AIR-CONDITIONER SERVICE MANUAL (MULTI TYPE) R410A PRINTED IN JAPAN, Aug., 2015 ToMo. <High Static Ducted Type> MMD- AP0724H2UL MMD- AP0964H2UL

Size: px
Start display at page:

Download "AIR-CONDITIONER SERVICE MANUAL (MULTI TYPE) R410A PRINTED IN JAPAN, Aug., 2015 ToMo. <High Static Ducted Type> MMD- AP0724H2UL MMD- AP0964H2UL"

Transcription

1 FILE N. A0-506 SERVICE MANUAL AIR-CNDITINER (MULTI TYPE) <High Static Ducted Type> MMD- AP0724H2UL MMD- AP0964H2UL R40A PRINTED IN JAPAN, Aug., 205 ToMo

2 CNTENTS SAFETY CAUTIN SPACIFICATINS CNSTRUCTIN VIEWS (EXTERNAL VIEWS) WIRING DIAGRAM PARTS RATING FAN CHARACTERISTIC REFRIGERATING CYCLE DIAGRAM CNTRL UTLINE APPLIED CNTRL AND FUNCTIN TRUBLESHTING DETACHMENTS P. C. BARD EXCHANGE PRCEDURES EXPLDED VIEWS AND PARTS LIST... 80

3 SAFETY CAUTIN The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them. The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual. [Explanation of indications] Indication DANGER WARNING CAUTIN Explanation Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed. Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed. Indicates contents assumed that an injury or property damage ( ) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed. Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet [Explanation of illustrated marks] Mark Explanation Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents. Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents. Indicates cautions (Including danger/warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents. [Confirmation of warning label on the main ] Confirm that labels are indicated on the specified positions (Refer to the Parts disassembly diagram (utdoor ).) If removing the label during parts replace, stick it as the original. DANGER Turn off breaker. Execute discharge between terminals. Turn FF the breaker before removing the front panel and cabinet, otherwise an electric shock is caused by high voltage resulted in a death or injury. During operation, a high voltage with 400V or higher of circuit ( ) at secondary circuit of the high-voltage transformer is applied. If touching a high voltage with the naked hands or body, an electric shock is caused even if using an electric insulator. :# For details, refer to the electric wiring diagram. When removing the front panel or cabinet, execute short-circuit and discharge between high-voltage capacitor terminals. If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury. After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor. Do not turn on the breaker under condition that the front panel and cabinet are removed. An electric shock is caused by high voltage resulted in a death or injury. Prohibition 3

4 WARNING Check earth wires. Prohibition of modification. Use specified parts. Do not bring a child close to the equipment. Insulating measures No fire Refrigerant Assembly/Cabling Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main, otherwise an electric shock is caused when a leak occurs. If the earth wire is not correctly connected, contact an electric engineer for rework. Do not modify the products. Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury. For spare parts, use those specified ( ). If unspecified parts are used, a fire or electric shock may be caused. : For details, refer to the parts list. Before troubleshooting or repair work, do not bring a third party (a child, etc.) except the repair engineers close to the equipment. It causes an injury with tools or disassembled parts. Please inform the users so that the third party (a child, etc.) does not approach the equipment. Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users side. When repairing the refrigerating cycle, take the following measures. ) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire. 2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused. 3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables. Check the used refrigerant name and use tools and materials of the parts which match with it. For the products which use R40A refrigerant, the refrigerant name is indicated at a position on the outdoor where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22. Do not useany refru\igerant different from the onespecified for complement or replacement. therwise, abnormally high pressuremay be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body. For an air conditioner which uses R40A, never use other refrigerant than R40A. For an air conditioner which uses other refrigerant (R22, etc.), never use R40A. If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused. Do not charge refrigerant additionally. If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount. When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R40A into the specified refrigerant. If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage. After installation work, check the refrigerant gas does not leak. If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous. Never recover the refrigerant into the outdoor. When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor ; otherwise a serious accident such as breakage or injury is caused. After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before. Perform the work so that the cabinet or panel does not catch the inner wires. If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is caused at user s side. 4

5 WARNING Insulator check Ventilation Be attentive to electric shock Compulsion Check after repair After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2MΩ or more between the charge section and the non-charge metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric shock is caused at user s side. When the refrigerant gas leaks during work, execute ventilation. If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation. When checking the circuit inevitably under condition of the power-n, use rubber gloves and others not to touch to the charging section. If touching to the charging section, an electric shock may be caused. When you access inside of the service panel to repair electric parts, wait for about five minutes after turning off the breaker. Do not start repairing immediately. therwise you may get electric shock by touching terminals of high-voltage capacitors. Natural discharge of the capacitor takes about five minutes. When the refrigerant gas leaks, find up the leaked position and repair it surely. If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous. When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks. If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused. For the installation/moving/reinstallation work, follow to the Installation Manual. If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused. After repair work has finished, check there is no trouble. If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker. After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound. If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet. Check after reinstallation Check the following items after reinstallation. ) The earth wire is correctly connected. 2) The power cord is not caught in the product. 3) There is no inclination or unsteadiness and the installation is stable. CAUTIN Put on gloves Cooling check Be sure to put on the gloves ( ) and a long sleeved shirt: otherwise an injury may be caused with the parts, etc. ( ) Heavy gloves such as work gloves When the power was turned on, start to work after the equipment has been sufficiently cooled. As temperature of the compressor pipes and others became high due to cooling/heating operation, a burn may be caused. 5

6 Refrigerant (R40A) This air conditioner adopts HFC type refrigerant (R40A) which does not deplete the ozone layer.. Safety Caution Concerned to Refrigerant (R40A) The pressure of R40A is high.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with refrigerant (R40A) during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R40A to purpose a safe work. 2. Cautions on Installation/Service ) Do not mix the other refrigerant or refrigerating oil. For the tools exclusive to R40A, shapes of all the joints including the service port differ from those of the former refrigerant in order to prevent mixture of them. 2) As the use pressure of the refrigerant (R40A) is high, use material thickness of the pipe and tools which are specified for R40A. 3) In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean pipes. Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.) 4) For the earth protection, use a vacuum pump for air purge. 5) R40A refrigerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner change.) 3. Pipe Materials For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum. ) Copper pipe <Piping> The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type. When using a long copper pipe for R40A, it is recommended to select Copper or copper-base pipe without seam and one with bonded oil amount lbs / 32 0 (40mg / 0m) or less. Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.) <Flare nut> Use the flare nuts which are attached to the air conditioner. 2) Joint The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installation of the air conditioner. However clear impurities when using them. 6

7 4. Tools. Required Tools for R40A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. ) Tools exclusive for R40A (Those which cannot be used for conventional refrigerant (R22)) 2) Tools exclusive for R40A, but can be also used for conventional refrigerant (R22) 3) Tools commonly used for R40A and for conventional refrigerant (R22) The table below shows the tools exclusive for R40A and their interchangeability. Tools exclusive for R40A (The following tools for R40A are required.) Tools whose specifications are changed for R40A and their interchangeability R40A air conditioner installation Conventional air conditioner installation No. Used tool Usage Whether conven- tional equipment can be used Existence of new equipment for R40A Whether conventional equipment can be used Flare tool Pipe flaring Yes *(Note) Yes Copper pipe gauge for adjusting projection margin Flaring by conventional flare tool Yes *(Note) *(Note) Torque wrench Tightening of flare nut Yes No No Gauge manifold Charge hose Evacuating, refrigerant charge, run check, etc. Yes No No Vacuum pump adapter Vacuum evacuating Yes No Yes Electronic balance for refrigerant charging Refrigerant charge Yes Yes Yes Refrigerant cylinder Refrigerant charge Yes No No Leakage detector Gas leakage check Yes No Yes (Note) When flaring is carried out for R40A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary. General tools (Conventional tools can be used.) In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools. ) Vacuum pump. Use vacuum pump by attaching vacuum pump adapter. 7) Screwdriver (+, ) 2) Torque wrench 8) Spanner or Monkey wrench 3) Pipe cutter 9) Hole core drill 4) Reamer 0) Hexagon wrench (pposite side 4mm) 5) Pipe bender ) Tape measure 6) Level vial 2) Metal saw Also prepare the following equipments for other installation method and run check. ) Clamp meter 3) Insulation resistance tester (Megger) 2) Thermometer 4) Electroscope 7

8 Concealed Duct High Static Pressure Type. SPACIFICATINS Model name MMD- AP0724H2UL AP0964H2UL Cooling Capacity kbtu/h Heating Capacity kbtu/h 8 08 Electrical Power supply 230V(208/230V) phase 60Hz charastaristics Power consumption(208v / 230V) kw.37 / /.63 Appearance Zinc hot dipping steel plate Height In 8.5 Unit Width In 54.3 Dimension Depth In 49.2 Height In 24.0 Packing Width In 6.8 Depth In 55.3 Total weight Unit lbs 362 Packed lbs 47 Heat exchanger Finned tube Fan Centrifugal fan Standard air flow cfm Motor output W Fan External static pressure (*) Factory setting (208/230V) In WG / / V(High / Mid / Low) (*3) In WG V(High / Mid / Low) (*3) In WG Air flow limt Lower limit cfm Upper limit cfm Air filter Gas side In Connecting pipe Liquid side In Drain port (Nominal dia.) In Sound puressure level (*2) 208V(High / Mid / Low) (*3) db(a) 230V(High / Mid / Low) (*3) db(a) Field supply 7/8" /2" VP25(Polyvinyl chloride tube: External Dia.-/4 Internal Dia.) 5 / 49 / / 5 / 50 Note (*) Non attached filter (*2) The actual values in an external opeating environment are generally higher than the indicated values due to the contribution from ambient noise. (*3) The tap is set by wire connection change of fan motor. 8

9 2. CNSTRUCTIN VIEWS ³ (EXTERNAL VIEWS) Space required for installation or service work Check port 23.6"(600) Service space Service space Distance from building Check port <Note>. Indoor does not have air filter its inside. So be sure to set an air filter(local arrangements) in the position maintained easily such as a suction grills. (If there is no air filter, dusts are blocked in the air heat exchanger and it may cause failure or water leak in air-conditioner.) 2. Leave sufficient space to remove the air filter when you attach it. Attention Be sure to set the plug and to make it to be able to cleaning, because garbage in drain piping piles up easily in drain trap. Plug (Check and cleaning port) Check panel Hole for hanging bolt (4-Ø/2"(2) 3.6"(92)) Screw hole for duct mounting(7-m5) Screw hole for duct mounting(7-m5) Electric parts box Refrigerant pipe connecting port (Liquid side Ø/2"(2.7) Flared) Air discharge port Ø"(26) Hole for control wire and remote control wiring Ø7/8"(22.2) Hole for power supply cable Drain pipe connecting port(v25) Taper screw for R,"(25.4) pipes Z Air suction port Refrigerant pipe connecting port (Gas side Ø7/8"(22.2) Brazed) Screw hole for duct mounting (6-M5) Screw hole for duct mounting (6-M5) Z view Unit:in(mm) 9

10 3. WIRING DIAGRAM Symbol 43F,F2,F3 CN** F,2,3 F30 FM PMV RC RY002 RY005,006,007 TA TB0,02,03 04,05,06 TC,TC2,TCJ TR Parts Name Fan motor Control Relay Connector Fuse for Fan Motor Fuse Fan Motor Pulse Motor Valve Running Capacitor Drain Control Relay Fan Motor Control Relay Indoor temp sensor Terminal Block Temp sensor Transformer CLR IDENTIFICATIN RED : RED WHI : WHITE YEL : YELLW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK RN : RANGE BRW : BRWN GRN : GREEN RED 43F3 Spark killer 43F Spark killer 43F2 Spark killer WHI RED WHI RED WHI 7 RED WHI TB03 TB03 6 Line Filter BLK RED P30 CN304 GRY CN67 BLK CN66 WHI CN40 BLU F30 T5A 250V 3 CN4 BLU CN309 YEL RY004 CN83 WHI RY007 CN50 WHI MCC CN82 BLU RY006 CN75 WHI RY005 Control P.C. Board for Indoor Unit Power supply circuit M PMV RY CN WHI CN68 BLU RY00 CN7 CN72 3 CN6 YEL CN33 GRN (CHK) (DISP) CN32 WHI CN30 3 RED 2 2 CN04 YEL CN02 RED 2 CN0 BLK CN00 BRW CN80 GRN 2 3 CN73 RED 2 CN70 WHI CN8 BLK CN60 WHI t TA t TCJ t TC2 t PNL EXCT FILTER TC.Broken line indicate the wiring at site. Long dashed short dashed line indicate the accessories. indicates the terminal block. indicates the connection terminal. indicates the connector on the control P.C. board. 2. indicates the protection ground. 3. indicates the control P.C. board. 4. A position is connected to terminal block when change to static pressure. exchange the lead wire of arrow( ) position after check the terminal number as figure and lead wire's color of fan motor. Flow selector Earth screw Indoor Earth screw RED TB0 WHI WHI 8 TB03 RED RED utdoor U U2 A B U U2 A B F 0A F2 0A RED RED RED F3 0A RED BLU BLU BLK BLK 43F2 TB02 Remote controller 5 RN TB03 43F3 43F2 TR CN02 YEL Sub P.C. Board MCC-520 CN0 WHI RN 43F3 T0 Fan motor inside wiring diagram BLK WHI GRY RED FAN DRIVE 49F PTIN Motor over heating protection switch 43F RN BLU RN BRW 43F Power supply 208/ RED RC WHI GRY P RED FAN3 A F F2 YEL BLU RN F3 TB04 F4 RED WHI 2 RC GRY 4P A 34 BLU YEL FAN2 F F2 F3 F4 BLU RN TB05 RED WHI 2 RC GRY 4P 34 WHI FAN A YEL F BLU F2 RN F3 TB06 F4 MS FM3 MS FM2 MS FM 0

11 4. PARTS RATING Model MMD- AP0724H2UL AP0964H2UL Fan motor Running condenser for fan motor Pulse motor Pulse motor valve TA sensor Lead wire TC sensor TC2 sensor TCJ sensor STF AR AC 450 V, 2 μf EDM-MD2TF-3 EDM-BAYGTF- length: 88 mm Ø4 size lead wire length: 2000 mm Vinyl tube (Blue) Ø6 size lead wire length: 2000 mm Vinyl tube (Black) Ø6 size lead wire length: 2000 mm Vinyl tube (Red)

12 5. FAN CHARACTERISTIC MMD-AP0724H2UL Power source: 230 V / 60 Hz Power source: 208 V / 60 Hz tap External static pressure Standard air flow rate tap External static pressure Standard air flow rate (in.wg) (cfm) (in.wg) (cfm) High.22 High Middle Middle Low Low Fan motor current (A) External static pressure (in.wg)e Air flow rate (cfm) Air flow rate lower limit Air flow rate lower limit Since external static pressure value is big, it cannot be applied. High tap Middle tap Low tap High tap Middle tap Low tap Air flow rate upper limit Air flow rate upper limit Fan motor current (A) External static pressure (in.wg)e Air flow rate (cfm) Air flow rate lower limit Air flow rate lower limit High tap Middle tap Low tap High tap Middle tap Low tap Air flow rate upper limit Air flow rate upper limit Air flow rate (cfm) Air flow rate (cfm) 2

13 MMD-AP0964H2UL Power source: 230 V / 60 Hz Power source: 208 V / 60 Hz tap External static pressure Standard air flow rate tap External static pressure (in.wg) (cfm) (in.wg) Standard air flow rate (cfm) High.099 High Middle Middle Low Low Fan motor current (A) External static pressure (in.wg)e Air flow rate (cfm) Air flow rate lower limit Air flow rate lower limit High tap Middle tap Low tap High tap Middle tap Low tap Air flow rate upper limit Air flow rate upper limit Fan motor current (A) External static pressure (in.wg)e Air flow rate (cfm) Air flow rate lower limit Air flow rate lower limit High tap Middle tap Low tap High tap Middle tap Low tap Air flow rate upper limit Air flow rate upper limit Air flow rate (cfm) Air flow rate (cfm) 3

14 Wire connection change of fan motor This duct is composed of 3 fan motors. To change external static pressure by duct resistance, connect the 3 connectors of the orange lead wires that are connected to the underside of the fan tap changing terminal block to the same number (F, F2 or F3) terminal. The wires of the fan motor has been connected to (F2) [External static pressure 4 mmaq (37 Pa)] as factory default. Low static pressure (F) FM FM FM YEL: Yellow BLU: Blue RG: range Fan motor Fan motor Fan motor YEL BLU RG YEL BLU RG YEL BLU RG F F2 F3 F4 F F2 F3 F4 F F2 F3 F4 RG FAN3 RG FAN2 RG FAN Standard (Middle) static pressure (F2) Fan tap changing terminal block Electrical control box Fan motor Fan motor Fan motor YEL BLU RG YEL BLU RG YEL BLU RG Control P.C. board 4P terminal block RG RG RG FAN3 FAN2 FAN 2P terminal block 3P terminal block High static pressure (F3) Fan motor Fan motor Fan motor YEL BLU RG YEL BLU RG YEL BLU RG RG FAN3 FAN2 FAN RG RG * Do not use F4. NTE Model name Voltage / Frequency Fan motor wiring Model name Voltage / Frequency Fan motor wiring Terminal block No. Wire color 230 V / 50 Hz External static pressure (in.wg) MMD-AP0724H2UL Wire color 208 V / 60 Hz External static pressure (in.wg) F Yellow Yellow F2 Blue Blue F3 range.22 range Terminal block No. Wire color 230 V / 50 Hz External static pressure (in.wg) MMD-AP0964H2UL Wire color 208 V / 60 Hz External static pressure (in.wg) F Yellow Yellow F2 Blue Blue 0.37 F3 range.099 range When the external static pressure is changed, write down the static pressure once change in the wiring diagram of the indoor is made. 4

15 6. REFRIGERATING CYCLE DIAGRAM Liquid side Gas side Strainer Capillary tube Air heat exchanger at indoor side Pulse Motor Valve (PMV) Sensor (TC2) Strainer Sensor (TCJ) Fan Sensor (TC) Sensor (TA) M Fan motor Functional part name Functional outline Pulse Motor Valve Temp. sensor PMV. TA 2. TC 3. TC2 4. TCJ (Connector CN082 (6P): Blue) ) Controls super heat in cooling operation 2) Controls under cool in heating operation 3) Recovers refrigerant oil in cooling operation 4) Recovers refrigerant oil in heating operation (Connector CN04 (2P): Yellow) ) Detects indoor suction temperature (Connector CN00 (3P): Brown) ) Controls PMV super heat in cooling operation (Connector CN0 (2P): Black) ) Controls PMV under cool in heating operation (Connector CN02 (2P): Red) ) Controls PMV super heat in cooling operation 5

16 7. CNTRL UTLINE No. Item utline of specifications Remarks When power supply is reset ) Distinction of outdoor When the power supply is reset, the outdoors are distinguished and the control is selected according to the distinguished result. 2) Setting of indoor fan speed and existence of air direction adjustment Based on EEPRM data, select setting of the indoor fan speed and the existence of air direction adjustment. 3) If resetting the power supply during occurrence of a trouble, the check code is once cleared. After N/FF button of the remote controller was pushed and the operation was resumed, if the abnormal status continues, the check code is again displayed on the remote controller. Air speed (rpm)/ Air direction adjustment 2 peration mode selection ) Based on the operation mode selecting command from the remote controller, the operation mode is selected. Remote controller command STP FAN DRY CL HEAT Control outline Air conditioner stops. Fan operation Drying operation Cooling operation Heating operation 3 Room temp. control ) Adjustment range: Remote controller setup temperature ( F [ C] ) CL/DRY HEAT Wired type 64 F [8 C] to 84 F [29 C] 64 F [8 C] to 84 C [29 C] Wireless type 64 F [8 C] to 86 F [30 C] 6 F [6 C] to 86 F [30 C] 2) Using the Item code 06, the setup temperature in heating operation can be corrected. Setup data Setup temp. Correction Setting at shipment F +3.6 F +7.2 F +0.8 F [+0 C] [+2 C] [+4 C] [+6 C] Shift of suction temperature in heating operation Except while sensor of the remote controller is controlled (Code No. [32], 000 ) Setup data 2 6

17 No. Item utline of specifications Remarks 4 Automatic capacity control ) Based on the difference between Ta and Ts, the operation capacity is determined by the outdoor. Ta F ( C) +3.6 (+2) CL SD Ta F ( C) +.8 (+) +.8 (+) SB S9 Ts Ts S7 S5.8 ( ).8 ( ) S3 S0 3.6 ( 2) HEAT S3 S0 S5 S7 S9 SB SD SF Ts: Setup temp. Ta: Room temp. 5 Air speed selection ) peration with (HH), (H), (L) or [AUT] mode is carried out by the command from the remote controller. 2) When the air speed mode [AUT] is selected, the air speed varies by the difference between Ta and Ts. HH > H+ > H > L+ > L > UL <CL> Ta F ( C) +5.4 (+3.0) +4.5 (+2.5) +3.6 (+2.0) +2.7 (+.5) +.8 (+.0) +0.9 (+0.5) Tsc 0.9 ( 0.5) HH <HH> H+ <HH> H <HH> L+ <H+> L <H> L <H> L <L+> A B C D E F G < > : Indicate automatic cooling. Controlling operation in case when thermo of remote controller works is same as a case when thermo of the body works. If the air speed has been changed once, it is not changed for 3 minutes. However when the air volume is exchanged, the air speed changes. When cooling operation has started, select a downward slope for the air speed, that is, the high position. If the temperature is just on the difference boundary, the air speed does not change. Code No : Body thermo. (Main ) 000: Remote controller thermo. 7

18 No. Item utline of specifications Remarks 5 Air speed selection (Continued) <HEAT> Ta F ( C) ( 0.9).8 [( 0.5).0] (0) Tsh (+0.9) +.8 [(+0.5) +.0] (+.8) +3.6 [(+.0) +2.0] (+2.7) +5.4 [(+.5) +3.0] (+3.6) +7.2 [(+2.0) +4.0] L <L+> L+ <H> H <H+> H+ <HH> HH <HH> E D C B A < > : Indicate automatic heating. Body thermostat works. Remote controller thermostat works. Value in the parentheses indicates one when thermostat of the remote controller works. Value without parentheses indicates one when thermostat of the body works. If the air speed has been changed once, it is not changed for minute. However when the air speed exchanged, the air speed changes. When heating operation has started, select an upward slope for the air speed, that is, the high position. If the temperature is just on the difference boundary, the air speed does not change. In TC2 40 F[60 C], the air speed increases by step. TC2: Indoor heat exchanger sensor temperature 6 Prevention of cold air discharge. In heating operation, the higher temperature of TC2 sensor and TCJ sensor is compared with temperature of TC sensor and then the lower temperature is used to set the upper limit of the fan tap. When B zone has continued for 6 minutes, the operation shifts to C zone. In defrost time, the control point is set to +0.8 F[6 C]. TCJ:Temperature of indoor heat exchanger sensor In D and E zones, priority is given to remote controller air speed setup. In A zone is displayed. F ( C) 90 (32) 86 (30) 82 (28) 79 (26) 68 (20) 6 (6) D C E B A A zone: FF B zone: ver 79 F (26 C), below 82 F (28 C), ULTRA LW (LL) C zone: ver 82 F (28 C), below 86 F (30 C), LW (L) D zone: ver 86 F (30 C), below 90 F (32 C), MED (H) E zone: HIGH (HH) 8

19 No. Item utline of specifications Remarks 7 Freeze prevention control (Low temp. release). In all cooling operation, the air conditioner operates as de-scribed below based upon temp. detected by TC, TC2 and TCJ sensors. When J zone is detected for 5 minutes, the thermostat is forcedly off. In K zone, the timer count is interrupted, and held. When I zone is detected, the timer is cleared and the operation returns to the normal operation. If J zone continues, operation of the indoor fan in LW mode continues until it reaches the I zone. It is reset when the following conditions are satisfied. Reset conditions ) TC > 54 F [2 C] and TC2 > 54 F [2 C] and TCJ > 54 F [2 C]. 2) 20 minutes passed after stop. TC: Temperature of indoor heat exchanger sensor F ( C) P Q J K a P Q TC 50 C [0 C] 4 C [5 C] 32 F [0 C] TC2, TCJ 4 C [ 0 C] 7 F [ 4 C] ( ) value: When the power supply is turned on, the forced thermo FF if the temperature is less than this indicated temperature. 2. In all cooling operation, the air conditioner operates as described below based upon temp. detected by TC2 and TCJ sensors. When M zone is detected for 30 minutes, the thermostat is forcedly off. In N zone, the timer count is interrupted and held. When shifting to M zone again, the timer count restarts and continues. If L zone is detected, the timer is cleared and the operation returns to normal operation. Reset conditions ) TC > 54 F [2 C] and TC2 > 54 F [2 C] and TCJ > 54 F [2 C]. 2) 20 minutes passed after stop. F ( C) P2 Q2 L N M P2 Q2 TC2, TCJ 4 F [5 C] 28 F [ 2.0 C] In a Model without TC2, TC2 is not judged. 8 Recovery control for cooling oil (Refrigerant) The indoor which is under STP/Thermo-FF status or which operates in [FAN] mode performs the following controls when it received the cooling oil (Refrigerant) recovery signal from the outdoor. ) pens PMV of the indoor with a constant opening degree. 2) perates the drain pump for approx. minute during recovery control and after finish of control. Recovery operation is usually performed every 2 hours 5 minuts. 9

20 No. Item utline of specifications Remarks 9 Recovery control for heating refrigerant (il) The indoor which is under STP/Thermo-FF status or which operates in [FAN] mode performs the following controls when it received the heating refrigerant (il) recovery signal from the outdoor. ) pens PMV of the indoor with a constant opening degree. 2) Detects temperature of TC2 and then closes PMV. The indoor which is under thermo-ff (CL) status or which operates in [FAN] mode stops the indoor fan and displays [READY ]. Recovery operation is usually performed every hour. (When there is even indoor which the thermo is off) 0 Compensation control for short intermittent operation ) For 3 minutes after start of operation, the operation is forcedly continued even if the enters in Thermo-FF condition. 2) However the thermostat is FF giving prior to CL/HEAT selection, READY for operation and protective control. Usually the priority is given to 5 minutes at outdoor controller side. Display of filter sign [ ] Separately set type TCB-AX2UL is prepared. ) The filter sign is displayed with LC by sending the filter-reset signal to the remote controller when the specified time (2500H) elapsed as a result of integration of the operation time of the indoor fan. 2) The integrated timer is cleared when the filter-reset signal is received from the remote controller. In this time, if the specified time elapsed, the counted time is reset and the LC display is deleted. [ FILTER] goes on. Filter time 2500H 20

21 No. Item utline of specifications Remarks 2 Display of [READY] [HEAT READY] < READY> Displayed on the remote controller ) When the following check codes are indicated pen phase of power supply wiring [P05] was detected. There is an indoor that detected the indoor overflow [P0]. There is an indoor that detected the interlock alarm [L30]. 2) During Force Thermo-FF [CL/DRY] operation is unavailable because the other indoor operates with [HEAT] mode. [HEAT] operation is unavailable because CL priority (SW-bit of the utdoor P. C. board is N) is set and the other indoor operates with [CL/DRY] mode. 3) The above indoor s that cannot operate stay in Thermo-FF status. 4) The indoor fan stops because the system performs [Recovery operation for heating refrigerant (il)]. <READY > display No display for wireless type remote controller <HEAT READY> Displayed on the remote controller. Normal thermo. FF During heating, the indoor goes thermo FF as the heating temperature setting is reached. 2. During heating, the fan rotates at a breeze speed (UL or lower) or remains stationary to prevent cold air from being discharged (including defrosting operation). 3. Forced thermo FF HEAT operation is unavailable because at least one indoor is operating in CL/DRY mode under priority cooling setting (bit of SW on outdoor P.C. board N). <HEAT READY > display 3 Selection of central control mode ) Selection of the contents that can be operated by the remote controller at the indoor side is possible according to setting at the central controller side. 2) Setting contents In case of TCC-LINK central control peration from TCC-LINK central control Individual [Central ] [Central 2] [Central 3] [Central 4] peration on RBC-AMT32UL N/FF peration Timer Temp. Air speed Air direction setting selection setting setting setting setting n RBC-AMT32UL [Central control] display ( : peration possible : peration impossible) 2

22 No. Item utline of specifications Remarks 4 Save operation ) The save operation starts when remotecontroller is turned on. SAVE button on the 2) While the save operation is performed, segment goes on the screen of the wired remote controller. 3) The request capacity ratio is restricted to approx. 75% during save operation. 4) If the save operation was validated, the contents are held during the operation stop, the operation mode change and the resetting of power supply. Therefore the operation at the next time also will be activated with Save operation is valid. 22

23 8-. Indoor Controller Block Diagram 8. APPLIED CNTRL AND FUNCTIN 8--. When Main (Simple) Wired Remote Controller Connected Indoor # PMV Indoor fan motor Main (Simple) wired remote controller (up to 2 s) Display LCD Display LED EEPRM CPU Function setting Key switch Remote controller communication circuit DC5V Power supply circuit A B #2 A B #3 A B Indoor control P. C. board (MCC-403) DC20V DC2V Remote controller communication circuit EEPRM DC5V TA sensor Power supply circuit CPU H8/3039 TC sensor TC2 sensor TCJ sensor Sameas left Sameas left Driver HA Fan motor relay circuit External output In operation Alarm Getting ready Thermostat N CL HEAT FAN AC synchronization signal input circuit BUS communication circuit U U2 U U2 L L2 L L2 Transformer L L2 Power source 208/ U U2 Indoor/outdoor communication U U2 utdoor Power source utdoor Power source utdoor Up to 8 s can be connected. 23

24 8--2. When Wireless Remote Controller Kit Connected Indoor # PMV Indoor fan motor A B #2 A B #3 A B Wireless remote controller kit Indoor control P.C. board (MCC-403) DC20V DC2V Remote controller communication circuit EEPRM Remote controller communication circuit Sensor P. C. board DC5V TA sensor Sensor circuit Display section Power supply circuit CPU H8/3039 TC sensor TC2 sensor TCJ sensor Sameas left Sameas left Driver Fan motor control circuit External output In operation Alarm Getting ready Thermostat N CL HEAT FAN AC synchronization signal input circuit BUS communication circuit HA L U U2 U U2 L2 L L2 Transformer L Power source 208/ L2 U U2 Indoor/outdoor communication U U2 utdoor Power source utdoor Power source utdoor Up to 8 s can be connected. 24

25 8--3. When Both Wired (Simple) Remote Controller and Wireless Remote Controller Kit Connected Indoor # PMV Indoor fan motor Main (Simple) wired remote controller (up to 2 s) Display LCD Display LED EEPRM CPU Function setting Key switch Remote controller communication circuit DC5V Power supply circuit A B #2 A B #3 A B Wireless remote controller kit Indoor control P.C. board (MCC-403) DC20V DC2V Remote controller communication circuit EEPRM Remote controller communication circuit DC5V TA sensor Sensor circuit Display section Power supply circuit CPU H8/3039 TC sensor TC2 sensor TCJ sensor Sameas left Sameas left Driver Fan motor control circuit External output In operation Alarm Getting ready Thermostat N CL HEAT FAN AC synchronization signal input circuit BUS communication circuit HA L U U2 U U2 L2 L L2 Transformer L Power source 208/ L2 U U2 Indoor/outdoor communication U U2 utdoor Power source utdoor Power source utdoor Up to 8 s can be connected. 25

26 8--4. Indoor Printed Circuit Board MCC-403 Power supply transformer (Primary side) /CN074 ptional power supply /CN309 Power supply /CN067 AC fan output /CN083 Power supply transformer (Secondary side) (ACV, 4V, 20V) /CN075 Microcomputer operation LED /D002 PMV output /CN082, DC2V EXCT /CN073, DC5V TA sensor /CN04 External input /CN080 TCJ sensor /CN02 TC2 sensor /CN0 TC sensor /CN00 Also used for communication of the central control system /CN040 Remote controller power supply LED /D203 HA (T0) /CN06, DC2V ptional output /CN060, DC2V Remote controller /CN4 DISP /CN72, DC5V CHK /CN07, DC5V 26

27 8--5. P.C. Board ptional Switch/Connector Specifications Function Connector No. Pin No. Specification Remarks Fan output HA ptional output External input CHK peration check DISP Display mode EXCT Demand CN32 CN6 CN60 CN80 CN7 CN72 CN73 DC2 V Factory default setting: N when indoor in operation and FF when indoor at rest utput 2 * Fan can be operated on its own by pressing FAN button on remote controller (DN = 3) Start / stop inpu Start / stop input for HA (J0: In place / Removed = Pulse input (factory default) / Step input) 2 0 V (CM) 3 Remote controller disabling inpu Enables / disables start / stop control via remote controller 4 In-operation output N during operation (HA answerback signal) 5 DC2 V (CM) 6 Alarm output N while alarm N DC2 V (CM) 2 Defrosting output N while outdoor defrosted 3 Thermostat N output N while real thermostat N (compressor N) Cooling output Heating output Fan output N while air conditioner in cooling or related operation (CL, DRY or cooling under AUT mode) N while air conditioner in heating operation (HEAT or heating under AUT mode) N while indoor fan N (air cleaner in use or via interlock wiring) DC2 V (CM) Generates test code L30 and automatically shuts down 2 DC2 V (CM) air conditioner (only if condition persists for minute) 3 External input Check mode input Used for indoor operation check (prescribed operational status output, such as indoor fan "H" or drain pump N, 0 V 2 to be generated without communication with outdoor or remote controller) Display mode input Product display mode - Communication just between 2 0 V indoor and remote controller enabled (upon turning on of power) Timer short-circuited out (always) Demand input Imposes thermostat FF on indoor 2 0 V 27

28 8-2. Functions at test run Cooling/Heating test run check The test run for cooling/heating can be performed from either indoor remote controller or outdoor interface P.C. board.. Start/Finish operation of test run Test run from indoor remote controller Wired remote controller: Refer to the below item of Test run of the wired remote controller. Wireless remote controller: Refer to the next page item of Test run of the wireless remote controller. In case of wired remote controller <RBC-AMT32UL> TEMP. TIMER SET TIME FAN SAVE N / FF MDE VENT 2, 4 3, 5 FILTER RESET TEST SET CL SWING/FIX UNIT LUVER Procedure peration contents Push [TEST] button for 4 seconds or more. [TEST] is displayed at the display part and the mode enters in TEST mode. TEST Push [N/FF] button. Change the mode from [CL] to [HEAT] using [MDE] button. Do not use [MDE] button for other mode except [CL]/[HEAT] modes. The temperature cannot be adjusted during test run. The detection is performed as usual. After test run, push [N/FF] button to stop the operation. (Display on the display part is same to that in Procedure.) TEST 5 Push [TEST] button to clear the TEST mode. ([TEST] display in the display part disappears and status becomes the normal stop status.) Note) The test run returns to the normal operation after 60 minutes. 28

29 <In case of wireless remote controller (TCB-AX2UL)> Procedure 2 Turn on power of the air conditioner. Description The operation is not accepted for 5 minutes when power has been turned on at first time after installation, and minute when power has been turned on at the next time and after. After the specified time has passed, perform a test operation. Push [Start/Stop] button and change the operation mode to [CL] or [HEAT] with [Mode] button. Then change the fan speed to [High] using [Fan] button. Test cooling operation Test heating operation Set temperature to [64 F (8 C)] using [Temperature set] button. After checking the receiving sound Pi, immediately push [Temperature set] button to set to [66 F (9 C)] After checking the receiving sound Pi, immediately push [Temperature set] button to set to [64 F (8 C)]. Set temperature to [86 F (30 C)] using [Temperature set] button. After checking the receiving sound Pi, immediately push [Temperature set] button to set to [84 F (29 C)]. After checking the receiving sound Pi, immediately push [Temperature set] button to set to [86 F (30 C)]. 6 7 Then repeat the procedure After approx. 0 seconds, all the display lamps on the sensor part of wireless remote controller, [peration] (Green), [Timer] (Green), and [Ready] (Yellow) flash and the air conditioner starts operation. If the lamps do not flash, repeat the procedure 2 and after. After the test operation, push [Start/Stop] button to stop the operation. Be sure to set the air speed to [High] 2 3, 4, 5, 6 2, 7 29

30 Check function for operation of indoor (Functions at indoor side) This function is provided to check the operation of the indoor singly without communication with the remote controller or the outdoor. This function can be used regardless of operation or stop of the system. However, if using this function for a long time, a trouble of the equipment may be caused. Limit using this function within several minutes. [How to operate] ) Short-circuit CHK pin (CN7 on the indoor P.C. board). The operation mode differs according to the indoor status in that time. Normal time: Both float SW and fan motor are normal. Abnormal time: Either one of float SW or fan motor is abnormal. 2) Restricted to the normal time, if short-circuiting DISP pin (CN72 on the indoor P.C. board) in addition to short-circuit of CHK pin (CN7 on the indoor P.C. board), the minimum opening degree (30pls) can be set to the indoor PMV only. When open DISP pin, the maximum opening degree (500pls) can be obtained again. [How to clear] pen CHK pin. While the system is operating, it stops once but automatically returns to operation after several minutes. Short-circuit of CHK pin(cn7) DISP pin open(cn7) Normal time DISP pin short circuit(cn7) Abnormal time Fan motor Indoor PMV ( ) Drain pump Communication P.C. board LED (H) (H) Stop Max. opening degree (500pls) Min. opening degree (30pls) Min. opening degree (30pls) N N N All ignored All ignored All ignored Lights Lights Flashes 30

31 8-3. Method to Set Indoor Unit Function DN Code (When performing this task, be sure to use a wired remote controller.) <Procedure> To be performed only when system at rest Push the + SET + CL buttons simultaneously and hold for at least 4 seconds. The No. displayed first is the address of the header indoor in group control. Then the fan and louver of the selected indoor move. 2 Each time the Select side of the UNIT LUVER button is pushed, one of the indoor Nos. under group control is displayed in turn. Then the fan of the selected indoor move. 3 Use the TEMP. button to select the CDE No. (DN code) of the desired function. 4 Use the button to select the desired SET DATA associated with the selected function. 5 Push the SET button. (The display changes from flashing to steady.) To change the selected indoor, go back to step 2. To change the selected function, go back to step 3. 6 When the SET button is pushed, the system returns to normal off state. 3 CDE No. SET DATA SETTING TEST UNIT No R.C. No. TEMP. FILTER RESET TEST TIMER SET SET TIME CL FAN SAVE SWING/FIX N / FF MDE VENT UNIT LUVER 3

32 Function CDE No. (DN Code) Table (Includes All Functions Needed to Perform Applied Control on Site) DN Item Descrip tion At sh ipment Filter display delay timer 0000: None 000: 50H According to type : 2500H 0004: 0000H 0003: 5000H 02 Dirty state of filter 0000: Standard 0000: Standard 000: High degree of dirt (Half of standard time) 03 Central control address 000: No. to 0064: No : Unfixed 0099: Unfixed 04 Specific indoor 0000: No priority 000: Priority 0000: No priority priority Heating temp shift 0000: No shift 000: + C(+.8 F) 0002: +2 C(+3.6 F) : +2 C(+3.6 F) to 000: +0 C(+8 F) (Up to +6 recommended) (Floor type 0000: 0 C) 0d Existence of [AUT] 0000: Provided 000: Not provided mode 000: Not provided (Automatic selection from connected outdoor ) 0F Cooling only 0000: Heat pump 0000: Heat pump 000: Cooling only (No display of [AUT] [HEAT]) 0006: High static Ducted Type 0 Type According to model type Indoor capacity 0000: Unfixed 000 to 0034 According to capacity type 2 Line address 000: No. to 0030: No : Unfixed 3 Indoor address 000: No. to 0064: No : Unfixed 4 Group address 0000: Individual 000: Header of group 0099: Unfixed 0002: Follower of group 28 2A 2E Automatic restart of power failure Selection of option/ input (CN23) HA terminal (CN6) select 0000: None 000: Restart 000: Restart 0000: Filter input 0002: External interlock 0000: Usual 0002: Fire alarm input 000: Alarm input (ption parts) 0002: External interlock 000: Leaving-N prevention control 0000: Usual (HA terminal) 3 Ventilating fan control 0000: Unavailable 000: Available 0000: Unavailable 32 TA sensor selection 0000: Body TA sensor 000: Remote controller sensor 0000: Body TA sensor 33 Temperature select 0000: C 000: F : (at factory shipment) 000: : F 60 Timer setting 0000: Available (can be performed) 0000: Available (wired remote controller) 000: Unavailable (cannot be performed) 92 utside interlock release condition 0000: peration stop 000: Release com munica tion signal receive 0000: peration stop Type DN code 0 Value Type Model 0006 High static Ducted MMD-AP *** H2UL * Default value stored in EEPRM mounted on service P.C. board Indoor Unit Capacity DN code Value 0000* Capacity Invalid * Default value stored in EEPRM mounted on service P.C. board type type ~ 32

33 8-4. Applied Control in Indoor Unit Remote location N/FF control box (TCB-IFCB-4UL) [Wiring and setup] Use the exclusive connector for connection with the indoor control P.C. board. In a group control, the system can operate when connecting with any indoor (Control P.C. board) in the group. However when taking out the operation/ signal from the other, it is necessary to take out from each individually.. Control items ) Start/Stop input signal : peration start/stop in 2) peration signal : utput during normal operation 3) Error signal : utput during alarm (Serial communication or indoor/outdoor protective device) operation 2. Wiring diagram using remote control interface (TCB-IFCB-4UL) Input IFCB-4UL : No voltage N/FF serial signal utput No voltage contact for operation, display Contact capacity: Below Max. AC240V 0.5A Indoor control P.C. board Remote location N/FF control box (TCB-IFCB-4UL) Start/Stop input CM (GND) 2 Remote controller prohibition/clear input 3 peration signal output 4 CM (+2V) 5 Error signal output 6 CN6 T0 (YEL) CN CN3 N/FF serial signal input CM peration signal output Error signal output Power supply 208/

AIR-CONDITIONER SERVICE MANUAL (MULTI TYPE) R410A PRINTED IN JAPAN, Mar., 2012 ToMo

AIR-CONDITIONER SERVICE MANUAL (MULTI TYPE) R410A PRINTED IN JAPAN, Mar., 2012 ToMo FILE NO. A11-020 SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) MMD- AP0074SPH2UL MMD- AP0094SPH2UL MMD- AP0124SPH2UL MMD- AP0154SPH2UL MMD- AP0184SPH2UL MMD-

More information

AIR-CONDITIONER SERVICE MANUAL (MULTI TYPE) R410A

AIR-CONDITIONER SERVICE MANUAL (MULTI TYPE) R410A FILE NO. A-0 Revision : Jun., 207 SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) Medium Static Ducted Type MMD- AP0074BH2UL MMD- AP0094BH2UL MMD- AP024BH2UL MMD- AP054BH2UL MMD- AP084BH2UL MMD- AP024BH2UL

More information

AIR-CONDITIONER SERVICE MANUAL SPLIT TYPE R410A OUTDOOR UNIT

AIR-CONDITIONER SERVICE MANUAL SPLIT TYPE R410A OUTDOOR UNIT FILE. A09-004 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE OUTDOOR UNIT RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT8Z-E RAV-SM2804AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT8ZG-E RAV-SM2244AT7

More information

SERVICE MANUAL MMU-AP0092H, MMU-AP0122H, MMU-AP0152H, MMU-AP0182H, MMU-AP0242H, MMU-AP0272H, MMU-AP0302H, MMU-AP0362H, MMU-AP0482H, MMU-AP0562H,

SERVICE MANUAL MMU-AP0092H, MMU-AP0122H, MMU-AP0152H, MMU-AP0182H, MMU-AP0242H, MMU-AP0272H, MMU-AP0302H, MMU-AP0362H, MMU-AP0482H, MMU-AP0562H, FILE NO. A08-004 SERVICE MANUAL MMU-AP0092H, MMU-AP022H, MMU-AP052H, MMU-AP082H, MMU-AP0242H, MMU-AP0272H, MMU-AP0302H, MMU-AP0362H, MMU-AP0482H, MMU-AP0562H, This Service

More information

FRESH AIR INTAKE INDOOR UNIT for S-MMS

FRESH AIR INTAKE INDOOR UNIT for S-MMS FILE NO. A06-016 SERVICE MANUAL FRESH AIR INTAKE INDOOR UNIT for S-MMS INDOOR UNIT MMD-AP0481HFE MMD-AP0721HFE MMD-AP0961HFE OUTDOOR UNIT For Service Manual of S-MMS and outdoor unit, refer to the Service

More information

SERVICE MANUAL MMU-AP0071MH MMU-AP0091MH MMU-AP0121MH MMU-AP0151MH MMU-AP0181MH. <Compact 4-Way Air Discharge Cassette Type> FILE NO.

SERVICE MANUAL MMU-AP0071MH MMU-AP0091MH MMU-AP0121MH MMU-AP0151MH MMU-AP0181MH. <Compact 4-Way Air Discharge Cassette Type> FILE NO. FILE. A06-002 SERVICE MANUAL MMU-AP007MH MMU-AP009MH MMU-AP02MH MMU-AP05MH MMU-AP08MH This Service Manual describes contents of the Compact 4-Way Air Discharge

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE. A07-003 Revised:Mar., 2008 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE INDOOR UNIT RAV-SM564UT-E RAV-SM804UT-E RAV-SM04UT-E RAV-SM404UT-E OUTDOOR UNIT RAV-SP404AT-E

More information

INDOOR UNIT <DIGITAL INVERTER>

INDOOR UNIT <DIGITAL INVERTER> FILE. SVM-13088-3 SERVICE MANUAL SPLIT TYPE INDOOR UNIT Concealed Duct Type RAV-SM406BTP-E RAV-SM406BTP-TR RAV-SM456BTP-E RAV-SM456BTP-TR RAV-SM566BTP-E RAV-SM566BTP-TR RAV-SM806BTP-E

More information

AIR-CONDITIONER SERVICE MANUAL (MULTI TYPE) RAV-SP181BT-UL RAV-SP241BT-UL RAV-SP301BT-UL RAV-SP361BT-UL RAV-SP421BT-UL

AIR-CONDITIONER SERVICE MANUAL (MULTI TYPE) RAV-SP181BT-UL RAV-SP241BT-UL RAV-SP301BT-UL RAV-SP361BT-UL RAV-SP421BT-UL FILE No. A0-606 SERVICE MANUAL AIR-CONDITIONER INDOOR UNIT Concealed Duct Type RAV-SP8BT-UL RAV-SP4BT-UL RAV-SP30BT-UL RAV-SP36BT-UL RAV-SP4BT-UL (MULTI TYPE) R40A PRINTED IN JAPAN,

More information

SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE)

SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) -1 SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) INDOOR UNIT MMC-AP0157HP-E (TR) MMC-AP0187HP-E (TR) MMC-AP0247HP-E (TR) MMC-AP0277HP-E (TR) MMC-AP0367HP-E (TR) MMC-AP0487HP-E (TR) MMC-AP0567HP-E

More information

MMK-AP0072H MMK-AP0092H MMK-AP0122H

MMK-AP0072H MMK-AP0092H MMK-AP0122H FILE. SVM-05052 SERVICE MANUAL MMK-AP0072H MMK-AP0092H MMK-AP0122H This Service Manual describes contents of the new High Wall indoor unit. For the outdoor unit, refer to the Manual with

More information

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) RAV-SM567CTP-E (TR) RAV-SM807CTP-E (TR) RAV-SM1107CTP-E (TR) RAV-SM1407CTP-E (TR) RAV-SM1607CTP-E (TR)

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) RAV-SM567CTP-E (TR) RAV-SM807CTP-E (TR) RAV-SM1107CTP-E (TR) RAV-SM1407CTP-E (TR) RAV-SM1607CTP-E (TR) -6 SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) INDOOR UNIT RAV-SM567CTP-E (TR) RAV-SM807CTP-E (TR) RAV-SM1107CTP-E (TR) RAV-SM1407CTP-E (TR) RAV-SM1607CTP-E (TR) Revised on Mar. 2014 Original

More information

AIR CONDITIONER (MULTI TYPE) SERVICE MANUAL

AIR CONDITIONER (MULTI TYPE) SERVICE MANUAL FILE No. A10-033 AIR CONDITIONER (MULTI TYPE) SERVICE MANUAL This service manual provides relevant explanations about new indoor unit (4 series). Please refer to the following service manuals for each

More information

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) RAV-SM564UTP-E (TR) RAV-SM804UTP-E (TR) RAV-SM1104UTP-E (TR) RAV-SM1404UTP-E (TR) RAV-SM1604UTP-E (TR)

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) RAV-SM564UTP-E (TR) RAV-SM804UTP-E (TR) RAV-SM1104UTP-E (TR) RAV-SM1404UTP-E (TR) RAV-SM1604UTP-E (TR) -5 SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) INDOOR UNIT RAV-SM564UTP-E (TR) RAV-SM804UTP-E (TR) RAV-SM1104UTP-E (TR) RAV-SM1404UTP-E (TR) RAV-SM1604UTP-E (TR) Revised on Apr. 2014

More information

SERVICE MANUAL. <High Wall Types> MMK-AP0074MH-E MMK-AP0094MH-E MMK-AP0124MH-E MMK-AP0074MH-TR MMK-AP0094MH-TR MMK-AP0124MH-TR

SERVICE MANUAL. <High Wall Types> MMK-AP0074MH-E MMK-AP0094MH-E MMK-AP0124MH-E MMK-AP0074MH-TR MMK-AP0094MH-TR MMK-AP0124MH-TR FILE NO. A0-034- SERVICE MANUAL MULT TYPE MMK-AP0074MH-E MMK-AP0094MH-E MMK-AP04MH-E MMK-AP0074MH-TR MMK-AP0094MH-TR MMK-AP04MH-TR This Service Manual describes contents of the new High

More information

RAV-SP180AT2-UL (2 HP) RAV-SP240AT2-UL (3 HP) RAV-SP300AT2-UL (4 HP) RAV-SP360AT2-UL (4, 5 HP) RAV-SP420AT2-UL (5 HP)

RAV-SP180AT2-UL (2 HP) RAV-SP240AT2-UL (3 HP) RAV-SP300AT2-UL (4 HP) RAV-SP360AT2-UL (4, 5 HP) RAV-SP420AT2-UL (5 HP) SERVICE MANUAL FILE. A09-00-2 Revised : Feb. 200 REVISI 2 : Jan.202 Re-edit version.( file volume down) Contents have T been changed. OUTDOOR UNIT SPLIT TYPE RAV-SP80AT2-UL (2

More information

Installation Manual PMV Kit RBM-PMV0363E RBM-PMV0903E

Installation Manual PMV Kit RBM-PMV0363E RBM-PMV0903E EB99802801-1 Installation Manual RBM-PMV0363E RBM-PMV0903E Installation Manual English OUTDOOR UNIT SIDE UPPER INDOOR UNIT SIDE Thank you very much for purchasing TOSHIBA Air conditioner. Please read this

More information

AIR-CONDITIONER SERVICE MANUAL SPLIT TYPE OUTDOOR UNIT RAV-GP1401AT-TR RAV-GP1101ATJ-E RAV-GP1401ATJ-E <SUPER DIGITAL INVERTER> FILE No.

AIR-CONDITIONER SERVICE MANUAL SPLIT TYPE OUTDOOR UNIT RAV-GP1401AT-TR RAV-GP1101ATJ-E RAV-GP1401ATJ-E <SUPER DIGITAL INVERTER> FILE No. FILE No. A0-809 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE OUTDOOR UNIT RAV-GP80AT-E RAV-GP0AT-E RAV-GP40AT-E RAV-GP80ATJ-E RAV-GP0ATJ-E RAV-GP40ATJ-E RAV-GP80AT-TR RAV-GP0AT-TR

More information

AIR-CONDITIONER MULTI TYPE

AIR-CONDITIONER MULTI TYPE Leading Innovation FILE NO. SVM-0 SERVICE MANUAL AIR-CONDITIONER MULTI TYPE < Console Type> MML-AP0074NH-E, -TR MML-AP0094NH-E, -TR MML-AP04NH-E, -TR MML-AP054NH-E, -TR MML-AP084NH-E, -TR This Service

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE. A06-00 Revised : Mar. 007 SERVICE MANUAL/INTEGRATION AIR-CONDITIONER SPLIT TYPE INDOOR UNIT RAV-SM56UT-E RAV-SM56BT-E RAV-SM56CT-E RAV-SM80UT-E RAV-SM80BT-E RAV-SM80CT-E RAV-SM0UT-E

More information

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) RAV-SM304ATP-E (TR) RAV-SM404ATP-E (TR) RAV-SM304ATJP-E RAV-SM404ATJP-E OUTDOOR UNIT <DIGITAL INVERTER>

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) RAV-SM304ATP-E (TR) RAV-SM404ATP-E (TR) RAV-SM304ATJP-E RAV-SM404ATJP-E OUTDOOR UNIT <DIGITAL INVERTER> FILE. SVM-14059-3 SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) OUTDOOR UNIT RAV-SM304ATP-E (TR) RAV-SM404ATP-E (TR) RAV-SM304ATJP-E RAV-SM404ATJP-E Revised on July, 2016 Original instruction

More information

SERVICE MANUAL/INTEGRATION

SERVICE MANUAL/INTEGRATION FILE. A05-08 Revised: Jul/5/005 SERVICE MANUAL/INTEGRATION SPLIT TYPE INDOOR UNIT RAV-SM56UT-E RAV-SM56BT-E RAV-SM56CT-E RAV-SM80UT-E RAV-SM80BT-E RAV-SM80CT-E RAV-SM0UT-E RAV-SM0BT-E

More information

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) RAV-SM1104AT8P-E (TR) RAV-SM1404AT8P-E (TR) RAV-SM1104AT8JP-E RAV-SM1404AT8JP-E

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) RAV-SM1104AT8P-E (TR) RAV-SM1404AT8P-E (TR) RAV-SM1104AT8JP-E RAV-SM1404AT8JP-E FILE. SVM-17005-2 SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) OUTDOOR UNIT DIGITAL INVERTER> RAV-SM1104AT8P-E (TR) RAV-SM1404AT8P-E (TR) RAV-SM1104AT8JP-E RAV-SM1404AT8JP-E Revised no March, 2017 FILE.

More information

SERVICE MANUAL Outdoor Unit

SERVICE MANUAL Outdoor Unit FILE No. A11-019 Revision 1 : Jun, 2013 AIR CONDITIONER (MULTI TYPE) SERVICE MANUAL Outdoor Unit Model name: MMY-MAP0724HT6UL MMY-MAP0964HT6UL MMY-MAP1144HT6UL

More information

Digital Inverter 4 series 8 & 10HP

Digital Inverter 4 series 8 & 10HP E6-H Digital Inverter 4 series 8 & 0HP High static duct type Indoor unit RAV-SM2244DTP-E RAV-SM2804DTP-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E Contents. Line up... 2. Indoor unit (High static duct

More information

Compact 4-way Cassette ( ) Type

Compact 4-way Cassette ( ) Type E08-0 Engineering Data Compact 4-way Cassette (600 600) Type Indoor Unit RAV-SM40MUT-E RAV-SM4MUT-E Outdoor Unit RAV-SP404AT-E RAV-SP44AT-E Contents. Specifications. Connecting pipe length and lift difference

More information

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE)

SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) -1 SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) OUTDOOR UNIT RAV-SM564ATP-E (TR) RAV-SM804ATP-E (TR) RAV-SM1104ATP-E (TR) RAV-SM1404ATP-E (TR) RAV-SM564ATJP-E RAV-SM804ATJP-E RAV-SM1104ATJP-E

More information

AIR-CONDITIONER SERVICE MANUAL SPLIT TYPE R410A RAV-SM566KRT-E, RAV-SM806KRT-E RAV-SM566KRT-TR, RAV-SM806KRT-TR INDOOR UNIT.

AIR-CONDITIONER SERVICE MANUAL SPLIT TYPE R410A RAV-SM566KRT-E, RAV-SM806KRT-E RAV-SM566KRT-TR, RAV-SM806KRT-TR INDOOR UNIT. FILE. SVM-2004 SERVICE MANUAL AIR-CONDITIONER INDOOR UNIT SPLIT TYPE High Wall Type RAV-SM566KRT-E, RAV-SM806KRT-E RAV-SM566KRT-TR, RAV-SM806KRT-TR R40A FILE. SVM-2004 Adoption of New Refrigerant This

More information

AIR CONDITIONER (MULTI TYPE) SERVICE MANUAL

AIR CONDITIONER (MULTI TYPE) SERVICE MANUAL AIR CNDITINER (MULTI TYPE) SERVICE MANUAL utdoor Unit < SUPER HEAT RECVERY MULTI-i > Model name: MMY-MAP074FT9UL MMY-MAP0964FT9UL MMY-MAP04FT9UL MMY-MAP074FT6UL MMY-MAP0964FT6UL MMY-MAP04FT6UL Flow Selector

More information

DX Interface : Dx-Controller (0-10V type) Installation manual ENGLISH. TCB-IFDD1GUL Dx-Controller (0-10V type) Model name:

DX Interface : Dx-Controller (0-10V type) Installation manual ENGLISH. TCB-IFDD1GUL Dx-Controller (0-10V type) Model name: DX Interface : Dx-Controller (0-10V type) Installation manual Model name: TCB-IFDD1GUL Dx-Controller (0-10V type) ENGLISH Please read this Installation Manual carefully before installing the Dx Interface

More information

SERVICE MANUAL SPLIT TYPE R410A <DIGITAL INVERTER> INDOOR UNIT RAV-SM562MUT-E FILE NO. A06-005

SERVICE MANUAL SPLIT TYPE R410A <DIGITAL INVERTER> INDOOR UNIT RAV-SM562MUT-E FILE NO. A06-005 FILE. A06-005 SERVICE MANUAL SPLIT TYPE INDOOR UNIT RAV-SM562MUT-E This Service Manual describes contents of the new indoor unit. For the outdoor unit, refer to the Service Manual with

More information

SERVICE MANUAL. Air to Air Heat Exchanger. Concealed microcomputer control type VN-M150HE VN-M250HE VN-M350HE VN-M500HE VN-M650HE VN-M800HE VN-M1000HE

SERVICE MANUAL. Air to Air Heat Exchanger. Concealed microcomputer control type VN-M150HE VN-M250HE VN-M350HE VN-M500HE VN-M650HE VN-M800HE VN-M1000HE FILE No. A10-021 Air to Air Heat SERVICE MANUAL Concealed microcomputer control type Model name: VN-M150HE VN-M250HE VN-M350HE VN-M500HE VN-M650HE VN-M800HE VN-M1000HE Contents 1 Features............................................................

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE NO. A06-05 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE INDOOR UNIT Heat Pump Model RAS-M0SMUV-E RAS-M3SMUV-E RAS-M6SMUV-E Cooling Only Model RAS-M0SMUCV-E RAS-M3SMUCV-E RAS-M6SMUCV-E R40A PRINTED IN

More information

TOSHIBA Carrier (UK) Ltd. LC DX Interface Installation manual ENGLISH. For commercial use. Model name:

TOSHIBA Carrier (UK) Ltd. LC DX Interface Installation manual ENGLISH. For commercial use. Model name: TOSHIBA Carrier (UK) Ltd. LC DX Interface Installation manual Model name: For commercial use RAV-DXC010 LC DX Interface ENGLISH Please read this carefully before installing the LC DX interface. This Manual

More information

Service Manual AIR TO WATER HEAT PUMP. Outdoor unit. Hydro unit

Service Manual AIR TO WATER HEAT PUMP. Outdoor unit. Hydro unit FILE. A10-1704 AIR TO WATER HEAT PUMP Service Manual Model name: Hydro unit HWS-805XWHM3-E(TR) HWS-805XWHT6-E(TR) HWS-805XWHT9-E HWS-1405XWHM3-E(TR) HWS-1405XWHT6-E(TR) HWS-1405XWHT9-E(TR) Outdoor unit

More information

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO AOYG8LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL For authorized service personnel only. English PART NO. 93778639 93778639_IM.indb /20/20 6:07:25 PM AIR CONDITIONER OUTDOOR UNIT INSTALLATION

More information

RAV-SM564KRT-E RAV-SM804KRT-E RAV-SM564KRT-TR RAV-SM804KRT-TR

RAV-SM564KRT-E RAV-SM804KRT-E RAV-SM564KRT-TR RAV-SM804KRT-TR FILE. A0-03 SERVICE MANUAL AIR-CONDITIONER HI WALL TYPE (INDOOR UNIT) RAV-SM564KRT-E RAV-SM804KRT-E RAV-SM564KRT-TR RAV-SM804KRT-TR ŸThe service parts will be supplied by TCTC. R40A PRINTED IN JAPAN, May.,

More information

1. ACCESSORIES SUPPLIED WITH THE AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNIT 3. INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 4.

1. ACCESSORIES SUPPLIED WITH THE AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNIT 3. INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 4. 1. ACCESSORIES SUPPLIED WITH THE AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNIT 3. INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 4. INSTALLATION OF THE INDOOR UNIT 5. CONDENSATE HOSE CONNECTION

More information

TCB-DP22CUL. Drain Pump Kit. Model name : AIR CONDITIONER (SPLIT TYPE) Installation Manual. Installation Manual 2 Air Conditioner (Split type) English

TCB-DP22CUL. Drain Pump Kit. Model name : AIR CONDITIONER (SPLIT TYPE) Installation Manual. Installation Manual 2 Air Conditioner (Split type) English AIR CONDITIONER (SPLIT TYPE) Model name : TCB-DP22CUL 2 Air Conditioner (Split type) English Manuel D installation Climatiseur (Type split) 12 Français Please read this carefully before installing the

More information

SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE)

SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) FILE NO. A10-1508 SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) OUTDOOR UNIT Model name: MCY-MHP0404HS8(J)-E/0504HS8(J)-E/0604HS8(J)-E MCY-MHP0404HS8(J)-TR/0504HS8(J)-TR/0604HS8(J)-TR MCY-MHP0404HS8(J)/0504HS8(J)/0604HS8(J)

More information

RAV-SM561KRT-E RAV-SM801KRT-E

RAV-SM561KRT-E RAV-SM801KRT-E FILE.SVM-05034- SERVICE MANUAL HI WALL TYPE (INDOOR UNIT) RAV-SM56KRT-E RAV-SM80KRT-E R40A CONTENTS. SPECIFICATIONS... 2 2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)... 4 3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM...

More information

SERVICE MANUAL SPLIT TYPE

SERVICE MANUAL SPLIT TYPE FILE. A0-04 SERVICE MANUAL SPLIT TYPE RAV-SM560AT-E/RAV-SM800AT-E RAV-SM560UT-E/RAV-SM800UT-E RAV-SM560BT-E/RAV-SM800BT-E RAV-SM560KRT-E/RAV-SM800KRT-E RAV-SM560XT-E/RAV-SM800XT-E R40A PRINTED IN JAPAN,

More information

4-Way Cassette type. Contents MMU-AP 2H2UL

4-Way Cassette type. Contents MMU-AP 2H2UL E15-3C1 6 Indoor unit MMU-AP 2H2UL 4-Way Cassette type MMU-AP0072H2UL MMU-AP0092H2UL MMU-AP0122H2UL MMU-AP0152H2UL MMU-AP0182H2UL MMU-AP0212H2UL MMU-AP0242H2UL MMU-AP0302H2UL MMU-AP0362H2UL MMU-AP0422H2UL

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3B54VA MXZ-4B71VA. English

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3B54VA MXZ-4B71VA. English Split-type Air-Conditioner MXZ-3B54VA MXZ-4B71VA INSTALLATION MANUAL English Refer to the installation manual of each indoor unit for indoor unit installation. IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS

More information

Installation manual. Branch kit 1:3 RBC-TRP100E AIR CONDITIONER (SPLIT TYPE) Model name: Installation manual. Air conditioner (Split type) 1 English

Installation manual. Branch kit 1:3 RBC-TRP100E AIR CONDITIONER (SPLIT TYPE) Model name: Installation manual. Air conditioner (Split type) 1 English EH99862001-2 AIR CONDITIONER (SPLIT TYPE) Installation manual Branch kit 1:3 Model name: RBC-TRP100E Installation manual Air conditioner (Split type) 1 English Please read this Installation Manual carefully

More information

Service Manual AIR TO WATER HEAT PUMP. Outdoor unit. Hydro unit HWS-804XWHT6-E1(TR) HWS-1104H-E1(TR) HWS-804XWHM3-E1(TR) HWS-804H-E1(TR)

Service Manual AIR TO WATER HEAT PUMP. Outdoor unit. Hydro unit HWS-804XWHT6-E1(TR) HWS-1104H-E1(TR) HWS-804XWHM3-E1(TR) HWS-804H-E1(TR) FILE. A10-1502 AIR TO WATER HEAT PUMP Service Manual Model name: Hydro unit Outdoor unit HWS-804XWHM3-E1(TR) HWS-804H-E1(TR) HWS-804XWHT6-E1(TR) HWS-1104H-E1(TR) HWS-804XWHT9-E1 HWS-1404H-E1(TR) HWS-1404XWHM3-E1(TR)

More information

AIR CONDITIONER (MULTI TYPE) Installation Manual. Indoor Unit. Model name:

AIR CONDITIONER (MULTI TYPE) Installation Manual. Indoor Unit. Model name: AIR CONDITIONER (MULTI TYPE) Installation Manual Indoor Unit Model name: For commercial use Pour usage commercial 4-way Cassette type MMU-AP0072H2UL MMU-AP0092H2UL MMU-AP0122H2UL MMU-AP0152H2UL MMU-AP0182H2UL

More information

Small VRF system. for light commercial and home use SERVICE MANUAL

Small VRF system. for light commercial and home use SERVICE MANUAL Small VRF system for light commercial and home use SERVICE MANUAL CONTENTS 1. TEST RUN 1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS... 01-01 1-2 TEST RUN METHOD... 01-03 1-2-1 Check Items Before

More information

SERVICE MANUAL SPLIT TYPE RAS-M07SKV-E RAS-M10SKV-E RAS-M13SKV-E RAS-M16SKV-E RAS-M10SKCV-E RAS-M13SKCV-E RAS-M16SKCV-E R410A.

SERVICE MANUAL SPLIT TYPE RAS-M07SKV-E RAS-M10SKV-E RAS-M13SKV-E RAS-M16SKV-E RAS-M10SKCV-E RAS-M13SKCV-E RAS-M16SKCV-E R410A. FILE. SVM-07034-2 SERVICE MANUAL SPLIT TYPE Indoor Unit RAS-M07SKV-E RAS-M10SKV-E RAS-M13SKV-E RAS-M16SKV-E RAS-M10SKCV-E RAS-M13SKCV-E RAS-M16SKCV-E

More information

RAS-10JKVP-E RAS-10JAVP-E RAS-13JKVP-E RAS-13JAVP-E

RAS-10JKVP-E RAS-10JAVP-E RAS-13JKVP-E RAS-13JAVP-E FILE NO. A0-05 SPLIT TYPE RAS-0JKVP-E RAS-0JAVP-E RAS-3JKVP-E RAS-3JAVP-E PRINTED IN JAPAN, Jun.,003 ToMo . EXPLODED VIEWS AND PARTS LIST -. Indoor Unit () 0 0 6 35 5 4 0 5 33 7 08 6 07 9 3 0 3 8 30 39

More information

Service Manual AIR TO WATER HEAT PUMP. Outdoor unit. Hydro unit HWS-P805XWHM3-E(TR) HWS-P805HR-E(TR) HWS-P805XWHT6-E(TR) HWS-P1105HR-E(TR)

Service Manual AIR TO WATER HEAT PUMP. Outdoor unit. Hydro unit HWS-P805XWHM3-E(TR) HWS-P805HR-E(TR) HWS-P805XWHT6-E(TR) HWS-P1105HR-E(TR) FILE. A10-1705 AIR TO WATER HEAT PUMP Service Manual Model name: Hydro unit Outdoor unit HWS-P805XWHM3-E(TR) HWS-P805HR-E(TR) HWS-P805XWHT6-E(TR) HWS-P1105HR-E(TR) HWS-P805XWHT9-E HWS-P1105XWHM3-E(TR)

More information

MMC-AP0181H2UL MMC-AP0241H2UL MMC-AP0361H2UL MMC-AP0421H2UL

MMC-AP0181H2UL MMC-AP0241H2UL MMC-AP0361H2UL MMC-AP0421H2UL AIR CONDITIONER (MULTI TYPE) Installation manual Indoor Unit Model name: Ceiling type MMC-AP0181H2UL MMC-AP0241H2UL MMC-AP0361H2UL MMC-AP0421H2UL Installation manual 1 English Manuel d installation 17

More information

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SM1403DT-A RAV-SM1603DT-A. Model name: Concealed Duct High Static Pressure Type

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SM1403DT-A RAV-SM1603DT-A. Model name: Concealed Duct High Static Pressure Type AIR CONDITIONER (SPLIT TYPE) Indoor Unit Not accessible to the general public Model name: Concealed Duct High Static Pressure Type RAV-SM1403DT-A RAV-SM1603DT-A Thank you very much for purchasing TOSHIBA

More information

AIR CONDITIONER CONSOLE

AIR CONDITIONER CONSOLE Installation manual ENGLISH AIR CONDITIONER CONSOLE English Indoor unit console type IT IS MANDATORY TO CUT OFF POWER SUPPLY BEFORE STARTING TO WORK IN THE ELECTRIC CASING BOXES. GENERAL RECOMMENDATIONS

More information

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-UL RAV-SP360CT-UL RAV-SP420CT-UL.

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-UL RAV-SP360CT-UL RAV-SP420CT-UL. AIR CONDITIONER (SPLIT TYPE) Unit Model name: Not accessible to the general public Vente interdite au grand public Under Ceiling Type RAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-UL RAV-SP360CT-UL RAV-SP420CT-UL

More information

Split-type Air-Conditioner

Split-type Air-Conditioner Split-type Air-Conditioner MXZ-2D52VA Installation Manual For INSTALLER This manual only describes the installation of outdoor unit. When installing the indoor unit, refer to the installation manual of

More information

RAS-10JKVP-E RAS-10JAVP-E RAS-13JKVP-E RAS-13JAVP-E

RAS-10JKVP-E RAS-10JAVP-E RAS-13JKVP-E RAS-13JAVP-E FILE. A02-05 SPLIT TYPE RAS-0JKVP-E RAS-0JAVP-E RAS-3JKVP-E RAS-3JAVP-E PRINTED IN JAPAN, Mar.,2002 ToMo CONTENTS. SPECIFICATIONS... 3 2. REFRIGERANT R40A... 5 3. CONSTRUCTION VIEWS... 3 4. WIRING DIAGRAM...

More information

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE -(1) SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-24UKHP-E3 / RAS-24UAH-E3 RAS-18UKHP-E3 / RAS-18UAH-E3 RAS-24UKP-E3 / RAS-24UA-E3 RAS-18UKP-E3 / RAS-18UA-E3 RAS-24UKP-AR3 / RAS-24UA-AR3 RAS-18UKP-AR3

More information

Installation Manual. Indoor Unit MMK-AP0073H2UL MMK-AP0093H2UL MMK-AP0123H2UL MMK-AP0153H2UL MMK-AP0183H2UL MMK-AP0243H2UL

Installation Manual. Indoor Unit MMK-AP0073H2UL MMK-AP0093H2UL MMK-AP0123H2UL MMK-AP0153H2UL MMK-AP0183H2UL MMK-AP0243H2UL AIR CONDITIONER (MULTI TYPE) Indoor Unit Model name: High Wall Type MMK-AP0073H2UL MMK-AP0093H2UL MMK-AP0123H2UL MMK-AP0153H2UL MMK-AP0183H2UL MMK-AP0243H2UL 1 English Manuel d installation 32 Français

More information

INSTALLATION MANUAL. Outdoor Unit. Indoor Unit FILE NO. A Cooling Only Model. Heat Pump Model. Heat Pump Model

INSTALLATION MANUAL. Outdoor Unit. Indoor Unit FILE NO. A Cooling Only Model. Heat Pump Model. Heat Pump Model FILE NO. A03-0 INSTALLATION MANUAL Unit MMU-AP009H, AP0H, AP05H, MMU-AP08H, AP04H, AP07H, MMU-AP030H, AP036H, AP048H MMU-AP056H MMU-AP007WH,

More information

SERVICE MANUAL AIR TO WATER HEAT PUMP. Hydro Unit. Outdoor Unit. Hot Water Cylinder

SERVICE MANUAL AIR TO WATER HEAT PUMP. Hydro Unit. Outdoor Unit. Hot Water Cylinder AIR TO WATER HEAT PUMP SERVICE MANUAL A10-006-1 REVISION 1 : Mar.2012 Re-edit version.( file volume down) Contents have NOT been changed. Model name: Hydro Unit HWS-803XWHM3-E(TR) HWS-803XWHT6-E(TR) HWS-803XWHD6-E

More information

[FLARE CONNECTION TYPE] ATTENTION

[FLARE CONNECTION TYPE] ATTENTION SPLIT-TYPE AIR CONDITIONERS Model MXZ-2A20NA [FLARE CONNECTION TYPE] HFC utilized R410A INSTALLATION MANUAL ATTENTION This manual mentions how to install only the outdoor unit, MXZ-2A20NA. As for the way

More information

8 Louver position display. 9 SWING display. 10 Set up temperature display. 11 Remote controller sensor display

8 Louver position display. 9 SWING display. 10 Set up temperature display. 11 Remote controller sensor display Wired remote controller (RBC-AMTE) Operation manual Parts Name of Remote Controller Display section In the display example, all indicators are displayed for the explanation. In reality only, the selected

More information

Service Manual. Room Air Conditioner Split Wall-Mounted Type. Applies to: HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1

Service Manual. Room Air Conditioner Split Wall-Mounted Type. Applies to: HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1 Service Manual Room Air Conditioner Split Wall-Mounted Type Applies to: HSG-09CRN1 HSG-12CRN1 HSG-18CRN1 HSG-24CRN1 HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1 NOTE: Please read this first before servicing

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL No. OCH468 REVISED EDITI-A HFC utilized R4A June 2 [Model name] MXZ-8B48NA PAC-AKA5BC PAC-AKA3BC (Indispensable

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Cassette type Duct type Ceiling type INVERTER AO* G45LETL AO* G54LETL

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Cassette type Duct type Ceiling type INVERTER AO* G45LETL AO* G54LETL SPLIT TYPE ROOM AIR CONDITIONER Cassette type Duct type Ceiling type INVERTER SERVICE INSTRUCTION Models Indoor unit AU* G45LRLA AR* G45LMLA AR* G45LHTA AB* G45LRTA Outdoor unit AO* G45LETL AO* G54LETL

More information

COMPLIANT MANAGER. Installation Manual. Model name: BMS-CM1280TLE BMS-CM1280FTLE. Save These Instructions! ENGLISH

COMPLIANT MANAGER. Installation Manual. Model name: BMS-CM1280TLE BMS-CM1280FTLE. Save These Instructions! ENGLISH COMPLIANT MANAGER Model name: BMS-CM1280TLE BMS-CM1280FTLE Save These Instructions! ENGLISH Contents 1 PRECAUTIONS FOR SAFETY........................................... 3 2 PACKAGED ITEMS OF COMPLIANT

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

AIR-CONDITIONER SERVICE MANUAL

AIR-CONDITIONER SERVICE MANUAL FILE NO. A90-9608 SERVICE MANUAL AIR-CONDITIONER S SPLIT BUILT-IN DUCT TYPE RAV-362B-PE/ RAV-462B-PE/ SPLIT CEILING TYPE RAV-362C-PE/ RAV-462C-PE/ SPLIT CASSETTE TYPE RAV-362U-PE/ RAV-462U-PE/ PRINTED

More information

RAS-13UKV-E RAS-13UAV-E

RAS-13UKV-E RAS-13UAV-E FILE NO. A0-00 SPLIT TYPE RAS-3UKV-E RAS-3UAV-E PRINTED IN JAPAN, Mar.,00 ToMo CONTENTS. SPECIFICATIONS... 3. REFRIGERANT R40A... 5 3. CONSTRUCTION VIEWS... 3 4. WIRING DIAGRAM... 5 5. SPECIFICATIONS OF

More information

Air to Water Heat Pump

Air to Water Heat Pump E7- Air to Water Heat Pump Hydro Unit HWS-55XWHM-E HWS-805XWHM-E HWS-805XWHT6-E HWS-805XWHT9-E HWS-05XWHM-E HWS-05XWHT6-E HWS-05XWHT9-E HWS-P805XWHM-E HWS-P805XWHT6-E HWS-P805XWHT9-E HWS-P05XWHM-E HWS-P05XWHT6-E

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G24LFL AO*G24LFCC AO*G30LFT

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G24LFL AO*G24LFCC AO*G30LFT SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS*G4LFCA AS*G4LFCC AS*G0LFCA AO*G4LFL AO*G4LFCC AO*G0LFT R40A CONTENTS. DESCRIPTION OF EACH

More information

FILE NO. SVM SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-13UKV-E2 / RAS-13UAV-E2

FILE NO. SVM SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-13UKV-E2 / RAS-13UAV-E2 SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-13UKV-E2 / RAS-13UAV-E2 Jun., 2003 CONTENTS 1. SPECIFICATIONS 1-1 Specifications 1-2 Operation Characteristic Curve 1-2 Capacity Variation Ratio According

More information

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF AOU 9RLFW AOURLFW R40A CONTENTS. DESCRIPTION OF EACH CONTROL OPERATION. COOLING

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS* A09LEC AS* A12LEC AO* R09LECN AO* R12LECN R410A CONTENTS 1. DESCRIPTION OF EACH CONTROL

More information

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

AIR CONDITIONER (MULTI TYPE) Installation Manual. Outdoor Unit. English. Model name:

AIR CONDITIONER (MULTI TYPE) Installation Manual. Outdoor Unit. English. Model name: DB04305801-00 AIR CONDITIONER (MULTI TYPE) Outdoor Unit For commercial use Model name: Heat Pump Model MCY-MHP0404HT-E MCY-MHP0504HT-E MCY-MHP0604HT-E MCY-MHP0404HTJ-E MCY-MHP0504HTJ-E MCY-MHP0604HTJ-E

More information

3. INDOOR UNIT OPERATION

3. INDOOR UNIT OPERATION 3. INDOOR UNIT OPERATION INDOOR UNIT OPERATION 3- FAN CONTROL 3-- Fan Speed Setting Fan speed setting Press the FAN CONTROL button to set the fan speed. AUTO HIGH MED LOW 3-- "AUTO" Position. COOL OPERATION

More information

SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE)

SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) FILE NO. A10-1510 SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) OUTDOOR UNIT Model name: MCY-MHP0404HS(J)-E/0504HS(J)-E/0604HS(J)-E MCY-MHP0404HS-TR/0504HS-TR/0604HS-TR MCY-MHP0404HS(J)/0504HS(J)/0604HS(J)

More information

TEST RUN SERVICE MANUAL

TEST RUN SERVICE MANUAL TEST RUN SERVICE MANUAL Model No. Outdoor Unit ME Class Model Name HP U-MEE 0HP U-0MEE HP U-MEE HP U-MEE HP U-MEE HP U-MEE 0HP U-0MEE U-MEEE U-0MEEE U-MEEE U-MEEE U-MEEE U-MEEE U-0MEEE Indoor Unit Class

More information

CONTENTS INSTALLATION MANUAL HFC FOR INSTALLER R410A. utilized 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2

CONTENTS INSTALLATION MANUAL HFC FOR INSTALLER R410A. utilized 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2 SPLIT-TYPE AIR CONDITIONER CONTENTS INSTALLATION MANUAL 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2 Model MXZ-A26/32WV HFC utilized R410A 2. INSTALLATION DIAGRAM & ACCESSORIES... 2 3. SELECTING

More information

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A.

More information

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E. Model name: Slim Duct Type.

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E. Model name: Slim Duct Type. AIR CONDITIONER (SPLIT TYPE) Indoor Unit Model name: Slim Duct Type RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E Not accessible to the general public Vente interdite au grand public Kein öffentlicher Zugang

More information

Split-type Air-Conditioner

Split-type Air-Conditioner Split-type Air-Conditioner MXZ-2C52VA Installation Manual For INSTALLER This manual only describes the installation of outdoor unit. When installing the indoor unit, refer to the installation manual of

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

Quick Reference. for Remote Countroller

Quick Reference. for Remote Countroller A1C-1405 Quick Reference for Remote Countroller Digital Inverter (DI) Super Digital Inverter (SDI) MiNi-Super Modular Multi System (MiNi-SMMS) Super Modular Multi System (SMMS) Super Modular Multi System-i

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

RAV-SP181BT-UL RAV-SP241BT-UL RAV-SP301BT-UL RAV-SP361BT-UL RAV-SP421BT-UL

RAV-SP181BT-UL RAV-SP241BT-UL RAV-SP301BT-UL RAV-SP361BT-UL RAV-SP421BT-UL AIR CONDITIONER (SPLIT TYPE) Installation Manual Indoor Unit Model name: For commercial use Pour usage commercial Concealed Duct Type RAV-SP8BT-UL RAV-SP4BT-UL RAV-SP30BT-UL RAV-SP36BT-UL RAV-SP4BT-UL

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

MMY-MAP0804T8P-E MMY-MAP1004T8P-E MMY-MAP1204T8P-E MMY-MAP1404T8P-E MMY-MAP1604T8P-E

MMY-MAP0804T8P-E MMY-MAP1004T8P-E MMY-MAP1204T8P-E MMY-MAP1404T8P-E MMY-MAP1604T8P-E AIR CONDITIONER (MULTI TYPE) Installation Manual Outdoor Unit Model name: MMY-MAP0804HT8P-E MMY-MAP1004HT8P-E MMY-MAP1204HT8P-E MMY-MAP1404HT8P-E MMY-MAP1604HT8P-E MMY-MAP0804HT8JP-E

More information

1 TECHNICAL CHANGES. MUZ-A09NA MUZ-A09NA - 1 MUZ-A09NA - U1 MUZ-A09NA - U2 1. Refrigerant system diagram has been changed.

1 TECHNICAL CHANGES. MUZ-A09NA MUZ-A09NA - 1 MUZ-A09NA - U1 MUZ-A09NA - U2 1. Refrigerant system diagram has been changed. 1 TECHNICAL CHANGES MUZ09UN MUZ-A09NA MUZ12UN MUZ-A12NA MUH15TN MUZ-A15NA MUH17TN MUZ-A17NA MUH24WN MUZ-A24NA MU15TN MUY-A15NA MU17TN MUY-A17NA MU24WN MUY-A24NA 1. Outdoor unit model has been changed.

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338 TECHNICAL & SERVICE MANUAL SA 128S5 FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-128S5-A 1 851 004 09 General (50Hz) & Europe SA 128S5 REFERENCE NO. SM700338 IMPORTANT!

More information

YC ON-OFF SERIES. Service Manual

YC ON-OFF SERIES. Service Manual YC ON-OFF SERIES Service Manual CONTENTS 1. Precaution... 3 1.1 Safety Precaution... 3 1.2 Warning... 3 2. Model Lists... 6 3. Dimension... 7 3.1 Indoor Unit... 7 3.2 Outdoor Unit... 11 4. Refrigerant

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

FILE NO. SVM SERVICE MANUAL SPLIT TYPE R410A

FILE NO. SVM SERVICE MANUAL SPLIT TYPE R410A SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit RAS-077SKV-E5 RAS-107SKV-E5 RAS-137SKV-E5 RAS-077SAV-E5 RAS-107SAV-E5 RAS-137SAV-E5 R410A March, 2013 CONTENTS

More information

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA 0.8180.472.0 07/2005 Page 1. SPECIFICATIONS 3 1-1 Unit Specifications 3 1-2 Major Component Specifications 4 2. DIMENSIONAL DATA 6 2-1 Unit Dimensions 6 3. ELECTRICAL

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information