Using the Time Delay of Radiant Systems to the Grid s Advantage
|
|
- Beverly Heath
- 5 years ago
- Views:
Transcription
1 Using the Time Delay of Radiant Systems to the Grid s Advantage Introduction Building operators and grid operators often find themselves at odds with one another. A building operator s goal is to create a comfortable environment for the occupants and to minimize occupant complaints of thermal discomfort. In order to do so, air conditioning systems are often run at their maximum capacity during the warmest part of the day to maintain a cool environment inside the space while the temperature rises outside. When all offices in a city respond to the rising afternoon temperatures in the same way, it puts a heavy strain on the electrical grid. For this reason, utilities often charge very high peak rates, and the building operators have sought ways to minimize electrical usage during the warmest part of the day. Some methods for avoiding peak demands include ice storage where the night hours are used to make ice, and cooling during the day is done by having air cooled by passing it over the ice that was formed the night before. Yet, this technique still uses air a natural insulator to conduct heat, and requires high fan energy use. A far more effective means of transporting heat is to use water which can be employed in a radiant system. Radiant HVAC systems have been receiving increased attention in the building community [1]. Radiant systems have been shown to provide better thermal comfort than their air-based counterparts [2]. They are increasingly cost competitive with traditional VAV systems [3]. They are able to use far less energy than air based heating and cooling systems by the nature of their thermal transport property differences. But most importantly, radiant systems reach their peak loads at very different times than conventional air systems do. As a result, having a number of buildings operating with radiant systems can provide a counterbalance to the typical load profiles of buildings with air-based heating and cooling. Because of this, the building operators are no longer pitted against grid operators. A building operator with a radiant system can run a radiant system in such a way as to maximize occupant comfort without worrying about having high peak demand charges from the utility. Unfortunately, radiant systems are relatively few in comparison with VAV systems, and either through miscommunication or a lack of sophisticated controls, they are sometimes managed as if they are air systems where the controllers call on the system to operate at full capacity during the hottest part of the day, when in fact this is entirely unnecessary. The nature of this research is to determine a more effective control system that maintains thermal comfort while shifting peak consumption to an earlier time.
2 Understanding Radiant System Operation There is a fundamental difference in the way that a radiant system keeps a space cool and the way that an air system keeps a space comfortable. In some sense it is a strange phenomenon that most buildings in the U.S. today are heated and cooled by air. Using air as a media to transport heat is thermodynamically inefficient. Water on the other hand is an excellent medium for transporting heat at temperatures suitable for building operation. It is almost a thousand times denser than air (832 times at STP) and has a much higher specific heat. Thus, a cubic centimeter of water can transport heat far more efficiently than a cubic centimeter of air at atmospheric conditions. Radiant systems are much more closely matched to how the human body exchanges heat as well. The human body exchanges its heat through 47% radiant transfer, 28% convective transfer, and 27% through exhalation and other processes [1]. However, many HVAC systems for buildings still marry their ventilation to their heating and cooling, which requires large fans and very large ductwork. Radiant systems have been installed in the past; there was a brief infatuation with the technology in the 1950 s. Even Frank Lloyd Wright was known to design them into his homes, like the Gordon House in Oregon. Unfortunately, these systems were often plagued by poor construction techniques and materials that failed to contain the water that would leak out from the pipes at the soldered joints [1]. As such, radiant systems in the United States fell out of favor in the building industry and all-air systems became the dominant vogue. Today, they are seeing a renaissance as architects seek to design buildings that are more comfortable and use less energy than their neighbors. One of the advantages of radiant systems is that a space can be considered thermally comfortable even at high indoor temperatures as long as the surrounding surfaces are kept at a cooler temperature and vice-versa. For example, if one leaves their car parked in the sun during the summer, it is a very unpleasant experience getting in and driving home. The driver will spend the first five minutes sweating even though the car s air conditioning is usually turned up to its maximum. Yet even with using lots of energy to blow cold air into the car, all the surfaces are hot to the touch, making it feel uncomfortably warm until the cold air eventually lowers the surface temperatures through convection (a very thermally inefficient process). This is how most buildings work during the peak cooling hours. The building has been sitting in the sun all day, with the radiant gains of the sun pouring in and heating up the walls and the floors. The air conditioning must ramp up to meet these needs at the worst possible time, and even then it may not be enough to provide comfort people will either be too close to a duct and be too cold, or will be too far away from one, and will be too warm. Imagine then reversing the scenario, so that on a hot summer day, your car seats had been kept at a very cool temperature the driver would not feel discomfort, even if the ventilation air blown into the car was not particularly cold. This is how a radiant system works it should circulate cool water all day to remove the heat from the sun, lights, computers, and occupants before it builds up. With a cool surface, the space can feel comfortable at an operative space temperature of 70 o F even if the air temperature is 85 o F as long as the surface temperatures are kept below 63 o F. Whereas for an airbased HVAC system, an air temperature of 58 o F is required to keep the same operative temperature when the surfaces are at 80 o F [1].
3 In an attempt to show their skill at energy-savvy design, an architecture firm recently renovated an old steel warehouse and installed a radiant slab for heating and cooling. It is one of the first businesses of its kind to have a radiant system designed to take care of the entire cooling needs of the space in the state of Idaho. Even so, the engineers installed a supplementary Roof Top Unit (RTU) system just in case the thermal comfort parameters in the space could not be met by the slab alone. One reason for the firm s trepidation for leaving the slab completely in charge of cooling the space is that radiant systems are notoriously difficult to manage. Most HVAC management systems today define thermal comfort in terms of indoor air temperature. In order for a radiant system to affect temperature, the fluid must first conduct enough heat to the surface to a temperature that has enough of a difference from the indoor air with the space that convection can occur. Eventually, the convection from the radiant surface is enough to affect the indoor air temperature. However, this can take hours to occur. For this reason, the time scales at which radiant and air systems see gains are very different. It is as though they communicate in two different languages. Solar gains are particularly difficult to deal with for HVAC systems of all types. When the sun strikes a surface, a person can feel the gain immediately. If the sun strikes a radiant (or thermally activated) surface, this is also an immediate gain that the system has to handle. However, for a system controlled by a thermostat measuring air temperature, it can take hours for the solar gain to be sensed. This observation was noted in a recent ASHRAE Journal publication by Bauman et al. [3]. In this article, the authors propose that while radiant systems still save significant amounts of energy, they may in fact have higher peak loads which occur earlier in the day than for an all-air system which senses loads based on rises in the indoor air temperature. The authors present an intriguing graph of required cooling rates as computed for a space in an EnergyPlus simulation as shown in Fig. 1: Figure 1: Contrasting Cooling Rates Required of Radiant and Air Systems from [3] The radiant loads appear to require a higher cooling rate because once again, these are sensing radiant loads in the space from the sun, lights, computers, occupants, etc... These gains take many minutes or even hours to be translated to the air temperature and affect the thermostat and air loads via convection. And, while the cooling rate may be higher, the radiant system will still likely use less energy, because it will cost less to transport that heat with a small amount of water through pumps than a large amount of air through fans.
4 Identifying a Better Control System In order to quantify the specific peak load and consumption profiles of the architecture firm for this case study, a research team installed over 70 data loggers throughout the space to monitor performance. These instruments included power and temperature sensors on each of the HVAC components including the RTUs, heat pumps, an Energy Recovery Ventilator (ERV), and cooling tower. The temperature of the slab was also monitored at four different points using thermocouples. The mean radiant temperature of the space was measured by means of a thermocouple embedded in a black hollow sphere [4] and was recorded in three different locations throughout the open office area. These instruments are providing physical data which can be compared against the suggested load profiles of Bauman et al. [3]. The research team was also granted access to all of the data being processed by the building s Energy Management System (EMS). All of this data will also serve to verify and calibrate the energy model that was the main focus of research for the past months. As building owners and occupants of fully functioning offices are often loathe to allow researchers to change system operations. These experiments could lead to the stressing of certain pieces of equipment or thermal discomfort for the occupants. Instead of managing the entire building s systems, these experiments will be performed on a virtual energy model of the building. This model was developed in OpenStudio 1.4 which is an interface for the DOE program EnergyPlus 8.1. Figure 2: EnergyPlus model of demonstration project as viewed in SketchUp EnergyPlus allows users to run the simulations and analyze temperatures throughout the space and even provide estimations of what the occupants comfort level might be in a metric called the Predicted Mean Vote (PMV). The PMV provides a parameter for various control schemes. The goal of these new
5 controls will be to regulate the system in such a way as to avoid heavy operation during peak hours and to minimize overall consumption. It was noted that air and radiant systems communicate as if in two different languages. Consequently, they must be controlled differently. Air systems must respond to air temperature control signals, while radiant systems must respond along surface temperature time scales. While EnergyPlus allows some flexibility in various operational schedules, interfacing with the virtual energy management system within the program can prove to be quite challenging and requires the user to learn a new computer language that is somewhat like the language Perl. In order to avoid this, the research team has decided to instead develop control schemes in Matlab and to apply those schemes to the EnergyPlus model through a couple of programs called Matlab-EnergyPlus (MLE+) and Building Controls Virtual Test Bed (BCVTB). BCVTB was developed by a team at Lawrence Berkeley National Lab as a way to connect EnergyPlus to outside programs. MLE+ was developed at the University of Pennsylvania and used BCVTB as a way to connect Matlab to EnergyPlus. These programs can also be used to link to a BACnet interface so that a controller can be programmed and installed physically based on the commands developed in Matlab and the energy information received inside EnergyPlus. The energy model of the architecture firm can be linked to the Matlab program so that the radiant system may be managed in new ways. The current arrangement in the physical building is for the slab to pre-cool the space only at night and then shut off before the occupants arrive. The commands sent to the heat-pumps operating the radiant floor system take their cue from a thermostat on the wall. The proposed scheme is based on Model Predictive Control (MPC). MPC is an optimization based strategy in which an explicit model is used to predict the behavior of the controlled plant over a receding window into the future [5]. It is a form of hard control linked to some sort of model inside a program (like EnergyPlus in this case). The model controls rely on historic and real-time data (occupancy profile, current weather and forecasted conditions, a test building s sub-metered data) to predict control parameters of a building s heating, cooling and ventilation systems. Linking the simulation to the control system can generate predicted building responses to varying inputs and thermal comfort ranges. With the rise in computing capabilities, MPC schemes have become increasingly feasible for controlling building HVAC systems. Developing MPCs unique to different HVAC components is an area of ongoing research, but has already proven capable of providing significant savings over conventional energy management systems. An MPC was applied to a district chiller on the campus of UT Austin and was able to save 9% of their energy usage and cost savings of up to 17% by reducing consumption during peak hours [6]. Other MPC systems have shown even more dramatic energy savings of 30-70% [7]. This set-up can be run passively where the information from the MPC is merely analyzed and compared to the existing controls or it can be used to actively manage the building s systems according to the model. This project is based on a passive system to analyze the results. Test implementation and active management of the system remain as areas of future work for this continuing project. Even though the MPC will be implemented passively without active control over
6 hardware the energy consumption profile of the scheme will be compared to the baseline system of packaged air handlers and their peaks and variations with temperature contrasted. Summary and Future Work Since radiant systems have such a different time variance and thermal profile from forced-air systems, this should provide insight into how to most effectively manage radiant controls. This research leverages the ability of MPC to manage radiant systems in a sensible manner. Successful implementation and a demonstration of the theoretical savings for a real building in the Pacific Northwest could further encourage the adoption of radiant systems that use far less energy than typical forced-air HVAC systems. This model will also be compared against utility data in short time intervals to minimize consumption during peak demand periods. Another advantage to MPC is that various systems can be linked together. This currently remains an area for future research in the coming months. For example, in addition to controlling several of the HVAC components, the controller built in EnergyPlus could also govern a dynamic façade. As mentioned previously, radiant slabs that serve to alternately heat and cool a space operate on much longer timescales than many other HVAC components and are dramatically affected by solar gains through unobstructed windows. This makes radiant slabs and active façades prime candidates for comprehensive governance by an MPC. Other work in this area could include the implementation of indoor comfort modules that monitor the thermal comfort performance of the system in real time and actively manage the control settings. From this, a design guide could be developed for buildings with different types of radiant HVAC systems. The current state of the research involves calibrating the energy model of the building in order to set the MPC on a verified foundation so that the virtual building will respond to control signals the same way the actual building might. As the energy consumption data is processed, and the predictive control tuned to this building, the research team aims to identify means of aligning occupant comfort with minimum peak demands. Of course, human s earliest dwellings (caves) were in fact net zero and used no electricity whatsoever. These were not however comfortable working environments. Someday though, it is hoped that many offices can exist with content occupants, relaxed building operators, and less demand on the grid during peak hours. The goal of this research is to facilitate that kind of future.
7 References [1] K. Moe, Thermally Active Surfaces in Architecture, 1 edition. New York: Princeton Architectural Press, [2] R. Rumsey and G. Sastry, VAV vs. Radiant Side-by-side Comparison ASHRAE JOURNAL, vol. 56, no. 5, pp , [3] F. Bauman, J. Feng, and S. Schiavon, Cooling Load Calculations For Radiant Systems, ASHRAE JOURNAL, vol. 55, no. 12, pp , [4] E. Berg et al., ASHRAE Handbook HVAC Applications, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. 2011, [5] Ma, Jingran., Qin, Joe,. Salsbury, Timothy., Xu, Peng Demand Reduction in Building Energy Systems Based on Economic Model Predictive Control. Chemical Engineering Science, 67(2012), [6] Powell, Kody., Cole, Wesley., Ekarika, Udememfon., Edgar, Thomas. (2012). Optimal Chiller Loading in a District Cooling System with Thermal Energy Storage. Energy, 50(2013), [7] Afram, Abdul., Janabi-Sharifi, Farrokh. (2013) Theory and Applications of HVAC Control Systems A Review of Model Predictive Control (MPC). Building and Environment, 16(11).
Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for
More informationSYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC
VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things
More informationRadiant Cooling Nonresidential HVAC Stakeholder Meeting #2
1 Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program Abhijeet Pande Heschong Mahone Group, Inc. Kristin Heinemeier Western Cooling Efficiency
More informationMarch 2014 AHRI Presents Research Findings at Low-GWP AREP Conference
March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference In addition to its regular research activities, AHRI is conducting the Low-Global Warming Potential Alternative Refrigerants Evaluation
More informationCooling load calculations of radiant and all-air systems for commercial buildings
Downloaded from orbit.dtu.dk on: Aug 17, 2018 Cooling load calculations of radiant and all-air s for commercial buildings Bourdakis, Eleftherios; Bauman, Fred; Schiavon, Stefano; Raftery, Paul; Olesen,
More informationHow to ensure Thermal Comfort in buildings with CFD
How to ensure Thermal Comfort in buildings with CFD Using CFD Simulations to analyze and improve HVAC Systems Simulation in your browser How to Ensure Thermal Comfort in Buildings with CFD How to use CFD
More informationDemonstration of 2nd Generation Ducted GE "Brillion" Hybrid Water Heater in the PNNL Lab Homes
Demonstration of 2nd Generation Ducted GE "Brillion" Hybrid Water Heater in the PNNL Lab Homes 2013 ACEEE Hot Water Forum Sarah Widder Research Engineer Pacific Northwest National Laboratory Project Participants
More informationImproving Control of Dual-Duct Single-Fan Variable Air Volume Systems
Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems Guanghua Wei, P.E. Joe Martinez Tom Minihan Assistant Research Engineer Research Engineering Associate Graduate Student Tim Brundidge
More informationMechanical System Redesign. Dedicated Outdoor Air System. Design Criteria
Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed
More informationThermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia
IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia To cite this article: N A Malek
More informationOpen Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System
Send Orders for Reprints to reprints@benthamscience.ae The Open Electrical & Electronic Engineering Journal, 215, 9, 7-14 7 Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning
More informationUsing Embedded Tube Radiant Cooling Systems to Maximize LEED Points
San Joaquin ASHRAE Chapter Using Embedded Tube Radiant Cooling Systems to Maximize LEED Points Devin Abellon, P.E. Business Development Manager Uponor November 4, 2010 LEED v3 new construction LEED Topic
More informationChilled Beams. Getting a Warmer Reception
Chilled Beams Getting a Warmer Reception Gain an understanding of how chilled-beam technology works, the difference between active/passive chilled beams and potential applications for its use. B y G r
More informationAs mentioned earlier, the fundamental purpose of HVAC systems is to provide human comfort.
Human Comfort Section Preview This section discusses the following topics: Factors of human comfort including air temperature, motion and cleanliness, and the relative humidity of the air HVAC engineering
More informationChilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget
VanceFox.com 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal Vol. 49, Jan. 2006. For personal use only. Additional reproduction,
More informationRadiant Heating & Cooling for Commercial Buildings
Radiant Heating & Cooling for Commercial Buildings Kaveesh Padiachy, PEng, PMP, LEED AP Business Development Manager Central Canada kaveesh.padiachy@uponor.com www.uponorpro.com/engineering Radiant Heating
More informationCommercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark
Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office
More informationASHRAE JOURNAL ON REHEAT
Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide
More informationMechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013
Mechanical Redesign, Proposal Elizabeth C. Mechanical Option September 18, 2013 State Institute of Rehabilitation T e c h n i c a l R e p o r t I 1 Mechanical Redesign, Proposal... 0 Executive Summary...
More informationENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory
Overview of Chilled Beam Technology Purpose Chilled beam technology is new to the United States but has been used in Europe since the 1950 s. Chilled beams can reduce energy costs, improve indoor air quality,
More informationVENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING
VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING Rebeca Barbosa 1, Martin Barták 1, Jan L. M. Hensen 1, 2, Marcel G. L. C. Loomans 2 1 Czech Technical
More informationCARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.
Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using
More informationPassive building in Hot and Humid Climates
9 th Annual North American Passive House Conference Passive building in Hot and Humid Climates Lisa White 1 Overview 1. Thermal Comfort 2. Drivers of sensible and latent cooling loads 3. Passive cooling
More informationSenior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1
Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9
More informationState-of-the-art Developments to Save Energy in Coating Drying
State-of-the-art Developments to Save Energy in Coating Drying Executive Summary Coating drying is expensive. A great deal of energy is needed to effectively evaporate sufficient water to dry the coating.
More informationRADIANT COOLING SYSTEMS OPPORTUNITIES FOR RADIANT COOLING IN NORTH AMERICAN CONSTRUCTION DALE HANSCOMB, REHAU Sales Manager Building Technology
RADIANT COOLING SYSTEMS OPPORTUNITIES FOR RADIANT COOLING IN NORTH AMERICAN CONSTRUCTION DALE HANSCOMB, REHAU Sales Manager Building Technology www.rehau.com Construction Automotive Industry LEARNING OBJECTIVES
More informationExperimental study of space cooling using ceiling panels equipped with capillary mats
Experimental study of space cooling using ceiling panels equipped with capillary mats Tiberiu Catalina and Joseph Virgone University of Lyon, France Corresponding email: tiberiu.catalina@insa-lyon.fr SUMMARY
More informationDevelopment of a Building Automation Laboratory
Session 1633 Development of a Building Automation Laboratory William J. Hutzel Purdue University, West Lafayette Abstract The Applied Energy Laboratory within the School of Technology at Purdue University
More informationTHE PRESSURIZED CONDENSATE RECOVERY SYSTEM:
BEST PRACTICE NO. 51 THE PRESSURIZED CONDENSATE RECOVERY SYSTEM: the solution to increasing a steam system s thermal cycle efficiency Pressurized condensate systems can provide plants with a minimum of
More informationA Technical Introduction to Cool Thermal Energy Storage Commercial Applications
A Technical Introduction to Cool Thermal Energy Storage Commercial Applications Cool Thermal Energy Storage is a new application of an old idea that can cut air conditioning energy costs in half while
More informationComfort and health-indoor air quality
Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental
More informationAnalysis and Evaluation of a Passive Evaporative Cool Tower in conjunction with a Solar Chimney
PLEA2005 - The 22 nd Conference on Passive and Low Energy Architecture. Beirut, Lebanon, 13-16 November 2005 1/6 Analysis and Evaluation of a Passive Evaporative Cool Tower in conjunction with a Solar
More informationSPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview
SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview As in residential buildings the purpose of mechanical conditioning and ventilation is to maintain air quality and thermal comfort in buildings, with
More informationTechnical Assignment 3
0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Technical Assignment 3 Mechanical Systems and Existing Conditions Report David H. Koch Institute for Integrative
More informationLiquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements. White Paper
Liquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements White Paper Abstract Cooling represents the third leading use of energy and source of carbon emissions in
More informationGROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE
Conference on Sustainable Building South East Asia, -7 November 27, Malaysia GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE G. REIMANN IEN Consultants,
More informationOptimisation of cooling coil performance during operation stage for improved humidity control
Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 741 Optimisation of cooling coil performance during operation stage for improved humidity control S.C. Sekhar * and L.T. Tan National
More informationT-Series Climate Changer Air Handler. It s Hard To Stop A Trane.
T-Series Climate Changer Air Handler TM It s Hard To Stop A Trane. T-Series Climate Changer Air Handler The Trane tradition of excellence continues with the T-Series Climate Changer air handler. Using
More informationterminal units only provide sensible cooling, a separate dehumidification system is usually needed.
providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can
More informationInternational Forum on Energy, Environment Science and Materials (IFEESM 2015)
The Comparison and Analysis of Humidity Environment between Floor and Ceiling Radiant Cooling Systems that Combined with Displacement Ventilation Kai SUN 1 a *, Chuan-hui ZHOU 1 1 College of Urban Construction,
More informationTHERMAL ANALYSIS OF CAR AIR COOLER
Journal of KONES Powertrain and Transport, Vol. 8, No. THERMAL ANALYSIS OF CAR AIR COOLER Daniel Trzebiski Silesian University of Technology, Institute of Thermal Technology Konarskiego Street, - Gliwice,
More informationFike set out to develop a better understanding of the power density trends in data centers around the world.
Fike set out to develop a better understanding of the power density trends in data centers around the world. We wanted to learn how increasing power density translates into energy augmented combustion.
More informationmaximize displacement ventilation Opportunities
maximize displacement ventilation Opportunities DESIGN STRATEGIES In Seattle, the Amazon Headquarters building, features an open air atrium that provides natural ventilation throughout the facility. DESIGN
More information4-Pipe VAV vs. Active Chilled Beams for Labs
Steven T. Taylor 4-Pipe VAV vs. Active Chilled Beams for Labs BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE Variable air volume (VAV) laboratory HVAC systems, including VAV fume hoods, are now standard practice
More informationCompression of Fins pipe and simple Heat pipe Using CFD
Compression of Fins pipe and simple Heat pipe Using CFD 1. Prof.Bhoodev Mudgal 2. Prof. Gaurav Bhadoriya (e-mail-devmudgal.mudgal@gmail.com) ABSTRACT The aim of this paper is to identify the advantages
More informationAPPLICATION OF CFD SIMULATIONS FOR LOCATING OUTDOOR UNITS ON HIGH RISE TOWER Basant Kumar Gupta 1, Anand Patil 2
APPLICATION OF CFD SIMULATIONS FOR LOCATING OUTDOOR UNITS ON HIGH RISE TOWER Basant Kumar Gupta 1, Anand Patil 2 1 Zeus Numerix Private Limited, Pune, India 2 Pankaj Dharkar & Associates, Mumbai, India
More informationThe Corbioli House is a single-family house situated
All-in-one high-performing system for ZEB houses Maria Ferrara Grant researcher TEBE Research Group Energy Department Politecnico di Torino at Turin, Italy maria.ferrara@polito.it Frederic Kuznik Full
More informationAir and operative temperature measurements in a plus-energy house under different heating strategies
Downloaded from orbit.dtu.dk on: Oct 03, 2018 Air and operative temperature measurements in a plus-energy house under different heating strategies Kazanci, Ongun Berk; Olesen, Bjarne W. Published in: Proceedings
More informationω = (1) Kirby S. Chapman Ph.D.
White Paper: Relative Humidity Impacts of the AirFloor System in the Built Environment Kirby S. Chapman Ph.D. kirby.chapman@scavengetech.com Introduction Relative humidity is specified as one of the seven
More informationExperimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump
Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump Koji Fujita, Graduate Student, Graduate School of Science and Technology, Kobe University; 039d892n@stu.kobe-u.ac.jp Atsushi
More informationHuman response to thermal environment in rooms with chilled beams
Human response to thermal environment in rooms with chilled beams Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, Risto Kosonen 3 1 International Center for Indoor Environment
More informationFeasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System
Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang
More informationDesign Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Design Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems Building
More informationThe Current (2017) State of the Art for Air Leakage in Ductwork
The Current (2017) State of the Art for Air Leakage in Ductwork Over the last ten years there has been a major shift in the way ASHRAE has approached air leakage in ductwork. This is reflected in the latest
More informationThe Basics of Package/Device Cooling
The Basics of Package/Device Cooling Various cooling methods are available for keeping electronic devices within their operating temperature specifications. Cooling Consumer Products In the case of consumer
More informationVariable Refrigerant Flow (VRF) Systems
Variable Refrigerant Flow (VRF) Systems Flexible Solutions for Comfort Carrier Corporation Syracuse, New York January 2013 TABLE OF CONTENTS INTRODUCTION... 2 VRF TECHNOLOGY... 2 ADVANTAGES OF A VRF SYSTEM...
More informationUFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas
UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully
More informationGEOTHERMAL DESIGN GUIDE
GEOTHERMAL DESIGN GUIDE BENEFITS OF THE BULLDOG SYSTEM CGC Version CGC Group of Companies Incorporated 2018 CONTENTS INTRODUCTION... 2 CHALLENGES FACING CONVENTIONAL GSHP SYSTEMS... 3 FACTORS WHICH IMPACTS
More informationDon t Turn Active Beams Into Expensive Diffusers
This article was published in ASHRAE Journal, April 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
More informationEnergy: Synthesis and Analysis
Energy Use in the Home Introduction Energy: Synthesis and Analysis The average household spends over $1,300 a year for energy to run the many devices found in the home 1. The vast majority of this cost
More informationALFAMINI-ALFAMAX Central Station air handling units high efficiency for wellness areas
ALFAMINI-ALFAMAX Central Station air handling units high efficiency for wellness areas 1 The plants are quite complex and, therefore, "Fascinating from engineering point of view Conditioning plants are
More informationDaikin Blueprint: Delivering Hot Water with a Chiller
Daikin Blueprint: Delivering Hot Water with a Chiller Analyzing the design of heat recovery on air-cooled chillers and the effect it has on building energy consumption By Paul Crisman Daikin Chiller Applications
More informationChilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle
Chilled Beam and Radiant Cooling Basics Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle nsearle@dadanco.com Contents Radiant Ceilings & Chilled Beam Basics Energy & Space Savings First and
More informationIAQ: Re-tuning Commercial Buildings
IAQ: Re-tuning Commercial Buildings A low-cost path to improved air quality and energy efficiency. B y S c o t t G o r d o n, C M All images courtesy of Johnson Controls Service. 10 RSES Journal FEBRUARY
More informationImpact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System
4 th International Conference On Building Energy Environment Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System J Y Park H W
More informationEnergy Recovery Ventilation
Published on Business Energy Advisor (https://oncor.bizenergyadvisor.com) Home > Energy Recovery Ventilation Energy Recovery Ventilation Proper ventilation is essential for maintaining good indoor-air
More informationSmall Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.
Small Commercial Business Energy Audits Recognizing and addressing the special requirements of the small business market segment. Class 7 Class 7: Refrigeration Fundamentals The Vapor-compression cycle
More informationExperimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant
Proceedings of the World Congress on Momentum, Heat and Mass Transfer (MHMT 16) Prague, Czech Republic April 4 5, 216 Paper No. ENFHT 111 DOI: 1.11159/enfht16.111 Experimental Investigation of a Multi
More informationV4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY)
V4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY) ACN 114 572 084 "Driving Sustainability through Teamwork" e: pcthomas@teamcatalyst.com.au m: 0417 405 478 CALCULATING COOL USER GUIDE V4 15JUNE2016 Page
More informationMODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS
MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS Clayton Miller 1,* and Chandra Sekhar 1 1 National University of Singapore, Singapore * Corresponding email: miller.clayton@nus.edu.sg
More informationIT S HOT UP HERE! A STUDY OF THERMAL COMFORT IN THE LILLIS BUSINESS COMPLEX 4TH FLOOR OFFICES
IT S HOT UP HERE! A STUDY OF THERMAL COMFORT IN THE LILLIS BUSINESS COMPLEX 4TH FLOOR OFFICES Martha Bohm M.Arch Candidate 2006 University of Oregon Eugene, OR 97403 Will Henderson M.Arch Candidate 2006
More informationSelected Laboratory Energy Efficiency Measures
Selected Laboratory Energy Efficiency Measures These are some of the most effective energy efficiency measures for laboratories 1. Reduce (optimize) air changes per hour in lab space 2. Design to the proper
More informationTrane Family of Terminal Products
Trane Family of Terminal Products It s time to take another look at terminal. As your partner, Trane understands it takes more than a concept to design an effective HVAC system. Between cost and code compliance
More informationKE2 EvaporatorEfficiency Theory of Operation
Theory T.1.1 June 011 TM thermsolutions ENTER BACK KE Therm Solutions, Advanced Energy Saving Technology for Commercial Refrigeration and AC Systems Page Table of Contents Basic Refrigeration System Evaporator
More informationCARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems
Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.
More informationRADIANT COOLING RESEARCH SCOPING STUDY
INTERNAL REPORT APRIL 2006 RADIANT COOLING RESEARCH SCOPING STUDY Timothy Moore, Fred Bauman, and Charlie Huizenga Center for the Built Environment (CBE) University of California, Berkeley April 20, 2006
More informationTemperature Control of Heat Exchanger Using Fuzzy Logic Controller
Vo1ume 1, No. 04, December 2014 999 Temperature Control of Heat Exchanger Using Fuzzy Logic Controller Aravind R. Varma and Dr.V.O. Rejini Abstract--- Fuzzy logic controllers are useful in chemical processes
More informationEngineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.
VAV Diffusers lease refer to the rice Engineer s HVAC Handbook for more information on VAV Diffusers. Diffuser Types Ceiling Diffusers Conventional air distribution systems typically group several rooms
More informationDesign Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System
Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,
More informationABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA R, ANUPRAJ JATHANNA, ARUN M KRAMADHARI
International Journal of Scientific & Engineering Research Volume 9, Issue 4, April-2018 238 ANALYSIS OF RADIANT COOLING IN CONCRETE SLABS WITH EMBEDDED PIPES ABHINAVA KARABA, V VIJENDRA BHAT, PRAMOD UPADHYAYA
More informationWhat is Smart Watering?
What is Smart Watering? What is Smart Watering? Smart Watering provides plants the exact water they need, when they need it without requiring continuous manual adjustment. Blossom s Smart Watering algorithm
More informationChallenges and Methods of Estimating a Conceptual HVAC Design
Challenges and Methods of Estimating a Conceptual HVAC Design ABSTRACT In any conceptual HVAC design, estimators are faced with the challenge of trying to capture all of the pieces that complete a system.
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More information2. CURRICULUM. Sl. No.
. CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration
More information1.1. SCOPE OF THE WORK:
Chapter 1: Introduction 1 1. INTRODUCTION 1.1. SCOPE OF THE WORK: Multi-stage refrigeration systems are an area of growing industrial importance in large plants. These systems are known to be large power
More informationHot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump
Available online at www.sciencedirect.com Procedia Engineering 8 (2011) 165 170 2 nd International Science, Social-Science, Engineering and Energy Conference 2010: Engineering Science and Management Hot
More informationNOVEMBER 2012 THE EUROPEAN EXPERIENCE
Radiant-cooling systems have progressed in the last few decades, garnering attention as a comfortable and energy- and material-efficient option. 1 Compared with air radiant-cooling hydronic systems use
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationENGINEERING. Edition No. 13 October 2002
Edition No. 13 October 2002 ENGINEERING S Y S T E M S O L U T I O N S W e at McQuay are very proud of our tradition of producing industry leading water source heat pumps. Our heritage stretches back more
More informationREPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop
Energy-Savings Strategies for Rooftop VAV Systems Occupied set-point temperature Unoccupied set-point temperature Rooftop variable-air-volume (VAV) s are used to provide comfort in a wide range of building
More informationCenter for the Built Environment October 2013
Thermal Comfort in the Context of Radiant Systems Center for the Built Environment University of California Berkeley Center for the Built Environment October 2013 Overview of talk A brief summary of research
More informationGENSET ENGINE HEATING IN A DATA CENTER ENVIRONMENT
GENSET ENGINE HEATING IN A DATA CENTER ENVIRONMENT Performance analysis of forced circulation heaters versus thermosiphon heaters installed on standby generators. October 2015 Devin Parker TABLE OF CONTENTS
More informationGHS VSD+ SOLUTIONS FOR CENTRALIZED VACUUM
GHS VSD+ SOLUTIONS FOR CENTRALIZED VACUUM Some key components: the engine, brains and remote communication options of your central system described in detail THE ENGINE OF YOUR CENTRAL SYSTEM The engine
More informationMechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation
Mechanical Technical Report 1 Standard 62.1 Ventilation Compliance Evaluation Lutheran Theological Seminary at Philadelphia The New Learning Center Prepared For: William P. Bahnfleth, Ph.D., P.E. Department
More informationReduced Order WECC Modeling for Frequency Response and Energy Storage Integration
Reduced Order WECC Modeling for Frequency Response and Energy Storage Integration Pranathi Bhattacharji, Student Member, IEEE, Ted K. A. Brekken, Senior Member, IEEE School of Electrical Engineering and
More informationMeasurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.
Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation. Bengt Perers 1, Elsa Andersen 2, Simon Furbo 2, Ziqian Chen 2 and Agisilaos
More informationDisplacement Ventilation in Classrooms
TWO DIFFUSERS, THE WHITE COLUMNS ON EACH SIDE OF THE WHITEBOARD, PROVIDE COOL SUPPLY AIR TO THE DEMONSTRATION DV CLASSROOM. THE DV CLASSROOM DEMONSTRATION FEATURED A CUSTOMIZED ROOFTOP HVAC UNIT. Displacement
More informationHow to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs
How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada
More informationHeat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling
Enhancement using Herringbone wavy & Smooth Wavy fin Exchanger for Hydraulic Oil Cooling 1 Mr. Ketan C. Prasadi, 2 Prof. A.M. Patil 1 M.E. Student, P.V.P.I.T.,Budhagaon,Sangli AP-India 2 Associate Professor,
More informationMadeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)
Madeira City Schools Madeira, Ohio HVAC Assessment December 2011 (Revised February 2012) Prepared by: CMTA Engineering Consultants, Inc. 10411 Meeting Street Prospect, KY 40059 www.cmtaegrs.com (502) 326-3085
More information