1 Geothermal/Water Source Heat Pumps Ton Horizontal Ton Vertical Installation Information Versatec Installation Manual Water Piping Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance IM /09

2 Model Nomenclature V L V 036 B C L T 1 SSA Model Type Operational Range L = Low Temperature (50-110) X = Extended Range (30-110)* Cabinet Configuration V = Vertical H = Horizontal Unit Capacity 85 F EWT Horizontal Vertical Vintage A = Multi-return verticals & horizontals except below B = Other verticals, horiz: 018, 030, 070 Voltage 0 = /60/1 (Commercial) 1 = /60/1 (Residential) 2 = /60/1 3 = /60/3 4 = 460/60/3 Hot Water Option 0 = None (all Horizontals) 1 = Hot Water Generation (Field installed external pump kit required) * ** *** Not available on Vertical 009 Commercial only Vertical Residential (009,070 & FX10 not available) Not available on Multi-Return Desuperheater only available on Vertical models Non-Standard Options N = Sound Kit S = Standard Alpha Char. = Option Controls 1 = Electro-mechanical 2 = Microprocessor ** 4 = FX10 5 = FX10 w/open N2 Com Card 6 = FX10 w/lanworks Com Card 7 = FX10 w/bacnet Com Card Discharge Air T = Topflow (Vertical) E = End (Horizontal) S = Side (Horizontal) Return Air F = Front (Commercial Vertical only) L = Left R = Right M = Multi-Return *** Coax Options C = Copper N = Cupronickel Cabinet 0 = Painted 1 = Unpainted 2

3 Table of Contents General Installation Information 4 General Piping and Water Quality 5 Installing Horizontal Units 6-7 Setting Vertical Units 8 Electrical Connections 9 Thermostat Connections 9 Optional Microprocessor Control & Operation Optional FX10 Microprocessor Control 13 Setting Blower Speed System Cleaning and Flushing 16 Unit Startup 17 Unit Operating Parameters Preventive Maintenance 22 Additional Product Notes 23 3

4 General Installation Information Safety Considerations Installing and servicing air conditioning and heating equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service these systems. Untrained personnel can perform the basic maintenance functions of cleaning coils and replacing air filters. Trained service personnel should perform all other operations. When working on air conditioning and heating equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have a fire extinguisher available for all brazing operations. Note: Before installing, check voltage of unit(s) to ensure proper voltage. WARNING: Before performing service or maintenance operations on the system, turn off main power switches to the unit. Turn off accessory heater power switch if applicable. Electrical shock could cause serious personal injury. Moving and Storage Move units in the normal Up orientation as indicated by the labels on the unit packaging. Units may be stacked a maximum of two high and should be unstacked before attempting to move units. When the equipment is received, all items should be carefully checked against the bill of lading to ensure that all crates and cartons have been received in good condition. Examine units for shipping damage, removing unit packaging if necessary to properly inspect unit. Units in question should also be internally inspected. If any damage is observed, the carrier should make the proper notation on delivery receipt acknowledging the damage. Unit Location Locate the unit in an indoor area that allows for easy removal of the air filter, service access panels and has enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connections. If the unit is located in a confined space such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Care should be taken when units are located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components. CAUTION: Duct connections should be made with 1/2-inch sheet metal screws to prevent damage to piping and other internal components. If the unit is connected to existing ductwork, the capacity and condition of the duct should be inspected to ensure that the new system will be capable of delivering adequate airflow. If any defects or problems are identified during the inspection, repairs should be made to the ductwork prior to the unit s installation. The duct system should be sized to handle the design airflow quietly. To maximize sound attenuation of the unit blower, the supply and return air plenums should be lined with an insulated duct liner or be constructed of ductboard for the first 10 feet. If air noise or excessive airflow is a problem, the blower speed can be changed. See the Fan Performance Data tables for further details and blower motor speed selections. CAUTION: Be sure to remove the shipping material from the blower throat before connecting ductwork. 4

5 General Piping and Water Quality Water Piping Connections Units should not be connected to the supply and return piping until the water system has been cleaned and flushed completely (see page 16). Supply and return water connections are standard female pipe thread. Never use flexible hoses with an inside pipe diameter that is smaller than the water connections on the unit and limit the hose length to 10 feet or less per connection. -pressure flexible hoses provide sound attenuation for both normal unit operating noise and hydraulic pumping noise. Hard piping can also be brought directly to the unit although it is not recommended since no vibration or noise attenuation can be accomplished. Supply and return water connections must have swivel union fittings to facilitate unit removal. A manual shutoff valve should be installed on the water supply line to allow removal of the unit without disturbing the operation of the water system. A manual or motor driven shutoff valve should be installed on the return water piping. The manual return valve can be used for system balancing and should be adjusted for proper water flow, or a flow control device may be used to regulate water flow through the unit. Slow acting motorized valves are recommended to reduce the effects of water hammer. Pressure/ temperature ports (P/T Plugs) should be installed for serviceability. Sealant compound or Teflon tape should be applied to threaded fittings to assure a proper seal. Use backup wrench on unit fittings to prevent damage to water lines. Check carefully for water leaks. Water Quality In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning. Material Note: Grains = PPM divided by 17 mg/l is equivalent to PPM Copper 90/10 Cupro-Nickel 316 Stainless Steel ph Acidity/Alkalinity Scaling Calcium and Magnesium Carbonate (Total Hardness) less than 350 ppm (Total Hardness) less than 350 ppm (Total Hardness) less than 350 ppm Hydrogen Sulfide (rotten egg smell appears at 0.5 PPM) ppm Less than 1 ppm Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm Chlorine Chlorides Less than 20 ppm Less than125 ppm Less than 300 ppm Carbon Dioxide Less than 50 ppm ppm ppm Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm Corrosion Ammonia Chloride Ammonia Nitrate Ammonia Hydroxide Ammonia Sulfate Total Dissolved Solids (TDS) Less than 1000 ppm ppm ppm LSI Index to to to -.05 Iron Fouling Bacterial Iron Potential (Biological Growth) Iron Oxide Erosion Suspended Solids Threshold Velocity (Fresh Water) <.2ppm <.2 ppm Less than 1 ppm. Above this level Less than 1 ppm. Above this level deposition will occur. deposition will occur. Less than 10 ppm and filtered for max of Less than 10 ppm and filtered for max of 600 micron size 600 micron size < 6 ft/sec < 6 ft/sec <.2 ppm Less than 1 ppm. Above this level deposition will occur. Less than 10 ppm and filtered for max of 600 micron size <6 ft/sec 5

6 Installing Horizontal Units Horizontal units are available with side or end discharge. Horizontal units are normally suspended from a ceiling by four 3/8-inch diameter threaded rods. The rods are usually attached to the unit corner posts by hanger bracket kits furnished with each unit. Securely tighten the hanging brackets to the unit. The bracket design allows it to be positioned at the end or to the side of the unit as shown in Figure 1. Measure bracket hole location for threaded rod and transfer dimensions to supporting structure for proper threaded rod placement. In some installations hanger brackets should be positioned at the end of unit to allow air filter removal. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut, (refer to Figure 2). The unit should be pitched approximately 1/4-inch towards the drain in both directions to facilitate condensate removal (refer to Figure 4). CAUTION: Do not use rods smaller than 3/8-inch diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling. Figure 1: Horizontal Unit Suspension Flexible Duct Collar Insulate supply plenum and use at least one 90 elbow to reduce noise 3/8 Threaded Rods To Line Power Hanging Brackets (Included) Hose Kits To Thermostat Disconnect Line Voltage Ball Valves Boiler/Cooling Tower Loop Some applications require an attic floor installation of horizontal units. In this case the unit is set in a full size secondary drain pan on top of vibration absorbing material. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material. 6

7 Installing Horizontal Units Horizontal Unit Hanger Location Figure 2: Hanger Location and Assembly 3/8î Threaded Rod (not supplied) Vibration Isolator Washer A C Bolt and Lockwasher Hex Nuts (not supplied) B D SIZE A B C D 009, , , Condensate Drain Connect the drain through a trap to the condensate drain system in conformance with local plumbing codes. The condensate line must be trapped a minimum of 1 1/2-inches as shown in Figure 3. The condensate line should also be pitched away from the unit a minimum of 1/8-inch per foot. The top of the trap must be below the unit drain connection. Horizontal units should be pitched approximately 1/4-inch towards the drain in both directions to facilitate condensate removal (see Figure 4 below). Figure 3: Condensate Drain Connection 3/4" Male Adapter Vent Figure 4: Unit Pitch for Drain 1/4 Pitch 1-1/2" 1-1/2" 3/4" PVC or Copper 1/8" Per Foot Drain 7

8 Setting Vertical Units The entire base of the unit should be supported by a level, vibration-absorbing pad that is slightly larger than the unit cabinet. It is not necessary to anchor the unit to the floor (see Figure 5). Duct System A supply air duct flange is provided for field installation to facilitate the secure duct connection at the job site. An optional filter rack/return air duct collar is available. A flexible connector is recommended for discharge and return air duct connections on metal duct systems to prevent vibration transmission. It is recommended that all ductwork be insulated with a minimum of 1/2-inch coated insulation. Installation of the units with uninsulated ductwork in an unconditioned space is not recommended, as the system s performance will be adversely affected. Figure 5 - Versatec Series with Vibration Absorbing Pad (left-hand return shown) Flexible Duct Connection Condensate Drain On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a 3/4-inch PVC female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PVC condensater piping. On vertical upflow units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary. The field installed PVC condensate piping and unit connection must be properly glued to prevent water leakage. Filter Rack Vibration Absorbing Pad Water Supply and Return Front Line Voltage Power Low Votage Power Field Conversion Residential Versatec vertical units are capable of being field converted from left return to front or right return by relocating the control box to the side (under the air coil) or to the back (respectively). To convert, remove four screws holding the control box in place. Relocate control box to desired location in compressor section. Replace screws. Ensure that wiring does not come in contact with water or refrigerant lines. Water connections on residential models are made inside the compressor compartment. Knockouts are provided in the units base to allow several field supplied piping connections. Figure 6 - Residential Versatec Series Base Pan Showing Water Piping Knockout Locations (left-hand return shown). Air Coil Side Front 8

9 Electrical Connections Be sure that the available power is the same voltage and phase as that shown on the unit serial plate(s). Line and Low voltage wiring must be done in accordance with local codes and/or the National Electric Code. Connecting the incoming line voltage wires to the L side of the compressor contactor makes the line voltage connection. Consult the unit data plate to determine the proper fuse size. Thermostat Connections Figure 7 - Electromechanical Thermostat Wiring Connections Field Connections 24 VAC COMMON REVERSING VALVE FAULT SIGNAL RUN SIGNAL COMPRESSOR FAN TB R C O L S Y G Unit Connections Yellow Red Green Orange Green Grd. Orange Brown Pink Yellow Violet Figure 8 - Microprocessor Thermostat Wiring Connections Requires common connection or 24 VAC for activation Used with TA32U02 thermostat only Field Connections 24 VAC COMMON COMPRESSOR REVERSING VALVE FAN LOCKOUT SIGNAL EMERGENCY SHUTDOWN NIGHT SETBACK LOAD SHED TB R C Y O G LO ES NS LS MICROPROCESSOR BOARD Figure 9 - Low Voltage Wiring for Auxiliary Heating EXTERNAL AUX HEATER R C GT G1 GU G W1 W2 R R C C G G W Y Y O O L L THERMOSTAT GEO UNIT (If the unit is equpiped with the Johnson Controls FX10 Controller, refer to page 13 and the Application Guide AGFX10 for installation instructions.) 9

10 Optional Microprocessor Control Note: The following applies to the standard microprocessor and NOT to the FX10 Controller. For FX10 instructions, refer to the Application Guide AGFX10. Startup The unit will not operate until all the inputs and safety controls are checked for normal operating conditions. Fault Retry All faults are tested twice before finally locking the unit out to prevent nuisance service calls. Component Sequencing Delays Components are sequenced and delayed for optimum unit performance. Short Cycle Protection and Random Start The control allows a minimum on or off time of 5 minutes for short cycle protection. A random time delay of 0 to 30 seconds is generated after each power up to prevent simultaneous start up of all units within a building after the release from an unoccupied cycle or power loss. Night Setback A grounded signal to common or connecting 24 VAC to the NS Terminal will initiate the night setback mode on the TA32U02 thermostat. Load Shed A grounded signal to common or connecting 24 VAC to the LS Terminal places the controller into the load shed mode. The compressor will become disabled and the fan will start upon a thermostat call for heating or cooling. Emergency Shutdown A grounded signal to common or connecting 24 VAC to the ES Terminal places the controller into the emergency shut down mode. The compressor and fan operation are suspended while in the emergency shutdown mode. Condensate Overflow Protection The board incorporates an impedance liquid sensor at the top of the condensate drain pan. Upon a continuous 30 second sensing of the condensate, the operation of the unit is suspended. Safety Controls The microprocessor board recieves separate signals from a high pressure switch for safety, a low pressure switch for safety, a low pressure switch to detect loss of refrigerant charge and a low suction temperature thermistor for watercoil low temperature limit. Upon a continuous 30-second measuremnent of the fault (immediate for high pressure), compressor operation is stopped. Water Coil Low Temperature Limit Note: For applications using a closed loop antifreeze solution, set the freeze protecion switch SW1 #2 on the printed circuit boards to LOOP (off). On applications using an open loop/ground water system, set to WELL (on). 10

11 Optional Microprocessor Control Figure 10 - Versatec Logic Board Physical Layout CC CCG C C R R P3 Fan Relay FAN Versatec Microprocessor Logic Control 17P529A01 FAN COM CC RELAY SW R C Y O G LO ES NS LS P2 CAUTION: The printed circuit board incorporates static sensitive CMOS devices. Touching the board or its components may result in damage as a result of static discharge. To prevent damage during service, it is recommened that the technician use a static discharge wrist strap, which is grounded to the heat pump chassis. When handling the circuit board, hold by the edges and avoid contact with electrical componenets. Circuit boards should always be stored in the manufacturer s static protected bag prior to installations. Operational Logic MODE INPUTS FAN COMP RV Htg Y ON ON OFF Clg Y,O ON ON ON Fan G ON OFF OFF Logic Board Operation NORMAL CONTROL TIMING Blower off delay 30 seconds Compressor on delay 10 seconds Short cycle delay 5 seconds Minimum compressor on time 60 seconds (except for fault condition) pressure fault recognition delay Less than 1 second Low pressure fault recognition delay 30 seconds Water coil low temperature limit fault recognition delay 30 seconds Condensate overflow fault recognition delay 30 seconds Low pressure fault bypass delay 2 minutes Water coil low temperature limit fault bypass delay 2 minutes Random start delay 0-30 seconds TEST CONTROL TIMING Blower off delay 5 seconds Compressor on delay 2 seconds Short cycle delay 15 seconds Minimum compressor on time 5 seconds (except for fault condition) pressure fault recognition delay Less than 1 second Low pressure fault recognition delay 30 seconds Water coil low temperature limit fault recognition delay 30 seconds Condensate overflow fault recognition delay 30 seconds Low pressure fault bypass delay 0 seconds Water coil low temperature limit fault bypass delay 0 seconds Random start delay 0 seconds 11

12 Optional Microprocessor Control Logic Board DIP Switch Setting SWITCH OFF ON SW1-1 SW1-2 SW1-3 SW1-4 (Versatec) SW1-4 (Split) SW1-5 SW2 Test - Selected timings sped up to facilitate troubleshooting Loop - Closed loop freeze protection Commercial - Enables NS features when TA32U02 thermostat is used IO Display* - Enables Input/Output display on external LED board Configures the board for Northern operation and disables the 2nd stage cooling Configures the board for Premier E Split operation and changes operation of SW1-4 to Split Mode OFF* - Normal or Input display mode activated Notes: * Refer to LED Display Mode for position of SW1-4 and SW2 Normal - Standard timings Well - Open loop Water coil low temperature limit setting (30F) Normal - Standard thermostat operation Normal* - Unit status display Configures the board for Split operation and enables the 2nd stage compressor Configures the board for Versatec operation and changes operation of SW1-4 to Versatec ON* - Current fault or Output display mode activated LED Normal Display Modes Drain LED Water Flow Pressure Low Pressure Airflow Status DHW Limit SW1 - #4 ON, SW2* OFF Drain Pan Overflow Lockout WCL Thermistor (loop<15 F, well<30 ) Lockout Pressure>380 PSI Lockout Low Pressure<15 PSI Lockout Not Used Microprocessor Malfunction** Not Used Notes: ** Flashing status light indicates microprocessor is functioning properly. Solid ON indicates microprocessor malfunction. LED Diagnostic Modes LED CURRENT FAULT STATUS INPUTS OUTPUTS SW1 - #4 ON, SW2* ON SW1 - #4 OFF, SW2* OFF SW1 - #4 OFF, SW2* ON Drain Drain Pan Overflow Lockout Y Compressor Water Flow WCL Thermistor (loop<15 F, well<30 ) Lockout G FAN Pressure Pressure>380 PSI Lockout O O Low Pressure Low Pressure<15 PSI Lockout ES ES Airflow Not Used NS NS Status Not Used LS LS DHW Limit Not Used Not Used Not Used Notes: * SW2 status (Down position = OFF ; Up position = ON ) Status board 17P503A01 needs to be purchased to show faults 12

13 FX10 Microprocessor Control The Johnson Controls FX10 board is specifically designed for commercial hat pumps and provides control of the entire unit as well as input ports for Open N2, LonTalk, BacNet communication protocols as well as an input port for a user interface. The user interface is an accessory item that can be used to aid in diagnostics and unit setup. A 16 pin low voltage terminal board provides terminals for common field connections. FX10 Operation Startup The unit will not operate until all the inputs and safety controls are checked for normal operating conditions. Fault Retry All faults are tested twice before finally locking the unit out to prevent nuisance service calls. Component Sequencing Delays Components are sequenced and delayed for optimum unit performance. See table below. Lead compressor ON delay Lag compressor ON delay Short cycle delay Minimum compressor ON time pressure fault recognition Low pressure fault recognition delay CONTROL TIMING Water coil low temperature limit fault recognition delay Condensate overflow fault recognition delay Water coil low temperature limit fault bypass delay Freeze protection fault bypass delay Random start delay 30 seconds 60 seconds 4 minutes 2 minutes (except for fault condition) Less than 1 second 30 seconds 30 seconds 30 seconds 2 minutes 2 minutes seconds Short Cycle Protection The control allow a minimum compressor off time of 4 minutes and a minimum compressor run time of 2 minutes for short cycle protection. Random Start A random start delay of 1 to 120 seconds is generated after each power up to prevent simultaneous startup of all units within a building after the release from an unoccupied cycle or power loss. Emergency Shutdown A normally open dry contact must be placed between DI2 and PB2-L2. Closing the contact will set the unit into emergency shutdown mode. All unit operation is suspended while in emergency shutdown mode. Condensate Overflow Protection The board incorporates an impedance liquid sensor at the top of the condensate drain pan. Upon a continuous 30- second sensing of the condensate, the operation of the unit is suspended. Safety Controls The FX10 board receives separate signals from a high pressure switch for safety, a low pressure switch to detect loss of refrigerant charge and a low suction temperature thermistor for freeze protection. Upon a continuous 30-second measurement of the fault (immediate for high pressure), compressor operation is stopped. Water Coil Low Temperature Limit Note: For applications using a closed loop antifreeze solution, remove the wire between DI5 and PB2-L1 (see unit schematic). On applications using an open loop/ground water system, make sure the wire is connected. (For additional information on the FX10 Control, refer to Application Guide AFGX10 or Submittal Data SD1981.) 13

14 Setting Blower Speed Fan Performance Data (Vertical Units) SIZE FAN SPEED MOTOR HP AIR FLOW (CFM) AT EXTERNAL STATIC PRESSURE Med /10 Med Low Low* Med * /10 Med Low Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 3/ Low Notes: Factory settings are indicated in bold print. * Denotes 265V setting. 14

15 Setting Blower Speed Fan Performance Data (Horizontal Units) SIZE FAN SPEED MOTOR HP AIR FLOW (CFM) AT EXTERNAL STATIC PRESSURE Med Med Low 1/ Low Low* Med Med Low 1/ Med Low* Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 1/ Low Medium 3/ Low Medium Notes: * Denotes 265V setting. Factory settings are indicated in bold print. Low

16 System Cleaning and Flushing Cleaning and Flushing Prior to start up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris. If the system is equipped with water shutoff valves, the supply and return runouts must be connected together at each unit location (This will prevent the introduction of dirt into the unit, see Figure 11). The system should be filled at the water make-up connection with all air vents open. After filling, vents should be closed. The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system. As water circulates through the system, the contractor should check and repair any leaks found in the piping system. Drain(s) at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure water fill valves are set at the same rate. Figure 11: Flushing with Water Shutoff Valve Equipped Systems Return Runout Supply Runout Rubber Hose Runouts Initially Connected Together Check the pressure gauge at the pump suction and manually adjust the make-up water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, until drain water is clean and clear. The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short-circuited supply and return runouts should now be connected to the unit supply and return connections. Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (ph 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Environol brand antifreeze is recommended.. Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure. In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up and for air and water balancing. Ground Source Loop System Checkout Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is needed. A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible; then pressurize the loop to a static pressure of PSI (summer) or PSI (winter). This is normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe expansion and loop temperature change. Running the unit for at least 30 minutes after the system has been completely purged of air will allow for the break-in period. It may be necessary to adjust static loop pressure (by adding water) after the unit has run for the first time. Loop static pressure will also fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially. Insure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger. Usually GPM of flow per ton of cooling capacity is recommended in earth loop applications. Mains 16

17 Unit Startup Connecting the incoming line voltage wires to the L side of the compressor contactor makes the line voltage connection. Consult the unit data plate to determine the proper fuse size. 208 Volt Operation All volt units are factory wired for 230-volt operation. For 208-volt operation, the red and blue transformer wires must be switched. Before powering the unit, check the following. NOTE: Use check, test & start form available from your equipment representative. Verify the following: voltage is correct and matches nameplate Fuses, breakers and wire size are correct Low voltage wiring is complete Piping is complete and the water system has been cleaned and flushed Air is purged from closed loop system Isolation valves are open and water control valves or loop pumps are wired Condensate line is open, trapped and correctly pitched Transformer has been switched to lower voltage tap if needed Blower rotates freely and shipping support has been removed Blower speed tap is wired to desired fan speed (See Blower Performance Data tables, page 14-15) Air filter is clean and in position Service/access panels are in place Return air temperature is between F in heating and in cooling Air coil is clean with a clean filter If unit is equipped with the FX10 Controller, the FX10 Application Guide (AGFX10) has been referenced. Startup Steps 1. Initiate a control signal to energize the blower motor. Check blower operation. 2. Initiate a control signal to place the unit in the cooling mode. Cooling set point must be set below room temperature. 3. Cooling will energize after a time delay. 4. Be sure that the compressor and water control valve or loop pumps are activated. 5. Verify that the water flow rate is correct by measuring the water pressure drop through the heat exchanger using the P/T plugs and comparing to water pressure drop found in Startup Performance Tables on pages Check the temperature of both the supply and discharge water. Refer to Startup Performance Tables on pages Check for an air temperature drop of F across the air coil, depending on the fan speed and entering water temperature. Refer to Startup Performance Tables on pages Adjust the cooling set point above the room temperature and verify that the compressor and water valve or loop pumps deactivate. 9. Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature. 10. First stage heating will energize after a time delay. 11. Check the temperature of both the supply and discharge water. Refer to Startup Performance Tables on pages Check for an air temperature rise of 20 F-35 F across the air coil, depending on the fan speed and entering water temperature. Refer to Startup Performance Tables on pages If auxiliary electric heaters are installed, adjust the heating set point until the electric heat banks are sequenced on. All stages of the auxiliary heater should be sequenced on when the thermostat is in the Emergency Heat mode. Check amperage of each element. 14. Adjust the heating set point below room temperature and verify that the compressor and water valve or loop pumps deactivate. 15. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required. 16. Set system to desired normal operating mode and set temperature to maintain desired comfort level. 17. Instruct the owner/operator of the proper operation of the thermostat and system maintenance. 17

18 Startup Perfomance for Vertical Units SIZE WATER FLOW GPM EWT, F WATER PRESSURE DROP, PSIG WATER TEMP. CHANGE, F AIR TEMP. CHANGE, F *HEATING **COOLING HEATING COOLING Notes: * Water temperature changes for heating are based on 70 F entering air. ** Water temperature changes for cooling are based on 80/67 F entering air. Air temperature changes for heating are based on 70 F entering air and high speed fan. Air temperature changes for cooling are based on 80/67 F entering air and high speed fan. 18

19 Startup Perfomance for Vertical Units SIZE WATER FLOW GPM EWT, F WATER PRESSURE DROP, PSIG WATER TEMP. CHANGE, F AIR TEMP. CHANGE, F *HEATING **COOLING HEATING COOLING Notes: * Water temperature changes for heating are based on 70 F entering air. ** Water temperature changes for cooling are based on 80/67 F entering air. Air temperature changes for heating are based on 70 F entering air and high speed fan. Air temperature changes for cooling are based on 80/67 F entering air and high speed fan. 19

20 Startup Perfomance for Horizontal Units SIZE WATER FLOW GPM EWT, F WATER PRESSURE DROP, PSIG WATER TEMP. CHANGE, F AIR TEMP. CHANGE, F *HEATING **COOLING HEATING COOLING Notes: * Water temperature changes for heating are based on 70 F entering air. ** Water temperature changes for cooling are based on 80/67 F entering air. Air temperature changes for heating are based on 70 F entering air and high speed fan. Air temperature changes for cooling are based on 80/67 F entering air and high speed fan. 20

21 Startup Perfomance for Horizontal Units SIZE WATER FLOW GPM EWT, F WATER PRESSURE DROP, PSIG WATER TEMP. CHANGE, F AIR TEMP. CHANGE, F *HEATING **COOLING HEATING COOLING Notes: * Water temperature changes for heating are based on 70 F entering air. ** Water temperature changes for cooling are based on 80/67 F entering air. Air temperature changes for heating are based on 70 F entering air and high speed fan. Air temperature changes for cooling are based on 80/67 F entering air and high speed fan. 21

22 Preventive Maintenance Water Coil/Desuperheater Coil Maintenance 1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Water lines should always be airtight. 2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off-cycles. Closed loop systems must have positive static pressure; otherwise air vents may draw air into the system. Note: If the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is best to establish a periodic maintenance schedule so the coil can be checked regularly. Should coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water flowing through the unit, the less chance for scaling to occur. Other Maintenance Air Filters - Filters must be clean to obtain maximum performance. They should be inspected every two to three months under normal operating conditions and be replaced when necessary. Units should never be operated without a filter. Condensate Drain - In areas where airborne bacteria produce a residual buildup in the drain pan, it may be necessary to chemically treat the pan to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the possibility of overflow. Air Coil - The air coil must be clean to obtain maximum performance. Check once a year under normal operating conditions and brush, vacuum or chemically clean the air coil if necessary. Care must be taken not to damage or disturb the aluminum fins while cleaning. CAUTION: Fin edges are sharp. Refrigerant System To maintain the factory sealed refrigerant circuit integrity, do not install service gauges unless unit operation appears abnormal. Reference the Startup Performance Tables on pages Verify that air and water flow rates are at proper levels prior to servicing the refrigerant circuit. In-Warranty Material Return Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance. 22

23 Additional Product Notes Desuperheater If unit is equipped with desuperheater for hot water assist, DPK5 (desuperheater pump kit) is required. Kit includes pump, fittings, relay, and complete instructions. Ordered separately. Water Coil Low Temperature Limit Kits - Not needed on units with microprocessor FPK - Open Loop FPKCL - Closed Loop Auxiliary Heaters HEATER MODEL MIN USED WITH VERSATEC MODEL ELECTRICAL KW CFM ECS4 240/ ESC42 277/ ECM4 240/ ECM8 240/ ECM12 240/ ECM16 240/ ECM42 277/ ECM82 277/ ECM / ECM / ECM83 240/ ECM / ECM / ECM84 480/ ECM / ECM / ECL10 240/ ECL15 240/ ECL20 240/ ECL / ECL / ECL / ECL / ECL / ECL / Notes: fan tap setting must be above the minimum CFM for the heater selected. 4KW heaters are single stage. All others are two stage. For installation instructions, refer to instructions packaged with the heater. 23

24 Manufactured by WaterFurnace International, Inc Conservation Way Fort Wayne, IN Product: Type: Size: Document: Versatec Geothermal/Water Source Heat Pumps Ton Installation Manual IM /09 WaterFurnace International, Inc. has a policy of continuous product research and development and reserves the right to change design and specifications without notice WaterFurnace International, Inc.

G Series. G Series 7-25 Tons Installation Manual. Water Source/Geothermal Heat Pump Commercial 7-25 Tons. Installation Information

G Series. G Series 7-25 Tons Installation Manual. Water Source/Geothermal Heat Pump Commercial 7-25 Tons. Installation Information G Series Water Source/Geothermal Heat Pump Commercial 7-25 Tons Installation Information Water Piping Connections Electrical Connections G Series 7-25 Tons Installation Manual Startup Procedures Preventive

More information

Versatec Ultra Series Installation Manual

Versatec Ultra Series Installation Manual Commercial Geothermal/Water Source Heat Pump R-410A Refrigerant 0.75-6 Tons Installation Information Water Piping Connections Hot Water Connections Electrical Startup Procedures Versatec Ultra Series Installation

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

Installation, Operation & Maintenance Manual. Geothermal/ Water Source Heat Pump. R-410A Refrigerant Ton. Design Features.

Installation, Operation & Maintenance Manual. Geothermal/ Water Source Heat Pump. R-410A Refrigerant Ton. Design Features. Geothermal/ Water Source Heat Pump R-410A Refrigerant 0.75-6 Ton Design Features Factory Options Accessories Dimensional Data Physical Data Performance Data Engineering Guide Specifications Installation,

More information

Versatec Installation Manual

Versatec Installation Manual Water Source/Geothermal Heat Pumps 7 thru 10 Ton Horizontal 7 thru 23 Ton Vertical Versatec Installation Manual Installation Information Water Piping Connections Electrical Connections Microprocessor Control

More information

RG Series Commercial Geothermal/Water Source Heat Pump R-410A Refrigerant Tons

RG Series Commercial Geothermal/Water Source Heat Pump R-410A Refrigerant Tons RG Series Commercial Geothermal/Water Source Heat Pump R-410A Refrigerant 0.75-6 Tons Design Features RG Series Installation Manual Factory Options Accessories Dimensional Data Physical Data Performance

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

ARBOR SERIES CONDO. Arbor Condo Series Installation Manual. Water Source/Geothermal Heat Pump R-410A Refrigerant Commercial

ARBOR SERIES CONDO. Arbor Condo Series Installation Manual. Water Source/Geothermal Heat Pump R-410A Refrigerant Commercial ARBOR SERIES CONDO Water Source/Geothermal Heat Pump R-410A Refrigerant Commercial 1.5-3.5 Ton Installation Information Water Piping Connections Hot Water Connections Arbor Condo Series Installation Manual

More information

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA. OWNER S MANUAL Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750 Proudly Made in the USA support@aquacomfort.com 888-475-7443 Manufacturing High Quality, High Efficiency Heat

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS HB Series Geothermal Heat Pump Sizes 018, 024, 030, 036, 042, 048, 060 TE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE. SAFETY

More information

EC SERIES MODEL NOMENCLATURE

EC SERIES MODEL NOMENCLATURE EC SERIES Table of Contents Model Nomenclature...1 Introduction...2 Initial Inspection...2 General Description...2 Moving and Storage...2 Safety Considerations...2 Location...2 Installation...2 Condensate

More information

GS SERIES. Table of Contents CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW

GS SERIES. Table of Contents CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW Table of Contents Model Nomenclature...1 Initial Inspection...2 General Description...2 Moving and Storage...2 Safety Considerations...2 Location...2 Installation...2 Condensate Drain...3 Duct System...3

More information

BasicTroubleshooting Information and Guidelines

BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines Information and Guidelines May 2017 BasicTroubleshooting PRIOR TO CONTACTING CLIMATEMASTER TECHNICAL SUPPORT,

More information

SPECIFICATION CATALOG. Low Sill Console 0.75 to 1.5 Ton. Geothermal/Water Source Heat Pump

SPECIFICATION CATALOG. Low Sill Console 0.75 to 1.5 Ton. Geothermal/Water Source Heat Pump SPECIFICATION CATALOG Low Sill Console 0.75 to 1.5 Ton Geothermal/Water Source Heat Pump Table of Contents Model Nomenclature.............................................................. 4 AHRI Data......................................................................

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION MODULAR AIR HANDLER MODEL: N*AH CONTENTS GENERAL... 1 INSPECTION... 2 REFERENCE... 2 LIMITATIONS... 2 LOCATION... 2 BLOWER/COIL ASSEMBLY UPFLOW AND HORIZONTAL INSTALLATIONS...

More information

Installation and Maintenance Manual TA Series

Installation and Maintenance Manual TA Series Installation and Maintenance Manual TA Series Copyright 2012 Bosch, Inc All rights reserved Table of Contents TA Series 3 Table of Contents Model Nomenclature...3 Initial Inspection...4 General Description...4

More information

Table of Contents. Commercial Horizontal & Vertical Packaged Water-Source Heat Pumps

Table of Contents. Commercial Horizontal & Vertical Packaged Water-Source Heat Pumps Tranquility 27 (TT) Series Tranquility 20 (TS) Series Tranquility 16 (TC) Series Genesis Ultra (GS) Series Genesis Standard (GR) Series Genesis Compact (GC) Series Commercial Horizontal & Vertical Packaged

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

NKW Reversible Chiller Installation Manual

NKW Reversible Chiller Installation Manual NKW 30 to 150 kw Commercial Reversible Chiller - 50 Hz Installation Information Water Piping Connections Electrical Data Microprocessor Control Startup Procedures Preventive Maintenance NKW Reversible

More information

NXW Reversible Chiller Installation Manual

NXW Reversible Chiller Installation Manual NXW 10 to 50 Tons Commercial Reversible Chiller - 60 Hz Installation Information Water Piping Connections Electrical Data Microprocessor Control Startup Procedures Preventive Maintenance NXW Reversible

More information

AP SERIES VOLTAGE DESIGNATION: 1-208/1/60 & 230/1/60 CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW

AP SERIES VOLTAGE DESIGNATION: 1-208/1/60 & 230/1/60 CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW Table of Contents Model Nomenclature...1 Initial Inspection...2 General Description...2 Moving and Storage...2 Safety Considerations...2 Location...2 Installation...2 Condensate Drain...3 Duct System...3

More information

LCU Series. Large Commercial Series Water Source Heat Pumps. Installation, Operation & Maintenance Instructions

LCU Series. Large Commercial Series Water Source Heat Pumps. Installation, Operation & Maintenance Instructions LCU Series Large Commercial Series Water Source Heat Pumps Installation, Operation & Maintenance Instructions TABLE OF CONTENTS Page General Information 3 Inspection 3 Introduction 3 Storage 3 Unit Protection

More information

GSW. GSW Installation Manual. Geothermal Hydronic Units R-410A Refrigerant 8-15 Ton. Design Features. Factory Options. Accessories.

GSW. GSW Installation Manual. Geothermal Hydronic Units R-410A Refrigerant 8-15 Ton. Design Features. Factory Options. Accessories. GSW Geothermal Hydronic Units R-410A Refrigerant 8-15 Ton GSW Installation Manual Design Features Factory Options Accessories Dimensional Data Physical Data Performance Data Engineering Guide Specifications

More information

Installation & Maintenance Data IM Contents

Installation & Maintenance Data IM Contents Installation & Maintenance Data IM 254-4 Group: Fan Coil Part Number: 107133000 Date: June 1999 SeasonMaker HiLine Fan-coil Units Type KZZ Contents Inspection..................................... 2 Riser

More information

Versatec Specification Catalog

Versatec Specification Catalog Water-to-Water Heat Pumps 15 and Tons Design Features Versatec Specification Catalog Factory Options Accessories Dimensional Data Physical Data Performance Data Engineering Guide Specifications SP1063

More information

Heating and Air Conditioning

Heating and Air Conditioning Heating and Air Conditioning INSTALLATION MANUAL AFFINITY GEOTHERMAL HEAT PUMPS DUAL-CAPACITY HYDRONIC MODELS: YAWT100-180 (8 THRU 15 NOMINAL TONS) Due to continuous product improvement, specifications

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

ES Series. Installation and Maintenance Manual

ES Series. Installation and Maintenance Manual ES Series Installation and Maintenance Manual 8733922027 (2014/01) Table of Contents Model Nomenclature...1 Initial Inspection...2 General Description...2 Moving and Storage...2 Safety Considerations...2

More information

Versatec Ultra Series Installation Manual

Versatec Ultra Series Installation Manual ommercial eothermal/water Source Heat Pump R-40A Refrigerant 0.75-6 Tons Installation Information Water Piping onnections Hot Water onnections Electrical Startup Procedures Versatec Ultra Series Installation

More information

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA OWNER S MANUAL Vintage Classic HEAT COOL models Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support 888-475-7443 Manufacturing High Quality, High Efficiency Heat Pump

More information

Model SV - i Series Geothermal Heat Pump

Model SV - i Series Geothermal Heat Pump Made in Florida Model SV - i Series Geothermal Heat Pump SV007 Thru SV070 Installation, Operation and Maintenance Manual 8 733 914 818 (2013/8) 2 SV Heat PumpSeries CONTENTS Model Nomenclature... 3 General

More information

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995 Replacement Parts List No. 055236000 Revision B 06/2015 McQuay Ceiling Concealed Horizontal Water Source Heat Pump CCH, CCG, CCW 048, 060 Vintage A Last Manufactured: 1995 To find your Daikin Applied parts

More information

SV Air Handler. Installation, Operation and Maintenance Manual (2015/01)

SV Air Handler. Installation, Operation and Maintenance Manual (2015/01) SV Air Handler Installation, Operation and Maintenance Manual 8 733 922 119 (2015/01) 2 Condensing Section/Air Handler Pairing SV Air Handler CONTENTS Condensing Section/Air Handler Pairing... 2 Key to

More information

Installation, Start-Up, and Service Instructions

Installation, Start-Up, and Service Instructions Aquazone 50PSH, PSV007-070 Single-Stage Water Source Heat Pumps with Puron Refrigerant (R-410A) Installation, Start-Up, and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS.....................

More information

INSTALLATION MB SERIES MANUAL TABLE OF CONTENTS MB SERIES ( INSTALLATION ) UNIT DESCRIPTION. FHP MB series are available in two models: VH CABINET:

INSTALLATION MB SERIES MANUAL TABLE OF CONTENTS MB SERIES ( INSTALLATION ) UNIT DESCRIPTION. FHP MB series are available in two models: VH CABINET: MB SERIES ( INSTALLATION ) INSTALLATION MANUAL MB SERIES TABLE OF CONTENTS Unit Description...1 Installation...2 General...2 Safety Considerations...2 Moving and Storage...3 Location...3 Acoustical Considerations...3

More information

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER ASPEN MANUFACTURING 373 ATASCOCITA RD. HUMBLE, TX 77396 TEL (281) 441-6500 FAX (281) 441-6510 > INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT: "The

More information

SPECIFICATION CATALOG. Console 0.75 to 1.5 Tons. Geothermal/Water Source Heat Pump

SPECIFICATION CATALOG. Console 0.75 to 1.5 Tons. Geothermal/Water Source Heat Pump SPECIFICATION CATALOG Console 0.75 to 1.5 Tons Geothermal/Water Source Heat Pump Table of Contents Model Nomenclature.............................................................. 4 AHRI Data......................................................................

More information

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80 Installation & Maintenance Data IM 255-6 SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80 Group: Fan coil Part Number: # 106332400 Date: August 2000 Table of Contents Inspection............................................................................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS HP Series Geothermal Heat Pump Sizes 024, 036, 048, 060, 072 TE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE. SAFETY CONSIDERATIONS...

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195) STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: 535.02-N2Y (795) 535.02-N2Y (1195) HEAT PUMP MODELS F1RP / F1FP018 thru 060 and COOLING MODELS F1RC / F1FC018 thru 036 035-13620

More information

ASTON CONSOLE SERIES

ASTON CONSOLE SERIES ASTON CONSOLE SERIES C O M M E R C I A L U N I T S AFFORDABLE RENEWABLE CLEAN Table of Contents Model Nomenclature.............................................................. 4 AHRI Data.....................................................................

More information

GUIDE SPECIFICATIONS AQUARIUS ii

GUIDE SPECIFICATIONS AQUARIUS ii Catalog (AP Technical Data Sheet) GUIDE SPECIFICATIONS AQUARIUS ii AP Series Two Stage R-410A GENERAL Units shall be performance certified to ISO standard 13256-1 for Water Loop Heat Pump, Ground Water

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION MANUAL AFFORDABLE RENEWABLE CLEAN ASTON SINGLE HYDRONIC UNIT GEOTHERMAL HEAT PUMPS

INSTALLATION MANUAL AFFORDABLE RENEWABLE CLEAN ASTON SINGLE HYDRONIC UNIT GEOTHERMAL HEAT PUMPS INSTALLATION MANUAL GEOTHERMAL HEAT PUMPS AFFORDABLE RENEWABLE CLEAN ASTON SINGLE HYDRONIC UNIT ASTON HYDRONIC INSTALLATION MANUAL Table of Contents Model Nomenclature..............................................................

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions CONTENTS PAGE Pre-Installation 3 Placement & Mechanical Information 4 System Application Options 10 Antifreeze Protection 14 Electrical

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION SINGLE PIECE AIR HANDLERS Supersedes: 535.02-N2V (598) 535.02-N2V (199) HEAT PUMP MODELS F+RP / F+FP018 thru 060 and COOLING MODELS F+RC / F+FC024 thru 036 035-14363 GENERAL This

More information

INSTALLATION AND SERVICE OF WATER-SOURCE AND GEOTHERMAL HEAT PUMPS WaterFurnace International

INSTALLATION AND SERVICE OF WATER-SOURCE AND GEOTHERMAL HEAT PUMPS WaterFurnace International INTRODUCTION It is assumed that the reader has sufficient knowledge of the heat pump refrigeration cycle, and electrical knowledge, to understand heat pumps and their refrigeration and electrical circuits.

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

Greensource i Series SV Model Installation and Maintenance Manual

Greensource i Series SV Model Installation and Maintenance Manual Greensource i Series SV Model Installation and Maintenance Manual 8733946175 (2016/12) 2 CONTENTS Key to Symbols...3 Safety Warnings...3 Model Nomenclature...4 General Description...5 Moving and Storage...5

More information

SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12

SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12 Installation & Maintenance Data IM 168-5 SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12 Group: Fan coil Part Number: # 107132900 Date: June 1999 Table of Contents Inspection............................................................................

More information

Versatec Installation Manual

Versatec Installation Manual Water-to-Water Heat Pumps 3, 5, 7, 10 Ton apacity Installation Information Versatec Installation Manual Water Piping onnections Electrical onnections Startup Procedures Preventive Maintenance IM1355 11/06

More information

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER MODEL (INCLUDING HEATER MODEL #) SERIAL # INSTALLER INSTALLATION DATE These instructions should

More information

Installation Instructions

Installation Instructions CNPHP Cased N Coils Horizontal Heating --- Cooling NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor IM-BAH-0662402-18 August 2018 Installation Instructions B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor TABLE OF CONTENTS

More information

Residential Packaged Geothermal Heat Pump

Residential Packaged Geothermal Heat Pump INSTALLATION, OPERATION & MAINTENANCE MANUAL Residential Packaged Geothermal Heat Pump HP Series 1 1 /2 to 5 Tons Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS C7BA Series Split System Indoor Cased Coils IMPORTANT ATTENTION INSTALLERS: It is your responsibility to know this product better than your customer. This includes being able

More information

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER IMPORTANT MASSAGE TO INSTALLER: "The United States Environmental Protection Agency ("EPA") has issued various regulations regarding the

More information

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer Technical Development Program PRESENTED BY: COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems Ray Chow Sales Engineer TDP Updates Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS C7BA & C7BH Series Split System Indoor Cased Coils INSTALLATION INSTRUCTIONS IMPORTANT It is your responsibility to know this product better than your customer. This includes being able to install the

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. VARIABLE SPEED ELECTRIC FURNACE INSTALLATION INSTRUCTIONS VARIABLE SPEED ELECTRIC FURNACE SAFETY...1 INSTALLATION REQUIREMENTS...2 Tools and Parts...2 Location Requirements...2 Installation Configurations...3

More information

ARBOR SERIES COMMERCIAL. Arbor Series Installation ti Manual. Water Source/Geothermal Heat Pump R-410A Refrigerant Commercial 0.

ARBOR SERIES COMMERCIAL. Arbor Series Installation ti Manual. Water Source/Geothermal Heat Pump R-410A Refrigerant Commercial 0. ARBOR SERIES OMMERIAL Water Source/eothermal Heat Pump R-40A Refrigerant ommercial 0.75-6 Ton Installation Information Arbor Series Installation ti Manual Water Piping onnections Hot Water onnections Electrical

More information

Heating and Air Conditioning

Heating and Air Conditioning Heating and Air onditioning INSTALLATION MANUAL LX ULTRA OMMERIAL EOTHERMAL/ WATER SOURE HEAT PUMPS SINLE APAITY MODELS: YS009-070 (.75 THRU 6 NOMINAL TONS) Due to continuous product improvement, specifications

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

RC Series. RC Series Installation Manual. Geothermal/Water Source Heat Pump R-410A Refrigerant Tons Single Speed. Installation Information

RC Series. RC Series Installation Manual. Geothermal/Water Source Heat Pump R-410A Refrigerant Tons Single Speed. Installation Information RC Series Geothermal/Water Source Heat Pump R-410A Refrigerant 0.75-1.5 Tons Single Speed Installation Information RC Series Installation Manual Water Piping Connections Electrical Startup Procedures Troubleshooting

More information

AHG**-0B Series Hydronic Air Handling Units

AHG**-0B Series Hydronic Air Handling Units HEAT CONTROLLER, INC. Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual AHG**-0B Series Hydronic Air Handling Units HEAT CONTROLLER, INC. 1900 Wellworth Ave.,

More information

SM Field Installed Electric Heat Kit

SM Field Installed Electric Heat Kit SM Field Installed Electric Heat Kit HK050 HK100 HK150 HK200 Installation Manual 8733822029 (2018/07) US 2 SM Series Electric Heat Installation Manual Data subject to change 07.2018 8733822029 Installation

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ,t_2007 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR 505,264M (65484504) 10/07 Supersedes 09/06 COILS n _putech blications ical Litho U.S.A. RETAIN THESE

More information

EC Large Series 072, 096, 120, 150, 151, 180, 181, 210, 240, 242, 300, 360. Installation, operation and Maintenance Manual T (01/15)

EC Large Series 072, 096, 120, 150, 151, 180, 181, 210, 240, 242, 300, 360. Installation, operation and Maintenance Manual T (01/15) EC Large Series 072, 096, 120, 150, 151, 180, 181, 210, 240, 242, 300, 360. Installation, operation and Maintenance Manual T111970289 (01/15) 2 CONTENTS Model Nomenclature... 3 Initial Inspection... 4

More information

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC ISO 9001 Certified Quality Management System SAFETY................................................

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS FCP2400D FCP3000D FCP3600D FCP4200D FCP4800D FCP6000D FCP2400C FCX2400C FCP3000C FCP3600C FCX3600C FCP4200C FCP4800C FCX4800C FCP6000C FCX6000C Require AMF001NHA Accessory No

More information

Installation Instructions Part No , Part No Part No

Installation Instructions Part No , Part No Part No Torsion-Flex Motor mount for PSC motors and Rigid-Mount for ECM motors Replacement Kit Cancels: New Installation Instructions Part No. 327752-401, Part No. 327753-401 Part No. 327754-401 IIK-310A-45-11

More information

Installation Instructions

Installation Instructions Installation Instructions Cased Horizontal Furnace Coil CK3B A96318 Fig. 1 Model CK3B Furnace Coil NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper

More information

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA OWNER S MANUAL Models: AC110, AC125, AC150 made from 2003 through 2010 Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support/ (888) 475-7443 Manufacturing High Quality,

More information

Installation, Start-Up, and Service Instructions

Installation, Start-Up, and Service Instructions Installation, Start-Up, and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS.................... 1,2 GENERAL........................................ 2 INSTALLATION................................

More information

Installation Instructions

Installation Instructions 50ES--A, 50EZ--A, 50VG--A, B, 50VL--A, B, 50VR--A, 50VT--A, B 604D-- --A, 607C-- --A, B, 607E-- --A, 704D-- --A, 707C-- --A, B, 707E-- --A PA3G -- -- A, PH3G -- -- A, PA4G, PH4G PAD3, PHD3, PAD4, PHD4,

More information

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: ORIFICE METERING DEVICE - G*FD024S14 - G*FD060S24 FACTORY INSTALLED TXV - G*FD024S14T - G*FD060S24T

More information

HEAT CONTROLLER, INC. HC Series 1/2 to 5 Tons Commercial Water Source Heat Pumps

HEAT CONTROLLER, INC. HC Series 1/2 to 5 Tons Commercial Water Source Heat Pumps HEAT CONTROLLER, INC. Installation, Operation and Maintenance Manual HC Series 1/2 to 5 Tons Commercial Water Source Heat Pumps HEAT CONTROLLER, INC. 1900 Wellworth Ave., Jackson, Michigan 49203 Ph. 517-787-2100

More information

GUIDE SPECIFICATIONS AQUARIUS ii

GUIDE SPECIFICATIONS AQUARIUS ii Catalog (AP Technical Data Sheet) GUIDE SPECIFICATIONS AQUARIUS ii AP Series Two Stage R-410A GENERAL Units shall be performance certified to ISO standard 13256-1 for Water Loop Pump, Ground Water Pump

More information

NDW Installation Manual

NDW Installation Manual NDW 8 to 5 on Hydronic Unit NDW Installation Manual Installation Information Water Piping Connections Electrical Data Microprocessor Control Startup Procedures Preventive Maintenance NDWIM 08/09 able

More information

SV Condensing Section

SV Condensing Section Installation, Operation and Maintenance Manual 8 733 922 119 (2015/01) 2 Condensing Section/Air Handler Pairing CONTENTS Condensing Section/Air Handler Pairing... 2 Key to Symbols... 3 Safety Warnings...

More information

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions 4201 Lien Rd Madison, WI 53704 TS-140F Revised 09-10 Owner s Manual Therma-Stor III Heat Recovery System Installation, Operation & Service Instructions Read and Save These Instructions Table Of Contents

More information

ICE AIR Vertical WSHP Technical Manual INSTALLATION

ICE AIR   Vertical WSHP Technical Manual INSTALLATION Hartford Avenue Mount Vernon New York 10553 Tel: 914-668-40 EXT. 203 Fax: 914-668-5643 www.ice-air.com Wo r l d C l a s s C o m f o r t Vertical WSHP Technical Manual INSTALLATION Note to INSTALLATION

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Packaged Chiller Models CC 6601, 6501, 6401, 6301, 6201, 6101 For Service, please contact Pfannenberg Service Company: U.S.A. Pfannenberg Inc. 68 Ward Road.

More information

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH 33-44-50 CAH 49-54-70 CAH VARIABLE SPEED AIR HANDLERS DIMENSIONS... 3 TECHNICAL SPECS... 4 INSTALLATION DON TS... 5 INSTALLATION DO S... 6 FREEZE STAT REQUIRED

More information

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts GTIP60 ISO GT Series, Inch Pounds 60 Hz GT010070 (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts Rev: 903 Rev 1 Revisions: 31103 Changed HZ dwg to field convertible 5902 changed Unit

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR COILS 505,264M (65484504) 05/08 Supersedes 10/07 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE

More information

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T15 Model INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Installation Guide & Owner s Manual. Water Source Heat Pumps Vertical / Horizontal 1 5 Nominal Ton GEOCOOL SERIES

Installation Guide & Owner s Manual. Water Source Heat Pumps Vertical / Horizontal 1 5 Nominal Ton GEOCOOL SERIES Installation Guide & Owner s Manual Water Source Heat Pumps Vertical / Horizontal 1 5 Nominal Ton Rev. 042012001 GEOCOOL SERIES Reader should pay particular attention to the words: NOTE, CAUTION, and WARNING.

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ,1,_2008 Lennox Industries Inc, Dallas, Texas, USA INSTALLATION INSTRUCTIONS CR33 Series Coils EVAPORATOR COILS _ Technical 505,056M LL.L[ Publications 04108 Litho U.S.A. Supersedes 05/05 CR33 Series Coils...

More information

Verde GSE PCA Bridge and Ground Mount Units 30/45/60/90/120 Tons. Installation and Maintenance Manual

Verde GSE PCA Bridge and Ground Mount Units 30/45/60/90/120 Tons. Installation and Maintenance Manual Verde GSE PCA Bridge and Ground Mount Units 30/45/60/90/120 Tons Installation and Maintenance Manual Rev. 09/17/2016 Table of Contents SAFETY... 3 GENERAL DESCRIPTION... 4 MOVING AND STORAGE... 4 INITIAL

More information