TAC Erie VL500. Application. Features. Zone Valve Control Center General Instructions
|
|
- Gillian Butler
- 5 years ago
- Views:
Transcription
1 TAC Erie VL500 Zone Valve Control Center General Instructions Application The VL500 zone control system provides control of up to five zone valves, a circulator and boiler control in a multi-zone hydronic heating system. Field selectable priority for zone 1 eliminates the need for additional relays to provide domestic hot water priority. Additional zones can be added. Features Field selectable priority or Priority Plus zone Unlimited zone expansion. Maximum load on any serially linked VL500 slave module should not exceed 50 VA Field replaceable relay LED status window Common 24 Vac transformer terminal Field replaceable fuse VL500 Printed in U.S.A Copyright 2008 TAC All Rights Reserved. F
2 SPECIFICATIONS Inputs Power (N-L1): 120 Vac, 50/60 Hz, 100 VA. Main Fuse (F2): 10A, 250 Vac slow blow (Bussman MDA-10 or equal) Thermostat/Heat Demand Dry Contacts (- through T5-T5): 24 Vac, Class 2 Switched load is 0.05A plus load current at corresponding "1-2" terminals. (Power supplied by this unit - do not connect external power source). Set thermostat anticipator per thermostat instructions to measured current. Zone in Terminals: External dry contacts rated for 24 Vac, 2.2 A (58VA), Class 2 Outputs Environment Line Voltage Circulator Output (C1-N): Motor: 1/3 120 Vac Boiler Output (Dry Contact X1-X2): General Purpose: 24 Vac, Class 2 Transformer: 24 Vac, 75 VA Class 2 (total external loads limited as specified below) Secondary Fuse (F1): 3.2A, 250 Vac slow blow (Bussman MDQ-3 2/10 or equal) Zone Valve Outputs (5 pair of terminals 1-2): 24 Vac, Class 2 Any Single Zone : 0.9A (22VA), Maximum Total for Master Zone Valves and Thermostats: 2.7A (65VA), Maximum Total for Slave Zone Valves and Thermostats: 2.1A (50VA), Zone Out Terminals: Switching capacity: 24 Vac, 2.2A (58VA), Class 2 Operating Temperature Limits: 32 to 104 F (0 to 40 C). Humidity: Up to 85% RH non-condensing. Shipping Weight: 6 lbs (2718 g). Location: NEMA Type 1 (IP20). 2 Copyright 2008 TAC All Rights Reserved. F
3 TYPICAL APPLICATIONS (wiring diagram) 4-WIRE JUMPER 3 & 4 WHEN USING S 2 WIRE JUMPER 3& VAC (Hot) 12:00 RWC Switched 24VAC (Com) COM T2 T T3 T T4 T T5 T PRIORITY 1 24VAC Fuse 2 3.2A/250V Slo-Blo Fuse F1 IN 10A/250V Slo-Blo Fuse F2 OUT 3 T2 T3 T4 T5 PL 120VAC Fuse 4 OFF P P+ S M Z1 Z2 Z3 Z4 Z5 ES/CIRC SYSTEM STATUS X T X T BOILER CONTROL C1 N CIRCULATOR (HOT) L1 N (COM) 120VAC Figure-1 Typical Wiring VL500 Series. DHW Controller DOMESTIC HOT WATER 4-WIRE END SWITCH R W JUMPER 3 & 4 WHEN USING S 2 WIRE JUMPER 3& VAC (Hot) 12:00 RWC Switched 24VAC (Com) COM T2 T T3 T T4 T T5 T PRIORITY 1 24VAC Fuse 2 3.2A/250V Slo-Blo Fuse F1 IN 10A/250V Slo-Blo Fuse F2 OUT 3 T2 T3 T4 T5 PL 120VAC Fuse 4 OFF P P+ S M Z1 Z2 Z3 Z4 Z5 ES/CIRC SYSTEM STATUS X X C1 N L1 N T T BOILER CONTROL (HOT) (COM) CIRCULATOR 120VAC Figure-2 Typical Wiring VL500 Series with Domestic Hot Water Priority Zone, Boiler Controller and Circulator. F Copyright 2008 TAC All Rights Reserved. 3
4 VL500 #2 (Slave) VL500 #1 (Master) NOTE: JUMPER 3&4WHEN USING S NOTE: JUMPER 3&4WHEN USING S DHW CONTROLLER 12:00 4-WIRE 12:00 4-WIRE RWC RWC END SWITCH VAC (COM) END SWITCH JUMPER 3&4 SWITCH 24 VAC (HOT) JUMPER 3&4 COM. COM. T5 T T2 T T3 T T4 T PRIORITY T5 T VAC Fuse 24VAC Fuse T2 T T3 T T4 T PRIORITY 3.2A/250V Slo-Blo Fuse F1 3.2A/250V Slo-Blo Fuse IN OUT A/250V Slo-Blo Fuse IN OUT 1 2 F2 10A/250V Slo-Blo Fuse 120VAC Fuse 120VAC Fuse T2 T3 T4 T5 PL T2 T3 T4 T5 PL C1 N L1 N X X 3 4 C1 N L1 N X X 3 4 ES/CIRC Z1 Z2 Z3 Z4 Z5 SYSTEM STATUS S M OFF P P+ ES/CIRC Z1 Z2 Z3 Z4 Z5 S M OFF P P+ SYSTEM STATUS To zone in additional slave units. CIRC. #2 CIRC. #1 T T BOILER CONTROL Master/Slave switch (COM) (HOT) 120 VAC Figure-3 Two VL500 series with Domestic Hot Water Priority, Nine Heating Zones, Boiler and Circulator Control. 4 Copyright 2008 TAC All Rights Reserved. F
5 INSTALLATION Inspection Precautions Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products. Requirements Tools (not provided) Digital multimeter Screw driver Wire stripper Training: Installer must be a qualified, experienced technician General W A R N I N G Electrical shock hazard! Disconnect power before installation to prevent electrical shock or equipment damage. Make all connections in accordance with the electrical wiring diagram and in accordance with national and local electrical codes. C A U T I O N Avoid locations where excessive moisture, corrosive fumes, explosive vapors, or vibration are present. Avoid electrical noise interference. Do not install near large conductors, electrical machinery, or welding equipment. Mounting Status Indicators Mount the VL500 to a solid vertical surface. Slotted keyholes and standard holes are provided for mounting purposes. Do not mount on a surface that exceeds 104 F (40 C). Avoid high humidity and overhead dripping liquids. - T5-T5 Red LEDs Lit Indicates zone 1 through zone 5 heat demand is present. Z1-Z1 Z5-Z5 Green LEDs Lit Indicates zone 1 through zone 5 valves are powered. ES/CIRC Green LED Lit Indicates end switch has closed and circulator has been powered. PL Yellow LED Lit Priority plus lock out has occurred. Domestic Hot Water zone (DHW) has called for more than 1 hour. Move the priority selection switch momentarily to the off position and reposition the DHW switch to the Priority Plus position to reset the DHW circuit. F Copyright 2008 TAC All Rights Reserved. 5
6 Wiring Requirements Terminal Descriptions (Figures 1, 2 and 3) Line Voltage Terminals: L1, 120 Vac hot. N, 120 Vac neutral input. C1, 120 Vac circulator power. N, 120 Vac Circulator neutral. Dry Contact Terminals: X, Dry contact heat demand. X, Dry contact heat demand. ZoneLink Expansion Domestic Hot Water (DHW) Priority Thermostat Anticipator Setting Low Voltage Terminals: COM, 24 Vac transformer common (for electronic thermostats). R, 24 Vac hot., (left), Zone 1 thermostat, (24V hot or R)., (right), Zone 1 thermostat, (W). 1, Zone valve 24 Vac (common). 2, Zone valve switched 24 Vac (hot). 3, Zone valve end switch (heat demand). 4, Zone valve end switch (24 Vac hot). The VL500 series is shipped from the factory with the master/slave switch in the M (master) position. To link one or more additional VL500 series: 1. Connect the OUT terminals of the master unit to the IN terminals of the slave unit. 2. Place the M/S switch of the master VL500 to the M position. 3. Place the M/S switch of the slave VL500 to the S position. 4. Additional VL500 series can be linked in a similar manner (refer to Figure-3). Move the OFF/PR/P+ switch to one of the following positions. Off no DHW priority. PR (Priority) Unlimited DHW priority. P+ (Priority Plus) 1 hour time limit DHW priority. N O T E Zone 1 must be used for Domestic Hot Water priority or Priority Plus. Refer to thermostat manufacturer s anticipator setting instructions and to the Specifications in this document. 6 Copyright 2008 TAC All Rights Reserved. F
7 CHECKOUT 1. Verify presence of 120 Vac power across L1 and N. 2. Verify presence of 24 Vac power across left side terminal and common C terminal. 3. Verify priority selection and master/slave switch positions. 4. Jumper - terminal. 5. Verify presence of 24 Vac power across zone valve terminals 1 and Jumper end switch terminal pair 3 and Verify contact closure across normally open dry contacts X and X. 8. Verify presence of 120 Vac power across circulator output terminals C1 and N. 9. Repeat steps 4 thru 9 for each zone if necessary. THEORY OF OPERATION The VL500 is a zone valve control relay capable of handling up to five heating zones or one priority Domestic Hot Water (DHW) zone, and four heating zones. See the Specifications in this document for load limitations. The VL500 zone input terminals - thru T5-T5 each receive a pair of thermostat wires. When a call for heat occurs on the zone thermostat, the VL500 supplies 24 V to the zone valves, routing this power on terminals 1 and 2. When the normally closed valve strokes open, the normally open end switch on the valve closes. Closure of the end switch completes a circuit through terminals 3 and 4 of the VL500 zone input terminals. During a call for heat, and once contact closure has occurred across terminals 3 and 4 of the zone, the normally open dry contacts for terminals X-X will go to the closed state. The X-X terminals are wired to the heat source, such as a boiler. Also occurring with any or all zone heat demands, power is routed to a circulator on VL500 terminals C1- N, which provide 120 Vac power to the main loop circulator. MAINTENANCE FIELD REPAIR Regular maintenance of the total system is recommended to assure sustained, optimum performance. The EXP-10 relay cube is replaceable. Replace any damaged or failed units with functional replacements. F Copyright 2008 TAC All Rights Reserved. 7
8 DIMENSIONAL DATA 7/8 (21) 5/16 (8) 5/16 (8) 6-1/2 (165) 3/16 (5) 1-7/8 (48) 2-7/8 (73) 12-3/8 (314) Figure-4 VL500 Series. Copyright 2008, TAC All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. TAC 1354 Clifford Avenue P.O. Box 2940 Loves Park, IL F
Schneider Electric Erie T155 Series
Schneider Electric Erie T Series Non-Digital, On/Off Thermostat General Instructions Application The T series thermostat provides on/off control for low voltage and line voltage valves, relays and fan
More informationErie WA300. Application. Features. Two Zone Hydro-Air Relay General Instructions
Building Systems - Americas Invensys Energy Solutions 354 lifford Avenue (Zip 6) P.O. Box 940 Loves Park, IL 63-940 United States of America www.ies.invensys.com Erie A300 wo Hydro-Air elay eneral Instructions
More informationBB3000 Series. Application. Features. Injection Pump Control General Instructions
BB3000 Series Injection Pump Control General Instructions Application The TAC Erie BB3000 Injection Pump Control with outdoor reset provides accurate control of the water temperature in the secondary (radiant)
More informationTC-5231 Series, TC-5232, & TC-5241 Series
TC-5231 Series, TC-5232, & TC-5241 Series Low Temperature Thermostats General Instructions Application The TC-5231, TC-5232, and TC-5241 low temperature thermostats are used to control temperature in air
More informationCP CP
CP-8161-333 CP-8161-433 Electronic Programmable Controller Six Stage, Dual Setpoint General Instructions APPLICATION Electronic six stage programmable controller with proportional output for heating, cooling
More informationWIRING GUIDE. Form rev.1. Certified to CSA C22-2 No.24 Conforms to UL Standard 873
WIRIG GUIDE The ZSR101 is a versatile single relay control with two outputs for operating a 120 VAC with boiler enable, or two 120 VAC devices without boiler enable. Features include rear knock outs for
More informationMaterials Housing plastic: Front display lights: Transformer voltage: Electrical switch rating, ZR/ZC, DHW, XX:
A10333 Z-one Relay Multi-Zone Valve Control Copyright 2014 Caleffi ZVR10X series Function The ZVR series is a multi-zone zone valve and boiler operating control for multiple zone hydronic heating or cooling
More information6 Zone 120/60/1vac 3A 24 VAC class 2 2 x 40 VA 2 x 5 amp fuses 1/6 hp, 120 VAC
Viega Zone Control Applications The Viega Zone Control is a wiring and switching center for individual and / or multi- room control. The Zone Control simplifies wiring between Thermostats and Powerheads.
More informationPower Supply Display Module PSDM. Installation and Operation Manual
Power Supply Display Module PSDM Installation and Operation Manual Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious
More informationInstruction manual. WMCR-2, WMCR-3, WMCR-4 and WMCR-6 Circulator Zone Controllers WMCR-1E and WMCR-4E Expansion Modules
Instruction manual WMCR-2, WMCR-3, WMCR-4 and WMCR-6 Circulator Zone Controllers WMCR-1E and WMCR-4E Expansion Modules This manual must only be used by a qualified heating installer/service technician.
More informationM6063A Compact Rotary Mixing Valve Actuator
M6063A Compact Rotary Mixing Valve Actuator PRODUC DAA FEAURES: 24 Vac floating input for automatic control. Single screw attachment to V5442 valve body. Multi-poise mounting. Color-coded position indicator.
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Keep these instructions with the boiler at all times. BOYERTOWN FURNACE CO. PO Box 100 BOYERTOWN, PA 19512 1-610-369-1450 www.boyertownfurnace.com 5-25-12 2 Danger Warning Caution
More informationMODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL. SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623
MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623 PHONE 585-321-5800 FAX 585-321-5218 REVISIONS, IF ANY,
More informationOutdoor Reset IQ Option Card, p/n
Outdoor Reset IQ Option Card, p/n 102723-01 Instruction Sheet CONTENTS Application... 1 General... 2 How it Works... 3 Installation.... 5 Wiring... 7 User Interface... 10 Using IQ Option Panel Display...
More informationYP7999A1000 ControLinks Fuel Air Ratio Control Panel
YP7999A1000 ControLinks Fuel Air Ratio Control Panel FEATURES INSTALLATION INSTRUCTIONS Pre-wired and ready to install Includes the R7999A control, wiring subbase and S7999D1048 touchscreen display Commission,
More informationInstallation, Operation & Service Manual
Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and
More informationQ7800H Integrated Burner Control Subpanel
Q7800H Integrated Burner Control Subpanel INSTALLATION INSTRUCTIONS FEATURES Unique subpanel design eliminates extensive wiring in the OEM control panel. One subpanel design covers multiple applications.
More informationGreentrol Automation, Inc.
Model GA-100 Technical Manual GreenAlert 100 Series Greentrol Automation, Inc. Installation, Operation and Maintenance Technical Manual GA-100 Document Name: TM_GA-100_R1C TM_GA-100_R1C Part Number: 960--0000
More informationOutdoor Reset IQ Option Card, p/n
Outdoor Reset IQ Option Card, p/n 102723-01 Instruction Sheet CONTENTS Application... 1 General... 2 How it Works... 3 Installation.... 5 Wiring... 7 User Interface... 10 Using IQ Option Panel Display...
More informationZ-one Relay Multi-Zone Pump Control. ZSR10X series.
A10334 G2 Z-one Relay Multi-Zone Pump Control Copyright 2015 Caleffi www.caleffi.com ZSR10X series Function The ZSR series is a multi-zone and boiler operating control for multiple zone hydronic heating
More informationAR861-2II AR822-II AR861-3II. ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY 13501
ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY 13501 AR822-II AR861-2II AR861-3II (Corporate Sales) 85 Middle Road Dunkirk, NY 14048 www.argoindustries.com An ISO 9001-2000 Certified Company P/N
More informationBGH Series Hot Surface Ignition Control
Installation Instructions BGH Series Issue Date April 14, 2011 BGH Series Hot Surface Ignition Control Application The BASO Gas Products BGH Series Hot Surface Ignition (HSI) control is microprocessor
More informationMANUAL RESET ALARM RELEASE
Fire Door Release MODEL AR-D MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual
More informationMULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS
LCB-I-O Rev B MULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS Models: KB 81-286, KBXL 400-801, WB 51-211, and WH 55-399 IMG00116 WARNING This manual must only be used by a qualified heating installer
More informationTK-1001, 1101, 1201, 1301, 1601
TK-1001, 1101, 1201, 1301, 1601 Pneumatic Room Thermostats General Instructions DEVICE INFORMATION Identification Thermostats of this family may be easily identified by referring to the part number located
More informationBulletin 1608N MiniDySC Dynamic Sag Corrector
User Manual Bulletin 1608N MiniDySC Dynamic Sag Corrector Single Phase Voltage Sag Correction 2...6 Amps (250...750 VA) Important User Information Solid-state equipment has operational characteristics
More informationARM SERIES Switching Relays With Priority
Models ARM-2P ARM-3P ARM-4P ARM-6P AD-1 AD-4 ARM SERIES Switching Relays With Priority INSTALLATION, OPERATION & MAINTENANCE MANUAL ARM-2P ARM-4P AD-1 ARM-3P ARM-6P AD-4 Information and specifications
More informationEnergy Manager INSTALLATION INSTRUCTIONS. Keep these instructions with the boiler at all times for future reference
INSTALLATION INSTRUCTIONS Energy Manager Keep these instructions with the boiler at all times for future reference BOYERTOWN FURNACE CO. PO Box 100 BOYERTOWN, PA 19512 1-610-369-1450 www.boyertownfurnace.com
More informationph COOLING TOWER CONTROLLER
LAKEWOOD INSTRUMENTS MODEL 350 ph COOLING TOWER CONTROLLER INSTRUCTION MANUAL SERIAL #: Lakewood Instruments 7838 North Faulkner Road, Milwaukee, WI 53224 USA Phone (800) 228-0839 Fax (414) 355-3508 http://www.lakewoodinstruments.com
More informationAUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL
AUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL AR C Rev.06 WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to
More informationARGO AR SERIES CONTROLS
ARGO AR SERIES CONROLS AR822-II, AR861-2II, AR861-3II INSALLAION, OPERAION & MAINENANCE MANUAL AR861-2II AR822-II AR861-3II Information and specifications outlined in this manual in effect at the time
More informationPARAGON Commercial Refrigeration Controls
PARAGON Commercial Refrigeration Controls ERC 2 Electronic Refrigeration Control The ERC 2 Electronic Refrigeration Control is a microprocessor-based electronic controller designed to control both the
More informationMASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc
MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page
More informationMULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS
LCB-I-O Rev D MULTI-TEMPERATURE LOOP CONTROL BOARD INSTRUCTIONS Models: KB 81-286, KBXL 400-801, WB 51-211, FTX 400-850 and WH 55-399 WARNING This manual must only be used by a qualified heating installer
More informationLeak Detection System Leak Minder Model: LDA-1 Instruction Manual
JWB Company Leak Detection System Leak Minder Model: LDA-1 www.jwbcompany.net Instruction Manual JWB Company For Support and Service: 65 August Avenue Wolcott, CT 06716 (203) 879-6959 (203) 879-7299 FAX
More informationHPS Controls Ltd. Series 100 LTV / CTV Zone Control Stations. Heating and Radiant Floor Zone Control Stations. Installation Instructions
Series 100 LTV / CTV Zone Control Stations Heating and Radiant Floor Zone Control Stations Installation Instructions Thank you for purchasing the finest in heating and radiant floor Control Stations. We
More informationSatchwell. DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL FEATURES
Satchwell DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL DC1100 Specification No. 04-03-105 The DC1100 energy controller is a self configuring optimiser/
More informationwww. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection
Ground Fault Protection GADD MKIII Ground Fault Indication System Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR
More informationCAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS
50T35-743 Integrated Furnace Control INSTALLATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY
More informationPremier 2-Zone Controller model Installer Guide
Premier 2-Zone ontroller model 140202 Installer uide ONTENTS 1 Specifications 4 onfiguration 2 Suitable Mounting Locations 5 System heckout 3 Wiring Diagrams 6 Operation Warning Read all of the instructions
More informationINSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.
MODEL 3200-Plus Temp Limit / LWCO Control with Thermal Targeting for Water Boilers 120 VAC Input / 24 VAC Burner Circuit PATENT. 7,891,572 INSTALLATION INSTRUCTIONS and OPERATING MANUAL Saves Fuel Features
More informationSERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION
R SERIES 35-703 120 VAC Microprocessor-Based Intermittent Pilot Ignition Control F-35-703 July 2016 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings
More informationHPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations
Series 600 LFI / CFI Series 700 HFS Zone Control Stations Heating and Radiant Floor Zone Control Stations Installation Instructions Thank you for purchasing the finest in heating and radiant floor Control
More informationVapor-logic 3 to Vapor-logic4
Vapor-logic 3 to Vapor-logic4 Adaptor Board Installation Manual Warnings and c autions Warnings and cautions WARNING Indicates a hazardous situation that could result in death or serious injury if instructions
More informationINSTALLATION INSTRUCTIONS FOR 7330*5511 OR 7330*5512 MOUNTING KIT 7330B751 CONTROL BOX KIT (12 VDC COOL ONLY)
INSTALLATION INSTRUCTIONS FOR 7330*5511 OR 7330*5512 MOUNTING KIT 7330B751 CONTROL BOX KIT (12 VDC COOL ONLY) 7530B750 CONTROL BOX KIT (24 VAC COOL ONLY) 8330A751 ZONE CONTROL KIT (12 VDC COOL ONLY) 8530B751
More informationHALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL
HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL SE R IA L N O. M O D E L N O. Tem p. Range 1 - = > 60 o F 2 - = 40-60 o F 3 - = < 40 o F G as Type 1 - R-11 2 - R-12 3
More informationAQ475A Aquatrol Outdoor Temperature Compensator for Boilers
A Aquatrol Temperature Compensator for s Features PRODUCT DATA Adjustable settings for boiler maximum temperature, boiler minimum temperature and outdoor low (design) temperature. Selectable Warm Weather
More information! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION
Series 61 Low Water Cut-Off Typical Applications: - Primary or secondary low water cut-off for hot water and steam boilers. - Low water cut-off - High water cut-off - Alarm actuator OPERATION Maximum Boiler
More informationInterrupted Ignition Series Oil Primary Control
Interrupted Ignition Series Oil Primary Control Application Guide & Installation Instruction for ICM1511*, ICM1512*, ICM151*, ICM1514* For more information on our complete range of American-made products
More informationTK-1801, TK-1811 TK-1801, TKR-1811
TK-1801, TK-1811 TK-1801, TKR-1811 Pneumatic Zero Energy Band Room Thermostats General Instructions APPLICATION For proportional control of pneumatically-operated sequenced heating and cooling valves and/or
More informationSAFETY INFORMATION AND WARNINGS
This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and
More informationbe liable for any other loss or damage, whether direct, indirect, incidental or consequential.
Integrated HydroStat 3200-Plus for Slant Fin Boilers Part No. 48-3200-03 and 48-3200-04 120 VAC Input / 24 VAC Burner Circuit PATENT S. 8.391,708; 7,891,572; 8,844,834; Others Pending INSTALLATION INSTRUCTIONS
More informationOperating Instructions. For. Alarm Control Module. Model SSR 500
SSR 500 LEVEL CONTROL RELAY MODULE Operating Instructions For Alarm Control Module Model SSR 500 SSR Operation Instructions Rev. 1 Jan 01 Page 1/7 1. Note Please read and take note of these operating instructions
More informationINTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION
INSTALLATION AND OPERATING INSTRUCTIONS FOR THE HARDY Fuel Oil Furnace Models D-140 & D-350 HARDY MANUFACTURING COMPANY, INC. 12345 ROAD 505 PHILADELPHIA, MS 39350 PHONE: (601) 656-5866 FAX: (601) 656-4559
More informationHPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations
Series 600 LFI / CFI Series 700 HFS Zone Control Stations Heating and Radiant Floor Zone Control Stations Installation Instructions Thank you for purchasing the finest in heating and radiant floor Control
More informationINSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.
MODEL 3200-Plus Temp Limit / LWCO Control with Thermal Targeting for Water Boilers 120 VAC Input / 24 VAC Burner Circuit PATENT. 8,931,708; 8,844,834; 7,891,572; others pending INSTALLATION INSTRUCTIONS
More informationSLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071
SLATE UV Ampli-Check Flame Amplifier R8001S1071 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform.
More informationMASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc
MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model
More informationCommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET
CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or
More informationHALOGUARD TM II MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL
HALOGUARD TM II MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL SERIAL NO. MODEL NO. Temp. Range - = > 0 o F - = 0-0 o F - = < 0 o F No. of Sensors/Gas Type A - R- B - R- C - R- Outputs D - R-a - x A
More informationAQ250 Series Hydronic Control Panels
AQ50 Series Hydronic Control Panels PRODUCT DATA Need new photo of AQ50 PRODUCT DESCRIPTION The AQ50 easily converts a single-zone heating system into a room-by-room comfort control system, or upgrades
More informationECAH SERIES ECM AIR HANDLER
ECAH SERIES ECM AIR HANDLER ECAH40 OPERATING MANUAL TABLE OF CONTENTS 1 GETTING STARTED... 3 2 ELECTRICAL CONNECTIONS... 3 3 DIMENSIONAL DATA... 4 4 PLUMBING... 5 4.1 OPEN SYSTEM... 5 4.2 CLOSED SYSTEM...
More informationRA889A Switching Relay
Switching Relay FEATURES PRODUT DATA High load switching capability. Troubleshooting LED. Push-to-test button. Replaceable transformer fuse. Long-life D relay drive control technology. Relay for use with
More informationDual Mixing Application
HBX MIXING APPICATION The CPU-000 configured as a Mixing Control allows for mixing of hitemp boiler (supply) water with lower temp system water, bringing several benefits to a hydronic design and installation.
More informationINSTALLATION INSTRUCTIONS MASTER CONTROLLERS MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH
INSTALLATION INSTRUCTIONS MASTER CONTROLLERS MODELS: MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual: 2100-189I
More informationSensor Interface Module Installation/Operation Instructions
TraceTek TTSIM-1 Sensor Interface Module Installation/Operation Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and VDE Certified. For
More informationRA889A Switching Relay
Switching Relay INSTALLATION INSTRUTIONS APPLIATION The Switching Relay provides intermediate switching of line- and low-voltage devices from a line- or low-voltage controller and is typically applied
More informationINSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL
INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL Figure 1 Series 9 Intermittent Pilot Ignition Control Application The Series 9 Intermittent Pilot Ignition Control is a microprocessor
More informationSystem Control. Installation, Operation & Service Manual WARNING. Installer
System Control Installation, Operation & Service Manual WARNING Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation,
More informationHALOGUARD TM II/IR MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL
HALOGUARD TM II/IR MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL SE R IA L N O. M O D E L N O. T em p. R ange - = > 0 o F - = 0-0 o F - = < 0 o F N o. of Sensors/G as T ype A - R - B - R - C - R -
More informationSLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001
SLATE Burner Control Module R8001B2001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform
More informationITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual
ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,
More informationARGO DPM-2 OUTDOOR TEMPERATURE SETBACK CONTROL
ARGO OUTDOOR TEMPERATURE SETBACK CONTROL INSTALLATION, OPERATION & MAINTENANCE MANUAL Information and specifications outlined in this manual in effect at the time of printing of this manual. ECR International,
More informationModel 17A00 Expansion Enclosure
HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number
More informationModels CHB/CCB APPLICATION GUIDE WALL MOUNTED GAS BOILER
Models CHB/CCB APPLICATION GUIDE WALL MOUNTED GAS BOILER This manual has been prepared for use with the appropriate Installation, Operation and Maintenance Manual. For use with CCB/CHB Boilers ONLY. Manufactured
More informationSLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031
SLATE Rectification Ampli-Check Flame Amplifier R8001V1031 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single
More informationInstallation & Operation Manual
tekmarnet 2 House Control 400 Installation & Operation Manual D 400 09/10 HVAC Systems Replaces: 01/10 Introduction The House Control 400 is designed to operate as part of a complete hydronic heating system
More informationInstallation Manual. Expansion Module 0100 Version 1.0 EXP HBX Control Systems Inc.
Installation Manual 000 Version.0 EXP-000 HBX Control s Inc. Control s Inc. HBX EXP 000 Version.0 HBX EXP-000 EXPANSION MODULE INTRODUCTION The EXP-000 is designed to be integrated with the HBX CPU-000
More informationInstruction manual 640 Securiterre
Instruction manual 640 Securiterre Instruction manual 640 Securiterre April 2014 Part no. 4417571 Rev. 5 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701100 Fax : +31 15 2701111 E-mail
More informationChapter 8: Troubleshooting. 8: Troubleshooting 8 TROUBLESHOOTING... 3
8: Troubleshooting 8 TROUBLESHOOTING... 3 8.0 NO HEAT... 3 8.1 NO OR LOW FLOW CONDITION... 3 8.2 NOZZLE DOES NOT PICK UP COMPONENT... 3 8.3 NO MOTION... 3 8.4 MACHINE ALARM CONDITIONS & ALARM SCREEN...
More informationqualified heating installer/service technician
Instruction manual This manual must only be used by a qualified heating installer/service technician. Failure to comply could result in severe personal injury, death or substantial property damage. Part
More informationInstallation & Operation Manual
tekmarnet 2 House Control 400 Installation & Operation Manual D 400 09/13 HVAC Systems Replaces: 09/10 Introduction The tn2 House Control 400 is designed to operate all of the mechanical equipment in a
More informationAIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.
wiring diagrams AIR-COOLED CONDENSING UNIT 566D Sizes 120-240 Cancels: New WD 566D.120.1 11/15/96 UNITS PRODUCED AFTER JANUARY, 1996 INDEX UNIT 566D 120-240 ELECTRICAL CHARACTERISTICS (V-Ph-Hz) SCHEMATIC
More informationUSER'S INFORMATION MANUAL
USER'S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use
More informationINSTALLATION INSTRUCTIONS MASTER CONTROLLERS MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH MC97AE-1
INSTALLATION INSTRUCTIONS MASTER CONTROLLERS MODELS: MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH MC97AE-1 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual:
More informationORP/MILLIVOLT CONTROLLER
LAKEWOOD INSTRUMENTS MODEL 330 ORP/MILLIVOLT CONTROLLER INSTALLATION & OPERATION MANUAL SERIAL #: Lakewood Instruments 7838 North Faulkner Road, Milwaukee, Wisconsin 53224 USA Phone (800) 228-0839 Fax
More informationEmerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING
Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL
More informationINSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY
INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY TABLE OF CONTENTS Warnings...3 Package Contents...3 General Information...3 Supply Ducting And Registers...3 Routing 115 VAC Wiring...5
More informationAQ252 Universal Injection/Mixing Boiler Reset Control Panels
AQ252 Universal Injection/Mixing Boiler Reset Control Panels FEATURES PRODUCT DATA PRODUCT DESCRIPTION The AQ252 family of AQUATROL Universal Injection/Mixing Boiler Reset Controls provides simplified,
More informationPower Flame Incorporated
Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas
More informationHot Plate HPS / HPL. Bedienungsanleitung Instructions for use Mode d emploi Manuale d istruzioni Manual de instrucciones
Hot Plate HPS / HPL Bedienungsanleitung Instructions for use Mode d emploi Manuale d istruzioni Manual de instrucciones Table of contents Safety recommendations 10 1 Introduction 11 2 Description 11 2.1
More informationWARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION
WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device
More informationInstallation Guide
Installation Guide 502-018 TOA1 Series Sensor SUPERSEDES: October 22, 2010 EFFECTIVE: November 17, 2010 Plant ID: 001-3966 Table of Contents TOA1 Sensor................................ 2 Features..................................
More informationSET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions
SET-000 Oil/Sludge Alarm Device for Oil Separators Copyright 007 Labkotec Oy We reserve the right for changes without notice TABLE OF CONTENTS GENERAL... INSTALLATION... 4. SET-000 Oil/Sludge Control Unit...
More informationLUH HORIZONTAL FAN-FORCED UNIT HEATER
LUH HORIZONTAL FAN-FORCED UNIT HEATER VERSATILE, FAN-FORCED HEATING FOR COMMERCIAL AND INDUSTRIAL COMFORT HEAT APPLICATIONS Horizontal airflow Wall or ceiling mounting Self-contained Totally enclosed fan
More information2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT
CONTENTS Installation Instructions for Heating & Air Conditioning 1F79 n-programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...
More informationINSTALLATION INSTRUCTIONS Model FH-2071-UM Enclosure
INSTALLATION INSTRUCTIONS Model FH-2071-UM Enclosure Enclosure INTRODUCTION The Model FH-2071-UM Enclosure from., used in Marine applications is robust and weather-resistant. Its durable design is customized
More informationTK-5001, Pneumatic Room Thermostats General Instructions GENERAL INFORMATION INSTALLATION
TK-5001, 5101 TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com Pneumatic Room Thermostats General Instructions GENERAL INFORMATION The pneumatic thermostats are used for proportional
More informationSERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS
SERIES 35-65 24 VAC Microprocessor-Based Hot Surface Ignition Control F-35-65 August 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings* 120/240
More informationUniversal Fire Tube Boiler Wall Mount Models
Universal Fire Tube Boiler Wall Mount Models USER S INFORMATION MANUAL Models WBRU**80W / 100W / 120W / 140W / 175W / 199W **NG denotes Natural Gas Model, LP Denotes Propane Model Heat Exchanger Bears
More information