LQQA Humidifier, for circulated water
|
|
- Jonah Hicks
- 5 years ago
- Views:
Transcription
1 Size Fig Control box, on the outside. Control box, on the inside. Shut-off valve (not included) 4. Water filter, max. 5 mm mesh (not included) 5. LQAZ-8 Water trap (accessory) 6. Water supply pipe 7. Humidifier fill 8. Droplet eliminator 9. Spray pipe. Pump. Flow controller. Valve with motor actuator. Overflow hose 4. Water level sensor 5. Solenoid valve. Flushing hose 7. End plug 8. Side wall Maintenance adjustments Water: Determine the calcium and bicarbonate content and the ph value of the water. These values can be obtained from a water analysis or from the local water authority. Plot the values of bicarbonate, calcium and ph in chart A B C Level monitors on page 5 to determine in which zone the water can be classified. If the water is of zone 4 type, it should be softened. Level monitors fig. Level monitor A: Level monitor A: Closes the water supply valve when the water reaches max. level A. Setting A: 65 mm from the upper edge of the water tray (sizes 84). Level monitor B: Opens the drain valve for water bleed-off. Setting B: The zone value obtained (see page 5) determines at which setting level monitor B (Fig. ) is to be preset. Level monitor C: Stops the circulation pump and opens the water supply valve if the water level drops below level C. Setting C: 5 mm from the bottom of the water tray (sizes 84) Fig. Z ON Zone Scale Level monitor B: Adjustable Adjusting screw Zon Level relays: NR, NR and NR are shown in Fig. 7. The level relays are preset at a sensibility of 4 kω. If softened water is used and the level monitors don t work, the sensibility setting can be increased to kω. Fläkt Woods 96 GB. Specifications are subject to alteration without notice
2 Maintenance adjustments (Contd.) The humidifier function: switch on the power supply to the humidifier. The water tray will start to fill with water. Check: that the pump has started and that it is pumping water. If there is no water flow, change the direction of rotation of the pump, see Fig. 5. preset the required supply water flow rate according to Table. This is done by setting the adjustment screw on the flow controller, shown in Fig. 4. that water is being discharged from all of the holes in the spray pipe(s). If any holes are clogged, use a needle to unclog them. If the spray pipe(s) is/are extremely clogged, remove the end plugs (7), brush inside them using a round brush and then flush them clean. that the flow of supply water stops when the water level in the tray reaches level monitor A. that water bleed-off can be done by manually opening the drain valve approx. half way (45 ), see Fig.. The valve can be reclosed by pressing a reset button on the control unit. When the water level has dropped below the lowest point of sensor B, the drain valve should open fully. If the water level continues to drop below the lowest point of sensor C, water inlet valve should begin to open and after a preset period (see Table, Fig. 6) the drain valve should start to close. When the water reaches level C, the pump should soon stop. (The pump should not run when the water level is below level C.) The preset period on the time relay should be according to Table, and Fig. 6. Droplet eliminator The droplet eliminator fills must be correctly fitted for the direction of air flow, see the arrow on the droplet eliminator. Table. Supply water flow Size Supply water flow, l/min Aluminium 9% % Adjusting screw Reading point Fig. Fig. 4 Fig. 5 Fläkt Woods 96 GB. Specifications are subject to alteration without notice
3 Table. Presetting the time relay Size Normal operation preset value Time required for emptying Time relay TR has been preset for normal operation. If the time required for emptying has to be increased due to humidification over a long period, this can be done as follows:. Select Function. Select the Range. Select Time If Range has red digits, Time shows tenths of Range If Range has black digits, Time shows thirtieths of Range. Example: Size 64, Δx>8 gram. Set a time of 4 sec. Select a Range of sec. (black digits) Select a Time of 4 (black digits) High humidification over a long period Δx >8 gram Δx >5 gram 9% % 9% % s A~+ 5 B Range Time M ETR4 69 A Rel Power TR Fig. 6 8 Function A~- Table. Presetting time relay TR Seconds Range s Time s red s black s black 4 s 4 red 5 s 5 red s 6 red 7 s 7 red 8 s 8 red 9 s 9 red s red s black 8 s 8 black 4 s 4 black s black K Q R TR NR NR NR Fig. 7 Components inside the control box Fläkt Woods 96 GB. Specifications are subject to alteration without notice
4 Water quality Evaporation causes an increase in the concentration of minerals in the circulating water, which necessitates continuous bleed-off and make-up with fresh water. The bleed-off rate is dependent on factors such as: the ph of the water the bicarbonate concentration (HCO ), mg/l the calcium concentration (Ca+), mg/l This data can be obtained from a municipal water authority or by analysing the water. Lime precipitation can be prevented by plotting the pertinent data in Chart on page 4 to determine the current risk zone. Water level monitor B can then be set according to the relevant zone. If the water is too hard, it may be necessary to subject it to partial softening. In addition to the risk of lime precipitation, the concentration of chlorine (Cl) and copper (Cu) must be taken into account. To ensure acceptable performance, the concentration of Cl in the fresh water must not exceed 5 mg/l and that of Cu must not exceed. mg/l. To set the timer for emptying and flushing For normal function, the timer should be preset to ON. When emptying, which can be programmed to occur once or several (optional) times every 4-hour period, the timer will reset itself to the OFF setting for minutes. After that, the timer will reset itself to ON for minutes to allow flushing. The timer will then reset itself to the OFF setting for minutes for additional emptying before resetting itself back to ON for normal operation. In the following example, emptying and flushing are required once every 4 hours from. to.5 as scheduled below. Period Timer setting Activity.. ON Normal operation.. OFF Emptying.. ON Flushing..5 OFF Additional emptying.5 4. ON Normal operation This can be done most easily by programming the operation times from.5 to. and from. to. on a daily basis! Emptying and additional emptying will then occur from Fläkt Woods 96 GB. 4 Specifications are subject to alteration without notice
5 Timer The timer has been preset at the factory for emptying and flushing as described above once every 4-hour period. The timer has also been preset for the following: Summer and winter time in the country where it is to be used. Date and time in the time zone where it is to be used. Day-by-day summary of the programmed connection times. Example: 5 = Friday Duct status ON = On, OFF = OFF Maintenance voltage OK: Indicated by flashing points between the numbers on the display. Running reserve mode: Indicated by flashing points between the numbers on the display. Choice of function: Ex: Auto, Prog, Pulse, Cycle, Delete 4 Auto MENU OK - + L N Display of special functions: Manual operation Permanent ON/OFF Symbols which indicate summer/winter function: Summer Winter The numbers under the display indicate days of the week = Monday, = Tuesday, etc. Choice Yes means choice of programming. Choice No means continue. N L L Change of current time of day. Press menu times - flashes. Press OK Display shows YEAR, change with + or. Press OK Display shows MONTH, change with + or 4. Press OK and continue for DAY, HOUR, MINUTE, SU/WI (SU = Summer, WI = Winter) For switching ON/OFF. Press menu time - Prog flashes. Press OK. Change to QUESTION with + or 4. Press OK 5. Press OK for next time. And continue to END 6. Press OK To INTERRUPT Press menu Change of ON/OFF. Press menu time - Prog flashes. Press OK Read text in the display! Select with + or Store with OK Manual operation of ON/OFF. Press both + and at the same time. ~ sec gives manual ON/OFF, (returns automatically) ~ sec gives permanent ON/OFF Resetting: Briefly press both + and at the same time. For further particulars, see the separate instructions supplied with the timer. Fläkt Woods 96 GB. 5 Specifications are subject to alteration without notice
6 Chart Zone is the safe zone, in which the water is soft or demineralized. Zone is the lower part of the transition zone, in which the water can be said to be of normal drinking quality. Zone is the upper part of the transition zone, in which the water is relatively hard. Zone 4 is the precipitation zone, in which the water is very hard. The water must be subjected to partial softening, so that its quality will be within zone. However, the softening treatment must not lower the quality of the water to zone. Example Data from the municipal water authority: ph = 7,6 Bikarbonate 7 mg/l Calcium mg/l From Chart, the operating point is in zone (safe zone). Calcium Ca + mg/l ph-value e Max. ph of aluminium Transition zone Safe zone Precipitation zone ,5 9 9, Water consumption The water consumption consists of the water evaporated and a certain amount of water bleed-off. This bleedoff flow is necessary to reduce the consumption of salts in the circulating water. If the concentration of salts is too high, salts may be deposited on the humidifier fill, which will have a detrimental effect on the performance of the humidifier. The chart above can be used to determine the appropriate bleed-off flow. If the humidifier has been sized for running over a long period at a high humidification rate Δx above 8 grams per kg of air (9% humidifier) and Δx above 5 grams per kg of air (% humidifier) respec- tively is recommended if the water tray is emptied and flushed twice a day. (See: To set the timer for emptying and flushing.) Periods out of service The controller of the humidifier switches to the emptying mode whenever the fan is switched out. Clean the water tray if the system is to be shut down for an extended period, such as during the annual holiday and long weekends. If the humidifier is to be out of service for some time, the humidifier fills should be removed, cleaned and stored in a place where they will not sustain damage. Bikarbonate HCO mg/l Fläkt Woods 96 GB. 6 Specifications are subject to alteration without notice
7 To shut down the humidifier A. Isolate the power supply B. Stop the fans, if they are operating. Cleaning or replacement of the humidifier fills and droplet eliminators A. Shut down the humidifier. B. Open the inspection door. C. Withdraw the spacer plate as shown in Fig. 8. D. Withdraw the droplet eliminators and humidifier fills straight out of the humidifier. See Fig. 8. Important! The inner humidifier fills can be reached if you carefully step on the edge of the water tray. Avoid walking on the bottom of the water tray, guide rails or electric cables. E. The fills are relatively fragile and therefore should be treated with great care. Clean by spraying with a jet of clean water, possibly containing the ULCZ- cleaning agent. When replacing the humidifier fills, see the appropriate instructions supplied with the new fills. F. Refit the components in the reverse order. G. Check the position of the spacer plate and close the door. Fig. 8 To clean the water tray A. Shut down the humidifier. B. Withdraw the humidifier fills and the droplet eliminators. C. Open the drain valve manually to drain the water tray. Important! Do not walk on the bottom of the water tray, guide rails or electric cables. D. The water tray is now exposed and can easily be cleaned with the flushing hose supplied. E. Refit the components in the reverse order. F. Check the position of the spacer plate and close the door. Fläkt Woods 96 GB. 7 Specifications are subject to alteration without notice
8 Service intervals Component Service work Interval, months Casing (water tray, ends, top, guide rails) Humidifier fills Droplet eliminator Water filter Drain the water tray. Clean the interior by flushing, wiping or brushin if necessary. Clean by flushing with water, possibly with ULCZ- cleaning agent, particularly if the humidification performance has deteriorated. Clean or replace the filter cartridge, if necessary. (The mesh must not exceed 5 μm.) Level monitor Check the water level and adjust as necessary. Water flow Clean the spray tubes as necessary. Water trap Clean and refill. 6 Water quality See under maintenance adjustments. Wiring diagram L L L N PE HB N SU Control box on outside F 4 A A 4 Timer SU 5 6 TF Emptying/ Flushing 6A 4 5 c no Interlock GM 4 c no Humidity control G/G NR Control box on inside 9 R M B Auxiliary relay 8 Level relay C B A A Prevents operation Emptying/ Flushing 5 5 B when the tray is dry K Q Q R Contactor A A CP K A A Contactor A A CP I> I> I> I> I> I> NR K U V W M CP K U V W M CP A B 7 A B B B 5 A 8 Level relay Maintains correct level Level relay Bleed-off 5 B B B A NR A 8 5 TR R R MV Solenoid valve Maintains correct level SV 4 B A TR A 5 Delayed closure, SV Valve actuator Q, Q Motor protection switch R Aux. relay NR Level monitor K, K Contactor F Automatic fuse TR Time relay HB Main switch TF Supply air fan SU Timer NR, NR Level monitor SV Valve actuator GM Hygrostat Fläkt Woods 96 GB. 8 Specifications are subject to alteration without notice
LQQA Humidifier, for circulated water
Size 5 Fig. 6 5 6 8 7 9 7 8. Control box, on the outside. Control box, on the inside. Shut-off valve (not included). Water filter, max. 5 mm mesh (not included) 5. LQAZ-8 Water trap (accessory) 6. Water
More informationEUQA Humidifier, for circulated water
Sizes 0 4, 50, 5 Sizes 44, 5 84 6 5 4 6 5 4 5 6 8 7 9 7 8 0. Control box, on the outside. Control box, on the inside. Shut-off valve (not included) 4. Water filter, max. 500 mm mesh (not included) 5. EUAZ-08
More informationHUMIDIFIER EQQA, EQQZ
HUMIDIFIER EQQA, EQQZ INSTALLATION AND MAINTENANCE INSTRUCTION EQQA Once-through water 2- EQQA for circulated water.. 6-1 EQQZ-1 Humidifier cassette Ordering code. 16 EQQA Once-trough water EQQA for circulated
More informationGlass and Dishwashers AMX / AUX Series
Glass and Dishwashers AMX / AUX Series INSTALLATION OPERATION REV. 8.xx 04.07.2005 Installation and Operation Instructions for Models of AMX / AUX Series Content Page 1 Installation... 3 2 Connections...
More informationGlass and Dishwashers AMX / AUX Series
Glass and Dishwashers AMX / AUX Series INSTALLATION OPERATION VERSION 24.02.04 Important Notes Use in Accordance with Regulations This machine is exclusively to be used to wash ware such as plates, cups,
More informationINSTALLATION & OPERATION Rev 1.00A DISTRIBUTED EXCLUSIVELY BY CMA DISHMACHINES KNOTT AVENUE GARDEN GROVE, CALIFORNIA 92841
MODEL UC 60e INSTALLATION & OPERATION Rev 1.00A DISTRIBUTED EXCLUSIVELY BY CMA DISHMACHINES 12700 KNOTT AVENUE GARDEN GROVE, CALIFORNIA 92841 800-854- 6417 FAX 714-895-2141 www.cmadishmachines.com TABLE
More informationWhat to expect from your water softener
What to expect from your water softener All water softeners work on the same basic principal. Hard water flows through a bed of resin and the calcium and magnesium, the minerals that are responsible for
More informationBarAid 400. Installation and. Starting from Serial No.:
Glasswasher BarAid 400 Installation and operation Instructions Starting from Serial No.: 8649 1065 REV. 19.01.2009 DE 1618-A-01-09 Content Page 1 Important Notes... 4 2 Installation... 5 2.1 Location...
More informationService Bulletin: TrueSTEAM Installation Best Practices Remote Installation Plumbing and Draining Water Quality
1 Service Bulletin: TrueSTEAM Installation Best Practices Remote Installation Plumbing and Draining Water Quality Remote Installation BEST PRACTICE #1 Length Mount the humidifier as close as possible to
More informationCHH30 Dishwasher. Wiring Diagram. Spare Parts List. Installation / Operation
CHH30 Dishwasher Installation / Operation Spare Parts List Wiring Diagram jw-06-2006 GB USE AND MAINTENANCE MANUAL Pag. 1 CONTENTS CHAP. 1 INTRODUCTION... 3 CHAP.2 INSTALLATION... 3 2.1 HANDLING AND UNPACKING...
More informationEngineers manual. Under counter machines
Table of Contents 1. INTRODUCTION... 3 1.1 1.2 1.3 INSTALLATION AND COMMISSIONING... 3 SERVICE AND REPAIRS... 3 MODIFICATION... 3 2. EXPLANATION OF SYMBOLS USED... 3 3. WARNING AND SAFETY INFORMATION...
More informationScotsman Technical Training. CU50 Cube Ice Machine
Scotsman Technical Training CU50 Cube Ice Machine Major Topics Overview Installation Start Up Sequence of Operation Maintenance Diagnostics Service Procedures Models Two Base Models Gravity Drain Pump
More informationGlass and Dishwashers. BarAid 500/800. Installation and. Starting from Serial No.:
Glass and Dishwashers BarAid 500/800 Installation and operation Instructions Starting from Serial No.: 8652 0001 REV. 19.01.2009 1617-A-01-09 Content Page 1 Important Notes... 4 2 Installation... 5 2.1
More informationHX-30/40 and HX-30/40 S Glass and Dishwashers
HX-30/40 and HX-30/40 S Glass and Dishwashers INSTALLATION OPERATION VERSION 18/01/00 2 Installation and Operation Instructions for Model HX-30/40 and HX-30/40 S (with built-in softener) Content Page 1
More informationMiniVap Humidifier Models LMV2 & LMV4
Ä MiniVap Humidifier Models LMV2 & LMV4 Please read these Instructions BEFORE Installation and Start-up Failure to observe manufacturer s recommendations may invalidate warranty Vapac Humidity Control
More informationGlass and Dishwashers 402/452/502. (original instructions) (incl. Australian /502) Starting from Serial No.:
Glass and Dishwashers ECOMAX 402/452/502 (incl. Australian 452-90/502) INSTALLATION AND OPERATION INSTRUCTIONS (original instructions) Starting from Serial No.: 8663 4000 REV. 05.10.2015 EN IMPORTANT NOTES
More information"ER" Series Electric Humidifier
ER-1 Standard Water "ER" Series Electric Humidifier The Electric Humidifier from PURE Humidifier Co. is loaded with features and options. All you need is tap water, electricity, and a sanitary drain the
More informationdanfoss Heating Solutions 5
4. Technical settings...22 4.1 Deactivating automatic daylight saving time...22 4.2 Adjusting to radiator/room...23 4.3 Deactivating intelligent control...23 4.4 Technical specifications...24 5. Safety
More informationEN 1508 OPERATION MANUAL. Steam humidifier Condair RS. Humidification and Evaporative Cooling
2583280 EN 1508 OPERATION MANUAL Steam humidifier Condair RS Humidification and Evaporative Cooling Thank you for choosing Condair Installation date (MM/DD/YYYY): Commissioning date (MM/DD/YYYY): Site:
More informationEUKC Cooling Unit. Compulsory declaration and recurring. The unit must NOT be used in any other way than as a cooling unit!
Safety Precautions IMPORTANT INFORMATION! The unit must NOT be used in any other way than as a cooling unit! Carefully read, study and understand the Operation and Maintenance Instructions before you commission
More informationInfinity Control. Homeowner s Guide. The New Feeling of Comfort
TM Infinity Control Homeowner s Guide The New Feeling of Comfort CONGRATULATIONS! Your decision to choose the Carrier Infinity Control puts you in a select group of homeowners who understand the value
More information3. Before switching the equipment on, make sure that the model plate data conforms to that of the electrical and water distribution network.
Manuale di istruzione per lavastoviglie Notice d utilisation pour lave-vaisselle Gebrauchsanweisung für Geschirrspüler Instruction manual for dishwashers Manual de instrucciones para lavavajillas LF315
More informationControl of the system, MLP RO pump station
Control of the system, MLP RO pump station Operating instructions TI071GB-02 /06.11.09/LJ 1/12 Table of contents Humidification pump Safety equipment Selecting RO type Choice of language Normal indications
More informationWARNING FIRE DOOR CLOSING
PRODUCT INSTRUCTIS Stock Code: 088 FCP - Lite Floats Road, Wythenshawe Manchester, M 9WB Tel: + (0) 9 Fax: + (0) 9 Doc No PI - 88 Iss:.0 WARNING FIRE DOOR CLOSING STOP Contents ) Blank ) Features and
More informationAQUAMAC MODELS
AQUAMAC MODELS 300-500-800-1000 OUR SYSTEMS CONFORM TO EC STANDARD 73/23 CEE - 89/336 INSTRUCTION MANUAL Cod. 71503095/0-5/97 WARNING! THE FOLLOWING OPERATIONS AND THOSE EVIDENCED WITH THE SYMBOL ON THE
More informationService Parts
GM Operator Manual !!!! WARNING Before installation and commisioning, you must read the safety instructions and warnings carefully and all the warning labels attached to the equipment. IMPORTANT Failure
More informationBrivis Service Manual
ISO Documents Last modified by: Felicity Devine Date last modified: 23/02/2005 Document: Brivis Service Manual Evaporative Cooler Contour N-E3 & BC-E1 1999 Supplement This manual is to be used in conjunction
More informationBx OVEN SET UP AND OPERATION OF OVEN AND CONDENSER UNIT (IF FITTED) CLASSIC
www.monoequip.com OVEN SERIAL NO. OVEN CODE 149 150 153 156 158 159 180 CONDENSER SERIAL No. (IF FITTED) In the event of an enquiry please quote these numbers. Bx OVEN SET UP AND OPERATION OF OVEN AND
More information1850 Series TRIPLE TREAT Operation Manual
1850 Series TRIPLE TREAT Operation Manual BRINE TANK RESIN TANK CARBON TANK System shown with optional tank jackets. Note: 1. Read all instructions carefully before operation. 2. Avoid pinched o-rings
More informationVERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual
VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual EN Table of Contents 1. INSTALLATION MANUAL...3 1.1. Air Handling Units Sections Connection...3
More informationNO. F ISSUED: JUN. 18, 2008 REVISED: JUN. 17, 2011 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER KM-100A KM-125A MODEL SERVICE MANUAL
NO. F003-756 ISSUED: JUN. 18, 2008 REVISED: JUN. 17, 2011 HOSHIZAKI SELF-CTAINED CRESCENT CUBER MODEL KM-100A KM-125A SERVICE MANUAL IMPORTANT This manual should be read carefully before the icemaker is
More informationGeyserWise MAX. Instruction manual. All in one hot water management
GeyserWise MAX All in one hot water management Before operating and installation, carefully read all instructions. Do not discard this manual. DISPLAY The display is the feedback mechanism to the user
More informationRC411 Operator Manual
RC411 Operator Manual Page 1 of 14 FOREWORD 1. Read the instructions contained in the enclosed booklet carefully, because it contains important information on installation, operation and maintenance safety.
More informationOPERATOR S MODEL HHC-901 HHC-904 HEATED HOLDING CABINET REGISTER WARRANTY ONLINE AT
OPERATOR S M A N U A L HEATED HOLDING CABINET MODEL HHC-901 HHC-904 REGISTER WARRANTY ONLINE AT WWW.HENNYPENNY.COM TABLE OF CONTENTS Section Page Section 1. INTRODUCTION... 1-1 1-1. Heated Holding Cabinet...
More informationService Parts
M2 Operator Manual !!!! WARNING Before installation and commissioning, you must read the safety instructions and warnings carefully and all the warning labels attached to the equipment. IMPORTANT Failure
More informationThe Classeq under counter range
Installation & Operators Manual The under counter range Part number 902.0011 Revision C Effective date January 2010 Language English Glasswashers Eco 1 Eco 2 Eco 3 Duo 2 Duo 3 Dishwasher Hydro 500 Hydro
More informationEBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL
EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com
More informationOWNER S MANUAL Venstar Inc. 08/07
Digital Thermostat commercial SCHOOL THERMOSTAT T2900SCH MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Energy Saving Operation Morning Warm-up Period Programmable Override Unoccupied until button press
More informationSUPPLEMENT TO OPERATION MANUAL Modular Air Handling Units CAIRplus ECOTWINcool
SUPPLEMENT TO OPERATION MANUAL Modular Air Handling Units CAIRplus ECOTWINcool Table of Contents Overview of units and packaged content... 3 Adiabatic cooling... 3 Design features... 4 Fan arrangement...
More informationOperating instructions
Operating instructions for Winterhalter Gastronom dishwasher GS 502 and GS 515 Contents Page 1 Intended use... 1 2 Installation and commissioning... 1 3 Safety instructions... 2 4 Operating panel... 3
More informationR410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
More informationAgrifim A675CT Timer. Frequently Asked Questions
Agrifim A675CT Timer Frequently Asked Questions 1 Contents How do I put batteries into the timer?.3 What type of batteries can be used?...3 How long will batteries last?...3 How do you program the timer?...3
More informationRoth Touchline. German quality since Quick and easy user manual 1/10
Roth Touchline Quick and easy user manual German quality since 197 1/10 230 V Pump N N L L 230 V 230 V 2 V 2 V c/o in %H c/o out c/o in Trafo out /TB in N L eco 2V CH 1 CH 2 CH 3 CH 2V 2V 2V 2V 2V Touchline,
More informationOperating manual. Wascator FOM71 CLS
Operating manual Wascator FOM71 CLS Operating manual in original language 438 9200-91/EN 2010.05.03 Register now And be able to join the Wascator FOM 71 CLS web site where you can find: General information
More informationSPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF AOU 9RLFW AOURLFW R40A CONTENTS. DESCRIPTION OF EACH CONTROL OPERATION. COOLING
More informationPUROTAP easy. Installation Function Operation Service. fast efficient safe. Demineralised heating water perfect for every system
EN Demineralised heating water perfect for every system PUROTAP easy Installation Function Operation Service fast efficient safe Minerals and salts in technical water circulations lead to corrosion and
More informationInstallation & Operators Manual
Installation & Operators Manual Eco, Hydro and Duo under counter range Part number 902.0001 Revison B Installation and Operation instructions For Classeq under counter range of glass and dishwashers. Section
More informationHMC300. Control unit. Operating Instructions. EMS plus (2014/10) O
HMC300 Control unit EMS plus 6 720 808 471-00.1O Operating Instructions 6 720 813 192 (2014/10) Contents Contents Key to symbols and safety instructions................3 1.1 Key to symbols...........................
More informationDishwasher technical manual
07/2017 ENG Dishwasher technical manual UNIKO WI-FI 1 CONTENTS CONTENTS... 2 MEANING OF THE ICONS... 4 START-UP... 5 CONNECTION TO WI-FI 1.0... 7 Wi-Fi activation... 7 Dishwasher connection... 7 CONNECTION
More informationEngineers manual. Pass Through machines P500 P500 A P500 AS P500 A WS P500 AS WS. A- AirBreak WS Water Softener. AS Dual Rinse Element
P500 P500 A P500 AS P500 A WS P500 AS WS A- AirBreak WS Water Softener AS Dual Rinse Element Table of Contents 1. INTRODUCTION... 3 1.1 1.2 1.3 INSTALLATION AND COMMISSIONING... 3 SERVICE AND REPAIRS...
More informationINSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A
INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS G 2000-S 25-35 - 45-55 60-70 - 100 (V13) 1 Index WARNINGS GAS FLOW RATE DIMSIONS SETTINGS PARAMETERS SERVICING THE URNER 3 8 13 OPERATING DESCRIPTION
More informationService Information. WNes 2956 appliance documentation. Service Information no. 27/2004 LHG/TKD-Fe/June SI
After Sales Service International Service Information Service Information no. 27/2004 LHG/TKD-Fe/June 2004 WNes 2956 appliance documentation Page 1/26 Contents 2.0. Extract from Operating Instructions
More informationSERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOU9RLS2H AOU12RLS2H AOU15RLS2H
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU9RLS ASURLS ASU5RLS AOU9RLSH AOURLSH AOU5RLSH R40A CONTENTS. DESCRIPTION OF EACH CONTROL
More information6 Setting Your Program Schedule 7 Operating Your Thermostat 8 Additional Operation Features 9 Thermostat Maintenance
Programmable Thermostats Detailed User Guide 2020NC 2220NC Single Stage Heat / Cool Conventional and Heat Pump Up to 2 Heat / 1 Cool Conventional and Heat Pump Model number is located on back of thermostat
More informationVIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B
Operating instructions for the system user VIESMANN Digital time switch for the Vitodens 100-W, type WB1B DIGITAL TIME SWITCH 5/2008 Please keep safe. Safety instructions For your safety Please follow
More informationSERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G24LFL AO*G24LFCC AO*G30LFT
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS*G4LFCA AS*G4LFCC AS*G0LFCA AO*G4LFL AO*G4LFCC AO*G0LFT R40A CONTENTS. DESCRIPTION OF EACH
More information.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers.
Issued 2006/08/01 Section 15751 Humidifiers Page 1 of 7 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section 01810 Commissioning..4 Section
More informationService Parts
UL Operator Manual !!!! WARNING Before installation and commisioning, you must read the safety instructions and warnings carefully and all the warning labels attached to the equipment. IMPORTANT Failure
More informationIssue 10.94e AIR CONDITIONING ULTRASONIC/BNB TECHNICAL MANUAL. We reserve the right to make technical changes
Issue 10.94e AIR CONDITIONING ULTRASONIC/BNB TECHNICAL MANUAL We reserve the right to make technical changes List of contents 1. Application areas and method of operation... 3 2. Technical data for the
More informationUser manual DHP-AQ VUGFB102
User manual DHP-AQ VUGFB102 Danfoss A/S reserves the right to make changes to components and specifications without prior notice. 2010 Danfoss A/S. The Swedish language is used for the original instructions.
More informationWater Softener & Single Tank Triple Treat System Installation Overview. Using 1850 Metered Valves
Water Softener & Single Tank Triple Treat System Installation Overview Using 1850 Metered Valves System Installation CAUTION: Do not use systems on untreated well water that is microbiologically unsafe.
More information6 Setting Your Program Schedule 7 Operating Your Thermostat 8 Additional Operation Features 9 Thermostat Maintenance
Programmable Thermostats Detailed User Guide 2020NC 2220NC Single Stage Heat / Cool Conventional and Heat Pump Up to 2 Heat / 2 Cool Conventional Up to 2 Heat / 1 Cool Heat Pump Model number is located
More informationHEAT COOL. Meets Commercial California Title 24
Digital Thermostat commercial THERMOSTAT T2900 7-DAY MABLE up to 3-heat & 2-cool HEAT COOL HEAT PUMP Control up to 3 Heat & 2 Cool Stages 3 Configurable Outputs Adjustable 2nd & 3rd Stage Timers & Deadbands
More informationModular Standard HP Chiller 1/4 screw compressor with Carel driver
Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?
More informationDOMESTIC STEAM GENERATOR Installation Instructions
DOMESTIC STEAM GENERATOR Installation Instructions Please read all of the instructions carefully before commencing installation or using the facility. Contents INTRODUCTION Page 2 TECHNICAL SPECIFICATION
More informationSERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS* A09LEC AS* A12LEC AO* R09LECN AO* R12LECN R410A CONTENTS 1. DESCRIPTION OF EACH CONTROL
More informationServicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use
GB122 Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C For trade use Please read thoroughly before attemting to diagnose fault 7217 4900 (03/2010) GB/IE List of contents
More informationOperating Manual. Reverse Osmosis Water Purifier. MELAdem 55
Operating Manual Reverse Osmosis Water Purifier MELAdem 55 Dear Doctor, Thank you for placing your trust in this reverse osmosis water purifier. Since 1951, MELAG has specialised in the production of sterilisation
More informationUser Manual. Dishwasher ZDM17301SA ZDM17301WA
EN User Manual Dishwasher ZDM17301SA ZDM17301WA Contents Safety information 2 Safety instructions 3 Product description 4 Control panel 5 Programmes 6 Daily Use 7 Hints and tips 10 Care and cleaning 11
More informationThe Professional s Choice
CPF Series Models: CPF2100, CPF210, CPF310, CPF4100-3, CPF4100-6 & CPF6100 Auto-Fill Catering Water Boiler With Integrated Multi-Filter Installation And User Instructions The Professional s Choice INSTANTA
More informationServicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use
GB122 7210 1300-12/2002 GB(EN) For trade use Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C Please read thoroughly before attempting to diagnose fault List of contents
More informationProdigy Eclipse Cuber Technical Training
Prodigy Eclipse Cuber Technical Training 600 800 1000 1200 1400 1800 2000 In This Presentation What Eclipse is Components and their functions Installation Operation Maintenance Service Diagnosis The Prodigy
More informationOperating instructions. For the operator. Operating instructions VRT 350. Room temperature-controlled controller GB, IE
Operating instructions For the operator Operating instructions VRT 350 Room temperature-controlled controller GB, IE Legal information Document type: Product: VRT 350 Target group: Language: Operating
More informationSG User Manual
SG 0004-5 User Manual The spa equipment requires a 44 amp outlet, preferably dedicated to the spa. Carefully read all of the instructions before enjoying the spa. WARNING: Operating the system without
More informationInstallation & Operators Manual
Installation & Operators Manual Eco, Hydro and Duo under counter range Part number 902.0011 Revision A Installation and Operation instructions For Classeq under counter range of glass and dishwashers.
More informationDec Wirsbo CoSy Radio. Installation and Operating Instructions
Dec. 2002 Wirsbo CoSy Radio Installation and Operating Instructions Contents 1. Overview... 3 2. Room thermostat... 3 2.1 Thermostat models... 3 2.2 Function... 4 2.3 Positioning... 4 2.4 Setting and limiting
More informationOperating Instructions Steam Ironing System
Operating Instructions Steam Ironing System To prevent accidents and appliance damage, read these instructions before installation or use. en-us,ca M.-Nr. 10 462 411 Caring for the environment Disposal
More informationACE. HydroStream Model HC-100. Evaporative Humidification (100 lbs/hr) Produces Already Humidified Air Information Specifications...
AC E Air Cleaning Equipment Inc 303 N Main St Broadway NC 27505 800-962-0650 www.industrialairtreatment.com Evaporative Humidification (100 lbs/hr) Produces Already Humidified Air Information Specifications...
More informationCLIM9000CE PORTABLE AIR CONDITIONER USER MANUAL
CLIM9000CE PORTABLE AIR CONDITIONER USER MANUAL Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. SAFETY INSTRUCTIONS Important! Carefully
More informationEBC20. Instructions for fitting, installation and operation. Read and save these instructions!
EBC20 UK Instructions for fitting, installation and operation Read and save these instructions! 2 3002878 EBC20 UK 290415 1. Product information............................................... 4 1.1 Delivery.............................................................
More informationYEAR-ROUND COMFORT EVOLUTION CONTROL ZONE CONTROL HOMEOWNER S GUIDE. The Ultimate Home Comfort System.
YEAR-ROUND COMFORT EVOLUTION CONTROL ZONE CONTROL HOMEOWNER S GUIDE The Ultimate Home Comfort System. CONGRATULATIONS! Your decision to choose the Bryant Evolution Control puts you in a select group of
More informationOWNER S MANUAL. Evaporative Cooler. Original English Instructions. (English) (LCB, CPL, CPS, BM)
OWNER S MANUAL Evaporative Cooler (English) (LCB, CPL, CPS, BM) Original English Instructions TABLE OF CONTENTS INTRODUCTION 4 WALL CONTROL FUNCTIONS 5 STARTING YOUR COOLER 5 AUTOMATIC MODE 6 MANUAL MODE
More informationCAIRplus ECOTWINcool SUPPLEMENT TO OPERATION MANUAL
CAIRplus ECOTWINcool SUPPLEMENT TO OPERATION MANUAL Table of Contents Overview of units and packaged content... 3 Adiabatic cooling... 3 Design features... 4 Fan arrangement... 4 Hood (protective hood
More informationInstaller & User Guide Effective February 2013
Model No. MONARCH WATER Installer & User Guide Effective February 2013 For Monarch Scaleout Suppliers to H.M. the Queens Estate at Sandringham Monarch Water Ltd. Halesworth Road Bramfield IP19 9HP T 01986
More informationLevControl LC PLUS OPERATING INSTRUCTIONS ALL OUR SYSTEMS COMPLY WITH DIRECTIVE 73/23 EEC - 89/336. Cod /0-12/97
LevControl LC PLUS ALL OUR SYSTEMS COMPLY WITH DIRECTIVE 73/23 EEC - 89/336 OPERATING INSTRUCTIONS Cod. 71503277/0-12/97 WARNING!!! THE OPERATIONS LISTED BELOW AND THOSE MARKED BY THIS SYMBOL ARE STRICTLY
More informationivector HEATER/COOLER 2 AND 4-PIPE MODELS.
25278 ivector Installation Guide US 02/01/2013 09:24 Page 2 ivector HEATER/COOLER 2 AND 4-PIPE MODELS. INSTALLATION, OPERATING, MAINTENANCE & AFTER SALES MANUAL JANUARY 2013, ISSUE 1 Product Serial Number:
More informationCQUBE EVO OPERATION MANUAL EVO_OM_VKI_EN. Part No.: _06
EVO_OM_VKI_EN Part No.: 1764212_06 CQUBE EVO OPERATION MANUAL CONTENTS GENERAL INFORMATION...3 Introduction... 3 Warnings... 3 Precautions... 4 Intended use... 4 Hazard intensity levels... 4 Facts & weight...
More informationSILENT 12 PORTABLE AIR CONDITIONER USER MANUAL
SILENT 12 PORTABLE AIR CONDITIONER USER MANUAL Thank you for choosing ElectriQ Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. Visit our
More informationOWNER S MANUAL. Evaporative Cooler. (English) (EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY
OWNER S MANUAL Evaporative Cooler REMOTE CONTROL AUTO COOL FAN SPEED PM ECONOMY ILL239-D ILL1140-A (English) (EXH, EZH) Introduction...4 Remote Thermostat Control...5 Wall Mounted Thermostat Control...11
More information"SXDDR" Series Steam Heat Exchanger Humidifiers
SXDDR-1 Deionized, Demineralized, or Reverse Osmosis Water "SXDDR" Series Steam Humidifiers Looking for an alternative to electrically generated humidification? Concerned about using chemically treated
More informationR410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G09LTCN AO*G12LTCN AO*G14LTCN
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS*G09LTCB AS*GLTCB AS*G4LTCB AO*G09LTCN AO*GLTCN AO*G4LTCN R40A CONTENTS. DESCRIPTION OF EACH
More informationOwner s Manual. Part Number 33CS250-FS and 33CS220-FS
Debonair 33CS Flush-Mounted Flatstat Commercial Programmable Thermostat IMPORTANT: Read entire instructions before programming the thermostat. Owner s Manual Part Number 33CS250-FS and 33CS220-FS GENERAL
More informationUser Operation Manual
APPROVED BY: JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL User Operation Manual PAGE 1 of 6 1 CONTENTS 1. FIRE - GENERAL... 3 2. FIRE - ZONES 1 OR 2 - AUTOMATIC MODE... 3 3. FIRE - ZONES
More informationDX2002 OPERATING AND PROGRAMMING INSTRUCTIONS
DX2002 OPERATING AND PROGRAMMING INSTRUCTIONS The four pushbuttons located at the bottom right of the circuit board are used to do all programming. Each button has more than one function. Alternate Settings
More informationIMPORTANT SAFETY INSTRUCTIONS READ ENTIRE MANUAL BEFORE INSTALLING SPA. PLEASE SAVE THIS MANUAL. OWNER S MANUAL. 8 Button Controller & Pack
PostScript Picture IMPORTANT SAFETY INSTRUCTIONS READ ENTIRE MANUAL BEFORE INSTALLING SPA. PLEASE SAVE THIS MANUAL. OWNER S MANUAL 8 Button Controller & Pack These instructions apply to: D, DC, DE, & DEC
More informationTechnical information for installation and operation
Technical information for installation and operation PR 24002.65 12-04-2016 Subject to technical modifications LogoFresh 100 & 120 fresh water station Electronically controlled GB Meibes System-Technik
More informationUser Manual. Universal Programmable Smart Wi-Fi Thermostat. For Systems Up to 3 Heat / 2 Cool with Wireless Humidity Control*
User Manual Universal Programmable Smart Wi-Fi Thermostat 7320 For Systems Up to 3 Heat / 2 Cool with Wireless Humidity Control* See Wi-Fi Setup Guide for Wi-Fi Setup Instructions Read all instructions
More informationInstructions for the BASIC BCRW Fan, Sizes General
Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation
More informationHEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE
OWNER S MANUAL COMMERCIAL THERMOSTAT P/N P374-2800 I 2 : 0 0 Su AUTO Pm 74 COOL 7 2 HEAT T O T A L I N E HEAT COOL 7-DAY HEAT PUMP PROGRAMMABLE DIGITAL THERMOSTAT 3 Configurable Outputs Control up to 2
More informationMAKING MODERN LIVING POSSIBLE. TP7001 Range Electronic 7 Day Programmable Room Thermostat. User Guide. Danfoss Heating
MAKING MODERN LIVING POSSIBLE TP7001 Range Electronic 7 Day Programmable Room Thermostat Danfoss Heating User Guide TP7001 Electronic 7 Day Programmable Room Thermostat For a large print version of these
More information