenser water is important. During periods of cool ambient temperatures the cooling tower will supply water colder than design conditions. The Templifier will consequently be operating with source water at lower than design temperature. This will result in a lower COP for the Templifier but a better efficiency for the chiller which usually has the larger electric load. The COP will usually be fluctuating over the course of the day and season. When the cooling load is large compared to the Templifier waste heat requirement, a cursory examination may be sufficient. The cost of fossil fuel used to fire the boiler that the Templifier will be replacing (or electricity if resistant heaters are used). The cost of electricity to operate the Templifier. The Templifier installed cost. If the need for other equipment (such as additional cooling tower or boiler) is eliminated because of the Templifier, the avoided cost saving should be credited against the Templifier cost. Financial information such as actual tax rate, cost of capital, analysis period and the owner's threshold payback or Return on Investment. 16 Cat Templifier-1

17 Selection Procedure Due to the large number of centrifugal component combinations available, units are selected on a computer program. The selections contained in Table 1 (60 Hertz) and Table 2 (50 Hertz) are for the specific flows and temperatures shown. The indicated performance is correct for these conditions and can also serve as an approximate guide for other conditions of service. The ratings are based on entering evaporator source water temperature, not leaving. Both evaporator and condenser are based on an approximate 10 degree F temperature range. 1. If job conditions have more source water available than the quantity show in the TSC Performance Tables, the evaporator leaving water temperature will be higher than used for the selection and the unit COP will improve. 2. If job conditions have less source water available than the quantity show in the TSC Performance Tables, the evaporator leaving water temperature will be lower than used for the selection and the unit COP will be lower than that shown. 3. If job conditions have hot condenser water flows within about 50% of the quantities shown, the unit performance will be close to that shown. Water pressure drops for the heat exchangers and flows shown in the Performance Tables are all less than 10 psi. Consult the local McQuay sales office for unit performance outside that given in the Performance Tables. Cat Templifier-1 17

18 Performance Data Table 1, Heating Capacities and Heating COP, 60 Hz Compressor Vessel Flow Gpm Entering Source Temp. F TSC E2612-CE C2212-CN TSC E3012-BE C2612-DN TSC E4212-CE C3612-CN TSC E4212-BE C3612-CN TSC E4812-CE C3612-BN Heating Capacity Tons Condenser Leaving Hot Water Temperature 110 F 120 F 130 F 140 F Input kwi COP Heating Capacity Tons Input kwi COP Heating Capacity Tons Input kwi COP Heating Capacity Tons MAU 20U (RLA=248 Amps) MAR 35U (RLA=383 Amps) MAP 35U (RLA=439 Amps) JAL 35U (RLA=441 Amps) MAU 20U (RLA=257 Amps) MAR 35U (RLA=438 Amps) MAQ 35U (RLA=438 Amps) JAL 35U (RLA=441 Amps) MAU 20U (RLA=251 Amps) MAR 35U (RLA=438 Amps) MAQ 35U (RLA=438 Amps) JAL 35U (RLA=441 Amps) LBA 35U (RLA=451 Amps) LAY 47U (RLA=560 Amps) LAV 49U (RLA=605 Amps) LAV 49U (RLA=605 Amps) LBA 35U (R;A=464 Amps) LAY 47U (RLA=590 Amps) LAV 49U (RLA=605 Amps) LAV 49U (RLA=604 Amps) LBA 35U (RLA=457 Amps) LAY 47U (RLA=578 Amps) LAV 49U (RLA=605 Amps) LAV 49U (RLA=605 Amps) MBE 49U (RLA=629 Amps) MBC 57U (RLA=701 Amps) MBA 66U (RLA=701 Amps) Input kwi No Selection MBE 57U (RLA=701 Amps) MBC 57U (RLA=701 Amps) MBA 66U (RLA=700 Amps) MAW 66U (RLA=701 Amps) MBE 57U (RLA=701 Amps) MBD 57U (RLA=702 Amps) MBA 66U (RLA=700 Amps) MA2 66U (RLA=700 Amps) MBK 73U (RLA=941 Amps) MBH 85U (RLA=1098 Amps) MBG K0U (RLA=1165 Amps) MBE N2U (RLA=1384 Amps) MBK 73U (RLA=936 Amps) MBH K0U (RLA=1167 Amps) MBG K0U (RLA=1278 Amps) MBE N2U (RLA=1501 Amps) MBK 73U (RLA=913 Amps) MBH K0U (RLA=1214 Amps) MBG K0U (RLA=1246 Amps) MBE N2U (RLA=1500 Amps) MBT N2U (RLA=1291 Amps) MBR N3U (RLA=1523 Amps) MBP N3U (RLA=1523 Amps) MBL N3U (RLA=1523 Amps) MBT N2U (RLA=1483 Amps) MBR N3U (RLA=1523 Amps) MBP N3U (RLA=1523 Amps) MBL N3U (RLA=1523 Amps) MBT N2U (RLA=1501 Amps) MBR N3U (RLA=1523 Amps) MBP N3U (RLA=1523 Amps) MBL N3U (RLA=1523 Amps) NOTES: 1. Capacity in condenser tons 2. COP=(condenser tons)(12,000) / (kw)(3415) 3. Evaporator tons=(cop-1 / COP)(condenser tons) 4. Delta-T=(tons)(24) / GPM 5. Alpha characters in table such as MBT N2U are compressor and motor ordering codes. COP 18 Cat Templifier-1

19 Table 2, Heating Capacities and Heating COP, 50 Hz Compressor Vessel Flow Gpm Evaporator Entering Source Temp. F ( C) TSC (23.9) E2612-CE (29.4) C2212-CN (35.0) TSC (23.9) E3012-BE (29.4) C2612-DN (35.0) TSC (23.9) E4212-CE (29.4) C3612-CN (35.0) TSC (23.9) E4212-BE (29.4) C3612-CN (35.0) TSC (23.9) E4812-CE (29.4) C3612-BN (35.0) Heating Capacity Tons Condenser Leaving Hot Water Temperature 110 F (43.3 C) 120 F (48.9 C) 130 F (54.4 C) 140 F (60.0 C) Input kwi COP Heating Capacity Tons Input kwi COP Heating Capacity Tons Input kwi COP MAN20F (RLA=265 Amps) MAK31F (RLA=367 Amps) MAH35F (RLA=442 Amps) Heating Capacity Tons Input kwi No Selection MAN20F (RLA=272 Amps) MAK31F (RLA=383 Amps) MAH35F (RLA=444 Amps) MAG35F (RLA=417 Amps) MAN20F (RLA=265 Amps) MAK31F (RLA=375 Amps) MAH35F (RLA=440 Amps) MAG35F (RLA=436 Amps) LAU41F (RLA=438 Amps) LAR45F (RLA=555 Amps) LAR49F (RLA=582 Amps) LAP49F (RLA=621 Amps) LAU41F (RLA=490 Amps) LAR49F (RLA=618 Amps) LAR49F (RLA=619 Amps) LAP49F (RLA=622 Amps) LAU41F (RLA=479 Amps) LAR49F (RLA=620 Amps) LAR49F (RLA=616 Amps) LAP49F (RLA=613 Amps) MAW57F (RLA=679 Amps) MAW57F (RLA=678 Amps) MAU62F (RLA=681 Amps) No Selection MAW57F (RLA=679 Amps) MAW57F (RLA=679 Amps) MAU62F (RLA=681 Amps) MAQ62F (RLA=688 Amps) MAW57F (RLA=679 Amps) MAW57F (RLA=679 Amps) MAU62F (RLA=681 Amps) MAQ62F (RLA=688 Amps) MBC85F (RLA=964 Amps) MBCN0F (RLA=1037 Amps) MBAN0F (RLA=1183 Amps) MB2N1F (RLA=1438 Amps) MBC85F (RLA=1030 Amps) MBCN0F (RLA=1166 Amps) MBAN0F (RLA=1327 Amps) COP MA2N1F (RLA=1426 Amps) MBCN0F (RLA=1155 Amps) MBCN0F (RLA=1233 Amps) MBAN0F (RLA=1302 Amps) MA2N1F (RLA=1387 Amps) MBKN2F (RLA=1530 Amps) MBKN2F (RLA=1530 Amps) MBHN2F (RLA=1531 Amps) MBEN2F (RLA=1530 Amps) MBKN2F (RLA=1530 Amps) MBKN2F (RLA=1530 Amps) MBHN2F (RLA=1530 Amps) MBEN2F (RLA=1510 Amps) MBKN2F (RLA=1530 Amps) MBKN2F (RLA=1531 Amps) MBHN2F (RLA=1531 Amps) MBEN2F (RLA=1530 Amps) NOTES: 1. Capacity in condenser kw thermal 2. COP=(condenser kw output) / (compressor kw input) 3. Evaporator kw=(cop-1 / COP)(condenser kw) 4. Delta-T=kW / (4.18 x L/s) 5. Alpha characters in table such as MBkN2F are compressor and motor ordering codes. Cat Templifier-1 19

20 Electrical Data Figure 11, TSC Field Wiring Diagram 20 Cat Templifier-1

21 Physical Data Table 3, TSC TSC 126 TSC UNIT SIZE TSC 063 TSC 079 TSC 087 TSC 100 TSC 126 COMPRESSOR Model CE 063 CE 079 CE 087 CE 100 CE126 Number Motor Speed 60/50 Hz 3550/ / / / /2960 CONDENSER Diameter/Length in./ft 22/12 26/12 36/12 36/12 36/12 mm/mm 559/ / / / /3658 Water Volume gal. (l) 76 (290) 111 (419) 234 (884) 234 (884) 234 (884) 2 Pass Connection Size in (mm) 8 (203) 8 (203) 12 (305) 12 (305) 12 (305) Working Press-Water, psi (kpa) 150 (1034) 150 (1034) 150 (1034) 150 (1034) 150 (1034) Working Press-Refrig, psi (kpa) 300 (2070) 300 (2070) 300 (2070) 300 (2070) 300 (2070) EVAPORATOR Diameter/Length in./ft 26/12 30/12 42/12 42/12 48/12 mm/mm 660/ / / / /3658 Water Volume gal. (l) 72 (273) 101 (381) 222 (841) 222 (841) 327 (1237) 2 Pass Connection Size in (mm) 8 (203) 10 (254) 14 (356) 14 (356) 18 (457) Working Press-Water, psi (kpa) 150 (1034) 150 (1034) 150 (1034) 150 (1034) 150 (1034) Working Press-Refrig, psi (kpa) 200 (1380) 200 (1380) 200 (1380) 200 (1380) 200 (1380) DIMENSIONS Length in. (mm) 169 (4293) 175 (4445) 175 (4445) 175 (4445) 175 (4445) Width w/ Starter in. (mm) 61 (1549) 71 (1803) 101 (2565) 107 (2718) Width w/o Starter in. (mm) 46 (1168) 56 (1422) 86 (2184) 86 (2184) 80 (2032) Height in. (mm) 80 (2032) 88 (2235) 111 (2819) 99 (2515) 99 (2515) WEIGHTS (w/ Starter) Shipping lb (kg) ( (7183) (11170) (13545) (15070) Operating lb (kg) (6358) (7938) (12892) (14270) (17610) WEIGHTS (w/o Starter) Shipping lb (kg) (5251) (6638) (10626) (12001) (14526) Operating lb (kg) (5678) (7394) (12349) (13726) (17066) Cat Templifier-1 21

22 Dimensional Data TSC MODEL TSC063/E2612/C2212 TSC079/E3012/C2612 TSC087/E4212/C3612 TSC100/E4212/C3612 TSC126/E4812/C3612 OVERALL LENGTH WIDTH CONNECTIONS CENTER OF 1&3 2 HEAD CONN HEIGHT W/O FOOTPRINT GRAVITY EVAP COND PASS PASS BOTH ENDS STARTER 2 2 A A A B C X Y Z D E F G PASS PASS (4293) (4166) (4293) (2032) (1219) (1753) (965) (533) (3759) (3683) (1219) (1016) (4445) (4267) (4445) (2235) (1422) (1778) (1041) (635) (3759) (3683) (1422) (1219) (4445) (4267) (4445) (2667) (2184) (1753) (1143) (889) (3759) (3683) (2184) (1981) (4445) (4318) (4445) (2515) (2184) (1753) (1168) (889) (3759) (3683) (2184) (1981) (4597) (4445) (4597) (2692) (2642) (1778) (1168) (1168) (3683) (3683) (2642) (2438) Cat Templifier-1

23 Sound Data Within a given size family the sound levels of McQuay Templifiers will vary as a function of impeller speed and other variables. The sound data in Table 4 is representative of the units shown and is the highest sound level expected for the TSC family size. The Range is the difference in sound level between the values shown and the lowest sound level expected for the unit size. Table 4, Sound Pressure at One Meter from Unit Envelope TSC Octave Band Sound Pressure Levels Per ARI Standard 575 (db) Overall "A" Model 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Weighted Range Options Vessels Marine water boxes Provides tube access for inspection, cleaning, and removal without dismantling water piping. Flanges (victaulic standard) ANSI raised face flanges on either the evaporator or condenser. Mating flanges are by others or in. tube wall thickness For applications with aggressive water conditions requiring thicker tube walls. Cupro-nickel or titanium tube material For use with corrosive water conditions, only available with clad tube sheets. Water side vessel construction of 300 psi (150 psi is standard) For high pressure water systems, typically high-rise building construction. Water flow or differential pressure switches A proof of flow device is mandatory in the water system. They can be field supplied, mounted and wired. This option provides them as a factory mounted and wired option. Double insulation, 1 ½ inch, on evaporator, suction piping, and motor barrel For high humidity locations and ice making applications. Electrical Optional starters for factory or field mounting See details in the Motor Starter section of this manual. NEMA 4 watertight enclosure For use where there is a possibility of water intrusion into the control panel. Cat Templifier-1 23

24 NEMA 12 Dust tight enclosure For use in dusty areas. Controls English or Metric Display Either English or metric units for operator ease of use. Modem for remote monitoring Includes the modem required for remote monitoring one or more units. Requires Monitor software. Monitor software Required for installation in a PC to complete remote monitoring capability. Unit Export packaging Can be either slat or full crate for additional protection during shipment. Units normally shipped in containers. Pumpout Unit Available in 1100 to 4900 pound sizes. Refrigerant monitor For remote mounting including accessories such as 4-20ma signal, strobe light, audible horn, air pick-up filter. Sound attenuation package Consists of acoustical insulation on the discharge line. Extended warranties Extended 1, 2, 3, or 4 year warranties for parts only or for parts and labor are available for the entire unit or compressor/motor only. 24 Cat Templifier-1

25 Guide Specifications SECTION 15XXX CENTRIFUGAL HEAT PUMP WATER HEATER PART 1 GENERAL 1.1 SUMMARY Section includes design, performance criteria, refrigerants, controls, and installation requirements for centrifugal heat pump water heater. 1.2 REFERENCES Comply with the following codes and standards Underwriters Laboratory ANSI/ASHRAE SUBMITTALS Submittals shall include the following: OSHA as adopted by the State ASME Section VIII A. Dimensioned plan and elevation view drawings, including motor starter cabinet, required clearances, and location of all field piping and electrical connections. B. Summaries of all auxiliary utility requirements such as: electricity, water, air, etc. Summary shall indicate quality and quantity of each required utility. C. Diagram of control system indicating points for field interface and field connection. Diagram shall fully depict field and factory wiring. D. Manufacturer s performance data. E F 1.4 QUALITY ASSURANCE Before shipment, submit a certification of satisfactory completion of factory run test signed by a company officer.. Installation and Operating Manuals. A. Qualifications: Equipment manufacturer must specialize in the manufacture of the products specified and have five years experience with the equipment and refrigerant offered. B. Regulatory Requirements: Comply with the codes and standards in Section 1.2. C. Water heater manufacturer plant shall be ISO Registered. 1.5 DELIVERY AND HANDLING A. Units shall be delivered to the job site completely assembled and charged with refrigerant and oil. B. Comply with the manufacturer s instructions for rigging and transporting units. Leave protective covers in place until installation. Cat Templifier-1 25

26 1.6 WARRANTY The refrigeration equipment manufacturer s warranty shall be for a period of one year from date of equipment start up or 18 months from shipment whichever occurs first. The warranty shall include parts and labor costs for the repair or replacement of defects in material or workmanship excluding refrigerant. 1.7 MAINTENANCE Unit maintenance shall be the responsibility of the owner with the following exceptions: PART 2 PRODUCTS 2.1 ACCEPTABLE MANUFACTURERS A. McQuay International B. (Approved Equal) 2.2 UNIT DESCRIPTION Provide and install as shown on the plans a factory assembled, factory charged, and factory run-tested heat pump water heater. Each unit shall be complete with a single-stage hermetic centrifugal compressor with lubrication and control system, (factory mounted starter), evaporator, condenser, refrigerant control device and any other components necessary for a complete and operable package. 2.3 DESIGN REQUIREMENTS A. General: Provide a complete heat pump water heater as specified herein. Machine shall be provided according to referenced standards Section 1.2. In general, unit shall consist of a compressor, condenser, evaporator, lubrication system, starter and control system. Note: Unit shall be charged with HCFC-134a refrigerant B. Performance: Refer to schedule on the drawings. C. Acoustics: Sound pressure levels for the complete unit shall not exceed the following specified levels. Provide the necessary acoustic treatment to the unit as required. Data shall be in db. Data shall be the highest levels recorded at all load points. Test shall be in accordance with ARI Standard 575. Octave Band dba 26 Cat Templifier-1

27 2.4 WATER HEATER COMPONENTS A. Compressor: 1. Unit shall have a single-stage hermetic centrifugal compressor. Casing design shall ensure major wearing parts, main bearings, and thrust bearings are accessible for maintenance and replacement. The lubrication system shall protect machine during coast down period resulting from a loss of electrical power. 2. The impeller shall be statically and dynamically balanced. The compressor shall be vibration tested and not exceed a level of 0.14 IPS. 3. Movable inlet guide vanes actuated by an internal oil pressure driven piston shall accomplish unloading. Compressors using an unloading system that requires penetrations through the compressor housing or linkages, or both that must be lubricated and adjusted are acceptable provided the manufacturer provides a five-year inspection agreement consisting of semi-annual inspection, lubrication, and annual change out of any compressor seals. A statement of inclusion must accompany any quotations. B. Lubrication System: The compressor shall have an independent lubrication system to provide lubrication to all parts requiring oil. Provide a heater in the oil sump to maintain oil at sufficient temperature to minimize affinity of refrigerant, and a thermostatically controlled water-cooled oil cooler. Coolers located inside the evaporator or condenser are not acceptable due to inaccessibility. A positive displacement oil pump shall be powered through the unit control transformer. C. Refrigerant Evaporator and Condenser: 1. Evaporator and condenser shall be of the shell-and-tube type, designed, constructed, tested and stamped according to the requirements of the ASME Code, Section VIII. Regardless of the operating pressure, the refrigerant side of each vessel will bear the ASME stamp indicating compliance with the code and indicating a test pressure of 1.3 times the working pressure but not less than 100 psig. Provide intermediate tube supports at a maximum of 24 inch spacing. 2. Tubes shall be enhanced for maximum heat transfer, rolled into steel tube sheets and sealed with Locktite or equal sealer. The tubes shall be individually replaceable. 3. Provide isolation valves and sufficient volume to hold the full refrigerant charge in the condenser or provide a separate pumpout system with storage tank. 4. The water sides shall be designed for a minimum of 150 psig or as specified elsewhere. Vents and drains shall be provided. Cat Templifier-1 27

Templifier Heat Recovery Water Heaters Catalog 614-2

Templifier Heat Recovery Water Heaters Catalog 614-2 Templifier Heat Recovery Water Heaters Catalog 614-2 Model TGZ-B, Scroll Compressor, 600 to 3,100 MBH (175 to 900 kw) Model TSC, Centrifugal, 3,000 to 18,000 MBH (880 to 5,300kW) R-134a 50/60 Hertz Engineered

More information

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters Energy Efficiency Through Waste Heat Recovery Heat Recovery Centrifugal Chillers and Templifier Water Heaters Innovative Solutions for Saving Energy McQuay offers two innovative methods of saving energy

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days Proposal Trane A Division of American Standard Inc. Prepared For: John Weston Desmet Ballestra Job Name: LAUER1 Biodiesel Chiller Pennsylvania Date: August 21, 2006 Proposal Number: G1-95502-1 Engineer:

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B.

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

Centrifugal, Magnetic Bearing, Compressor Water Chiller Model WMC-035T, 110 to 175 Tons

Centrifugal, Magnetic Bearing, Compressor Water Chiller Model WMC-035T, 110 to 175 Tons Catalog Cat WMC-1 Centrifugal, Magnetic Bearing, Compressor Water Chiller Model WMC-035T, 110 to 175 Tons 3/60/460, 3/50/400 R-134a HFC 134a, The Global Refrigerant of Choice Engineered for flexibility

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7

More information

SECTION CHILLERS

SECTION CHILLERS SECTION 15650 PART I - GENERAL 1.01 WORK INCLUDED A. Extent of work shall be as indicated on Drawings and provisions of this section, including schedules and equipment lists associated with either Drawings

More information

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller:

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller: SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC). 3. 15711 - Induced Draft Cooling Tower. B.

More information

Guide Specifications

Guide Specifications Guide Specifications Hot Water fired Adsorption Liquid Chillers Bry-Air Adsorption Chiller Overview The chiller shall be a Bry-Air ADC series. The chiller shall consist of a robust, compact, packaged chiller

More information

Air-Cooled Global Chiller

Air-Cooled Global Chiller Product Manual PM 970 Group: Chiller Effective: June 1997 Supersedes: None Air-Cooled Global Chiller Type AGR 055AS through 100AS Reciprocating Compressor with R-22 60 hertz 1997 McQuay International Table

More information

Open Protocol Data Communications

Open Protocol Data Communications MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way

More information

Engineered for flexibility and performance

Engineered for flexibility and performance Centrifugal Chillers 200 to 2700 tons Engineered for flexibility and performance Daikin McQuay Single Compressor Centrifugal Chillers A Life Cycle Return on Your Investment Centrifugal chillers are a significant

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES 60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Type of Compressors Compressor Rotary Scroll Reciprocating Screw Centrifugal Air Cooled Chiller 77 ~ 329TR (270 ~ 1156 kw) ACDX Series 100 ~ 520TR

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R Products That Perform...By People Who Care FORM NO: MS0455A WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R134a HXWC SERIES 205 to 560 Tons 60Hz INTRODUCTION Dunham-Bush's HXWC water cooled

More information

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

Product Data. Features/Benefits. 19XB Positive Pressure Storage System Product Data 19XB Positive Pressure Storage System 19XB028 Copyright 1992 Carrier Corporation 19XB052 Carrier s Positive Pressure Storage (PPS) System ensures the critical conservation of refrigerants

More information

Centrifugal Compressor Water Chillers Catalog 605 Models WSC, WDC, WCC, HSC

Centrifugal Compressor Water Chillers Catalog 605 Models WSC, WDC, WCC, HSC Centrifugal Compressor Water Chillers Catalog 605 Models WSC, WDC, WCC, HSC Engineered for flexibility and performance Cutaway view of McQuay Model CE 063 Compressor, Nominal 250 Tons MicroTech II Controller,

More information

SECTION CENTRIFUGAL WATER CHILLERS

SECTION CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Chiller package. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Condenser water connections. F. Variable

More information

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a Air-Cooled Variable Speed Drive Screw Chillers Super Efficient Super Quiet Cooling Capacity Range 540-1405 kw R134a World s first low sound Air-Cooled variable speed drive screw chiller The recognition

More information

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS)

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS) SECTION 23 64 01 AIR COOLED WATER CHILLERS (LESS THAN 150 TONS) PART 1: GENERAL 1.1 GENERAL A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish

More information

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South 3/5/2018 1 Update Dedicated Heat Recovery Chiller Technology Don Frye Gulf South Good design is an intentional act Begin with the end in mind Basic Bldg Tenants IAQ (low VOC & CO 2 ) Controlled Temp &

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

Centrifugal Compressor Water Chillers THE DISTINCTION SERIES

Centrifugal Compressor Water Chillers THE DISTINCTION SERIES Product Manual PM WSCWDC-2 Centrifugal Compressor Water Chillers THE DISTINCTION SERIES Model WSC, Single Compressor, Cooling Model WDC, Dual Compressor, Cooling Model HSC, Single Compressor Heat Recovery

More information

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated.

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated. NOMENCLATURE INTRODUCTION The HTT HWDX water-cooled chillers range is the latest addition to HTT s growing family of commercial products, featuring the most current technologies advances. The HWDX main

More information

AHRI Certification Program Scopes - COOLING

AHRI Certification Program Scopes - COOLING Air-to-Air Energy Recovery Ventilators (AHRI Std. 1060) Automatic Commercial Ice-Cube Machines and Ice Storage Bins (AHRI Stds. 810 & 820) Central Station Air-Handling Units (AHRI Std. 430) Commercial

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

1.2 REFERENCES - comply with the following codes and standards:

1.2 REFERENCES - comply with the following codes and standards: 15684 ROTARY SCREW AND SCROLL CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 SPECIFIER;

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series Centrifugal Chiller High Efficiency GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series Centrifugal Chiller High Efficiency Centrifugal Chiller HC-F-GFG-SSC Series (Super High Efficiency Type) HC-F-GXG-S

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation Air-Cooled Liquid Chillers www.eurovent-certification.com www.certiflash.com Quality Management Systems 0RB 008-05 Nominal cooling capacity 8- The new generation of Aquasnap liquid chillers was designed

More information

RTHE Series R Helical Rotary Liquid Chiller Tons 60Hz

RTHE Series R Helical Rotary Liquid Chiller Tons 60Hz Features Product and Benefits Catalog RTHE Series R Helical Rotary Liquid Chiller 75-255 Tons 60Hz January 2015 RTHE-PRC002-EN Introduction To meet a wide range of applications in the 75~255 ton water-cooled

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. Design and specify refrigeration systems and equipment in accordance with "Energy Conservation Standards" stipulated in Section 15010, Basic

More information

Leadership, Innovation, Advanced Technology Synergise Here!

Leadership, Innovation, Advanced Technology Synergise Here! Cooling Synergies Leadership, Innovation, Advanced Technology Synergise Here! 125 years of Engineering Innovation Kirloskar Chillers is proud to be a part of 125 years old Kirloskar Group. The diversified

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Material Handling Process Cooling Temperature Control Size Reduction Temperature Control Process Cooling Material Handling Size Reduction GP SERIES Packaged Chillers Precision Comprehensive Engineered

More information

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient PRODUCT SELECTION DATA Easy and fast installation Compact, reliable and efficient Class A variable speed circulator available Air-Cooled Liquid Chillers 0RB 008-015 CARRIER participates in the ECP programme

More information

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F Temperature Control Units Water & Oil - F Portable Chillers Air & Water-Cooled - 7 F Central Chillers Air & Water-Cooled Packages & Modules - 7 F Pump Tank Stations Chilled or Tower Water - gallons Cooling

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e. ORTEC Compressed Air, Gas & Fluid Technologies t a l r o n m e n i l y E n v F r i e n d t r a n l y R e i g e f r INDUSTRIAL FLUID CHILLERS FC SERIES (0-00 TONS) Application Flexibility Nortec Industrial

More information

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. SECTION 15650 REFRIGERATION EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. B. Related Section: 1. 11400

More information

Method to test HVAC equipment at part load conditions

Method to test HVAC equipment at part load conditions IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking

More information

Air-Cooled Screw Compressor Chillers

Air-Cooled Screw Compressor Chillers Catalog Cat AGSD-1 Air-Cooled Screw Compressor Chillers Models AGS 225D to AGS 450D 210 to 450 Tons, 740 to 1580 kw Packaged or with Remote Evaporator or Chilled Water Pump Package R-134a, Hz Engineered

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

THERMAL ICE STORAGE: Application & Design Guide

THERMAL ICE STORAGE: Application & Design Guide THERMAL ICE STORAGE: Application & Design Guide Table of Contents: 1. Introduction A. History of Thermal Energy Storage B. Operating and Cost Benefits 2. Applications A Fundamental System B. HVAC Cooling

More information

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

$42,000. Danfoss Turbocor Compressors Give INTERTECH PLASTICS A RESHORING ADVANTAGE. saved annually

$42,000. Danfoss Turbocor Compressors Give INTERTECH PLASTICS A RESHORING ADVANTAGE. saved annually CASE STUDY TWO $42,000 saved annually Intertech s new variable speed cooling system is precise, reliable, and efficient slashing cooling costs by approximately $42,000 annually. Danfoss Turbocor Compressors

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

All series is using Hitachi scroll compressor, low vibration and high efficiency. Internal thermostat embedded compressors, and it can react quickly.

All series is using Hitachi scroll compressor, low vibration and high efficiency. Internal thermostat embedded compressors, and it can react quickly. HITACHI proudly presents to our customers this wide range of split system air conditioners, from 4HP to 20 HP which is designed for high and medium outdoor temperature and comply with almost any types

More information

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications A Technical Introduction to Cool Thermal Energy Storage Commercial Applications Cool Thermal Energy Storage is a new application of an old idea that can cut air conditioning energy costs in half while

More information

OACS Outdoor Air-Cooled Central Chillers

OACS Outdoor Air-Cooled Central Chillers OACS Outdoor Air-Cooled Central Chillers Proudly Made In The USA since 1977 A Complete Central Chiller System Complete Central Chiller system with Integrated Reservoir and Pump all mounted on a single

More information

Modified by MSU Physical Plant / Engineering and Architectural Services

Modified by MSU Physical Plant / Engineering and Architectural Services Page 236426-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

water to water heat pumps

water to water heat pumps AQUARIUS WW SERIES water to water heat pumps O ur Aquarius WW Series water-cooled modular reverse cycle chillers are designed to meet all your replacement or new construction chiller requirements. Specifically

More information

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers GUIDE SPECIFICATIONS WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers WW024-072 Reverse Cycle Chillers / Low Temperature Boilers GENERAL Units shall be Underwriter Laboratories (UL) listed

More information

Catalog Water-Cooled Scroll Compressor Chillers

Catalog Water-Cooled Scroll Compressor Chillers Water-Cooled Scroll Compressor Chillers Model WGZ, D Vintage 30 to 200 Tons (100 to 700 kw) HFC-410A Refrigerant 60/50 Hz Packaged and Condenserless Units Catalog 613-3 Table of Contents Table of Contents

More information

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application 1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights

More information

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units. SECTION 15650 REFRIGERATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units. 4. Air

More information

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas Fired DOUBLE-EFFECT Chiller-Heater Absorption Principle Yazaki MG-Series

More information

ACMVTECH HIGH EFFICIENCY UNITARY AHU

ACMVTECH HIGH EFFICIENCY UNITARY AHU HIGH EFFICIENY UNITARY AHU 50 / 60 Hz R-134A, R407c R-407F, R-410A ACMVTECH HIGH EFFICIENCY UNITARY AHU WATER COOLED CONDENSERS VARIABLE and CONSTANT SPEED VSD FANS ; VSD COMPRESSORS ACMCVTECH UNITARY

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 236426.11 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Water-Cooled Screw Compressor Chillers

Water-Cooled Screw Compressor Chillers Catalog Cat WGS Water-Cooled Screw Compressor Chillers WGS 130AW To WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA To WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kw R-134A,

More information

RECORD SUBMITTAL COVER SHEET

RECORD SUBMITTAL COVER SHEET RECORD SUBMITTAL COVER SHEET PROJECT TITLE: AXCELLERATE PHARMA EQUIPMENT DESCRIPTION: CARRIER AQUASNAP AIR-COOLED CHILLER CH-1 OWNER: AXCELLERATE PHARMA MECHANICAL ENGINEER: ARDEN DATE: JUNE 27, 2014 SUBMITTED

More information

NQ Series Portable Chillers

NQ Series Portable Chillers NQ Series Portable Chillers Electrical Components Mounted and Wired All electrical components and sensors are mounted, wired, and fully tested at the factory to reduce installation time and ensure the

More information

Screw Compressors HSD SERIES. Capacities from: 816 to 3002 cfm Pressures from: 80 to 217 psig

Screw Compressors HSD SERIES. Capacities from: 816 to 3002 cfm Pressures from: 80 to 217 psig Screw Compressors HSD SERIES Capacities from: 816 to 3002 cfm Pressures from: 80 to 217 psig What do you expect from a large compressor system? All compressed air users need a reliable air system and want

More information

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units Precision control from the total provide Uncompromised precision More than ever data centers, server rooms, and

More information

CVGF. Water Cooled Centrifugal Chillers

CVGF. Water Cooled Centrifugal Chillers CVGF Water Cooled Centrifugal Chillers January 2010 CVGF Key Features 2 stage centrifugal compressor Semi-hermetic compressor R134a refrigerant Falling film evaporator Economizer cycle NEW Tracer Adaptiview

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

Air conditioning 23XRV

Air conditioning 23XRV High-Efficiency ChillerS with screw compressors Air conditioning Control CCN - Carrier Comfort Network Features The Evergreen range offers superior solutions with record capacities from 970 to 1880 kw,

More information

With the world-renowned SIGMA PROFILE

With the world-renowned SIGMA PROFILE www.kaeser.com Rotary Screw Compressors BSD/CSD/CSDX T SFC Series With the world-renowned SIGMA PROFILE Free air delivery 0.87 to 16.10 m³/min, Pressures 5.5 to 15 11 What do you look for in a compressor

More information

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR 5:1 FIRING RATE MODULATION LESS THAN 20 ppm NOx DIRECT VENT FLEXIBILITY TO 100 FEET 96% AFUE

More information

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years. TURBOCOR COMPRESOR CHILLERS General Description Microprocessor controlled, water chiller using HFC 134a refrigerant, two stage centrifugal oil free variable speed compressor's and electronic expansion

More information

AQUASNAP JUNIOR 30RHV

AQUASNAP JUNIOR 30RHV High-Efficiency Air-To-Water Heat Pumps Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. AQUASNAP JUNIOR 3RHV 6-11

More information

MEDICAL CHILLER SYSTEMS

MEDICAL CHILLER SYSTEMS Mission Critical Chilled Water Systems Engineered to Exacting Standards Magnetic Resonance Imaging Systems CT Scanners Oncology Linear Accelerators Blood Cooling Systems Precise Laboratory Applications

More information

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil.

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil. 1 1 1 1 1 1 1 1 0 1 0 1 SECTION 1 PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES A. Chiller package. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled

More information

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job. June 01 / BULLETIN - 3-Way Valves The right solenoid valve for any job. Page 2 / Bulletin - Advantages Sporlan 3-Way Valves 3-Way Pilot eliminates costly high- to low-side leaks. "B" reduces total installed

More information

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY Easy and fast installation Hydronic module available Compact, reliable and efficient Nominal cooling capacity : 8-40 kw Nominal heating capacity : 17-40 kw 50 410A Cooling or heating USE The air-to-water

More information

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE T he advent of the small scroll or screw chiller, capable of producing condenser water as high as 140

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

GEOTHERMAL DESIGN GUIDE

GEOTHERMAL DESIGN GUIDE GEOTHERMAL DESIGN GUIDE BENEFITS OF THE BULLDOG SYSTEM CGC Version CGC Group of Companies Incorporated 2018 CONTENTS INTRODUCTION... 2 CHALLENGES FACING CONVENTIONAL GSHP SYSTEMS... 3 FACTORS WHICH IMPACTS

More information

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Table 1. Series 200 Centrifugal Chiller. Point Type Range/Units 01

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

MicroTech Water-Cooled Screw Chiller Controller

MicroTech Water-Cooled Screw Chiller Controller BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software

More information