September 2016 AE Application Guidelines for Copeland CS**KIE Compressors in Ice Machines AE4-1421

Size: px
Start display at page:

Download "September 2016 AE Application Guidelines for Copeland CS**KIE Compressors in Ice Machines AE4-1421"

Transcription

1 AE September 2016 Application Guidelines for Copeland CS**KIE Compressors in Ice Machines TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons... 3 Safety Statements... 3 Introduction Nomenclature... 4 Operating Envelope... 4 Power Supply... 4 Electrical Connections... 4 Application Range & Approved Refrigerants... 4 Application Considerations Discharge Temperature... 4 Accumulators... 4 Superheat Requirements... 4 Crankcase Heaters... 5 Pressure Controls... 5 Pump Down Recommendations... 5 IPR Valve... 5 Internal Temperature Protection... 5 Motor Protection... 5 Oil Types... 6 Oil Charges... 6 Compressor Tubing & Mounting... 6 Starting Characteristics... 6 Shell Temperature... 6 Connection Fittings... 6 Deep Vacuum Operation... 6 Assembly Line Procedures Pulling Plugs... 6 Brazing Procedure... 6 Unbrazing System Components... 7 High Potential (Hipot) Testing... 7 Service Procedures Copeland Compressor Functional Check... 7 Compressor Replacement After Motor Burn... 7 Start-up of a New or Replacement Compressor New Installation... 8 Field Service... 8 Tables & Figures Tube Brazing... 8 CS**KIE Operating Envelope for R-404A... 9 Typical Mounting Assembly... 9 Build of Material Terminal Covers Electrical Connections Compressor Models & Approved Refrigerants Charge Limitations Crankcase Heater Kits Pressure Control Settings Recommended Oil Charges

2 Safety Instructions Copeland CS**KIE compressors are manufactured according to the latest U.S. and European Safety Standards. Particular emphasis has been placed on the user's safety. Safey icons are explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3. These instructions should be retained throughout the lifetime of the compressor. You are strongly advised to follow these safety instructions. Safety Icon Explanation DANGER WARNING CAUTION NOTICE CAUTION DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE is used to address practices not related to personal injury. CAUTION, without the safety alert symbol, is used to address practices not related to personal injury. 2

3 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons WARNING ELECTRICAL SHOCK HAZARD Disconnect and lock out power before servicing. Discharge all capacitors before servicing. Use compressor with grounded system only. Molded electrical plug must be used when required. Refer to original equipment wiring diagrams. Failure to follow these warnings could result in serious personal injury. WARNING PRESSURIZED SYSTEM HAZARD System contains refrigerant and oil under pressure. Remove refrigerant from both the high and low compressor side before removing compressor. Never install a system and leave it unattended when it has no charge, a holding charge, or with the service valves closed without electrically locking out the system. Use only approved refrigerants and refrigeration oils. Personal safety equipment must be used. Failure to follow these warnings could result in serious personal injury. WARNING BURN HAZARD Do not touch the compressor until it has cooled down. Ensure that materials and wiring do not touch high temperature areas of the compressor. Use caution when brazing system components. Personal safety equipment must be used. Failure to follow these warnings could result in serious personal injury or property damage. CAUTION COMPRESSOR HANDLING Use the appropriate lifting devices to move compressors. Personal safety equipment must be used. Failure to follow these warnings could result in personal injury or property damage. Safety Statements Refrigerant compressors must be employed only for their intended use. install, commission and maintain this equipment. All valid standards and codes for installing, servicing, and maintaining electrical and refrigeration equipment must be observed. 3

4 INTRODUCTION The Copeland CS**KIE compressor represents the latest generation of hermetic reciprocating technology for the ice machine industry. Nomenclature The refrigeration model numbers include the nominal capacity at standard 60HZ ARI rating conditions for medium temperature (20 F evap / 120 F cond / 20 F SH / 0 SC / 95 F amb). For additional information on this product, contact your Emerson representative. C = Compressor Family Series S = Medium Temperature 12K = Nominal Capacity (x 1,000 Btu/hr) I = Ice Machine Application E = POE Oil Operating Envelope The CS**KIE compressors are available in a 255 & 256 Bill of Material. The 255 build is complete with a rounded terminal cover while the 256 build is complete with a square terminal cover and is conduit ready. (See Figure 4 at the end of this bulletin). Both builds include sweat elbow up fittings. The CS**KIE ice machine compressor was designed for the use of R-404A and POE oil in ice machine applications only. The CS**KIE models are intended for medium temperature applications covering the full ice machine operating envelope. The approved operating envelopes for these models are such that they are ideally suited for ice machine applications. (See Figure 2) Power Supply All motors for the CS compressors whether single or three phase, with the exception of the PFV motor used on , 1Ø, 60 Hz power supply, are designed to operate within a voltage range of +/-10% above and below the voltages shown on the nameplate. Compressors with a PFV designated motor such as a CS14KIE-PFV, may only be operated in a range of volts, 60 Hz under maximum load conditions. Electrical Connections The orientation of the electrical connections of the CS**KIE compressors is shown in Figure 5. Compressor models can be ordered with the standard ¼ inch quick connects that come equipped with terminal box covers. Application Range & Approved Refrigerants All models are approved for use with refrigerant R-404A. All models may be operated within the entire operating envelope shown in Figure 2. CSKIE models are approved for use with R-404A. Use of refrigerants other than R-404A voids the UL listing of these models since they could affect the motor protector setting. R-404A can only be used with compressors containing Polyol Ester (POE) oil. Compressors containing POE have an 'E' just before the dash in the voltage code of the model number, e.g. CS14KIE-PFV. APPLICATION CONSIDERATIONS Discharge Temperature Figure 2 shows the operating envelope for the CS*KIE compressor. Operating beyond these limits can cause high compression ratios or excessive internal compressor temperatures. This will result in overheating the oil resulting in excessive wear or premature compressor failure. To prevent damage to the compressor the discharge temperature should never exceed 250 F. Discharge temperatures should be measured with an insulated probe 6 inches away from the discharge port of the compressor. Accumulators An accumulator is required on single compressor systems when the charge limitations exceed those values listed in Table 2. On systems with defrost/ harvest schemes or transient operations that allow prolonged uncontrolled liquid return to the compressor, an accumulator is required unless a suction header of sufficient volume to prevent liquid migration to the compressor is used. Excessive liquid flood back or repeated flooded starts will dilute the oil in the compressor causing inadequate lubrication and bearing wear. Proper system design will minimize liquid flood back, thereby ensuring maximum compressor life. Superheat Requirements In order to assure that liquid refrigerant does not return to the compressor during the running cycle, attention 4

5 must be given to maintaining proper superheat at the compressor suction inlet. Emerson recommends a minimum of 20 F (11 C) superheat, measured on the suction line 6 inches (152mm) from the suction valve, to prevent liquid refrigerant flood back. However, operation can be as low as 10 F at certain conditions. Another method to determine if liquid refrigerant is returning to the compressor is to accurately measure the temperature difference between the compressor oil crankcase and the suction line. During continuous operation we recommend that this difference be a minimum of 50 F (27 C). This 'crankcase differential temperature' requirement supersedes the minimum suction superheat requirement in the last paragraph. To measure oil temperature through the compressor shell, place a thermocouple on the bottom center (not the side) of the compressor shell and insulate from the ambient. During rapid system changes, such as during ice harvest cycles, this temperature difference may drop rapidly for a short period of time. When the crankcase temperature difference falls below the recommended 50 F (27 C), our recommendation is the duration should not exceed a maximum (continuous) time period of two minutes and should not go lower than a 25 F (14 C) difference. Contact your Emerson Climate Technologies representative regarding any exceptions to the above requirements. Crankcase Heaters Crankcase heaters are required on all CS**KIE compressors where the system charge exceeds the recommended charge limit or when ambient conditions can drop below 50 F. The listed crankcase heaters are intended for use only when there is limited access (see Table 3). Some heaters are equipped for use with electrical conduit. Where applicable, electrical safety codes require lead protection, a crankcase heater terminal box should be used. Recommended crankcase heater terminal box and cover kits numbers are listed in Table 3. Pressure Controls Both high and low-pressure controls are required on all models. See Table 4 for set points. Pump Down Recommendations If short cycling occurs please check these several factors: 1. Location of low-pressure control sensor. If it is located right at the suction inlet of the compressor, it will be more sensitive to pressure spikes. 2. Actual low-pressure setting. Refer to our recommended setting in Table 4. If the differential pressure setting is too close, this will increase the possibility of short cycling. 3. Type of Low-pressure control can have an effect on cycling. The encapsulated non-adjustable typeis more susceptible to causing excessive cycling due to tolerances. 4. If short cycling cannot be avoided, using a 5-minute time delay will limit the cycling of the compressor to an acceptable level. IPR Valve CS**KIE The internal pressure relief valve is located between the internal discharge and suction side of the compressor. It is designed to open when the dischargeto-suction pressure differential exceeds 450 to 550 psid. When the valve opens, hot discharge gas is released into the low pressure housing of the compressor. This has the effect of both increasing the suction pressure, and therefore load and current draw of the motor, as well as the temperature in the low side of the shell. Since the motor protector reacts to a combination of temperature and current it will trip and disconnect the motor once its set point is reached. Internal Temperature Protection CS**KIE ice machine compressors do not have internal discharge temperature protection. The protector opens the common connection of a single-phase motor and the center of the Y connection on three-phase motors. The three-phase protector provides primary single-phase protection. Both types of protectors react to current and motor winding temperature. In order to maintain safe discharge temperatures the compressor operation should not exceed the operating envelope. Motor Protection Conventional internal line break motor protection is 5

6 provided. The protector opens the common connection of a single-phase motor and the center of the Y connection on three-phase motors. The three-phase protector provides primary single-phase protection. Both types of protectors react to current and motor winding temperature Oil Types Polyol ester lubricants must be provided since the compressor is to be used with R-404A refrigerant. See Form for a complete list of all Emerson approved lubricants. POE must be handled carefully and the proper protective equipment (gloves, eye protection, etc.) must be used when handling POE lubricant. POE must not come into contact with any surface or material that might be harmed by POE, including without limitation, certain polymers (e.g. PVC/ CPVC and polycarbonate). Oil Charges The recommended oil charges for these compressors are shown in Table 5. Compressor Tubing and Mounting Compressor mounting must be selected based on application. See Figure 3. Consideration must be given to sound reduction and tubing reliability. Some tubing geometry or shock loops may be required to reduce vibration transferred from the compressor to external tubing. Starting Characteristics Single-phase CS**KIE compressors are designed for use with a PTC device or a start capacitor and relay. One of these start assist devices is recommended to prevent start up issues during high compression ratios or low voltage supply. Shell Temperature Since the entire shell of the CS compressor is only exposed to suction pressure it will normally be relatively cool to the touch with the exception of the compressor sump which depending on operating conditions may get as hot as 200 F. A hotter sump would indicate operation outside of approved parameters. Connection Fittings CS**KIE compressors are provided only with sweat connections. (Consult your Emerson Climate Technologies representative for details). See New Installation section for suggestions on how to properly braze these fittings. Deep Vacuum Operation Do not run any refrigeration compressor in a deep vacuum. Failure to heed this advice can result in permanent damage to the compressor. A low-pressure control is required for protection against deep vacuum operation. See the section on pressure controls for the proper set points. (See Table 4) Refrigeration compressors should never be used to evacuate refrigeration or air conditioning systems. See AE for proper system evacuation procedures. ASSEMBLY LINE PROCEDURES Pulling Plugs All hermetic compressors are pressurized with 7 to 15 psi (.5-1 kg/cm2) of dry air before they leave the factory. The plugs that seal the compressors should not be removed until the compressor has had sufficient time to reach factory temperature, if stored in an unheated space, and is ready to be brazed into the system. If a compressor contains POE oil, it should not be open to the atmosphere longer than 5 minutes. The larger suction tube plug must be pulled first to relieve most of the pressure in the compressor. Brazing Procedure Figure 1 discusses the proper procedures for brazing the suction and discharge lines to a CSKIE compressor with a copper plated steel suction fitting. It is important to flow nitrogen through the system while brazing all joints during the system assembly process. Nitrogen displaces the air and prevents the formation of copper oxides in the system. If allowed to form, the copper oxide flakes can later be swept through the system and block screens such as those protecting capillary tubes, thermal expansion valves, and accumulator oil return holes. This can lead to a blockage of oil or refrigerant which in turn can cause damage to the system and compressor. 6

7 Unbrazing System Components If the refrigerant charge is removed from a unit the high and low side of the system must be evacuated. Refrigerant will not be able to cross the valve plate inside the compressor. If one side is not evacuated and a brazing torch is then applied, the pressurized refrigerant oil mixture could ignite as it escapes and contacts the brazing flame. It is important to check both the high and low sides with manifold gauges before unbrazing. In the case of an assembly line repair, remove the refrigerant from both the high and low sides. Instructions should be provided in appropriate product literatures and assembly areas. High Potential (Hipot) Testing When Copeland compressors are Hipot tested and liquid refrigerant is in the shell, they can show higher levels of leakage current. This phenomenon can occur with any compressor when the motor is immersed in refrigerant. The level of current leakage does not present any safety issue. To lower the current leakage reading, the system should be operated for a brief period of time to redistribute the refrigerant to a more normal configuration and the system Hipot tested again. See bulletin AE for Megohm testing recommendations. Under no circumstances should the Hipot or Megohm test be performed while the compressor is under a vacuum. SERVICE PROCEDURES Copeland Compressor Functional Check The following diagnostic procedure should be used to evaluate whether a CS**KIE compressor is functioning properly: 1. Proper voltage to the unit should be verified. Determine if the internal motor overload protector has opened or if an internal motor short or ground fault has developed. If the protector has opened, the compressor must be allowed to cool sufficiently to allow it to reset. 2. Check that the compressor is correctly wired. 3. Verify that no system safety devices are keeping the compressor off. Check that the condenser fan is properly working. 4. With service gauges connected to suction and discharge pressure fittings, turn on the compressor. If suction pressure falls below normal levels the system is either low on charge or there is a flow blockage in the system. 5. To test if the compressor is pumping properly, the compressor current draw must be compared to published compressor performance curves using the operating pressures and voltage of the system. If the measured average current deviates more than ±15% from published values, a faulty compressor may be indicated. A current imbalance exceeding 15% of the average on the three phases of a threephase compressor should be investigated further. A more comprehensive trouble-shooting sequence for compressors and systems can be found in Section H of the Emerson Electrical Handbook, Form Before Replacing or Returning a Compressor Be certain that the compressor is actually defective. As a minimum, recheck a compressor for Hipot, winding resistance, and ability to start before returning to Emerson. More than one-third of compressors returned to Emerson for warranty analysis are determined to have nothing found wrong. Compressor Replacement after Motor Burn In the case of a motor burn, the majority of contaminated oil will be removed with the compressor. The rest of the oil is cleaned through use of suction and liquid line filter dryers. A 100% activated alumina suction filter drier is recommended but must be removed after 72 hours. See AE for cleanup procedures and AE for liquid line filter-drier recommendations. It is highly recommended that the suction accumulator be replaced if the system contains one. This is because the accumulator oil return orifice or screen may be plugged with debris or may become plugged shortly after a compressor failure. This will result in starvation of oil to the replacement compressor and a second failure. Start-up of a New or Replacement Compressor It is good service practice, when charging a system, to charge liquid refrigerant into the high side only and charge the low side of the system with vapor only. It is not good for any compressor to have liquid refrigerant 7

8 dumped from a refrigerant cylinder into the crankcase of the compressor. Do not start the compressor while the system is in a deep vacuum. Internal arcing may occur when a compressor is started in a vacuum. Do not operate compressor without enough system charge to maintain at least 7 psig (0.5 kg/cm2) suction pressure. Do not operate with a restricted suction. Do not operate with the low pressure cut-out disabled. Allowing suction pressure to drop below 7 psig (0.5 kg/cm2) for any length of time may overheat the compressor and cause early bearing and piston ring damage. Never install a system in the field and leave it unattended with no charge, a holding charge, or with the service valves closed without securely locking out the system. This will prevent unauthorized personnel from accidentally operating the system and potentially ruining the compressor with no refrigerant flow. New Installation The copper-coated steel suction, discharge, on CS**KIE compressors can be brazed in approximately the same manner as any copper tube. Recommended brazing material - Any Silfos material is recommended, preferably with a minimum of 5% silver. However, 0% silver is acceptable. Use of a dry nitrogen purge to eliminate possibility of carbon buildup on internal tube surfaces is recommended. Be sure process tube fitting I.D. and process tube O.D. are clean prior to assembly. Apply heat in Area 1. As tube approaches brazing temperature, move torch flame to Area 2. (See Tube Brazing figure below.) As with any brazed joint, overheating may be detrimental to the final result. Field Service To disconnect: Recover refrigerant from both the high and low side of the system. Cut tubing near compressor. To reconnect: Recommended brazing materials -Silfos with minimum 5% silver or silver braze material with flux. Reinsert tubing fitting. Heat tube uniformly in Area 1, moving slowly to Area 2. When joint reaches brazing temperature, apply brazing material. (See figure below) Heat joint uniformly around the circumference to flow braze material completely around the joint. Slowly move torch in Area 3 to draw braze material into the joint. Do not overheat joint. 3 2 }1 } } Figure 1 Tube Brazing Heat Area 2 until braze temperature is attained, moving torch up and down and rotating around tube as necessary to heat tube evenly. Add braze material to the joint while moving torch around circumference. After braze material flows around joint, move torch to heat Area 3. This will draw the braze material down into the joint. The time spent heating Area 3 should be minimal. 8

9 Condensing Temp, F Evaporating Temp, C Condensing Temp, C Evaporating Temp, F Figure 2 CS**KIE Operating Envelope for R-404A (Ice Machine Application) Spacer # Sleeve # Kit # Figure 3 Typical Mounting Assembly for Grommets Designed for Straight Through Sleeves or Studs 9

10 -255 BOM -256 BOM Figure 4 Bill of Material Terminal Covers 1 T1,C T2,S T3,R 2 3 Figure 5 Motor Winding Connections 10

11 Model CS10KIE Motor Code HP Refrigerant Lubricant 3/4 CS12KIE PFV, TF5 1 CS14KIE 1-1/4 R-404A POE Table 1 Compressor Models and Approved Refrigerants/Lubricants See Form for a complete list of all Emerson approved lubricants. Model Family CS10KIE - CS14KIE Table 2 Charge Limitations Charge Limits 6 lbs Model Part # Volts Watts Description CS10KIE, CS12KIE, CS14KIE /265 40/ /575 45/ Table 3 Crankcase Heater Kits EHP Flexible 60 SS Rigid s/conduit Box Model Pressure Control R-404A CS**KIE Low 20 PSIG Min Cut Out High Table 4 Pressure Control Settings 450 PSIG Max Cut Out Model Initial (oz) Recharge (oz) CS10KIE - CS14KIE Table 5 Recommended oil Charges The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively "Emerson"), as applicable, reserve the right to modify the design or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user. 11

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors AE4-1296 R3 March 2013 Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Instructions... 2 Safety Icon Explanation... 2

More information

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors August 2017 Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Safety... 2 Safety Instructions... 2 Safety Icon Explanation... 2 Instructions

More information

Application Guidelines for ZS**KAE Refrigeration Copeland Scroll Compressors HP

Application Guidelines for ZS**KAE Refrigeration Copeland Scroll Compressors HP AE4-1387 R8 April 2015 Application Guidelines for ZS**KAE Refrigeration Copeland Scroll Compressors 1.3-4.5 HP TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2

More information

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A AE4-1392 July 2014 Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A Section TABLE OF CONTENTS Page Safety Safety Instructions...2 Safety Icon Explanation...2 Instructions

More information

AE R17 November 2016

AE R17 November 2016 AE4-1344 R17 November 2016 Application Guidelines for Copeland RFT, RRT, RST Compressors For Refrigerants R-134A, R-450A,R-513A, R-290, R-404A, R-448A, R-449A and R-507 Section TABLE OF CONTENTS Page Safety

More information

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) 4-1280 Application Engineering Bulletin AE-1280R4 Revised April, 1995 APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) Introduction The Compliant Scroll Compressor has been

More information

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors October 2017 1.5 to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury

More information

AE R21 September 2017

AE R21 September 2017 September 2017 Application Guidelines for Copeland AF, AR & AS Refrigeration Hermetic Compressors For Refrigerants R-22, R-134A, R-404A, R-507, R-290, R-450A, R-513A, R-448A, R-449A TABLE OF CONTENTS Revision

More information

AE R20 January Cooling Requirements for Copelametic and Copeland Discus Compressors

AE R20 January Cooling Requirements for Copelametic and Copeland Discus Compressors January 2018 Cooling Requirements for Copelametic and Copeland Discus Compressors TABLE OF CONTENTS Safety... 2 Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk of

More information

AE R3. July 2016 AE R3. Replaces AE CR KQ, CR K6, CR_5, CR K7 Hermetic Reciprocating Compressors

AE R3. July 2016 AE R3. Replaces AE CR KQ, CR K6, CR_5, CR K7 Hermetic Reciprocating Compressors Replaces AE4-1289 CR KQ, CR K6, CR_5, CR K7 Hermetic Reciprocating Compressors AE4-1329 R3 July 2016 Introduction The CR KQ, CR K6, CR_5 and CR K7 Copeland hermetic compressors include a wide range of

More information

AE R4 July 2015 Guide for the Use of R-290 Refrigerant in Copeland Refrigeration Compressors

AE R4 July 2015 Guide for the Use of R-290 Refrigerant in Copeland Refrigeration Compressors July 2015 Guide for the Use of R-290 Refrigerant in Copeland Refrigeration Compressors TABLE OF CONTENTS Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk of

More information

Application Engineering

Application Engineering APPLICATION GUIDELINES FOR ZB*KC/ZB*KCE COPELAND SCROLL REFRIGERATION COMPRESSORS 7 TO 15 HP AE4-1318 R1 June 2008 Introduction The Copeland Scroll ZB*KC/ZB*KCE refrigeration compressor product offering

More information

Application Engineering

Application Engineering Application Engineering Application Guidelines For ZR90K3 to ZR19M3 and ZR250KC to ZR300KC Copeland Scroll Compressors AE-1316 R1 August 2009 Introduction This bulletin describes the operating characteristics,

More information

Application Guidelines for ZB*KC/ZB*KCE Copeland Scroll Refrigeration Compressors 7 to 15 HP

Application Guidelines for ZB*KC/ZB*KCE Copeland Scroll Refrigeration Compressors 7 to 15 HP Application Application Engineering Engineering AE4-1318 R8 April 2014 Application Guidelines for ZB*KC/ZB*KCE Copeland Scroll Refrigeration Compressors 7 to 15 HP TABLE OF CONTENTS Section Page Section

More information

AE R9. AE R9 May Application Guidelines For K4 Refrigeration Copeland Scroll Compressors Horsepower

AE R9. AE R9 May Application Guidelines For K4 Refrigeration Copeland Scroll Compressors Horsepower AE4-1302 R9 May 2014 Application Guidelines For K4 Refrigeration Copeland Scroll Compressors 7.5-15 Horsepower TABLE OF CONTENTS Section Page Section Page Safety Instructions... 2 Safety Icon Explanation...

More information

AE R1 Application Guidelines for ZB*KAU Copeland R-290. August Scroll Compressors

AE R1 Application Guidelines for ZB*KAU Copeland R-290. August Scroll Compressors Application Guidelines for ZB*KAU Copeland R-290 August 2018 Scroll Compressors TABLE OF CONTENTS Safety... 3 Safety Instructions... 3 Safety Icon Explanation... 3 Instructions Pertaining to Risk of Electrical

More information

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate Technologies, Inc. does not advocate

More information

Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE

Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE About this guideline... 1 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety statements... 1 1.3 General

More information

AE R8 March 2015

AE R8 March 2015 March 2015 Copeland Discus Compressors with Demand Cooling System TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk

More information

Refrigerant Recovery Machine. Model No Operating Manual

Refrigerant Recovery Machine. Model No Operating Manual Refrigerant Recovery Machine Model No. 25700 Operating Manual Safety Precautions WARNING : TO PREVENT PERSONAL INJURY AND / OR EQUIPMENT DAMAGE, CAUTION - Risk of injury. This equipment should only be

More information

AE ZJ36 to ZJ54KHE R410A Copeland Scroll Compressors

AE ZJ36 to ZJ54KHE R410A Copeland Scroll Compressors AE4-1415 December 2015 ZJ36 to ZJ54KHE R410A Copeland Scroll Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

Residential Piping and Long Line Guideline

Residential Piping and Long Line Guideline AC / HP R-410A Refrigerant Systems Single-Stage, Two-Stage and Variable Speed Models Residential Piping and Long Line Guideline TABLE OF CONTENTS Safety Considerations... 2 Definitions... 2 Introduction...

More information

Refrigerant changeover guidelines

Refrigerant changeover guidelines Refrigerant changeover guidelines HCFC R-22 to HFC R-407A/F, R-448A or R-449A for medium and low temperature applications HCFC R-22 to HFC R-407C for high, medium and low temperature applications HCFC

More information

NO: 9-16 DATE: 2/11/16 EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -EMERSON TM TECHNICAL SPECIALISTS -BRANCH PERSONNEL

NO: 9-16 DATE: 2/11/16 EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -EMERSON TM TECHNICAL SPECIALISTS -BRANCH PERSONNEL NO: 9-16 DATE: 2/11/16 TO: EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -EMERSON TM TECHNICAL SPECIALISTS -BRANCH PERSONNEL SUBJECT: Procedure for Changing CS Compressor to Copeland

More information

7 to 15 Ton ZR*KC and ZP*KC Copeland Scroll Compressors

7 to 15 Ton ZR*KC and ZP*KC Copeland Scroll Compressors 7 to 15 Ton ZR*KC and ZP*KC Copeland Scroll Compressors AE4-1303 R15 AE4-1303 R15 June 2016 TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2 Instructions

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M 2004 Lennox Industries Inc. Dallas, Texas KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04 Supersedes 503,249M Litho U.S.A. COMPRESSOR REPLACEMENT KIT INSTALLATION INSTRUCTIONS FOR COMPRESSOR

More information

Application Guidelines

Application Guidelines Application Guidelines Copeland Scroll Variable Speed Heat Pump Compressors ZHW015* & ZHW030* About these guidelines... 1 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety statements... 1

More information

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual RecoverX Oil-Filled Hermetic Refrigerant Recovery System Operation and Maintenance Manual Table of Contents Page General Safety Instructions 2-3 System Overview 3 Operating Guide 4 Restart Procedure 4

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Warranty Information Ritchie Engineering guarantees YELLOW JACKET products to be free of defective material and workmanship which could affect the life of the product when used for the purpose for which

More information

Application Guidelines. Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K*

Application Guidelines. Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K* Application Guidelines Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K* About these guidelines... 1 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety statements...

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

REFRIGERANT CHANGEOVER

REFRIGERANT CHANGEOVER Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants

More information

Application Guidelines. Copeland Scroll Summit Series ZB50KCE to ZB114KCE & ZB66K5E to ZB114K5E ZF25K5E to ZF49K5E

Application Guidelines. Copeland Scroll Summit Series ZB50KCE to ZB114KCE & ZB66K5E to ZB114K5E ZF25K5E to ZF49K5E Application Guidelines Copeland Scroll Summit Series ZB50KCE to ZB114KCE & ZB66K5E to ZB114K5E ZF25K5E to ZF49K5E About these guidelines... 1 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety

More information

Digital Scroll Compressors for Air Conditioning

Digital Scroll Compressors for Air Conditioning Application Guidelines TM Digital Scroll Compressors for Air Conditioning ZRD42K* to ZRD125K*, ZPD34K* to ZPD182K* About these guidelines... 1 1 Safety instructions... 1 1.1 Icon explanation... 1 1.2 Safety

More information

APPROVAL SHEET SPECIFICATIONS OF HERMETIC SCROLL COMPRESSOR C-SBR180H16A

APPROVAL SHEET SPECIFICATIONS OF HERMETIC SCROLL COMPRESSOR C-SBR180H16A No. :WXXS-000-GGSY-12 APPROVAL SHEET SPECIFICATIONS OF HERMETIC SCROLL COMPRESSOR MODEL C-SBR180H16A NO. DATE PAGE REVISION DETAILS SANYO SIGNED CLIENT SIGNED REVISION RECORD USER: MANUFACTURER: DALIAN

More information

AE R13 August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS

AE R13 August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS Safety Instructions... 3 Safety Icon Explanation... 3 Instructions Pertaining to Risk of Electrical Shock,

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

Digital. Application Guidelines Digital Scroll Compressors for Refrigeration ZBD21K* to ZBD114K* ZFD13KVE to ZFD25KVE ZFD41K5E

Digital. Application Guidelines Digital Scroll Compressors for Refrigeration ZBD21K* to ZBD114K* ZFD13KVE to ZFD25KVE ZFD41K5E Digital Application Guidelines Digital Scroll Compressors for Refrigeration ZBD21K* to ZBD114K* ZFD13KVE to ZFD25KVE ZFD41K5E About these guidelines... 1 1 Safety instructions... 1 1.1 Icon explanation...

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET General Piping Recommendations and Refrigerant Line Length for Split-System Air Conditioners and Heat Pumps GENERAL GUIDELINES This Split-System (Air Conditioning Condensing/Heat

More information

HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B COUNTER SHOWCASE MODEL SERVICE MANUAL HOSHIZAKI

HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B COUNTER SHOWCASE MODEL SERVICE MANUAL HOSHIZAKI NO. S051-800 ISSUED: MAR. 26, 2010 REVISED: HOSHIZAKI COUNTER SHOWCASE MODEL HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B SERVICE MANUAL IMPORTANT This manual should be read carefully

More information

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration

More information

Danfoss Inverter scroll compressor, VRJ

Danfoss Inverter scroll compressor, VRJ Application Guidelines Danfoss Inverter scroll compressor, VRJ For Residential Applications - R410A http://danfoss.us.com/ Contents Introduction...6 Scroll compressor components... 6 Compressor size...

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

TRS21 IGNITION PROOF SERIES

TRS21 IGNITION PROOF SERIES TRS21 IGNITION PROOF SERIES 2 Cylinder Commercial Recovery Machine OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TRS21A, TRS21E TO BE OPERATED BY QUALIFIED

More information

Installation Instructions

Installation Instructions Performance Series Heat Pumps with PURONr Refrigerant 1 --- 1/2 to 5 Nominal Tons Installation Instructions Fig. 1 --- A07532 NOTE: Read the entire instruction manual before starting the installation.

More information

Air Conditioning Operation and Troubleshooting Matt Dunham

Air Conditioning Operation and Troubleshooting Matt Dunham Air Conditioning Operation and Troubleshooting Matt Dunham Major Components (10 Minutes) Compressor heart of the system, causes refrigerant to flow by increasing the pressure of the refrigerant Metering

More information

Application Engineering

Application Engineering Application Engineering May 2010 Cooling Requirements for Copelametic and Copeland Discus Compressors Introduction In response to customer inquires, both domestic and international, Emerson Climate Technologies

More information

Application Guidelines. Copeland Scroll Compressors for Refrigeration. ZB15K* to ZB220K*, ZS21K* to ZS11M* ZF06K* to ZF48K*, ZF13KVE to ZF48KVE

Application Guidelines. Copeland Scroll Compressors for Refrigeration. ZB15K* to ZB220K*, ZS21K* to ZS11M* ZF06K* to ZF48K*, ZF13KVE to ZF48KVE Application Guidelines Copeland Scroll Compressors for Refrigeration ZB15K* to ZB220K*, ZS21K* to ZS11M* ZF06K* to ZF48K*, ZF13KVE to ZF48KVE About these guidelines... 1 1 Safety instructions... 1 1.1

More information

Copeland Scroll Condensing Units for the Food Service Market

Copeland Scroll Condensing Units for the Food Service Market Copeland Scroll Condensing Units for the Food Service Market...with Best In Class Emerson System Protection Components Medium and Low Temperature Refrigeration Applications R-404A 1.5 to 10 Hp Reliable

More information

R100 Oil-Less Refrigerant Recovery Unit

R100 Oil-Less Refrigerant Recovery Unit R100 Oil-Less Refrigerant Recovery Unit Operation Manual 1 INTRODUCTION Welcome to simple, efficient refrigerant recovery with your new YELLOW JACKET Refrigerant Recovery Unit, R100. This unit combines

More information

OPERATION & MAINTENANCE MANUAL TX600

OPERATION & MAINTENANCE MANUAL TX600 OPERATION & MAINTENANCE MANUAL TX600 RTI TECHNOLOGIES, INC. 4075 East Market Street York, PA 17402 Manual P/N 035-80118-00 (Rev B) ! TABLE OF CONTENTS! TX600 Before Using Page 2 Safety Precautions Page

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

MAKING MODERN LIVING POSSIBLE. Residential and light commercial scroll compressors Hz R-407C / R-22 / R-410A SELECTION & APPLICATION GUIDELINES

MAKING MODERN LIVING POSSIBLE. Residential and light commercial scroll compressors Hz R-407C / R-22 / R-410A SELECTION & APPLICATION GUIDELINES MAKING MODERN LIVING POSSIBLE Residential and light commercial scroll compressors 50-60 Hz R-407C / R-22 / R-410A SELECTION & APPLICATION GUIDELINES CONTENTS Scroll compression principle... 5 The scroll

More information

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER! 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS INSTALLATION GUIDE R-410A ATTENTION, INSTALLER! After installing the system, show the user how to turn off electricity to the unit. Point out control and switch

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 2-Stage R-410A Split System These units have been designed and tested for capacity & efficiency in accordance with A.H.R.I. Standards.

More information

TRS21 IGNITION PROOF SERIES

TRS21 IGNITION PROOF SERIES TRS21 IGNITION PROOF SERIES 2 Cylinder Commercial Recovery Machine OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TRS21, TRS21C, TRS21S Evaluated for

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

A Series Inertia Compressor Applications. Application Bulletin 115

A Series Inertia Compressor Applications. Application Bulletin 115 A Series Inertia Compressor Applications Application Bulletin 115 Application Bulletin Subject: A Series Inertia Compressor Applications Number: 115 Release EN: 006X04 Date: 1/6/92 Revision EN: Z27301

More information

Installation Instructions

Installation Instructions 25HHA4 Performance Series Heat Pump with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-25HHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS 22-1182 Application Engineering Bulletin AE-1182-R24 Revised April 1, 1993 LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS One of the major causes of compressor failure is damage

More information

Danfoss Scroll for Refrigeration MLM / MLZ

Danfoss Scroll for Refrigeration MLM / MLZ s Danfoss Scroll for Refrigeration MLM / MLZ 50-60 Hz - R404A - R507 - R134a - R22 - R407A - R407F http://danfoss.us.com/ Contents Features... 6 Scroll compression principle... 7 The scroll compression

More information

H29A Series Compressor Applications. Application Bulletin 139

H29A Series Compressor Applications. Application Bulletin 139 H29A Series Compressor Applications Application Bulletin 139 Application Bulletin Subject: H29A Series Compressor Applications Number: 139 Release EN: J28319 Date: 4/26/02 Revision EN: Z27301 Date: 10/2/15

More information

Performer Heat Pump scroll compressors 50 Hz - R407C Selection & application guidelines

Performer Heat Pump scroll compressors 50 Hz - R407C Selection & application guidelines MAKING MODERN LIVING POSSIBLE Performer Heat Pump scroll compressors 50 Hz - R407C Selection & application guidelines CONTENTS SCROLL COMPRESSION PRINCIPLE... 3 Scroll compressor components... 3 The

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11 SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-479 Supersedes: NEW File: Volume

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

RecoverX-CAR Contaminated Automotive Refrigerant Recovery System Operation and Maintenance Manual

RecoverX-CAR Contaminated Automotive Refrigerant Recovery System Operation and Maintenance Manual RecoverX-CAR Contaminated Automotive Refrigerant Recovery System Operation and Maintenance Manual (English) Table of Contents Page General Safety Instructions...2 System Overview...3 RecoverX-CAR Operation

More information

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

POLICY BULLETIN Tecumseh Compressor Company Compressor Group PAGE: 1 of 4 A rotary compressor is a precision piece of equipment, designed and manufactured to very close tolerances. For superior performance and long term reliability the following parameters must

More information

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3) www.dometic.com Freightliner Refrigerator Troubleshooting Guide For Before initiating troubleshooting, the following equipment is recommended: Multimeter, 20 gauge (min) wires to use as jumpers, and 12Vdc

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Split System Cooling Condensers Model CTA 7 1/2 to 15 Tons Models A and later Design Sequence CTA 090A***A 60 HZ 120A***A 60 HZ 120B***A 60 HZ 180B***A 60 HZ SS-SVN11A-EN

More information

NO. 15FD-742 ISSUED: AUG. 10, 2007 REVISED: SEP. 30, 2013 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER KM-30A KM-35A KM-50A KM-75A MODEL SERVICE MANUAL

NO. 15FD-742 ISSUED: AUG. 10, 2007 REVISED: SEP. 30, 2013 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER KM-30A KM-35A KM-50A KM-75A MODEL SERVICE MANUAL NO. 15FD-742 ISSUED: AUG. 10, 2007 REVISED: SEP. 30, 2013 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER MODEL KM-30A KM-35A KM-50A KM-75A SERVICE MANUAL CONTENTS PAGE I. SPECIFICATIONS--------------------------------------------------------------------------------------1

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

Danfoss scroll for refrigeration LLZ013 to low temperature

Danfoss scroll for refrigeration LLZ013 to low temperature MAKING MODERN LIVING POSSIBLE Application guidelines Danfoss scroll for refrigeration LLZ013 to 033 - low temperature 50-60 Hz - R404A - R507 http://cc.danfoss.com Contents Features...4 Scroll compression

More information

HSXA15 HSXB15. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.

HSXA15 HSXB15. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A. Service Literature Corp. 0128 L12 Revised 10 2004 HSXB15 & HSXB15 SERIES UNITS The and HSXB15 are high efficiency residential split system condensing units, which features a scroll compressor and R410A

More information

Código : Motc.PANASC/SANYO-CSB453H8A--6HP-15100fr

Código : Motc.PANASC/SANYO-CSB453H8A--6HP-15100fr Código : 98422 Motc.PANASC/SANYO-CSB453H8A--6HP-151fr Section 1. General Specifications Content Unit Specification Compressor Model (Code) C-SB453H8A (89 86 88) Type Application Evap. Temp. Range Compressor

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS R 410A Ducted Horizontal Air Conditioner Product Family: HC4A3 Fig. 1 - HC4A3 NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE

More information

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

2 shp 13 lc 1 36 t - 1 a

2 shp 13 lc 1 36 t - 1 a HEAT PUMPs 2SHP3 PRODUCT SPECIFICATIONS Dry Charge Split System - 60 HZ Bulletin No. 20645 July 203 Supersedes June 202 3 to 5 Tons MODEL NUMBER IDENTIFICATION 2 shp 3 lc 36 t - a Refrigerant Type 2 =

More information

Daikin Direct Expansion (DX) Cooling Coils

Daikin Direct Expansion (DX) Cooling Coils Installation and Maintenance Manual IM 902 Daikin Direct Expansion (DX) Cooling Coils Group: Applied Air Part Number: IM 902 Date: February 2008 Types EN, EF, ER, EJ, EK 2008 Daikin Applied Contents Introduction...

More information

OPERATION & MAINTENANCE MANUAL TC670

OPERATION & MAINTENANCE MANUAL TC670 OPERATION & MAINTENANCE MANUAL TC670 Refrigerant Management Center (Convertible For Use With R12 or R134a) RTI TECHNOLOGIES, INC. 4075 East Market Street York, PA 17402 Manual P/N 035-80342-02 TC670 CONVERTIBLE

More information

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Commercial Refrigerators & Freezers Models RR28A RR55A RF28A RF55A A Superior Degree of Reliability SERVICE MANUAL www.hoshizaki.com Number: 73139 Issued: 8-31-2006 IMPORTANT Only

More information

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved. GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant

More information

MAKING MODERN LIVING POSSIBLE. MLZ / MLM Refrigeration scroll compressors Hz - R404A - R507 - R134a - R22. Selection & application guidelines

MAKING MODERN LIVING POSSIBLE. MLZ / MLM Refrigeration scroll compressors Hz - R404A - R507 - R134a - R22. Selection & application guidelines MAKING MODERN LIVING POSSIBLE MLZ / MLM Refrigeration scroll compressors 50-60 Hz - R404A - R507 - R134a - R22 Selection & application guidelines Contents Features... 4 Scroll compression principle...

More information

F-2000MLF(-C) F-2000MWF(-C) F-2000MRF(-C) F-2000MRF3(-C)

F-2000MLF(-C) F-2000MWF(-C) F-2000MRF(-C) F-2000MRF3(-C) NO: 73099 ISSUED: AUG. 29, 2001 REVISED: DEC. 16, 2003 HOSHIZAKI MODULAR FLAKER MODEL F-2000MLF(-C) F-2000MWF(-C) F-2000MRF(-C) F-2000MRF3(-C) SERVICE MANUAL IMPORTANT Only qualified service technicians

More information

OWNER S MANUAL (English)

OWNER S MANUAL (English) TRS600 IGNITION PROOF SERIES Refrigerant Recovery Machines OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TRS600, TRS600K, TRS600S Evaluated for performance

More information

HS25 SERVICE UNIT INFORMATION

HS25 SERVICE UNIT INFORMATION SERVICE UNIT INFORMATION HS25 Corp. 9327-L3 Litho U.S.A. HS25 SERIES UNITS The HS25 is a high efficiency residential split system condensing unit which features a scroll compressor. It operates much like

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information