COMMERCIAL AIR COOLERS AIR AND ELECTRIC DEFROST

Size: px
Start display at page:

Download "COMMERCIAL AIR COOLERS AIR AND ELECTRIC DEFROST"

Transcription

1 INSTALLATION, OPERATION & MAINTENANCE MANUAL CAH CEH CDH High profile unit coolers COMMERCIAL AIR COOLERS AIR AND ELECTRIC DEFROST Index 1. Warranty statement 2 2. General Safety Information 3 3. Inspection 4 4. Unloading 4 5. Mounting 5 6. Refrigerant piping 6 7. Expansion valve 6 8. Drain line 7 9. Wiring Evacuation Installation Start-up Maintenance and service Electrical data Spare Parts Trouble shooting Reference data 13 1

2 1.- Warranty Statement The supplier warrants against defects in workmanship and materials of the product supplied for a period of 24 months from the time of transfer of risk, provided that they are correctly installed and operated within the recommended limits of the manufacturer s technical documentation. The supplier at its option shall repair, or replace, free of charge to the purchaser all goods which become defective during the warranty period as a result of defects in design, workmanship or materials, fair wear and tear excluded, provided, however, that; - the application is correct - operating and installation instructions are complied with - system component and piping design is in accordance with good refrigeration practice - Nitrogen or an inert gas must be introduced into the piping during the brazing of the piping installation In order to execute the corrective work or replacement supply that appears necessary, within the supplier s reasonable discretion, the purchaser must, following communication with the supplier, provide the necessary time and opportunity, or the supplier will be freed from the liability of the defect. The costs arising directly from the corrective work or replacement supply, transport and exchange costs in particular, shall be borne by the purchaser himself. The supplier shall not be liable for costs incurred in dismantling or fitting replacement parts or for any independent inspection undertaken by the purchaser. The purchaser shall return any allegedly defective goods, carriage paid, to the supplier s works. Upon receipt of the goods and inspection thereof the supplier shall repair or replace, at the supplier s discretion, the defective goods and return freight, carriage paid, and without any further expenses. This shall constitute full compliance of the supplier s obligations. No liability is accepted for the consequences of modifications or repair work being carried out by the purchaser or a third party incorrectly or without the prior permission of the supplier. It is clearly understood and agreed that any further claims, in particular claims for compensation for damage and consequential damages not occurring on the supplied item itself, are excluded. Furthermore the supplier shall not be liable to the purchaser, or client of the purchaser, for any direct or indirect damages, injury to persons or property or any consequential loss or loss of profits arising from defective goods or workmanship or from any other cause whatsoever. To obtain warranty service, please contact: quality@guentner.com.mx 2

3 2. GENERAL SAFETY INFORMATION All installation and maintenance procedures should be performed by qualified personnel already familiarized with the equipment. All field wiring should match the requirements of the equipment, as well as any local or national codes. Coil edges and other sharp objects should be met with caution, as they can cause serious injury. Fan blades are especially sharp, and therefore should be handled only while wearing protective gloves. All power sources should be disconnected before any type of service work is performed on the equipment. For cleaning the equipment, reinstall the drain pan after every cleaning session. Failure to follow these steps can result in damaged equipment or personal injury. Inhalation of certain refrigerants can be harmful, or even fatal. Failure to implement proper detection devices, ventilation, and procedures can result in serious injury or death. Ventilation of all refrigerants should follow all related regulations, as certain refrigerants are harmful to the environment. For more information, refer to any local or national codes that may apply. High temperatures can cause damage to the equipment. The expansion valve must be covered in heat absorbent material and the suction line sensor removed while brazing the refrigerant connections. Never use the refrigeration compressor to evacuate the equipment. Never start the refrigeration compressor if it is in a vacuum. Fan motors are sealed and do not need lubrication 3

4 3. INSPECTION Each shipment should be carefully checked against the bill of loading at time of receipt. The shipping receipt should not be signed until all items listed on the bill of loading have been accounted for. Check carefully for any damage. Any and all shortages or damages should be reported to the delivery carrier. Damaged equipment during shipment becomes the delivery agent s responsibility and should not be returned unless prior approval has been given. The equipment is pressurized with 29 psi (2 Bars) dry air during manufacturing. If the unit lost pressure during transportation, contact the Sales Department (sales@guentner.com.mx). For special requirements please contact our factory. 4. UNLOADING Normal care should be taken while unpacking and uncrating equipment so that damage and injury can be prevented. Heavy equipment should be kept on the original pallet until ready for final installation. While using lifting belts, ensure that a spreader bar is used, and that the belts do not compress the sheet metal construction. When using a truck lift, ensure that the unit is positioned as shown in the picture below. 2

5 5. MOUNTING The equipment can be mounted using rod hangers, lag screws and/or bolts. Units should be hung with no degree of inclination so that the condensate drainage can be properly maintained. Proper airflow through the unit is essential for efficient performance and maintenance of design storage temperatures. Never install an evaporator over a doorway. The drain pan should be fitted only after the installation of the equipment. DIMENSIONS CAH CEH - CDH CEH - CDH (ELECTRIC DEFROST) Dimensions Model Dimensions Connections Weight L H B E Liquid Suction Drain No Fan in mm in mm in mm in mm lbs kg in mm in mm in mm CEH 6 FPI /8 1, / / / / / / /8 1, / / / / / / , / / / / / / , / / / / / / /8 3, / / / / / / /8 3, / / / / / / /4 4, / / / / / / /4 4, / / / / / /4 32 CDH 4 FPI /8 1, / / / / / / /8 1, / / / / / / , / / / / / / , / / / / / / /8 3, / / / / / / /8 3, / / / / / / /4 4, / / / / / / /4 4, / / / / / /4 32 CAH (AIR DEFROST) Dimensions Model Dimensions Connections Weight L H B E Liquid Suction Drain No Fan in mm in mm in mm in mm lbs kg in mm in mm in mm CAH 6 FPI /8 1, / / / / / / /8 1, / / / / / / , / / / / / / , / / / / / / /8 3, / / / / / / /8 3, / / / / / / /4 4, / / / / / / /4 4, / / / / / /4 32 5

6 CAH-CEH-CDH Mounting reference n = number of units to install Lr = length of room NOTES Do not place the cooler directly over or next to a door. Do not place produce directly in front of the cooler. Do not place coolers in front of each other at a distance less than their air throw indicated in the technical specification sheet. In the case of electric defrost units, make sure to leave a free space of at least the length of the unit on the electric connection side to remove the heaters in case of failure. The minimum distance between units must be 6 for hot gas and air defrost units. If you have reduced space or special room construction, please contact your local sales office to receive the correct advice on unit mounting. 6. REFRIGERANT PIPING Type, sizing and installation of all piping must be in accordance with the recommended and accepted practices for Freon refrigeration applications. All low temperature piping should also be insulated in accordance with standards ASHRAE. Suction traps should be used when and if the suction line rises above the unit cooler. 7. EXPANSION VALVE For direct expansion units, select an expansion valve in accordance with capacity data and as required by expansion valve manufacturer. Expansion valves with external equalizers should be used. After the temperature has reached design conditions, adjust the expansion valve to obtain 8 to 10º F superheat at the suction line. Expansion valves are to be installed in accordance with the specific manufacturer s recommendations. Units that require an external equalized expansion valve must have that line connected. Proper location of the bulb is extremely important to the performance of the coil. Good thermal contact to the suction line is also essential. On solder type valves, a wet cloth wrapped around the valve during installation will protect it from overheating and damage. On multiple evaporator systems, the piping should be arranged such that the flow from any valve cannot affect the bulb of another. 2

7 8. DRAIN LINE The drain line must be pitched to effectively drain condensate. All drain lines subject to freezing temperatures must have drain line heaters and be insulated. Drain line traps must also be heated to prevent freezing up of the drain line and trap. 9. WIRING All wiring must be done in strict accordance with local and national electrical codes. Fan motor(s), local isolators, electrical heater elements and controllers must be wired in accordance with the electrical wiring diagrams provided. Use copper conductors of appropriate size only. All electrical installations should only be performed by qualified and authorized personnel. For thermal motor protection, the installed thermal contacts must be used and wired according to the circuit diagram attached to the unit. 10. EVACUATION Proper evacuation is essential prior to charging the refrigerant for the system. This avoids many problems that can arise due to lack of detail within this step. The system should be checked through all cycles to ensure proper operation. 11. INSTALLATION The installation and maintenance of this equipment should be performed only by qualified professional personnel who are familiar with this type of equipment. The equipment is pressurized with dry air. All equipment must be evacuated before charging the system with refrigerant. All field wiring should be checked and be in strict conformity with the equipment requirements, as well as all national and local codes. Use the name plate electrical data for conductor and fuse sizing. Avoid contact with any sharp edges or sharp coil surfaces. These can be a potential injury hazard. Make sure that all power sources are disconnected before any service work is done on equipment. CAUTION: BEFORE STARTING UP UNIT MAKE SURE ALL ACCESSIBLE ELECTRICAL PARTS ARE SECURED! 12. START-UP At start-up the following items should be checked: - Check all screwed connections, especially at moveable parts. - Check tube connections, make sure that brackets are in place and connection screws are secured. - Check electrical connections of motors, heater elements and any additional components, if applicable. - Run the fans and check the direction of rotation. Make sure that there is no transport damage. The system should be properly evacuated. - During the test run observe the equipment and take notice of the following: o Silent operation of the fans (bearings, contacts, balance) o Power requirements of electrical motors o Leakages o Check superheat - After 48 hours of operation re-check the equipment, especially all rotating parts. 7

8 13. MAINTENANCE AND SERVICE CAUTION: DISCONNECT ALL POWER BEFORE SERVICE! PREVENTIVE MAINTENANCE FOR COMMERCIAL EVAPORATORS CLEAN using a brush, pressurized water, or a mild detergent. Make sure the product you use is approved for your particular application. NEVER USE ACID BASED CLEANER. RINSE coil until no residue remains CHECK each fan rotates freely and quietly. Replace any motor that vibrates or makes unusual noise INSPECT unit for unusual vibration in ventilators or casing. Determine which ventilator is causing vibration INSPECT Drain pan to insure that drain is clear of any obstructions, including ice buildup INSPECT for ice accumulation in coil CHECK all blades for wear, cracks or dents. CHECK calibration of defrost controller CHECK that heaters are working accordingly during defrost CHECK heater current consumption against the electrical schematic CHECK drain line heater is working properly CHECK all fan screws are tight, and torque if needed AS REQUIRED MONTHLY EVERY 3 MONTHS EVERY 6 MONTHS EVERY YEAR INSPECT unit for corrosion on fins, tray, casing, soldered joints, copper tubes INSPECT unit for oil stains in headers, return bends and coil fins. Check for possible leaks INSPECT all wiring for wear, tears, and unprotected wire. Replace any wiring necessary INSPECT all ground connections are tight 13.1 FAN MOTORS AND HEATERS The only electrical components vulnerable to potential malfunction are the fan, motors, and electrical defrost heaters. In the event of motor or heater failure, the affected motor should be removed from the unit and tested separately. If the motor and/or heaters continue to malfunction then they will need to be replaced DRAIN PAN Periodic inspection of the drain pan is recommended. Accumulated dirt and dust should be cleaned out with soap and warm water. If a sign of improper drainage is apparent then the drain line pitch, drain line heater (if applicable) and drain trap should be checked for proper operation. Unit can be cleaned using warm water and soap. Special care should be taken when cleaning the unit around the electrical areas including motor, wiring and junction boxes. Water could potentially damage the electrical motor INSPECTION AND MAINTENANCE Verify the following points when visually inspecting the equipment: - Secured screw connections - Leakages - Silent operation of the fans 2

9 - General state of the unit such as cleanliness and corrosion The cleaning of the finned heat exchanger is of the upmost importance to ensure smooth operation and long life of the equipment. - There is no general rule how often it should be cleaned. Frequency and method of cleaning depend on the customer and must be determined by the customer s operating personnel. If need be, ice must be defrosted with a hot air drier or hot water. - The equipment is always supplied in a clean condition. If, during installation and/or first operation hours, contamination reaches a state where capacity can be affected, it is necessary that the unit is cleaned before operation. When cleaning the unit it must be out of operation and all electrical power disconnected. Mechanical Cleaning of the Heat Exchanger - Blow down the fins with air (only suitable for light, dry and dusty deposits). - Cleaning with compressed air (maximum pressure 6 bar, minimum distance from fins 8 inches). - If some contamination is located mainly at the inlet of the fins, clean with a soft brush or use an industrial vacuum cleaner. Hydraulic Cleaning of the Heat Exchanger - For oil containing deposits, it is acceptable to add detergent to the water. Make sure not to deform the fins. - When using chemical substances, make sure they do not corrode the heat exchanger material and casing. Rinse the heat exchanger and casing after treatment. - When cleaning with liquid or compressed air, the fans must be switched off. Do not spray them directly. - Clean the coil from top to bottom in order to allow the contamination to drain downwards. Cleaning must be continued until all contamination has been removed. - Always clean/spray in the direction of the fins. Never clean at 90 to the fins! - Maximum allowed vapor pressure is 6 bar. Maximum allowed water pressure before the outlet is 80 to 100 bar. 14. ELECTRICAL DATA CAH (AIR DEFROST) Electrical Data Fan Data Fan motor Data Model Fans Diameter Voltage "L" 460/3/60 Voltage "V" 230/3/60 # in mm Watts Amps Total Amps rpm Watts Amps Total Amps rpm CAH 6 FPI , , , , , , , , , , , , , , , ,370 9

10 CEH - CDH (ELECTRIC DEFROST) Electrical Data Model Fan motor Data Heater Data Fan Data Voltage "L" 460/3/60 Voltage "V" 230/3/60 Voltage "L" 460/3/60 Voltage "V" 230/3/60 Fa n Diamete r T otal T otal T ray Coil T otal T otal T ray Coil T otal T otal Watts Amps rpm Watts Amps rpm # in mm Amps Amps Watts Watts Watts Amps Watts Watts Watts Amps CEH 6 FPI , , , , , , , , , , , , , , , , CDH 4 FPI , , , , , , , , , , , , , , , ,

11 15. SPARE PARTS CAH Fan Main J/Box VT.Num. Drain Model 460V-3Ph-60Hz 230V-3Ph-60Hz 230V-1Ph-50/60HZ CAH 0350 VT01163U VT01186U PC m UL BGAB114K CAH 0470 VT01163U VT01186U PC m UL BGAB114K CAH 0700 VT01163U VT01186U PC m UL BGAB114K CAH 0930 VT01163U VT01186U PC m UL BGAB114K CAH 0575 VT01163U VT01186U PC m UL BGAB114K CAH 1050 VT01163U VT01186U PC m UL BGAB114K CAH 1410 VT01163U VT01186U PC m UL BGAB114K CAH 0840 VT01163U VT01186U PC m UL BGAB114K CAH 1400 VT01163U VT01186U PC m UL BGAB114K CAH 1900 VT01163U VT01186U PC m UL BGAB114K CAH 1140 VT01163U VT01186U PC m UL BGAB114K CAH 1630 VT01163U VT01186U PC m UL BGAB114K CEH Fan Heater Coil Heater Tray VT.Num. Heater Number Heater Number Drain Model 460V-3Ph-60Hz 230V-3Ph-60Hz 460V-3Ph-60Hz 230V-3Ph-60Hz 460V-3Ph-60Hz 230V-3Ph-60Hz CEH 0300 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CEH 0370 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CEH 0600 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CEH 0780 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CEH 0520 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CEH 0900 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CEH 1200 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CEH 0735 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CEH 1060 VT01163U VT01186U U07EB U04BB U07EB U07EB BGAB114K CEH 1400 VT01163U VT01186U U07EB U04BB U07EB U07EB BGAB114K CEH 0865 VT01163U VT01186U U07EB U04BB U07EB U07EB BGAB114K CEH 1220 VT01163U VT01186U U07EB U04BB U07EB U07EB BGAB114K CDH Fan Heater Coil Heater Tray VT.Num. Heater Number Heater Number Drain Model 460V-3Ph-60Hz 230V-3Ph-60Hz 460V-3Ph-60Hz 230V-3Ph-60Hz 460V-3Ph-60Hz 230V-3Ph-60Hz CDH 0280 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CDH 0360 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CDH 0550 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CDH 0740 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CDH 0890 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CDH 0980 VT01163U VT01186U U07EB U04BB U07EB U04CB BGAB114K CDH 1100 VT01163U VT01186U U07EB U04BB U07EB U07EB BGAB114K CDH 1080 VT01163U VT01186U U07EB U04BB U07EB U07EB BGAB114K 11

12 16. TROUBLESHOOTING Symptoms Possible Causes Possible Corrective steps 1. Fan is not working 2. Room Temperature too High 1.1 Main switch Open Close Switch 1.2 Blown Fuses Check for short circuits or overloads. Replace damaged fuse 1.3 Damaged timer or defrost thermostat Replace controller 1.4 Unit in defrost cycle Wait until cycle completion 1.5 Coil does not get cold enough to reset thermostat Increase fan delay time after defrost cycle 1.6 Motor is burnt Check for Voltage surge and replace motor Check for any obstruction (ice, debris, etc..) and remove 1.7 Ventilator does not turn Check junction box in fan for any short circuit and repair 2.1 Room thermostat set too high Reduce thermostat setting Check if TXV is feeding correctly and clean strainer filter Check if bulb is placed in correct position and adjust if necessary Adjust the superheat on TXV. 2.2 Superheat too high Check for low refrigerant charge in system. Go to Low refrigerant in system Check for leaks and charge additional refrigerant in system 2.4 Coil blocked with Ice Make manual defrost in coil. Check defrost system. 2.5 Unit cooler too close to doors Relocate unit or add strip/air curtain to door Check for door seals and replace if necessary 2.6 Excessive Air infiltration due to open doors Keep doors closed as long as possible 2.7 Product has just been loaded into cold room Wait until product temperature is lower 2.8 System is turned off Turn on refrigeration system 2.9 Power surge in system fails Restore power surge 2.10 Poor air flow in room Make sure all fans turn in correct direction See Possible cause See Symptom Check unit placement recommendations 2.11 Pressure drop across evaporator too high Replace TXV with valve having external pressure equalization, adjust superheat on valve 2.12 Lack of subcooling in the system Establish a subcooling in the system 2.13 Pressure drop across the valve is larger than the design pressure of the valve Select a new valve with the desired pressure drop Expansion valve is blocked with ice due to moisture in the system Change drier filter, and clean ice off valve Clean the valve port, and strainer Clean the solenoid valve and its filter 2.15 Expansion valve is blocked with wax or other impurities Replace the oil in the refrigeration system 2.16 Expansion valve is too small Select and replace valve with higher capacity valve or orifice TXV Bulb charge lost Replace valve (or powerhead if possible) 2.18 Incorrect TXV powerhead selected Select a powerhead according to the application TXV Bulb is not making good contact with suction line Fasten bulb to suction line appropiately 2.20 TXV bulb is not insulated Place insulation over the whole bulb 2.21 TXV bulb is located near large valves, flanges, headers, or rising pipe Place TXV bulb in horizontal pipe between suction line and oil trap. 3. Ice build-up 3.1 Defrost cycle is too long Decrease time on defrost on ceiling 3.2 Fan delay not working after defrost cycle Adjust defrost thermostat correctly, or go to 3.3 around 3.3 Defective defrost thermostat or timer Replace component evaporator and/or on fan nozzles, blades, or grill 4. Coil not 3.4 Too many defrosts Reduce number of defrosts per day 4.1 Heater not working Make sure all heaters are working. clearing frost 4.2 Hot gas supply is not enough Make sure there is sufficient hot gas volume to defrost unit. 4.3 Not enough defrost cycles per day Increase the number of defrost cycles per day after defrost 4.4 Defrost cycle too short Increase time on defrost thermostat or timer for longer cycle cycle 4.5 Defrost Thermostat or timer not working Replace component 5. Uneven coil 5.1 Distributor in horizontal position Change distributor to vertical position frosting during 5.2 Distributor or capillaries are blocked Replace distributor with capillaries 5.3 After defrost, dripping time too short Increase time for dripping refrigeration 5.4 Incorrect or missing distributor nozzle Add or replace nozzle with appropiate size orifice for conditions cycle 5.5 Located too close to door opening Relocate evaporator 6.1 Drain line heater not working Check heater power supply Change drain line heater 6.2 Tray heater not working Check heater power supply Change tray heater 6. Ice 6.3 Unit tilted unproperly Level unit to horizontal position accumulation on drain pan 6.4 Drain line plugged Clean drain line Insulate drain line properly (if blocked with ice) 6.6 Thermostat not working Replace defective component 6.6 Drain line without water tramp Install water tramp in drain line outside cold room 6.7 Drain pan not placed properly in unit after mainteinance Make sure drain pan is close to heaters or hot gas coil. 7. Water 7.1 Drain line plugged Clean drain line accumulation on drain pan or 7.2 Drain pan not placed properly in unit after mainteinance Make sure drain pan is leveled towards the back water spreading outside unit 7.3 Unit tilted unproperly Level unit to horizontal position 2

13 17. REFERENCE DATA Service Record CAH / CEH / CDH A data sheet for each installation and each unit cooler must be filled out, with one copy for the owner, one copy for the installing contractor and the original for Coilexpert. Güntner. If another firm is to handle service and maintenance, additional copies should be prepared as necessary. System Reference Data The following information should be filled out and signed by the Refrigeration Installation Contractor Date System Installed: Installer and Address: Evaporator(s) Evaporator Model No. Evaporator Serial No. Electrical Volts Phase Expansion Valve Manufacturer/Model Ambient at Start-Up ºF Design Box Temperature ºF Operating Box Temperature ºF Thermostat Setting ºF Defrost Setting /day minutes fail-safe /day minutes fail-safe Suction Line Evaporator ºF Superheat at Evaporator ºF Evacuation No. times Final Micron No. Times Final Micron Evaporator Drain Line Trapped Outside of Box Yes No Güntner de México S.A. de C.V Av. Rogelio González Caballero No.1000, Parque Industrial Stiva Aeropuerto Apodaca Nuevo León México, cp Office tel: Office fax: sales@guentner.com.mx 13

COMMERCIAL AIR COOLERS AIR AND ELECTRIC DEFROST

COMMERCIAL AIR COOLERS AIR AND ELECTRIC DEFROST INSTALLATION, OPERATION & MAINTENANCE MANUAL CAC CEC CDC Ceiling mounted Reach in unit coolers COMMERCIAL AIR COOLERS AIR AND ELECTRIC DEFROST Index 1. Warranty statement 2 2. General Safety Information

More information

COMMERCIAL AIR COOLERS AIR, ELECTRIC AND HOTGAS DEFROST

COMMERCIAL AIR COOLERS AIR, ELECTRIC AND HOTGAS DEFROST INSTALLATION, OPERATION & MAINTENANCE MANUAL CAM CEM CDM CGM - CKM Mediun profile unit coolers COMMERCIAL AIR COOLERS AIR, ELECTRIC AND HOTGAS DEFROST Index 1. Warranty statement 2 2. General Safety Information

More information

COMMERCIAL AIR COOLERS AIR, ELECTRIC AND HOTGAS DEFROST

COMMERCIAL AIR COOLERS AIR, ELECTRIC AND HOTGAS DEFROST INSTALLATION, OPERATION & MAINTENANCE MANUAL GAL GEL GDL GGL - GKL Low profile unit coolers COMMERCIAL AIR COOLERS AIR, ELECTRIC AND HOTGAS DEFROST Index 1. Warranty Statement 2 2. General Safety Information

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Owner s Manual Window Air Conditioner

Owner s Manual Window Air Conditioner Owner s Manual Window Air Conditioner G17-5MCVWAC1 G16-5MCVWAC Write the model and serial numbers below for your records: Model # Serial # Date Purchased Please read the entire manual carefully to ensure

More information

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- 8610 Production Avenue San Diego, California 92121 (858) 566-7465 Fax (858) 566-1943 WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS-- Thank you for choosing a BREEZAIRE cooling unit. We believe

More information

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL www.polartemp.com TABLE OF CONTENT Disclaimer.......................................... Page 3 Inspection, unpacking and FMU setup.................. Page

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual

REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual For service information call 800-544-3057 Please have the following information available before calling. Information can be found on

More information

InstructIon Manual KrEs EQuIPMEnt stands

InstructIon Manual KrEs EQuIPMEnt stands Instruction Manual Instruction Manual SELF-CONTAINED AND REMOTE Kairak KRES model refrigerated equipment stand units are available in many lengths from 36 to 120 inches long. These units are available

More information

RPI Industries, Inc.

RPI Industries, Inc. RPI Industries, Inc. AIR SCREEN and SELF-SERVE OPERATION AND SERVICE MANUAL WARRANTY INFORMATION For Models Stratus SCRFC48R-SSI SCRFC60R-SSI SCRFC72R-SSI SCRFC48R-SSII SCRFC72R-SSII SCRFC48R-SSIII SCRFC72R-SSIII

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

NEWGATE TECHNOLOGIES, INC.

NEWGATE TECHNOLOGIES, INC. www W.newgatetechnologies.com NEWGATE TECHNOLOGIES, INC. Installation & Operations Manual SYNERGY Series High Inlet Temperature Refrigerated Air Dryers Models SYNERGY 025 ~ SYNERGY 125 Includes Safety

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products, Inc. 700 Thimble Shoals Blvd, Suite 109 Newport News, VA. 23606-2575 Tel: (757) 873 6800 Fax: (757) 873 3632

More information

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT Concepcion Carrier Air conditioning Company Philippines INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT CONTENTS Safety Considerations 1 Complete

More information

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features. Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com UNPACKING

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products, Inc. 700 Thimble Shoals Blvd, Suite 109 Newport News, VA. 23606-2575 Tel: (757) 873 6800 Fax: (757) 873 3632 Website www.ebacusa.com

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

MODEL RD-8 Self Contained MODEL RD-2

MODEL RD-8 Self Contained MODEL RD-2 MODEL RD-8 Self Contained REFRIGERATED SHOWCASE MODEL RD-2 REFRIGERATED SHOWCASE Document Part #: 1150285 Rev: I ECN: 55118 Rev. Date: 5-28-14 The RD-2 and RD-8 refrigerated display showcase units have

More information

INSTRUCTIONS! DO NOT DISCARD!

INSTRUCTIONS! DO NOT DISCARD! INSTRUCTIONS! DO NOT DISCARD! CAUTION! Do NOT install where injury might occur due to Moving parts, Sharp corners, Hot surfaces or electrical components dn0521 Page 1 of 12 INSTALLATION INSTRUCTIONS CAUTION

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation

More information

T-Series Air Conditioner T53 Model

T-Series Air Conditioner T53 Model INSTRUCTION MANUAL T-Series Air Conditioner T53 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

T-Series Air Conditioner T20 Model

T-Series Air Conditioner T20 Model INSTRUCTION MANUAL T-Series Air Conditioner T20 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

OWNER S MANUAL. Installation Operation Maintenance. Saturn Equipment

OWNER S MANUAL. Installation Operation Maintenance.   Saturn Equipment OWNER S MANUAL Saturn Stainless Steel Sandwich/Salad Table & Mega Top Refrigerators Undercounter Refrigerators & Undercounter Freezers Installation Operation Maintenance Saturn Equipment www.saturnequipment.com

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News VA 23606 Telephone (757) 873-6800 FAX (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information

R Series Cooling Modules

R Series Cooling Modules R Series Cooling Modules Models RCM/RPM 50 RCM 70 RM 100 RM 140 Manufactured By Energy Saving Products Ltd. Standard ESP 105.03 Refrigerant Modules (RCM/RM) Fig. 02 - Mounting brackets The cooling coil

More information

ThermoSaver TM Hot Gas Defrost System

ThermoSaver TM Hot Gas Defrost System PRODUCT DATA, APPLICATION & INSTALLATION GUIDE Supplement to Condensing Unit Installation and Maintenance Manual Bulletin B40-THERM-PDI-14 1069132 ThermoSaver TM Hot Gas Defrost System For use on select

More information

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL KOMPACT OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the Kompact is a rugged, industrial unit, which utilizes

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T15 Model INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 700 Thimble Shoals Boulevard Newport News VA 23606-2575 Telephone (757) 873-6800 Fax (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance

More information

R Series Cooling Modules

R Series Cooling Modules TM Small Duct High Velocity Heating, Cooling and Indoor Air Quality Systems R Series Cooling Modules Models RCM-50 RCM-70 RM-100 Manufactured By Module-RCM/RM-Series-Installation-Manual-120113 Refrigerant

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

BX Series. Installation, Operation, Maintenance Instructions & Spare Parts

BX Series. Installation, Operation, Maintenance Instructions & Spare Parts ISO 9001 BX Series Installation, Operation, Maintenance Instructions & Spare Parts WARNING WARNING. The BX convection heater is a heavy duty baseboard designed for use in industrial environments and is

More information

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL DATE OF PURCHASE: MODEL: SERIAL NO.: Record above information from nameplate. Retain this information for future reference.

More information

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL WM150 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an

More information

Owner / Operator Use and Care Guide I SERIES 224 ICE CUBE MACHINE

Owner / Operator Use and Care Guide I SERIES 224 ICE CUBE MACHINE Owner / Operator Use and Care Guide I SERIES 224 ICE CUBE MACHINE THE HOTTEST MACHINES ON ICE CORNELIUS INC www.cornelius.com IMPORTANT: TO THE INSTALLER. It is the responsibility of the Installer to ensure

More information

KR Series Air Defrost Unit Coolers Operating and Installation Manual

KR Series Air Defrost Unit Coolers Operating and Installation Manual KR Series Air Defrost Unit Coolers Operating and Installation Manual KR Air Defrost Unit Coolers (PN E108317_L) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT... 2 1.1 INSPECTION... 2 1.2 LOSS OF GAS HOLDING

More information

INSTRUCTIONS! DO NOT DISCARD!

INSTRUCTIONS! DO NOT DISCARD! INSTRUCTIONS! DO NOT DISCARD! CAUTION! Do NOT install where injury might occur due to Moving parts, Sharp corners, Hot surfaces or electrical components dcn0620 Page 1 of 12 INSTALLATION INSTRUCTIONS CAUTION

More information

Field Top Mounted Condensing Unit

Field Top Mounted Condensing Unit Field Top Mounted Condensing Unit INSTALLATION & OPERATIONS MANUAL RF/RF-N, RM/RM-N IMPORTANT Keep in store for future reference! REVISION HISTORY VERSION 1.0 New manual This manual is specific to the

More information

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S Polar Air Dryer R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S PDRCF1150029 PDRCF4602000 Instructions Manual TABLE OF CONTENTS 1. Important safety notes - Please read... 1 1.1. Transportation...

More information

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit January 2008 WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit Installation Operation Maintenance The units are designed for permanent up flow, counter flow, or horizontal left or right airflow

More information

User Manual. Commercial Chest Freezer User s Manual 360CF5, 360CF8, 360CF14, 360CF18

User Manual. Commercial Chest Freezer User s Manual 360CF5, 360CF8, 360CF14, 360CF18 Commercial Chest Freezer User s Manual 360CF5, 360CF8, 360CF14, 360CF18 11/2017 Please read the manual thoroughly prior to equipment set-up, operation and maintenance. - 1 - Installation Important!!! Please

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

High Profile Evaporator

High Profile Evaporator PRODUCT DATA & INSTALLATION Bulletin K30-KHPA-PDI-5 Part # 1081585 PRODUCT SUPPORT web: k-rp.com/khp email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: High Profile Evaporator High & Medium Temperature

More information

RCM Refrigerant Module

RCM Refrigerant Module Small Duct High Velocity Heating, Cooling and Home Comfort Systems RCM Refrigerant Module Installation Manual Manufactured By Module-RCM-Refrigerant-Module-Installation-0666 Refrigerant Modules (RCM) Fig.

More information

Installation & Operations Manual for. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers. 4/17 Rev.

Installation & Operations Manual for. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers. 4/17 Rev. Installation & Operations Manual for BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers 4/17 Rev. D 57-02398 4/17 Rev. D 57-02398 2 TABLE OF CONTENTS INTRODUCTION.. 4

More information

Drop-In Refrigeration System

Drop-In Refrigeration System Drop-In Refrigeration System Original Instructions Installation, Operation and Maintenance Manual This manual is updated as new information and models are released. Visit our website for the latest manual.

More information

EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL CD60 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the CD60 dehumidifier is a rugged, industrial unit which utilizes

More information

EBAC MODEL BD-150 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL BD-150 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL BD-150 (1025000) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL BD-150 OWNERS MANUAL Page 1 of 12 INTRODUCTION Designed for a wide range of applications, the BD-150 dehumidifier is a super high capacity

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

MECHANICAL INTEGRITY INSPECTIONS OF AIR COOLERS

MECHANICAL INTEGRITY INSPECTIONS OF AIR COOLERS By Joe Fazzari, P.E, Vice President of Colmac Coil Manufacturing, Inc. MECHANICAL INTEGRITY INSPECTIONS OF AIR COOLERS Owners should perform periodic mechanical integrity inspections on air coolers to

More information

Installation & Operations Manual for R-290 SERIES. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers 2/

Installation & Operations Manual for R-290 SERIES. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers 2/ Installation & Operations Manual for R-290 SERIES BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers 2/19 57-02650 2/19 57-02650 2 TABLE OF CONTENTS INTRODUCTION.. 4 STORE

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350 Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others

More information

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER Room Air Conditioner Installation and Operation Manual UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER (VOLTS) MIN. MAX. MIN. F ( C) MAX. F ( C) WAC060K7A 127-1-60 114.3 139.7 70(20.1)

More information

GRUNDFOS INSTRUCTIONS. Sololift2 C-3. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Sololift2 C-3. Installation and operating instructions GRUNDFOS INSTRUCTIONS Sololift2 C-3 Installation and operating instructions English (US) English (US) Installation and operating instructions Original installation and operating instructions. CONTENTS

More information

Owner s Manual Refrigerated Compressed Air Dryer Model F-50

Owner s Manual Refrigerated Compressed Air Dryer Model F-50 Owner s Manual Refrigerated Compressed Air Dryer Model F-50 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all

More information

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the MYSTICOOL Max Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

Model No. Serial No. Original Purchaser. Address. City and State Zip. Dealer. Address. City and State Zip. Installation Date Name Signature

Model No. Serial No. Original Purchaser. Address. City and State Zip. Dealer. Address. City and State Zip. Installation Date Name Signature Your Warranty The manufacturer, Lanco, warrants this fan coil to the original purchaser under the following conditions: LIMITED ONE-YEAR WARRANTY 1. Any part thereof which proves to be defective in material

More information

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the XSTREAM Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual Instructions Manual 1. Important safety notes - Please read... 1 1.1. Transportation... 1 1.2 Positioning... 1 1.3 Installation... 1 1.4 Before operating... 1 1.5 Maintenance by an engineer... 1 1.6 Maintenance

More information

SM/SV-Space Master Unit Coolers (E R.0)

SM/SV-Space Master Unit Coolers (E R.0) SM/SV Series Space Master Unit Coolers Operating and Installation Manual SM/SV-Space Master Unit Coolers (E316008 R.0) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT 3 1.1 INSPECTION 3 1.2 LOSS OF GAS HOLDING

More information

EBAC MODEL NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL NEPTUNE OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the Neptune dehumidifier is a super high capacity industrial

More information

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill of lading

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

RPI Industries, Inc.

RPI Industries, Inc. IMPORTANT: THE FOLLOWING INFORMATION SHOULD BE RETAINED FOR FUTURE REFERENCE RPI Industries, Inc. building a better case for sales BAKERY and DELI USE AND SERVICE MANUAL WARRANTY INFORMATION SPECIFICATIONS

More information

INSTRUCTIONS! DO NOT DISCARD!

INSTRUCTIONS! DO NOT DISCARD! INSTRUCTIONS! DO NOT DISCARD! CAUTION! Do NOT install where injury might occur due to Moving parts, Sharp corners, Hot surfaces or electrical components d N0417 Page 1 of 10 INSTALLATION INSTRUCTIONS CAUTION

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers Installation & Operations Manual for BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers 2 TABLE OF CONTENTS INTRODUCTION..... 4 STORE CONDITIONS........ 4 WARNING LABELS AND

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT

More information

UNDERCOUNTER DISHWASHER

UNDERCOUNTER DISHWASHER OWNER S MANUAL BLAKESLEE Division of The Legacy Companies UNDERCOUNTER DISHWASHER UC20 Blakeslee Division of The Legacy Companies 1228 Capitol Drive Addison, IL 60101 Phone (630) 532-5021 Fax (630) 532-5020

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

ROTARY CONTROL AIR CONDITIONER

ROTARY CONTROL AIR CONDITIONER USE & CARE MANUAL NOTE: This USE & CARE MANUAL provides specific operating instructions for your model. Use the room air conditioner only as instructed in this USE & CARE MANUAL. These instructions are

More information

Daikin Direct Expansion (DX) Cooling Coils

Daikin Direct Expansion (DX) Cooling Coils Installation and Maintenance Manual IM 902 Daikin Direct Expansion (DX) Cooling Coils Group: Applied Air Part Number: IM 902 Date: February 2008 Types EN, EF, ER, EJ, EK 2008 Daikin Applied Contents Introduction...

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

Owner s Manual Refrigerated Compressed Air Dryers Model F-100

Owner s Manual Refrigerated Compressed Air Dryers Model F-100 Owner s Manual Refrigerated Compressed Air Dryers Model F-100 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC ISO 9001 Certified Quality Management System SAFETY................................................

More information

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION INSTRUCTIONS...4

More information

ref. com Owner s Manual for models: A Step Above the Standard Thank you for choosing EVEREST

ref. com Owner s Manual for models: A Step Above the Standard Thank you for choosing EVEREST www.everest ref. com Owner s Manual for models: Back Bar Coolers " Deep Back Bar Coolers Glass Door Back Bar Coolers " Deep Galss Door Back Bar Coolers " Deep Galss Sliding Door Back Bar Coolers EBB3,

More information

Installation Instructions

Installation Instructions CNPVP CNRVP Cased N Coils Upflow --- Downflow Heating --- Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

R Series Cooling Manual

R Series Cooling Manual Mini Duct Heating and Air Conditioning Indoor Air Quality Systems R Series Cooling Manual Includes: RPM-E-50 Cooling Module RPM-E-0 Cooling Module RPM-E-00 Cooling Module Manufactured By Energy Saving

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS SPECIALTY REFRIGERATED TRANSPORT CABINETS FOR SATELLITE LOCATIONS RBQ-96 Caution: Read the instructions before using the machine. CONGRATULATIONS......and thank you for purchasing

More information

Portable Dehumidifier

Portable Dehumidifier Portable Dehumidifier OPERATING INSTRUCTIONS HMT-D30-A Model Numbers: HMT-D30-A HMT-D45E-A HMT-D70E-A HMT-D45E-A HMT-D70E-A 3058080 V.161115 PURCHASE INFORMATION Thank you for choosing a Soleus Air Portable

More information

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N T-SERIES Air Conditioner T50 Model INSTRUCTION MANUAL Rev. F P/N 10-1008-203 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1.0 SCOPE: This Operations and Maintenance

More information

Sporlan Valve Division Parker Hannifan/CIC Group

Sporlan Valve Division Parker Hannifan/CIC Group www.parker.com/cic Sporlan Valve Division Parker Hannifan/CIC Group Matt McGrath, SW Regional Sales Manager Bob Dolan, Sales Engineer - Atlanta www.parker.com/cic Why Discuss TEVs Today? Expansion Valves

More information

Ui REFRIGERATOR SPEC SHEET

Ui REFRIGERATOR SPEC SHEET Ui REFRIGERATOR SPEC SHEET ISOMETRIC VIEW 19 7/8 20 1/2 32 3/4 FRONT VIEW NOTES: 1. CUTOUT DIMENSIONS: 20 1/2"W X 33"L X 20 3/4"D 2. CUTOUT DIMENSIONS ARE FOR REFRIGERATOR ONLY. REFER TO STAINLESS STEEL

More information