1 Eden Mills Community Hall York Street Eden Mills, ON Energy Audit For Eden Mills Going Carbon Neutral 22 April 2009 Prepared by Enermodal Engineering Limited 650 Riverbend Drive Kitchener, ON N2K 3S2 tel: fax: web site:

2 Eden Mills Community Hall Energy Audit prepared for Eden Mills Going Carbon Neutral 22 April 2009 Richard Lay, P.Eng., Christianne Aussant Enermodal Engineering Page i

3 Index Introduction 1 Description of Building 1 Construction 2 Mechanical Equipment 4 Energy Use 4 Blower Door Test 5 Energy Simulation Model and Results 8 Analysis of Energy Conservation Measures 15 Greenhouse Gas Reductions 25 Recommendations 26 Appendices A Energy Costs B Blower Door Air Leakage Test Results C Air Sealing Article D Heating Cost Comparison Enermodal Engineering Page ii

4 Introduction Enermodal Engineering Ltd undertook this energy audit for the Eden Mills Going Carbon Neutral Project, a project of Eden Mills Millpond Conservation Association, during the spring and summer of We conducted an inspection of the building, with particular attention to the mechanical system and building envelope. We performed a blower door test to depressurize the building and measure the leakiness of the building envelope. We created an energy simulation model to estimate the energy use by a various building functions and through the components of the building. Based on this information, we reviewed various possible building modifications and estimated how much they could reduce the annual energy use. The focus of this report is therefore on energy use and potential for reduction rather than on the physical condition of the building. Description of building Address: 108 York Street, Eden Mills ON N0B 1P0 Owner: Eden Mills and District Community Club Inc. Date of construction: early 1900s, with renovations and additions Gross Floor Area: 5,378 sq ft (502.6 sq m) including new stairwell solid brick building built in 1900 and renovated with an addition to the north for a stage upstairs meeting room, a second floor balcony addition for a small storage room overhanging the sidewalk along York Street and an exit stairway to the East, View from York St, showing wall construction, overhanging storage room Enermodal Engineering Page 1

5 The hall is used for community functions including meetings, entertainment, activities of community groups, and rented for various social functions. It is used most days of the week and year round. Main meeting, assembly and dance hall. Plaster on lath on brick walls. Operable double hung DG windows Construction stone foundation on bedrock slab on grade ground floor in a stone foundation walls at ground floor level, mortar plaster, drywall or wood finishing board solid brick walls at second floor level of original building, mortar plaster, plaster (This construction can be seen in the attic above the hall ceiling) 2x4 wood framed walls on additions peaked roof, framed on site, asphalt shingles and Enermodal Engineering Page 2

6 Windows: vinyl frame, cleared double glazed sealed units, operable horizontal slider bottom sections. About 20 yr old in the main building. View from rear, showing framed addition on masonry block foundation View from parking lot. Older hall to right, Centennial addition to left Insulation: slab on grade floor none stone and brick walls none framed walls of back addition R12 ceiling of second floor hall approximately 4 inches of loose fill mineral fiber, placed directly on top of wood ceiling with no air barrier =>R15 Enermodal Engineering Page 3

7 Mechanical Equipment 2 high efficiency propane furnaces, 50,000 BTU/h output, nominal 94% efficiency, Bryant Model 350MAV ABKA B, nominal cfm airflow. 2 split air conditioning units, DX coils in furnace plenums, Luxaire Model HABA F0365 outdoor units L (40 gallon) electric storage tank water heater, 3 kw Local exhaust fan in downstairs washroom Well water system: submersible pump, UV sterilizer Wastewater: on site septic tank and disposal bed 2 high efficiency propane forced air furnaces. Electric domestic water heater. Enermodal Engineering Page 4

8 Energy Use The Hall has reduced its consumption of electricity and propane over the last 3 years, as shown in Table 1 below. See also Appendix A. Table 1: Electricity & Propane Metered energy use EMCC fiscal year Electricity (kwh) Propane (L) The 2007 electricity use was 43 kwh/day over the whole year. However, Electricity use in the most recent period of 295 days from June 2008 to April 2009 was lower 38 kwh/d, showing a continuing reduction in use. This is comparable to typical household use in Eden Mills. Of this total, domestic hot water (DHW) accounts for 2.6 kwh/d (measured by run time meter over 354 days from April 2008 to April 2009). The total energy use intensity in 2007 was [15,130 + (5,362 x 7.06)]/502.6 = 105 kwh/sq m d. This is relatively low compared to other institutional buildings in Canada, partly because it is not occupied fulltime. Blower Door Test Building scientists agree that building envelopes should be airtight and ventilation should be at controlled rate and location. Uncontrolled leakage that varies with outdoor conditions (wind, temperature) does not benefit the durability of the building, occupant comfort or energy operating costs. A Minneapolis Blower Door was installed in the west exterior door to the parking lot and operated to depressurize the building to 50 Pa negative pressure. Fan air flow was measured at this and intermediate pressures in order to determine the equivalent leakage area of the building envelope according to normally accepted practice. Results are shown in Appendix B. Also, a number of air leakage paths were identified using a smoke pencil. Summary Results: Equivalent Leakage Area: sq m Normalized Leakage Area: 3.3 cm2/m2 Leakage Rate: 5.18 air changes per 50 Pa Enermodal Engineering Page 5

9 (New tight construction is less than Pa) Normalized Leakage Rate: Pa Estimated Leakage Rate at design conditions: 0.9 ACH, Pa Comments: The building is extremely leaky and loses a lot of heat in winter through warm air escaping and cold air leaking in. In summer, air leakage imposes an additional load on the air conditioning. It is important to note that this air leakage is far in excess of what is required for acceptable air quality, approximately 7 L/s per person. Significant air leaks were identified in the following locations: 1. the entire ceiling of the second floor hall, which is constructed in of thin would tongue and groove boards fastened to the underside of the roof framing, with no air barrier. Most of the joints between the boards are very leaky and some joints are open enough to let the loose fill insulation fall through. In addition, there is no air sealing around the many electrical boxes, for example for the light fixtures that penetrate the ceiling. This is the main route through which the heated air from the building in the wintertime leaves the building and is lost to the outside. The condition of the roof framing and roof boards looked to be excellent despite its age, probably because of this huge amount of unintended and expensive ventilation during the wintertime. From the attic hatch, there was no visible moisture damage. There are also pipes which penetrate the wood ceiling near the attic hatch and which offer an unfortunately excellent route for air to leave the building. Ceiling of main hall is tongue and groove wood not airtight at all. Enermodal Engineering Page 6

10 Roof truss framing and loose fill attic insulation. No air barrier, but no rot. 2. The stairway to the third floor trustee's office is a major leakage path. A storage closet off to the side of the stairway connects directly to an unsealed storage area and the outdoors. A huge amount of air was felt blowing through this location. Door to storage attic Storage attic is ventilated to the outdoors. 3. trustee's office: window, office closet, electrical receptacles in the walls, any other penetrations through the wall. There does not seem to be any air barrier in the wall and ceiling assemblies. Enermodal Engineering Page 7

11 4. Second floor doors to the small storage room over the sidewalk. some leakage but not too bad, considering these are not intended as exterior doors. The storage room addition itself is built relatively tightly. View from York St looking north Stairwell addition on east side, propane tank, chimney 5. Kitchen exterior door is very poorly sealed, fits poorly in the frame, is uninsulated, and should be replaced 6. Exit door from hall to new exit stairway has minor leakage. The stairway itself and exterior door was not examined. 7. Old back door to the parking lot is poorly sealed, fits poorly in the frame, is uninsulated and should be replaced. 8. Not examined: Mechanical room, adjacent storage room, Friendly Seniors meeting room. ENERGY SIMULATION MODEL In order to determine the effects of potential energy efficiency upgrades, an energy model of the Eden Mills Community Hall was developed using the following assumptions: Envelope: Table 1: Envelope Insulation Component R value Exterior Walls 6 Slab on Grade 1.5 Roof/Ceiling 16 Enermodal Engineering Page 8

12 Heating and Cooling: The heating system was modeled as a propane fired furnace with a nominal efficiency of 90%. The cooling system was modeled as a DX system with an EER =11. Heating Temperatures: occupied = 22 C, unoccupied = 15 C Cooling Temperatures: occupied = 24 C, unoccupied = 28 C Lighting: The lighting power was determined using fixture and wattage data provided. Occupancy Schedule: 3 days/wk: 7:00PM 9:30PM 3 days/wk: 9:00AM 11:00AM 1 day/wk: 10:00AM 11:00PM Energy costs Electricity: $ 0.15/ kwh Propane: $ 0.61 / litre BASE CASE MODEL: An energy model of the existing building was developed using the above assumptions. Tables 2 and 3 list the actual energy consumption of the Eden Mills Community Hall based on utility bill data (Appendix A), and the estimated energy consumption based on the energy model. Month Table 3: Actual and Estimated Electricity Actual Monthly (kwh/month) Electricity Simulated Monthly (kwh/month) Percentage Difference JAN % FEB % MAR % APR % MAY % JUN % JUL % AUG % SEP % OCT % Enermodal Engineering Page 9

13 NOV % DEC % TOTAL % There are considerable differences between the actual and estimated electricity consumption for some months. This is likely due to differences in the actual and assumed occupancy schedule and use patterns. However, the estimated electricity consumption is within 5% of the actual electricity consumption when compared on an annual basis Actual Estimated JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Chart 1: Actual and Estimated Electricity Table 4: Actual and Estimated Propane Propane Actual Annual (litres/year) Simulated Annual (litres/year) Percentage Difference % The actual and estimated propane consumption could not be compared on a monthly basis however; the estimated propane consumption is within 6% of the estimated value when compared on an annual basis. Enermodal Engineering Page 10

14 Litres Actual Estimated Chart 2: Actual and Estimated Propane Chart 3 illustrates the electricity end use break down. 12% 6% 15% 2% 59% Lighting Receptacles Cooling Pumps Fans DHW 6% Chart 3: Electricity End Use Breakdown (%) Enermodal Engineering Page 11

15 832 kwh 260 kwh 1795 kwh 2348 kwh 983 kwh 9065 kwh Lighting Receptacles Cooling Pumps Fans DHW Chart 4: Electricity End Use Breakdown (kwh) 60% 24% 2% 6% 5% 0.7% 2% Lighting Receptacles Cooling Pumps Fans DHW Space Heating Chart 5: Total Energy Cost End Use Breakdown (%) Enermodal Engineering Page 12

16 $3477 $1360 $148 $352 $39 $269 $125 Lighting Receptacles Cooling Pumps Fans DHW Space Heating Chart 6: Cost End Use Breakdown ($) Tables 5 & 6 list the UA value (imperial and SI) for the different building components, indicating their relative contribution to heat loss. Understanding where the majority of the heat is lost will help determine the best energy saving measures. Table 5: Building Component UA Values (Imperial Units) Component Area (ft 2 ) U value (BTU/hr ft 2 F) UA (BTU/hr F) Exterior Walls Windows Roof/ ceiling Floor & foundation Table 6: Building Component UA Values (SI Units) Component Area (m 2 ) U value (W/ m 2 K) UA (W/K) Exterior Walls Windows Roof Flr & foundation Enermodal Engineering Page 13

17 Table 7 lists the peak heating load components, on a building level. Table 7: Peak Heating Load Components Component Peak Heat Loss (kw) Percentage (%) Wall + Roof Conduction % Window Conduction 3.0 5% Floor and foundation Conduction % Infiltration % 18% 46% 5% Wall + Roof Conduction Window Conduction Foundation Conduction Infiltration 31% Chart 7: Peak Heating Load Components At peak conditions, infiltration is the largest contributor to heat loss, accounting for almost half of the total building heat loss. Enermodal Engineering Page 14

18 ENERGY CONSERVATION MEASURES (ECMs): Three basic conservation measures were modeled: 1. Increase insulation in walls and ceiling 2. Upgrade windows 3. Air seal the whole building (reduce infiltration) ECM 1: Improved Envelope Performance (Insulation) To reduce energy consumption, additional insulation can be added to the exterior walls and attic floor or roof. Table 8 lists the upgraded insulation levels: Table 8: Upgraded Envelope Insulation Component R value Exterior Walls 16 Slab on Grade No change Ceiling 28 Roof No change Tables 9 and 10 list the energy consumption using the upgraded insulation levels. Table 9: ECM1 Estimated Electricity Electricity Month Base Case Monthly (kwh/month) ECM1 Monthly (kwh/month) Percentage Difference JAN % FEB % MAR % APR % MAY % JUN % JUL % AUG % SEP % OCT % NOV % DEC % TOTAL % Enermodal Engineering Page 15

19 Table 10: ECM1 Insulation Estimated Propane Base Case Annual (litres/year) Propane ECM1 Annual (litres/year) Percentage Difference % Figures 9 and 10 illustrate the electricity and propane consumption for the Base Case vs. ECM kwh 1000 Base Case ECM JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Chart 8: Base Case and ECM1 (Insulation) Electricity Litres Base Case ECM1 Chart 9: Base Case and ECM1 (Insulation) Propane Enermodal Engineering Page 16

20 There is some electricity saving realized due to the decreased heating load resulting in fan energy savings. Table 10 shows that increasing the exterior wall R value to R 16 and the attic R value to R 28 results in a 37% reduction in annual propane consumption. It is possible however that the model underestimates the heat lost through the existing ceiling because of its leaky construction; increasing attic/roof insulation would therefore have a greater benefit than predicted here. ECM 2: Improved Window Performance Windows with better glazing can be installed to reduce heating energy. The upgraded windows used in this simulation are double glazed, argon filled, with low e coating (e3=0.1) and insulating spacers. Tables 11 and 12 list the energy consumption using the upgraded windows. Table 11: ECM2 Windows Estimated Electricity Electricity Month Base Case Monthly (kwh/month) ECM2 Monthly (kwh/month) Percentage Difference JAN % FEB % MAR % APR % MAY % JUN % JUL % AUG % SEP % OCT % NOV % DEC % TOTAL % Table 12: ECM2 Windows Estimated Propane Propane Base Case Annual (litres/year) ECM2 Annual (litres/year) Percentage Difference % Enermodal Engineering Page 17

21 Charts 10 & 11 illustrate the electricity and propane consumption for the Base Case vs. ECM kwh 1000 Base Case ECM JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Chart 10: Base Case and ECM2 Windows Electricity Litres Base Case ECM Chart 11: Base Case and ECM2 Propane As can be seen from Table 12/ Chart 11, improving window performance results in a 6% reduction in annual propane consumption. Enermodal Engineering Page 18

22 ECM 3: Reduced Infiltration This is a big one. Reducing the air infiltration from test values of 50Pa to the R2000 standard 50Pa is equivalent to reducing design rates at 5 Pa from 410 L/s to 200 L/s and gives significant energy savings. Tables 13 and 14 list the electricity and propane consumption assuming reduced air infiltration. Table 13: ECM3 Air seal Estimated Electricity Electricity Month Base Case Monthly (kwh/month) ECM3 Monthly (kwh/month) Percentage Difference JAN % FEB % MAR % APR % MAY % JUN % JUL % AUG % SEP % OCT % NOV % DEC % TOTAL % Table 14: ECM3 Estimated Propane Propane Base Case Annual (litres/year) ECM3 Annual (litres/year) Percentage Difference % Figures 13 and 14 illustrate the electricity and propane consumption for the Base Case vs. ECM3. Enermodal Engineering Page 19

23 kwh 1000 Base Case ECM JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Chart 12: Base Case and ECM3 air seal Electricity Litres Base Case ECM Chart 13: Base Case and ECM3 air seal Propane ECM 1 and 2: Improved Envelope and Window Performance Tables 15 and 16 list the electricity and propane consumption including both increased envelope and window performance. Enermodal Engineering Page 20

24 Table 15: ECM1&2 Estimated Electricity Electricity Month Base Case Monthly (kwh/month) ECM1&2 Monthly (kwh/month) Percentage Difference JAN % FEB % MAR % APR % MAY % JUN % JUL % AUG % SEP % OCT % NOV % DEC % TOTAL % Table 16: ECM1&2 Estimated Propane Propane Base Case Annual (litres/year) ECM1&2 Annual (litres/year) Percentage Difference % Charts 14 and 15 illustrate the electricity and propane consumption for the Base Case vs. ECM1&2 Enermodal Engineering Page 21

25 kwh 1000 Base Case ECM1& JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Chart 14: Base Case and ECM1&2 Electricity Litres Base Case ECM1& Chart 15: Base Case and ECM1&2 Propane As can be seen from Figure 16, improving both envelope and window performance results in 42% reduction in annual propane consumption. ECM 1, 2 and 3: Improved Envelope and Window Performance and Reduced Infiltration Tables 17 and 18 list the electricity and propane consumption including increased envelope and window performance and reduced infiltration. Enermodal Engineering Page 22

26 Table 17: ECM1,2 and 3 Estimated Electricity Month Base Case Monthly (kwh/month) Electricity ECM1&2&3 Monthly (kwh/month) Percentage Difference JAN % FEB % MAR % APR % MAY % JUN % JUL % AUG % SEP % OCT % NOV % DEC % TOTAL % Table 18: ECM1,2 and 3 Estimated Propane Base Case Annual (litres/year) Propane ECM1&2&3 Annual (litres/year) Percentage Difference % Charts 16 and 17 illustrate the electricity and propane consumption for the Base Case vs. ECM1&2 Enermodal Engineering Page 23

27 kwh 1000 Base Case ECM1,2 and JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Chart 16: Base Case and ECM1&2 Electricity Litres Base Case ECM1,2 and Chart 17: Base Case and ECM1&2 Propane As can be seen from Chart 17, improving envelope and window performance and reducing infiltration results in a 62% reduction in annual propane consumption. Enermodal Engineering Page 24

28 GREENHOUSE GAS EMISSIONS REDUCTION: The above ECMs will reduce greenhouse gas (GHG) emissions. Table 19 lists the GHG emissions factors used in the following GHG analysis, while Table 20 lists the GHG reductions associated with each ECM. Table 19: GHG Emissions Factors Electricity Propane 222g CO 2 eq/kwh 1602g CO 2 eq/litre Table 20: GHG Emissions Source GHG Emissions (tonnes CO 2 eq/year) Base Case ECM1 ECM2 ECM3 ECM1&2 ECM 1&2&3 Electricity Propane Total ECM1 insulation ECM2 windows ECM3 air seal The potential GHG reductions are: 1.45 tonnes CO 2 eq/year increased envelope performance 0.73 tonnes CO 2 eq/year increased window performance 2.99 tonnes CO 2 eq/year reduced air infiltration 2.18 tonnes CO 2 eq/year increased envelope performance and increased window performance 5.15 tonnes CO 2 eq/year increased envelope and window performance and reduced air infiltration Enermodal Engineering Page 25

29 RECOMMENDED ENERGY CONSERVATION MEASURES Air Sealing Uncontrolled air leakage accounts for 47% of the building heating, or about 2700 L propane/ yr, worth about $2000 at $0.75/L. This cost will rise. An air sealing contractor should be hired to seal the Hall ceiling, 3 rd Flr stairway and meeting room, various doors. Doors Front door, kitchen side door, back door (poor or missing weatherstrip and bottom sweeps. Big gap at bottom of kitchen door.) Hall ceiling (no air barrier, no seal on access hatch, multiple penetrations at light fixtures) Hall storage verandah (drafts at double doors, no weather seals) 3 rd Flr mtg room & closet and closet beside stair (open to roof, no air barrier. The existing insulation is not an air barrier.) One method to seal the ceiling would be to remove the existing loose fill insulation and apply a thin (3 6 cm) layer of spray polyurethane foam on top of the wood ceiling. This has some insulating value as well as acting as an air barrier. The ceiling at the sloped sections would have to be removed and ventilation channels installed in each rafter space between the soffit and the attic. The underside of the roof could then be sealed and insulated with spray polyurethane foam to achieve a continuous air barrier from wall to ceiling. The wood ceiling would then be re installed. This work should be coordinated with any roof modifications, eg. new ventilation chimney. Products: medium density spray polyurethane foam (SPF), Heat Loc Soya Spray insulation contractors: WayMar, Elora; Strassburger, Kitchener. Air sealing contractor: Canam Air Leakage Control, Toronto Roof and Ceiling Insulation Once the ceiling above the main hall is air sealed, then re insulate the attic above with additional blowin fibre insulation. However, as long as the existing wooden ceiling remains as leaky as it is now, adding fibrous insulation would be ineffective, other than as an air filter. As an alternative to the above, it would be better to abandon the attic ceiling insulation and insulate the entire underside of the roof with spray polyurethane foam (SPF) insulation. The insulation should be continuous from the top of the walls to the peak of the roof, changing the roof to a cathedral roof insulation design. No attic ventilation would be required nor provided. Again, the wood ceiling on the sloping sections would have to be removed for access to the roof and to seal the top of the walls to the underside of the roof. Adding 6 of SPF between the rafters would provide about R30 insulation. Enermodal Engineering Page 26

30 If a new metal roof is to be installed, then after the asphalt shingles are removed, 1 rigid insulating could be applied to the exterior of the wood sheathing, strapped with 1 x 4 wood, then the metal roof applied. The rigid insulation would add about R5 and provide a thermal break above the rafters. Roof material should be light in colour or galvanized to keep the roof cool in summer. A building envelope specialist should be consulted to carefully detail and specify this work. It should also be coordinated with any roof modifications, eg. adding a ventilation chimney. Wall Insulation The solid brick and masonry walls have no insulation and account for about 15 % of the annual heating energy or 850 L propane, worth about $640/ year at current propane price. This will increase. It is preferable to insulate the exterior of such walls rather than the interior. Insulating the interior of existing walls requires replacement of all interior finishes, and leaves significant thermal bridges at floors and interior walls where it is difficult to install a continuous layer of insulation. Insulation installed on the exterior can be continuous across interior walls and floors and can include an air barrier. It also moves the existing brick and masonry to the interior of the insulation where it adds beneficial thermal mass to improve comfort and reduce cooling and heating loads when outside temperatures fluctuate. A high mass building is much slower to heat up in the summer and requires less cooling capacity. Adding 50 mm (2 ) of rigid insulation (R10 R14) would reduce the annual heating energy by about $500. The insulation could be finished with stucco, brick or prefinished siding. The most common exterior insulation finish system (EIFS) consists of rigid polystyrene insulation and acrylic stucco. If we wish to preserve the appearance of the existing building, a new brick exterior could be installed using steel angle brink ledge fastened to the existing foundation and brick ties up the wall, but would add another 100 mm (4 ) to the wall thickness and would require some architectural treatment at the roof to maintain the same soffit profile. Windows would also have to be trimmed out. EIFS Systems Product: Sto Dryvit Replacement Windows The windows in the hall and downstairs were replaced about 20 years ago and are reasonably airtight. Replacing them with new low e argon units with insulating spacers would reduce heating energy about $250, but is hard to justify at a cost of about $1000 per window. The windows in the washrooms and 3 rd Flr meeting room however are very leaky double hung wood units from the original construction in about 1950 and should be replaced. Water Heater The electric water heater is already well insulated with additional glass fibre blanket and uses about 2.6 kwh/day, presently worth $140/yr at $0.15/kWh. The next improvement should be to insulate all Enermodal Engineering Page 27

31 accessible hot water piping. This can be done by Club members for under $50. for insulation material. A solar water heater would be hard to justify economically at cost of $4000. Heating and Air Conditioning Equipment The 2 propane furnaces are high efficiency condensing type with nominal 90% efficiency. Furnace #1 leads, furnace #2 follows. At the next service, the actual combustion efficiency should be measured to check that they are operating as well as possible. If they are, there is little energy saving potential in replacing them with newer furnaces at 94% rated efficiency. The first investments should focus on improving airflow and reducing heat losses. For example, furnace #1 has a serious restriction in return airflow. System improvements include: Improve the distribution of warm air Not enough warm air is reaching places where it is needed (eg. your feet, in the Community Room), and too much is going places it shouldn t. Community Room warm ceiling/ cold floor: 2 ceiling diffusers, wrong type, wrong location. Warm air doesn t reach the floor. Bsmt Hall dead grille: no air supplied from grille low on the wall. No other grilles or register here. Cold drafts from front door can attack ankles in Community Room and Kitchen without challenge. Kitchen Pantry warm fridge and freezer: This room has an uncontrolled supply air grille, keeping the fridge, freezer, pots and pans warm. Who wants to keep the freezer warm? Kitchen warm ceiling/ cold floor: 2 ceiling diffusers, wrong type. Do your feet ever get cold in here? Hall damaged floor registers, uneven airflow. Lightweight residential style not appropriate for a fine rental hall. Registers closest to furnace give lots of air; those farthest away, very little. Less significant than other problems, but still worth replacing registers with heavy duty registers with integral balancing dampers. Duct joints are not sealed. A lot of heated air leaks into the furnace room (to be recycled back to the return) and into floor joist spaces above the bsmt ceiling. Wasted, and steals air from the spaces that need it. Improve the design of return air ducting The return air duct for Furnace 1 is too small ( only 14 x 4 for cfm) and should be reworked. This restriction in airflow could cause the furnace to overheat and trip on high limit. It will certainly reduce the heating effectiveness and efficiency. Only one return grille for Furnace 1 was found in whole bldg in the floor in front of stage in Hall. More return grilles should be installed, and the system should either be separately zoned or combined; at present, the returns serve separate spaces, but the supplies are combined. Furnace 2 appears to return only from the bsmt storage room, through 2 holes cut in top of return trunk duct. Sheet metal joist liners nearby do not connect to the duct, don t go anywhere and are useless. Trunk runs above kitchen ceiling to go where??? Enermodal Engineering Page 28

32 Consequently, furnaces are drawing a lot of return air from the furnace room and the adjacent bsmt storage room. Since the furnace room is poorly sealed to the outdoors, the furnaces draw in a lot of outside air, heat it, then the leaky building lets it escape through the roof, etc. This gives a very well ventilated building, but at a very high energy cost, especially since it is usually empty with no one to enjoy the high ventilation rate. Return air is supposed to come from the occupied rooms. Furthermore, these basement rooms are dirty and are used to store cleaning products; the furnaces pump that air through the rest of the bldg. Recommendations: 1. Seal all sheet metal joints in supply and return ducts. with water based duct sealant. Seal all connections at furnaces. 2. Install balancing dampers at all accessible branch ducts. 3. Community Room: Either just replace existing diffusers with double deflection or nozzle type diffusers, or relocate them to low on the corridor wall, with double deflection grilles. 4. Close off supply air grille in kitchen pantry. 5. Check if bsmt hall register is connected to anything. (Maybe by restricting other outlets temporarily.) If it is, rebalancing airflows may revive it. Otherwise, add new supply register or two for the bsmt hall. 6. Kitchen: Replace existing ceiling diffusers with double deflection grilles. 7. Hall: Consider replacing all floor registers with linear bar grilles with balancing dampers (partly for better appearance & durability, partly for better air balance and airflow pattern) 8. Close duct and diffuser to bsmt storage rm. 9. Investigate where return ducts go, and it there are other return grilles, possibly covered. Is there a return grill in senior s room? 10. Provide new return grille in bsmt hall, either in wall with furnace room or ceiling outside of storage room. 11. Seal 2 holes in top of return trunk duct in bsmt storage room. Remove redundant joist liner. 12. Consider connecting both return trunk ducts together in furnace room. Improve the controls The building has at least 2 or 3 different areas by function Hall, Bsmt Community Rm, Seniors Rm and 2 furnaces, but only one thermostat, which is located in the basement hall. This is a simple arrangement but inefficient, and certain to dissatisfy some of the users. The system is not zoned if heat is required only in the Seniors Room, for example, the whole building has to be heated. When the Hall is the principle use, the thermostat does not respond to changes in load, eg. when there are 100 people dancing and warming up the room but the thermostat doesn t know and still calls for the furnaces to work. Or when the exterior doors are open and cool air enters the hall, it fools the thermostat to heat the whole hall. Furnaces are connected with a common supply air plenum but have separate return ducts and venting. The system should either be separately zoned or combined, not both. Enermodal Engineering Page 29

33 Recommendations 1. Investigate if there is a simple 2 stage thermostat that could control the 2 furnaces in sequence ( and air conditioners). Ie. first one turns on, then, if still needed, the second. If so, add a backdraft damper at the return air connections at each furnace beside air filter so that one furnace can run at a time. Since supply duct is shared, a single furnace will still supply air to all outlets, just less. 2. Investigate if zone dampers and thermostats for some zones, eg. seniors rm, are feasible. In the simplest scenario, they would be a sub zone or slave to the master thermostat. 3. It is probably not feasible to separate the ground floor from the upper floor and allocate one furnace to each, with separate thermostats. At present, spaces in the two floors share a common supply air trunk duct. They could be separated, but this would require more sheet metal and drywall ceiling work. Should be investigated 4. Investigate feasibility of converting to wood pellets at least for one of the two furnaces, if the supply of pellets becomes reliable, and there is a commitment to provide the regular maintenance required handling fuel, ash disposal, cleaning grate, etc. See Appendix D for comparative heating costs. 5. Investigate the feasibility of converting to heat pumps for both heating and cooling. See Appendix D. Electricity We did not specifically look at electrical equipment, but did notice the following: 1. Some fixtures still use incandescent bulbs. Eg. front entrance canopy, stage floods, Trustees Room. Incandescent bulbs that are used for more than a few hours per month should be changed to compact fluorescent bulbs. 2. Have exit lights all been changed to LED type fixtures or to compact fluorescent? 3. Whenever major appliances need replacement, buy EnergyStar labeled appliances. Choose appliance with lowest kwh/year rating. 4. Labels: Put better labels on controls and instructions where to find them if it is not obvious, eg. Hall ceiling fans. How DO you turn them off? They do not save heating energy when the bldg is unoccupied (the thermostat is in the bsmt and doesn t know what the fans are doing) and therefore should be turned off. Enermodal Engineering Ltd. Richard Lay, M.A.Sc., P.Eng. Christianne Aussant, M.A.Sc. Enermodal Engineering Page 30

Practical and Effective Approaches to Residential Ventilation for Production Builders

Practical and Effective Approaches to Residential Ventilation for Production Builders Practical and Effective Approaches to Residential Ventilation for Production Builders by Armin Rudd USDOE Building America Program for Affordable Comfort Conference 2002 Cincinnati, Ohio 18 April 2002

More information

Pro Eco-Energy. Home Assessment

Pro Eco-Energy. Home Assessment Pro Eco-Energy Home Assessment Prepared for: Prepared by: Pro Eco Energy Andrew Aliferis PO Box 445 Scotland, PA 17254 717-446-0575 ABOUT THIS REPORT Your in-home evaluation was conducted on 2/12/2013.

More information

Retrofitting a Multi-Unit Residential Building To Reduce Purchased Energy by a Factor of 10. Chris Richards

Retrofitting a Multi-Unit Residential Building To Reduce Purchased Energy by a Factor of 10. Chris Richards Retrofitting a Multi-Unit Residential Building To Reduce Purchased Energy by a Factor of 10 Chris Richards MSc Candidate, Mechanical Engineering University of Saskatchewan Saskatchewan Research Council

More information

MBPA Home Performance FIELD DATA COLLECTION FORM

MBPA Home Performance FIELD DATA COLLECTION FORM MBPA Home Performance FIELD DATA COLLECTION FORM Customer Information Test Date: Name Address City State Zip Phone: ( ) Email: Electric Provider Heating Fuel Provider Account Number Account Number Customer

More information

Cork County Energy Agency

Cork County Energy Agency Cork County Energy Agency Energy Audit Midleton Area Office December 2009 Table of Contents 1. Introduction...1 2. Site description...2 3. On site energy use...3 3.1 Energy management...3 3.2 Breakdown

More information

The Art of Building Science

The Art of Building Science The Art of Building Science What is Building Science? Building Science seeks to apply the scientific fundamentals of building dynamics to the functional relationships between the house s components and

More information

tççç= ÜÉ~íáåÖ çéíáçåë

tççç= ÜÉ~íáåÖ çéíáçåë 3. tççç= ÜÉ~íáåÖ çéíáçåë There are several different types of wood-heating appliances to choose from. Each type is intended for a particular use, and each has its own set of advantages and disadvantages.

More information

Energy problems in small apartment buildings

Energy problems in small apartment buildings Energy problems in small apartment buildings Uneven heating and drafts, window condensation, complaints about odors and burned out lamps these are common problems in four-unit to eight-unit apartment buildings.

More information

Energy Conservation Measures For the Town of Lakeville. Locations Town Hall Fire Department Police Department Council on Aging

Energy Conservation Measures For the Town of Lakeville. Locations Town Hall Fire Department Police Department Council on Aging Energy Conservation Measures For the Town of Lakeville Locations Town Hall Fire Department Police Department Council on Aging March 05 Location Town Hall 36 Bedford Street Energy Conservation Measures

More information

HOME PERFORMANCE ENERGY ANALYSIS

HOME PERFORMANCE ENERGY ANALYSIS Certifed Home, Termite, Green & Commercial Inspectors HOME PERFORMANCE ENERGY ANALYSIS ON 1234 ANY STREET; PHOENIX, AZ PREPARED FOR: JOHN DOE JANUARY 23, 2009 BY: PAUL A. FURMAN, P.E., LEED-AP Hire the

More information

Home Energy Assessment Report

Home Energy Assessment Report Home Energy Assessment Report Prepared for Prepared by Nathaniel Dick 50 Washington St Westborough, MA 01581 Assessment Date Powered by Conservation Services Group Assessment Summary About Your Home Year

More information

Northeast Oklahoma REC s Do It Yourself Home Energy Audit Silver Level

Northeast Oklahoma REC s Do It Yourself Home Energy Audit Silver Level Northeast Oklahoma REC s Do It Yourself Home Energy Audit Silver Level Start today and start saving! First project (circle and initial when completed) Hot Water Tank Blanket Objective: Install a blanket

More information

qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system.

qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system. 8. qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system. How Chimneys Work An effective chimney is an important part of any successful wood-burning system. Many of

More information

Evaluate your insulation. Look for a tag in the attic that shows the R-Values of insulation in the floors, walls and ceiling.

Evaluate your insulation. Look for a tag in the attic that shows the R-Values of insulation in the floors, walls and ceiling. There are many reasons to save energy whether to keep more money in your pocket or out of concern for the environment. The good news is, you don t have to sacrifice comfort and convenience to save. In

More information

Ways to Save. Energy efficiency tips to help you lower your monthly power bill. 1 Ways To Save

Ways to Save. Energy efficiency tips to help you lower your monthly power bill. 1 Ways To Save Ways to Save Energy efficiency tips to help you lower your monthly power bill 1 Ways To Save 2 Ways To Save Money Saving Advice Jackson EMC is a good resource to use in your energy planning. We can show

More information

Supplement A- Improving Forced Air Heating Systems

Supplement A- Improving Forced Air Heating Systems Supplement A Improving Forced Air Heating Systems The Challenge Recent research and testing of new homes in the Pacific Northwest and across the United States shows the importance of a properly installed

More information

RESNET HERS Rater Sample Test Questions 2

RESNET HERS Rater Sample Test Questions 2 RESNET HERS Rater Sample Test Questions 2 1. Which of the following is the best device for removing standing water from a crawl space? A. Dehumidifier B. Sump pump C. Air-to-air heat exchanger D. Crawl-space

More information

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems about your house CE 28 k Assessing the Comfort and Safety of Your Home s Mechanical Systems The heating, ventilating and air conditioning (HVAC) systems are a vital part of every home. These mechanical

More information

Insulating Unvented Attics With Spray Foam

Insulating Unvented Attics With Spray Foam Insulating Unvented Attics With Spray Foam Closed-cell polyurethane foam provides the insulation, air barrier, and vapor retarder necessary for an unvented attic assembly by James Morshead As a general

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS

RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS ESL-TR-7-9-1 RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS A Project for Texas Senate Bill 5 Legislation For Reducing Pollution in Nonattainment and Affected Areas

More information

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money. What is condensation?

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money. What is condensation? EASY$ TIP SHEETS Energy Advice Saving Yukoners Money Quick Links What is condensation? Condensation on windows Hidden condensation Causes and solutions Controlling humidity in your home Humidity and Condensation

More information

Energy Efficiency Programs in Action

Energy Efficiency Programs in Action Cape Light Compact Energy Efficiency Programs in Action Case Study: CYNTHIA HAUN - HYANNIS RESIDENT PROJECT DESCRIPTION Hyannis resident Cynthia Haun successfully reduced her annual electricity use by

More information

Consumer Features & Benefits of Energy Efficient Products

Consumer Features & Benefits of Energy Efficient Products Consumer Features & Benefits of Energy Efficient Products Summary of the ENERGY STAR Features Campaign City Green Solutions 1 Our Role z In-Depth Product Research z Consumer Centric Language z Visually

More information

Attic ventilation options can be confusing to roofing contractors

Attic ventilation options can be confusing to roofing contractors 30 www.professionalroofing.net JANUARY 2014 Attic ventilation options can be confusing to roofing contractors by Joan P. Crowe, AIA Attic ventilation can be a confusing, complex subject and is the topic

More information

ENERGY & WATER EFFICIENCY: HOME ASSESSMENTS. Jim Riggins Monument, CO

ENERGY & WATER EFFICIENCY: HOME ASSESSMENTS. Jim Riggins Monument, CO ENERGY & WATER EFFICIENCY: HOME ASSESSMENTS Jim Riggins Monument, CO Overview Home Energy Efficiency Basics Sample Energy Audit Results The Professional Energy Audit Benefits of Energy Efficiency U.S.

More information

EARTH ADVANTAGE HVAC REQUIREMENTS

EARTH ADVANTAGE HVAC REQUIREMENTS EARTH ADVANTAGE HVAC REQUIREMENTS Homes are performance tested by approved performance testing (PTCS) technicians to ensure systems and equipment work as designed. Technicians must follow the ENERGY STAR

More information

Sample Report Site Visits Any Capitol, Any State Date

Sample Report Site Visits Any Capitol, Any State Date Sample Report Site Visits Any Capitol, Any State Date Unit #1: Single-family wood-frame home 1 Measures: Attic air sealing and insulation, wall air sealing and insulation, new gas wall furnace, weatherstrip

More information

Heating and Hot Water

Heating and Hot Water Heating and Hot Water Funding Funding for this class was provided by the Alaska Housing Finance Corporation (AHFC). This course is designed to empower homeowners with the knowledge to live in and maintain

More information

Unvented Roof Summary Article

Unvented Roof Summary Article building science.com 2008 Building Science Press All rights of reproduction in any form reserved. Unvented Roof Summary Article Research Report - 0301 2003 Kohta Ueno Abstract: This article was written

More information

Energy Efficiency Practices for the Low- Income Population

Energy Efficiency Practices for the Low- Income Population Energy Efficiency Practices for the Low- Income Population Donald Fournier Managing Director SEDAC University of Illinois Residential Energy American homes use almost 25% of the energy consumed in the

More information

CHIMNEYS AND VENTS CHAPTER 8

CHIMNEYS AND VENTS CHAPTER 8 CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

Basic Home Energy Audit

Basic Home Energy Audit Basic Home Energy Audit The purpose of this information is to help you perform your own basic home energy audit. Improved energy efficiency can contribute to lower bills, increased comfort, lower utility

More information

1960s or 70s One-Storey Homes

1960s or 70s One-Storey Homes R enovating for energy savings 1960s or 70s One-Storey Homes October 2004 Issue 4 What you ve got More than 550,000 one-storey houses (also known as bungalows or ranchers) were built in all parts of Canada

More information

Bedroom 100. True or False: Space heaters are more energy efficient and inexpensive to heat large areas than central heating systems.

Bedroom 100. True or False: Space heaters are more energy efficient and inexpensive to heat large areas than central heating systems. Bedroom 100 True or False: Space heaters are more energy efficient and inexpensive to heat large areas than central heating systems. Bedroom 200 Insulation: A) Facilitates the exchange of air from external

More information

Energy Efficient Measures That Add Little or no. Program Lights & Appliances: How To Benefit from the Low-Hanging Fruit

Energy Efficient Measures That Add Little or no. Program Lights & Appliances: How To Benefit from the Low-Hanging Fruit Energy Efficient Measures That Add Little or no FirstEnergy Cost Energy to Construction Efficient New Homes Program Lights & Appliances: How To Benefit from the Low-Hanging Fruit 1 2 Optimizing Savings

More information

Riverdale NetZero Project Summary of Costs and Expected Performance

Riverdale NetZero Project Summary of Costs and Expected Performance Riverdale NetZero Project Summary of Costs and Expected Performance Natural Resources Canada Sustainable Buildings and Communities Edmonton, Ottawa 2009 January 07 Gordon Howell, P.Eng. 2008-2009 Progressively

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

BALTIMORE GAS AND ELECTRIC COMPANY (BGE) Home Performance with ENERGY STAR Program. Rebate and Incentive Instructions

BALTIMORE GAS AND ELECTRIC COMPANY (BGE) Home Performance with ENERGY STAR Program. Rebate and Incentive Instructions Rebate and Incentive Instructions Contents Application Instructions... 1 Rebate Requirements Summary... 2 Comprehensive Home Energy Audit (CHEA) Rebate... 4 Air Sealing and Insulation Rebate... 4 Air sealing...

More information

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed

More information

Special Topics on Residential HVAC

Special Topics on Residential HVAC Special Topics on Residential HVAC by Armin Rudd USDOE Building America Program for EEBA Conference 2002 Phoenix, Arizona 10 October 2002 Page 1 of 25 Two Main Topics: 1. Cyclical trade-offs between building

More information

ENERGY PERFORMANCE SCORE

ENERGY PERFORMANCE SCORE ENERGY PERFORMANCE SCORE Address: 327 Randolph Ave Seattle, WA 98122 Reference Number: 530002857 Energy Score: 27,000 kwhe/yr $1,922 Electric: 27,500 kwh/yr $1,922 Natural Gas: 0 therms/yr $0 Carbon Score:

More information

2015 MECHANICAL CODE REQUIREMENTS

2015 MECHANICAL CODE REQUIREMENTS 2015 MECHANICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Mechanical requirements for residential buildings per

More information

New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011

New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011 New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011 Customer: Street: City: Zip: Phone: (Home): ( ) - Phone: (Work): ( ) - Owner: Yes No/ Name: Phone: ( )

More information

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on HOME PROPERTY SCAN INSPECTIONS The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on January 11, 2010 and

More information

Storing excess daytime solar energy to heat greenhouse at night!

Storing excess daytime solar energy to heat greenhouse at night! Storing excess daytime solar energy to heat greenhouse at night Russell Benoy March 21, 2014 Having built a well insulated greenhouse, I was amazed at how often the exhaust fan ran to maintain a reasonable

More information

Energy-saving tips. For apartments and condos. pse.com/multifamilyretrofit. Bellevue, WA Puget Sound Energy. P.O. Box /17

Energy-saving tips. For apartments and condos. pse.com/multifamilyretrofit. Bellevue, WA Puget Sound Energy. P.O. Box /17 1232 01/17 Puget Sound Energy P.O. Box 97034 Bellevue, WA 98009-9734 pse.com/multifamilyretrofit Energy-saving tips For apartments and condos In this guide 5 Heating 6 Water heating 7 Insulation 8 Air

More information

Time-Based Scheduling of Residential Ventilation

Time-Based Scheduling of Residential Ventilation Time-Based Scheduling of Residential Ventilation by Armin Rudd USDOE Building America Program for EEBA Conference 2000 Building for Peak Performance Denver, Colorado 26 October 2000 Climate Specific Design

More information

Dehumidification: Energy Efficiency Comparisons

Dehumidification: Energy Efficiency Comparisons Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,

More information

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist BSC Building America High Performance Homes: Today & Tomorrow Peter Yost Senior Building Scientist Building America homes... create energy efficient environments that: - are affordable to operate - use

More information

Illinois Home Weatherization Assistance Program - Field Standards Manual

Illinois Home Weatherization Assistance Program - Field Standards Manual Illinois Home Weatherization Assistance Program - Field Standards Manual Contents 100 Diagnostic Standards 111 Blower Door 1111 House Set-Up 11111 Basements 1112 Blower Door Test 11121 Building Tightness

More information

CMHC HOME MAINTENANCE CHECKLIST

CMHC HOME MAINTENANCE CHECKLIST Make sure air vents indoors and outdoors (intake, exhaust and forced air) are not blocked by snow or debris. Check and clean range hood filters on a monthly basis. Test ground fault circuit interrupter(s)

More information

I. STRUCTURAL SYSTEMS

I. STRUCTURAL SYSTEMS I. STRUCTURAL SYSTEMS A. Foundations Type of Foundation(s): Pier & Beam - Crawlspace Opinion: All exposed areas of the foundation were examined visually. Examination of the foundation was limited to photographs

More information

Energy efficiency: Present and Future. Paul Kando Midcoast Green Collaborative

Energy efficiency: Present and Future. Paul Kando Midcoast Green Collaborative Energy efficiency: Present and Future Paul Kando Midcoast Green Collaborative More than twice the energy for the same result More than half the energy we use is WASTED Vaclav Smil, University of Manitoba

More information

Insulate your exterior walls. Air seal and insulate your attic

Insulate your exterior walls. Air seal and insulate your attic Energy Fitness Plan For: Test Report 416 Testing rd, Minneapolis, MN 55343 By: Kyle Shannon, Dan May Date: Nov 01, 2013 YOUR ENERGY FITNESS SCORE 0 INEFFICIENT HOUSE ACTION NEEDED 41 100 32 11 3 13 EFFICIENT

More information

Powerful Money Saving Ideas BROUGHT TO YOU BY TVA AND YOUR LOCAL POWER COMPANY

Powerful Money Saving Ideas BROUGHT TO YOU BY TVA AND YOUR LOCAL POWER COMPANY Powerful Money Saving Ideas BROUGHT TO YOU BY TVA AND YOUR LOCAL POWER COMPANY How saving energy saves you money. Your local power company and TVA have come up with a way to help you save both energy and

More information

Strategies for Summer Utility Savings. Residential Environmental Program Series May 15, 2013

Strategies for Summer Utility Savings. Residential Environmental Program Series May 15, 2013 Strategies for Summer Utility Savings Residential Environmental Program Series May 15, 2013 Are FC Summers Getting Hotter? 200 Fort Collins Annual Hours 90 F or Above 150 100 50 1970 1980 1990 2000 2010

More information

Overview. Case Study 2008 Building America Prototype ICI Showcase House. Daytona Beach, Florida. Project Team: ICI Homes, Building Science Corporation

Overview. Case Study 2008 Building America Prototype ICI Showcase House. Daytona Beach, Florida. Project Team: ICI Homes, Building Science Corporation 008 /009Building America Prototype ICI Showcase House Case Study 008 Building America Prototype ICI Showcase House Daytona Beach, Florida Project Profile Overview Building Science Corporation (BSC) collaborated

More information

Residential New Home Construction Checklist

Residential New Home Construction Checklist Residential New Home Construction Checklist A separate permit is required for each address. Address/PID: All materials and the installation of all materials must comply with the Minnesota State Building

More information

Basic Building Science insights for Spray Foam, HVAC and Moisture

Basic Building Science insights for Spray Foam, HVAC and Moisture Basic Building Science insights for Spray Foam, HVAC and Moisture Claudette Hanks Reichel, Ed.D. Professor and Extension Housing Specialist Director, LaHouse Resource Center When the blind leads the blind

More information

Inside Out Home Inspections

Inside Out Home Inspections Cover Page Inside Out Home Inspections Property Inspection Report Inspection prepared for: John Doe & Jane Doe Date of Inspection: 5/10/2014 Inspector: Lucas Sargent PO Box 514, Tioga, PA 16946 Phone:

More information

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report East Liberty Presbyterian Church 14 009 For: By: East Liberty Presbyterian Church Jeffery Ison, James Construction Date: October

More information

Home Performance Science

Home Performance Science Home Performance Science Symptoms of a Sick House Too hot/too cold rooms Respiratory problems Headaches/nausea Smoky fireplace Foggy windows Stuffy air and lingering odors Peeling paint Constant dust problems

More information

Are you warming up with space heaters?

Are you warming up with space heaters? Are you warming up with space heaters? As the temperature drops, many families may use portable electric space heaters to help warm their homes. The Electrical Safety Foundation International warns that

More information

Getting in the Zone with Zonal Pressure Diagnostics

Getting in the Zone with Zonal Pressure Diagnostics Getting in the Zone with Zonal Pressure Diagnostics NYSCAA/NYSWDA Lake Placid June 2, 2017 Presented by: Al McMahon New York State Weatherization Directors Association On many projects, air sealing is

More information

Inspection Report 123 My Street Midland, GA

Inspection Report 123 My Street Midland, GA Buying, Selling or Building Your Home Inspection Company ROFESSIONAL INSPECTION SERVICES, LLC P.O. Box 9774 Columbus, GA 31908 706-565-0333 1-866-298-4251 Inspection Report 123 My Street Midland, GA This

More information

BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST

BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST 1. Pre-Inspection Homeowner Interview (3 minutes) A. Turn on & zero CO Meters. Determine ambient CO : B. Record Outside Temperature: C. Homeowner interview:

More information

Caulking and weather-stripping the gaps in your home probably offer the best use of your bucks in terms of home energy improvements.

Caulking and weather-stripping the gaps in your home probably offer the best use of your bucks in terms of home energy improvements. Efficiency Pays Small Changes Equal Big Savings Bernd Geisler 2005 Bernd Geisler Caulking and weather-stripping the gaps in your home probably offer the best use of your bucks in terms of home energy improvements.

More information

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency NAHB Green Home Building Guidelines Energy Efficiency 3.1 Prerequisites 3.1.1 Home is equivalent to the IESS 2003 or local energy code. Conformance shall be based on plan analysis using software. 3.1.2

More information

Home Energy Audit. 170 Security Circle Suite 104 Athens, GA

Home Energy Audit. 170 Security Circle Suite 104 Athens, GA 170 Security Circle Suite 104 Athens, GA 30605 706-248-0821 Home Energy Audit Customer: John Customer Auditor: Brian Young BPI# 5015564 Address: 0000 Deer Run Drive Date: 08/17/2010 Type: Single Family

More information

Julie Klump, POAH Rick Fenuccio, Tom Hartman Marc Rosenbaum Melpet preliminary heat loss and energy model results and implications

Julie Klump, POAH Rick Fenuccio, Tom Hartman Marc Rosenbaum Melpet preliminary heat loss and energy model results and implications January 9, 2014 To: Cc: From: Subject: Julie Klump, POAH Rick Fenuccio, Tom Hartman Marc Rosenbaum Melpet preliminary heat loss and energy model results and implications Approach I sent BLF&R input spreadsheets

More information

InterNACHI Home Energy Inspection for th Street

InterNACHI Home Energy Inspection for th Street InterNACHI Home Energy Inspection for 1750 30th Street Estimated Yearly Energy Costs: $1,491 per year Dear Client, This house has been scored on a scale of 1 to 100. A 100 would represent a home with perfect

More information

Home Performance Analysis

Home Performance Analysis 395 National Drive Suite 15 Burtonsville, MD 2866 www.efficienthomellc.com 31-476-768 FAX: 31-476-7717 info@efficienthomellc.com Home Performance Analysis ENERGY AUDIT REPORT Prepared For: Matthew Lesko

More information

Lighting. The vast majority of lighting was fluorescent, either compact or linear.

Lighting. The vast majority of lighting was fluorescent, either compact or linear. Sustainability Audit Report Submitted: September 24, 2008 Audit performed by: Greg Smith and Kelsey Fisher Space/Date Audited: Student Sustainability Center/July 30, 2008 Lighting The vast majority of

More information

Tips To Help Conserve Electricity

Tips To Help Conserve Electricity Tips To Help Conserve Electricity AND REDUCE YOUR POWER BILL Cut Your Power Bill Nobody wants to pay more than necessary for power! But a lot of us do. And that hurts when you live in a place with warm

More information

DO IT YOURSELF ENERGY AUDIT

DO IT YOURSELF ENERGY AUDIT DO IT YOURSELF ENERGY AUDIT Taking control of your energy use is probably easier than you realize. That's because you have almost complete control over which appliances and electrical devices in your home

More information

Objectives. Home Performance Diagnostics with the House of Pressure (Part 1) How can Pressure effect Building Performance?

Objectives. Home Performance Diagnostics with the House of Pressure (Part 1) How can Pressure effect Building Performance? Home Performance Diagnostics with the House of Pressure (Part 1) Objectives Learn the basic rules of air flow and differences Begin to be able to recognize building problems related to airflow and differences

More information

The Ed Roberts Campus Berkeley, CA

The Ed Roberts Campus Berkeley, CA The Ed Roberts Campus Berkeley, CA Anderson Clemenceau Mechanical Option Penn State A.E. Senior Thesis April 14, 2015 Leddy Maytum Stacy Architects, Photo by Tim Griffith ASHRAE Climate Zone 3C 99.6% Heating

More information

Designed with the environment in mind.

Designed with the environment in mind. Designed with the environment in mind. www.mcguinnhomes.com sm Designed with the environment in mind. Why are McGuinn hybrid homes sm different? Simple... we pay close attention to those areas of your

More information

Inspection Report. Prepared for: Tonia Mann. Property Address: 402 Leslie Court McDonough, GA Date: March 07, 2013

Inspection Report. Prepared for: Tonia Mann. Property Address: 402 Leslie Court McDonough, GA Date: March 07, 2013 Inspection Report Prepared for: Tonia Mann Property Address: 402 Leslie Court McDonough, GA 30253 Date: March 07, 2013 Inspector: Charles Mann Edifice Inspections, Inc. (770) 594-2222 www.edificeinspections.com

More information

Overview of Presentation. Airflow Control: Why. Air Barriers and Energy

Overview of Presentation. Airflow Control: Why. Air Barriers and Energy Overview of Presentation John Straube, Ph.D., P.Eng Spray Foam Air Flow Control Why control airflow? Vapor flow? Review of Driving Forces Air Barrier Systems Functions + Requirements Airflow Within Enclosures

More information

August 15, 2013 Page 1 of 19

August 15, 2013 Page 1 of 19 Section C401 Application Compliance with C402, C403, C404 and C405 AND (either C406.2, C406.3 or C406.4) Compliance with C402, C403, C404 or C405 Section C402 Building Envelope (Climate Zone 5A) Space-Conditioning

More information

Energy-saving tips. Energy-saving tips For your home. For your home. part of your home. save energy in every. and ideas to help you

Energy-saving tips. Energy-saving tips For your home. For your home. part of your home. save energy in every. and ideas to help you Low-cost, no-cost tips and ideas to help you save energy in every part of your home Energy-saving tips For your home Puget Sound Energy P.O. Box 97034 Bellevue, WA 98009-9734 pse.com/myrebates 1230 08/14

More information

Canadian Property Inspections

Canadian Property Inspections Cover Page Canadian Property Inspections Home Inspection Report N6J-3A8 Inspection prepared for: Josh Baran Date of Inspection: 3/7/2017 Time: 9am Age of Home: 40 Size: 1500 Weather: Cloudy,cool,light

More information

Better Buildings By Design What are the best HVAC solutions for low-load, high performance homes? February 6-7, 2013

Better Buildings By Design What are the best HVAC solutions for low-load, high performance homes? February 6-7, 2013 What is Low-load? - Definition(s) Dr John Straube, P.Eng. What are the Best HVAC Solutions for Low Load, High Performance Homes?! Residence that requires a heating capacity of less than +/-25 kbtu/hr or

More information

Customized Energy Audit Report

Customized Energy Audit Report Customized Energy Audit Report PREPARED FOR: Tom Homeowner 1234 First Street Anytown, OH 45050 Homeowner, Tom PREPARED BY: Clint Cravens Building Performance Expert Email: ccravens@greenstreethome.us Dear

More information

Home Maintenance Schedule

Home Maintenance Schedule Home Maintenance Schedule Regular Maintenance is the Key Inspecting your home on a regular basis and following good maintenance practices are the best way to protect your investment in your home. Whether

More information

Town of Windham North Fire Station Energy Assessment Report. Table of Contents

Town of Windham North Fire Station Energy Assessment Report. Table of Contents Table of Contents 1. Table of Contents 1 2. Project Description 2 3. Executive Summary 2 1. Introduction 2. Identified Energy Conservation Measures 4. Energy Usage 6 1. Electrical 2. #2 Fuel 5. Building

More information

Fixing the Pretty Good House. Marc Rosenbaum, P.E. South Mountain Company West Tisbury, MA

Fixing the Pretty Good House. Marc Rosenbaum, P.E. South Mountain Company West Tisbury, MA Fixing the Pretty Good House Marc Rosenbaum, P.E. South Mountain Company West Tisbury, MA Specs West Tisbury, MA location One of 16 houses in Island Cohousing, developed, designed, and built in 99-00 by

More information

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. M&V Real Results of High Performance Design Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. Overview Measurement & Verification (M&V) Plan for New

More information

DISCOVER SAVINGS AT HOME. Cut costs and save energy with our rebates and programs

DISCOVER SAVINGS AT HOME. Cut costs and save energy with our rebates and programs DISCOVER SAVINGS AT HOME Cut costs and save energy with our rebates and programs Find your savings in the lighting aisle LED bulbs: Cut energy costs by 75 percent. Stay cool to the touch. Provide quality

More information

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance June 2018 Residential Air Leakage (Blower Door) Testing for Florida Code Compliance Infiltration or uncontrolled air leakage into buildings is a result of the number and size of cracks and gaps in the

More information

Homeowner s Guide: Being Energy Efficient

Homeowner s Guide: Being Energy Efficient Homeowner s Guide: Being Energy Efficient Most people don t know how easy it is to make their homes run on less energy. Drastic reductions in heating, cooling and electricity costs can be accomplished

More information

Low-Impact Remodeling

Low-Impact Remodeling Low-Impact Remodeling Mike O Brien, OSD Green Building Specialist Building envelope Solar heating & cooling Space heating Water heating Ventilation Moisture control Combustion safety Performance testing

More information

WHY IS BUILDING SCIENCE IMPORTANT?

WHY IS BUILDING SCIENCE IMPORTANT? OUTLINE Why Building Science is Important Building Science Key Components Controlling Air Flow Controlling Thermal Flow Controlling Moisture Flow ENERGY STAR Solutions Action Plan WHY IS BUILDING SCIENCE

More information

2010/2011 GOOD ENERGY REBATE PROGRAM

2010/2011 GOOD ENERGY REBATE PROGRAM 2010/2011 GOOD ENERGY REBATE PROGRAM YUKON GOVERNMENT S ENERGY SOLUTIONS CENTRE FINAL REPORT December 9, 2011 TABLE OF CONTENTS TABLE OF CONTENTS...2 1. PROGRAM OVERVIEW...3 2. PROJECT BUDGET...4 3. PROJECT

More information

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce. Ventilation ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce /NDCommerce /NDCommerce /NDCommerce /NDCommerce WHATS NEW IN ASHRAE 62.2 2016 Controls (Override) Shutoff for maintenance

More information

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings research highlight October 2005 Technical Series 05-112 Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings INTRODUCTION The provision of airtight interior

More information

USING INFRARED TECHNOLOGY TO DEFINE ENERGY SAVINGS OPPORTUNITIES. James L. Park Energy Conservation Specialist I-Star Energy Solutions

USING INFRARED TECHNOLOGY TO DEFINE ENERGY SAVINGS OPPORTUNITIES. James L. Park Energy Conservation Specialist I-Star Energy Solutions USING INFRARED TECHNOLOGY TO DEFINE ENERGY SAVINGS OPPORTUNITIES James L. Park Energy Conservation Specialist I-Star Energy Solutions Facilities are inundated with people selling devices and technology

More information

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM SUMMARY 1234 Main St.Severn 21144 Buyer Name 07/18/2018 9:00AM Henry Toman MD License 32391 1st American Home Inspection, LLC 443-685-4062 henrytoman61@gmail.com The summary is meant to organize the defects

More information