1 Steam Trap Survey For: ABC Corporation Anywhere, MI 7/0/07 Prepared by: Armstrong International 8 Maple Street Three Rivers, MI United States

2 General Summary The General Summary reviews the Scope of Work, final reports, and steam losses associated with this steam trap survey.

3 Armstrong International Three Rivers 8 Maple Street Three Rivers, MI : 7/0/07 To: ABC Corporation Anywhere, MI Re: Steam Trap Survey Between 9//05 and 9//05 Armstrong International Three Rivers conducted a steam trap survey at your facility. 4 in service traps were tested. All failed or defective traps were tagged with a red and white tag for ease in field identification. The field investigation and computer analysis reveals that 32.% of the in-service traps were found to be defective. The failed traps wasting steam resulted in an estimated annualized loss of 4,535,0 lb of steam and a corresponding monetary loss of 4,875 USD. In addition to the traps wasting steam, 2 failed in plugged and/or flooded conditions. These traps are not losing steam, but rather causing a loss of heat, water hammer, corrosion and possibly freezing damage to heat transfer equipment. The following is a breakdown of defective traps as a percentage of the total in-service traps: Blow Thru 28.3% Leaking 0.0% Plugged 4.3% Rapid Cycling 0.0% Flooded 0.0% Total 32.% Refer to the defective trap report for a complete listing of all failed traps. We thank you for the opportunity to assist in your energy conservation efforts and steam maintenance program. If we can be of any further service, or if you wish to discuss any aspects of this report, please do not hesitate to contact us.

4 STEAM TRAP SURVEY SCPE F WRK & TECNICAL SPECIFICATINS AT TE JB SITE. All steam traps are located, identified, and tagged with a stainless steel or aluminum tag and clip. 2. Each trap is tested to determine its operating condition. The method used shall include ultrasonic listening and visual inspection where possible (the customer should supply a means to reach traps that are difficult to access, e.g. ladders, forklifts, etc.). 3. A temporary red and white paper tag is attached to each FAILED trap in addition to the stainless steel or aluminum tag. 4. Note is made of specific problems. Some examples are: water hammer, poor or improper insulation, steam leaks in piping or valves, improper installation of traps, and other steam related problems. 5. n-the-job-training is provided to those plant personnel who are helping our Technicians with the survey. ne plant maintenance person should accompany each survey team.. Trap Survey Log Sheet Data: a. Tag Number b. Location c. Elevation d. Manufacturer and Model Number e. Connection Size f. Pressure i. Pressure In (P.I) actual steam pressure leading to the trap ii. Pressure ut (P..) actual steam pressure leaving the trap g. Application (Drip, Tracer, Coil, Process, Air Vents, Liquid Drainer) h. Equipment (Unit eater, Radiator, umidifier, etc.) i. Piping (Direction, Valve-In, Strainer, Valve-ut) j. Trap Condition (perating Mode) k. Note: All personnel testing traps are certified, factory trained technicians.

5 Recommended Steam Trap Testing Procedures Armstrong International, Inc.

6 STEAM TRAP TESTING A combination of testing methods is used in accurately predicting the operating condition of a trap. We recommend the use of an ultrasonic listening device with visual observation when possible. When an atmospheric discharge is not possible, the use of the ultrasonic listening device can be used to determine the operating condition of the steam trap. Temperature measurement cannot show the operating condition of the trap. It is merely a sign of corresponding saturation steam pressure upstream of the trap and pressure on the condensate return system downstream of the trap. Determining the amount of back pressure in the condensate system helps to quantify the amount of live steam lost through a failed trap. The ultrasonic listening device gives a fairly clear understanding of how the trap is operating. A normally operating inverted bucket trap emits a definite burst of sound when the bucket sinks and opens the trap valve, thereby discharging condensate until entering steam floats the bucket and closes the valve. In the presence of extremely low loads, the bucket is heard as a continuous clattering sound. This is sometimes called a dribbling trap. This is still a normal operating steam trap with no steam loss. This could also be a sign of an oversized trap, therefore requiring a smaller or restrictive orifice. The normal operating sounds of a float and thermostatic trap are difficult to distinguish as it is a constant flow device with no cycle rate. By shutting off the inlet valve, letting condensate collect, and then releasing a large condensate load to the trap, the trap is heard opening and then modulating down the steady state flow. The thermostatic air vent in a float and thermostatic trap often opens rather infrequently to release air, making its working condition difficult to determine. A thermostatic steam trap has a cycle, but it is much more gentle in nature than the inverted bucket or disc trap. A sub cooling thermostatic steam trap is similar in operation to the float trap. It may have either a bellows or a bimetallic spring as the actuation device, opening and closing the trap according to the set temperature differential.

7 STEAM TRAP TESTING (Continued) A final determination of the operation of a steam trap is visual. This test can only be done if there is an atmospheric discharge or test valve. If there is a test valve after the trap, close off the valve to condensate return and open the test valve to the atmosphere. The steam trap will now act as an atmospheric discharge trap. If there is high back pressure in the condensate return system, some generic types of steam traps operate differently when discharging to the atmosphere than to the condensate return system. Therefore it is important to know how the different generic types of traps operate under varying conditions. pening a test valve ahead of the trap can also determine if the trap is backing up condensate. The actual piping arrangement with the application can give some insight as to freezing problems, formation of vacuum, back pressure and poor piping configurations that may affect the operation of the trap. Use a systems approach when testing steam traps. There are times when, after further investigation, what seems to be a defective trap is actually a piping or application problem. Armstrong International, Inc. Three Rivers, MI Phone: + (29) Fax: + (29) Web:

8 Executive Summary Report The Executive Summary Report includes the following information: Condition Summary - a listing of steam traps by operating mode Trap Type Summary - a listing of steam traps by generic type Application Summary - a listing of steam traps by application Manufacturer Summary - a listing of steam traps by manufacturer Annualized Loss Summaries - a total breakdown of estimated steam and monetary loss

9 STEAM TRAP EXECUTIVE SUMMARY ABC Corporation - SAM-002 Survey : 9//05 TRAP TYPE SUMMARY TTAL ANNUALIZED SUMMARIES Generic Type Population Count % of Total Failure Count In Service Failure BI Bi-Metal 3 5.% 50.0% Steam Loss (lb) 4,535,0 DC Disc.9% 00.0% Monetary Loss (USD) 4,875 FL Float % % Repair Cost/Trap (USD) 750 IB Inverted Bucket % 8 2.7% Savings (USD) 4,25 UK Unknown.9% 00.0% Payback Period (months) 0.2 C2 Emissions (lb),9,553,7,74 Totals: 54 00% 5 32.% Fuel used to generate lost steam 4,394 Manufacturer MANUFACTURER SUMMARY Population Count % of Total Failure Count In Service Failure (lb) Condition CNDITIN SUMMARY Population Count AND Anderson 3 5.% 2.7% Blow Thru 3 24.% ARM Armstrong 3.7% 8 2.7% K Good % BES Bestobell 3 5.% 50.0% S Not in Service 8 4.8% CC Cochran.9% 0 0.0% PL Plugged 2 3.7% CE Coe.9% 0 0.0% SAR Sarco.9% 00.0% Totals: 54 00% TLV TLV 8 4.8% % UNK UNKNWN.9% 00.0% Totals: 54 00% 5 32.% % of Total Application APPLICATIN SUMMARY Population Count % of Total Failure Count In Service Failure CL Coil 9.7%.7% Drip % 2 3.4% PR Process 5 9.3% 50.0% TR Tracer 5 9.3% 20.0% Totals: 54 00% 5 32.%

10 STEAM TRAP EXECUTIVE SUMMARY ABC Corporation - SAM-002 Survey : 9//05 TRAP TYPE SUMMARY CNDITIN SUMMARY APPLICATIN SUMMARY Generic Type Population Count % of Total Failure Count In Service Failure Condition Population Count % of Total Application Population Count % of Total Failure Count BI Bi-Metal 3 5.% 50.0% Blow Thru 3 24.% CL Coil 9.7%.7% DC Disc.9% 00.0% K Good % Drip % 2 3.4% FL Float % % S Not in Service 8 4.8% PR Process 5 9.3% 50.0% IB Inverted Bucket % 8 2.7% PL Plugged 2 3.7% TR Tracer 5 9.3% 20.0% UK Unknown.9% 00.0% Totals: 54 00% Totals: 54 00% 5 32.% Totals: 54 00% 5 32.% In Service Failure

11 MANUFACTURER SUMMARY ABC Corporation - SAM-002 Survey : 9//05 MANUFACTURER SUMMARY MANUFACTURER SUMMARY Manufacturer Population Count % of Total Failure In Service Failure Count AND Anderson 3 5.% 2.7% ARM Armstrong 3.7% 8 2.7% BES Bestobell 3 5.% 50.0% CC Cochran.9% 0 0.0% CE Coe.9% 0 0.0% SAR Sarco.9% 00.0% TLV TLV 8 4.8% % UNK UNKNWN.9% 00.0% Totals: 54 00% 5 32.%

12 Defective Trap Report The Defective Trap Report includes the following information: Blow Through, Leaking and Rapid Cycling Traps - a listing of defective traps wasting steam with a condition of, LK or RC Plugged and Flooded Traps - a listing of defective traps not wasting steam but backing up condensate due to a failed closed (PL) or flooded (FL) condition

13 DEFECTIVE TRAP REPRT SAM-002 Technician Page 7/0/07 3 Customer Location ABC Corporation Drip 2 Coil Tracer 2 Process 2 Applic ation Equip MFR Model PM Conn Size Line Sz In ut Condensate Lift Load Pressure In ut Insulati on Direction Piping Strainer Valve In Steam Valve ut Supply Discharge Condition Tag# 00 utside X Location Elevation 2 ft NRT SIDE F BILER BLWDWN dup? TR Installed SAR 00 psig TD52 /2" Check Valve x /2" /2",000 lb/hr 0 psig V 0 PL Tag# 00 utside X Location Elevation 7 ft Bldg. right outside dock area to left U Installed UNK UNK 3/4" 9.2 Conn Type ANSI Flanged 300# 5//02 Check Valve 3/4" 3/4" 2,000 lb/hr psig 0 C M 2' X 2' CIL Tag# 00 utside 2.50 USD Location Elevation 3 ft SW Corner in marble cutting room 3,33,79 lb/yr 39,5 USD Eq Installed ARM 5 psig 983 " NTP Threaded 5//02 Check Valve 2,000 lb/hr psig ARM 8 3/4" 250# rifice comments here Tag# 007 utside Location Elevation 2 ft Equip. storage room south side 74,735 lb/yr 5.50 USD 4 USD CL U Installed ARM 20 psig 880 /2" 9 Conn Type NTP Threaded 5//02 Check Valve 0 psig Recommendat 2' x 2' Coil Tag# utside USD Location Elevation 8 ft Cell Room #4 South Cell vhd 8,447 lb/yr 37 USD Installed ARM 250 psig 88 " NTP Threaded 5//02 Check Valve 0 psig ole in pipe - '"

14 DEFECTIVE TRAP REPRT SAM-002 Technician Page 7/0/ Customer Location ABC Corporation Drip 2 Coil Tracer 2 Process 2 Applic ation Equip MFR Model PM Conn Size Line Sz In ut Condensate Lift Load Pressure In ut Insulati on Direction Piping Strainer Valve In Steam Valve ut Supply Discharge Condition Tag# utside USD Location Elevation 8 ft n catwalk by west wall PC-82 8,447 lb/yr 37 USD Installed ARM 250 psig 88 " NTP Threaded 5//02 Check Valve " " 0 0 C 0 psig Tag# utside 024 Location Elevation 8 ft Catwalk on 2nd floor in process area Installed BES 200 psig " NTP Threaded 5//02 Check Valve 5 psig Dripping BC-32 Vacuum Jets Tag# utside 03 Location Elevation 8 ft Lvl ' West of BC-52 E Installed TLV 200 psig J5N- " NTP Threaded 5//02 Check Valve 0 psig PL 3/4 Bushed to /2 before PRV-Main steam header Tag# utside Location Elevation 8 ft 2nd Level W Wall ,888 lb/yr 5.50 USD 24 USD E Installed ARM 250 psig 88 " NTP Threaded 5//02 Check Valve 0 psig Recommendat Tag# utside USD Location Elevation 8 ft at BC-2 Vacuum pump 20,747 lb/yr 4 USD Installed TLV J3N 2 5// psig " Conn Type NTP Threaded Check Valve 0 psig

15 DEFECTIVE TRAP REPRT SAM-002 Technician Page 7/0/ Customer Location ABC Corporation Drip 2 Coil Tracer 2 Process 2 Applic ation Equip MFR Model PM Conn Size Line Sz In ut Condensate Lift Load Pressure In ut Insulati on Direction Piping Strainer Valve In Steam Valve ut Supply Discharge Condition Tag# utside USD Location Elevation 8 ft Btw Tank 2 & 3 on N wall 55,00 lb/yr 853 USD Installed ARM 20 psig 880 /2" NTP Threaded 5//02 Check Valve 0 0 C 0 psig Tag# utside USD Location Elevation 8 ft South of tank BC-3 05,78 lb/yr 582 USD Installed ARM 25 psig 88 " NTP Threaded 5//02 Check Valve 0 psig Tag# utside USD Location Elevation 22,230 lb/yr,442 USD PR AV Installed AND 5 psig 05T -/4" 8 Conn Type Socket-Weld Check Valve 0 psig 0 C Tag# utside 2 Location Elevation 0 ft Bldg. right out of dock door to left 3rd bay 5,88 lb/yr 5.50 USD 285 USD AV Installed ARM 25 psig /2" 2 ft 0 C FM 880 /2" 3/8" 0 psig M NTP Threaded /5/04 Check Valve Recommendat comments. Tag# utside dfdf sdf 5.50 USD Location sdf Elevation 2 ft 550,84 lb/yr 3,029 USD ST Installed AND 5 psig 05T -/4" Check Valve x,000 lb/hr 0 psig C

16 Trap s Report The Trap s Report is a complete listing of all failed traps and suggested methods of repair.

17 Trap s Report SAM-002 Technician Page 7/0/07 3 Customer Location ABC Corporation Drip 2 Coil Tracer 2 Process 2 Applic ation Equip MFR Model PM Conn Size Line Sz In ut Condensate Lift Load Pressure In ut Insulati on Direction Piping Strainer Valve In Steam Valve ut Supply Discharge Condition Tag# 00 utside X Location Elevation 2 ft NRT SIDE F BILER BLWDWN dup? TR Installed SAR 00 psig TD52 /2" Check Valve x /2" /2",000 lb/hr 0 psig V 0 PL Tag# 00 utside X Location Elevation 7 ft Bldg. right outside dock area to left U Installed UNK UNK 3/4" 9.2 Conn Type ANSI Flanged 300# 5//02 Check Valve 3/4" 3/4" 2,000 lb/hr psig 0 C M 2' X 2' CIL Tag# 00 utside 2.50 USD Location Elevation 3 ft SW Corner in marble cutting room 3,33,79 lb/yr 39,5 USD Eq Installed ARM 5 psig 983 " NTP Threaded 5//02 Check Valve 2,000 lb/hr psig ARM 8 3/4" 250# rifice comments here Tag# 007 utside Location Elevation 2 ft Equip. storage room south side 74,735 lb/yr 5.50 USD 4 USD CL U Installed ARM 20 psig 880 /2" 9 Conn Type NTP Threaded 5//02 Check Valve 0 psig Recommendat 2' x 2' Coil Tag# utside USD Location Elevation 8 ft Cell Room #4 South Cell vhd 8,447 lb/yr 37 USD Installed ARM 250 psig 88 " NTP Threaded 5//02 Check Valve 0 psig ole in pipe - '"

18 Trap s Report SAM-002 Technician Page 7/0/ Customer Location ABC Corporation Drip 2 Coil Tracer 2 Process 2 Applic ation Equip MFR Model PM Conn Size Line Sz In ut Condensate Lift Load Pressure In ut Insulati on Direction Piping Strainer Valve In Steam Valve ut Supply Discharge Condition Tag# utside USD Location Elevation 8 ft n catwalk by west wall PC-82 8,447 lb/yr 37 USD Installed ARM 250 psig 88 " NTP Threaded 5//02 Check Valve " " 0 0 C 0 psig Tag# utside 024 Location Elevation 8 ft Catwalk on 2nd floor in process area Installed BES 200 psig " NTP Threaded 5//02 Check Valve 5 psig Dripping BC-32 Vacuum Jets Tag# utside USD Location Elevation 8 ft 2nd Level W Wall 43,888 lb/yr 24 USD E Installed ARM 250 psig 88 " NTP Threaded 5//02 Check Valve 0 psig Tag# utside Location Elevation 8 ft at BC-2 Vacuum pump ,747 lb/yr 5.50 USD 4 USD Installed TLV 284 psig J3N " NTP Threaded 5//02 Check Valve 0 psig Recommendat Tag# utside USD Location Elevation 8 ft Btw Tank 2 & 3 on N wall 55,00 lb/yr 853 USD Installed ARM 20 psig 880 /2" NTP Threaded 5//02 Check Valve 0 psig

19 Trap s Report SAM-002 Technician Page 7/0/ Customer Location ABC Corporation Drip 2 Coil Tracer 2 Process 2 Applic ation Equip MFR Model PM Conn Size Line Sz In ut Condensate Lift Load Pressure In ut Insulati on Direction Piping Strainer Valve In Steam Valve ut Supply Discharge Condition Tag# utside USD Location Elevation 8 ft South of tank BC-3 05,78 lb/yr 582 USD Installed ARM 25 psig 88 " NTP Threaded 5//02 Check Valve 0 0 C 0 psig Tag# utside USD Location Elevation 22,230 lb/yr,442 USD PR AV Installed AND 5 psig 05T -/4" 8 Conn Type Socket-Weld Check Valve 0 psig 0 C Tag# utside USD Location Elevation 0 ft Bldg. right out of dock door to left 3rd bay 5,88 lb/yr 285 USD AV Installed ARM 25 psig 880 /2" NTP Threaded /5/04 Check Valve /2" 2 ft 3/8" FM 0 psig 0 M C comments. Tag# utside Location Elevation 2 ft dfdf sdf sdf 550,84 lb/yr 5.50 USD 3,029 USD ST Installed AND 5 psig 05T -/4" Check Valve x,000 lb/hr 0 psig C Recommendat Tag# utside Location Elevation Installed Conn Type NPT Pipe Thread Check Valve

20 Appendix The Appendix includes the following reference information: Terminology a glossary of terms used on survey reports. Trap Condition Reference descriptions for each trap condition reported.

21 TERMINLGY TERMS DESCRIPTIN DEFINITIN TAG NUMBER Trap identification no. A sequence of up to 5 alphanumeric characters. LCATIN Trap location General description of the trap location, i.e. Building, Floor, Room, etc. INSIDE/UTSIDE Whether the trap is located within a protective structure or is exposed to the elements. I=Inside, =utside ELEVATIN Elevation of the trap eight above/below the floor/ground surface MFG Trap manufacturer A three character designation of the trap manufacturer (e.g. ARM=Armstrong) MDEL Trap model number The model number designated by the trap manufacturer. TYPE Generic type of trap Type designated by single letter, e.g. IB=Inverted Bucket. CNN SIZE Connection size Connection size of the trap (not necessarily the same as the pipe size). INSPECTIN FREQUENCY Trap inspection schedule Recommended number of times the trap should be tested in months, (e.g. every months).

22 TERMINLGY (Continued) TERMS DESCRIPTIN DEFINITIN EQUIPMENT Equipment being serviced Actual equipment being serviced by the steam trap, e.g. Unit eater. P I Pressure In The gauge pressure or nominal pressure on the inlet side of the trap. P Pressure ut The gauge pressure or nominal pressure on the outlet side of the trap (also called Back Pressure) SUP Supply side of trap Supply side pressure in terms of C=Constant Supply Pressure; M=Modulating Supply Pressure RETURN Discharge side of trap Discharge side of trap is either C=Closed or =pen to atmosphere APP Application Application serviced by trap, e.g. =Drip Trap, etc. TIME IN SERVICE Amount of annual use The number of hours the trap is under load, expressed in months per year (e.g. 2,0 hours = 3 months). PIPING Direction of piping =orizontal, V=Vertical, etc. V I Valve In Type of valve on inlet side of trap (0=None, =on/off, 2=2 or 3 way valve) V Valve ut Type of valve on outlet side of trap (0=None, =on/off, 2=2 or 3 way valve) STR Strainer Type of strainer ahead of trap, 0=None; =Inline; 2=Inline w/blowdown valve CND. Condensate Load Actual load of condensate at the trap. LAD CND. LIFT Condensate Lift Actual height condensate must be lifted to overhead return.

23 TERMINLGY (Continued) TERMS DESCRIPTIN DEFINITIN INSUL Insulation Type Actual type of insulation surrounding pipes and traps, e.g. Asbestos, Calcium Silicate, etc. CNN. TYPE Connection Type Actual trap connection, e.g. SCR=Screwed, FLG=Flanged, etc. SUPEREAT present Indicates whether superheat is present at the trap. SD Shutdown required Indicates that system or plant shutdown must be initiated to repair the failed trap. LINE SIZE IN Line size in Nominal size of the inlet line/pipe LINE SIZE UT Line size out Nominal size of the outlet line/pipe

24 TRAP CNDITIN ABBREVIATIN DESCRIPTIN DEFINITIN K Good Trap Trap in normal operating mode. Blow Through Trap has failed in an open mode with maximum steam loss. Trap should be repaired or replaced. LK Leaking Trap has failed in a partially open mode with a steam loss of approximately 25% of maximum. Trap should be repaired or replaced. RC Rapid Cycling Disc trap going into failure mode. PL Plugged Trap has failed in a closed position and is backing up condensate. Trap should be repaired or replaced. FL Flooded Trap is assumed to be undersized and unable to handle the condensate load. Trap should be replaced with proper size. S ut of Service The steam supply line is off and the trap is not in service. NT Not Tested Trap in service but not tested due to inaccessibility, unable to reach, too high, etc.

25 ARMSTRNG TERETICAL STEAM LSS CALCULATINS (IP UNITS) The basic formulas used to estimate the live steam loss of defective traps are as follows: MASNEILAN S FRMULA ( o 2. )( C V) P( Pi + P ) = Blow Through Where: C V = Flow Coefficient P = P i P o P i = Inlet Pressure (psia) P o = utlet Pressure (psia) NAPIER S FRMULA ( 5. 43)( Pi )( A0) Where: A 0 = Area of rifice These are general formulas used in determining steam loss through and orifice. Based on data compiled in the field as well as actual test data from our lab in Michigan, certain changes have been made to these formulas. In addition to inlet pressure, back pressure, and orifice size, piping configurations, severity of feailure, and condensate load influence the quantity of steam loss through a trap. Consequently, service and very light condensate loads as found in drip and tracer service and the much higher condensate loads associated with coil and process applications. Back pressure, service time and modulating conditions are incorporated in the calculations. Naturally, some information such as how many months a trap operates per year is determined by data supplied by plant personnel.

26 ARMSTRNG ADJUSTED STEAM LSS CALCULATINS (IP UNITS) Given from trap survey log sheet: P.I. = Inlet pressure (psig) P.. = utlet pressure (psig) Step : Convert pressures to psia: P.I = P i, actual inlet pressure (psia) P = P o, actual outlet pressure (psia) Step 2: Determine P o, outlet pressure(psia) to be used in calculations: If P o 0.5 P i, then use P o If P0 < 0.5 P i, then use 0.5 P i Step 3: Determine P using P i and P o found in step 2: P = P i P o Step 4: Calculate steam flow or blow through (lb/hr): W = ( 0. 9)( CV) P( Pi + Po) for coil & process applications W = (. 4)( CV) P( Pi + Po) for tracer & drip applications Where: W = Steam flow or blow through (lb/hr) C V = Flow coefficient P i = Inlet pressure (psia) P o = utlet pressure (psia) P = P i P o

27 STEAM LSS CALCULATIN EXAMPLES (IP UNITS) A. Coil Application Given: P.I = 00 psig P.. = 0 psig C V = 32. Step : P i = = 4.7 P o = = Step 2: = 0. 3 < 0.5, therefore 4. 7 P o = (0.5)(Pi) = (0.5)(4.7) = Step 3: P = P i P o = = Step 4: W = ( 0. 9)( 32. ) ( ) = 2, 89 lb/hr B. Drip Application Given: P.I = 00 psig P.. = 0 psig C V = 32. Step : P i = = 4.7 P o = = Step 2: = , therefore 4. 7 P o = Step 3: P = P i P o = = 40 Step 4: W = (. 4)( 32. ) 40( ) = 3, 92 lb/hr

28 STEAM LSS CALCULATIN EXAMPLES (IP UNITS) (Continued) C. Tracer Application Given: P.I = 00 psig P.. = 45 psig C V = 32. Step : P i = = 4.7 P o = = Step 2: = , therefore 4. 7 P o = 59.7 Step 3: P = P i P o = = 55 Step 4: W = (. 4)( 32. ) 55( ) = 4, 40 lb/hr

TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY

TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY A steam trap, which is a fully automated condensate drainage device, generally does not require routine maintenance. Steam

More information

Steam Trap Inspection Methods And Steam Cost Analysis

Steam Trap Inspection Methods And Steam Cost Analysis Steam Trap Inspection Methods And Steam Cost Analysis 14 Hayes Street, Elmsford NY 10523-2536 USA Tel: 914-592-1220 Toll Free USA & Canada 24 Hour Fax Email: Internet 800-223-1325 914-347-2181 info@uesystems.com

More information

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle

Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle Steam Trap Presentation for IDEA Distribution Workshop Presenter: Joe Radle Proper Piping when Reducing Pipe Size Concentric reducer Eccentric reducer Correct Wrong Typical Steam Main Drip Station D Size

More information

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual Armstrong J Series, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual This bulletin should be used by experienced personnel as a guide to the installation

More information

Why steam trap survey?

Why steam trap survey? Why steam trap survey? Why does our customer need to have a steam trap survey regularly? Leaking steam trap wasting steam away steam boiler keep producing steam that will be wasted away Blocked steam trap

More information

Inverted Bucket Steam Traps. for efficient condensate drainage of industrial and HVAC equipment

Inverted Bucket Steam Traps. for efficient condensate drainage of industrial and HVAC equipment Inverted ucket Steam Traps for efficient condensate drainage of industrial and HVC equipment Inverted ucket steam traps The proper drainage of condensate is essential to efficient steam system operation.

More information

STEAM TRAP HEALTH MONITORING SERVICE EXECUTIVE SUMMARY

STEAM TRAP HEALTH MONITORING SERVICE EXECUTIVE SUMMARY STEAM TRAP HEALTH MONITORING SERVICE EXECUTIVE SUMMARY OVERVIEW Emerson s Steam Trap Health Monitoring Service at customer facility began November 15, 2015. A total of 184 steam traps are being monitored

More information

How to Trap: Installation and Testing

How to Trap: Installation and Testing How to Trap: Installation and Testing 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down

More information

How to Trap: Trap Selection and Safety Factors

How to Trap: Trap Selection and Safety Factors How to Trap: Trap Selection and Safety Factors Bringing Energy Down to Earth Say energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. Less

More information

Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment

Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment Float & Thermostatic Steam Traps from Spirax Sarco About float & thermostatic steam traps Most

More information

Installation and Testing of Inverted Bucket Steam Traps Manual

Installation and Testing of Inverted Bucket Steam Traps Manual Installation and Testing of Inverted Bucket Steam Traps Manual 307-EN Please read and save these instructions Armstrong IB Traps Installation Before Installing Run pipe to trap. Before installing the trap,

More information

Installation and Maintenance "L" and "LS" Series

Installation and Maintenance L and LS Series Installation and Maintenance "L" and "LS" Series IB-43-E This bulletin should be used by experienced personnel as a guide to the installation and maintenance of "L" and "LS" Series ultra capacity float

More information

APPLICATION GUIDELINES STEAM MAIN DRAINAGE

APPLICATION GUIDELINES STEAM MAIN DRAINAGE APPLICATION GUIDELINES STEAM MAIN DRAINAGE 1) Steam Main Drip Leg Dimensions 2) Types of Warm-Up a) Supervised b) Automatic 3) Spacing of Drip Legs 4) Low Pressure Drainage-- Sizing Traps for Automatic

More information

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM BEST PRACTICE NO. 30 WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM Air and noncondensable gases are one of the major problems in a steam system that can cause production

More information

Chapter 2.3: Steam System

Chapter 2.3: Steam System Part I: Objective type Questions and Answers Chapter 2.3: Steam System 1. For industrial process heating, the best quality of steam is: a) dry saturated steam b) superheated steam c) wet steam d) high

More information

Economical and simplified solutions that offer quality and optimum steam trap service.

Economical and simplified solutions that offer quality and optimum steam trap service. Economical and simplified solutions that offer quality and optimum steam trap service. It All Comes Down To Protection Regardless of the temperature and pressure characteristics of steam line drips or

More information

THE THERMOSTATIC STEAM TRAP

THE THERMOSTATIC STEAM TRAP THE THERMOSTATIC STEAM TRAP The purpose of any steam trap is to discharge, promptly, all condensate (as well as air and other non-condensible gases) without discharging live steam. Since steam is a vapor

More information

Steam Trap Selection

Steam Trap Selection Steam Trap Selection Bringing Energy Down to Earth Say energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. Less energy consumed means less

More information

How to Trap: Steam Tracer Lines

How to Trap: Steam Tracer Lines How to Trap: Steam Tracer Lines 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down to Earth

More information

Hoffman Specialty General Catalog

Hoffman Specialty General Catalog Hoffman Specialty General Catalog HS-900E ESP-PLUSTM For computer aided selection of Steam Trap and Regulators, please refer to the Steam Specialty Component Selectors in the Hoffman Specialty website

More information

HEAT EXCHANGER FORMULAS & EXAMPLE

HEAT EXCHANGER FORMULAS & EXAMPLE Formulas for Heat Exchanger System using a Modulating Control Valve Definition of Terms and Units: E = Mean Heat Transfer Rate or Heat Load (Btu/hr) E D = Design Heat Load (Btu/hr) U = Overall Heat Transfer

More information

YARWAY PROCESS THERMODYNAMIC STEAM TRAPS SERIES 40/40D AND C250/260

YARWAY PROCESS THERMODYNAMIC STEAM TRAPS SERIES 40/40D AND C250/260 SERIES 40/40D AND C250/260 Designed for a variety of high pressure and high capacity applications found in utility, industrial and marine service FEATURES Designed to fail open. Designed for superheat

More information

How to Trap: Process Air Heaters

How to Trap: Process Air Heaters How to Trap: Process Air Heaters 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down to Earth

More information

Mini Pump Trap. Features: n Low maintenance - No leaking seals, impeller or motor problems reducing maintenance and downtime.

Mini Pump Trap. Features: n Low maintenance - No leaking seals, impeller or motor problems reducing maintenance and downtime. Armstrong Mini Pump Bulletin AFH-223 The Armstrong mini pump trap is the smallest non-electric solution that can move condensate or other liuids from lower to higher points and from lower to higher pressures.

More information

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107 TABLE OF CONTENTS FLOAT AND THERMOSTATIC SERIES PAGE How to Select All 107 C 14 H 8 I 12 X 14 Competitive Changeover 18 THERMOSTATIC 8C 22 9C 2 17C 20 Competitive Changeover 17C 24 Replacement Modules

More information

How to Trap: Troubleshooting

How to Trap: Troubleshooting How to Trap: Troubleshooting Bringing Energy Down to Earth Say energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. Less energy consumed means

More information

WATER HAMMER something that never should occur in a steam system

WATER HAMMER something that never should occur in a steam system BEST PRACTICE NO. 11 WATER HAMMER something that never should occur in a steam system 1. STEAM AND CONDENSATE WATER HAMMER Water hammer is never normal in a steam and condensate system, and it is totally

More information

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S SERIES PB, 29, 129Y AND 29S Economical and simplified solutions that offer quality and optimum steam trap service FEATURES 29S 29 Thermostatic traps Pressure assisted fail-open design Freeze proof Easy

More information

Bringing Energy Down to Earth

Bringing Energy Down to Earth Bringing Energy Down to Earth Say energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. Less energy consumed means less waste, fewer emissions

More information

STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY. Information Reviewed and Reaffirmed. August No.

STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY. Information Reviewed and Reaffirmed. August No. STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY Information Reviewed and Reaffirmed August 196 No. 1664 11111111111134 areillin1111111 1 11111111 1 1[1 11 nin FOREST

More information

Yarway Repairable Drip and Tracer Steam Traps Series 751/761, 711/721, 731/741, 500/546, 460/515/D3

Yarway Repairable Drip and Tracer Steam Traps Series 751/761, 711/721, 731/741, 500/546, 460/515/D3 Wide range of steam traps that provide consistent performance in less than perfect conditions Features 1 1 Thermostatic Traps Repairable Pressure assisted fail-open design Freeze proof Easy to check cyclic

More information

Steam System Best Practices Document No. 11

Steam System Best Practices Document No. 11 Plant Support & Evaluations, Inc 400 Lombardi Ave. Green Bay, WI 54304 888-615-3559 www.plantsupport.com Fax: 888-615-8664 Steam System Best Practices Document No. 11 The Number One Problem in a Steam

More information

UNIVERSAL STYLE STEAM TRAPS WU450 Series

UNIVERSAL STYLE STEAM TRAPS WU450 Series Watson McDaniel reserves the 2010 Watson McDaniel Company UNIVERSL STYLE STEM TRPS WU450 Series Universal Connectors for Universal Steam s STEM TRPS Model WU450, WU450S, WU450SB WU450S-LR, WU450SB-LR,

More information

How to Trap: Rotating Dryers Requiring Syphon Drainage

How to Trap: Rotating Dryers Requiring Syphon Drainage How to Trap: Rotating Dryers Requiring Syphon Drainage 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing

More information

PIP PNE00004 Steam Trap Guidelines

PIP PNE00004 Steam Trap Guidelines July 2016 Piping PIP PNE00004 Steam Trap Guidelines PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from

More information

Removal of Non-condensable Gases and Air Is Critical In A Steam System

Removal of Non-condensable Gases and Air Is Critical In A Steam System Removal of Non-condensable Gases and Air Is Critical In A Steam System Air and non-condensable gases are one of the major problems in a steam system. Both can cause production problems for a steam system

More information

STEAM CONSERVATION GUIDELINES

STEAM CONSERVATION GUIDELINES STEAM CONSERVATION GUIDELINES FOR CONDENSATE DRAINAGE Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. CG-1 Table

More information

STEAM TRAPS

STEAM TRAPS STEAM TRAPS 08.2016 info@ayvaz.com www.ayvaz.com SELECTION OF STEAM TRAPS In order to get maximum efficiency and service life from the steam lines and steam related systems, it is crucial to make the correct

More information

Steam trap checking WHY WE NEED TO CHECK STEAM TRAPS METHODS OF CHECKING TRAPS ADVANTAGES AND DISADVANTAGES PRACTICAL DEMONSTRATION

Steam trap checking WHY WE NEED TO CHECK STEAM TRAPS METHODS OF CHECKING TRAPS ADVANTAGES AND DISADVANTAGES PRACTICAL DEMONSTRATION STEAM TRAP CHECKING Steam trap checking WHY WE NEED TO CHECK STEAM TRAPS METHODS OF CHECKING TRAPS ADVANTAGES AND DISADVANTAGES PRACTICAL DEMONSTRATION Steam Traps Review - Mechanical Traps Float Inverted

More information

Our Know-How. Your Peace of Mind. Steam Solutions

Our Know-How. Your Peace of Mind. Steam Solutions Our Know-How. Your Peace of Mind. Steam Solutions Steam Solution Know-How Our team of specialists have years of experience in planning and engineering. This knowledge, combined with our valuable manufacturer

More information

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions 0772150/4 IM-P077-02 ST Issue 4 S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning

More information

Insty-Pac Steam Humidifiers

Insty-Pac Steam Humidifiers IP-1 Insty-Pac Steam umidifiers The PURE umidifier Co. Insty-Pac (patent no. 6,065,740) steam injection humidifier is jobengineered to assure highly efficient steam release into the air stream. Each humidifier

More information

Steam Conservation Guidelines for Condensate Drainage Steam Trap Sizing and Selection.

Steam Conservation Guidelines for Condensate Drainage Steam Trap Sizing and Selection. Handbook P-101 Steam Conservation Guidelines for Condensate Drainage Steam Trap Sizing and Selection. Table of Contents Recommendation Charts and Instructions for Use...CG-2 Steam Tables...CG-3 Steam...Basic

More information

UFGS (May 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (May 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-23 22 13.35 40 (February 2011) ----------------------------------- Preparing Activity: NASA Superseding UFGS-23 22 13.35 (May 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT

KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT Jerry Wright Paramount Supply Company Eugene, OR Introduction Keep your trap shut or get the condensate out. Which way is it? Can you have it both ways? Which

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

A M E M B E R O F T H E K E N D A L L G R O U P

A M E M B E R O F T H E K E N D A L L G R O U P A M E M B E R O F T H E K E N D A L L G R O U P Presented by: Dan Gallagher Energy Opportunities in a Steam System What makes up your Steam System Boiler Room Distribution System Mechanical Rooms Point

More information

Ball Float Controlled. Thermo Dynamic(TD) Trap Safety Valve Condensate Pump Flash Vessel Moisture Separators Deaerator Head Steam Injector Sight Glass

Ball Float Controlled. Thermo Dynamic(TD) Trap Safety Valve Condensate Pump Flash Vessel Moisture Separators Deaerator Head Steam Injector Sight Glass Product of Quality Best Performance Ball Float Controlled Steam Traps Auto Drain Traps Float Valve Air Vent Valves Feed Control Valve Drain Control Valve Thermo Dynamic(TD) Trap Safety Valve Condensate

More information

Emerson Plantweb Insight

Emerson Plantweb Insight Emerson Plantweb Insight Configuration and Information Overview............................................................................ page 1 Global settings.......................................................................

More information

Steam Conservation Guidelines for. Drainage. Mead O'Brien (800) LP Steam. Condensate. HP Steam RECEIVER TANK HEATER

Steam Conservation Guidelines for. Drainage. Mead O'Brien (800) LP Steam. Condensate. HP Steam RECEIVER TANK HEATER HP Steam Steam Conservation Guidelines for Condensate Drainage LP Steam RECEIVER TANK HEATER RECEIVER PUMP HP Condensate Return Table of Contents Recommendation Charts and Instructions for Use...CG-2 Steam

More information

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils Installation, Operation and Maintenance Guide Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils

More information

Steam Traps and Steam Specialties

Steam Traps and Steam Specialties Steam Traps and Steam Specialties The new shape in steam traps... Bestobell s Delta Element A sophisticated, yet simple, design that will provide years of trouble-free service with no live steam loss.

More information

INSTRUCTION MANUAL. Keep this manual in a safe place for future reference FREE FLOAT TYPE STEAM TRAPS SS3/SS5 SERIES. Manufacturer

INSTRUCTION MANUAL. Keep this manual in a safe place for future reference FREE FLOAT TYPE STEAM TRAPS SS3/SS5 SERIES. Manufacturer INSTRUCTION MANUAL Keep this manual in a safe place for future reference FREE FLOAT TYPE STEAM TRAPS SS3/SS5 SERIES SS3N SS3V / SS5N SS5V / SS5NH SS5VH Manufacturer 881 Nagasuna, Noguchi, Kakogawa, Hyogo

More information

Inverted Bucket Float & Thermostatic Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS

Inverted Bucket Float & Thermostatic Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS Inverted Float & Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS ABOUT US In 1916, the company, then known as the Sterling Engineering Company, began designing and manufacturing valves, traps, strainers

More information

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016 Boiler Condensate Return Basics Presented by Steve Connor February 24, 2016 What We Are Covering Today? Brief review of the total steam system Why a proper condensate return system is so important Condensate

More information

STAINLESS STEEL TRAP VALVE STATION

STAINLESS STEEL TRAP VALVE STATION STAINLESS STEEL TRAP VALVE STATION MAKES A LONG STORY... 36 [914 MM]...SHORT. 4.75 [121 MM] THE INNOVATION IS INTEGRATION Armstrong stainless steel Trap Valve Station (TVS) reduces your costs for installation,

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 22 13.35 40 (February 2017) ----------------------------------- Preparing Activity: NASA Superseding UFGS-23 22 13.35 40 (February 2014) UFGS-23 22 13.35 (May 2010)

More information

PRESSURE MOTIVE PUMP (PMP) APPLICATIONS

PRESSURE MOTIVE PUMP (PMP) APPLICATIONS DRAINAGE of a SINGLE SOURCE of for a CLOSED LOOP SYSTEM PURPOSE: For removing condensate from below steam heat transfer equipment when a modulating valve is used for control and stall conditions will exist.

More information

STEAM AND TRAP FUNDAMENTALS

STEAM AND TRAP FUNDAMENTALS STEAM AND TRAP FUNDAMENTALS Nick Westerberg Westerberg and Associates Newman Lake, WA Steam is an invisible gas that is generated by adding heat energy to water, usually from burning fuel in a boiler.

More information

ø D ø g ø k Max. service [barg] pressure [psig] H 1 96 L BK 45 with butt-weld ends End connections Screwed Socket-weld

ø D ø g ø k Max. service [barg] pressure [psig] H 1 96 L BK 45 with butt-weld ends End connections Screwed Socket-weld GESTRA Steam Trap RHOMBUSline BK 45 and BK 45U International patents Issue date: /00 BK 45 and BK 45U A Space required for opening trap 70 b Thermostatic steam trap with corrosion-resistant thermostatic

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

APT and APT14 Automatic Pump Traps. for effective condensate drainage and removal

APT and APT14 Automatic Pump Traps. for effective condensate drainage and removal APT10-4.5 and Automatic Pump Traps for effective condensate drainage and removal 1 An innovative solution for effective heat User benefits Self contained compact unit. Operates with 8 in. installation

More information

FT600 & FT601* Steam Traps Float & Thermostatic Steam Trap. Float & Thermostatic STEAM TRAPS

FT600 & FT601* Steam Traps Float & Thermostatic Steam Trap. Float & Thermostatic STEAM TRAPS STEAM TRAPS Steam Traps Steam Trap Model * Sizes 3/4, 1, 1 1 /2, 2, 3, 4 Connections NPT, SW, FLG Body Material Carbon Steel or 316SS Options Live Orifice Air Vent PMO Max. Operating Pressure 450 PSIG

More information

GESTRA Information A 1.5

GESTRA Information A 1.5 Issue Date: 9/06 GESTRA Steam Systems GESTRA Information A 1.5 How to avoid operating trouble in steam and condensate systems caused by freezing of equipment and plant The recent cold winter brought us

More information

Bulletin 301-N SERVICE GUIDE. Armstrong Inverted Bucket Steam Traps

Bulletin 301-N SERVICE GUIDE. Armstrong Inverted Bucket Steam Traps Bulletin 301-N SERVICE GUIDE Armstrong Inverted Bucket Steam Traps A B T T D C Table of Contents Trap Priming 2 Installation 3-8 Testing 9-10 Inspection & Repair 10-14 Trouble Shooting 14-18 Optional Accessories

More information

AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions

AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions 138-EN Please read and save these instructions Contents General Safety Information... 3 Product Information...3-5 Product

More information

Disc Type Steam Trap TSD-42

Disc Type Steam Trap TSD-42 Disc Type TSD-42 TSD-42 is disc type steam trap for high pressure (maximum pressure: 4.2 MPa). It is compact and lightweight, and can be installed horizontally or vertically. Disc Ring By-Metal Valve seat

More information

Efficient Steam System Design

Efficient Steam System Design Efficient Steam System Design The word Efficient is often used to describe the general performance of a system. However it is important to distinguish between efficiency and effectiveness. Efficiency is

More information

Intelligent System Solutions Steam Air Hot Water

Intelligent System Solutions Steam Air Hot Water Intelligent System Solutions Steam Air Hot Water Featured Products Trap Valve Station and Associated Traps Steam System Testing and Monitoring The TVS 4000 Series Stainless Steel Trap Valve Station enhances

More information

Series 300 VTB. Installation Instructions

Series 300 VTB. Installation Instructions Series 300 VTB Installation Instructions Sizes 7 12 16 20 30 HP #2 Fuel Oil Gas (500 to 2500 BTU) Gas Light Oil Combination High Pressure Steam Sizes 7 thru 16 HP (125 PSI) Sizes 20 and 30 HP (150 PSI)

More information

Condensate Pumps Jones Boulevard Limerick Airport Business Center Pottstown PA Tel:

Condensate Pumps Jones Boulevard Limerick Airport Business Center Pottstown PA Tel: www.watsonmcdaniel.com 428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 129 Return Introduction Return System Shown below is a simplified view of a steam system

More information

The right trap for the right application.

The right trap for the right application. The right trap for the right application. Whenever you re faced with a process application, it s not enough to just select any steam trap to solve your problem. Instead, remember to match your application

More information

ICS Float and Thermostatic Steam Trap Installation and Operation Manual

ICS Float and Thermostatic Steam Trap Installation and Operation Manual ICS Float and Thermostatic Steam Trap Installation and Operation Manual 59 Table of Contents. General Safety Information. 3 Product Information. 4 Product Installation. 5 Service and Maintenance. 6 Troubleshooting.

More information

Improved Dryer Control

Improved Dryer Control Improved Dryer Control Kenneth C. Hill President Kadant Johnson Systems Division David Vijh Senior Process Control Engineer Technical White Paper Series EXECUTIVE SUMMARY Significant improvements in dryer

More information

VIFB Coil Technical Guide

VIFB Coil Technical Guide TGVIFB-3 VIFB Coil Technical Guide VERTICAL TUBE INTEGRAL FACE AND BY-PASS HEATING COILS FOR PREHEATING Since 1875, the L.J. Wing Company has been a leader in providing innovative solutions for diffi cult

More information

SERVICE GUIDE Armstrong Inverted Bucket Steam Traps

SERVICE GUIDE Armstrong Inverted Bucket Steam Traps Bulletin 301-L SERVICE GUIDE Armstrong Inverted Bucket Steam Traps A B T T D C Table of Contents Trap Priming 2 Installation 3-8 Testing 9-10 Inspection & Repair 10-14 Trouble Shooting 14-18 Optional Accessories

More information

VIFB Coil Technical Guide

VIFB Coil Technical Guide TGVIFB-4 VIFB Coil Technical Guide VERTICAL TUBE INTEGRAL FACE AND BY-PASS HEATING COILS FOR PREHEATING Since 1875, the L.J. Wing Company has been a leader in providing innovative solutions for diffi cult

More information

MODELING THE SEATTLE STEAM CO. DISTRIBUTION SYSTEM WITH RELAP5-3D

MODELING THE SEATTLE STEAM CO. DISTRIBUTION SYSTEM WITH RELAP5-3D MODELING THE SEATTLE STEAM CO. DISTRIBUTION SYSTEM WITH RELAP5-3D Richard R. Schultz Idaho National Engineering & Environmental Laboratory PO Box 1625 Idaho Falls, ID 83415 ABSTRACT Steam generation is

More information

Armstrong Steam System Solutions for the Hydrocarbon and Chemical Processing Industries

Armstrong Steam System Solutions for the Hydrocarbon and Chemical Processing Industries Bulletin 290-B Armstrong Steam System Solutions for the Hydrocarbon and Chemical Processing Industries Packaged Piping Solutions - Steam Distribution Manifolds - Condensate Collection Assemblies - Trap

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier OM001 Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier These operating and maintenance instructions are for standard semi-storage calorifiers (vessels fitted with

More information

Liquid Drainers LIQUID DRAINERS

Liquid Drainers LIQUID DRAINERS Liquid Drainers 206 Liquid Drainers Model/Series Type Body Material PMO Sizes Connection Page No. (PSIG) WLDE Float Ductile Iron 200 1 1 /2, 2, 2 1 /2 NPT WLDES Float Cast Steel 300 2 1 /2 NPT, SW, FLG

More information

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

Steam Trap BK 45 BK 45-U BK 45-LT BK 46 Steam Trap BK 45 BK 45-U BK 45-LT BK 46 Original Installation Instructions 810437-08 Contents Foreword... 3 Availability... 3 Formatting features in the document... 3 Safety... 3 Use for the intended purpose...

More information

Product. Add Efficiency To Your Steam Investment... Steam Traps Drain Traps Air Vents & Eliminators Accessories Piping Assemblies Replacement Kits

Product. Add Efficiency To Your Steam Investment... Steam Traps Drain Traps Air Vents & Eliminators Accessories Piping Assemblies Replacement Kits Engineering Products for the Steam Industry Since 985 Product Catalog Steam Traps Drain Traps Air Vents & Eliminators Accessories Piping Assemblies Replacement Kits Add Efficiency To Your Steam Investment...

More information

THERMOSTATIC STEAM TRAPS

THERMOSTATIC STEAM TRAPS THERMOSTATIC STEAM TRAPS Nicholson is the originator of the bellows actuated Thermostatic Steam. Nicholson s thermostatic product range spans applications from critical tracing to high capacity process.

More information

opening trap 30 mm Space required for Space required for opening trap 30 mm MK 45-1 with flanged ends (to DIN)

opening trap 30 mm Space required for Space required for opening trap 30 mm MK 45-1 with flanged ends (to DIN) Issue Date: 4/06 GESTRA Steam Systems Thermostatic Steam Traps MK 45-, MK 45-2 PN 40, DN 5, 20, 25 (½", ¾", ") Product Range A MK 45- MK 45-2 Description Thermostatic steam trap with membrane regulator.

More information

LIQUIDATOR 450 SERIES

LIQUIDATOR 450 SERIES LIQUIDATOR 450 UMT SERIES TRAP AND UMTC CONNECTOR APPLICATIONS Unit Heaters Steam Tracing Drip Legs Tire Presses Cooking Equipment Laundry Equipment Plating Tanks Platen Presses Air Vents OPTIONS SLR -

More information

Pure Performance For Steam Mains and Tracers

Pure Performance For Steam Mains and Tracers Pamphlet A2004-2 Thermodynamic Steam Traps P Series FP Series HR Series Pure Performance For Steam Mains and Tracers Are you looking for Improved Performance? Disc traps are valued for their compact size

More information

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT CEMLINE Unfired Steam Generators are designed to produce clean steam with steam or high temperature hot water as an energy source for use where there is a need to produce clean steam from boiler steam

More information

Steam Site Guide. Steam Site Guide. Heat Exchange Applications - SI Units

Steam Site Guide. Steam Site Guide. Heat Exchange Applications - SI Units Steam Site Guide Steam Site Guide Heat Exchange Applications - SI Units Steam Site Guide Content Introduction... 03 01. Estimating Steam Loads... 04 02. Steam Table SI... 07 03. Sizing a Steam Pipe...

More information

Technical Data CONDENSATE COMMANDER PUMP SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 9902D

Technical Data CONDENSATE COMMANDER PUMP SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 9902D Technical Data SD 9902D SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 PRINTED IN U.S.A. SD 79902D/9803 Condensate Commander Pump Dimensions Weight Size A B C D E* F Lbs. 1"x

More information

Hydrocarbon & Chemical Processing Solutions

Hydrocarbon & Chemical Processing Solutions Hydrocarbon & Chemical Processing Solutions Table of Contents Armstrong Packaged Piping Solutions...3-4 Steam Distribution Manifolds (MSD/SMSD) & Cost Comparison Worksheet...5-7 Condensate Collection Assembly

More information

Inverted Bucket Steam Traps

Inverted Bucket Steam Traps INSTALLATION AND MAINTENANCE INSTRUCTIONS IM-2-00-US December 201 Inverted Bucket Steam Traps Safety Information Safe operation of these products can only be guaranteed if they are properly installed,

More information

Bringing Energy Down to Earth

Bringing Energy Down to Earth Bringing Energy Down to Earth ay energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. ess energy consumed means less waste, fewer emissions

More information

SH-300, SH-900, SH-1500, SH-1600 and SH-1700 Bimetallic Steam Trap Installation and Operation Manual

SH-300, SH-900, SH-1500, SH-1600 and SH-1700 Bimetallic Steam Trap Installation and Operation Manual SH-300, SH-900, SH-1500, SH-1600 and SH-1700 Bimetallic Steam Trap Installation and Operation Manual 111-EN SH-300 SH-900 SH-1500 SH-1600 SH-1700 Table of Content. General Safety Information. 3 Product

More information

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to "HOW TO ORDER" page.

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to HOW TO ORDER page. PT5 Thermodynamic Steam Traps MATERIAL : No. PART MATERIAL QTY. (Nos.). BODY ASTM A743 Gr. CA 40 0 (Seat Hardened) (Cast Equiv. AISI 420) 2. DISC CAP ASTM A743 Gr. CA 40 0 (Cast Equiv. AISI 420) 3. DISC

More information

Series 151 and AV5. A wide range of process thermostatic steam traps is available to match almost any application need.

Series 151 and AV5. A wide range of process thermostatic steam traps is available to match almost any application need. A wide range of process thermostatic steam traps is available to match almost any application need. FEATURES Simple construction Easy to maintain as installed Excellent air handling capability Pressure

More information

How to Trap: Conversion Factors

How to Trap: Conversion Factors How to Trap: Conversion Factors 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down to Earth

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL IFB HEATING COILS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL IFB HEATING COILS IOMIFB-6 INSTALLATION, OPERATION AND MAINTENANCE MANUAL IFB HEATING COILS ATTENTION: READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE

More information