CONDENSING UNIT WARNING AIR CONDITIONING INSTALLATION & SERVICE REFERENCE. Important Safety Instructions. Shipping Inspection. Codes & Regulations

Size: px
Start display at page:

Download "CONDENSING UNIT WARNING AIR CONDITIONING INSTALLATION & SERVICE REFERENCE. Important Safety Instructions. Shipping Inspection. Codes & Regulations"

Transcription

1 ONDENSING UNIT AIR ONDITIONING INSTALLATION & SERVIE REFERENE Important Safety Instructions The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage. HIGH VOLTAGE! Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. ONLY individuals meeting the requirements of an Entry Level Technician as specified by the Air onditioning, Heating and Refrigeration Institute (AHRI) may use this information. Attempting to install or repair this unit without such background may result in product damage, personal injury, or death. IMPORTANT NOTE TO THE OWNER REGARDING PRODUT WAR AR- RANTY Your warranty certificate is supplied as a separate document with the unit installed by your contractor. Read the limited warranty certificate carefully to determine what is and is not covered and keep the warranty certificate in a safe place. If you are unable to locate the warranty certificate please contact your installing contractor or contact customer service ( ) to obtain a copy. To receive the 10-Year Parts Limited Warranty for Amana branded products, online registration must be completed within 60 days of installation. Online registration is not required in alifornia or Quebec. Full warranty details available at To receive the 10-Year Parts Limited Warranty for Goodman branded products, online registration must be completed within 60 days of installation. Online registration is not required in alifornia or Quebec. Full warranty details available at IMPORTANT: To register your Goodman brand unit, go to lick on the word Warranty located on the left side of the home page. Next, click on the word Product Registration located on the left side of the Warranty page and complete the forms in the manner indicated on the Product Registration page Goodman Manufacturing ompany, L.P. 11 San Felipe, Suite 00, Houston, TX or- P/N: IO-28G Date: October 2009 To register your Amana brand unit, go to lick on the word Warranty located on the top right of the home page. Next, click on the word Product Registration located on the left side of the Warranty page and complete the forms in the manner indicated on the Product Registration page. Product limited warranty certificates can be viewed at or Each product overview page contains a Product Warranty link; by clicking on it you will be able to view the limited warranty coverage for that specific product. To view warranty registration information, click on the Product Warranty text on the left navigation panel on the home page of each website. The Online Product Registration pages are located in this same section. Shipping Inspection Always keep the unit upright; laying the unit on its side or top may cause equipment damage. Shipping damage, and subsequent investigation is the responsibility of the carrier. Verify the model number, specifications, electrical characteristics, and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units. odes & Regulations This product is designed and manufactured to comply with national codes. Installation in accordance with such codes and/ or prevailing local codes/regulations is the responsibility of the installer. The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations. The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Should you have any questions please contact the local office of the EPA. If replacing a condensing unit or air handler, the system must be manufacturer approved and Air onditioning, Heating and Refrigeration Institute (AHRI) matched. NOTE: Installation of unmatched systems is strongly discouraged. Operating the unit in a structure that is not complete (either as part of new construction or renovation) will void the warranty. Installation learances Special consideration must be given to location of the condensing unit(s) in regard to structures, obstructions, other units, and any/all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unobstructed; however, if vertical conditions require placement beneath an obstruction there should be a minimum of 60 inches between the top of the unit and the obstruction(s). The specified dimensions meet requirements for air circulation only. onsult all appropriate regulatory codes prior to determining final clearances.

2 Another important consideration in selecting a location for the unit(s) is the angle to obstructions. Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance. orner installations are strongly discouraged. A A NOT REOMMENDED B B B B OK! OK! OK! OK! OK! OK! Minimum Airflow learance Model Type A B Residential 10" 10" 18" 20" Light ommercial 12" 12" 18" 24" This unit can be located at ground floor level or on flat roofs. At ground floor level, the unit must be on a solid, level foundation that will not shift or settle. To reduce the possibility of sound transmission, the foundation slab should not be in contact with or be an integral part of the building foundation. Ensure the foundation is sufficient to support the unit. A concrete slab raised above ground level provides a suitable base. Rooftop Installations If it is necessary to install this unit on a roof structure, ensure the roof structure can support the weight and that proper consideration is given to the weather-tight integrity of the roof. Since the unit can vibrate during operation, sound vibration transmission should be considered when installing the unit. Vibration absorbing pads or springs can be installed between the condensing unit legs or frame and the roof mounting assembly to reduce noise vibration. Safe Refrigerant Handling While these items will not cover every conceivable situation, they should serve as a useful guide. To avoid possible injury, explosion or death, practice safe handling of refrigerants. Refrigerants are heavier than air. They can "push out" the oxygen in your lungs or in any enclosed space.to avoid possible difficulty in breathing or death: Never purge refrigerant into an enclosed room or space. By law, all refrigerants must be reclaimed. If an indoor leak is suspected, throughly ventilate the area before beginning work. Liquid refrigerant can be very cold. To avoid possible frostbite or blindness, avoid contact and wear gloves and goggles. If liquid refrigerant does contact your skin or eyes, seek medical help immediately. Always follow EPA regulations. Never burn refrigerant, as poisonous gas will be produced. To avoid possible explosion: Never apply flame or steam to a refrigerant cylinder. If you must heat a cylinder for faster charging, partially immerse it in warm water. Never fill a cylinder more than 80% full of liquid refrigerant. Never add anything other than R-22 to an R-22 cylinder or R-410A to an R-410A cylinder. The service equipment used must be listed or certified for the type of refrigerant used. Store cylinders in a cool, dry place. Never use a cylinder as a platform or a roller. To avoid possible explosion, use only returnable (not disposable) service cylinders when removing refrigerant from a system. Ensure the cylinder is free of damage which could lead to a leak or explosion. Ensure the hydrostatic test date does not exceed years. Ensure the pressure rating meets or exceeds 400 lbs. When in doubt, do not use cylinder. Refrigerant Lines The compressor POE oil for R-410A units is extremely susceptible to moisture absorption and could cause compressor failure. Do not leave system open to atmosphere any longer than necessary for installation. Use only refrigerant grade (dehydrated and sealed) copper tubing to connect the condensing unit with the indoor evaporator. After cutting the tubing, install plugs to keep refrigerant tubing clean and dry prior to and during installation. Tubing should always be cut square keeping ends round and free from burrs. lean the tubing to prevent contamination. Do NOT let refrigerant lines come in direct contact with plumbing, ductwork, floor joists, wall studs, floors, and walls. When running refrigerant lines through a foundation or wall, openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap between foundation or wall and refrigerant lines should be filled with a pliable silicon-based caulk, RTV or a vibration damping 2

3 material. Avoid suspending refrigerant tubing from joists and studs with rigid wire or straps that would come in contact with the tubing. Use an insulated or suspension type hanger. Keep both lines separate and always insulate the suction line. These sizes are recommended for line lengths of 79 feet or less. For other line sizing option or runs of more than fifty feet, refer to Remote ooling Service Manual, or TP-106 Long Line Set Application R-22, or TP-107 Long Line Set Application R- 410A or contact your distributor for assistance. REOMMENDED INTERONNETING TUBING (Ft) ond * Unit Line Diameter (In. OD) Tons Suct Liq Suct Liq Suct Liq 1 1/2 /8 1/4 3/4 3/8 3/4 3/8 2 /8 1/4 3/4 3/8 3/4 3/8 2 1/2 /8 1/4 3/4 3/8 7/8 3/8 3 3/4 3/8 7/8 3/8 1 1/8 3/8 3 1/2 7/8 3/8 1 1/8 3/8 1 1/8 3/8 4 7/8 3/8 1 1/8 3/8 1 1/8 3/8 7/8 3/8 1 1/8 3/8 1 1/8 3/8 * Lines greater than 79 feet in length or vertical elevation changes more than 0 feet refer to the Remote ooling Service Manual or contact your distributor for assistance. NOTE: Line sets for VS130181**, VS130241**, and VS130301** shall not exceed 7 feet. Where possible, drain as much residual compressor oil from existing systems, lines, and traps; pay close attention to low areas where oil may collect. NOTE: If changing refrigerant types, ensure the indoor coil and metering device is compatible with the type of refrigerant being used; otherwise, the indoor coil must be replaced. Burying Refrigerant Lines If burying refrigerant lines can not be avoided, use the following checklist. 1. Insulate liquid and suction lines separately. 2. Enclose all underground portions of the refrigerant lines in waterproof material (conduit or pipe) sealing the ends where tubing enters/exits the enclosure. 3. If the lines must pass under or through a concrete slab, ensure lines are adequately protected and sealed. Refrigerant Line onnections IMPORTANT To avoid overheating the service valve, TXV valve, or filter drier while brazing, wrap the component with a wet rag, or use a thermal heat trap compound. Be sure to follow the manufacturer s instruction when using the heat trap compound. Note: Remove Schrader valves from service valves before brazing tubes to the valves. Use a brazing alloy of 2% minimum silver content. Do not use flux. Torch heat required to braze tubes of various sizes is proportional to the size of the tube. Tubes of smaller size require less heat to bring the tube to brazing temperature before adding brazing alloy. Applying too much heat to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed. Note: The use of a heat shield when brazing is recommended to avoid burning the serial plate or the finish on the unit. 1. The ends of the refrigerant lines must be cut square, deburred, cleaned, and be round and free from nicks or dents. Any other condition increases the chance of a refrigerant leak. Insulation is necessary to prevent condensation from forming and dropping from the suction line. Armflex (or satisfactory equivalent) with 3/8 min. wall thickness is recommended. In severe conditions (hot, high humidity areas) 1/2 insulation may be required. Insulation must be installed in a manner which protects tubing from damage and contamination Sweep the refrigerant line with nitrogen or inert gas during brazing to prevent the formation of copper-oxide inside the refrigerant lines. The POE oils used in R-410A applications will clean any copper-oxide present from the inside of the refrigerant lines and spread it throughout the system. This may cause a blockage or failure of the metering device. 3. After brazing, quench the joints with water or a wet cloth to prevent overheating of the service valve. 4. Ensure the filter drier paint finish is intact after brazing. If the paint of the steel filter drier has been burned or chipped, repaint or treat with a rust preventative. This is especially important on suction line filter driers which are continually wet when the unit is operating. NOTE: Be careful not to kink or dent refrigerant lines. Kinked or dented lines will cause poor performance or compressor damage.

4 Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing. NOTE: Before brazing, verify indoor piston size by checking the piston kit chart packaged with indoor unit. Leak Testing (Nitrogen or Nitrogen-Traced) To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gases for leak testing of a refrigeration system. To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 10 psig. Pressure test the system using dry nitrogen and soapy water to locate leaks. If you wish to use a leak detector, charge the system to 10 psi using the appropriate refrigerant then use nitrogen to finish charging the system to working pressure then apply the detector to suspect areas. If leaks are found, repair them. After repair, repeat the pressure test. If no leaks exist, proceed to system evacuation. System Evacuation ondensing unit liquid and suction valves are closed to contain the charge within the unit. The unit is shipped with the valve stems closed and caps installed. Do not open valves until the system is evacuated. REFRIGERANT UNDER PRESSURE! Failure to follow proper procedures may cause property damage, personal injury or death. NOTE: Scroll compressors should never be used to evacuate or pump down a heat pump or air conditioning system. Prolonged operation at suction pressures less than 20 psig for more than seconds will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seal. 1. onnect the vacuum pump with 20 micron capability to the service valves. 2. Evacuate the system to 20 microns or less using suction and liquid service valves. Using both valves is necessary as some compressors create a mechanical seal separating the sides of the system. 3. lose pump valve and hold vacuum for 10 minutes. Typically pressure will rise during this period. If the pressure rises to 1000 microns or less and remains steady the system is considered leak-free; proceed to startup. 4 VAUUM IN MIRONS LEAK(S) PRESENT ONDENSIBLES OR SMALL LEAK PRESENT NO LEAKS NO ONDENSIBLES MINUTES If pressure rises above 1000 microns but holds steady below 2000 microns, moisture and/or noncondensibles may be present or the system may have a small leak. Return to step 2: If the same result is encountered check for leaks as previously indicated and repair as necessary then repeat evacuation. If pressure rises above 2000 microns, a leak is present. heck for leaks as previously indicated and repair as necessary then repeat evacuation. Electrical onnections HIGH VOLTAGE! Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death due to electric shock. Wiring must conform with NE or E and all local codes. Undersized wires could cause poor equipment performance, equipment damage or fire. To avoid the risk of fire or equipment damage, use copper conductors. NOTIE Units with reciprocating compressors and non-bleed TXV s require a Hard Start Kit. The condensing unit rating plate lists pertinent electrical data necessary for proper electrical service and overcurrent protection. Wires should be sized to limit voltage drop to 2% (max.) from the main breaker or fuse panel to the condensing unit. onsult the NE, E, and all local codes to determine the correct wire gauge and length. Local codes often require a disconnect switch located near the unit; do not install the switch on the unit. Refer to the installation instructions supplied with the indoor furnace/air handler for specific wiring connections and indoor unit configuration. Likewise, consult the instructions packaged with the thermostat

5 for mounting and location information. Overcurrent Protection The following overcurrent protection devices are approved for use. Time delay fuses HAR type circuit breakers These devices have sufficient time delay to permit the motorcompressor to start and accelerate its load. Three Phase ompressor Rotation O YLO/YI Y/Y2 YLO/YI Y/Y2 Y/Y2 YL0/Y1 G R W2 W1 B/ G R W1 W2 R Thermostat Two-Stage Heating with (Two-Stage ooling DEHUM TWIN FURNAE OR AIR HANDLER Use care when handling scroll compressors. Dome temperatures could be hot. OD UNIT Two-Stage Thermostat with Three Low Voltage Wires to Remote Three phase compressors are power phase dependent and can rotate in either direction. Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized. NOTE: When operated in reverse, a three phase scroll compressors is noisier and its current draw substantially reduced compared to marked values. To correct, disconnect power and switch any two leads at the unit contactor and re-observe. High Voltage onnections Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram provided inside the control panel cover. Low Voltage onnections ondensing unit control wiring requires 24 Volt minimum, 2VA service from the indoor transformer. Low voltage wiring for twostage units depends on the thermostat used and the number of control wires between the indoor unit and the condensing unit. Route control wires through the low voltage port and terminate in accordance with the wiring diagram provided inside the control panel cover. O Y Y REMOTE G R W1 B/ G R W1 R Y Thermostat Single-Stage Heating with (Single-Stage ooling DEHUM TWIN FURNAE OR AIR HANDLER Single-Stage Thermostat with Two Low Voltage Wires to Remote NOTE: For two-stage condensing units, refer to the Installation Instructions supplied with the variable speed indoor units for field wiring connections. System Start Up POSSIBLE REFRIGERANT LEAK To avoid a possible refrigerant leak, open the service valves until the top of the stem is 1/8 from the retainer. When opening valves with retainers, open each valve only until the top of the stem is 1/8 from the retainer. To avoid loss of refrigerant, DO NOT apply pressure to the retainer. When opening valves without a retainer remove service valve cap and insert a hex wrench into the valve stem and back out the stem by turning the hex wrench counterclockwise. Open the valve until it contacts the rolled lip of the valve body. NOTE: These are not back-seating valves. It is not necessary to force the stem tightly against the rolled lip. NOTE: Power must be supplied to the 18 SEER outdoor units containing EM motors before the power is applied to the indoor unit. Sending a low voltage signal without high voltage power present at the outdoor unit can cause malfunction of the control module on the EM motor. Adequate refrigerant charge for a matching evaporator and 1 feet lineset is supplied with the condensing unit. If line set exceeds 1 feet in length, refrigerant should be added at.6 ounces per foot of liquid line. Open the suction service valve first! If the liquid service valve is opened first, oil from the compressor may be drawn into the indoor coil TXV, restricting refrigerant flow and affecting operation of the system. After the refrigerant charge has bled into the system, open the liquid service valve. The service valve cap is the secondary seal for the valves and must be properly tightened to prevent leaks. Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap. Tighten cap finger-tight and then tighten additional 1/6 of a turn (1 wrench flat), or to the following specification, to properly seat the sealing surfaces. 1. 3/8 valve to - 10 in-lbs 2. /8 valve to - 20 in-lbs 3. 3/4 valve to - 20 in-lbs 4. 7/8 valve to - 20 in-lbs

6 Do not introduce liquid refrigerant from the cylinder into the crankcase of the compressor as this may damage the compressor. POSSIBLE REFRIGERANT LEAK To avoid a possible refrigerant leak, open the service valves until the top of the stem is 1/8 from the retainer. 1. Break vacuum by fully opening liquid and suction base valves. 2. Set thermostat to call for cooling. heck indoor and outdoor fan operation and allow system to stabilize for 10 minutes for fixed orifices and 20 minutes for expansion valves. harge Verification REFRIGERANT UNDER PRESSURE! Do not overcharge system with refrigerant. Do not operate unit in a vacuum or at negative pressure. Failure to follow proper procedures may cause property damage, personal injury or death. Use refrigerant certified to AHRI standards. Used refrigerant may cause compressor damage, and will void the warranty. Most portable machines cannot clean used refrigerant to meet AHRI standards. NOTIE Violation of EPA regulations may result in fines or other penalties. Operating the compressor with the suction valve closed will void the warranty and cause serious compressor damage. Final harge Adjustment The outdoor temperature must be 60 F or higher. Set the room thermostat to OOL, fan switch to AUTO, and set the temperature control well below room temperature. After system has stabilized per startup instructions, check subcooling and superheat as detailed in the following section. Fixed Orifice To prevent personal injury, carefully connect and disconnect manifold gauge hoses. Escaping liquid refrigerant can cause burns. Do not vent refrigerant into the atmosphere. Recover all refrigerant during system repair and before final unit disposal. 1. Purge gauge lines. onnect service gauge manifold to base-valve service ports. Run system at least 10 minutes to allow pressure to stabilize. 2. Temporarily install thermometer on suction (large) line near suction line service valve with adequate contact and insulate for best possible reading. 3. Refer to the superheat table provided for proper system superheat. Add charge to lower superheat or recover charge to raise superheat. 4. Disconnect manifold set, installation is complete. Superheat Formula = Suct. Line Temp. - Sat. Suct. Temp. Expansion Valve System Single Speed Application 1. Purge gauge lines. onnect service gauge manifold tobase-valve service ports. Run system at least 10 minutes to allow pressure to stabilize. 2. Temporarily install thermometer on liquid (small) line near liquid line service valve with adequate contact and insulate for best possible reading. 3. heck subcooling and superheat. Systems with TXV ap- SYSTEM SUPERHEAT Ambient ondenser Return Air Tem perature ( 0%RH ) Inlet Tem perature Drybulb Wetbulb Drybulb Wetbulb Drybulb Wetbulb Drybulb Wetbulb Drybulb Wetbulb ( F Drybulb ) 6º 4º 70º 8º 7º 63º 80º 67º 8º 71º * NOTE: * harge super heat, all other could be ± 2 F 6

7 plication should have a subcooling of 7 ± 2 ºF and superheat of 7 to 9 ºF. a. If subcooling and superheat are low, adjust TXV to 7 to 9 ºF superheat, then check subcooling. NOTE: To adjust superheat, turn the valve stem clockwise to increase and counter clockwise to decrease. b. If subcooling is low and superheat is high, add charge to raise subcooling to 7 ± 2ºF then check superheat. c. If subcooling and superheat are high, adjust TXV valve to 7 to 9 ºF superheat, then check subcooling. d. If subcooling is high and superheat is low, adjust TXV valve to 7 to 9 ºF superheat and remove charge to lower the subcooling to 7 ± 2ºF. NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge. 4. Disconnect manifold set, installation is complete. Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp. Two Speed Application Run the remote on low stage cooling for 10 minutes until refrigerant pressures stabilize. Follow the guidelines and methods below to check unit operation and ensure that the refrigerant charge is within limits. harge the unit on low stage. 1. Purge gauge lines. onnect service gauge manifold to base-valve service ports. 2. Temporarily install thermometer on liquid (small) line near liquid line service valve with adequate contact and insulate for best possible reading. 3. heck subcooling and superheat. Systems with TXV application should have a subcooling of to 7 ºF and superheat of 7 to 9 ºF. a. If subcooling and superheat are low, adjust TXV to 7 to 9 ºF superheat, then check subcooling. NOTE: To adjust superheat, turn the valve stem clockwise to increase and counter clockwise to decrease. b. If subcooling is low and superheat is high, add charge to raise subcooling to to 7 ºF then check superheat. c. If subcooling and superheat are high, adjust TXV valve to 7 to 9 ºF superheat, then check subcooling. d. If subcooling is high and superheat is low, adjust TXV valve to 7 to 9 ºF superheat and remove charge to lower the subcooling to to 7 ºF. NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge. 4. Disconnect manifold set, installation is complete. Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp. NOTE: heck the Schrader ports for leaks and tighten valve cores if necessary. Install caps finger-tight. SATURATED SUTION PRESSURE TEMPERATURE HART SUTION PRESSURE SATURATED SUTION TEMPERATURE ºF PSIG R-22 R-410A SATURATED LIQUID PRESSURE TEMPERATURE HART LIQUID PRESSURE SATURATED LIQUID TEMPERATURE ºF PSIG R -22 R-410A n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a 12

8 Troubleshooting Information omplaint No ooling Unsatisfactory ooling System Operating Pressures POSSIBLE AUSE DOTS IN ANALYSIS GUIDE INDIATE "POSSIBLE AUSE" SYMPTOM System will not start ompressor will not start - fan runs ompressor and ondenser Fan will not start Evaporator fan will not start ondenser fan will not start ompressor runs - goes off on overload ompressor cycles on overload System runs continuously - little cooling Too cool and then too warm Not cool enough on warm days For detailed service information refer to the Remote ondensing Unit Service manual. ertain areas to cool others to warm ompressor is noisy Low suction pressure Low head pressure High suction pressure High head pressure Test Method Remedy Power Failure Test Voltage Blown Fuse Impact Fuse Size & Type Loose onnection Inspect onnection - Tighten Shorted or Broken Wires Test ircuits with Ohmmeter Open Overload Test ontinuity of Overloads Faulty Thermostat Test ontinuity of Thermostat and Wiring Faulty Transformer heck ontrol ircuit with Voltmeter Shorted or Open apacitor Test apacitor Internal ompressor Overload Open Test ontinuity of Overload Shorted or Grounded ompressor Test Motor Windings ompressor Stuck Use Test ord Faulty ompressor ontactor Test ontinuity of oil and ontacts Faulty Fan Relay Test ontinuity of oil and ontacts Open ontrol ircuit Test ontrol ircuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper ooling Anticipator heck Resistance of Anticipator Shortage or Refrigerant Test For Leaks, Add Refrigerant Restricted Liquid Line Replace Restricted Part Undersized Liquid Line Replace Line Undersized Suction Line Replace Line Not Enough Air across Indoor oil Speed Blower, heck Duct Static Pressure Too Much Air across Indoor oil Reduce Blower Speed Overcharge of Refrigerant Recover Part of harge Noncondensibles Recover harge, Evacuate, Recharge Recirculation of ondensing Air Remove Obstruction to Air Flow Infiltration of Outdoor Air heck Windows, Doors, Vent Fans, Etc. Improperly Located Thermostat Relocate Thermostat Air Flow Unbalanced Readjust Air Volume Dampers System Undersized Refigure ooling Load Broken Internal Parts Replace ompressor Broken Valves Test ompressor Efficiency Inefficient ompressor Test ompressor Efficiency High Pressure ontrol Open Reset and Test ontrol Unbalanced Power, 3PH Test Voltage Wrong Type Expansion Valve Replace Valve Expansion Valve Restricted Replace Valve Oversized Expansion Valve Replace Valve Undersized Expansion Valve Replace Valve Expansion Valve Bulb Loose Tighten Bulb Bracket Inoperative Expansion Valve heck Valve Operation Loose Hold-down Bolts Tighten Bolts NOTIE Units with rotary or reciprocating compressors and non-bleed TXV s require a Hard Start Kit. 8

CONDENSING UNIT WARNING WARNING AIR CONDITIONING INSTALLATION & SERVICE REFERENCE. Important Safety Instructions. Installation Clearances

CONDENSING UNIT WARNING WARNING AIR CONDITIONING INSTALLATION & SERVICE REFERENCE. Important Safety Instructions. Installation Clearances ONDENSING UNIT AI ONDITIONING INSTALLATION & SEVIE EFEENE Important Safety Instructions The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards.

More information

CONDENSING UNIT INSTALLATION INSTRUCTIONS

CONDENSING UNIT INSTALLATION INSTRUCTIONS ONDENSING UNIT INSTALLATION INSTRUTIONS ONDENSING UNIT SAFETY PRES...1 Important Note to the Owner Regarding Product Warranty...2 Shipping Inspection...2 odes and Regulations...2 Installation learances...2

More information

CONDENSING UNIT INSTALLATION INSTRUCTIONS. AIR CONDITIONING INSTALLATION & SERVICE REFERENCE Important Safety Instructions. Shipping Inspection

CONDENSING UNIT INSTALLATION INSTRUCTIONS. AIR CONDITIONING INSTALLATION & SERVICE REFERENCE Important Safety Instructions. Shipping Inspection INSTALLATION INSTRUTIONS ONDENSING UNIT AIR ONDITIONING INSTALLATION & SERVIE REFERENE Important Safety Instructions The following symbols and labels are used throughout this manual to indicate immediate

More information

CONDENSING UNIT INSTALLATION INSTRUCTIONS

CONDENSING UNIT INSTALLATION INSTRUCTIONS CONENSING UNIT INSTALLATION INSTRUCTIONS CONENSING UNIT SAFETY...1 INSTALLATION REQUIREMENTS...2 Tools and Parts...2 System Requirements...3 Location Requirements...3 Electrical Requirements...4 INSTALLATION

More information

CONDENSING UNIT IMPORTANT SAFETY INSTRUCTIONS SHIPPING INSPECTION CODES & REGULATIONS AIR CONDITIONING INSTALLATION & SERVICE REFERENCE

CONDENSING UNIT IMPORTANT SAFETY INSTRUCTIONS SHIPPING INSPECTION CODES & REGULATIONS AIR CONDITIONING INSTALLATION & SERVICE REFERENCE CONDENSING UNIT AIR CONDITIONING INSTALLATION & SERVICE REFERENCE IMPORTANT SAFETY INSTRUCTIONS The following symbols and labels are used throughout this manual to indicate immediate or potential safety

More information

CONDENSING UNIT IMPORTANT SAFETY INSTRUCTIONS FEATURES SHIPPING INSPECTION CODES & REGULATIONS AIR CONDITIONING INSTALLATION & SERVICE REFERENCE

CONDENSING UNIT IMPORTANT SAFETY INSTRUCTIONS FEATURES SHIPPING INSPECTION CODES & REGULATIONS AIR CONDITIONING INSTALLATION & SERVICE REFERENCE CONDENSING UNIT AIR CONDITIONING INSTALLATION & SERVICE REFERENCE IMPORTANT SAFETY INSTRUCTIONS The following symbols and labels are used throughout this manual to indicate immediate or potential safety

More information

SHIPPING INSPECTION CODES & REGULATIONS

SHIPPING INSPECTION CODES & REGULATIONS CONDENSING UNIT HEAT PUMP INSTALLATION & SERVICE REFERENCE IMPORTANT SAFETY INSTRUCTIONS The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards.

More information

CONDENSING UNIT IMPORTANT SAFETY INSTRUCTIONS SHIPPING INSPECTION CODES & REGULATIONS HEAT PUMP INSTALLATION & SERVICE REFERENCE

CONDENSING UNIT IMPORTANT SAFETY INSTRUCTIONS SHIPPING INSPECTION CODES & REGULATIONS HEAT PUMP INSTALLATION & SERVICE REFERENCE CONDENSING UNIT HEAT PUMP INSTALLATION & SERVICE REFERENCE 2009-2014, 2016 Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com -or- www.amana-hac.com P/N:

More information

INSTALLATION INSTRUCTIONS R-410A Split System Air Conditioner

INSTALLATION INSTRUCTIONS R-410A Split System Air Conditioner Product Family: R4A3, WA3**4 These instructions must be read and understood completely before attempting installation. DANGER, WARNING, AUTION, and NOTE The signal words DANGER, WARNING, AUTION, and NOTE

More information

Installation Instructions

Installation Instructions PA13NA; PA14N; PA15N; PA16NW SPLIT -SYSTEM AIR ONDITIONER WITH R-410A REFRIGERANT 1-1/2-5 TONS Installation Instructions SAFETY ONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioners

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioners INSTALLATION INSTRUTIONS R 410A Split System Air onditioners NXA5, R4A5, WA5 These instructions must be read and understood completely before attempting installation. SAFETY ONSIDERATIONS Improper installation,

More information

VERTICAL MOUNT AIR HANDLERS

VERTICAL MOUNT AIR HANDLERS VERTICAL MOUNT AIR HANDLERS INSTALLATION INSTRUCTIONS 2005-2009 Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com -or- www.amana-hac.com P/N: IO-281J

More information

Installation Instructions

Installation Instructions A13NA 018---060 A16NA 018---030 Baset Series Air onditioners with Puronr Refrigerant Installation Instructions SAFETY ONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

INSTALLATION INSTRUCTIONS R 22 or R 407C Air Conditioner Outdoor Component

INSTALLATION INSTRUCTIONS R 22 or R 407C Air Conditioner Outdoor Component R 22 or R 407 Air onditioner Outdoor omponent R2A3**GKR, R2A3**GHR, R2A3**GLR, R2A3**AKR, R2A3**AHR These instructions must be read and understood completely before attempting installation. IMPORTANT:

More information

CONDENSING UNIT AVXC20 AIR CONDITIONING INSTALLATION & SERVICE REFERENCE

CONDENSING UNIT AVXC20 AIR CONDITIONING INSTALLATION & SERVICE REFERENCE CONDENSING UNIT AVXC20 AIR CONDITIONING INSTALLATION & SERVICE REFERENCE CAPACITOR... 27 TROUBLESHOOTING... 31 SETTING THE MODE DISPLAY... 36 7-SEGMENT DISPLAY... 42 START-UP CHECKLIST... 46 IMPORTANT

More information

HEAT PUMP UNIT AVZC20 HEAT PUMP INSTALLATION & SERVICE REFERENCE

HEAT PUMP UNIT AVZC20 HEAT PUMP INSTALLATION & SERVICE REFERENCE HEAT PUMP UNIT AVZC20 HEAT PUMP INSTALLATION & SERVICE REFERENCE CAPACITOR... 28 TROUBLESHOOTING... 33 SETTING THE MODE DISPLAY... 38 7-SEGMENT DISPLAY... 44 START-UP CHECKLIST... 47 IMPORTANT SAFETY INSTRUCTIONS

More information

Installation Instructions

Installation Instructions 24AAA5, 24AAA6 24ABB3, 24AB6 24AA4, 24A4 Single---Stage omfort Series Air onditioners with Puronr Refrigerant 1---1/2 To 5 Nominal Tons (Sizes 18 to 60) Installation Instructions SAFETY ONSIDERATIONS Improper

More information

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioner N4A3, C4A3, H4A3, T4A3, NXA6, CXA6, HXA6, TXA6

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioner N4A3, C4A3, H4A3, T4A3, NXA6, CXA6, HXA6, TXA6 N4A3, 4A3, H4A3, T4A3, NXA6, XA6, HXA6, TXA6 These instructions must be read and understood completely before attempting installation. DANGER, WARNING, AUTION, and NOTE The signal words DANGER, WARNING,

More information

CONDENSING UNIT WARNING

CONDENSING UNIT WARNING CONDENSIN UNIT HEAT PUMP INSTALLATION & SEVICE EFEENCE Important Safety Instructions The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards.

More information

UPFLOW/DOWNFLOW COILS

UPFLOW/DOWNFLOW COILS UPFLOW/DOWNFLOW COILS INSTALLATION INSTRUCTIONS 1. Important Safety Instructions The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SCU16LT Series Split System Air Conditioner WARNING

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SCU16LT Series Split System Air Conditioner WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SCU16LT Series Split System Air Conditioner WARNING The equipment covered in this manual is to be installed by trained and experienced service and installation

More information

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER! 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS INSTALLATION GUIDE R-410A ATTENTION, INSTALLER! After installing the system, show the user how to turn off electricity to the unit. Point out control and switch

More information

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES 11-AC11D2-5 INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: Condensing Units 2A7A5024-048, 2A7A4018-060, 2A7A2018-060 & 2A7A1018-060 IMPORTANT

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SHP13LE Series Split System Heat Pump

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SHP13LE Series Split System Heat Pump INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SHP13LE Series Split System Heat Pump WARNING The equipment covered in this manual is to be installed by trained and experienced service and installation technicians.

More information

38TKB Air Conditioning Unit Installation and Start-Up Instructions

38TKB Air Conditioning Unit Installation and Start-Up Instructions 38TKB Air onditioning Unit Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY ONSIDERATION Improper installation, adjustment, alteration,

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES C US INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES Made in the USA by: Goodman Manufacturing Company, L.P. I0-240B 2550 North Loop West, Suite 400, Houston, TX 77092 www.goodmanmfg.com

More information

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11 SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-479 Supersedes: NEW File: Volume

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 2SCU13 Series Split System Air Conditioner WARNING

INSTALLATION AND MAINTENANCE INSTRUCTIONS 2SCU13 Series Split System Air Conditioner WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS 2SCU13 Series Split System Air Conditioner WARNING The equipment covered in this manual is to be installed by trained and experienced service and installation

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SHP16LT Series Split System Heat Pump

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SHP16LT Series Split System Heat Pump INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SHP16LT Series Split System Heat Pump WARNING The equipment covered in this manual is to be installed by trained and experienced service and installation technicians.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2016 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Elite Series XC16 Units AIR CONDITIONER 507161-01 8/2016 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE General This

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Installation Instructions

Installation Instructions 25HHA4 Performance Series Heat Pump with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-25HHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

Installation Instructions

Installation Instructions Baset Series Heat Pumps with Puronr Refrigerant 1---1/2 To 5 Nominal Tons (Sizes 18 to 60) Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS

More information

Installation Instructions

Installation Instructions 214D, 215B, 225B Single -Stage Split System Heat Pump with Puronr Refrigerant 1 1/2 To 5 Nominal Tons Installation Instructions NOTE: Read the entire instruction manual before starting the installation.

More information

Residential Piping and Long Line Guideline

Residential Piping and Long Line Guideline AC / HP R-410A Refrigerant Systems Single-Stage, Two-Stage and Variable Speed Models Residential Piping and Long Line Guideline TABLE OF CONTENTS Safety Considerations... 2 Definitions... 2 Introduction...

More information

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE GENERAL..............................................1 SAFETY................................................1

More information

Installation Instructions

Installation Instructions Performance Series Heat Pumps with PURONr Refrigerant 1 --- 1/2 to 5 Nominal Tons Installation Instructions Fig. 1 --- A07532 NOTE: Read the entire instruction manual before starting the installation.

More information

INSTALLATION INSTRUCTIONS GPC15 / GPH16 (15/16 SEER H SERIES)

INSTALLATION INSTRUCTIONS GPC15 / GPH16 (15/16 SEER H SERIES) INSTALLATION INSTRUCTIONS GPC15 / GPH16 (15/16 SEER H SERIES) SELF-CONTAINED PACKAGE AIR CONDITIONERS AND HEAT PUMP UNITS WITH R-410A ATTENTION INSTALLING PERSONNEL Prior to installation, thoroughly familiarize

More information

ACU Split System Air Conditioners

ACU Split System Air Conditioners Installation and Maintenance Manual IM-802 Group: Unitary Part Number: IM-802 Date: August 2005 Supersedes: March 2005 ACU Split System Air Conditioners 7-1/2 & 10 TON 2004 McQuay International IM-802

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS R-410A Two-Stage Split System Air Conditioner Product Family: H4A6, C4A6, T4A6 H4A8, C4A8, T4A8 These instructions must be read and understood completely before attempting installation. DANGER, WARNING,

More information

CONDENSING UNIT WARNING

CONDENSING UNIT WARNING CONDENSIN UNIT SINLE / THEE PHASE HEAT PUMPS INSTALLATION & SEVICE EFEENCE 2010-2011 oodman Manufacturing Company, L.P. 11 San Felipe, Suite 00, Houston, TX 7706 www.goodmanmfg.com -or- www.amana-hac.com

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Refrigerant Recovery Machine. Model No Operating Manual

Refrigerant Recovery Machine. Model No Operating Manual Refrigerant Recovery Machine Model No. 25700 Operating Manual Safety Precautions WARNING : TO PREVENT PERSONAL INJURY AND / OR EQUIPMENT DAMAGE, CAUTION - Risk of injury. This equipment should only be

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS STELLAR AIR CONDITIONING UNIT SPLIT-SYSTEM COOLING CONTENTS GENERAL..................................... 2 NOMENCLATURE........................... 2 SAFETY...................................

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

CAUTION. Check Equipment and Job Site. Clearance Requirements. Unpack Unit

CAUTION. Check Equipment and Job Site. Clearance Requirements. Unpack Unit INSTALLATION IMPORTANT: Effective January 1, 2015, all split system and packaged air conditioners must be installed pursuant to applicable regional efficiency standards issued by the Department of Energy.!

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Merit Series 13ACX Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service

More information

AR SERIES COMMERCIAL AIR HANDLERS INSTALLATION & OPERATING INSTRUCTIONS

AR SERIES COMMERCIAL AIR HANDLERS INSTALLATION & OPERATING INSTRUCTIONS AR SERIES COMMERCIAL AIR HANDLERS INSTALLATION & OPERATING INSTRUCTIONS NOTE: AR models are suitable for Upflow and Horizontal Installations only. Do not use for Downflow Installations RECOGNIZE THIS SYMBOL

More information

Installation Instructions

Installation Instructions 25HBB, 25HBC Baset Series Heat Pumps with Puronr Refrigerant 1 --- 1/2 To 5 Nominal Tons Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION INSTALLATION INSTRUCTION CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS Supersedes: 550.44-N1Y (1194) 550.44-N1Y (495) MODELS H*DE018 THRU H*DE060 035-11029 WARNINGS are given to alert the installer

More information

INSTALLATION INSTRUCTIONS FOR SELF-CONTAINED PACKAGE AIR CONDITIONERS AND HEAT PUMP UNITS GPC/GPH 13 SEER M SERIES WITH R-410A

INSTALLATION INSTRUCTIONS FOR SELF-CONTAINED PACKAGE AIR CONDITIONERS AND HEAT PUMP UNITS GPC/GPH 13 SEER M SERIES WITH R-410A INSTALLATION INSTRUCTIONS FOR SELF-CONTAINED PACKAGE AIR CONDITIONERS AND HEAT PUMP UNITS GPC/GPH 13 SEER M SERIES WITH R-410A C US RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION. ATTENTION INSTALLING PERSONNEL

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M 2004 Lennox Industries Inc. Dallas, Texas KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04 Supersedes 503,249M Litho U.S.A. COMPRESSOR REPLACEMENT KIT INSTALLATION INSTRUCTIONS FOR COMPRESSOR

More information

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

Cased Aluminum Convertible Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC** 18- AH44D1-4 Cased Aluminum "Convertible" Coils 4TXCB003CC3HC 4TXCB004CC3HC 4TXCC005CC3HC 4TXCC006CC3HC 4TXCC007CC3HC 4TXCC008CC3HC 4TXCD009CC3HC 4TXCD010CC3HC May be "A" or "B" ALL phases of this installation

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 2SHP13 Series Split System Heat Pump WARNING

INSTALLATION AND MAINTENANCE INSTRUCTIONS 2SHP13 Series Split System Heat Pump WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS 2SHP13 Series Split System Heat Pump WARNING The equipment covered in this manual is to be installed by trained and experienced service and installation technicians.

More information

Installation Instructions / User s Manual NAXA00101DB Communicating Daughter Board

Installation Instructions / User s Manual NAXA00101DB Communicating Daughter Board Installation Instructions / User s Manual NAXA00101DB ommunicating Daughter Board The NAXA00101DB daughter board control allows for using 4 existing thermostat wires in an existing, finished home to communicate

More information

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS INTRODUCTION Please note that HUD Manufactured Home Construction and Safety Standard Section 3280.714, paragraph (a) and subparagraph

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS SPLIT AIR CONDITIONER OUTDOOR SECTION Models: HAC481-B HAC602-B For Use With: Matching Indoor Blower Coil Units and Matching Add On Coil Units Only Bard Manufacturing Company,

More information

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA 18- AH39D1-4 Cased Aluminum "Convertible" Coils 2/4TXCA018BC3HCA 2/4TXCA024BC3HCA 2/4TXCB025BC3HCA 2/4TXCB031BC3HCA 4TXCB032BC3HCA 2/4TXCB036BC3HCA ALL phases of this installation must comply with NATIONAL,

More information

Horizontal/Side Discharge Condensing Units

Horizontal/Side Discharge Condensing Units INSTALLATION, OPERATION & MAINTENANCE MANUAL Horizontal/Side Discharge Condensing Units Models CMA12SD-0 CMA18SD-1 CMA24SD-1 CMA30SD-1 CMA36SD-1 CMA48SD-1 517.787.2100 www.marsdelivers.com Horizontal/Side

More information

Operation and Maintenance Manual

Operation and Maintenance Manual Warranty Information Ritchie Engineering guarantees YELLOW JACKET products to be free of defective material and workmanship which could affect the life of the product when used for the purpose for which

More information

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual RecoverX Oil-Filled Hermetic Refrigerant Recovery System Operation and Maintenance Manual Table of Contents Page General Safety Instructions 2-3 System Overview 3 Operating Guide 4 Restart Procedure 4

More information

R100 Oil-Less Refrigerant Recovery Unit

R100 Oil-Less Refrigerant Recovery Unit R100 Oil-Less Refrigerant Recovery Unit Operation Manual 1 INTRODUCTION Welcome to simple, efficient refrigerant recovery with your new YELLOW JACKET Refrigerant Recovery Unit, R100. This unit combines

More information

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC ISO 9001 Certified Quality Management System SAFETY................................................

More information

XC13. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

XC13. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A. Service Literature Corp. 0521 L9 Revised 09 2007 XC13 SERIES UNITS XC13 The XC13 is a high efficiency residential split system condensing unit, which features a scroll compressor and R 410A refrigerant.

More information

PL Series Premier Indoor Plenum Coils

PL Series Premier Indoor Plenum Coils IM-PLC-0667392-04 April 2016 PL Series Premier Indoor Plenum Coils Installation Instructions GENERAL ADP evaporator coils are designed for use with condensing units or heat pump units. These instructions

More information

Installation Instructions

Installation Instructions 25HBB, 25HBC, 25HCD Comfortt Series Heat Pumps with Puronr Refrigerant 1 1/2 To 5 Nominal Tons Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY

More information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS R 410A Ducted Horizontal Air Conditioner Product Family: HC4A3 Fig. 1 - HC4A3 NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE

More information

Installation Instructions

Installation Instructions Installation Instructions SPLIT SYSTEM Premium Line AC & HP CONDENSERS Save This Manual for Future Reference 421 01 3201 07 Dec. 2004 Installation Instructions Split System Condensers Installation/ Startup

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT Concepcion Carrier Air conditioning Company Philippines INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT CONTENTS Safety Considerations 1 Complete

More information

442 Chapter 16. Figure 16-5 Gas leak detection

442 Chapter 16. Figure 16-5 Gas leak detection BRORANE BRORANEBRORANEBRORANEBRORANEBRORANEBRORANEBRORANE 442 Chapter 16 Tur n e r BRORANE FUEL EBRORANEBRORANEBRORANEBRORANEBRORANE Figure 16-5 Gas leak detection is easy. This sensitive halide detector

More information

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

Cased Aluminum Coils Dedicated Upflow / Downflow Convertible to horizontal with separately purchased kit 18-AD32D1-3 Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit Upflow models: 4PXCAU24BS3HAA 4PXCBU24BS3HAA 4PXCBU30BS3HAA 4PXCCU30BS3HAA 4PXCBU36BS3HAA

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

Installation Instructions

Installation Instructions Installation Instructions SPLIT SYSTEM Performance Line AC & HP CONDENSERS NOTE: See Back Cover for shipping bracket Save This Manual for Future Reference 421 01 3001 07 Dec. 2004 Installation Instructions

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS INSTALLATION AND OPERATING INSTRUCTIONS HIGH-EFFICIENCY CONDENSING UNITS RAWD- 6 1 2 & 7 1 2 TON RAWE - 6 1 2 & 7 1 2 TON! RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!! WARNING

More information

Safety Labeling and Signal Words

Safety Labeling and Signal Words Theseinstructionsmust bereadand understoodcompletelybeforeattemptinginstallation. DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 205 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Merit Series ML4XC Units AIR CONDITIONERS 507524-0 07/205 Litho U.S.A. Improper installation, adjustment, alteration, service or

More information

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X Installation Truck Refrigeration & Commissioning Manual: INSTALLATION AND COMMISSIONING MANUAL for Neos 100S Integra 20X, 30S, 35X, 40X, 50X Direct Drive Refrigeration Units 2017 Carrier Corporation Printed

More information

Installation Instructions

Installation Instructions Evaporator Coil A Coil --- Cased Multipoise NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

For 18 SEER R410A Series Unitary Ducted Split AC

For 18 SEER R410A Series Unitary Ducted Split AC For 18 SEER R410A Series Unitary Ducted Split AC Thermostat Owner's Manual Commercial Air Conditioners Thank you for choosing MRCOOL, please read this owner s manual carefully before operation and keep

More information

Installation Instructions

Installation Instructions Installation Instructions For R410-A Refrigerant SPLIT SYSTEM Premium Line AC CONDENSERS Save This Manual for Future Reference 421 01 3204 03 Dec. 2004 I Installation Instructions R410-A Split System Condensers

More information

LENNDX INSTALLATION INSTRUCTIONS. IIlIIIIIIIIIIIIIIIIIIIIIIIHI A, WARNING A, WARNING WARNING RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE

LENNDX INSTALLATION INSTRUCTIONS. IIlIIIIIIIIIIIIIIIIIIIIIIIHI A, WARNING A, WARNING WARNING RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE LENNDX,1,_2000 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS HS40 S UNITS CONDENSING UNITS lie_ :.) Technical 504,186M.LU_ Publications 11/2002 Lithe U.S.A. Supersedes 4/2000 HS40

More information

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215) National Comfort Products 539 Dunksferry Road Bensalem, PA 19020 (215) 244-1400 1-800-523-7138 Fax: (215) 244-9579 SPLIT-SYSTEM CONDENSING UNIT INSTALLATION INSTRUCTIONS 1000 3000 4000 SERIES 1. 2. 3.

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Dave Lennox Signature Collection XC15 Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment,

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2015 Lennox Industries Inc. Dallas, Texas, USA RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE General This XP20 outdoor heat pump is designed for use with HFC-410A refrigerant only. This unit must be installed

More information

TSA WARNING. Service Literature TSA SERIES UNITS. 6, 7.5, 10, 12.5, 15 & 20 ton

TSA WARNING. Service Literature TSA SERIES UNITS. 6, 7.5, 10, 12.5, 15 & 20 ton Service Literature Corp. 0903 L1 Revised: March 2011 TSA SERIES UNITS TSA 6, 7.5, 10, 12.5, 15 & 20 ton The TSA units are designed for light commercial applications, with a remotely located blower coil

More information