Cab Heater and Air Conditioner, Water-Valve Controlled 83.02

Size: px
Start display at page:

Download "Cab Heater and Air Conditioner, Water-Valve Controlled 83.02"

Transcription

1 Preliminary Checks Before testing the operation of the air conditioning system, make the following checks: 1. Make sure the drive belt on the refrigerant compressor is not damaged and is correctly tensioned. Also check the compressor mountings for tightness. For instructions and other information, refer to the applicable refrigerant compressor section in this group. 2. Using a feeler gauge, check for correct refrigerant compressor clutch clearance. For instructions, refer to the applicable refrigerant compressor section in this group. 3. Check for broken, burst, or cut hoses. Also check for loose fittings on all parts. 4. Check for road debris buildup on the condenser coil fins. Using air pressure and a whiskbroom or a soapy spray of water, carefully clean off the condenser. Be careful not to bend the fins. 5. Check the color of the moisture indicator sight glass. If the color is blue, the refrigerant charge is dry. If the indicator is not blue, the system is contaminated with moisture. Recover the refrigerant, evacuate the system, replace the receiverdrier, and add a full refrigerant charge. 6. If there is not enough airflow, make sure that leaves or other debris have not entered the fresh air ports under the windshield. If debris have entered, it could clog the fins of the evaporator core and block airflow. Also be sure that all ducts are connected to the dash louvers and that the air-control flaps in the heater housing are moving properly. Performance Tests Following is a brief description of symptoms or conditions that could exist if something goes wrong with a refrigerant part. Air Conditioning Protection Unit (ACPU) NOTE: For more information about the ACPU, see Subject 050. The ACPU was installed on vehicles built before April 16, IMPORTANT: The ACPU control system consists of an electronic control module, high and low pressure switches, and the thermostatic switch. The control module monitors system conditions (low or high refrigerant charge) and controls the operation of the refrigerant compressor and the on-off fan drive. On Century Class Conventionals, the ACPU is located under the hood on the right side of the frontwall. On Argosy COEs, the ACPU is located on the right side of the vehicle behind the bumper. See Fig. 1 and Fig /14/98 1. ACPU Control Module 2. High Pressure Switch 3. Low Pressure Switch f Fig. 1, ACPU Mounting, Century Class Conventional The control module registers fault codes that warn of existing or impending problems in the air conditioning system. Table 1 provides a list of ACPU messages broadcast to the Instrumentation Control Unit (ICU) message display screen. Additionally, corresponding fault codes are provided. Use Table 1 to assist in troubleshooting the ACPU control system. For further information on system fault codes, see the section in Group 54 that discusses the Instrumentation Control Unit. Additionally, if ServicePro is available, a technician diagnostic routine is available covering the ACPU system. Century Class Trucks Workshop Manual, Supplement 23, December /1

2 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled 06/24/98 f ACPU Control Module 2. Low Pressure Switch 3. High Pressure Switch Cooling Check 1 Fig. 2, ACPU Mounting, Argosy COE When outside temperature and humidity are high, it will take longer to cool the cab, especially if the fresh air vents are left open. To determine if the air conditioner is cooling enough: 1. Set the engine speed at 1500 rpm. The engine fan should be on. 2. On Century Class Conventionals, open the hood. On Century Class Conventionals and Argosy COEs, open the cab doors. 3. Turn on the cab air conditioner. Set the controls at air conditioning (not max AC), fresh air (not recirculated air), and maximum blower speed. The compressor must be engaged during this test. 4. In the sleeper (if equipped), turn the temperature control knob all the way counterclockwise to COOL. Turn the fan control knob to position 3 (high). 5. Allow the system to run for at least 10 minutes (longer on hot and humid days). 6. In the cab, place a thermometer inside the center dash outlet. In the sleeper, place a thermometer inside the lower outlet. Make sure the controls are set so that air flows out of the duct being tested Record the temperatures and take pressure readings at the service valves. Record the readings again after three minutes. If the temperature readings have not stabilized, run the system for an additional three minutes and record the readings again. 8. Compare the measured temperature readings to the readings in the temperature/pressure tables in Specifications 400. If the duct s air temperature is higher than normal readings, the system isn t cooling enough. For possible causes, see the troubleshooting chart. Receiver-Drier The receiver-drier is normally at outside temperature. To the touch, the entire length of the unit should be the same temperature. If noticeable cool spots exist, replace the receiver-drier. A blockage at the inlet of the unit will cause high head pressures. Outlet blockages will cause low head pressures and little or no cooling. If the moisture indicator is pink or white (showing that the system is wet), the receiver-drier is saturated with moisture and must be replaced. Cooling System Although they are not physically connected, there is a close tie between a vehicle s air conditioner and its cooling system. Poor air conditioner cooling can be the result of a problem in the cooling system. If the cooling system does not work correctly, the heat of the engine will rise to abnormal levels. The added heat will transfer to the air conditioner, other underhood parts, and maybe make its way into the cab. The added heat makes it necessary for the air conditioner to work harder and, at the same time, it reduces the air conditioner s ability to cool down the air in the cab. Also, if the water regulating valve isn t closing all the way, heat will enter the cab, giving the impression that the air conditioning system is not working. Refer to Group 20 for cooling system troubleshooting and to the engine manufacturer s service manual for other details about cooling system problems. 300/2 Century Class Trucks Workshop Manual, Supplement 23, December 2004

3 ACPU Fault Codes and Tests ICU Text Message Problem MID SID FMI REFRIG PRES HIGH REFRIG PRES LOW Refrigerant charge above normal, high pressure Refrigerant charge is below normal, low pressure CLUTCH CIR OPEN Open circuit CLUTCH CIR SHORT Short circuit BAT VOLTAGE LOW Low battery voltage LO PRES SW OPEN Low pressure switch, open circuit HI PRES SW OPEN High pressure switch, open circuit HI PRES SW CALIBRT High pressure switch, life cycle exceeded Condenser is clogged, or the system is overcharged. Clean the condenser, then check system pressure. If okay, start the engine. After system pressure reaches 290 to 310 psi (1999 to 2137 kpa) on vehicles built before December 11, 1998 or 340 to 375 psi (2344 to 2586 kpa) on vehicles built from December 11, 1998 the fan should come on. If it doesn t, the fan hub could be damaged. Check system pressure. If the low-side pressure is below 35 psi (241 kpa) there is a loss of refrigerant charge. Perform a leak test. Repair any leaks, evacuate the system, replace the receiver-drier, and add a full charge of refrigerant. If the pressure is okay, use an ohmmeter to measure the resistance between the low pressure switch wires. Replace the switch if resistance is not kilo ohms. Check the wiring to the compressor clutch. Repair or replace as needed. Check the wiring to the compressor clutch. Repair or replace as needed. Check for excessive electrical loads, a damaged alternator, or a discharged battery. Repair or replace as needed. Check that the correct switches are installed. Check the switch wiring. Repair or replace as needed. Use an ohmmeter to measure the resistance between the low pressure switch wires. Replace the switch if resistance is not kilo ohms when the switch is open. Check that the correct switches are installed. Check the switch wiring. Repair or replace as needed. Use an ohmmeter to measure the resistance between the high pressure switch wires. Replace the switch if resistance is not kilo ohms when the switch is open. Replace the high pressure switch. After replacing the high pressure switch, reset the high pressure cycle to zero. For more information on resetting this parameter, see the Freightliner ServiceLink on-line help program. Century Class Trucks Workshop Manual, Supplement 23, December /3

4 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled ACPU Fault Codes and Tests ICU Text Message Problem MID SID FMI TSTAT CIR ERRATIC Evaporator coil thermostatic switch Table 1, ACPU Fault Codes and Tests Test the thermostatic switch following the instructions provided elsewhere in this subject. Expansion Valve Problems that start in the expansion valve show up as follows: when stuck closed, the evaporator coil and the expansion valve will be at outside temperature; when stuck open, both the coil and the valve will be extremely cold with frost or ice buildup. Because the expansion valve channels are very small, blockages in the system tend to be found here (the valve is very sensitive to contamination). Usually, the contaminant is water; less than a drop of water is all it takes to make the valve inoperative. When water reaches the valve, the extreme cold that results from the pressure drop freezes the water, forming a block of ice in the valve. After the system shuts down and the valve warms up, the ice melts, and the valve operates again, only to freeze-up when the moisture returns. On-and-off operation of the expansion valve means that the receiver-drier is not removing moisture from the system. These contaminants should cause the moisture indicator to turn white and then pink. Refrigerant Compressor Compressor problems usually show in one of four ways: abnormal noise, seizure, leakage, or low suction and discharge pressures. Resonant compressor noises are not causes for alarm. Irregular noise or rattles are likely to be caused by broken parts. To check for seizure, deenergize the magnetic clutch and see if the drive plate can be turned. If it won t turn, the compressor has seized. Low discharge pressure may be caused by not enough refrigerant, not enough belt tension, or a blockage somewhere in the system. These things should be checked before servicing the compressor. Evaporator The evaporator coils are basically trouble-free when airflow over the fins is not blocked. External or, less often, internal blockages will cause low suction pressure as well as little or no cooling. If a leak exists in the system, and it cannot be traced to other parts or fittings, suspect damage to one of the evaporator coils. Condenser The condenser is usually trouble-free. Normally, the temperature of the condenser outlet line is noticeably cooler than the inlet line. However, when road debris, such as leaves or dirt, build up, airflow over the condenser fins is blocked. Air is not able to absorb enough heat to turn the hot refrigerant gas into a liquid. High head pressures will result. In these cases, carefully clean off the outer surfaces of the condenser with compressed air or a soap and water solution. Be careful not to bend the fins. High head pressures will also occur if the condenser s tubing is abnormally bent, blocking the flow of refrigerant. Frost will appear at the point where the flow is restricted. Less common internal blockages (bits of foreign material or metallic grit buildup) will stop the flow of refrigerant. A quick test to check that poor system performance is caused by the condenser is to direct a spray of water onto the condenser while the system is running. If the air conditioner cools better because of the assist provided by the water, it is a sign that the condenser is not working. When troubleshooting a suspected condenser problem, remember that the problem may be caused by the radiator transferring high levels of heat to the condenser. Refer to Group 20 of this manual for cooling system troubleshooting and to the engine 300/4 Century Class Trucks Workshop Manual, Supplement 23, December 2004

5 manufacturer s service manual for other details about cooling system problems. Thermostatic Switch IMPORTANT: Before troubleshooting the thermostatic switch, be sure there is a full charge of refrigerant in the system. The compressor will not operate or will cycle too often if there is not enough refrigerant in the system. Quick or delayed cycling of the compressor may be caused by a thermostatic switch that is working, but is out of adjustment. If, after doing the tests below, the switch seems to be out of adjustment, replace it (the thermostatic switch cannot be recalibrated). 1. Be sure the compressor clutch is operating correctly. See the applicable refrigerant compressor section in this group. 2. Expose the evaporator coil. See Subject 180 for instructions. 3. Start the engine. Place the air conditioner control at its coldest setting. Turn on the air conditioner and the fan. 4. Place an accurate thermometer in contact with a tube on the evaporator coil. Be sure the thermometer is in good contact with the tube or you will get a wrong reading. When the temperature drops below 31 to 36 F ( 1 to 2 C), the compressor clutch should disengage and remain this way until the temperature rises to 39 to 44 F (4 to 7 C). 5. If the compressor did not engage when the temperature was above the accepted high range, do the following test: 5.1 Connect a voltmeter or a test light from one of the terminals on the thermostatic switch to ground. Repeat this test with the other terminal on the switch. 5.2 With the engine running and the air conditioner and blower on, both terminals will show voltage when the compressor should be engaged. One terminal will show voltage when the compressor should be disengaged. If there is no voltage, there is a problem in the electrical system from the batteries to the thermostatic switch. Check all circuits for the cause, and repair or replace the wiring or parts. In all other cases where the compressor is not engaging and disengaging properly, the thermostatic switch is the cause. Replace it with a new switch. 6. Shut down the engine and, to prevent accidental electric shock or shorting during dash assembling, disconnect the batteries. 7. Assemble the dash. See Subject 180 for instructions. Discharge Temperature Control (DTC) System The water regulating valve clicks when it opens and closes. The clicks can be used to confirm operation of the water valve. The valve is normally open (NO). When the potentiometer is turned to full cold and the cab is warm, the controller should send electricity to the solenoid that closes the water valve and stops coolant flow through the heater core. By listening for the sound of the valve opening and closing, the technician can determine if the water valve is operating. See Fig. 3 for the wiring schematic for the cab Discharge Temperture Control (DTC) module. See Table 2 for the electrical pinout descriptions of the DTC module. DTC Module Pinout Pin Electrical Function A Ground B Potentiometer Input ( ) Cold C Potentiometer Input (wiper) D Potentiometer Input (+) Hot E Solenoid Valve Output ( ) F Solenoid Valve Output (+) G Ignition +12V Table 2, DTC Module Pinout Use the troubleshooting procedures in Table 3 first. Use the troubleshooting procedures in Table 3 before using the procedures in Table 4. Use the troubleshooting procedures in Table 3 and Table 4 before using the procedures in Table 5. Century Class Trucks Workshop Manual, Supplement 23, December /5

6 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled 2 3 A GND B POT ( ) POT (CCW Cold) C DTC Module w/sensor C POT ( IN ) D POT ( + ) POT (Center Tap) POT (CW Hot) B A Temperature POT E Water Valve ( ) F Water Valve (+) G V IGN (12V) 1 B WV Solenoid (338W+) GND 98 B D GND V IGN (12V) A WV Solenoid (338W ) 09/19/2003 f Water Valve Solenoid (NO) 2. DTC Module With Sensor 3. Potentiometer Fig. 3, Cab Discharge Temperature Control Schematic Use the troubleshooting procedures in Table 3 before using the procedures in Table 6. Use the troubleshooting procedures in Table 3 before using the procedures in Table 7. See Table 8 for the electrical pinout descriptions of the DTC module. Line Restrictions A restricted suction line causes low suction pressure at the compressor and little or no cooling. A restriction in a line between the compressor and the expansion valve can cause high discharge and low suction pressure, and insufficient cooling. Usually, areas of ice or frost buildup mean a blockage. Parts that often freeze-up are probably corroded or inoperative and should be replaced. Parts (such as the expansion valve) that freeze-up once in a while may do so because of moisture in the system, which will cause the moisture indicator to turn white or pink. If this happens, recover the refrigerant charge, evacuate/recycle the system refrigerant, replace the receiver-drier, and install a new charge. Test No. 1 Measure voltage at the water valve by backprobing the connector. Voltage should be approximately 12V. CDTC System Initial Electrical Diagnosis Test Procedure Test Criteria Test Result Action Engine running Engine at normal operating temperature Temperature setting at full cold OK Go to test no. 2. Not OK Go to test no /6 Century Class Trucks Workshop Manual, Supplement 23, December 2004

7 Test No. 2 Measure voltage at the water valve by backprobing the connector. Voltage should be approximately 0V. CDTC System Initial Electrical Diagnosis Test Procedure Test Criteria Test Result Action 3 Repeat test no. 1 using a known good ground instead of water valve ground wire. Voltage should be approximately 12V. 4 Check the ground wire to the controller (terminal A). Engine running Engine at normal operating temperature Temperature setting at full hot Engine running Engine at normal operating temperature Temperature setting at full cold OK Not OK There are no apparent electrical problems with the system. With the engine at normal operating temperature, hot air should come from the vents when the temperature setting is full hot. When switched to full cold, cooler air should come from the vents within approximately 10 minutes. If the system does not operate as stated above, refer to one of the following: For little or no heat symptom, see Table 6. For blowing warm/hot air symptom, see Table 7. Perform tests in Table 4, CDTC System Temperature Potentiometer Test. OK Go to test no. 4. Not OK OK Not OK Table 3, CDTC System Initial Electrical Diagnosis Perform tests in Table 4, CDTC System Temperature Potentiometer Test. Perform tests in Table 4, CDTC System Temperature Potentiometer Test. Repair controller ground circuit. CDTC System Temperature Potentiometer Test Test No. Test Procedure Test Result Action 1 Disconnect the temperature potentiometer from the harness. Using an ohmmeter, measure the potentiometer resistance as follows: A to B (knob full CCW) 8000 to 12,000 ohms A to B (knob full CW) 40 to 60 ohms B to C (knob full CCW) 40 to 60 ohms B to C (knob full CW) 8000 to 12,000 ohms OK Not OK Go to test no. 2. Replace temperature potentiometer. NOTE: Resistance ranges are approximate. Century Class Trucks Workshop Manual, Supplement 23, December /7

8 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled CDTC System Temperature Potentiometer Test Test No. 2 Connect the potentiometer. Disconnect the harness from the controller. Using an ohmmeter, measure the potentiometer resistance through the harness pins at the controller as follows: C to D (knob full CCW) 8000 to 12,000 ohms C to D (knob full CW) 40 to 60 ohms B to C (knob full CCW) 40 to 60 ohms B to C (knob full CW) 8000 to 12,000 ohms Test Procedure Test Result Action NOTE: Resistance ranges are approximate. OK Not OK Table 4, CDTC System Temperature Potentiometer Test Temperature potentiometer and wires are okay. Perform tests in the table titled CDTC System Controller Test. Repair wiring between temperature potentiometer and CDTC controller. Test No. 1 Disconnect the harness from the CDTC controller. Measure voltage across pins A and G. Voltage should be approximately 12V. 2 Connect the harness to the CDTC controller. Measure voltage by backprobing one meter lead to pin F and placing the other lead to a known good ground. Voltage should be approximately 12V. CDTC System Controller Test Test Procedure Test Criteria Test Result Action 3 Measure voltage by backprobing pins F and E of the CDTC controller connector. Voltage readings should be: Slightly less than 12V when the control knob is full cold (CCW) 0V when the control knob is full hot (CW). Ignition on CDTC controller disconnected Ignition on CDTC controller connected Ignition on CDTC controller connected OK Go to test no. 2. Not OK Check power supply wire and fuse to CDTC controller. Check CDTC controller ground circuit. Repair as necessary. OK Go to test no. 3. Not OK OK Not OK Table 5, CDTC System Controller Test Replace the CDTC controller. No problem found. Repeat tests Table 3. Replace the CDTC controller. 300/8 Century Class Trucks Workshop Manual, Supplement 23, December 2004

9 CDTC System Special Test-Symptom: Little or No Heat and Passes All Electrical Tests Test No. Test Procedure Test Result Action 1 Check to make sure that the coolant source from the OK Go to test no. 2. engine is connected to the inlet pipe on the water valve. Not OK Route hose to correct connections. 2 Check to make sure that the water inlet hose at the water valve is hot. OK Not OK Check for blocked heater core and repair as necessary. Check for closed heater hose shutoff valve. If okay or not present, repair engine cooling system as necessary. Table 6, CDTC System Special Test-Symptom: Little or No Heat and Passes All Electrical Tests CDTC System Special Test-Symptom: Blows Warm/Hot Air and Passes All Electrical Tests Test No. 1 Remove the water valve and visually inspect the inside of the outlet tube to see if the plunger is broken or if debris is preventing the plunger from seating properly. Test Procedure Test Result Action OK If the vehicle: Has a 2002 or newer Detroit Diesel engine, or Has an MBE engine, or If water pump pressure or flow is higher than a standard truck, then Install a water flow restrictor, part number RCV H (available in the PDCs). Install the flow restrictor in the heater hose between the engine and the inlet side of the water valve. IMPORTANT: Make sure the flow restrictor is installed so that the flow direction arrow is toward the water valve, which is the direction of coolant flow. Not OK If plunger is broken, replace the water valve. If debris is present, clean the cooling system. Table 7, CDTC System Special Test-Symptom: Blows Warm/Hot Air and Passes All Electrical Tests DTC Module Pinout Pin Electrical Function A Ground 2 B Potentiometer (CCW cold) 98U C Potentiometer (center tap) 98T D Potentiometer (CW hot) 98J E Water Valve ( ) 98X F Water Valve (+) 98W DTC Module Pinout Pin Electrical Function G Ignition Power (12V) 98N Table 8, DTC Module Pinout Fault Analysis Flow Chart See Fig. 4 for the fault analysis flow chart. Century Class Trucks Workshop Manual, Supplement 23, December /9

10 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled ICE BLOCKING EVAPORATOR Check for low suction pressure. Check thermo static switch. INSUFFICIENT COOLING NO OR LOW AIR FLOW Check blower operation. CHECK AIR FLOW BLOWER NOT OPERATING Check for blown circuit breaker, damaged blower switch, broken wire, loose connections, damaged blower motor. NORMAL BLOWER OPERATION Check for restriction or leakage in air ducts or clogged evaporator core. NORMAL AIR TEMPERATURE Check for air leaks through cab doors and windows. HIGH SUCTION PRESSURE DISCHARGE PRESSURE LOW NORMAL HIGH NORMAL AIR FLOW Inspect system for visual defects. Check air temperature. HIGH AIR TEMPERATURE NORMAL SUCTION PRESSURE Check compressor. Expansion valve stuck open, or thermostatic switch not working. DISCHARGE PRESSURE LOW Check for over charge or block age downstream of the measure ment point and before the expansion valve. NORMAL Check for belt tension, restriction in suction line, or compressor. Check seal around evaporator or therm ostatic switch. LOW SUCTION PRESSURE DISCHARGE PRESSURE LOW NORMAL TO HIGH 04/30/2003 System Tables Fig. 4, Fault Analysis Flow Chart Check for blockage upstream of the measurement point and before the compressor. Check for blockage downstream of the measurement point and before the expansion valve. f /10 Century Class Trucks Workshop Manual, Supplement 23, December 2004

11 Problem Little or No Airflow The blower is not operating. There are restrictions or leaks in the air ducts. Ice has formed on the evaporator coil. Problem Little or No Airflow Check for an open circuit breaker. An open circuit indicates a short in the electrical system, which must be located and repaired. Check the air conditioner relays for operation. Replace, as necessary. Make sure the blower motor switch is working. Replace, if necessary. Check the wiring to the blower motor. If any connections are loose, securely tighten them. Make sure the wiring conforms to the applicable diagram under Specifications 400. Check the blower motor for operation. Replace if sticking or otherwise inoperative. Check the resistor block. Replace, if necessary. CAUTION Never try to bypass the fuse in the resistor block. To do so could cause the blower motor to overheat, resulting in serious damage to the heater/ air-conditioning system. Examine all air ducts and remove any blockages. Stop any leaks or replace any portion where the leaks cannot be stopped. Defrost the evaporator coil before resuming operation of the air conditioner. Review "Performance Tests" in this subject for possible causes and corrective action. Problem Warm Airflow When the Air Conditioner Is On There is no refrigerant charge in the system. Moisture in the system. The refrigerant compressor is not operating. Ice has formed on the evaporator coil. Problem Warm Airflow When the Air Conditioner Is On Perform a leak test. Repair any leaks, evacuate the system, replace the receiver-drier, and add a full charge of refrigerant. If moisture is in the system, ice crystals may form at the expansion valve, blocking the flow of refrigerant (off and on). Recover the refrigerant charge, replace the receiver-drier, evacuate the system, and add a full charge of refrigerant. If the refrigerant charge is low, charge and leak test the system. Repair any leaks. The refrigerant compressor clutch or drive belt needs repair or replacement. For instructions, see the applicable refrigerant compressor section elsewhere in this group. Defrost the evaporator coil before resuming operation of the air conditioner. Review "Performance Tests" in this subject for possible causes and corrective action. Century Class Trucks Workshop Manual, Supplement 23, December /11

12 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled Problem Low Evaporator Coil Outlet Pressure (Low Compressor Suction Pressure) Problem Low Evaporator Coil Outlet Pressure (Low Compressor Suction Pressure) The expansion valve is not working. Replace the expansion valve. There are restrictions in the line to the Remove the line restrictions. expansion valve. There is an insufficient refrigerant charge in the system. Locate the leak. Recover the charge, replace the receiver-drier, and add a full refrigerant charge. Problem High Compressor Discharge Pressure Problem High Compressor Discharge Pressure The shutters are not opening. Replace the shutter solenoid valve, Air Conditioning Protection Unit high pressure switch, or both. Airflow through the condenser is restricted. Remove the debris from the condenser. There is an internal restriction in the Replace the condenser. condenser. Ice buildup on the condenser or a cool spot on the line from the condenser to the receiver-drier. Air is present in the system. Heavy frosting on the suction line suggests that the evaporator coil is flooded. The engine is overheated. Restriction in the compressor discharge line. Perform a leak test. Repair any leaks, evacuate the system, and add a full charge of refrigerant. Defrost the evaporator coil before resuming operation of the air conditioner. See the engine manufacturer s operations manual for corrective measures. Repair or replace the line. Problem Evaporator Outlet Air Temperature Increases as the Compressor Discharge Pressure Drops Problem Evaporator Outlet Air Temperature Increases as the Compressor Discharge Pressure Drops There are leaks in the system. Leak test the system. The expansion valve setting is too low. Replace the expansion valve. Add a full charge of refrigerant. Too much oil is in the system. An indication of this is clutch or belt slippage at governed engine speed. Check and remove excess refrigerant oil. For instructions, see the applicable refrigerant compressor section elsewhere in this group. Problem Compressor Operates Too Often or Continuously Problem Compressor Operates Too Often or Continuously There is too little refrigerant in the system. Perform a leak test. Repair any leaks, and add a full charge of refrigerant. 300/12 Century Class Trucks Workshop Manual, Supplement 23, December 2004

13 Problem Compressor Operates Too Often or Continuously Ice has formed on the evaporator coil. Defrost the evaporator coil before resuming operation of the air conditioner. Check the operation of the thermostatic switch, and replace as necessary. There is a restriction in the refrigerant Remove the restriction from the line. system. Dirt and debris are clogging the condenser Remove all dirt and debris from the condenser fins. fins. The thermostatic switch isn t working. Replace the thermostatic switch. Problem Quick or Delayed Cycling of the Compressor Problem Quick or Delayed Cycling of the Compressor The thermostatic switch operates, but is Replace the thermostatic switch. Do not attempt to adjust it. out of adjustment. Loss of refrigerant is causing a delayed Leak test and add a full charge of refrigerant. cycling of the compressor. Problem Temperature in the Cab Too Low or No Heat Problem Temperature in the Cab Too Low or No Heat The water regulating valve is not opened. Move the temperature control knob toward warm. The water regulating valve is not opening Adjust the water regulating valve cable. all the way. The water regulating valve is not working. Replace the water regulating valve. A heater hose is pinched or twisted. Repair or replace the heater hose. Coolant is leaking from the system. Check for leakage at the heater core, and at all hose connections from the heater core to the engine. Check the radiator coolant level, as instructed in the vehicle driver s manual, and add coolant, if necessary. Check and repair any leaks at the radiator. Dust or dirt is clogging the heater core Remove and clean the heater core. fins. Problem Condensed Water Is Leaking from the Air Conditioner Problem Condensed Water Is Leaking from the Air Conditioner The drain tubes are plugged. Clean the drain holes and drain tubes. Century Class Trucks Workshop Manual, Supplement 23, December /13

14 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled the Refrigerant System Using ACPU Fault Codes For ACPU faults accompanied by fault messages, Fig. 5 and Table 9 list faults that the ACPU is capable of detecting. The wording of the fault message display may vary depending on the level of software installed in the instrument cluster. Use ServicePro to clear fault codes. See Fig. 6 for the ACPU system schematic. Fault Code Definitions High Pressure: The high pressure condition is detected by monitoring high pressure switch activity after the fan has been engaged. This fault can be caused by fan drive failure, condenser airflow blockage, or refrigerant overcharging. High Pressure Switch Open: Indicates that the wiring to the high pressure switch is an open circuit. This can be caused by an unseated connector, a break in the wiring harness, or moisture intrusion into the connectors or switch. When continuity to the switch resumes, this fault becomes inactive. High Voltage: Indicates a high supply voltage condition (greater than 16 volts). This can be caused by a defective alternator, voltage regulator or surges on the supply line. The high voltage warning goes away when the supply voltage returns to normal (below 16 volts). Low Pressure: This is detected by monitoring the ambient temperature and activity of the low pressure switch. It indicates a loss of refrigerant. Low Pressure Switch Open: Indicates that the wiring to the low pressure switch is an open circuit. This can be caused by an unseated connector, break in the wiring harness, or moisture intrusion into the connectors or switch. When continuity to the switch resumes, this fault code becomes inactive. Low Voltage: Indicates a low supply voltage condition. This can be caused by a defective alternator, discharged batteries or excessive loads. The low voltage warning goes away when the supply voltage returns to normal (above 11 volts). 08/18/97 A/C SYST REFRIG PRES HIGH 190 S A/C SYST REFRIG PRES LOW 190 S A/C SYST LO PRES SW OPEN 190 S A/C SYST CLUTCH CIR OPEN 190 S A/C SYST CLUTCH CIR SHORT 190 S A/C SYST TSTAT CIR ERRATIC 190 S A/C SYST BAT VOLTAGE LOW 190 S A/C SYST HI PRES SW OPEN 190 S A/C SYST HI PRES SW CALIBRT 190 S f High Pressure Fault 2. Low Pressure Fault 3. Low Pressure Switch Open 4. Open Wire to Clutch 5. Shorted Clutch 6. Erratic Thermostatic Switch 7. Low Battery Voltage 8. High Pressure Switch Open 9. High Pressure Switch Life has Exceeded 260,000 Cycles Fig. 5, ACPU Fault Messages Open Clutch: If no current is sensed when the AC clutch is engaged, an open connection to the clutch coil is inferred. When continuity to the clutch resumes, this fault becomes inactive. If this fault is detected, the AC is held off for the remainder of the ignition cycle. Shorted Clutch: This is detected by excessive current flowing to the compressor clutch. This indicates /14 Century Class Trucks Workshop Manual, Supplement 23, December 2004

15 power ground ACPU 12V IGNIT GND RED BLACK F D FIREWALL HARNESS 97B GND H4 B1 MAIN CAB HARNESS 97B GND AF5 NA3 10A PDO21 PDM GND BUS IGNIT digital I/O digital I/O digital Input J1587+ J1587 THERMOSTAT PINK VIOLET GREEN A B C J1587+ J T B3 B4 H1 97T LC1 B11 LC1 B4 TO THERMOSTAT P2 CLUSTER (LEFT SIDE) output FAN REQUEST ORANGE G 234A ELEC ENG HARNESS TO ECM output A/C CLUTCH BLUE E (NOT USED) H 97C 97C A/C CLUTCH 3.3 OHMS NOMINAL analog Input HPx YELLOW 12V ENGINE HARNESS signal return HPx RETURN YELLOW/BLACK 2.49K HIGH PRESS analog Input LPx WHITE signal return LPx RETURN WHITE/BLACK 2.49K LOW PRESS 08/14/97 f541631a Fig. 6, ACPU System Schematic either a shorted clutch coil or shorted wiring to the clutch. If this fault is detected, the AC is held off for the remainder of the ignition cycle. Erratic Thermostatic Switch: The thermostatic switch input has been detected to be switching on and off at a rapid rate. This indicates a bad AC selector, fan switch, thermostatic switch, or intermittent connections in the wiring or connectors. High Pressure Switch Calibration: Cycle life of the high pressure switch has been exceeded (260,000 cycles). Replace the switch and reset the ACPU by pressing the HPX button in ServiceLink. NOTE: Use ServiceLink to clear fault codes. ACPU Table Century Class Trucks Workshop Manual, Supplement 23, December /15

16 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled ACPU Table Dash Message Definition Action See Fig. 7. High pressure fault. The system is exhibiting abnormal high pressure activity. Fan drive failure Inspect for proper operation of the solenoid valve/relay and/or related components. Blocked air flow Remove the restriction from the condenser. Refrigerant overcharge Recover refrigerant and charge to the manufacturer recommended specification. See Fig. 8. See Fig. 9. Low pressure fault. This is detected by monitoring the ambient temperature and the switching activity of the low pressure switch. Open in wiring to the low pressure switch. Indicates that the wiring to the low pressure switch is damaged. High pressure switch out of tolerance Fan circuit has not been turned on in the Engine Control Module Partial or total loss of refrigerant A damaged low pressure switch Unseated connector Break between wiring harness and pressure switch Moisture intrusion into the connectors or switch Incorrect pressure switch installed Perform steps 3.1 through 3.7 in the following section to test fan and compressor operation and replace the high pressure switch if necessary. Disconnect the main harness to the ACPU module. If the engine fan engages, replace the ACPU module. If the engine fan doesn t engage, check the fan circuit in the ECM, and have the ECM programmed to accept ACPU input. Check the system for leaks. Disconnect the low side pressure switch connector and measure the resistance value of the switch. If the resistance shows 2490 ohms, the switch is operating properly, if resistance shows less than 5 ohms, replace the switch. NOTE: This check must be done with the switch installed, the ignition in the off position, and the system properly charged. Check the connectors at the module and the pressure switch for loose pins. Using an ohmmeter, probe the white and white/black pins of the module harness. Resistance should read 2490 ohms with the switch installed and proper charge. Check seals and inspect wires for hole punctures. Install the correct pressure switch. 300/16 Century Class Trucks Workshop Manual, Supplement 23, December 2004

17 ACPU Table Dash Message Definition Action See Fig. 10. Open wire to the A/C clutch. Detected by inadequate current A break in the wiring between the ACPU through the compressor clutch. If no module and the A/C current is sensed when the A/C compressor clutch drive is turned on, an open connection to the clutch coil is indicated. See Fig. 11. See Fig. 12. See Fig. 13. See Fig. 14. See Fig. 15. Shorted wire or A/C clutch. Detected by excessive current through the compressor clutch. Erratic evaporator thermostatic switch. The thermostat input has been detected to be switching on and off at a rapid rate. Low system voltage. Indicates voltage has dropped below 11.0 volts. Open in wiring to the high pressure switch. Indicates that the wiring to the high pressure switch is damaged. Cycle life of the high pressure switch has been exceeded. Poor electrical contact between the compressor and the vehicle ground No clutch output from the ACPU This means either a shorted clutch coil or shorted wiring to the clutch No clutch output from the ACPU An erratic power signal between the A/C cab controls and the ACPU module Possibly caused by a defective alternator, discharged batteries or excessive electrical loads Unseated connector Break between wiring harness and pressure switch Moisture intrusion into the connectors or the switch Incorrect pressure switch installed High pressure switch has exceeded more than 260,000 cycles Use an ohmmeter to check the wiring for continuity. Using an ohmmeter, test the resistance between the clutch and the compressor, and between the compressor and the engine block. If necessary, loosen the mounting on the compressor and retighten it to repair the contacts. Replace the ACPU with a binary switch. For instructions, see Service Bulletin With the use of an ohmmeter, check the resistance of the clutch coil. If the reading is less than 2.8 ohms, replace the clutch. Replace the ACPU with a binary switch. For instructions, see Service Bulletin Check for a bad A/C-On switch, thermostat, or an intermittent connection in the wiring or connection between the cab controls and the ACPU module (pin c). Check voltage at the control module harness by probing pins D (ground) and F (power). If voltage is less than 11.0 volts, start checking for voltage drops. Check connectors at the module and the pressure switch for loose pins. With the use of an ohmmeter, probe the yellow and yellow/black pins of the switch harness. Replace the switch if resistance is greater than 5 ohms. Check seals and inspect wires for continuity. Install the correct pressure switch. Replace the pressure switch with F/L part number Using ServiceLink, reset the high pressure cycle counter to zero. Century Class Trucks Workshop Manual, Supplement 23, December /17

18 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled ACPU Table Dash Message Definition Action No Dash Message. No Dash Message. No Dash Message. No Dash Message. Clutch is engaged, A/C is not cooling. A/C compressor is not engaging. A/C system is not cooling properly. Inoperative blower motor, or loose or broken compressor belts System air pressure is less than 60 psi (414 kpa) Cable to the heater control valve is disconnected or the valve is not completely closing Check for proper operation of the blower motors. Tighten or replace the compressor belts. Check for low air pressure. Check the cable at the heater control valve and behind the dash. Be sure the valve opens and closes completely. A/C compressor is not engaging. Engine rpm is less than 300 Check the cause of the low rpm. Table 9, ACPU Table NOTE: Use ServiceLink to clear fault codes. A/C SYST REFRIG PRES HIGH 190 S /13/97 A/C SYST CLUTCH CIR OPEN 190 S f /13/97 f Fig. 10, Open Wire to Clutch Fault Code Fig. 7, High Pressure Fault Code A/C SYST REFRIG PRES LOW 190 S /13/97 A/C SYST CLUTCH CIR SHORT 190 S f /13/97 f Fig. 11, Shorted Clutch Fault Code Fig. 8, Low Pressure Fault Code A/C SYST LO PRES SW OPEN 190 S /13/97 A/C SYST TSTAT CIR ERRATIC 190 S f /13/97 Fig. 9, Low Pressure Switch Open Fault Code f Fig. 12, Erratic Thermostatic Switch Fault Code the ACPU Use the following procedure for troubleshooting ACPU faults not accompanied by fault codes. 300/18 Century Class Trucks Workshop Manual, Supplement 23, December 2004

19 08/13/97 08/13/97 A/C SYST BAT VOLTAGE LOW 190 S Fig. 13, Low Battery Voltage Fault Code A/C SYST HI PRES SW OPEN 190 S f f Fig. 14, High Pressure Switch Open Fault Code 08/13/97 A/C SYST HI PRES SW CALIBRT 190 S f Fig. 15, High Pressure Switch Life Has Exceeded 260,000 Cycles Fault Code 1. Connect ServiceLink to the truck and download the fault codes. 1.1 Make repairs to correct existing fault codes. 1.2 Clear the fault codes using ServiceLink. 1.3 If the ACPU does not report on Service- Link, see Table Check for initial (lube) cycle. 2.1 With the main AC selector in the AC off position, start the truck. The compressor clutch should remain disengaged for about 15 seconds after starting the truck, then the compressor should engage for 15 seconds and shut off. This is the initial (lube) cycle. 2.2 If the compressor does not complete the initial (lube) cycle, see Table Test fan and compressor operation. 3.1 Apply the parking brakes and chock the tires. 3.2 Connect a refrigerant service cart to the truck air conditioning system. 3.3 Place cardboard in front of the air conditioning condenser so that it blocks all air from being drawn into the condenser. 3.4 Start the truck with the transmission in neutral, the main cab air conditioning selector switch in the on position, and the fan switch on high (position 4). 3.5 Check that the air conditioning compressor engages after about 15 seconds. 3.6 Check the reading of the high pressure gauge on the service cart when the fan comes on the first time. The fan should come on between 290 and 310 psi (1999 and 2137 kpa) on vehicles built before December 11, 1998 or between 340 and 375 psi (2344 and 2586 kpa) on vehicles built from December 11, This is the high pressure switch set point. The pressure may not reach the set point of the high pressure switch if the ambient air temperature is below 60 F (16 C). 3.7 If the compressor disengages after 15 seconds, see Table If the fan does not come on between 290 and 310 psi (1999 and 2137 kpa) on vehicles built before December 11, 1998 or between 340 and 375 psi (2344 and 2586 kpa) on vehicles built from December 11, 1998, see Table 13 and refer to step 3 in the ACPU Control Rules section of Service Bulletin Continue to observe the reading of the high pressure gauge on the service cart as the pressure falls. The compressor should re-engage at between 250 and 270 psi (1724 and 1862 kpa). This is the high pressure switch reset point. If the compressor does not re-engage at between 250 and 270 psi (1724 and 1862 kpa), see Table 14. Century Class Trucks Workshop Manual, Supplement 23, December /19

20 83.02 Cab Heater and Air Conditioner, Water-Valve Controlled Problem ACPU Not Reported on ServiceLink No power supply to the ACPU. Check the voltage between pins D (ground) and F (power) at the frontwall harness connector to the ACPU. If the voltage is less than 11.0 volts, start checking for voltage drops. Open J1587 circuit. Check for voltage between pins A (J1587+) and B (1587-) at the frontwall harness connector to the ACPU using a voltmeter in AC mode. The reading on the J1587 bus should be a constantly varying voltage between 0.5 and 5 volts. If there is no voltage signal on the J1587 bus with the ignition on, check for an open circuit in the J1587 bus. ACPU not responding. Replace the ACPU with a binary switch. For instructions, see Service Bulletin Table 10, Problem-ACPU Not Reported on ServiceLink Normal operation Active fault codes. Low air pressure. The high pressure switch is reporting a high pressure situation to the ACPU The low pressure switch is reporting a low pressure situation to the ACPU. Low or no battery power to the ACPU. Problem Compressor Doesn t Engage for Initial (Lube) Cycle If the AC is on, the compressor will operate longer than 15 seconds after the initial engagement. Use ServiceLink to download fault codes and perform necessary repairs. Check the air pressure. It must be above 60 psi (414 kpa) for the compressor to engage. Check the resistance between the leads to the high pressure switch. If it is greater than one ohm, check the air conditioning system pressures. If the high side pressure is below 250 to 270 psi (1724 to 1862 kpa), replace the high pressure switch and use ServiceLink to reset the HPX switch counter. Check the resistance between the leads to the low pressure switch. If it shows less than one ohm, check the air conditioning system pressures. If the low side pressure is above 34 psi (234 kpa), replace the low pressure switch. Check the voltage between pins D (ground) and F (power) at the frontwall harness connector to the ACPU. If the voltage is less than 11.0 volts, start checking for voltage drops. ACPU is not operating correctly. Replace the ACPU with a binary switch. For instructions, see Service Bulletin Table 11, Problem-Compressor Doesn t Engage for Initial (Lube) Cycle Problem The Compressor Doesn t Engage or Stays Engaged After the Initial (Lube) Cycle Active fault codes. Use ServiceLink to download fault codes and perform necessary repairs. High pressure switch reporting a high pressure situation to the ACPU. No power from the thermostat to the ACPU. Check resistance between the leads to the high pressure switch after the initial (lube) cycle. If the resistance is greater than one ohm and the pressure on the high side of the system is less than 250 to 270 psi (1724 to 1862 kpa), replace the high pressure switch and use ServiceLink to reset the high pressure switch counter. With the AC on, check for voltage between pins D (ground) and C (thermostat) at the frontwall harness connector to the ACPU. If the voltage is less than 11.0 volts check the circuit from the main cab HVAC selector switch, through the thermostatic switch, to the ACPU. 300/20 Century Class Trucks Workshop Manual, Supplement 23, December 2004

21 Problem The Compressor Doesn t Engage or Stays Engaged After the Initial (Lube) Cycle The thermostatic sensor detects an evaporator freeze condition. Determine if the freeze condition should exist. Refer to the steps for the thermostatic switch in this subject. The ACPU is not operating correctly. Replace the ACPU with a binary switch. For instructions, see Service Bulletin Table 12, Problem-The Compressor Doesn t Engage or Stays Engaged After the Initial (Lube) Cycle Fault code. Temperature too cold. Low refrigerant charge. Fan does not engage. Fan request lead is grounded. The set point of the high pressure switch is incorrect. Problem The Fan Doesn t Engage at the Set Point Check ServiceLink for fault codes, make necessary repairs, and clear fault codes with ServiceLink. If the ambient temperature is too cold (60 F [16 C] or below) the high side pressure may not reach the high pressure set point. If the system does not reach the high pressure set point, there may not be a proper charge in the air conditioning system. Disconnect the main connector to the ACPU and start the engine. If the fan does not come on immediately check to see if the fan request lead from the ACPU to the engine control module is grounded. Replace the high pressure switch and use ServiceLink to reset the HPX switch counter. The ACPU is not operating correctly. On increasing pressure, if the fan does not come on before the compressor shuts off, the ACPU is not operating correctly. Replace the ACPU with a binary switch. For instructions, see Service Bulletin Table 13, Problem-The Fan Doesn t Engage at the Set Point Problem The Compressor Doesn t Re-Engage at the Reset Point Fault code. Check ServiceLink for fault codes, make necessary repairs, and clear fault codes with ServiceLink. The reset point of the high pressure switch is incorrect. The thermostatic sensor detects an evaporator freeze condition. Replace the high pressure switch and use ServiceLink to reset the high pressure switch counter in the ACPU. Determine if a freeze condition should exist. Refer to the information on the thermostatic switch in this subject. The ACPU is not operating correctly. Replace the ACPU with a binary switch. For instructions, see Service Bulletin Table 14, Problem-The Compressor Doesn t Re-Engage at the Reset Point Century Class Trucks Workshop Manual, Supplement 23, December /21

A/C-HEATER SYSTEM - MANUAL

A/C-HEATER SYSTEM - MANUAL A/C-HEATER SYSTEM - MANUAL 1986 Isuzu Trooper II 1986 A/C-HEATER SYSTEM Isuzu A/C-Heater Systems - Manual P UP, Trooper II * PLEASE READ THIS FIRST * CAUTION: When discharging air conditioning system,

More information

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC. Fig. 2: Blower & Evaporator Unit Specifications 2004 HVAC SYSTEMS Manual HVAC System - Sorento GENERAL SPECIFICATIONS AIR CONDITIONER Fig. 1: Air Conditioner Specifications BLOWER AND EVAPORATOR UNIT HEATER

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

Section 12-00: Climate Control System Service 1997 Town Car Workshop Manual DIAGNOSIS AND TESTING Procedure revision date: 06/29/2000 Climate Control System Inspection and Verification 1. Verify the customer's

More information

REFRIGERANT ON-VEHICLE INSPECTION AC 14

REFRIGERANT ON-VEHICLE INSPECTION AC 14 14 REFRIGERANT ON-VEHICLE INSPECTION 1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET (a) This is a method to specify trouble areas by using a manifold gauge set. Read the manifold gauge pressure

More information

Heater and Air Conditioner, R 134a Systems 83.03

Heater and Air Conditioner, R 134a Systems 83.03 Heater and Air Conditioner, R 4a Systems 8.0 WARNING R 4a is the only refrigerant that is approved for use on Freightliner LLC vehicles. Several companies offer less expensive, hydrocarbonbased refrigerants,

More information

2004 HVAC. Heating, Ventilation and Air Conditioning - Hummer H2. Fastener Tightening Specifications Specification Application

2004 HVAC. Heating, Ventilation and Air Conditioning - Hummer H2. Fastener Tightening Specifications Specification Application SPECIFICATIONS 2004 HVAC Heating, Ventilation and Air Conditioning - Hummer H2 FASTENER TIGHTENING SPECIFICATIONS Fastener Tightening Specifications Specification Application Metric English A/C Accumulator

More information

Motor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle

Motor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle Motor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle At Sea level water boils at 212⁰ F R 134a boils at 15⁰ F At Sea level R 134a boils at 15⁰ F At 30 psig R 134a boils at 35⁰

More information

MINI SLIMLINE COOL VUY-A VUY-A

MINI SLIMLINE COOL VUY-A VUY-A an ISO 900:2008 Registered Company MINI SLIMLINE COOL 030-VUY-A 040-VUY-A 8865 GOLL ST. - SAN ANTONIO, TX. - 78266 ph.20-654-77 - fax 20-654-33 900302 REV D 0/28/4, MINI SLIMLINE COOL PG OF Table of Contents

More information

MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM

MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM SECTION 7B MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM CAUTION: Disconnect the negative battery cable before removing or installing any electrical unit or when a tool or equipment

More information

Sleeper Heater and Air Conditioner, Blend Air System 83.05

Sleeper Heater and Air Conditioner, Blend Air System 83.05 Sleeper Heater and Air Conditioner, Blend Air System 8.0 General Information General Description The sleeper heater and air conditioner assembly is mounted in either the baggage compartment or under the

More information

HEATING AND AIR CONDITIONING

HEATING AND AIR CONDITIONING WJ HEATING AND AIR CONDITIONING 24-1 HEATING AND AIR CONDITIONING TABLE OF CONTENTS page SERVICE PROCEDURES REFRIGERANT OIL LEVEL...1 REFRIGERANT RECOVERY....1 REFRIGERANT SYSTEM CHARGE...1 REFRIGERANT

More information

an ISO 9001:2008 Registered Company GOLL ST. - SAN ANTONIO, TX ph fax MINI SPACE SAVER HEAT /COOL

an ISO 9001:2008 Registered Company GOLL ST. - SAN ANTONIO, TX ph fax MINI SPACE SAVER HEAT /COOL an ISO 9001:2008 Registered Company 18865 GOLL ST. - SAN ANTONIO, TX. - 78266 - ph.210-654-7171 - fax 210-654-3113 MINI SPACE SAVER HEAT /COOL 01000-QUX-A 01000-VUX-A 900101-VUX-A REV C 3/5/14, MINI SPACE

More information

HEATING AND VENTILATION

HEATING AND VENTILATION SECTION 14-102.04 14-102.04/ 1 2007OC19 DESCRIPTION The heating, ventilation and air conditioning (HVAC) system is designed to optimize passenger comfort. The system regulates interior vehicle atmosphere,

More information

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features. Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause

More information

an ISO 9001:2008 Registered Company MINI SPACE SAVER HEAT /COOL/DEFROST QUZ-A VUZ-A

an ISO 9001:2008 Registered Company MINI SPACE SAVER HEAT /COOL/DEFROST QUZ-A VUZ-A an ISO 900:2008 Registered Company MINI SPACE SAVER HEAT /COOL/DEFROST 0000-QUZ-A 0000-VUZ-A 8865 GOLL ST. - SAN ANTONIO, TX. - 78266 - ph.20-654-77 - fax 20-654-33 90000-VUZ-A REV E 3/5/4, MINI SPACE

More information

WB Holden Aircondtioning Re-Instalation

WB Holden Aircondtioning Re-Instalation WB Holden Aircondtioning Re-Instalation My Ute has the rudimentary remains of the Airconditioning System in the form of the Evaporator/Heater airbox mounted forward and aft of the firewall. The original

More information

1998 Expedition/Navigator Workshop Manual

1998 Expedition/Navigator Workshop Manual Page 1 of 8 SECTION 412-00: Climate Control System - General Information 1998 Expedition/Navigator Workshop Manual DESCRIPTION AND OPERATION Procedure revision date: 02/11/2000 Climate Control System WARNING:

More information

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3) www.dometic.com Freightliner Refrigerator Troubleshooting Guide For Before initiating troubleshooting, the following equipment is recommended: Multimeter, 20 gauge (min) wires to use as jumpers, and 12Vdc

More information

The breaker trips at once when it is set to ON. The breaker trips in few minutes when it is set to ON.

The breaker trips at once when it is set to ON. The breaker trips in few minutes when it is set to ON. Trip of breaker or The breaker trips at once when it is set to O. Measure insulation resistance to ground to see if there is any leakage. Air conditioner can not start up blow of fuse The air conditioner

More information

ASSIGNMENT OBJECTIVES

ASSIGNMENT OBJECTIVES LESSON 2 HVAC DIAGNOSIS covers the diagnosis, or troubleshooting, of the HVAC system and the tools used to perform that diagnosis. The lesson contains one reading assignment. ASSIGNMENT 1 HEATING AND AIR-CONDITIONING

More information

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s) Electrical Problems Fuse(s) blow or circuit breaker trips Does the unit use circuit breakers or fuses? Fuse(s) Circuit breakers Are the fuses dual element time delay? Is the circuit breaker HACR rated?

More information

Installation Instructions

Installation Instructions PAGE 1 Installation Instructions Important information about your new a/c system. Please read the following directions prior to installing this a/c system. PN: CK6772-1CHPU 1967-1972 Chevy PU A/C Kit Contact

More information

1956 FORD F-100 TRUCK

1956 FORD F-100 TRUCK an ISO 9001:2008 Registered Company INSTALLATION INSTRUCTIONS FOR 1956 FORD F-100 TRUCK HEAT/COOL/DEFROST 75456-LFZ-A 18865 GOLL ST. - SAN ANTONIO, TX. - 78266 - ph.210-654-7171 - fax 210-654-3113 905456-LFZ-A

More information

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST CHEVROLET NOVA

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST CHEVROLET NOVA specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST 1966-67 CHEVROLET NOVA CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

Climate Control System

Climate Control System Page 1 of 13 SECTION 412-00: Climate Control System General Information DESCRIPTION AND OPERATION 1998 Mark VIII Workshop Manual Climate Control System Cautions and Warnings WARNING: To avoid accidental

More information

R E N HI ITI CUSTOM AN LO +12v ADJUSTMENT

R E N HI ITI CUSTOM AN LO +12v ADJUSTMENT PAC-2000 REV D ELECTRIC COOLING FAN CONTOLLER PAC-2000 REV D FAN CONTROLLER SW1 FAN HIGH FAN LOW GND +12v SENDER A/C IGNITION SW2 CUSTOM ADJUSTMENT Choose option below GAUGE +12 V with key ON A/C clutch

More information

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11 SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-479 Supersedes: NEW File: Volume

More information

Each heater has slightly different operational characteristics

Each heater has slightly different operational characteristics NOTE, YOU MAY WANT TO PRINT THIS GUIDE TO ASSIST YOU IN TROUBLE SHOOTING New information regarding the Ultra Low Sulfur Diesel Fuel Heater Trouble Shooting Guide Customer Name Phone Step 1. Basic Information

More information

Vehicle Level Heating and Air Conditioning Description and Operation A/C System - Manual. A/C System - Manual

Vehicle Level Heating and Air Conditioning Description and Operation A/C System - Manual. A/C System - Manual 1 of 5 4/7/2008 8:32 AM Home Account Contact ALLDATA Log Out Help Select Vehicle New TSBs Technician's Reference Component Search: METRO TOYOTA OK 1999 Ford Truck F 450 2WD Super Duty V10-6.8L VIN S Vehicle

More information

π H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY

π H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY π H-6621 INDUSTRIAL DEHUMIDIFIER 1-800-295-5510 uline.com WARNINGS Plug into a grounded 3 prong outlet. Do not remove ground prong. Do not use an adapter. Do not use an extension cord if possible. Failure

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

HEATING AND AIR CONDITIONING

HEATING AND AIR CONDITIONING PL HEATING AND AIR CONDITIONING 24-1 HEATING AND AIR CONDITIONING CONTENTS page GENERAL INFORMATION INTRODUCTION... 2 SAFETY PRECAUTIONS AND WARNINGS... 2 DESCRIPTION AND OPERATION A/C REFRIGERANT LINES...

More information

SERVICING S-15 CHECKING CAPACITOR

SERVICING S-15 CHECKING CAPACITOR S-15 CHECKING CAPACITOR The direct drive motors are of the permanent split capacitor design. A run capacitor is wired across the auxiliary and a portion of the main windings. The capacitors primary function

More information

Trouble Shooting Guide PWA, 3-phase (D10571)

Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage Loose wire

More information

HEATER, AIR CONDITIONING AND VENTILATION

HEATER, AIR CONDITIONING AND VENTILATION 55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-10 DUCT

More information

TOYOTA FJ-40 DIRECTIONS

TOYOTA FJ-40 DIRECTIONS PAGE 1 TOYOTA FJ-40 DIRECTIONS Please read the following directions prior to installing this a/c system. Contact us by email or phone if you need any assistance or information regarding this a/c system.

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

HEATING AND AIR CONDITIONING

HEATING AND AIR CONDITIONING XJ HEATING AND AIR CONDITIONING 24-1 HEATING AND AIR CONDITIONING TABLE OF CONTENTS page AND ACCUMULATOR...2 BLOWER MOTOR...2 BLOWER MOTOR RELAY...2 BLOWER MOTOR RESISTOR...3 BLOWER MOTOR SWITCH....3 COMPRESSOR...3

More information

Product Information and Technical Guide

Product Information and Technical Guide Product Information and Technical Guide Side by Side and Top Mount Refrigerators July 2003 - December 2003 White-Westinghouse 5995540384 January 2004 TABLE OF CONTENTS Safe Servicing Practices ------------------------------------------------------------------------------------------

More information

Full Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start

Full Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start Mokon Troubleshooting Guide Model 311 Process pump will not start Process pump shuts down during operation Pump seal leak Tank overflows or will not fill on systems with autofill option (water makeup valve)

More information

TROUBLESHOOTING GENERAL TROUBLESHOOTING PROBLEM PROBABLE CAUSE CORRECTIVE ACTION

TROUBLESHOOTING GENERAL TROUBLESHOOTING PROBLEM PROBABLE CAUSE CORRECTIVE ACTION GENERAL TROUBLESHOOTING Compressor Conditioning system OFF Turn ON conditioning system will not run No electrical power Check fuses Wrong voltage to applied to unit Compressor internal overload tripped

More information

AIR CONDITIONING SYSTEM

AIR CONDITIONING SYSTEM AC1 AC2 General Information GENERAL INFORMATION 1. WHEN HANDLING REFRIGERANT (R12), FOLLOWING PRECAUTIONS MUST BE OBSERVED. (a) Do not handle refrigerant in an enclosed area or near an open flame. (b)

More information

NEWMAR CORPORATION. Technician Training By Evans Tempcon Inc.

NEWMAR CORPORATION. Technician Training By Evans Tempcon Inc. NEWMAR CORPORATION Technician Training By Evans Tempcon Inc. EVANS TEMPCON S WEBSITE www.evanstempcon.com PART 1 RV OWNER S RESOURCE SECTION Section available for RV owners WEB BASED OWNERS RESOURCES

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com UNPACKING

More information

COMPAC GEN II HEAT/COOL VUX-A. an ISO 9001:2008 Registered Company #10 SUCTION HOSE COMPRESSOR #8 DISCHARGE HOSE EVAPORATOR DRIER CONDENSER

COMPAC GEN II HEAT/COOL VUX-A. an ISO 9001:2008 Registered Company #10 SUCTION HOSE COMPRESSOR #8 DISCHARGE HOSE EVAPORATOR DRIER CONDENSER an ISO 900:2008 Registered Company COMPAC GEN II HEAT/COOL 68000-VUX-A EVAPORATOR #0 SUCTION HOSE COMPRESSOR #8 DISCHARGE HOSE DRIER #6 LIQUID LINE CONDENSER 90680-VUX-A REV E 2/28/4, INST. GEN II COMPAC

More information

Heavy Duty Heater / Air Conditioner Model R-8545

Heavy Duty Heater / Air Conditioner Model R-8545 Heavy Duty Heater / Air Conditioner Model R-8545 INSTALLATION INSTRUCTIONS NOTE 1. Please read instructions all the way through, making sure you have all the parts and tools 2. While working on or around

More information

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to dryer before servicing, unless testing requires power.

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to dryer before servicing, unless testing requires power. 27 Domestic Dryer Technical Information MDE6700A*, MDG6700A* Due to possibility of personal injury or property damage, always contact an authorized technician for servicing or repair of this unit. Refer

More information

Recreational Vehicle

Recreational Vehicle Evans Tempcon, Inc. Recreational Vehicle FRONT OCCUPANTS HVAC Service Manual (All Electric Control Systems) EVANS TEMPCON, INC. 701 ANN ST. NW GRAND RAPIDS, MI 49504 (616) 361-2681 WWW.EVANSTEMPCON.COM

More information

Performance Automotive Air Conditioning

Performance Automotive Air Conditioning Performance Automotive Air Conditioning The Basics 18865 GOLL ST. - SAN ANTONIO, TX. - 78266 ph.210-654-7171 - fax 210-654-3113 The Basics of Performance Air Conditioning 1. Primary purpose of air conditioning

More information

an ISO 9001:2008 Registered Company ShortPac HEAT/COOL (05000-QUX-A/05000-VUX-A)

an ISO 9001:2008 Registered Company ShortPac HEAT/COOL (05000-QUX-A/05000-VUX-A) an ISO 9001:2008 Registered Company ShortPac (05000-QUX-A/05000-VUX-A) 18865 GOLL ST. - SAN ANTONIO, TX. - 78266 - ph.210-654-7171 - fax 210-654-3113 900499 REV C 3/7/14, ShortPac EVAPORATOR KIT PG 1 OF

More information

PAC-2750 ELECTRIC COOLING FAN CONTROLLER

PAC-2750 ELECTRIC COOLING FAN CONTROLLER PAC-2750 ELECTRIC COOLING FAN CONTROLLER IMPORTANT NOTE: The +12V for the controller should NOT be taken from the same circuit as the Fan Power 12V as this can cause the fan to cycle on and off. Required

More information

Thermo 230 / 231 / 300 / 301 / Troubleshooting

Thermo 230 / 231 / 300 / 301 / Troubleshooting Thermo 230 / 231 / 300 / 301 / 350 5 Troubleshooting 5 Troubleshooting 5.1 General This section describes troubleshooting procedures for the heaters Thermo 230, 231, 300, 301 and 350. CAUTION Troubleshooting

More information

Product Information and Technical Guide

Product Information and Technical Guide Product Information and Technical Guide Side by Side and Top Mount Refrigerators January 2004 - March 2004 White-Westinghouse 5995413308 July 2004 TABLE OF CONTENTS Safe Servicing Practices ------------------------------------------------------------------------------------------

More information

BC BRONCOS AIR CONDITIONING UNIT

BC BRONCOS AIR CONDITIONING UNIT BC BRONCOS AIR CONDITIONING UNIT CAUTION If you are not familiar with the principals of air conditioning, have an authorized air conditioning technician evacuate and charge the system. Serious damage to

More information

P0032-O2 SENSOR 1/1 HEATER CIRCUIT HIGH

P0032-O2 SENSOR 1/1 HEATER CIRCUIT HIGH 8 - ND - DODGE DAKOTA -.7L MAGNUM V8 P-O SENSOR / HEATER CIRCUIT HIGH S6 K9 BR/DG - LEFT FRONT K99 Z K K9 8 8 BR/TN BK/LB DB/LB BR/DG G8 8 C C C O / O / O RETURN HEATER SIGNAL (UPSTREAM) CONTROL CONTROL

More information

Streamline Gen II Oval Control Panel Polished (48104-RHQ)

Streamline Gen II Oval Control Panel Polished (48104-RHQ) an ISO 900:05 Registered Company Streamline Gen II Oval Control Panel Polished (4804-RHQ) 8865 Goll St. San Antonio, TX 7866 Phone: 800-86-6658 Sales: sales@vintageair.com Tech Support: tech@vintageair.com

More information

SUPER GEN II HEAT/COOL VUX-A. an ISO 9001:2008 Registered Company EVAPORATOR #10 SUCTION HOSE COMPRESSOR #8 DISCHARGE HOSE DRIER CONDENSER

SUPER GEN II HEAT/COOL VUX-A. an ISO 9001:2008 Registered Company EVAPORATOR #10 SUCTION HOSE COMPRESSOR #8 DISCHARGE HOSE DRIER CONDENSER an ISO 900:2008 Registered Company SUPER GEN II HEAT/COOL 6005-VUX-A EVAPORATOR #0 SUCTION HOSE COMPRESSOR #8 DISCHARGE HOSE DRIER #6 LIQUID LINE CONDENSER 90606-VUX-A REV E 2/28/4, INST. GEN II SUPER

More information

442 Chapter 16. Figure 16-5 Gas leak detection

442 Chapter 16. Figure 16-5 Gas leak detection BRORANE BRORANEBRORANEBRORANEBRORANEBRORANEBRORANEBRORANE 442 Chapter 16 Tur n e r BRORANE FUEL EBRORANEBRORANEBRORANEBRORANEBRORANE Figure 16-5 Gas leak detection is easy. This sensitive halide detector

More information

DCC-2200 / DCC-2300 CLIMATE CONTROL MODULE for Vintage Air Gen II Modules

DCC-2200 / DCC-2300 CLIMATE CONTROL MODULE for Vintage Air Gen II Modules BLACK DIM IGN CABIN- CABIN+ VENT- VENT+ FLOOR- FLOOR+ GND FAN MED A/C FAN HI +12V EVP-(R) EVP+(Y) DCC-2200 / DCC-2300 CLIMATE CONTROL MODULE for Vintage Air Gen II Modules TO AVOID DAMAGE TO GEN II UNIT,

More information

HEAT/ COOL/ DEFROST FORD THUNDERBIRD

HEAT/ COOL/ DEFROST FORD THUNDERBIRD specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1964-66 FORD THUNDERBIRD CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

OPERATION AND SERVICE for

OPERATION AND SERVICE for T-313 Manual OPERATION AND SERVICE for 68RM50-100/101 MICROMAX T-313 REV. 07/2012 2012 Mobile Climate Control SAFETY SUMMARY GENERAL SAFETY NOTICES The following general safety notices supplement the specific

More information

Thermostat Cold Air Evaporator

Thermostat Cold Air Evaporator Chart Thermostat Cold Air Evaporator 4 Expansion Valve 5 Evaporator Blower 6 Compressor Condenser Sight Glass Pressure Switch Fan Desiccant 3 Receiver Drier High Pressure Gas High Pressure Liquid Low Pressure

More information

Climate Control. Service Training Course No. 701

Climate Control. Service Training Course No. 701 Service Training Course No. 701 Climate Control This publication is intended for instructional purposes only. Always refer to the appropriate Jaguar Service publication for specific details and procedures.

More information

PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1968 CHEVROLET IMPALA

PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1968 CHEVROLET IMPALA specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1968 CHEVROLET IMPALA CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

AIR CONDITIONING SYSTEM

AIR CONDITIONING SYSTEM AIR CONDITIONING SYSTEM PRECAUTION CAUTION: AIR CONDITIONING SYSTEM Because the compressor has a highvoltage circuit, wear insulated gloves and pull out the service plug to cut the highvoltage circuit

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

an ISO 9001:2015 Registered Company

an ISO 9001:2015 Registered Company an ISO 9001:2015 Registered Company Mark IV (672001-VHY) 18865 Goll St. San Antonio, TX 78266 Phone: 800-862-6658 Sales: sales@vintageair.com Tech Support: tech@vintageair.com www.vintageair.com 902001-VHY

More information

specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic hi l PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST FORD TRUCK

specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic hi l PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST FORD TRUCK specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic hi l PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST 1967-72 FORD TRUCK CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

TROUBLESHOOTING VANGUARD

TROUBLESHOOTING VANGUARD TROUBLESHOOTING VANGUARD IMPORTANT: Only a qualified Service Person should service internal components or electrical wiring. WARNING: Disconnect electrical power to the Unit to prevent personal injury

More information

OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series

OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com Owner s Manual MGD-B SERIES GAS FURNACE

More information

Troubleshooting & Reference

Troubleshooting & Reference Troubleshooting & Reference Error Code Descriptions Description of Error Codes - 9, 12 MBH code malfunction Error Display Repair Method 1 Storage slug (EEPROM) 2 Indoor PCB malfunction 3 Anti-freezing

More information

SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL

SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL MODEL AT105 AT115 AT130 with Titanium Heat Exchanger 2213 Andrea Lane Ft. Myers FL 33912 888-297-3826 941-482-0606 www.aquathermheatpumps.com DIGITAL

More information

Emissions testing Honda Accord/Prelude

Emissions testing Honda Accord/Prelude Emissions testing Honda Accord/Prelude 1984-1995 PVC TESTING See Figure 4 The PCV valve is easily checked with the engine running at normal idle speed (warmed up). Gently pinch the hose shut, then release

More information

PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST PLYMOUTH BELVEDERE

PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST PLYMOUTH BELVEDERE PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1966-67 PLYMOUTH BELVEDERE CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect Fit system. Offers complete comfort capabilities in virtually every

More information

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST MUSTANG

PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST MUSTANG specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST 1965-66 MUSTANG CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL www.polartemp.com TABLE OF CONTENT Disclaimer.......................................... Page 3 Inspection, unpacking and FMU setup.................. Page

More information

Norcold Repair Guide for Ice Maker

Norcold Repair Guide for Ice Maker Norcold Repair Guide for Ice Maker Section 10 Table of Contents Page: 10-2 General Description 10-2 Refrigerator Specifications 10-2 Refrigerator Operating Limits 10-2 Refrigerator Current Draws 10-2 Ice

More information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient

More information

WARNING WARNING TROUBLESHOOTING GUIDE INTEGRATED FURNACE CONTROL MODULE

WARNING WARNING TROUBLESHOOTING GUIDE INTEGRATED FURNACE CONTROL MODULE TROUBLESHOOTING INTEGRATED FURNACE Failure to read and follow all instructions carefully before installing or operating this control, could cause personal injury and/ or property damage. 50A55 INTEGRATED

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

Fig. 1 - Unit PHD4 and WPH4

Fig. 1 - Unit PHD4 and WPH4 OWNER S MANUAL 14 SEER Single -Package Heat Pump System with R -410A Refrigerant Single Phase and Three Phase 2 to 5 Nominal Tons PHD4 Series F and WPH4 Series B Fig. 1 - Unit PHD4 and WPH4 A09034 NOTE

More information

Heat Pump Defrost Board Replacement Kit

Heat Pump Defrost Board Replacement Kit Bard Manufacturing Company, Inc. Bryan, Ohio 43506 8620-223 Heat Pump Defrost Board Replacement Kit KIT FEATURES This kit is made up of the current defrost control board 8201-129 and a new defrost sensor.

More information

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES C US INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES Made in the USA by: Goodman Manufacturing Company, L.P. I0-240B 2550 North Loop West, Suite 400, Houston, TX 77092 www.goodmanmfg.com

More information

INSTALLATION AND TROUBLE SHOOTING MANUAL for all Models of Nova Kool Remote Condensing units & Cold plates.

INSTALLATION AND TROUBLE SHOOTING MANUAL for all Models of Nova Kool Remote Condensing units & Cold plates. INSTALLATION AND TROUBLE SHOOTING MANUAL for all Models of Nova Kool Remote Condensing units & Cold plates. Thank you for choosing Nova Kool for your refrigeration needs. For over 20 years we have been

More information

CIRRUS AIRPLANE MAINTENANCE MANUAL

CIRRUS AIRPLANE MAINTENANCE MANUAL COOLING 1. DESCRIPTION On aircraft serials 183 and subsequent, an optional air condition system is available. This section contains the maintenance practices pertinent to this system. Cabin ventilation

More information

SEA FROST BD 12 OR 24-VOLT D.C. AIR-COOLED SYSTEM

SEA FROST BD 12 OR 24-VOLT D.C. AIR-COOLED SYSTEM 148 OLD CONCORD TURNPIKE BARRINGTON, NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 E-Mail:sales@seafrost.com www.seafrost.com SEA FROST BD 12 OR 24-VOLT D.C. AIR-COOLED SYSTEM CONDENSING

More information

EVANS TEMPCON DASH HEATER A/C All Electric Control Systems

EVANS TEMPCON DASH HEATER A/C All Electric Control Systems EVANS TEMPCON DASH HEATER A/C All Electric Control Systems Owner s Manual Operating Instructions For additional owner and operator information visit us on the web at www.evanstempcon.com WARNING This heater

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

Refrigerator KE T

Refrigerator KE T Refrigerator KE 680-1-3T Service Manual: H8-74-07 Responsible: U. Laarmann KÜPPERSBUSCH HAUSGERÄTE AG E-mail: uwe.laarmann@kueppersbusch.de Tel.: (0209) 401-732 Customer Service Fax: (0209) 401-743 Postfach

More information

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1.0 SCOPE: This Operations and Maintenance

More information

Product Information and Technical Guide

Product Information and Technical Guide Product Information and Technical Guide Side by Side and Top Mount Refrigerators January 2005 - June 2005 White-Westinghouse 5995449906 October 2005 TABLE OF CONTENTS Safe Servicing Practices ------------------------------------------------------------------------------------------

More information

HEATING AND AIR CONDITIONING

HEATING AND AIR CONDITIONING Z HEATING AND AIR CONDITIONING 24-1 HEATING AND AIR CONDITIONING CONTENTS page CLIMATE CONTROL SYSTEM... 39 COMPRESSOR SERVICE PROCEDURES... 36 GENERAL INFORMATION... 1 page SYSTEM DIAGNOSTICS... 8 REFRIGERANT

More information

SECTION 50 - CAB CLIMATE CONTROL

SECTION 50 - CAB CLIMATE CONTROL AIR CONDITIONING SYSTEM DYNAMIC DESCRIPTION The refrigerant circuit of the air conditioning system contains five major components: Compressor, Condenser, Receiver/Drier, Expansion Valve, and Evaporator.

More information

Electronic Ignition Water Heater

Electronic Ignition Water Heater Electronic Ignition Water Heater TROUBLE SHOOTING GUIDE Effective: 5/26/98 Guides are only intended for use on Atwood products by service technicians who have successfully completed Atwood training. This

More information

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration Calhoon MEBA Engineering School Study Guide for Proficiency Testing Refrigeration 1. To prevent an injury when working with refrigerants, what safety precautions are necessary? 2. When halogens are in

More information

SEA FROST BD 12 OR 24 VOLT D.C. SYSTEM With Water Cooling Option

SEA FROST BD 12 OR 24 VOLT D.C. SYSTEM With Water Cooling Option 148 OLD CONCORD TURNPIKE BARRINGTON, NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 E-Mail:sales@seafrost.com www.seafrost.com SEA FROST BD 12 OR 24 VOLT D.C. SYSTEM With Water Cooling

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 2-Stage R-410A Split System These units have been designed and tested for capacity & efficiency in accordance with A.H.R.I. Standards.

More information

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table) 1 2 Warning: - Do not place your hand or any other objects into the air outlet and fan. It could damage the heat pump and cause injuries; - In case of any abnormality with the heat pump, cut off the power

More information

Bulletin (Jan 2011) And User s Guide

Bulletin (Jan 2011) And User s Guide Bulletin 30 32 (Jan 2011) Unichiller Installation And User s Guide Customer Service If you have questions about Installation, operation and Maintenance of the Unichiller or would like to order replacement

More information