1 T-16DNH E DOUBLE EFFECT DIRECT FIRED ABSORPTION CHILLER : 1350 USRt Heating Capacity: kw

2 Carrier makes the world a better place to live by creating a comfortable, productive and healthy environment regardless of climate. It is our mission is to be customer s first choice for air conditioning, heating and refrigeration solutions everywhere around the world. Features/Benefits Operation Cycle Physical & Performance Data Features / Benefits 16DNH offers a viable alternative to traditional electric driven chillers. Fired by natural gas or light oil, 16DNH reduces costly electricity bills and qualifies for utility rebates and incentives as a gas cooling product. 16DN can operate in the heating mode to provide hot water, thereby reducing the size of the required boiler or even eliminating the need for a boiler. Performance Curve 4 Excellence Efficiency Overall Dimension 5-9 COP=1.36 ( cooling water inlet temperature is 30 C) Great Hall of the People, Beijing, China 2-Piece Dimension Foundation Control system Wiring Diagram Standard Options Standard Tubing Flow Chart High quality plate heat exchanger and tubes contribute to a high efficiency, more compact profile, lighter weight. Uniquely designed flue gas heat exchanger fully recover exhaust heat, increase efficiency and decrease flue gas temperature. Environmentally Friendly Chiller Using water and lithium bromide which are natural as refrigerant medium, no CFCs; Fired by clean burning natural gas, light oil, few electricity cost. Few moving parts enable quiet and vibration-free operation. Burning System 15 Superior Part Load Performance Thermal Insulation 16 Concentration control system allows stable, part-load operation at cooling water temperatures as low as 15 C ( 60.8 F ) Kremlin, Moscow, Russia Hoisting & Shipping 17 without a cooling tower bypass. For maximum efficiency, a VFD pump automatically maintains optimum solution flow rate at all operating conditions. Continuous operating range from 100% to 25% capacity for gas-fired series and 100% to 30% for oil-fired series, based Nomenclature on minimum fire requirements for the burner. Reliable Operation Microprocessor control center continuously monitors machine operation, ensuring precise control. Superior corrosion protection. White House, Washington, USA Automatic, motorless purge system extends machine life and ensures optimum efficiency and performance. Rugged machine construction. Anti-crystallization controls maintain proper solution concentration. Advanced Control System Imperial Palace, Tokyo, Japan H - Non-Standard Heating Capacity Fuel Type: N Natural Gas L Light oil Product Specification Double Effect Direct Fired Chiller Absorption Product Code Human friendly interface between chiller and user, all text strings for display and all alarm messages are provided in several languages. Excellent algorithms provide precise capacity control and optimize chiller operation. Automatically calculates a solution concentration with cycle temperature and prevents a solution crystallization by control the fuel input. Having the ability to counicate with central control system and telecounicate with telephone network.

3 Operation Cycle Physical & Performance Data Cooling cycle Water is used as the refrigerant in evaporator maintained under low highly vacuum state. In the cooling mode, the chiller operates on the principle that under vacuum, water boils at a low temperature, thereby cooling chilled water. To make the cooling process continuous, refrigerant vapor must be removed as it is produced. A lithium bromide solution (which has a high affinity for water) is used to absorb refrigerant vapor. As this process continues, lithium bromide becomes diluted, reducing its absorption capacity. A solution pump then transfers this weak solution to the high temperature generator where it is heated and re-concentrated to a medium concentration solution by the heat from the combustion of fuel. The medium concentration solution flows to the low temperature generator where it is heated and re-concentrated to a strong solution by the high temperature water vapor released from the solution in high temperature generator. The water vapor released in the shell-side of low temperature generator, in addition to the condensed water vapor from the tube- side of low temperature generator, enters the condenser to be cooled and returned to a liquid state. The refrigerant water then returns to the evaporator to begin a new cycle. To remove heat from the machine, cooling water is first circulated through the tubes of the absorber to remove the heat of the evaporator. Then it is circulated through the tubes of condenser. The strong solution from the low-temperature generator flows back to the absorber to begin a new cycle. Chilled Water Cooling Water Model Heating Capacity Inlet/Outlet Temp Flow Rate Pressure Drop Connection Size Pass No. Inlet/Outlet Temp Flow Rate Pressure Drop Connection Size 16DNH USRt kcal/h kw kcal/h kw m 3 /h mh2o kpa A() m 3 /h mh2o kpa A() /7 32/37.5 High Temp Generator Exhaust Exhaust Heat Recovery Condensate Heat Recovery Low Temp Generator Condenser Cooling Water Pass No. Inlet/Outlet Temp Flow Rate A C m 3 /h /60 Hot Water Pressure Drop mh2o kpa Chilled Water Connection Size A() Pass No Burner Spray Pump Absorber Evaporator Chilled Water Fuel Natural Gas Connecti on Size Light Oil Nm 3 /h kg/h Gas A() Oil A() High Temp Heat Exchanger Low Temp Cooling Water Heat Exchanger Solution Pump Refrigerant Pump Exhaust Size Power Supply A() 290 X X X X X 670 3Ø-380V-50Hz 406X X X X X X 1080 Heating cycle High temperature water vapor produced in the high temperature generator is passed directly to the evaporator via absorber where it condenses and transfers its heat to hot water circulating through the evaporator tubes. This condensed water then flows to the absorber where it mixes with the concentrated solution returning from the high temperature generator. The diluted solution is then pumped back to the hightemperature generator to repeat the vapor generation phase for the heating function. Electric Dimensi on Ref. Pump Solution Pump Auxiliary Pump Burner Fan Capacity Length Width Height kw kw kw kw kva Exhaust High Temp Generator Condensate Heat Recovery Low Temp Generator Condenser Weight Net Weight Operating Weight kg kg Exhaust Heat Recovery Burner Spray Pump Absorber Evaporator Hot Water Hot Water 1.Fouling factor of chilled / hot water and cooling water is 0.086m2 /kw. 2.Capacity range: 25~100% (natural gas), 30~100% (oil). 3.Fuel consumption is based on: heating value of natural gas is 11,000 kcal/nm3, heating value of light oil is 10,400 kcal/kg, both these values are low heating value. 4.Flue gas temperature: 140 (cooling cycle) 120 (heating cycle) 5.Inlet size of natural gas is base on its inlet pressure of 7kPa; Inlet size of oil is base on light oil. Please contact Carrier for non-standard condition. High Temp Heat Exchanger Low Temp Heat Exchanger Solution Pump Refrigerant Pump 02 03

4 Performance Curve Overall Dimension 16DNH Cooling Water, & COP Operation Condition: Temp Chilled Water Flow Rate Cooling Water Flow Rate Fouling Factor 7 C 100% 100% 0.086m 2. K/kW Temp Chilled Water, & COP Dimensions in brackets are data of 16DNH018 Operation Condition: the height of skid is 200 Temp Temp Chilled Water Flow Rate Cooling Water Flow Rate Fouling Factor 32 C 100% 100% 0.086m 2. K/kW 16DNH Fuel Consumption & Natural Gas Consumption Rate(Nm 3 /husrt) [Low Heating Value 1100kcal/Nm 3 ] Temp Operation Condition: Cooling Water Flow Rate Fouling Factor 100% 0.086m 2. K/kW (280) Dimensions in brackets are data of 16DNH024 the height of skid is

5 Overall Dimension Overall Dimension 16DNH DNH Dimensions in brackets are data of 16DNH033 the height of skid is 200 Dimensions in brackets are data of 16DNH050 the height of skid is DNH DNH Dimensions in brackets are data of 16DNH040 the height of skid is 200 Dimensions in brackets are data of 16DNH066 the height of skid is

6 Overall Dimension Overall Dimension 16DNH080 16DNH120 Dimensions in brackets are data of 16DNH080 the height of skid is 200 Dimensions in brackets are data of 16DNH120 the height of skid is DNH100 16DNH135 Dimensions in brackets are data of 16DNH100 the height of skid is 200 Dimensions in brackets are data of 16DNH135 the height of skid is

7 2-Piece Dimension Foundation Tube Cleaning Space L Embedded cable conduit Embedded cable conduit 8-M20 Anchor bolt(supplied by customer) Hole depth Foundation load bearing capacity is designed subject to unit load W1 and W2. 2. Foundation levelness should be within 1/ Square holes in foundation are used to fix foundation bolts. Slope at one side of the square hole is used to pour mortar. 4. Space for tube cleaning may be set at either end of the unit. 5. Shade part and square hole represents base angle and bolt hole of the unit respectively ditch set around the unit Model 16DNH 015/ / / / / / A / B C D E F G Model Whole Piece 1 L W H G L W H G L 16DNH kg kg H I J K L M ( * ) N ( * ) P Load W1 Load W2 kg kg / / / / / /2010 2/ / / / / / / / / / / / / Piece 2 W H G kg

8 Control System Wiring Diagram ICVC International Chiller Visual Controller Convenient Operation, Powerful Function Perfect Man-Machine Interface Easy to operate, the function can be completed just by a touch. Advanced control logic; Convenient and reliable operation. Support display of great information contents (more than 200 pieces of information); Perfect manmachine interface Liquid crystal touch screen Background light is adjustable Powerful Self-Diagnosis Function Controller and sensor self-check work will be done before the unit is started Display and record the latest 40 alarm logs and provide detailed diagnosis report Automatic Restart Function After power is restored, the unit may be restarted automatically to further reduce the possibility of crystallization Early Warning System In case any of the following potential risk factors occurs, the unit will implement automatic protective restriction to ensure safe operation of the unit. High temperature of concentrated solution exiting high temperature generator High liquid level of solution in high temperature generator Overload/high temperature of refrigerant pump Overload/high temperature of solution pump Backup safety device Low temperature of refrigerant Low temperature of chilled water High temperature of dilute solution exiting absorber Voltage failure of pressure sensor CCN overruns and stops Chilled water outlet temperature limitation Excessive concentration of solution in high temperature generator Safety Protection Device Chilled water flow break protection Cooling water flow break protection (optional) Chilled water low temperature protection Anti-crystallization system High temperature generator high temperature/high pressure protection Burner failure protection Solution pump/refrigerant pump overload/overflow protection Sensor error detection Flue gas tube high temperature protection 12 Many acquisition points for operating parameters, wide control range The controller contains 1 ICVC display module, 3 CCN acquisition modules, 13 temperature sensors, 1 pressure switch, 1 temperature switch and pump protection, etc. Great storage capacity, more than 200 pieces of relevant information can be stored in the unit Solution circulation regulated by variable frequency driver is within 10~100%. Group Control Function Support three operating modes: single, remote control and CCN CCN can be connected through Carrier DATAPORT Building automation system can be connected through RS485 and RS232 standard serial counication interface Advanced Timing Function Everyday can be divided into 8 time intervals. Different operating modes can be set for each time interval, and time intervals may vary from day to day in a week 10 holidays can be set, and operating mode can be set for 8 operating time intervals of each holiday Control Stable & Accurate Cooling capacity is controlled by acquisition of inlet/outlet temperature of chilled water and that of cooling water Automatic adjustment for outputa of the burner Automatic adjustment for solution circulation Energy saving correction when cooling capacity decreases, the unit can automatically correct it Advanced Anti-Crystallization Automatically monitor concentration, temperature and pressure at seven state points of the solution, and adjust it to optimum state Several operating states are set for the unit, such as normal operation, warning, alarm and stop. Failure preprocessing function is added for the unit, which effectively prevents from crystallization. Auxiliary Facilities Interlocking Support interlock control over chilled water pump, cooling water pump, cooling tower so that the unit can operate more safely 1# Termination 3# Termination 220v-1Ph-50Hz 380v-3Ph-50Hz Field Wiring Unit Wiring Option Wiring Standard Options Chilled water Cooling water Burner energy valve OFF Concentric line Burner energy valve ON 2# palladium unit power supply 1# palladium unit power supply Burner control power supply Field Wiring Red White Black Red White Black Auxiliary hot water pump control (optional) Unit operation signal Alarm signal Cooling tower fan control Cooling water pump control Chilled water pump control Auxiliary hot water discharge temp (optional) Auxiliary hot water mixing temp (optional) Auxiliary hot water outlet temp (optional) Auxiliary hot water inlet temp (optional) Cooling water flow switch (optional) Standby safety protection input Remote control start contacts Auxiliary hot water inlet pressure (optional) Auxiliary hot water outlet pressure (optional) Temperature reset signal Standard feedback temp sensor (optional) Standard input temp sensor (optional) Remote end temp reset sensor (optional) Item Standard Option Fluid Type Fresh Water Ethylene Glycol Propylene Glycol Tube Copper Cu/Ni Max. Working Pressure 1.0MPa 1 1.6MPa; 2 2.0MPa Fluid Type Fresh Water Ethylene Glycol Propylene Glycol Tube Copper Cu/Ni Max. Working Pressure 1.0MPa 1 1.6MPa; 2 2.0MPa Condenser Tube Copper Cu/Ni Low Temp Generator Tube Copper Cu/Ni Shipment 1-Piece 2-Piece Power supply 380v-3Ph-50Hz 400v, 415v, 460v 60Hz Control ICVC CCN Burner Light oil or natural gas type Sookook burner Dual fuel burner Weishaupt burner Heating Capacity Standard type Heating amplification type 13

9 Standard Tubing Flow Chart Burning System Automatic water makeup Automatic water makeup Exhaust Exhaust Flue Natural Gas System Exhaust Pressure Gauge Ball valve Filter Flowmeter Pressure Gas Leakage Regulating Valve Switch Burner High Temp Generator Low Pressure Gas Switch Electromagnetic valve High Pressure Gas Switch Scope of Supply by Customer Scope of Supply by Carrier 14 Pressure Gauge Thermometer Flowmeter Check Valve Three-Way Valve Water Filter Chilled Water Pump Cooling Water Pump Air Handling Unit Chilled Water Supply Pipe Chilled Water Return Pipe Expansion Tank Flue Cooled Water Supply Pipe Cooling Water Return Pipe Cooling Tower 1. Please refer to Overall Dimension & Physical Data for pipe connection positions and sizes. 2. Positions of the equipment such as chilled (warm) water pump, cooling water pump, expansion tank, etc. shall take account of water level difference and static pressure to ensure the gauge pressure of the unit does not exceed 1.0MPa (it is the non-standard model if water pressure is greater than 1.0MPa). 3. Each unit shall be configured with relevant special chilled water pump, cooling water pump and cooling tower. Meanwhile, each unit shall be connected to other units so that they can serve as standby for each other. 4. (8~10 meshes) filter shall be installed in front of the inlet of chilled water and cooling water system tube of the unit. 5. Pressure gauge (0~1.5MPa) and thermometer (0~100 C) shall be set at the inlet/outlet of the chilled water and cooling water of the unit. 6. Air vent valve shall be set at the position where chilled water and cooling water system pipe higher than each water chamber, and drain valve shall be set the bottom of the inlet pipe of chilled water and cooling water. 7. Air vent (R3/4 ) shall be set at the top of the water chamber of evaporator and absorber of the unit. 8. outlet (R3/4 ) shall be set at the bottom of the water chamber of evaporator and absorber of the unit, where pipe to the drainage ditch shall be installed. 9. If cooling water inlet temperature tends to decrease to below 15 C, a bypass valve shall be installed at the place indicated with dashed line in the figure to maintain cooling water temperature not lower than 15 C. 10. Please set water flow adjusting valve at the inlet pipe of cooling water. 11. Please provide support for piping. All pipes shall carry no load. 12. While the unit stops during heat supply operation in winter, it must guarantee that the water in the unit and pipes can be drained completely to prevent from frost damage to the pipe. 13. During heat supply operation of the unit, outer wall temperature of the pipes connected to the absorber may reach over 80 C. High temperature resistant material shall be used for thermal insulation for a section of cooling water pipe close to the absorber. 14. Connecting hose shall be set at the connecting part of the unit and each pipe. 15. Water pressure detection for chilled water and cooling water system must be carried out in accordance with relevant standard. It is strictly forbidden to adopt air pressure detection. 16. It would be better to set expansion tank on chilled water system. 17. To measure flow in chilled water pipe, it is recoended to set flowmeter on the pipe. 18. Please refer to relevant contents for chilled water and cooling water quality control to decide whether water treatment equipment should be set or not. 19. Cooling tower should be set at well-ventilated place, in the upwind direction of smoke, dust, etc Machine room environment: poor ventilation may cause the machine room to become humid, which may corrode machine. Too high temperature may damage electric components of the unit, while too low temperature may lead to frost crack of copper tube. Temperature in machine room shall be controlled within 5~40 C, and humidity shall be controlled below 95%. Light Oil System Oil Supply Valve Blow-Off Valve Water Quality Control Breather Valve Oil Pump Blow-Off Valve Breather valve Flowmeter Gas-Oil Separator Pipe indicated by dashed line shall be set if the oil storage tank is higher than daily oil tank Scope of Supply by Customer Burner Oil Pressure Regulator Electromagnetic valve Scope of Supply by Carrier High Temp Generator 1.Design of exhaust system (1)In design of flue and chimney, fuel gas outlet pressure of the unit shall maintain -49~0Pa (-5~0H2O). (2)Fume condensate exhaust tube shall be set at the lowest place of the horizontal flue above the unit to drain condensate water into sewer smoothly. (3) Thermal insulating material shall be based on temperature of 350 C. 3.The above-mentioned natural gas system is based on the inlet pressure of 7kPa Items Cooling Water * Chilled/Hot Water Tendency One-pass Circulating Make-up Circulating Make-up Corrosion Scale PH (25 C) 6.8 ~ ~ ~ ~ ~ 8.0 O O Electrical Conductivity (25 C ms/m) O O M Alkalinity (mg/l) O Total Hardness (mg/l) O Chlorine Ion (mg/l) O Sulfuric Acid Ion (mg/l) O Total Iron (mg/l) O O Sulfur Ion (mg/l) Not Detected O Aonium Ion (mg/l) O Silica (mg/l) O Total Copper (mg/l) O 15

10 Thermal Insulation Hoisting & Shipping Schematic of Thermal Insulation Hoisting & Shipping Evaporator Condenser Low Temp Genarator An absorbing pad should be placed below the support of the unit to reduce vibration during the shipment. Transport personnel should decelerate when driving on bumpy road to prevent unit from damage due to intense vibration. (1)Please hoist the unit carefully. Ensure no part will be damaged. If lifting rope contacts wearing part, length of lifting rope shall be adjusted to avoid contacting wearing part. (2)When lifting down the unit, please keep the horizontality of the unit. Ensure base frame of the unit contacts ground simultaneously. (3)Bed plate only serves as an anti-vibration tool, instead of standard component part of the unit; When the unit is installed in place, bed plate shall be removed. Refrigerant Pump Solution Pump Absorber Control Panel High Temp Generator 75 thick thermal insulating material: high temperature generator, etc. 50 thick thermal insulating material: low temperature generator, vapor pipe. 25 thick thermal insulating material: heat exchanger, etc. 50 thick thermal insulating material: evaporator, etc. 25 thick thermal insulating material: solution pump, refrigerant pump, etc. Thermal insulation shall be made after installation and coissioning Insulating material shall not be inflaable, water absorbent or air permeable. Thermal insulation for water chamber shall facilitate opening/closing of water cover during maintenance. Thickness and area of insulation material is shown in the following table. Control panel and motors of solution pump and refrigerant pump do not require thermal insulation. Joint of the thermal insulation material shall be sealed with tape to avoid dampness. Bonding agent should be used in installation of thermal insulation. Welding is strictly prohibited. Placement Thermal Insulation Area Thickness Usage () 75 Hot Area 50 (m 2 ) Cold Area (m 2 ) 25 Location High Temp Generator Low Temp Generator, vapor Pipe Solution Heat Exchanger Evaporator Pump, Pipe 16DNH (1)Before the installation, confirm that concrete foundation has enough hardness. (2)After the installation, adjust the longitudinal and horizontal level of the unit based on level benchmark point of the tube plate of the unit. Adjusted level error shall be less than 1/1000. (3)After level adjustment is completed, pour concrete mortar into square foundation bolt holes, and tighten foundation bolts used to fix the unit after concrete mortar is hardened. Longitudinal level measuring point Horizontal level measuring point 1. Insulation material for hot area : glass fiber, asbestos or material with similar performance 2. Insulation material for cold area : polyethylene foamed plastic or material with similar performance 16 17

DOUBLE EFFECT ABSORPTION CHILLERS

DOUBLE EFFECT ABSORPTION CHILLERS DOUBLE EFFECT ABSORTION CHILLERS STEAM CONSUMTION RATE3.9kg/(hUSRt) 3.95kg/(hUSRt) Model in this catalog is our model code. MODEL REW is; The double effect chiller is high efficiency model, The chiller

More information

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER HEATER 1. General Description The Contractor shall furnish and install (Qty) Yazaki model CH- Gas Fired,

More information

Specifications in the catalogue are subject to change without notice. AR-1012 Printed in Korea

Specifications in the catalogue are subject to change without notice. AR-1012 Printed in Korea Seoul office : 1094, Hwagok-6Dong, Kangseo-Ku, Seoul, Korea (ZIP code : 157-927) Head office : 1Dongsan-lee, Tangjung-myun, san-chi, Chungnam, Korea Tel : 82-2-2600-9596 Fax : 82-2-2600-9549 E-mail : sales@century.co.kr

More information

Absorption Chiller Heat Pump

Absorption Chiller Heat Pump For Future Energy & Environment - KTL KITECH World Energy bsorption Chiller Heat Pump CONTENT Features / Control Sytstem / bsorption Cycle 2 1 Double Effect Exhaust Gas Driven bsorption Machine 12 2 Single

More information

Guide Specifications

Guide Specifications Guide Specifications Hot Water fired Adsorption Liquid Chillers Bry-Air Adsorption Chiller Overview The chiller shall be a Bry-Air ADC series. The chiller shall consist of a robust, compact, packaged chiller

More information

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities

Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Cooling Capacities Gas Fired Double-Effect Chiller-Heater CH-MG Series: 150 and 200 RT Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas Fired DOUBLE-EFFECT Chiller-Heater Absorption Principle Yazaki MG-Series

More information

SYSTEM DESIGN REQUIREMENTS

SYSTEM DESIGN REQUIREMENTS P a g e 1 SYSTEM DESIGN REQUIREMENTS WFC-S SERIES WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLERS / CHILLER-HEATERS Yazaki WFC-S Series water-fired chillers and chiller-heaters are available with nominal

More information

16LJ Single-Effect Hot Water-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw

16LJ Single-Effect Hot Water-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw Single-Effect Hot Water-Fired Absorption Chillers SUPER ABSORPTION GB/T-191-2 to ISO91/2 16LJ 11-53 Nominal cooling capacity 264-1846 kw The Carrier Corporation has more than 1 years experience in providing

More information

TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series

TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series Absorption Chillers TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series Stable Chilled Water Outlet Temperature PID control is applied to maintain constant chilled water outlet temperature. When the cooling

More information

MODELS LIST. Nominal Capacity RT

MODELS LIST. Nominal Capacity RT 1. MODELS LIST. NOMENCLATURE 3. FEATURES 4. PRODUCT DATA 5. PERFORMANCE CORRECTION 6. ANTIFREEZE 7. INSTALLATION 8. ELECTRICAL DATA 9. SCHEMATIC WIRING DIAGRAM 10.MICROPROCESSOR CONTROLLER 11.APPLICATION

More information

16TJ Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw

16TJ Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION GB/T-191-2 to ISO91/2 16TJ 11-53 Nominal cooling capacity 352-2461 kw The Carrier Corporation has more than 1 years experience in providing

More information

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation Air-Cooled Liquid Chillers www.eurovent-certification.com www.certiflash.com Quality Management Systems 0RB 008-05 Nominal cooling capacity 8- The new generation of Aquasnap liquid chillers was designed

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

16TJ Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw

16TJ Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION. Nominal cooling capacity kw Single-Effect Steam-Fired Absorption Chillers SUPER ABSORPTION GB/T-191-2 to ISO91/2 16TJ 11-53 Nominal cooling capacity 352-2461 kw The Carrier Corporation has more than 1 years experience in providing

More information

Gas-Fired Double-Effect Chiller-Heater

Gas-Fired Double-Effect Chiller-Heater Gas-Fired Double-Effect Chiller-Heater CH-K Series: 30, 40, 50, 60, 80, 100 RT Cooling with Standard Heating Capacities W E A R E F R I E N D L Y T O T H E E A R T H Gas-Fired Double-Effect Chiller-Heater

More information

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient PRODUCT SELECTION DATA Easy and fast installation Compact, reliable and efficient Class A variable speed circulator available Air-Cooled Liquid Chillers 0RB 008-015 CARRIER participates in the ECP programme

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

AQUASNAP JUNIOR 30RHV

AQUASNAP JUNIOR 30RHV High-Efficiency Air-To-Water Heat Pumps Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. AQUASNAP JUNIOR 3RHV 6-11

More information

Technical Catalog SAB-LW Series Single Effect Double Lift Hot Water Driven Absorption Chiller 65 to 1,300 Nominal Tons (229 to 4,571 kw)

Technical Catalog SAB-LW Series Single Effect Double Lift Hot Water Driven Absorption Chiller 65 to 1,300 Nominal Tons (229 to 4,571 kw) Technical Catalog SAB-LW Series Single Effect Double Lift Hot Water Driven Absorption Chiller 65 to 1,300 Nominal Tons (229 to 4,571 kw) 1 SAB-LW, Single Effect Double Lift Hot water driven absorption

More information

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw AIR-COOLED LIQUID CHILLER REVERSIBLE AIR-TO-WATER HEAT PUMP PRO-DIALOG PLUS 30RB/RQ 039S-60S Refrigerant HFC-40A Nominal cooling capacity 40-58 kw Nominal heating capacity 4-59 kw The new generation of

More information

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Air Conditioning Clinic Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Absorption Water Chillers One of the Equipment Series A publication of The Trane Company Worldwide Applied Systems

More information

Product Data. Features/Benefits. 16JT Double-Effect Hermetic. Absorption Liquid Chillers Provide. With Product Integrated Controls (PIC)

Product Data. Features/Benefits. 16JT Double-Effect Hermetic. Absorption Liquid Chillers Provide. With Product Integrated Controls (PIC) Product Data 16JT Double-Effect Hermetic Absorption Liquid Chiller With Product Integrated Controls (PIC) Nominal 100 to 1700 Tons (352 to 5980 kw) Carrier s 16JT Double-Effect Hermetic Absorption Liquid

More information

DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1

DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1 DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1 Specifications CH-MG150CE CH-MG200CE Version 9.10 Contents Page 1. General Information 1.1 Chiller-heater... 2 1.1.1 Chiller-heater Specification. 2

More information

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers Self-adjusting electronic control Cooling capacity: 35 to 700 kw 410A Cooling Operation DYNACIAT - DYNACIAT POWER

More information

Submittal Data GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating

Submittal Data GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating The High Efficiency AYF60-119 units are 2 module appliances; each AYF is

More information

16TJ Single-Effect Steam-Fired Absorption Chillers

16TJ Single-Effect Steam-Fired Absorption Chillers 16TJ Single-Effect Steam-Fired Absorption Chillers Nominal cooling capacity 352-2461 kw 50 Hz Operation and maintenance instructions GB/T-19001-2000 to ISO9001/2000 NOTES TO USERS Thank you for purchasing

More information

BROAD PACKAGED POWER-EFFICIENT CHILLER

BROAD PACKAGED POWER-EFFICIENT CHILLER BROAD CENTRAL AIR CONDITIONING & MAGNETIC BEARING OIL FREE CHILLER BROAD PACKAGED POWER-EFFICIENT CHILLER MODEL SELECTION & DESIGN MANUAL Application Provide chilled water for central air conditioning

More information

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers. NEW GXG-S Series GSG-S Series Debut

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers. NEW GXG-S Series GSG-S Series Debut Featuring Ozone-safe HFC134a Hitachi Centrifugal Chillers NEW GXG-S Series GSG-S Series Debut Centrifugal Chiller New GXG-S, GSG-S Series Debut High-efficiency New series Centrifugal Chillers that use

More information

16NK Double-Effect Steam-Fired Absorption Chillers

16NK Double-Effect Steam-Fired Absorption Chillers 16NK Double-Effect Steam-Fired Absorption Chillers Nominal cooling capacity 345-4652 kw 50 Hz Operation and maintenance instructions GB/T-19001-2000 to ISO9001/2000 Notes to Users Thank you for purchasing

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: 40-158 kw Nominal heating capacity: 41-159 kw Carrier China Carrier Corporation is a subsidiary of the United Technologies

More information

Air-Cooled Condensing Units with Compact Screw Compressors

Air-Cooled Condensing Units with Compact Screw Compressors LK-SCUTB March 2015 Air-Cooled Condensing Units with Compact Screw s Technical Bulletin Models SSV DSV Table of Contents Nomenclature Chart... 2 Introduction... 3 Bitzer TM s... 4 Magnum TM Microprocessor...

More information

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers NEW. GXG-S Series GSG-S Series. Debut

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers NEW. GXG-S Series GSG-S Series. Debut Featuring Ozone-safe HFC134a Hitachi Centrifugal Chillers NEW GXG-S Series GSG-S Series Debut Centrifugal Chiller New GXG-S, GSG-S Series Debut High-efficiency New series Centrifugal Chillers that use

More information

Technical Catalog. SAB-HW Series Hot Water Driven Absorption Chiller 15 to 1000 Nominal Tons (52 to 3516 kw) ISO 9001 ISO CHP Solution Inc.

Technical Catalog. SAB-HW Series Hot Water Driven Absorption Chiller 15 to 1000 Nominal Tons (52 to 3516 kw) ISO 9001 ISO CHP Solution Inc. Technical Catalog SAB-HW Series Hot Water Driven Absorption Chiller 15 to 1000 Nominal Tons (52 to 3516 kw) ISO 9001 ISO 14001 CHP Solution Inc. USA 1 SAB-HW, Hot water driven absorption chillers, provides

More information

WFC-M Series Installation. WFC- M Series. Hot Water Fired single Effect Absorption Chiller. Installation WFC-M100 Version 1.0 (Original/Document)

WFC-M Series Installation. WFC- M Series. Hot Water Fired single Effect Absorption Chiller. Installation WFC-M100 Version 1.0 (Original/Document) WFC- M Series Hot Water Fired single Effect Absorption Chiller 2 Installation WFC-M100 Version 1.0 (Original/Document) - 0 - Contents 1. General Information 1.1 Precautions... 2 1.2 Receiving... 2 1.3

More information

products 22 º C Ventilation Air Conditioning Refrigeration Maritime Absorption Chiller Inside PROVIDED BY HEINEN & HOPMAN

products 22 º C Ventilation Air Conditioning Refrigeration Maritime Absorption Chiller Inside PROVIDED BY HEINEN & HOPMAN products > Maritime Absorption Chiller OUTSIDE 35 C HUMIDITY 90% 22 º C Inside PROVIDED BY HEINEN & HOPMAN Heating Ventilation Air Conditioning Refrigeration INTRODUCTION Absorption chillers use heat to

More information

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW TECHNICAL INSTRUCTIONS PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER to KW PHRT PHRT PHRT PHRT For terminal units and boiler overhaul applications Heating Cooling PHRT.00 kw -. kw PHRT.0 kw /.0 kw

More information

Double Effect Exhaust Gas Driven Absorption Machine

Double Effect Exhaust Gas Driven Absorption Machine For Future Energy & Environment erformance Data Double Effect Gas Driven Absorption Machine Double Effect Gas Driven ype (50~R) Unit CH005 CH006 CH007 CH008 CH010 CH012 CH015 CH018 CH021 CH024 CH028 CH032

More information

Product Data. Features/Benefits. 16TJ Single-Effect, Steam Hermetic Absorption Liquid Chiller. 100 to 700 Nominal Tons

Product Data. Features/Benefits. 16TJ Single-Effect, Steam Hermetic Absorption Liquid Chiller. 100 to 700 Nominal Tons Product Data 16TJ Single-Effect, Steam Hermetic Absorption Liquid Chiller 100 to 700 Nominal Tons Carrier-Sanyo s 16TJ single-effect hermetic absorption liquid chiller is an efficient and functional alternative

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost LL Chillers and Outdoor Mechanical Rooms Air-Cooled Features: Air-cooled condenser chillers with capacities from 35-345 tons Evaporative-cooled condenser chillers with capacities from 35-540 tons Variable

More information

Water-Fired Chiller/Chiller-Heater. WFC-S Series: 5, 10, 20, 30 and 50 RT Cooling

Water-Fired Chiller/Chiller-Heater. WFC-S Series: 5, 10, 20, 30 and 50 RT Cooling Water-Fired Chiller/Chiller-Heater WFC-S Series: 5, 10, 20, 30 and 50 RT Cooling Water-Fired SINGLE-EFFECT Chiller or Chiller-Heater Yazaki Water-Fired SINGLE-EFFECT chillers have cooling capacities of

More information

BROAD X VACUUM BOILER

BROAD X VACUUM BOILER BROAD X VACUUM BOILER MODEL SELECTION & DESIGN MANUAL Function Heating, hot water (Dedicatedly or simultaneously) Application Applicable for any building heating systems Produce hot water below 95 Heating

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

Screw Water Cooled Chiller SCW210

Screw Water Cooled Chiller SCW210 Screw Water Cooled Chiller SCW210 Nominal Cooling Capacity 185.1 to1480.8 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data 5 Unit Performance 8 Chiller Selection 9 Physical

More information

Technical Data Sheet

Technical Data Sheet Technical Data Sheet Bulletin : BAA:D0054 Effective : April. 06, 2015 Supercedes Date : ADSORPTION CHILLER ADC Series C-FRAME FEATURE HIGHLIGHTS * Ultra low electricity consumption * Ease of maintenance

More information

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series Centrifugal Chiller High Efficiency GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series Centrifugal Chiller High Efficiency Centrifugal Chiller HC-F-GFG-SSC Series (Super High Efficiency Type) HC-F-GXG-S

More information

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2 MARKING This product marked conforms to the essential

More information

Product Data. Features/Benefits. 30RQ Air-cooled Modular Chiller R22 & R410A & R407C

Product Data. Features/Benefits. 30RQ Air-cooled Modular Chiller R22 & R410A & R407C Product Data 30RQ Air-cooled Modular Chiller R22 & R410A & R407C Introduction Air-cooled modular chiller is a kind of central airconditioning unit which adopts air as the cooling (or heating) source and

More information

Commercial Air Conditioners 2017/2018

Commercial Air Conditioners 2017/2018 Coercial ir Conditioners 207/208 Water Cooled Screw Chiller Flooded type 340-780kW (R34a) Midea CC Midea CC is a key division of the Midea Group, a leading producer of consumer appliances and provider

More information

Product Data. Features/Benefits. 16JB Steam/Hot Water Single Effect, Hermetic Absorption Liquid Chiller 50/60 Hz

Product Data. Features/Benefits. 16JB Steam/Hot Water Single Effect, Hermetic Absorption Liquid Chiller 50/60 Hz Product Data 16JB Steam/Hot Water Single Effect, Hermetic Absorption Liquid Chiller 50/60 Hz 108 to 680 Nominal Tons (380 to 2392 kw) Carrier s 16JB single effect hermetic absorption liquid chiller offers

More information

Modular Water Cooled Water Chiller

Modular Water Cooled Water Chiller Modular Water Cooled Water Chiller Shandong Vicot Air Conditioning Co., Ltd. Shandong Vicot Air Conditioning Co., Ltd. is one of the major players in the Chinese air conditioning industry, specialized

More information

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS David Grassl PE Mechanical Engineer Principal Similar to traditional boiler systems, condensing boiler systems have many designs they can operate

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY Easy and fast installation Hydronic module available Compact, reliable and efficient Nominal cooling capacity : 8-40 kw Nominal heating capacity : 17-40 kw 50 410A Cooling or heating USE The air-to-water

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7

More information

Recirculating Coolers

Recirculating Coolers 09 Recirculating Coolers (chillers) General Recirculating Coolers Low Temp. Recirculating Coolers Advanced Low Temp. Recirculating Coolers High Temp. Recirculating Coolers Compact Recirculating Cooler

More information

Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products. Product overview

Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products. Product overview Product overview 1 Company Profile Yantai Oceanair Refrigeration & Air-Conditioning Co.,Ltd. was established in 2004 and has been listed on the New OTCBB (Stock Code: 831870). We are mainly specialized

More information

MAC-D R410A Series Air-cooled Modular Chiller/Heat pump

MAC-D R410A Series Air-cooled Modular Chiller/Heat pump Catalogue MAC-D-2013 (50Hz) MAC-D R410A Series Air-cooled Modular Chiller/Heat pump Model: Refrigerant: Cooling Capacity: Heating Capacity: MAC210D5-MAC1680D5 MAC230D5-MAC1840D5 MAC210DR5-MAC1680DR5 MAC230DR5-MAC1840DR5

More information

Refrigerated Compressed Air Dryer

Refrigerated Compressed Air Dryer Manual Instruction for Refrigerated Compressed Air Dryer Warning: Place the dryer machine horizontal. Never upside down Dino-power Industry & Trade Co., Ltd www.aircompressorschina.com Dino-power 1 PREPARED

More information

ABSORPTION CHILLER PRODUCT CATALOGUE

ABSORPTION CHILLER PRODUCT CATALOGUE China Well-known Trade Mark China Famous Brand ABSORPTION CHILLER PRODUCT CATALOGUE Flue Gas Operated LiBr Absorption Chiller/Heater Hot Water Operated LiBr Absorption Chiller Steam Operated LiBr Absorption

More information

FEATURS HYUNDAI CLIMATE CONTROL CO., LTD.

FEATURS HYUNDAI CLIMATE CONTROL CO., LTD. FEATURS 1. Direct-fired absorption chiller-heater gives both heating and cooling. 2. The high efficiency associated with the absorption chilling system has reduced the space required for installation.

More information

GAS ABSORPTION HEAT PUMP

GAS ABSORPTION HEAT PUMP G A H P VV GAS ABSORPTION HEAT PUMP Water Cooled Gas Fired Absorption Heat Pump > Make a choice to build up the future G A H P VV GAS ABSORPTION HEAT PUMP WATER COOLED GAS FIRED ABSORPTION HEAT T PUMP

More information

Scroll Water Cooled Chiller

Scroll Water Cooled Chiller Scroll Water Cooled Chiller SRW145 Nominal Cooling Capacity 77 to 1232 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data 5 Unit Performance 8 Chiller Selection 9 Physical

More information

1.0 CONDITIONS FOR CHILLED WATER SUPPLY (PRIMARY SIDE BY DHCS SUPPLIER)

1.0 CONDITIONS FOR CHILLED WATER SUPPLY (PRIMARY SIDE BY DHCS SUPPLIER) GENERAL This document contains the basic technical information for Architectural, Civil & Structural and M&E Building Services as required by supplier to achieve optimum operation. The time frame required

More information

Vicot Air Conditioning Co., Ltd. CONTENT

Vicot Air Conditioning Co., Ltd. CONTENT CONTENT I. Introduction 2 II. Absorption Principle 3 III. GAX Absorption Cycle 3 IV. Major Component Description and Function 4 V. Features 4 VI. Performance curve 5 VII. Nomenclature 5 VIII. Technical

More information

Hitachi Centrifugal Chillers

Hitachi Centrifugal Chillers Featuring Ozone-safe HCF134a Hitachi Centrifugal Chillers HC-F-GXG Higher-efficiency Type ARI temperature condition JIS temperature condition 1,463 kw to 4,571 kw (416 USRT to 1, USRT) 1,407 kw to 4,395

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

Adsorption Chillers Energysmart Green Cooling

Adsorption Chillers Energysmart Green Cooling Adsorption Chillers Energysmart Green Cooling New Partners in innovation Leaders in Dehumidification... Worldwide Power Partner Inc USA www.bryair.com Recover Low Grade Process Waste Heat For Energy Smart

More information

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation AIR-TO-WATER HEAT PUMPS 30RQV 017-021 NEW Nominal cooling capacity 15-18 kw Nominal heating capacity 17-21 kw greenspeed Easy and fast installation Hydronic module available Inverter technology compressor

More information

MAC-A R410A Series Air cooled Modular Chiller

MAC-A R410A Series Air cooled Modular Chiller Catalogue MAC R410A 2011(60Hz) MAC-A R410A Series Air cooled Modular Chiller Model: Refrigerant: Co ling Capacity: MAC210A5 R410A 72kW Overview Based on the successful McQuay air-cooled modular chiller,

More information

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: ,

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: , DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: +971-6-5432526, Fax#: +971-6-5432415, Email: dolcool@emirates.net.ae, web site: www.dolphinheattransfer.com NOMENCLATURE: INTRODUCTION DOLCOOL branded

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

19DV Back-to-Back Centrifugal Liquid Chiller with PUREtec TM Refrigerant and Greenspeed TM Intelligence

19DV Back-to-Back Centrifugal Liquid Chiller with PUREtec TM Refrigerant and Greenspeed TM Intelligence 19DV Back-to-Back Centrifugal Liquid Chiller with PUREtec TM Refrigerant and Greenspeed TM Intelligence 19DV Two-stage: 600-800Ton (Air-conditioning Low voltage VFD) Turn To The Experts Inheriting a rich

More information

Method to test HVAC equipment at part load conditions

Method to test HVAC equipment at part load conditions IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking

More information

ERACS.C-N Higher efficiency air-cooled screw pump

ERACS.C-N Higher efficiency air-cooled screw pump ELITE TM Series COOLING ERACS.C-N Higher efficiency air-cooled screw pump HEATING HOT WATER Cooling Capacity:5~1341 (7~381 Tons) Heating Capacity:60~1363 (74~388 Tons) High Efficiency Air-cooled Heat Pump

More information

120D, 150D, 190D, 240D, 370B. How to Order 220V 240V 400V 440V. Note 1) Select one applicable voltage. Voltage. Voltage. Symbol. Model 370B 220V 240V

120D, 150D, 190D, 240D, 370B. How to Order 220V 240V 400V 440V. Note 1) Select one applicable voltage. Voltage. Voltage. Symbol. Model 370B 220V 240V Refrigerant R7 0, 0 90 I ir compressor Refrigerant 0kW kw 90kW kw Refrigerant R 70 I Refrigerant R7, R Series I Large 0,, 90,, 70 0 90 R7 Size 70 7 9 0 90 Three Voltage 7 9 Voltage 00/00 to 0V (/Hz) 0V

More information

precision controlled industrial process chillers cooling capacity: ,255,668 BTU /hr ( tons) improved productivity & reduced costs

precision controlled industrial process chillers cooling capacity: ,255,668 BTU /hr ( tons) improved productivity & reduced costs next generation C precision controlled industrial process chillers cooling capacity: 6824 -,255,668 BTU /hr (0.6-04.6 tons) cooling capacity: 6,824 -,254,303 BTU/hr (0.6-04.5 tons) precision controlled

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01

ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01 ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01 1. Use and construction of the pump and control unit The pump and control unit is designed to work with solar collectors in systems with required

More information

DEVELOPMENT OF THE WORLD S FIRST SMALL-SCALE TWO-STAGE ABSORPTION CHILLER/HEATER/HOT-WATER SYSTEM

DEVELOPMENT OF THE WORLD S FIRST SMALL-SCALE TWO-STAGE ABSORPTION CHILLER/HEATER/HOT-WATER SYSTEM DEVELOPMENT OF THE WORLD S FIRST SMALL-SCALE TWO-STAGE ABSORPTION CHILLER/HEATER/HOT-WATER SYSTEM Zhang Yue, CEO Broad Air Conditioning, Ltd., Changsha, China Ronald Fiskum, Integrated Energy Systems Project

More information

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01 b cool manufacturers of air-conditioning equipment ltd BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION Ver. 1.01 Ver. 3.02 01_18 BCool# 1 brt c/h r407c / r410a

More information

Be sustainable while protecting your business

Be sustainable while protecting your business Be sustainable while protecting your business Aquaflair 50Hz Air-cooled chillers and free-cooling chillers with double screw compressors and HFO R1234ze refrigerant (400V/3ph/50Hz) 300-1000 kw Aquaflair

More information

Tel: Fax: Website:

Tel: Fax: Website: Vacuum Dehydration Oil Purification System(Oil Purifier) The water and particles contamination in lubrication, hydraulic and dielectric oils badly affect the oils performance and threaten system reliability.

More information

3 0 H X C A - H P 2

3 0 H X C A - H P 2 3 0 H X C 1 3 0 A - H P 2 Max. Leaving Water Temperature (Heating Mode) 1 for 47 O C,2 for 60 O C Water-to-Water Screw Heat Pump 3 rd Generation Global Water Cooled Chiller Norminal Capacity (USRT) Carrier

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

LG HVAC SOLUTION AIR COOLED SCROLL CHILLER

LG HVAC SOLUTION AIR COOLED SCROLL CHILLER LG HVAC SOLUTION AIR COOLED SCROLL CHILLER Nomenclature Factory Refrigerant: U: China, R410A Cooling Type: A: Air cooled C/O H: Air cooled H/P Capacity: [Air Cooled C/O & H/P ] Unit: 020 : 20RT Line up:

More information

BROAD X Absorption Chiller

BROAD X Absorption Chiller BROAD X Absorption Chiller Model Selection & Design Manual Function cooling, heating, hot water Application To Provide chilled/heating water for large-scale buildings To Produce chilled water over 3 C

More information

AHU Plus. DX Air Handling Units

AHU Plus. DX Air Handling Units AHU Plus DX Air Handling Units AHU Plus DX DX Air Handling Units AHUPlusDX-TH: DX Air Hadling Unit with 100% Fresh Air AHUPlusDX -IGK: DX Air Hadling Unit with 100% Fresh Air and Heat Recovery AHUPlusDX-KH:

More information

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG +

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG + Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG + Quality Management Systems 30RBY/RQY 017-033 Nominal cooling capacity 15-33 kw Nominal heating capacity 17-31 kw The new

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

16TJ Single-Effect Steam-Fired Absorption Chillers

16TJ Single-Effect Steam-Fired Absorption Chillers 16TJ Single-Effect Steam-Fired Absorption Chillers Nominal cooling capacity 35-461 kw 5 Hz Installation instructions GB/T-191- to ISO91/ Notes to Users Thank you for purchasing a Carrier/Sanyo absorption

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

Neosys Product catalogue

Neosys Product catalogue 00/0 Neosys Product catalogue Providing indoor climate comfort NEOSYS 00 0 kw Air cooled chiller/heat pump YEAR WARRANTY* Quality makes the difference* Introduction to the range NEOSYS is providing chilled

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Material Handling Process Cooling Temperature Control Size Reduction Temperature Control Process Cooling Material Handling Size Reduction GP SERIES Packaged Chillers Precision Comprehensive Engineered

More information

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a Air-Cooled Variable Speed Drive Screw Chillers Super Efficient Super Quiet Cooling Capacity Range 540-1405 kw R134a World s first low sound Air-Cooled variable speed drive screw chiller The recognition

More information

Chemistry diaphragm pumps

Chemistry diaphragm pumps Oil-free vacuum for corrosive gases and vapors Chemistry diaphragm pumps Series overview Examples of use Down to 70 Pumping of aggressive gases and vapors For low-boiling solvents Vacuum filtration Down

More information

TCHE-THHE TCEE

TCHE-THHE TCEE K11206-GB ed. 6 TCHE-THHE 155 2130 TCEE 155 2130 Q-Flow range Macrosystem 50,2 124,5 kw TCHE-THHE - Water cooled water chillers and heat pumps units with environmentally friendly refrigerant. Range with

More information

Appendix A. Glossary of Common Terms

Appendix A. Glossary of Common Terms Glossary of Common Terms Glossary of Common Terms Absorption chiller A refrigeration machine using heat as the power input to generate chilled water. Adjustable speed drive A means of changing the speed

More information