GROUNDING AND BONDING

Size: px
Start display at page:

Download "GROUNDING AND BONDING"

Transcription

1 PHYSICAL INFRASTRUCTURE SYSTEMS GROUNDING AND ONDING Panduit grounding and bonding solutions meet customer needs and today s critical application requirements for grounding data centers and telecommunication spaces. Panduit StructuredGround Grounding provides a high quality, visually verifiable, and dedicated grounding path to maintain system performance and protect network equipment and personnel. Panduit grounding and bonding components are designed for use on racks and cabinets which meet EIA-30. A. Ensures highest network system performance Prevents equipment damage Maximizes uptime Meets TIA-942, TIA-607-, IEEE Std 00 (IEEE Emerald ook), UL and CSA Promotes personnel protection Designed for flexibility and easy installation StructuredGround Grounding components provide a low resistance grounding path for reliability; include factory terminated jumpers for easy installation; and are kitted for convenience. Jumper kits include Panduit Compression Electrical Connectors that meet NES Level 3 Criteria, the highest level of operability within the network facility environment. A full line of manual, controlled cycle, and battery operated hydraulic crimping tools meet application needs and provide lowest installed cost. For the complete line of Panduit Electrical and Grounding Connectors and crimping tools, visit or refer to the Electrical Solutions Catalog SA-ELC0. For service and technical support, call (outside the U.S. and Canada, see back c).

2 A. PHYSICAL INFRASTRUCTURE SYSTEMS THE PURPOSE OF GROUNDING AND ONDING The grounding and bonding system is more than just an insurance policy against a lightning strike or other surge event. It is an active, functioning system that provides protection for personnel and equipment. Proper grounding and bonding are essential for efficient network performance in the modern data center and telecommunication spaces. A primary purpose of the grounding and bonding system is to create an adequate-capacity path for electrical surges and transient voltages to return to their source (which may include the earth). Lightning, fault currents, circuit switching (motors turning on and off), activation of surge protective devices (SPDs) and electrostatic discharge are common causes of these electrical surges and transient voltages. An effective grounding and bonding system minimizes the detrimental effects of these electrical surges and transient voltages. A properly designed grounding and bonding system is intentional, visually verifiable, and adequately sized to handle expected currents safely and without undue effect on susceptible electronic equipment. Any metallic component that is part of the data center infrastructure (such as equipment, racks, ladder racks, cabinets, cable trays, etc.) must be properly connected to the grounding and bonding system. WHAT ARE THE EFFECTS OF IMPROPER GROUNDING? Lower Reliability An improperly designed grounding (and bonding) system may be a primary source of interference and emission According to the IEEE, the typical AC third-prong ground circuit is almost never sufficient to prevent damage to network equipment susceptible to ground-fault related potentials Poorly designed or improperly applied grounding, bonding, and shielding techniques often adversely affect the performance of electronic equipment from the circuit board to the network system Approximately 70% of all anomalies, dysfunctions, or problems associated with power distribution systems are directly or indirectly related to bonding and grounding issues Safety Risks Personal injury from electric shock caused by improper grounding and bonding can cause immeasurable human suffering and significant expense Potential fire hazards exist when heat is generated from electrical surges that occur on a high impedance grounding and bonding path. Ott, Henry. Noise Reduction Techniques in Electronic., 2nd edition. NY: Wiley-Interscience, Institute of Electrical and Electronics Engineers. IEEE Std IEEE Recommended Practice for ing and Grounding Electronic Equipment. 3. Quoted from Doug Dorr, Senior Project Manager, EPRI and William ush, Industry Consultant for and Grounding and Surge Protection. oth serve on the IEEE P00 committee (Emerald ook) in leadership positions and also on the IEEE SPD committee, as well as other standards organizations. 4. Quoted from S. Frank Waterer, Electrical Engineering, Fellow, at Schneider Electric with 30 years experience, Vice-Chair of IEEE/SPDC, NEMA member. 2

3 PHYSICAL INFRASTRUCTURE SYSTEMS CAN YOU AFFORD IMPROPER GROUNDING? According to IEEE, grounding and bonding are an essential part of the infrastructure, not just a tool to achieve power quality. Network equipment, such as switches, routers, and storage devices, costs anywhere from thousands of dollars to hundreds of thousands of dollars. The cost of proper grounding is only a tiny fraction of the cost of the equipment it is protecting. Clearly the cost of proper grounding and bonding is a small fraction of the larger cost of improper grounding and bonding mainly, the inability to service customers properly. Protect your infrastructure with the most comprehensive grounding system, designed specifically for easy selection and installation with the highest quality components to minimize your risk. From the data center, to the manufacturing floor, to facilities operations, there are critical systems and equipment that require proper grounding and bonding. Protecting those systems, equipment, and personnel helps to ensure equipment reliability and thus availability of services, while resulting in lower operational expense. Comprehensive, integrated technology from Panduit addresses the grounding and bonding needs of the entire infrastructure including electrostatic discharge (ESD) protection, racks, cabinets, enclosures, access floors, control panels, service entrance, and direct burial applications. These industry-leading solutions deliver reliability, availability, safety and lower total cost of ownership. As a solution architecture, the StructuredGround Grounding is complemented by a range of installation tooling, design software, and services. Panduit StructuredGround Grounding gives you what you need to properly protect your investment. A.. Ott, Henry, Noise Reduction Techniques in Electronic, 2nd edition, NY; Wiley-Interscience, Institute of Electrical and Electronics Engineers, IEEE Std , IEEE Recommended Practice for ing and Grounding Electronic Equipment. 3. Quoted from Doug Dorr, Senior Project Manager, EPRI and William ush, Industry Consultant for and Grounding and Surge Protection. oth serve on the IEEE P00 committee (Emerald ook) in leadership positions and also on the IEEE SPD committee, as well as other standards organizations. 4. Quoted from S. Frank Waterer, Staff Engineer at Schneider Electric with 30 years experience. For service and technical support, call (outside the U.S. and Canada, see back c). 3

4 A. PHYSICAL INFRASTRUCTURE SYSTEMS Common Network (CN) Roadmap Panduit StructuredGround Grounding is a complete, highly reliable line of products to ground your building and network equipment in compliance with ICSI TDM Manual,2th Edition and TIA-607-,TIA-942, IEEE Std 00 (IEEE Emerald ook), UL and CSA Telecommunications Room (see roadmap on page 6) Data Center (see roadmaps on pages 8 9) Service Entrance (see roadmap on page 5) For more data center grounding information, see 4

5 Service Entrance Grounding Roadmap PHYSICAL INFRASTRUCTURE SYSTEMS Complies with TIA-607- and IEEE Std 00 (IEEE Emerald ook) Grounding Equalizer (GE) is required when two or more Telecommunications ackbones (T) are used within a multi-story building; bond Ts together with a GE at the top floor and at a minimum of every third floor in between Telecommunications ackbone (T)** 3 2 Grounding Equalizer (GE) Conduit A. 8 5 Earth Ground AC Panel* 2 Compression HTAP and Clear C: HTWC (pages 4 thru 42) ronze, U-olt Grounding Clamp: GPL (page 44) AC Service Entrance Water Meter 4 4 Telecommunications Main Grounding usbar (TMG) and usbar Label (page 29) Telecommunications Grounding and Conductor Label Kit: LTYK (page 29) Entrance 3 Compression, Two-Hole, Long arrel with Window Lug: LCC-W (pages 36 38) 7 Universal eam Grounding Clamp: GUC500-6 (page 3) 4 ronze, Water Pipe Grounding Clamp: KP (page 44) 8 E Style Grounding Connector: GCE For the complete line of StructuredGround Direct urial Compression Grounding, visit *AC panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer s specifications. **TIA-607- specifies different size conductors based on the length of the Telecommunications ackbone (T). For service and technical support, call (outside the U.S. and Canada, see back c). 5

6 A. PHYSICAL INFRASTRUCTURE SYSTEMS Telecommunications Room Grounding Roadmap Complies with ICSI TDM Manual, 2th Edition and TIA-607-, TIA-942, IEEE Std 00 (IEEE Emerald ook), UL and CSA hardware is recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between metallic components and the grounded rack or cabinet Can be used to ground equipment mounted in racks and cabinets which meet EIA-30; installer should bond all racks and cabinet members to the grounding strip ack of Racks Shown Grounding Equalizer (GE) Conduit AC Panel* 6 Telecommunications ackbone (T) uilding Steel Compression HTAP and Clear C: HTWC (pages 4 42) Compression, Two-Hole, Long arrel with Window Lug: LCC-W (pages 36 38) Telecommunications Grounding usbar (TG) and usbar Label (page 29) Auxiliary racket: GAC (page 3) Telecommunication Equipment Conductor (TEC) Kits: (pages 2 22) Universal eam Grounding Clamp: GUC500-6 (page 3) Electrostatic Discharge (ESD) Port Kit: RGESD (page 24) Wyr-Grid Overhead Tray (page 65 74) 6 *AC panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer s specifications. A typical head cabling system includes a multitude of metallic components which are connected together. It is the responsibility of the installer to insure all of the metallic components are bonded, which means that they are connected together electrically in accordance with applicable specifications. The Panduit Grounding and does not insure required bonding of the head cabling system metallic components.

7 PHYSICAL INFRASTRUCTURE SYSTEMS Access Floor Mesh Common Network (MCN) Roadmap Complies with ICSI TDM Manual, 2th Edition and TIA-607-, TIA-942, IEEE Std 00 (IEEE Emerald ook), UL and CSA MCN for access floor deployment is recommended in a grid design on 4 foot intervals, allowing for bonding of every other access floor pedestal; this design enables the bonding of at least one pedestal from each access floor tile directly to the MCN network ond all metallic elements to the MCN, including rack/cabinet grounding jumpers, wire basket, water pipes and air conditioning units A Compression HTAP and Clear C: HTWC (pages 4 42) 5 4 Code Conductor, Thin Wall, CTAP: CTAPF (page 43) (Some pedestals lightened for clarity) 2 ronze, U-olt Grounding Clamp: GPL (page 44) 5 Split olt, : SC (page 45) 3 Access Floor Grounding Clamp: GPQC (page 6) 6 GridRunner (pages 75 79) For service and technical support, call (outside the U.S. and Canada, see back c). 7

8 A. PHYSICAL INFRASTRUCTURE SYSTEMS Data Center Rack and Cabinet Grounding Roadmap Complies with ICSI TDM Manual, 2th Edition and TIA-607-, TIA-942, IEEE Std 00 (IEEE Emerald ook), UL, and CSA hardware is recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between metallic components and the grounded rack or cabinet Designed for use on racks and cabinets which meet EIA-30, see pages 74 for the Panduit cabinets, racks, and cable management offering ack of Racks Shown 3 4 Data Equipment Racks AC Panel* uilding Steel Conduit 7 Telecommunications ackbone (T) 8 9 Mesh Common Network (MCN) Access Floor Pedestal 2 2 Compression HTAP and Clear C: HTWC (pages 4 42) Access Floor Grounding Clamp: GPQC (page 6) Compression, Two-Hole, Long arrel with Window Lug: LCC-W (pages 36 38) Telecommunications Grounding usbar (TG) and usbar Label (page 29) Universal eam Grounding Clamp: GUC500-6 (page 3) 8 *AC panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer s specifications. A typical access floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of the access floor to insure all the access floor metallic components are bonded which means that they are connected together electrically in accordance with applicable specifications. The Panduit Grounding and does not insure required bonding of the access floor metallic components.

9 ack of Cabinets Shown PHYSICAL INFRASTRUCTURE SYSTEMS Data Equipment Cabinets A. (Sides/ doors removed for clarity) 7 2 Mesh Common Network (MCN) Access Floor Pedestal 6 Telecommunications Grounding and Conductor Label Kit: LTYK (page 29) 8 Code Conductor, Thin Wall, CTAP: CTAPF (page 43) 7 Surge Suppressor Jumper Kit: SSGK (page 20) 9 Common Network (CN) Jumper Kit: RGCNJ (page 6) A typical access floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of the access floor to insure all the access floor metallic components are bonded which means that they are connected together electrically in accordance with applicable specifications. The Panduit Grounding and does not insure required bonding of the access floor metallic components. For service and technical support, call (outside the U.S. and Canada, see back c). 9

10 A. PHYSICAL INFRASTRUCTURE SYSTEMS Selection Guide StructuredGround Kits for Net-Access Cabinets Complies with the Telecommunications Standard for Data Centers as described in TIA-942 and TIA-607- Maximizes uptime, maintains system performance, and protects network equipment Provides a dedicated, low resistance, and visually verifiable ground system Flexible design for use on EIA-30 compliant cabinets Typical cage nut application ack of cabinet shown (Sides/doors removed for clarity) Kits for threaded and thru-hole also available Grounding Strip Kit: RGS (page 7) Patented hardware provides a bond between grounding strip and cabinet, eliminating the need to scrape paint Electrostatic Discharge (ESD) Port Kit: RGESD (page 24) ent 45 acts as a hook to hold ESD wrist strap Cage Nut: CNK (page 25) Patented, bonds equipment and patch panels to cabinet rails Electrostatic Discharge (ESD) Wrist Strap Kits: RGESDWS (page 24) Prevents damaging electrostatic discharge to equipment and personnel Common Network (CN) Jumper Kit: RGCNJ (page 6) Connects grounding busbar to MCN in access floor and head grounding applications Equipment Jumper Kit: RGEJ (page 9) onds network equipment to the grounding strip or grounding busbar Mesh Common Network (MCN) 0

11 PHYSICAL INFRASTRUCTURE SYSTEMS Selection Guide StructuredGround Kits for Net-Access Cabinets (continued) Cabinet Grounding Selection in 2 Easy Steps:. What type of fasteners do your mounting rails require? 2. What is the maximum depth of the equipment being mounted? A. Selection Criteria Grounding Strip Kit^ ESD Port Kit (2 required) ESD Wrist Strap ( per ESD Port) Grounding usbar Kit^ Front to ack Rail Jumper Kit^ Common Network (CN) Jumper Kit* Equipment Jumper Kit** Hardware*** Panduit Net-Access Cabinets: CN, CN2, CN4, CN5, CNCN, CN2CN, CS, CS2 and CS3. Rail Fasteners Threaded #2-24 RGS34-Y RGESD2- RGESDWS Cage Nut RGS34- RGESD2- RGESDWS EIA-30 Compliant Cabinets. Rail Fasteners Threaded #2-24 or M6 Cage Nut 2. Rail Depth up to 20" (.5M) StructuredGround Kits for Data Center Cabinet Grounding RGCNJ660P22 GJS660U StructuredGround Kits for Data Center Cabinet Grounding CGJ620U 30" (.75M) RGS34-Y RGESD2- RGESDWS RGR9U CGJ630U 40" (M) CGJ640U 20" (.5M) CGJ620U 30" (.75M) RGS34- RGESD2- RGESDWS RGR9CN CGJ630U 40" (M) CGJ640U RGCNJ660P22 GJS660U ^Grounding strip kits, grounding busbar kits, and front to back rail jumper kits are supplied with mounting hardware based upon rail type. Grounding strip kits also available in packages of ten. RGTSG-C ( Screw) CNK ( Cage Nut) RGTSG-C or RGTSM6G-C CNK ( Cage Nut) ESD port recommended for use on front and back of cabinet. *CN jumper kit supports MCN connection up to #2 (35mm 2 ). Use RGCNJ660PY for cable sizes up to 250kcmil (20mm 2 ). **Additional equipment jumper kits available in different sizes with different termination options, refer to page 9. One equipment jumper kit is required per component. ***Use bonding hardware to mount and bond equipment to the cabinet. Threaded #2-24 rails are included with the CN, CN2, CN4 and CN5 cabinets. Cage nut equipment rails are sold in pairs for the cabinets, order part number CNRC, CNCN, CN2CN, CS, CS2 or CS3. For service and technical support, call (outside the U.S. and Canada, see back c).

12 A. PHYSICAL INFRASTRUCTURE SYSTEMS Selection Guide StructuredGround Kits for Racks Complies with the Telecommunications Standard for Data Centers as described in TIA-942 and TIA-607- Maximizes uptime, maintains system performance, and protects network equipment Provides a dedicated, low resistance, and visually verifiable ground system Flexible design for use on EIA-30 compliant racks New installation Typical threaded application ack of rack shown Kits for cage nut and thru-hole also available Screw: RGTS (page 25) Patented, bonds equipment and patch panels to the front of the rack. Paint Piercing Grounding Washer Kit: RGW (page 26) Provides a superior bond between frame members, serrations eliminate the need to scrape paint Electrostatic Discharge (ESD) Port Kit: RGESD (page 24) ent 45 acts as a hook to hold ESD wrist strap Equipment Jumper Kit: RGEJ (page 9) onds network equipment to the grounding strip or grounding busbar Electrostatic Discharge (ESD) Wrist Strap Kit: RGESDWS (page 24) Prevents damaging electrostatic discharge to equipment and personnel Common Network (CN) Jumper Kit: RGCNJ (page 6) Connects grounding strip or grounding busbar to MCN in access floor and head grounding applications Grounding Strip Kit: RGS (page 7) Thread-forming hardware provides a bond between grounding strip and rack, eliminating the need to scrape paint 2 Mesh Common Network (MCN)

13 PHYSICAL INFRASTRUCTURE SYSTEMS Selection Guide StructuredGround Kits for Racks (continued) For Panduit racks: Simply find your rack part number and follow across. For other EIA-30 compliant racks, follow these two easy steps:. What type of installation do you have? 2. What type of fasteners do your mounting rails require? A. Selection Criteria Grounding Strip Kit ESD Port Kit (2 required)* ESD Wrist Strap ( per ESD Port) Grounding usbar Kit Common Network (CN) Jumper Kit Equipment Jumper Kit** Hardware*** Panduit Racks 2 Post Racks StructuredGround Kits for Data Center Rack Grounding R2P, R2P48, R2PS New Installation R2P, R2P48, R2PS Retrofit Installation NFR84 New Installation NFR84 Retrofit Installation 4 Post Racks R4P, R4P96 New Installation R4P, R4P96 Retrofit Installation R4PCN, R4P96CN New Installation R4PCN, R4P96CN Retrofit Installation EIA-30 Compliant Racks RGS34-Y RGESD2- ( each) RGESD-Y and RGESD2- RGESDWS The paint piercing grounding washers work with 3/8" (M8) hardware, for all other sizes, use the grounding solution for retrofit installations. *ESD port recommended for use on front and back of rack. **Additional equipment jumper kits available in different sizes with different termination options, refer to page 9. One equipment jumper kit is required per component. ***Use bonding hardware to mount and bond equipment to the rack. RGR9U RGCNJ660P22 RGRKCNJY RGESDWS RGR9U RGCNJ660P22 GJS660U GJS660U RGS34-Y GJS660U RGESD2- RGESDWS RGR9U GJS660U RGCNJ660P22 RGS34- GJS660U RGESD2- RGESDWS RGR9CN GJS660U RGS34-Y RGESD2- RGESD2A- RGESDWS RGESD2- RGR9U RGCNJ660P22 RGCNJ660P22 RGRKCNJY GJS660U GJS660U RGTSG-C (#2-24) RGTSG-C CNK RGTSG-C (#2-24) or RGTSM6G-C (M6) RGTS032G-C (#0-32) or RGTSM5G-C (M5) RGTSG-C (#2-24) or RGTSM6G-C (M6) For service and technical support, call (outside the U.S. and Canada, see back c). 3

14 A. PHYSICAL INFRASTRUCTURE SYSTEMS Features and enefits StructuredGround Kits for Cabinets Panduit offers a variety of kits with premium components engineered specifically to meet TIA-942 and TIA-607- for reliable cabinet grounding. Provides a dedicated, low resistance, and visually verifiable ground system to maximize uptime, maintain data center system performance, and protect network equipment and personnel Incorporates a flexible design that can be used with cabinets which meet EIA-30 Offers ease of installation no paint scraping required to bond cabinets; factory terminated jumpers simply bolt in place Grounding Strip Kit (see page 7) A C D E F Cage Nut is a patented hardware with paint piercing serrations designed to create a bond point between the cabinet rail and the equipment being installed Grounding Strip is made from high conductivity wrought copper and tin-plated to inhibit corrosion, providing the lowest resistance path to ground Reverse ent Lugs are factory terminated on front to back rail jumper kits to bond the front and back cabinet rails; innovative design maximizes space by utilizing only one RU Studs include patented paint piercing serrations to create a bond point between the cabinet rail, strip, busbar and lug; equipment can be installed at any time without removal of stud Grounding usbar is made from high conductivity, low resistance wrought copper and tin-plated to inhibit corrosion Electrostatic Discharge (ESD) Port is made from high conductivity, low resistance copper and tin-plated to inhibit corrosion plus it functions as an ESD wrist strap hanger D H C F A Electrostatic Discharge (ESD) Port Kit (page 24) Equipment Jumper Kit (page 9) Surge Suppressor Jumper Kit (page 20) G H Compression HTAP is UL Listed and CSA Certified; used to make a highly reliable, permanent bond between the mesh common bonding network and common bonding network (CN) jumper kit Jumper has UL, VW- flame rated green-and-yellow insulation and is factory terminated with copper compression, two-hole, long barrel with window lug; lug is UL Listed, CSA Certified and meets NES Level 3 E Grounding usbar Kit (page 7) G Front to ack Rail Jumper Kit (page 8) Common Network (CN) Jumper Kit (page 6) 4 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

15 PHYSICAL INFRASTRUCTURE SYSTEMS Features and enefits StructuredGround Kits for Racks Panduit offers a variety of kits with premium components engineered specifically to meet TIA-942 and TIA-607- for reliable rack grounding. Provides a dedicated, low resistance, and visually verifiable ground system to maximize uptime, maintain data center system performance, and protect network equipment and personnel Incorporates a flexible design that can be used with racks which meet EIA-30 Offers ease of installation no paint scraping required to bond racks; factory terminated jumpers simply bolt in place A A. A C Paint Piercing Grounding Washer is made from hardened steel and electro zinc plated which inhibits corrosion to provide a superior bond between frame members on bolt-together racks Grounding Strip is made from high conductivity wrought copper and tin-plated to inhibit corrosion, providing the lowest resistance path to ground Thread-Forming Screws are made from electro zinc plated steel and provide a bond to the rack by removing paint from threaded holes without creating metal shavings Grounding Strip Kit (page 7) E D C Electrostatic Discharge (ESD) Port Kit (page 24) D Electrostatic Discharge (ESD) Port is made from high conductivity, low resistance copper and tin-plated to inhibit corrosion plus it functions as an ESD wrist strap hanger G E F G Electrostatic Discharge (ESD) Protection Sticker is provided in black and yellow for high visibility and easy identification as an ESD port Compression HTAP is UL Listed and CSA Certified; used to make a highly reliable permanent bond between the mesh common bonding network and common bonding network (CN) jumper kit Jumper has UL, VW- flame rated green-and-yellow insulation and is factory terminated with copper compression, two-hole, long barrel with window lug; lug is UL Listed, CSA Certified and meets NES Level 3 with a single stud hole and slot which allows mounting for /2" to 5/8" hole spacing and accommodates stud sizes /4", #2, and 6mm Equipment Jumper Kit (page 9) Surge Suppressor Jumper Kit (page 20) F Common Network (CN) Jumper Kit (page 6) For service and technical support, call (outside the U.S. and Canada, see back c). 5

16 A. PHYSICAL INFRASTRUCTURE SYSTEMS Access Floor Grounding Clamps ond mesh common bonding network (MCN) conductors to each other and bond the access floor pedestals to the conductors Specifically designed to bond perpendicular MCN conductors per TIA-942 and TIA-607- ond to the pedestal with a single bolt to simplify installation Accommodate conductors from #6 /0, minimizes inventory requirements ond round and square access floor pedestals for greater flexibility W D H Installed on Pedestal Round Square MCN Conductor Size Figure Dimensions Tightening Torque Pedestal Pedestal Range Lbs. Ctn. D W H Conductor Clamp GPQC07-/0 3/4 7/8 #6 SOL /0 STR GPQC0-/0 /8 7/8 #6 SOL /0 STR GPQC2-/0 /4 #6 SOL /0 STR GPQC5-/0 /2 #6 SOL /0 STR GPQC7-/0 3/4 #6 SOL /0 STR GPQC20-/0 2 #6 SOL /0 STR D RATED Split olt Quad Clamp, ronze Split bolt design allows easy insertion of perpendicular conductors speeding installation UL 467 Listed and CSA Certified for direct burial in earth or concrete UL Listed and CSA Certified for use up to 600 V and temperature rated 90 C Each clamp accepts up to two conductors for a high performance bond with faster installation Wide wire range-taking capability minimizes inventory requirements Made from high strength, electrolytic bronze to provide reliable grounding connections W E L Conductor Size Range Figure Dimensions E W L Tightening Torque Lbs. SQC/0-X #6-/ #6 #4 65 #3 # 275 / Common Network (CN) Jumper Kits ond the rack or cabinet to the MCN HTAPs, included in kits, require crimping tool and die; see the CT-930 crimping tool on page 47, the CT-2930/L and crimping tools on page 48 and the CD-930H-250 and CD-920H-2 crimping dies on page 49 HTAPs are UL Listed and CSA Certified for applications up to 600 V when crimped with Panduit and specified competitor crimping tools and Panduit crimping dies Engineered to comply with US and International grounding requirements RGCNJ660P22 RGCNJ660PY MCN Conductor Size HTCT2-2- #6 #2 HTCT #2 250 kcmil *HTAPs also sold separately, see pages Part Description #6 (6mm²) jumper; 60" (.52m) length; 45 bent lug on grounding strip side; provided with.6 oz. (5cc) of antioxidant, two each #2-24 x /2", M6 x 2mm, #0-32 x /2" and M5 x 2mm threadforming screws and a copper compression HTAP* for connecting to the MC Ctn Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

17 PHYSICAL INFRASTRUCTURE SYSTEMS A. Grounding Strip Kits onds up to 45 RU per rack EIA Universal mounting hole pattern Engineered to comply with US and International grounding requirements Part Description Grounding Strip Kits for Threaded Rail Fasteners Threaded Rail Kit RGS34-Y Grounding strip; 78.65" (2m) length;.67" (7mm) width;.05" (.27mm) thickness; provided with.6 oz. (5cc) of antioxidant, one grounding sticker and three each #2-24 x /2" and M6 x 2mm thread-forming screws. RGS34-0-Y Ten grounding strips; 78.65" (2m) length;.67" (7mm) width;.05" (.27mm) thickness; provided with.6 oz. (5cc) of antioxidant, ten grounding stickers and 30 each #2-24 x /2" and M6 x 2mm thread-forming screws. Grounding Strip Kits for Cage Nut Rail Fasteners RGS34- Grounding strip; 78.70" (2m) length;.67" (7mm) width;.05" (.27mm) thickness; provided with.6 oz. (5cc) of antioxidant, one grounding sticker, three cage nut bonding studs, eight #2-24 bonding nuts and three strip clips. Cage Nut Rail Kit RGS34-0- Ten grounding strips; 78.70" (2m) length;.67" (7mm) width;.05" (.27mm) thickness; provided with.6 oz. (5cc) of antioxidant, ten grounding stickers, 30 cage nut bonding studs, 80 #2-24 bonding nuts and 30 strip clips. Grounding usbar Kits Provide the common grounding point within the cabinet Optimized for installation on 9" racks or cabinets that meet EIA-30 Can be positioned anywhere on the rack or cabinet Available pre-assembled with twenty mounting screws for quick and easy installation Engineered to comply with US and International grounding requirements RGR9U Part Description Grounding usbar Kits for Threaded Rail Fasteners RGR9Y Grounding busbar; 9" (483mm) length; tin-plated; fourteen holes arranged for flexibility in mounting; provided with two each #2-24 x /2" and M6 x 2mm thread-forming screws. RGR9U Grounding busbar; 9" (483mm) length; tin-plated; twenty holes arranged for flexibility in mounting with twenty #2-24 x /2" hex head screws installed; mounting hole sets have 5/8" (5.9mm) spacing; provided with two each #2-24 x /2", M6 x 2mm thread-forming screws, and two #2 flat washers for mounting. Grounding usbar Kit for Cage Nut Rail Fasteners RGR9CN Grounding busbar; 9" (483mm) length; tin-plated; twenty holes arranged for flexibility in mounting with twenty #2-24 x /2" hex head screws installed; mounting hole sets have 5/8" (5.9mm) spacing; provided with two cage nut bonding studs and four #2-24 bonding nuts. For service and technical support, call (outside the U.S. and Canada, see back c). 7

18 A. PHYSICAL INFRASTRUCTURE SOLUTIONS Front to ack Rail Jumper Kits ond the front and back cabinet rails to the cabinet grounding busbar Patent pending hardware incorporates paint piercing serrations to create a bond point between the cabinet rail and lug; hardware never needs to be removed for new equipment installations Length (m) oth ends are factory terminated with reverse bent lugs that save space, confining the connection to one RU Available in three lengths, 20", 30", and 40" to satisfy a wide range of cabinet rail depths Engineered to comply with US and International grounding requirements Part Description Front to ack Rail Jumper Kits for #2-24 or M6 Rail Fasteners CGJ620U 20 (.50) CGJ630U 30 (.75) CGJ640U 40 (.00) Two #6 (6mm²) jumpers; factory terminated on both ends with 90 reverse bent lugs; provided with.6 oz. (5cc) of antioxidant, two grounding stickers, eight each #2-24 and M6 bonding studs and sixteen each #2-24 and M6 bonding nuts. Front to ack Rail Jumper Kits for Cage Nut Rail Fasteners CGJ620U 20 (.50) CGJ630U 30 (.75) CGJ640U 40 (.00) Two #6 (6mm²) jumpers; factory terminated on both ends with 90 reverse bent lugs; provided with.6 oz. (5cc) of antioxidant, two grounding stickers, eight cage nut bonding studs and 24 #2-24 bonding nuts. 8 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

19 ond network equipment to grounding strip or grounding busbar Jumper kit available with both ends factory terminated to provide a bolt-on solution Jumper kit available with one end factory terminated to attach to the grounding strip or grounding busbar; free end accommodates unique equipment terminations PHYSICAL INFRASTRUCTURE SYSTEMS Use jumpers with 90 bent lug, on grounding strip side, for high density grounding requirements up to one ground point per RU Use jumpers with 45 bent lugs, on grounding strip side, for improved cable management Engineered to comply with US and International grounding requirements A. 60 (.52) Straight #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with 0 96 (2.44) LCC6-4JAW- Straight 0 24 (0.6) 24 (0.6) 36 (0.9) 24 (0.6) #0 (6mm²) jumper; bent lug on grounding strip side to straight lug on equipment; provided with.6 oz. (5cc) of antioxidant and two each #2-24 x /2", M6 x 2mm, #0-32 x /2" and M5 x 2mm thread-forming screws Straight #0 (6mm²) jumper, 24 in. (609.6mm) L, pre-terminated with two #0 (5.3mm) stud hole ring terminals to provide a bolt-on solution for grounding network equipment. 24 (0.6) 24 (0.6) 36 (0.9) 60 (.52) 96 (2.44) #6 (6mm²) jumper; bent lug on grounding strip side to straight lug on equipment; provided with.6 oz. (5cc) of antioxidant and two each #2-24 x /2", M6 x 2mm, #0-32 x /2" and M5 x 2mm thread-forming screws #6 (6mm²) jumper; bent lug on grounding strip side to straight lug on equipment (.52) 96 (2.44) Straight #6 (6mm²) jumper, 60 in. (524mm) L, pre-terminated with two straight slotted lugs to provide a bolt-on solution for grounding network equipment. Straight #6 (6mm²) jumper, 96 in. (2438.4mm) L, pre-terminated with two straight slotted lugs to provide a bolt-on solution for grounding network equipment. 57 (.45) 90 #0 (6mm²) jumper; bent lug on grounding strip side; provided with.6 oz. (5cc) of antioxidant and two each #2-24 x /2", M6 x 2mm, #0-32 x /2" and M5 x 2mm thread-forming screws. 57 (.45) 90 #6 (6mm²) jumper; bent lug on grounding strip side; provided with.6 oz. (5cc) of antioxidant and two each #2-24 x /2", M6 x 2mm, #0-32 x /2" and M5 x 2mm thread-forming screws For service and technical support, call (outside the U.S. and Canada, see back c). 9

20 A. PHYSICAL INFRASTRUCTURE SOLUTIONS Surge Suppressor Jumper Kit onds power or data line surge suppressor to grounding strip or grounding busbar oth ends factory terminated to provide a bolt-on solution SSGK- Engineered to comply with US and International grounding requirements Part Description #0 (6mm²) jumper; 24" (.6m) length; factory terminated on both ends; one-hole lug on surge suppressor to two-hole lug on grounding strip/busbar side; provided with.6 oz. (5cc) of antioxidant and two each #2-24 x /2", M6 x 2mm, #0-32 x /2" and M5 x 2mm thread-forming screws. Armored Grounding Kit Provides a secure bond to the armor sheath on indoor and indoor/outdoor fiber optic cables at both cassette and enclosure ends Worm-gear design evenly distributes forces across the armor Made from steel and aluminum material is compatible with common armor for long term reliability lack insulating c protects and hides the connection for an aesthetically pleasing work area Complies with industry requirements ensuring a high level of reliability and safety Part Description ACG24K #6 (6mm 2 ) jumper for armored cable diameter up to 0.84" (2.3mm); 24" (609.6mm) length; factory terminated on one end with LCC6 two-hole copper compression lug and the other end with grounding terminal; provided with two each #2-24 and M6 thread-forming screws and a black polypropylene terminal c. ACG24K-500 ACG24KX-500 ACGK ACGKX #6 (6mm 2 ) jumper for armored cable diameter 0.85" (2.3mm) to.03" (26.2mm); 24" (609.6mm) length; factory terminated on one end with LCC6 two-hole copper compression lug and the other end with grounding terminal; provided with two each #2-24 and M6 thread-forming screws and a black polypropylene terminal c. #6 (6mm 2 ) jumper for armored cable diameter 0.94" (23.9mm) to.5" (38.mm); 24" (609.6mm) length; factory terminated on one end with LCC6 two-hole copper compression lug and the other end with grounding terminal; provided with two each #2-24 and M6 thread-forming screws and a black polypropylene terminal c. Armored cable grounding kit with one grounding terminal for #6 and one #0 mechanical clamp, 9/6" /6" diameter range. Armored cable grounding kit with one grounding terminal for #6 and one #6 mechanical clamp, 5/6" /2" diameter range. 20 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

21 PHYSICAL INFRASTRUCTURE SYSTEMS Telecommunication Equipment Conductor (TEC) Kits onds the rack or cabinet to the telecommunications grounding busbar (TG) Jumper kit available with both ends factory terminated to provide a bolt-on solution Jumper kit available with one end factory terminated to attach to the rack or cabinet; free end accommodates unique length requirements Engineered to comply with US and international grounding requirements A. Length m Angle Part Description Pre-Terminated on oth Ends Jumpers Pre-Terminated on oth Ends GJ672UH Straight and 45 One 72" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- GJ696UH Straight and 45 One 96" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- GJ620UH Straight and 45 One 20" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- GJ644UH Straight and 45 GJ668UH Straight and 45 GJ692UH Straight and 45 GJ626UH Straight and 45 GJ6240UH Straight and 45 One 44" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- One 68" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- One 92" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- One 26" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- One 240" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- GJ6264UH Straight and 45 One 264" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- GJ6288UH Straight and 45 One 288" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAWH-L and the other end with LCC6-4JAW- Table continues on page 22 For service and technical support, call (outside the U.S. and Canada, see back c). 2

22 A. PHYSICAL INFRASTRUCTURE SOLUTIONS Telecommunication Equipment Conductor (TEC) Kits (continued) Pre-Terminated on One End Length m Angle Part Description Jumpers Pre-Terminated on One End GJS620U Straight One 20" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAW- GJS680U Straight One 80" length #6 green wire with yellow horizontal stripe. Jumper is pre-terminated on one end with LCC6-4JAW- Hardware for TEC Kits Part Description Hardware for TEC Kits HDW/4-KT HDW3/8-KT HDW/4-A-KT HDW3/8-A-KT Stainless steel mounting hardware for busbar; two /4-20 hex bolts, two /4-20 hex nuts, four /4 flat washers and two /4 elleville compression washers. Mounting hardware for rack or cabinet; two #2-24 thread-forming screws and two M6 thread-forming screws. Stainless steel mounting hardware for busbar; two 3/8-6 hex bolts, two 3/8-6 hex nuts, four 3/8 flat washers and two 3/8 elleville compression washers. Mounting hardware for rack or cabinet; two #2-24 thread-forming screws and two M6 thread-forming screws. Stainless steel mounting hardware for busbar; two /4-20 hex bolts, two /4-20 hex nuts, four /4 flat washers and two /4 elleville compression washers. Mounting hardware for rack or cabinet; two #0-32 thread-forming screws and two M5 thread-forming screws. Stainless steel mounting hardware for busbar; two 3/8-6 hex bolts, two 3/8-6 hex nuts, four 3/8 flat washers and two 3/8 elleville compression washers. Mounting hardware for rack or cabinet; two #0-32 thread-forming screws and two M5 thread-forming screws. 22 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

23 PHYSICAL INFRASTRUCTURE SYSTEMS Enclosure Grounding Kit Patented bracket provides equipotential bonding and protection from static electricity for equipment housed in enclosures A discrete grounding point for each piece of equipment within the enclosure allows equipment to be easily added or moved without disturbing other grounding connections Anti-rotation design prevents one-hole lugs from loosening PZAEGK Grounding washer provides a high performance electrical bond, eliminating the need to manually remove paint uilt-in ESD port provides a convenient docking station for ESD wrist strap Provides proper bonding of Pan Active Wall Mount Enclosure PZAEWM3, see page 5 Part Description One tin-plated copper bracket; 3.92" L x.56" W x.79" H (99.6mm x 4.2mm x 20.mm); provided with four #2-24 screws, one each #0-32 and #0-24 hex nut, #0 split lock washer, grounding washer and ESD protection sticker. A. Shielded Jack Module Grounding Kit Alternate method for grounding modules to another grounding wire in shielded applications CJSGK-XY Part Description Kit used to ground enhanced Giga-TX Style Shielded Jack Modules to another ground wire in shielded applications. Ctn For service and technical support, call (outside the U.S. and Canada, see back c). 23

24 A. PHYSICAL INFRASTRUCTURE SOLUTIONS Electrostatic Discharge (ESD) Port Kits and Wrist Strap Accommodate standard ESD wrist strap 4mm plug Wrist strap provides rapid and continuous drain of electrostatic charge between a person and the surface that the wrist strap is bonded to, thus preventing damaging static discharge into equipment Can be mounted to front or back of rack or cabinet for convenient access ent 45, acts as a hook to hold wrist strap Two-hole configuration provides anti-rotation and prevents loss of bond arrel permanently marked with the protective earth (ground) symbol Engineered to comply with US and International grounding requirements RGESD2- RGESD2- ESD port must be attached to a grounded member. ESD wrist strap sold separately. Part Description ESD Port Kit for #2-24 or M6 Rail Fasteners RGESD2- Two-hole ESD port with 5/8" hole spacing; provided with an ESD protection sticker,.6 oz. (5cc) of antioxidant, and two each #2-24 x /2" and M6 x 2mm thread-forming screws. ESD Port Kit for Cage Nut Rail Fasteners RGESD2- Two-hole ESD port with 5/8" hole spacing; provided with an ESD protection sticker,.6 oz. (5cc) of antioxidant, two cage nut bonding studs and two #2-24 bonding nuts. ESD Wrist Strap RGESDWS Adjustable fabric ESD wrist strap with 6' coil cord, banana plug, megohm resistor and 4mm snap. Ctn RGESDWS 24 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

25 PHYSICAL INFRASTRUCTURE SYSTEMS A. Screws Patented screws create an electrical bond between painted patch panels and racks or cabinets Serrations on bottom of screw remove paint from patch panel, providing metal-to-metal contact Available in two color options to meet different application needs Thread-forming, provides a bond to the rack or cabinet by removing paint from threaded holes and minimizing metal shavings Permanently marked with the protective earth (ground) symbol and Panduit logo Easily installed with Phillips screwdriver Part Description RGTSG-C Green thread-forming bonding screw, #2-24 x /2". 00 RGTSM6G-C Green thread-forming bonding screw, M6 x 5mm. 00 RGTS032G-C Green thread-forming bonding screw, #0-32 x /2". 00 RGTSM5G-C Green thread-forming bonding screw, M5 x 5mm. 00 Cage Nut Patented, creates an electrical bond between the mounting rails and equipment Conforms to EIA-30 specifications for racks and cabinets CN4K CNK Made from high carbon steel Easily installed with a Phillips, flat blade, or nut screwdriver Part Description Green bonding cage nut, includes 4 #2-24 bonding cage nuts (.06. thick panel) and 4 #2-24 x /2" bonding screws with #2 Phillips/slotted combo hex head (use 5/6" or 8mm socket). Ideal for patch panel applications. Green bonding cage nut, includes 50 #2-24 bonding cage nuts (.06. thick panel) and 50 #2-24 x /2" bonding screws with #2 Phillips/slotted combo hex head (use 5/6" or 8mm socket). Thread-Forming Screws Thread-forming, provide a bond to the rack or cabinet by removing paint from threaded holes and minimizing metal shavings Easily installed with 5/6" (8mm) socket head wrench or flat blade screwdriver Part Description RGTS-CY Thread-forming grounding screw, #2-24 x /2". 00 RGTSM6-C Thread-forming grounding screw, M6 x 2mm. 00 RGTS032-C Thread-forming grounding screw, #0-32 x /2". 00 RGTSM5-C Thread-forming grounding screw, M5 x 2mm For service and technical support, call (outside the U.S. and Canada, see back c). 25

26 A. Paint Piercing Grounding Washer Kit onds frame members on bolt-together racks No paint scraping required Green color-coding to indicate bonding application PHYSICAL INFRASTRUCTURE SOLUTIONS Engineered to comply with US and International grounding requirements Part Description RGW-00-Y 00 paint piercing bonding washers for 3/8" (M8) stud size;.875" (22.2mm) ; provided with.6 oz. (5cc) of antioxidant. Hardware Kits Patented bonding hardware kits incorporate paint piercing serrations to create a bond point between the rack or cabinet and painted patch panels, mounted equipment, servers, busbars, and jumpers TRSK CGNSK Thread-forming, provide a bond to the rack or cabinet by removing paint from holes and minimizing metal shavings Green color-coding to indicate bonding application Part Description Stud Kits for Threaded Rail Fasteners TRSK stud kit for threaded #2-24 rail fasteners; includes 25 bonding studs and 50 bonding nuts. TRSM6K stud kit for threaded M6 rail fasteners; includes 25 bonding studs and 50 bonding nuts. Stud Kit for Cage Nut Rail Fasteners CGNSK stud kit for cage nut rail fasteners; includes 25 bonding studs and 50 bonding nuts. Nuts GN-C nut for threaded #2-24, cage nut, and /4" thru-hole rail fasteners. 00 GNM6-C nut for threaded M6 rail fasteners. 00 GN 26 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

27 PHYSICAL INFRASTRUCTURE SYSTEMS Retrofit Cabinet Grounding Kits Provide a dedicated ground system to maintain system performance and protect network equipment when equipment is already installed Patented hardware incorporates paint piercing serrations to create a bond point between the cabinet rail, grounding busbar and lug; hardware never needs to be removed for new equipment installations Optimized for installation on 9" cabinets that meet EIA-30, with functioning equipment, and are deployed in the field Provides a complete system of matched components to save cost and labor Engineered to comply with US and International grounding requirements A. Electrostatic Discharge (ESD) Port Kit RGESD (page 24) CGR630U Equipment Jumper Kit RGEJ (page 9) Common Network (CN) Jumper Kit RGCN (page 6) Retrofit Cabinet Grounding Kit CGR630 Part Description CGR630U Retrofit grounding kit for installation on cabinets with threaded #2-24 or M6 rail fasteners and rail depth up to 30" (.75m); includes one RGR9U grounding busbar kit and one CGJ630U front to back rail jumper kit. CGR630U Retrofit grounding kit for installation on cabinets with cage nut rail fasteners and rail depth up to 30" (.75m); includes one RGR9U grounding busbar kit and one CGJ630U front to back rail jumper kit. For service and technical support, call (outside the U.S. and Canada, see back c). 27

28 A. PHYSICAL INFRASTRUCTURE SOLUTIONS Retrofit Rack Grounding Kits Provide a dedicated ground system to maintain system performance and protect network equipment when equipment is already installed Optimized for installation on 9" racks that meet EIA-30, with functioning equipment, and are deployed in the field Provide a complete system of matched components that can be easily selected to save cost and labor Thread-forming screws eliminate the need to manually remove paint from the rack Engineered to comply with US and International grounding requirements Network Equipment Rack Grounding usbar RGR HTAP (page 4) Grounding Jumper RGREJ696Y Lug (see pages 36 38) Rack Grounding Kit RGRKCNJEJY Grounding Jumper RGREJ696Y or RGREJ096Y RGRKCNJEJY usbar and Jumper Kits RGRKCNJEJY RGRKCNJY usbar Kits RGR9Y RGR9U RGRKCNJY Part Description Rack grounding kit to ground the rack and one piece of equipment; includes one RGR9U busbar, one HTCT HTAP, and two RGREJ696Y grounding jumpers. Rack grounding kit to ground the rack; includes one RGR9U busbar, one HTCT HTAP, and one RGREJ696Y grounding jumper. Grounding busbar; 9" (483mm) length; tin-plated; fourteen holes arranged for flexibility in mounting; provided with two each #2-24 x /2" and M6 x 2mm thread-forming screws. Grounding busbar; 9" (483mm) length; tin-plated; twenty holes arranged for flexibility in mounting with twenty #2-24 x /2" hex head screws installed; mounting hole sets have 5/8" (5.9mm) spacing; provided with two each #2-24 x /2", M6 x 2mm thread-forming screws, and two #2 flat washers for mounting. Rack Grounding Kit RGRKCNJY RGR9CN Equipment Jumper Kits Grounding busbar; 9" (483mm) length; tin-plated; twenty holes arranged for flexibility in mounting with twenty #2-24 x /2" hex head screws installed; mounting hole sets have 5/8" (5.9mm) spacing; provided with two bonding cage nuts and four #2-24 bonding screws. RGREJ696Y Grounding jumper; #6 (6mm²); 96" (2.44m) length; one end factory terminated to lug; provided with.6 oz. (5cc) of antioxidant and two each #2-24 x /2", M6 x 2mm, #0-32 x /2" and M5 x 2mm thread-forming screws. RGREJ096Y Grounding jumper; #0 (6mm²); 96" (2.44m) length; one end factory terminated to lug; provided with.6 oz. (5cc) of antioxidant and two each #2-24 x /2", M6 x 2mm, #0-32 x /2" and M5 x 2mm thread-forming screws. 28 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

29 PHYSICAL INFRASTRUCTURE SYSTEMS ICSI/TIA-607- Telecommunications Grounding usbars Meet ICSI and TIA-607- requirements for network systems grounding applications Made of high conductivity copper and tin-plated to inhibit corrosion TG TMG Come pre-assembled with brackets and insulators attached for quick installation Use Panduit component labels, sold separately, to identify busbars to meet TIA-607-, see chart below Telecommunications Grounding and Conductor Label Kit ar Size Part Description No. of Mounting Positions /4" Stud Hole with 5/8" Hole Spacing LTYK Label kit includes printed tag and one flame retardant cable tie. For complete labeling solutions and product information, reference charts on pages 25. 3/8" Stud Hole with " Hole Spacing Telecommunications Grounding usbars (TG) G20304TPI- /4" x 2" x 0" 4 3 G20306TPI- /4" x 2" x 2" 6 3 G2032TPI- /4" x 2" x 20" 2 3 G2054TPI- /4" x 2" x 24" 4 5 Telecommunications Main Grounding usbars (TMG) G4062TPI- /4" x 4" x 2" 2 6 G40624TPI- /4" x 4" x 20" 24 6 G4028TPI- /4" x 4" x 24" 28 0 A. Component Labels for ICSI/TIA-607- Telecommunications Grounding usbars Telecommunications Grounding usbar All G2 and G4 Parts Laser/Ink Jet Desktop Printer Label Suggested Label Solutions for TIA-607- Compliance TDP43ME Thermal Transfer Desktop Printer Label PanTher LS8E Hand-Held Printer Label Cougar LS9 Hand-Held Printer Label C200X00FJJ C200X00YPT C200X00FJC T00X000VPC-K For service and technical support, call (outside the U.S. and Canada, see back c). 29

30 A. PHYSICAL INFRASTRUCTURE SOLUTIONS NEMA Hole Pattern Grounding usbars Provided with standard NEMA hole pattern spacing Made of high conductivity copper and tin-plated to inhibit corrosion Come pre-assembled with brackets and insulators attached for quick installation Insulators provide 600 V of insulation ar Size No. of Mounting Positions /2" Stud Hole with 3/4" Hole Spacing G4N0007TPI- /4" x 4" x 2" 7 G4N006TPI- /4" x 4" x 24" 6 G4N0024TPI- /4" x 4" x 36" 24 G4N0026TPI- /4" x 4" x 48" 26 G4N0034TPI- /4" x 4" x 60" 34 Grounding usbar Inch Hole Spacings Provided with inch hole D pattern spacing Made of high conductivity copper and tin-plated to inhibit corrosion See pages for Lug information Come pre-assembled with brackets and insulators attached for quick installation Insulators provide 600 V of insulation ar Size No. of Mounting Positions 3/8" Stud Hole with " Hole Spacing G2D0008TPI- /4" x 2" x 2" 8 G2D002TPI- /4" x 2" x 24" 2 G2D0033TPI- /4" x 2" x 36" 33 G2D0044TPI- /4" x 2" x 48" 44 G2D0056TPI- /4" x 2" x 60" 56 usbar Type ICSI G2..series NEMA usbar Pattern D N 30 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

31 PHYSICAL INFRASTRUCTURE SYSTEMS Universal eam Grounding Clamp Universal, fits on a wide range of standard (angled) and wide flange (parallel) structural steel beams Provide a mounting pad suitable for a two-hole compression lug Install quickly and easily with standard /4" key hex wrench tooling Conductor Size Range Flange Thickness Stud Size Hole Spacing UL 467 Listed and CSA 22.2 Certified for grounding and bonding suitable for direct burial in earth or concrete Comply with vibration tests per MIL--202G (METHOD 20A) For the complete line of StructuredGround Direct urial Compression Grounding, visit Thread Size Length Width Height GUC500-6 # /2.75 / A. Auxiliary rackets and Jumpers onds ladder rack, wire basket and Panduit Wyr-Grid sections together without drilling holes Supports grounding conductors in the telecommunications room, allows separation of grounding conductors from other cables Holds up to four conductors in sizes up to 750 kcmil onds to all " and 2" ladder rack rails Paint piercing teeth provide electrical continuity between cable pathway sections while minimizing debris Front and back mounting screw options allow easy installation and visual inspection GAC-2 and GAC-3 can be mounted above or below the cable pathway system for flexibility rackets Meet TIA-607- W GAC GAC-2 GAC-3 Part Description GACJ68U Ctn. Auxiliary rackets GAC- Auxiliary cable bracket;.25" (3.8mm) width; 7.00" (77.8mm) height; 4.87" (23.7mm) depth; provided with one mounting screw. 0 GAC-2 Auxiliary cable bracket;.63" (4.4mm) width, 3.95" (00.3mm) height, 5.22" (32.6mm) depth; provided with one mounting screw. 0 H GAC-3 Auxiliary cable bracket;.88" (47.6mm) width, 4.58" (6.3mm) height, 5.29" (34.4mm) depth; provided with one mounting screw. 0 Jumper Kits D GACJ68U GACJ62U GACJ68U Auxiliary cable bracket jumper for bonding pathway sections; #6 (6mm²); 8.0" (203mm) length; factory terminated on both ends with straight, two-hole, long barrel compression lugs; provided with.6 oz. (5cc) of antioxidant and four mounting screws. Auxiliary cable bracket jumper for bonding pathway sections; #6 (6mm²); 2.0" (305mm) length; factory terminated on both ends with straight, two-hole, long barrel compression lugs; provided with.6 oz. (5cc) of antioxidant and four mounting screws. Auxiliary cable bracket jumper for bonding pathway sections; #6 (6mm²); 8.0" (457mm) length; factory terminated on both ends with straight, two-hole, long barrel compression lugs; provided with.6 oz. (5cc) of antioxidant and four mounting screws. For service and technical support, call (outside the U.S. and Canada, see back c). 3

32 A. D RATED PHYSICAL INFRASTRUCTURE SYSTEMS One-Hole Grounding Lay-In Lug Used for quick installation of a continuous grounding conductor UL 467 Listed for grounding and bonding, copper lugs UL Listed for direct burial in earth or concrete Tin-Plated Aluminum Set Screw Material UL Listed for use up to 600 V and temperature rated 90 C Wide wire range-taking capability minimizes inventory requirements Conductor Size Range Stud Hole Size Hex Key Size Length Width Height **Uses slotted head set screw. The use of Panduit oxide inhibiting joint compound (CMP) is recommended for pad to conductor connections. Refer to for more information. ody LICC4-22-C Stainless Steel #4 # ** Tin-Plated ody LICC4-22TP-C Stainless Steel #4 # ** Tin-Plated Aluminum ody LIAC4-22-C Stainless #4 # ** Steel LIAS/0-4-L Zinc Plated #4 / ** Steel LIAS Q Zinc Plated Steel #6 250 kcmil 0.33 / Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

33 PHYSICAL INFRASTRUCTURE SYSTEMS Ring Terminal, Vinyl Expanded Insulation Expanded wire entry designed to accommodate wire with a larger insulation thickness Ring tongue design assures a secure connection in high vibration applications Insulation support helps to prevent wire damage in bending applications razed seam protects terminal barrel from splitting during the crimp process L Internal barrel serrations assure good wire contact and maximum tensile strength UL Flammability UL 94V-0, maximum insulation temperature 22 F (05 C) UL and CSA rated up to 600 V per UL 486A/ A. C W Wire Range Color Max. Ins. Dia. Stud Size Length Width Clearance mm 2 Code mm mm mm mm mm Panduit Crimping Tool PV4-8RX-C #8 M PV4-0RX-C #0 M CT-00A, CT-600-A, PV4-4RX-L lue /4" M CT-550, PV4-56RX-L /6" M CT-55, CT-2500 PV4-38RX-L /8" M PV0-8RX-L #8 M PV0-0RX-L #0 M CT-00A, CT-600-A, PV0-4RX-L Yellow /4" M CT-550, PV0-56RX-L /6" M CT-55, CT-2500 PV0-38RX-L /8" M PV8-0RX-QY #0 M PV8-4RX-QY /4" M CT-720 with Die Insert PV8-56RX-QY CD-720PV8-2, Red /6" M CT-2600 with Die Insert PV8-38RX-QY /8" M CD-2600-PV Ctn PV8-2RX-XY /2" M PV6-0RX-X #0 M CT-720 with Die Insert PV6-4RX-X /4" M CD-720PV8-2, lue PV6-56RX-X /6" M CT-2600 with Die Insert 0 00 CD-2600-PV6 PV6-38RX-X /8" M PV4-4RX-E /4" M CT-720 with Die Insert PV4-56RX-E /6" M CD-720PV8-2, Yellow PV4-38RX-E /8" M CT-2600 with Die Insert CD-2600-PV4 PV4-2RX-E /2" M PV2-4RX-XY /4" M CT-720 with Die Insert PV2-56RX-XY /6" M CD-720PV8-2, Red PV2-38RX-XY /8" M CT-2600 with Die Insert 0 00 CD-2600-PV2 PV2-2RX-XY /2" M UL and CSA approved tooling/product combinations. For crimping tool information, see page 46. For the full selection of Panduit Crimping Tools see For service and technical support, call (outside the U.S. and Canada, see back c). 33

34 A. PHYSICAL INFRASTRUCTURE SYSTEMS Ring Terminal, Nylon Insulated Funnel Entry Ring tongue design assures a secure connection in high vibration applications Metal insulation grip sleeve crimps to wire insulation, providing protection to the crimp joint during high vibration applications L Internal barrel serrations assure good wire contact and maximum tensile strength UL Flammability UL 94V-2/H, maximum insulation temperature 22 F (05 C) UL and CSA rated up to 600 V per UL 486A/ C W Wire Range Color Max. Ins. Stud Size Length Width Clearance mm 2 Code mm mm mm mm mm PNF4-8R-C #8 M CT-00A, PNF4-0R-C #0 M CT-600-A, 6 4 PNF4-4R-C lue /4" M CT-550, CT-55, PNF4-56R-C /6" M CT-2500 PNF4-38R-L /8" M PNF0-8R-L #8 M CT-00A, PNF0-0R-L #0 M CT-600-A, 2 0 PNF0-4R-L Yellow /4" M CT-550, CT-55, PNF0-56R-L /6" M CT-2500 PNF0-38R-L /8" M UL and CSA approved tooling/product combinations. For crimping tool information, see page 46. For the full selection of Panduit Crimping Tools see Multiple Stud Terminal, Nylon Insulated Teardrop shaped mounting hole of multiple stud terminals permits use with #6, #8, or #0 size studs Ring tongue design assures a secure connection in high vibration applications Metal insulation grip sleeve crimps to wire insulation, providing protection to the crimp joint during high vibration applications L Panduit Crimping Tool Internal barrel serrations assure good wire contact and maximum tensile strength UL Flammability UL 94V-2/H, maximum insulation temperature 22 F (05 C) UL and CSA rated up to 600 V per UL 486A/ Ctn. C W Wire Range Color Max. Ins. Stud Size Length Width Clearance mm 2 Code mm mm mm mm mm PN4-60R-C 6 4 PN0-60R-L lue #6, #8, # Yellow #6, #8, #0 UL and CSA approved tooling/product combinations. For crimping tool information, see page 46. For the full selection of Panduit Crimping Tools see Panduit Crimping Tool M3.5 M CT-00A, CT-600-A, CT-550, CT-55, CT-2500, CT-400, CT-460 M3.5 M CT-00A, CT-600-A, CT-550, CT-55, CT-2500, CT Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL Ctn

35 PHYSICAL INFRASTRUCTURE SYSTEMS Ring Terminal, Non-Insulated Ring tongue design assures a secure connection in high vibration applications Internal barrel serrations assure good wire contact and maximum tensile strength razed seam protects terminal barrel from splitting during the crimp process arrel of terminal internally beveled to provide quick and easy wire insertion Maximum recommended operating temperature 302 F (50 C) UL and CSA rated up to 2000 V per UL 486A/, where applicable A. L C W P4-8R-C Wire Range UL and CSA approved tooling/product combinations. For crimping tool information, see page 46. For the full selection of Panduit Crimping Tools see Stud Size Length Width Clearance mm 2 mm mm mm mm #8 M Panduit Crimping Tool P4-0R-C #0 M CT-00A, P4-4R-C CT-200, 8 4 /4" M CT-600-A, P4-56R-C 5/6" M CT-570, P4-38R-C 3/8" M CT Ctn P4-2R-L /2" M P0-8R-L #8 M P0-0R-L #0 M CT-00A, CT-200, P0-4R-L 4 0 /4" M CT-600-A, P0-56R-L 5/6" M CT-570, P0-38R-L 3/8" M CT-70, CT P0-2R-L /2" M P8-0R-Q #0 M P8-4R-Q /4" M CT-70, P8-56R-Q /6" M CT-2600 with Die Insert P8-38R-Q 3/8" M CD P8-2R-Q /2" M P6-0R-E #0 M P6-4R-E /4" M CT-70, P6-56R-E /6" M CT-2600 with Die Insert P6-38R-E 3/8" M CD P6-2R-E /2" M P4-4R-E /4" M P4-56R-E 5/6" M CT-70, P4-38R-E CT-2600 with Die Insert 3/8" M CD P4-2R-E /2" M P2-4R-X /4" M P2-56R-X 5/6" M CT-70, 0 00 P2-38R-X CT-2600 with Die Insert 3/8" M CD P2-2R-X /2" M For service and technical support, call (outside the U.S. and Canada, see back c). 35

36 A. PHYSICAL INFRASTRUCTURE SYSTEMS Code Conductor, Two-Hole, Long arrel with Window Lug For Use with Stranded Conductors T W HOLE SPACING L INSPECTION WINDOW Figure : Straight Meets TIA-607- requirements for network systems grounding applications Tested by Telcordia meets NES Level 3 with conductor Requires crimping tools and dies, see pages UL Listed and CSA Certified with conductor for use up to 35 KV** and temperature rated 90 C when crimped with Panduit and specified competitor crimping tools and dies T W HOLE SPACING INSPECTION WINDOW Figure 2: 45 ent L 45 T W HOLE SPACING Color-coded barrels marked with Panduit and specified competitor die index numbers for proper crimp die selection Long barrel maximizes number of crimps and provides premium wire pull-out strength and electrical performance Inspection window to visually assure full conductor insertion Tin-plated to inhibit corrosion Available with NEMA hole sizes and spacing L 90 Figure 3: 90 ent INSPECTION WINDOW W HOLE SPACING L INSPECTION WINDOW T W HOLE SPACING INSPECTION WINDOW L 45 T W HOLE SPACING 90 INSPECTION WINDOW Figure 4: Slotted, Straight Figure 5: Slotted, 45 ent L Figure 6: Slotted, 90 ent Figure No. LCC0-4JAW-L* 4 Conductor Size Stud Hole Size Stud Hole Spacing Figure Dimensions W L / LCC0-4JAWH-L* LCC0-4JAWF-L* 5 6 #4 #0 STR, #2 #0 SOL /4 / LCC0-4AW-L* / LCC8-0AW-L # LCC8-4AWH-L 2 / #8 LCC8-4AWF-L 3 / LCC8-38DW-L 3/ See pages for Panduit and competitor tool and die information. *Not tested to NES Level 3 requirements. **Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000 V. ^See page 30 for busbar patterns. NEMA hole sizes and spacing. Panduit Crimping Tool CT-570, CT-70 CT-700, CT-930, Panduit Die Color and Die No. Wire Strip Length 9/6 Red P2 3/4 usbar Pattern^, D Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

37 Figure Conductor No. Size LCC6-0AW-L 4 PHYSICAL INFRASTRUCTURE SYSTEMS Code Conductor, Two-Hole, Long arrel with Window Lug (continued) Stud Hole Size Figure Dimensions Stud Hole Spacing W L # LCC6-4JAW-L 4 / LCC6-4JAWH-L 5 / LCC6-4JAWF-L 6 / #6 LCC6-4AW-L / LCC6-38DW-L 3/ See pages for Panduit and competitor tool and die information. *Not tested to NES Level 3 requirements. **Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000 V. ^See page 30 for busbar patterns. NEMA hole sizes and spacing. Panduit Crimping Tool CT-700, CT-930, Panduit Die Color and Die No. Wire Strip Length LCC6-2W-L / /8 LCC4-4AW-L LCC4-38DW-L #4 #3 STR, 3/ #2 LCC4-2W-L SOL / LCC2-4AW-Q / / LCC2-38DW-Q 3/ #2 LCC2-2W-Q / LCC/0-4AW-X / LCC/0-38DW-X 3/ /0 LCC/0-2W-X / LCC2/0-4AW-X / LCC2/0-38DW-X 3/ /0 LCC2/0-2W-X / LCC3/0-38DW-X 3/0 LCC3/0-2W-X / LCC4/0-38DW-X 3/ /0 LCC4/0-2W-X / LCC250-38DW-X 3/ / kcmil LCC250-2W-X / CT-700, CT-930, CT-700, CT-930, CT-930, CT-930, CT-930, CT-930, CT-930, lue P24 Gray P29 rown P33 Pink P42 lack P45 Orange P50 Purple P54 Yellow P62 /8 /8 usbar Pattern^ Table continues on page 38 For service and technical support, call (outside the U.S. and Canada, see back c)., D N, D /8 N /4 /2 9/6 9/6 5/8 /6, D N, D N, D N, D N N N, D N A. 37

38 A. PHYSICAL INFRASTRUCTURE SYSTEMS Code Conductor, Two-Hole, Long arrel with Window Lug (continued) Figure Conductor LCC350-2W-X No. Size Stud Stud Figure Dimensions Hole Hole Size Spacing W L / See pages for Panduit and competitor tool and die information. *Not tested to NES Level 3 requirements. **Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000 V. ^See page 30 for busbar patterns. NEMA hole sizes and spacing. Panduit Crimping Tool Panduit Die Color and Die No. Red LCC350-38DW-X 350 kcmil 3/ CT-930, P7 Red P7 LCC400-2W-6 / lue CT-930, P kcmil LCC400-38DW-6 3/ lue P76 LCC500-2W-6 / rown CT-930, P kcmil LCC500-38DW-6 3/ rown P87 LCC600-2W-6 / Green CT-930, P kcmil LCC600-38DW-6 3/ Green P94 LCC750-2W-6 / lack CT-930, P kcmil LCC750-38DW-6 3/ lack P06 Wire Strip Length 2 5/6 2 3/8 2 9/6 2 3/4 2 5/6 usbar Pattern^ N 0, D 0 N 6, D 6 N 6, D 6 N 6, D 6 N 6, D 6 38 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

39 PHYSICAL INFRASTRUCTURE SYSTEMS Flex Conductor, Two-Hole, Long arrel with Window Lug For Use with Flexible, Extra-Flexible, and Code Stranded Conductors T W HOLE SPACING L INSPECTION WINDOW Figure : Straight Fig. No. LCCX8-4A-L Flex Conductor Size Class G,H, I, K, M Meets TIA-607- requirements for network systems grounding applications Requires crimping tools and dies, see pages UL Listed and CSA Certified with conductor for use up to 35 KV** and temperature rated 90 C when crimped with Panduit and specified competitor crimping tools and dies Color-coded barrels marked with Panduit and specified competitor die index numbers for proper crimp die selection T W HOLE SPACING INSPECTION WINDOW Figure 2: 45 ent See pages 54 and 55 for Panduit and competitor tool and die information. **Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000 V. ^See page 30 for busbar patterns. NEMA hole sizes and spacing. L 45 T W Can be used with code conductor and flex conductor class: G, H, I,K, M and Diesel Locomotive Long barrel maximizes number of crimps and provides premium wire pull-out strength and electrical performance Inspection window to visually assure full conductor insertion Generously beveled wire entry prevents bent back strands when inserting conductor into barrel Tin-plated to inhibit corrosion Available with NEMA hole sizes and spacing HOLE SPACING Diesel Locomotive Code Conductor Size Stud Hole Size Stud Hole Spacing W L 90 Figure Dimensions / L Figure 3: 90 ent INSPECTION WINDOW Panduit Crimping Tool Panduit Die Color & Die No. Wire Strip Length usbar Pattern^ LCCX8-4AH-L 2 / CT-700, CT-930, Red #8 #8 #8 3/4 LCCX8-4AF-L 3 / P2 50 LCCX8-38D-L 3/ LCCX6-4A-L / LCCX6-4AH-L 2 / CT-700, CT-930, lue #6 #6 #6 /8 LCCX6-4AF-L 3 / P24 50 LCCX6-38D-L 3/ , D, D A. Table continues on page 40 For service and technical support, call (outside the U.S. and Canada, see back c). 39

40 A. PHYSICAL INFRASTRUCTURE SYSTEMS Flex Conductor, Two-Hole, Long arrel with Window Lug (continued) Fig. No. LCCX4-4A-L Flex Conductor Size Class G,H, I, K, M Diesel Locomotive Code Conductor Size Stud Hole Size Stud Hole Spacing Figure Dimensions #5, #4, #3 #4 #4 LCCX4-38D-L 3/ LCCX2-4A-E W / / LCCX2-38D-E 3/ #2 #2 #2 LCCX2-2-E / LCCX/0-4A-X / LCCX/0-38D-X 3/ /0 /0 /0 LCCX/0-2-X / L Panduit Crimping Tool CT-700, CT-930, CT-700, CT-930, CT-930, Panduit Die Color & Die No. Gray P29 rown P33 Pink P42 Wire Strip Length /8 7/6 9/6 usbar Pattern^, D, D N, D N /0 4/0 LCCX4/0-2-X 4/0 / LCCX2/0-4A-X / LCCX2/0-38D-X 3/ /0 2/0 2/0 LCCX2/0-2-X / See pages 54 and 55 for Panduit and competitor tool and die information. **Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000 V. ^See page 30 for busbar patterns. NEMA hole sizes and spacing. CT-930, LCCX3/0-38D-X 3/0 3/0 3/0 3/ CT-930, LCCX4/0-38D-X LCCX250-38D-X 250 kcmil LCCX kcmil LCCX350-38D kcmil LCCX kcmil LCCX450-38D kcmil LCCX kcmil LCCX500-38D kcmil 4/0 3/ CT kcmil 3/ CT-930, kcmil / CT-930, kcmil 3/ CT-930, kcmil / CT-930, kcmil 3/ CT-930, kcmil / CT-930, kcmil 3/ CT-930, LCCX kcmil / CT-930, lack P45 Orange P50 Purple P54 Yellow P62 lue P76 lue P76 rown P87 rown P87 Pink P99 Pink P99 lack P06 9/6 5/8 2 5/6 2 5/6, D N, D, D N, D /6 N 6 2 9/6, D 6 2 3/4 N 6 2 3/4, D 6 2 5/6 2 5/6 N 6, D N 6 40 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

41 PHYSICAL INFRASTRUCTURE SYSTEMS A. HTAP Code/Flex Conductor HTAP RUN Used to tap into continuous conductors as a splice or pigtailing Each HTAP terminates a wide range of conductor sizes and combinations of code and flex conductors Class G, H, I and Locomotive to suit a variety of applications Slotted design allows quick and easy assembly of conductor to HTAP using three Panduit 94V-0 cable ties included Tap grooves are separated from one another allowing them to function independently so HTAP can be used with a single or multiple taps providing maximum design and installation flexibility Color coded and marked with Panduit die index numbers for proper crimp die selection Requires crimping tools and dies, see pages UL Listed and CSA Certified with conductor for applications up to 600 V when crimped with Panduit and specified competitor crimping tools and Panduit crimping dies Tin plated to inhibit corrosion TAP RUN H W L RUN H W L RUN H W L RUN H W L TAP HTCT6X-6X TAP 2 TAP HTCT2-2 TAP 3 TAP TAP 2 TAP HTCT250-2 HTCT HTCT6X-6X- HTCT2-2- HTCT Conductor Size Range See page 58 for Panduit and competitor tool and die information. Figure Dimensions Wire Strand Type Run Tap Tap 2 Tap 3 L W H Code Flex Code Flex Code Flex #6 #4 #6 #4 #2 #6 STR/SOL #6 #4 #6 #4 #2 #6 STR/SOL #8 #4 #2 #8 #2 #8 #8 #4 250 kcmil #2 4/0 #2 HTCT Code 250 kcmil #2 Flex 4/0 #2 #2 #6 STR/SOL #8 #4 #2 #8 #8 #4 250 kcmil #2 4/0 #2 #8 #4 #8 #4 Panduit Crimping Tool CT-930, CT-930, CT-930, CT-930, Panduit Die Color & Die No. Orange PH6 rown PH2 Purple PH25 Purple PH25 Wire Strip Length /6 3/6 For service and technical support, call (outside the U.S. and Canada, see back c). 4

42 A. PHYSICAL INFRASTRUCTURE SYSTEMS Clear Cs for HTCT HTAPs Made of high impact plastic to provide high impact strength and 360 inspections of crimped connection to assure the crimp is complete and the correct die was used Incorporate dual self-latching spring loaded latches and supplied with two Panduit UL 94V-0 cable ties to allow for easy snap-on assembly and ensure cs are secured Low profile design minimizes space requirements Each c half supports installation information labels inside plastic retainer strips to allow labels to be viewed on either side of c and to protect labels from being removed Incorporate molded in flash barriers which encompass the HTAP installation providing protection against electrical flash UL 94V-0 flame rating and oxygen index of 28 providing self-extinguishing, flame retardant properties Part number, voltage rating, temperature rating and HTCT part number molded into c for easy identification Flexible fingers located at each end of c prevent foreign objects from entering c and are made from ductile plastic material that allows easy installation and will not damage conductor insulation Figure Dimensions Use With HTAP L W H CLRCVR- HTCT6X-6X CLRCVR2- HTCT CLRCVR3- HTCT250-2-, HTCT Labels for clear cs are sold separately and are printed with the Panduit PanTher LS8E Hand-Held Thermal Transfer Printer, see pages 25. H L W Shown Assembled Code/Flex Conductor HTAP Kits HTAP Part No. Components Clear C Part No. HTWC6X-6X- HTCT6X-6X- CLRCVR- HTWC2-2- HTCT2-2- CLRCVR2- HTWC HTCT CLRCVR3- HTWC HTCT CLRCVR3-42 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

43 T PHYSICAL INFRASTRUCTURE SYSTEMS Code Conductor, Thin Wall, Tin-Plated, CTAPF L For copper-to-copper tapping splicing or pigtailing Wide wire range-taking capability minimizes inventory requirements Color-coded for proper crimp die selection Ribbed design provides high strength Made from high conductivity wrought copper Tin-plated to inhibit corrosion and oxidation UL Listed and CSA Certified with conductor to 600 V and temperature rated to 90 C when crimped with Panduit and specified competitor crimping tools and dies A. V Q Conductor Size Number Figure Dimensions Run Tap of Ribs L T V Q CTAPF4-2TP-C #6 #8 #6 #5, #4 #2 # Panduit Crimping Tool CT-700, CT-930, Panduit Color Code Wire Strip Length rown 5/6 00 CTAPF/0-2TP-L #2 #4 #2 # #4 #3 /0 #2 #4 CTAPF2/0-2TP-Q # #2 # CT-930, Orange 7/8 50 /0 #3 #2 2/0 #2 # CT-930, Purple 7/8 25 See pages for Panduit and competitor tool and die information. For service and technical support, call (outside the U.S. and Canada, see back c). 43

44 A. D RATED PHYSICAL INFRASTRUCTURE SYSTEMS Grounding Clamp, U-olt, ronze Used to ground copper conductor parallel or at a right angle to a rod, tube, or pipe Made from high strength, electrolytic cast bronze High strength silicon bronze hardware provides long term reliable assembly Accommodates a wide range of pipe, tube, rod and conductor sizes minimizes inventory UL Listed for grounding and bonding with conductor and suitable for direct burial in earth or concrete H W L Ground Rod Size Iron Pipe Size Conductor Size Range Figure Dimensions L W H GPL-8-Q 7/8 or /2 or 3/4 #8 SOL #4 STR /8 9/6 25 GPL-4-X olt Dia. Hex Size #8 SOL #4 STR /8 9/6 0 GPL-5-X GPL-6-X #4 SOL 2/0 STR /8 9/6 0 2/0 SOL 250 kcmil /8 9/6 0 GPL-22-X GPL-28-X /4 2/0 SOL 250 kcmil /8 9/6 0 /2 2/0 SOL 250 kcmil /8 9/6 0 GPL /0 SOL 250 kcmil /8 9/6 3 Grounding Clamp for Water Pipes, ronze Used to ground copper code conductor to water pipe or copper tube Cast from high strength, electrolytic bronze to provide reliable grounding connections Plated steel screws provide high strength and inhibit corrosion Accommodates a wide range of pipe, tube, rod and conductor sizes minimizes inventory UL Listed for grounding and bonding with conductor and suitable for direct burial in earth or concrete L W Water Pipe Range Conductor Size Range Figure Dimensions KP-C /2 #0 SOL #2 STR KP2-L /4 2 #0 SOL #2 STR L W 44 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

45 PHYSICAL INFRASTRUCTURE SYSTEMS Grounding Clamp for Water Pipes, Aluminum Dual-rated for grounding aluminum or copper code conductors to copper water pipe, galvanized pipe, or steel conduit Made from high strength, extruded aluminum alloy to provide long term durability Tin-plated to inhibit corrosion and oxidation and for low contact resistance Water Pipe Range Plated steel screws provide high strength and inhibit corrosion Accommodates a wide range of pipe, tube, and conductor sizes minimizes inventory requirements UL Listed and CSA Certified for grounding and bonding Conductor Size Range Figure Dimensions L W GC-5A-Q /2 3/4 # /0 GC-8A-X /4 /2 2 #6 250 kcmil A. GC-22A-4 2 /2 3 3 /2 4 #6 250 kcmil L W Split olt, Made from high strength copper alloy to resist corrosion and provide premium electrical and mechanical performance Wire range-taking capability minimizes inventory requirements Nut hex provides correct fit with socket, box, or open end wrenches resulting in proper torquing of electrical connection E Pressure bar provides secure connection on a full range of conductor combinations used with each connector assuring premium wire pull-out strength UL Listed and CSA Certified with conductor for use up to 600 V and temperature rated 90 C SCT3-C is tin-plated for bonding to galvanized wire baskets L SC3-C SCT3-C Tin-Plated W Conductor Figure Range of Equal Run and Tap Min. Tap with Dimensions One Max. Run Min. Max. E W L UL Listed and CSA Certified with Code Conductors SC3-C #8 STR #4 STR #4 STR UL Listed and CSA Certified with and Aluminum Code Conductors SCT3-C* #8 STR #4 STR #0 STR *The use of Panduit oxide inhibiting joint compound (CMP-00) is recommended. Refer to for more information. For service and technical support, call (outside the U.S. and Canada, see back c). 45

46 A. PHYSICAL INFRASTRUCTURE SYSTEMS Hand Operated Plier Type Tools Installer controlled crimp Available with wire stripping and cutting features Plier type crimp for #22 thru 0 insulated and non-insulated terminal products CT-00A Part Description Crimps most Panduit #22 0 insulated and non-insulated terminals, disconnects, and splices. Crimps 4mm² 6mm² copper metric lugs. Cuts #4, #6, #8 and #0 screw sizes. Cuts and strips wire. Excellent all-around application tool of heat treated finished steel with comfortable cushioned plastic grip handles. Contour Crimp Controlled Cycle Tools Controlled cycle mechanism assures high quality, consistent terminations Ergonomic tool design assures operator comfort, safety, and performance Polypropylene, elastomeric handles provide chemical resistance and a cushioned, non-slip grip CT-550 CT-570 CT- 700 Part Description CT-550 Crimps most Pan-Term #22 0 nylon and vinyl insulated terminals, splices, and disconnects. The CT-550 has the red/blue pocket closest to the pivot which provides a reduced crimp effort for those who make red/blue terminations. CT-570 Crimps most Pan-Term #22 0 and.5 6.0mm² non-insulated terminals and disconnects. Crimps Panduit #22 0 and.5 6.0mm² non-insulated splices, #4 #0 copper code conductor lugs, and 4mm² 6mm² copper metric lugs. CT-700 CT-70 Crimps Panduit #8 2 non-insulated tubular terminals (S series), #8 copper code conductor lugs and splices, #8 2 copper flex conductor lugs, #6 4 dual rated aluminum lugs and splices and CTAPF0-6 to CTAPF3-2 copper taps. Includes 5-position, color coded rotating die. Crimps Panduit #0 2 non-insulated large gauge ring terminals (P series), #2 4 non-insulated heavy duty ring terminals (P series), #4 0 copper code conductor lugs, and 4mm² 6mm² copper metric lugs. Includes 5-position, rotating die. CT Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

47 PHYSICAL INFRASTRUCTURE SYSTEMS Die Type, Manual Hydraulic, 4 Ton, Crimping Tool Two-stage rapid advance hydraulic system minimizes number of pumps required to complete a crimp saves time Cushioned grip prevents hands from slipping on tool reduces fatigue Provides UL Listed and CSA Certified connections on Panduit copper and aluminum lugs and splices and copper taps Open "C-Head" design allows easy loading of crimping dies and connectors, saves time Requires crimping dies, see page 49 Dies installed using spring loaded die retention pins, no need for tools Rubber boot on crimp head provides abrasion protection Audible "pop-off" valve indicates crimp completion Crimp head rotates 80, provides versatility for use in restricted spaces A. CT-930 Terminates Panduit Compression Connectors: Part Description compression lugs and splices for #8 750 kcmil code conductor compression lugs and splices for #8 600 kcmil flex conductor compression lugs and splices for 0mm² 400mm² Class 2r metric conductor compression lugs and splices for 0mm² 300mm² Class 5f and 0mm² 240mm² Class 6f metric conductor StructuredGround Direct urial Compression Grounding Connectors for #6 250 kcmil code conductor and select 500 kcmil conductor combinations compression CTAPF taps for #0 3/0 code conductor compression CTAP taps for #8 4/0 code conductor compression HTCT taps for #4 250 kcmil code conductor, #4 4/0 flex conductor Aluminum compression lugs and splices for #6 600 kcmil code conductor Panduit Pan-Term Tubular Terminals for #8 250 kcmil code conductor Specifications: Output: 4 tons Jaw opening:.65" Weight: 6.5 lbs. Length: 25" Handle span: 7 /2" (open), 6" (closed) Warranty: 5 years CT-930 includes: Tool Plastic tool case with die storage Compatible with CD-920 and CD-930 crimping dies, sold separately, see page For service and technical support, call (outside the U.S. and Canada, see back c). 47

48 A. PHYSICAL INFRASTRUCTURE SYSTEMS Die Type, Lithium-Ion ed Hydraulic, 4 Ton, Crimping Tool Lithium-Ion battery powered, provides fingertip operation and up to 7.5% more crimps per battery charge than tools powered with NiCd or NiMH batteries Pistol grip tool design with open "C-Head" provides easy loading of crimping dies and rotates 80, for reaching into tight spaces Provides UL Listed and CSA Certified connections on Panduit copper and aluminum lugs and splices and copper taps Tool provided with two, Milwaukee M8 XC high capacity RED lithium-ion 8VDC rechargeable batteries, battery charger and shoulder strap atteries incorporate LED fuel gage so battery charge level can be checked to allow for continuous operation Approximately 9.6 second crimp cycle time provides quick terminations, 30% faster than tools using NiCd or NiMH batteries attery charger charges expended batteries completely in 60 minutes Requires crimping dies, see page 49 Dies installed using spring loaded die retention pins, no need for tools Tool provided with heavy-duty, soft sided tool bag with 58 pockets for storing tool, batteries, charger, dies, etc. CT-2930/L and FREE! Heavy-Duty Soft Sided Tool ag Included Charger Voltage Part Description CT-2930/L 20 VAC 230 VAC Terminates Panduit compression connectors: compression lugs and splices for #8 750 kcmil code conductor compression lugs for #8 600 kcmil flex conductor compression S Series, Pan-Term Tubular Terminals for #8 250 kcmil code conductor compression lugs and splices for 0mm² 400mm² Class 2r conductor compression lugs and splices for 0mm² 300mm² Class 5f conductor and 0mm² 240mm² Class 6f conductor StructuredGround Direct urial Compression Grounding connectors #6 250 kcmil code conductor and select 500 kcmil conductor combinations compression CTAPF taps for #0 3/0 code conductor compression CTAP taps for #8 4/0 code conductor compression HTCT taps for #4 250 kcmil code conductor, #4-4/0 flex conductor Aluminum compression lugs and splices for #6 600 kcmil code conductor Specifications: Output: 4 tons (24.5 Kn) Jaw opening:.65" (4.9mm) Weight: 7.90 lbs. (8. kg) with battery Length: 4.5" (368.3mm), Height: 6.5" (49.mm), Width: 3.25" (82.6mm) Warranty: 5 years on tool, batteries and charger Tool includes: Two Milwaukee M8 XC high capacity RED lithium-ion 8VDC rechargeable batteries One Milwaukee battery charger One shoulder strap Heavy-duty bag with storage for tool, batteries, charger, and crimping dies; includes 58 pockets and a shoulder strap for added convenience; 8"L x 7"W x 4"H* Compatible with CD-920, CDM-920, and CD-930 crimping dies, sold separately, see page 49. Tool bag also sold separately, see part number PT-GP on 48 Order number of pieces required, in multiples of Standard Package Quantity. Prime items appear in OL

49 CD-920 Crimping Dies Crimping dies and connectors are color-coded for easy matching Emboss die index number on connector barrels for post crimp inspection Part number permanently marked on crimping die for easy identification Die Color PHYSICAL INFRASTRUCTURE SYSTEMS Provide circumferential crimp results in terminations with premium electrical and mechanical performance Used in Panduit crimping tools; see the CT-930 crimping tool on page 47 and the CT-2930/L and crimping tools on page 48 A. Die Number Patented Locator HTAP Die with Patented Locator CD-920 CD-930H CDM Used to Install Panduit Compression Lug and Splice Sizes Code Conductor Size and Die Color and Die No. Single Crimp Dies CD #8, Red P2 CD #6, lue P24 CD #4, Gray P29 CD #2, rown P33 CD-920- #, Green P37 CD-920-/0 /0, Pink P42 CD-920-2/0 2/0, lack P45 CD-920-3/0 3/0, Orange P50 CD-920-4/0 4/0, Purple P54 CD kcmil, Yellow P62 CD kcmil, Red P7 CD kcmil, lue P76 CD kcmil, rown P87 CD A 500 kcmil, Pink P99 CD kcmil, Green P94 CD kcmil, lack P06 Used to Install Panduit HTAP s HTAP and Die Color and Die No. Single Crimp Dies with Patented Locator CD-920H-6 HTCT6X-6X-, Orange PH6 CD-920H-2 HTCT2-2-, rown PH2 CD-930H-250 HTCT250-2-, HTCT , Purple PH25 Used to Install Panduit CTAPF s CTAPF and Die Color and Die No. Multi-Crimp Dies CDM CTAPF4, rown P33M CDM-920-3/0 CTAPF/0, Orange P50M CDM-920-4/0 CTAPF2/0, Purple P54M For service and technical support, call (outside the U.S. and Canada, see back c). 49

StructuredGround Direct Burial Compression Grounding System

StructuredGround Direct Burial Compression Grounding System StructuredGround Direct urial Compression Grounding System The StructuredGround Direct urial Compression Grounding System provides the highest performance and most reliable compression connection in the

More information

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cabinets, Racks, Frames and Enclosures

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cabinets, Racks, Frames and Enclosures PART 1 GENERAL 1.1 WORK INCLUDED Section 27 11 00 COMMUNICATION EQUIPMENT ROOM FITTINGS Section 27 11 16 Communications Cabinets, Racks, Frames and Enclosures A. Provide all labor, materials, and equipment

More information

HBBBxxxx Busbars. None. HGBL: Lugs HYG14B: Busbar Taps HGRKT: Ground Kits HPENE: Penetrox anti oxidant

HBBBxxxx Busbars. None. HGBL: Lugs HYG14B: Busbar Taps HGRKT: Ground Kits HPENE: Penetrox anti oxidant HBBBxxxx Busbars Product Launch Summary * * INTERNAL USE ONLY * * Date: 01/23/2012 Copper Busbars are used in the Service Entrance, Telecommunications Room, Data Center, and on Equipment Racks. All busbar

More information

Industrial Automation Enclosure

Industrial Automation Enclosure Industrial Automation Enclosure Part Number: IAEIP66, IAEFK54 Panduit Corp. 2004 INSTALLATION INSTRUCTIONS Important Notice: Should Fan Kit P/N IAEFK54 be integrated into the enclosure, P/N IAEIP66, the

More information

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Installing the Cisco ONS FAP-4 Fuse Alarm Panel Installing the Cisco ONS 15454-FAP-4 Fuse Alarm Panel Product Number: 15454-FAP-4= This document explains how to install, test, operate, and maintain the Cisco ONS 15454-FAP-4 fuse alarm panel. This document

More information

6U Wall-Mount Server Rack Cabinet - Up to 14.8 in. Deep

6U Wall-Mount Server Rack Cabinet - Up to 14.8 in. Deep 6U Wall-Mount Server Rack Cabinet - Up to 14.8 in. Deep Product ID: RK616WALM This 6U server rack cabinet lets you mount your EIA-310 compliant equipment to the wall. The enclosure features a mounting

More information

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY TABLE OF CONTENTS Warnings...3 Package Contents...3 General Information...3 Supply Ducting And Registers...3 Routing 115 VAC Wiring...5

More information

8U Vertical Server Cabinet - 30 in. depth

8U Vertical Server Cabinet - 30 in. depth 8U Vertical Server Cabinet - 30 in. depth Product ID: RK830WALVS This 8U vertical server cabinet offers a space-saving way to keep your network and server equipment secure. With its 30 in. depth, and a

More information

FLUSH MOUNT INSTALLATION MANUAL

FLUSH MOUNT INSTALLATION MANUAL FLUSH MOUNT INSTALLATION MANUAL CONTENTS DISCLAIMER 1 RATINGS 2 MARKINGS 2 CHECKLIST 3 1. ATTACH BASES 4 2. PLACE RAILS 4 3. SECURE LUGS 5 4. SECURE MODULES 5 EXPANSION JOINTS 6 ELECTRICAL DIAGRAM 6 FLASHFOOT

More information

SWITCHING SWITCHING. Overhead Electric Distribution Standards INTRODUCTION

SWITCHING SWITCHING. Overhead Electric Distribution Standards INTRODUCTION INTRODUCTION 1. All group-operated switches installed shall be load-break. The interrupters are now included with the plates and no longer need to be itemized as in the past. The identification plates

More information

Installation Manual. Model 200QF 8/8 Model 200QF 8/ DC Edge III

Installation Manual. Model 200QF 8/8 Model 200QF 8/ DC Edge III Installation Manual Model 200QF 8/8 Model 200QF 8/8 +24 DC Edge III Model 200QF 8/8 +24; Model 200QF 8/8 Part# 1101-1006 (Positive Polarity); 1101-1051 (Negative Polarity) Installation Manual DC Edge III

More information

Band Heaters W A T L O W. Special Mica Barrel and Nozzle

Band Heaters W A T L O W. Special Mica Barrel and Nozzle W A T L O W For over 80 years, Watlow has been solving complex and unique application problems with standard mica barrel and nozzle heaters. Watlow is continuously improving design and application knowledge

More information

Standard Downrod for ceilings 8-10 feet high. Longer Downrod for ceilings 10 feet or higher

Standard Downrod for ceilings 8-10 feet high. Longer Downrod for ceilings 10 feet or higher Table of Contents www.casablancafanco.com To register your fan, please visit: www.casablancafanco.com/register What to Expect with Your Installation Save your receipt for proof of purchase. Ceiling Bracket??

More information

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters 1200 North Main Street Fostoria, OH 44830 Phone: 800-495-4525 Fax: 419-435-0842 A DIVISION OF www.fostoriaindustries.com OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters *EXCLUDING

More information

Installation and Maintenance Manual IM 1038

Installation and Maintenance Manual IM 1038 Installation and Maintenance Manual IM 1038 BACnet VAV Actuator Room Sensor Group: Controls Part Number: IM 1038 Date: March 2010 Models 2508031 and 2508032 Table of Contents Introduction.... 2 Revision

More information

J-PRO TM Cable Support System

J-PRO TM Cable Support System Frequently Asked Questions Cable Support System What references define how and where J-hooks are used? J-hooks are a horizontal pathway promoted in the BICSI TDM manual as a means to route small to medium

More information

Heat Exchanger Block Replacement Instructions

Heat Exchanger Block Replacement Instructions Series 1-4 Gas-fired water boiler Heat Exchanger Block Replacement Instructions Ultra-80 S1-4 Heat Exchanger Block Replacement Kit, Part No. 383-500-773 Ultra-105 S1-4 Heat Exchanger Block Replacement

More information

Universal Connectivity Platform A Modular Approach to Infrastructure Design

Universal Connectivity Platform A Modular Approach to Infrastructure Design A Modular Approach to Infrastructure Design TE Connectivity s Universal Connectivity Platform (UCP) provides a fully modular approach to designing data centers and telecommunications rooms. This patch

More information

INSTALLATION GUIDE KT-CDR2 & KT-CDR3. For COOLDOME ENCLOSURE SERIES

INSTALLATION GUIDE KT-CDR2 & KT-CDR3. For COOLDOME ENCLOSURE SERIES INSTALLATION GUIDE KT-CDR2 & KT-CDR3 Including Mounting & Sealing of Housing & Electrical Details For COOLDOME ENCLOSURE SERIES KT-CDR2 For D2 COOLDOME KT-CDR3 For D3 COOLDOME PRODUCT INSTALLATION PRECAUTIONS

More information

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels Installation Instructions For the 18 Built-In Dishwasher and Front Color Panels Printed in USA 154232102 Before You Begin DO NOT INSTALL DISHWASHER UNTIL YOU HAVE READ ALL INSTRUCTIONS. FOR YOUR SAFETY,

More information

Table of Contents. What to Expect with. Mounting Options. Tools Needed

Table of Contents.   What to Expect with. Mounting Options. Tools Needed Table of Contents www.hunterfan.com What to Expect with Your Installation Congratulations on purchasing your new Hunter ceiling fan! It will provide comfort and performance in your home or office for many

More information

Room Sensor for BACnet VAV Actuator

Room Sensor for BACnet VAV Actuator BACnet VAV Actuator Room Sensor Installation Manual IM 1038 Group: Controls Part Number: IM 1038 Date: 3/4/2010 Supersedes: New Room Sensor for BACnet VAV Actuator Model(s): 2508031 & 2508032 2010 McQuay

More information

Roof Mounting System. Installation Manual. Standard (XRS) and Light (XRL) Rails with Integrated Grounding *ETL Listed Per UL Edition v1.

Roof Mounting System. Installation Manual. Standard (XRS) and Light (XRL) Rails with Integrated Grounding *ETL Listed Per UL Edition v1. Roof Mounting System Standard (XRS) and Light (XRL) *ETL Listed Per UL2703 2013 Edition v1.1 A complete manual for the installation of IronRidge s rail systems with integrated grounding. This Installation

More information

Installation Instructions

Installation Instructions GE Consumer & Industrial Appliances Installation Instructions Junction Box Cover Within this user bag, you will find a junction box cover and a #10 hex head screw used to attach the junction box cover

More information

Installation Instructions 30 French Door Built-in Wall Ovens

Installation Instructions 30 French Door Built-in Wall Ovens Installation Instructions 30 French Door Built-in Wall Ovens Questions? Call 1.800.GE.CARES (1.800.432.2737) or visit www.geappliances.com In Canada, call 1.800.561.3344 or visit www.geappliances.ca DESIGN

More information

INSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM

INSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM INSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM TABLE OF CONTENTS Warnings...2 Package Contents...2 General Information...3 Ceiling Plenum Installation Requirement...3 Supply Ducting

More information

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT RV Products Division INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330A755 CONTROL BOX KIT (12 VDC HEAT/COOL) 8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)

More information

READ ALL DIRECTIONS CAREFULLY BEFORE BEGINNING INSTALLATION

READ ALL DIRECTIONS CAREFULLY BEFORE BEGINNING INSTALLATION INSTRUCTIONS AND REPAIR PARTS LIST CQB20 CHICK AND QUAIL BROODER CGO20 GROW-OUT PEN READ ALL DIRECTIONS CAREFULLY BEFORE BEGINNING INSTALLATION TOOLS REQUIRED: Straight Blade Screwdriver, Phillips Head

More information

Built-In Dishwasher. Installation Instructions. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT The dishwasher MUST be

Built-In Dishwasher. Installation Instructions. BEFORE YOU BEGIN Read these instructions completely and carefully. IMPORTANT The dishwasher MUST be Installation Instructions Built-In Dishwasher If you have questions, call 800.GE.CARES (800.432.2737) or visit our website at: www.ge.com BEFORE YOU BEGIN Read these instructions completely and carefully.

More information

EHT/EHTD. Electromechanical Closer-Holder Release Devices

EHT/EHTD. Electromechanical Closer-Holder Release Devices 351 EHT/EHTD Electromechanical Closer-Holder Release Devices Copyright 2003-2009, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved. Table of Contents Table of Contents Page

More information

Universal Connectivity Platform

Universal Connectivity Platform Enabling Business Transformation through Agility Availability Efficiency UCP provides a fully modular approach to accommodate both copper and fiber into one common footprint, simplifying network architecture

More information

You work hard on your panel. we work hard in your panel. PRODUCTS FOR

You work hard on your panel. we work hard in your panel. PRODUCTS FOR You work hard on your panel we work hard in your panel. PRODUCTS FOR 2 PRODUCTS FOR You simply won t find better panel components. Thomas & Betts has everything you need to make your panel better than

More information

wholesalesolar.com Table of Contents 1. Racking Layout Options (page 2-3) 2. IronRidge Roof Mounting System (page 4-12)

wholesalesolar.com Table of Contents 1. Racking Layout Options (page 2-3) 2. IronRidge Roof Mounting System (page 4-12) wholesalesolar.com Table of Contents 1. Racking Layout Options (page 2-3) 2. IronRidge Roof Mounting System (page 4-12) 3. WEEB Installation Instructions (page 13-24) Page 1 RACKING LAYOUT OPTIONS MID

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS BUILT-IN BOTTOM MOUNT REFRIGERATOR/FREEZER DBRTGK72SS-GRILLE KIT (FOR designer SERIES ONLY) VIKING RANGE CORPORATION 111 Front Street Greenwood, Mississippi (MS) 38930 USA (662)

More information

2408/2900. Fire Guard

2408/2900. Fire Guard 2408/2900 Fire Guard Table of Contents Features and Additional Fire Opening Devices... 1 2408 Single-Point Hold Open Applications and Mounting Details... 2 2408 Track Assemblies, Arms and Components...

More information

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions. Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Dryer. User manual DV22K6800** DV22K A-00_EN (US)_ indd :15:41

Dryer. User manual DV22K6800** DV22K A-00_EN (US)_ indd :15:41 Dryer User manual DV22K6800** DV22K6800-03650A-00_EN (US)_151211.indd 1 2015-12-11 7:15:41 Before installation Read through the following instructions before installing the dryer, and keep this manual

More information

Vertical Wall-Mount Server Rack - Solid Steel - 6U

Vertical Wall-Mount Server Rack - Solid Steel - 6U Vertical Wall-Mount Server Rack - Solid Steel - 6U Product ID: RK619WALLV This wall-mount bracket provides 6U of storage space to vertically mount your equipment on the wall. The 6U wall-mount rack is

More information

2409/2900. Fire Guard

2409/2900. Fire Guard 2409/2900 Fire Guard Table of Contents Features and Additional Fire Opening Devices... 1 2409 Single-Point Hold Open Applications and Mounting Details... 2 2409 Track Assemblies, Arms and Components...

More information

DAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz

DAGNY LK. Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 110V~60Hz DAGNY LK Ceiling Mounted Rotational Fan READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 110V~60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any

More information

Installation Guide. Model: IC15- MF Model: IC15- MFSilent Model: IC30- MF Model: IC30- MFSilent

Installation Guide. Model: IC15- MF Model: IC15- MFSilent Model: IC30- MF Model: IC30- MFSilent Installation Guide Model: IC15- MF Model: IC15- MFSilent Model: IC30- MF Model: IC30- MFSilent IMPORTANT SAFETY INFORMATION READ AND SAVE THESE INSTRUCTIONS WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC

More information

Owner s Guide and Installation Manual

Owner s Guide and Installation Manual Tribeca Owner s Guide and Installation Manual English Form# M6000-01 20120416 2012 Casablanca Fan Co. Welcome Your new Casablanca ceiling fan is an addition to your home or office that will provide comfort

More information

2408/2900. Fire Guard. SARGENT Manufacturing Company 2004, 2007 All rights reserved

2408/2900. Fire Guard. SARGENT Manufacturing Company 2004, 2007 All rights reserved Fire Guard SARGENT Manufacturing Company 2004, 2007 All rights reserved Fire Guard Table of Contents Features and Additional Fire Opening Devices............................1 2408 Single-Point Hold Open

More information

Installation Instructions Built-In Dishwasher

Installation Instructions Built-In Dishwasher GE Consumer & Industrial Appliances Installation Instructions Built-In Dishwasher If you have questions, call 800.GE.CARES (800.432.2737) or visit our website at: www.ge.com BEFORE YOU BEGIN Read these

More information

Please read the following installation instructions first after purchasing this product or transporting it to another location.

Please read the following installation instructions first after purchasing this product or transporting it to another location. 9 Installation Overview Please read the following installation instructions first after purchasing this product or transporting it to another location. 1 Unpacking your refrigerator 2 Choosing the proper

More information

Table of Contents. What to Expect with. Tools Needed. Mounting Options. Blades

Table of Contents.   What to Expect with. Tools Needed. Mounting Options. Blades Table of Contents 1.888.830.1326 Ceiling Bracket 30 inches Ladder Downrod 3 Wiring 10 Operation, Maintenance & Cleaning Light Kit 11 Troubleshooting??? 17 15 1 13 5 Blades 9 Switch Housing 12 Canopy 6

More information

CATALOG OF REPLACEMENT PARTS

CATALOG OF REPLACEMENT PARTS CATALOG OF REPLACEMENT PARTS HPR SERIES PROOFER/RETARDER MODEL HPR1 ML-132406 30 In. (Standard) ML-132407 50 In. (Standard) ML-132408 63 In. (Standard) ML-132409 83 In. (Standard) ML-132410 96 In. (Standard)

More information

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions. Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

569, 570, 571, 572 Series

569, 570, 571, 572 Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

FitchTM. Instruction Manual. Includes our Basic Function CoolTouch TM Control System Looks permanent, but goes wherever you go!

FitchTM. Instruction Manual. Includes our Basic Function CoolTouch TM Control System Looks permanent, but goes wherever you go! Includes our Basic Function CoolTouch TM Control System Looks permanent, but goes wherever you go! FitchTM A Kichler Décor ceiling fan U.S. Patent Pending Kichler Lighting 7711 East Pleasant Valley Road

More information

Table of Contents. 1 M /10/14 Casablanca Fan Company. What to Expect with Tools Needed.

Table of Contents. 1 M /10/14 Casablanca Fan Company.   What to Expect with Tools Needed. www.casablancafanco.com Table of Contents Congratulations on purchasing your new Casablanca ceiling fan! It will provide comfort and performance in your home or ofice for many years. This installation

More information

Table of Contents. What to Expect with. Mounting Options. Tools Needed. Wall Control

Table of Contents.   What to Expect with. Mounting Options. Tools Needed. Wall Control Table of Contents www.casablancafanco.com What to Expect with Your Installation Congratulations on purchasing your new Casablanca ceiling fan! It will provide comfort and performance in your home or office

More information

MC CHANGER CABINET INSTALLATION INSTRUCTIONS

MC CHANGER CABINET INSTALLATION INSTRUCTIONS 8M00356 REV. 12 July 25, 2017 www.standardchange.com 1-800-968-6955 Technical Phone Support is from 8:00AM to 7:30PM E.S.T., Monday-Friday Walk-in Service is from 8:00AM to 4:30PM E.S.T., Monday-Friday

More information

Table of Contents. What to Expect with Your Installation. Tools Needed. Mounting Options. Ceiling Bracket. Wiring.

Table of Contents.   What to Expect with Your Installation. Tools Needed. Mounting Options. Ceiling Bracket. Wiring. www.hunterfan.com Table of Contents What to Expect with Your Installation Congratulations on purchasing your new Hunter ceiling fan! It will provide comfort and performance in your home or office for many

More information

WARNING DESCRIPTION PART NUMBER QTY PLUMBING, DYNATEMP DRAIN QUENCH BRACKET, THERMOSTAT DRAIN QUENCH

WARNING DESCRIPTION PART NUMBER QTY PLUMBING, DYNATEMP DRAIN QUENCH BRACKET, THERMOSTAT DRAIN QUENCH ! WARNING WARNING: This kit should be installed only by qualified service personnel to reduce the risk of electric shock, serious injury, or fire. A plumbing permit and the services of a licensed plumber

More information

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST CHEVROLET CHEVELLE/ EL CAMINO NOTE: INSTRUCTIONS DEPICT CHEVELLE

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST CHEVROLET CHEVELLE/ EL CAMINO NOTE: INSTRUCTIONS DEPICT CHEVELLE specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST 1964-65 CHEVROLET CHEVELLE/ EL CAMINO NOTE: INSTRUCTIONS DEPICT CHEVELLE CONTROL

More information

IT Module. User Manual. Document Revision Number 1 07/2013

IT Module. User Manual. Document Revision Number 1 07/2013 IT Module User Manual Document Revision Number 1 07/2013 Schneider Electric IT Module User Manual Table of Contents Table of Contents... 2 1. Safety Information... 3 2. Transportation and Installation...

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling

More information

standards: standards:

standards: standards: INSTRUCTION MANUAL D2xB1LD2 LED Beacons For use in Hazardous Locations 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGISED POTENTIAL ELECTROSTATIC CHARGING HAZARD

More information

Installation Instructions

Installation Instructions GE Consumer & Industrial Appliances Installation Instructions Junction Box Cover Within this user bag, you will find a junction box cover and a #10 hex head screw used to attach the junction box cover

More information

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION DET-TRONICS SPECIFICATION DATA Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION The EQ2200UVHT UV Flame Detector is used with the Eagle Quantum

More information

Carbon Rack Enclosure

Carbon Rack Enclosure USER S MANUAL Carbon Rack Enclosure CRxU Series SAVE THESE INSTRUCTIONS Please read this manual and follow the instructions for installation and use. Copyright 07 Cyber Power Systems, Inc. All rights reserved.

More information

Table of Contents What to Expect with Your Installation. Top Housing. Ceiling Plate. Tools Needed.

Table of Contents What to Expect with Your Installation. Top Housing. Ceiling Plate. Tools Needed. Table of Contents Congratulations on purchasing your new Hunter ceiling fan! It will provide comfort and performance in your home or office for many years. This installation and operation manual contains

More information

Tools & Test Equipment

Tools & Test Equipment Tools & Test Equipment With such a large complement of connectors to offer, it is only fitting that you ll find an equally complete offering of Emerson termination tools.this line of products includes

More information

Veritas Appliance Hardware Service Procedure

Veritas Appliance Hardware Service Procedure Veritas Appliance Hardware Service Procedure Power Supply Replacement: NetBackup 0 Appliance Document Number: 77 Version:.0 (7/0/6) Purpose This document describes the process for replacing a power supply

More information

Pole Mounting System Installation & Certification Manual

Pole Mounting System Installation & Certification Manual Pole Mounting System Installation & Certification Manual IronRidge Pole Mount Installation Guide... 2 IronRidge Certification Letter... 11 IronRidge Wet Stamped Drawing... 12 www.ironridge.com 800-227-9523

More information

P-16 ENGINEER NO. DATE DESCRIPTION 1 01/19/2016 FOR CONSTRUCTION 2 03/11/2016 REVISION # 2 DRAWN BY: CHECKED BY: DATE: SCALE: DRAWING NUMBER

P-16 ENGINEER NO. DATE DESCRIPTION 1 01/19/2016 FOR CONSTRUCTION 2 03/11/2016 REVISION # 2 DRAWN BY: CHECKED BY: DATE: SCALE: DRAWING NUMBER PRESSIONAL P-16 PRESSIONAL PRESSIONAL PRESSIONAL 1 ONE LINE DIAGRAM 3 EMEGENCY LIGHTING SCHEME 2 FEEDER SCHEDULE PRESSIONAL PRESSIONAL PRESSIONAL PRESSIONAL LOCAL SINGLE POLE SWITCH 3-WAY SWITCH 3-WAY

More information

-J:, WALL. Before you begin. A. Space requirements

-J:, WALL. Before you begin. A. Space requirements FREE-STANDING RANGE lve Ovens, Compactors, Room Air Conditioners, Dehumidifiers, Automatic Washers, Clothes Dryers, Freezers, Refrigerator-Freezers, Ice Makers,Oishwi u Before you begin Read these instructions

More information

Helpful Tip: NOTE:

Helpful Tip: NOTE: Grounded electrical supply required. Do not run drain lines, water lines or electrical wiring where they can interfere with or contact dishwasher motor or legs. The location where the dishwasher will be

More information

Orrin. Instruction Manual. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go! U.S.

Orrin. Instruction Manual. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go! U.S. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go! U.S. Patent Pending Orrin A Kichler Select ceiling fan Kichler Lighting 7711 East Pleasant Valley Road P.O. Box 318010

More information

Viking Installation Guide

Viking Installation Guide Viking Installation Guide Viking Range Corporation 111 Front Street Greenwood, Mississippi 38930 USA (662) 455-1200 For product information, call 1-888-VIKING1 (845-4641) or visit the Viking Web site at

More information

Heat Exchanger Tube Change Procedure

Heat Exchanger Tube Change Procedure Heat Exchanger Tube Change Procedure Application: DATS II, DATS III, CorrDATS, CFM-500 and high temp, 120 or 240 VAC manufactured after 1 May 01 Last Update: 17 Dec 02 The DATS II and III systems use identical

More information

2 PREPARE THE OPENING

2 PREPARE THE OPENING Installation Instructions 27 & 30 Electric Built-In Wall Ovens Questions? Call 1.800.GE.CARES (1.800.432.2737) or visit www.geappliances.com In Canada, call 1.800.561.3344 or visit www.geappliances.ca

More information

Table of Contents What to Expect with Your Installation. Tools Needed. Wall Control

Table of Contents What to Expect with Your Installation. Tools Needed. Wall Control Table of Contents Congratulations on purchasing your new Casablanca ceiling fan! It will provide comfort and performance in your home or office for many years. This installation and operation manual contains

More information

29 IN. (73.7 CM) ELECTRIC DRYER INSTALLATION INSTRUCTIONS DRYER SAFETY

29 IN. (73.7 CM) ELECTRIC DRYER INSTALLATION INSTRUCTIONS DRYER SAFETY 9 IN. (7.7 CM) ELECTRIC DRYER INSTALLATION INSTRUCTIONS DRYER SAFETY... INSTALLATION INSTRUCTIONS... Tools and Parts... Location Requirements... Electrical Requirements... Electrical Connection...4 Venting

More information

Table of Contents What to Expect with Your Installation. Tools Needed. Wall Control

Table of Contents What to Expect with Your Installation. Tools Needed. Wall Control Table of Contents Congratulations on purchasing your new Casablanca ceiling fan! It will provide comfort and performance in your home or office for many years. This installation and operation manual contains

More information

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER. IMPORTANT: SAVE FOR LOCAL ELECTRICAL INSPECTOR'S USE. READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. U.S.A. WARNING FOR YOUR

More information

569, 570, 571, 572 Series

569, 570, 571, 572 Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions. Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Installation. Leveling

Installation. Leveling Your refrigerator was packed carefully for shipment. Remove and discard shelf packaging and tape. Do not remove the serial plate. Location Do not install refrigerator near oven, radiator or other heat

More information

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT RV Products Division INSTALLATION INSTRUCTIONS FOR 8330-5501 MOUNTING KIT 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330B755 CONTROL BOX KIT (12 VDC HEAT/COOL) 8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)

More information

Centrifugal, tank pump designed to remove condensate water from air conditioners, refrigeration equipment, gas boilers and de-humidifiers. Engineered with contractor input and Little Giant quality, the

More information

POINT HELIDECK LIGHTS PRL-LSM LED LOW SURFACE MOUNT LIGHT

POINT HELIDECK LIGHTS PRL-LSM LED LOW SURFACE MOUNT LIGHT Compliances: ETL Listed to UL 98 US & CSA C22.2 No..-4 Canada ETL Listed to UL 98A Marine Vessels IMO 9 MODU Code () paragraph 13.. FAA AC /39-2B Heliport Design Guide ICAO Annex 14, Volume II UK CAA CAP

More information

60" Tulle PatioTM. Instruction Manual. A Kichler Select ceiling fan

60 Tulle PatioTM. Instruction Manual. A Kichler Select ceiling fan 60" Tulle PatioTM A Kichler Select ceiling fan cul Certified for Wet Location Kichler Lighting 7711 East Pleasant Valley Road P.O. Box 318010 Cleveland, Ohio 44131-8010 Customer Service 866.558.5706 8:30

More information

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any Matthews Fan Company

More information

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS FOSTORIA INDUSTRIES, INC. A DIVISION OF FES - Series Portable Electric Heaters YES - Series Suspended Electric Heaters (FES-1524-3E shown) IMPORTANT SAFETY INFORMATION INSIDE Serious injury or death possible.

More information

Thermal Devices, Inc. Mount Airy, Maryland USA C D E F. Typical Maxiband Clamping

Thermal Devices, Inc. Mount Airy, Maryland USA   C D E F. Typical Maxiband Clamping Maxiband Heaters The Most Sought After Band Heater A B Maxiband General purpose terminal box offers excellent protection to the exposed terminals. To simplify electrical wiring, the box has two 1/2" trade

More information

INSTALLATION INSTRUCTIONS FOR 6797A737 HEAT PUMP FLUSH MOUNT CEILING PLENUM

INSTALLATION INSTRUCTIONS FOR 6797A737 HEAT PUMP FLUSH MOUNT CEILING PLENUM INSTALLATION INSTRUCTIONS FOR 6797A737 HEAT PUMP FLUSH MOUNT CEILING PLENUM TABLE OF CONTENTS Warnings............................................................................... 2 Package Contents........................................................................

More information

Table of Contents What to Expect with Your Installation. Ceiling Plate. Tools Needed.

Table of Contents What to Expect with Your Installation. Ceiling Plate. Tools Needed. Table of Contents Congratulations on purchasing your new Casablanca ceiling fan! It will provide comfort and performance in your home or office for many years. This installation and operation manual contains

More information

Owner s Guide and Installation Manual

Owner s Guide and Installation Manual For Your Records and Warranty Assistance For reference, also attach your receipt or a copy of your receipt to the manual. Model Name Type 3 Models Owner s Guide and Installation Manual Model No. Date Purchased

More information

INSTRUCTION MANUAL. D1xB2XH2 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

INSTRUCTION MANUAL. D1xB2XH2 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information INSTRUCTION MANUAL D1xB2XH2 Xenon Beacon For use in Hazardous Locations 2) Rating & Marking Information 2.1 Public Mode Fire Alarm Ratings The D1xB2XH2 is certified for use as public mode visual alarm

More information

INSTRUCTION MANUAL. D1xB2XH1 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information

INSTRUCTION MANUAL. D1xB2XH1 Xenon Beacon For use in Hazardous Locations. 2) Rating & Marking Information INSTRUCTION MANUAL D1xB2XH1 Xenon Beacon For use in Hazardous Locations 2) Rating & Marking Information 2.1 Public Mode Fire Alarm Ratings The D1xB2XH1 is certified for use as public mode visual alarm

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS BUILT-IN BOTTOM MOUNT REFRIGERATOR/FREEZER BRTGK72SS-GRILLE KIT (FOR PROFESSIONAL SERIES ONLY) VIKING RANGE CORPORATION 111 Front Street Greenwood, Mississippi (MS) 38930 USA

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Coaxial cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control

More information

ST. KITTS CEILING FAN

ST. KITTS CEILING FAN ITEM #0845047 ST. KITTS CEILING FAN MODEL #40829 Questions, problems or missing parts? Before returning this item to your retailer, call our customer service department at 1-800-643-0067, Monday - Thursday,

More information

ultra quiet fan USER MANUAL INSTALLATION OPERATION MAINTENANCE

ultra quiet fan USER MANUAL INSTALLATION OPERATION MAINTENANCE USER MANUAL ultra quiet fan INSTALLATION OPERATION MAINTENANCE Z0414808 rev A ISSUED 02/2014 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. safety and handling Safety Warning

More information

Table of Contents. What to Expect with. Tools Needed. Mounting Options. Blades

Table of Contents.  What to Expect with. Tools Needed. Mounting Options. Blades www.hunterfan.com Table of Contents Ceiling Bracket 30 inches Downrod Ladder 3 Wiring Operation, Maintenance & Cleaning Light Kit 11 Troubleshooting??? 16 15 1 12 10 9 5 Blades Canopy 6 4 PÁGINA 2 7 feet

More information

WARNING. Failure to install this kit within the guidelines might adversely affect safety, performance, component life and warranty coverage.

WARNING. Failure to install this kit within the guidelines might adversely affect safety, performance, component life and warranty coverage. ! WARNING WARNING: This kit should be installed only by qualified service personnel to reduce the risk of electric shock, serious injury, or fire. A plumbing permit and the services of a licensed plumber

More information

Undercarpet Cabling Products Undercarpet Power, Voice and Data Distribution

Undercarpet Cabling Products Undercarpet Power, Voice and Data Distribution Undercarpet Cabling Products TE Connectivity Enterprise Networks Warranty Power Distribution Product Coverage* TE Connectivity warrants that all Undercarpet cabling system products within this catalog

More information