Close Control Twin Circuit Air Cooled Range

Size: px
Start display at page:

Download "Close Control Twin Circuit Air Cooled Range"

Transcription

1 Close Control Twin Circuit Air Cooled Range Air Cooled Units R407C Installation, Operation & Maintenance Manual 50Hz/60Hz

2 INSTALLATION OPERATION & MAINTENANCE MANUAL Index Description Page INSTALLATION General 3 Mechanical Installation 4 Air Cooled Units 5 Setting the Thermostatic Expansion Valve 7 Water and Drain Connections 8 General Engineering Details 9 Electrical Connections 10 Electrical Details 11 OPERATION General EC Fan Heating Operation 14 Cooling Operation 14 Dehumidification Control 15 Humidification Cycle 15 PGD Display 17 Alarms 18 MAINTENANCE General 21 Common Components 21 Refrigeration Components 22 Air Cooled Units 23 Electric Panel Inspection & Functional Tests 23 Steam Humidifier Canister Cleaning & Removal 24 Thermostatic Expansion Valve Calibration 24 Refrigerant Control Settings 24 Fault Finding Guide 25 Monthly Maintenance Inspection Check 28 Annual Maintenance Inspection Check 29 While every precaution has been taken to ensure accuracy and completeness in this manual, Edpac assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Document reference E

3 INSTALLATION GENERAL INSPECTION On receiving the equipment it should be checked to ensure that it is complete and in perfect condition. The carrier should be notified immediately, in writing, of any damage that might have been caused in transit. HANDLING Always keep the unit vertically upright and do not leave it out in the open. The unit can be moved with a pallet truck. If a forklift is being used ensure the forks extend beyond the pallet. Care should be taken not to damage the bottom of the unit. If a crane is being used to move the unit leave the packaging intact and place spreader bars across the top of the unit to prevent the slings causing damage. The unit should be moved as near as possible to the installation position before removing the cardboard packing and the pallet. UNPACKING THE UNIT 1) Cut the three straps binding the unit taking care to avoid any backlash caused by their tightness. 2) Remove the lid. 3) The cardboard sleeve will then unravel itself revealing a plastic dust cover. 4) Remove dust cover. If it is a downflow model, to remove the front panels use the key attached to the sensor on the top of the unit. 5) Remove the two bolts securing the unit to the skid (19 mm spanner). 6) Manoeuvre the unit carefully from the pallet. If it is necessary, use rollers underneath the unit to locate it in its final position. 7) If the unit requires a plenum fix same before final positioning. 8) Ensure the unit is positioned on a level floor. POSITIONING The Twin Circuit Air Cooled Range is built on a level base and its positioning is most important. The unit should be firmly supported on the floor itself or on an optional floorstand. Ensure that the unit is level in all directions as failure to do so will result in operational problems, particularly with regards to drainage. Care should be taken in manoeuvring the unit as the paintwork could be damaged. Use rollers where possible and apply pressure to the bottom of the unit for final positioning. Before final positioning ensure that inaccessible panels are correctly fitted and plenums are secured. ATTACHING THE PLENUM The plenum and unit are pre-drilled. At the time of installation remove the grilles from the plenum and secure the plenum internally by means of self tapping screws provided. Also secure to the back of the unit. AIR COOLED CONDENSERS Locate these as close to their final position as possible before uncrating. A full set of assembly instructions are attached to the unit. Headers and return bends are not to be used in the moving of the condenser. When locating the condenser ensure that it is in an open area with unrestricted airflow shaded from direct sunlight. Install in an environment free of debris to avoid the fins becoming blocked. Ensure that some form of vibration elimination is installed between the condenser legs and the roof of the building. Condensers are not to be ducted on either side. Where noise is critical in relation to the condenser make ensure that this is clearly specified at the time of order. SERVICE ACCESS Downflow Units Service of a downflow unit can be generally completed from the front of the unit. To remove certain components from the unit it may be easier and quicker to have side access to assist in these operations. When positioned there should be a minimum clearance in front of the unit of 0.6m. If it is feasible, leave a distance of 0.6m at the side of the unit. Access to the back of the unit is not necessary. It it strongly recommended to leave a distance of 0.6m at both sides of the unit. There is a minimum distance of 150mm needed above the unit to allow removal of the filters. 3

4 Upflow Units Unlike the downflow, side access is necessary for servicing the upflow. When installing ensure the left-hand side of the unit has access for the purpose of servicing, especially the motor. On the small frame the motor is actually mounted 'piggyback' on the blower and on the mid and large frame the motor is located on the left-hand side of the blower On the Twin Circuit upflow units the fan motor arrangement is such that access is required at either end of the unit. The master's motor is located to the left of the blower as standard while the slave's motor is configured to the right handside of the blower. Access to the back of the unit is not required. It it strongly recommended to leave a distance of 0.6m at both sides of the unit. The filters are located in the bottom front panel; a minimum distance of 1m is needed to allow the return air to enter the unit. Space above the unit will be determined by location. If a standard plenum is being installed the overall height of the unit is extended to 2380mm. MECHANICAL INSTALLATION SYSTEM APPLICATION To achieve maximum performance and efficient energy usage following considerations should be given. 1) The room should be sealed effectively against air and vapour to minimise the loss and infiltration of uncontrolled humidity through concrete slab, walls, ceiling, roof, doors or any other opening or aperture. 2) Room location and orientation should be considered with regard to heat load and external variables should be reduced to a minimum. 3) The room should be kept at a positive pressure by introduction of pre-treated fresh air. 4) Low resistance to conditioned air distribution can be achieved by providing the maximum raised flooring height, Room Unit Room Unit Upflow Twin Circuit Unit Service Access Downflow Twin Circuit Unit Service Access minimum cable bunching and correct position of pipework (i.e. parallel to air flow). 5) Pipework that is not isolated or is fastened inadequately can transmit vibration along its full length. 4

5 AIR COOLED UNITS GENERAL PIPING PRACTICES Refrigerant connections must be made between the indoor unit and the air cooled condenser, i.e. liquid and discharge. The indoor units are delivered with a holding pressure of 75 p.s.i. /5.4 bar. Discharge this pressure before commencing work on the unit. All pipework should adhere to national and local codes. Extreme care should be taken to keep tubing clean and dry prior to and during installation particular attention should be paid to the following points: Use only refrigeration quality copper tubing properly sealed against contamination, and always cap the free end of the tubing while carrying out installation. Do not leave compressors or filter driers open to atmosphere any longer than is necessary. When brazing refrigerant lines, an inert gas should be passed through the line at low pressure to prevent scaling and oxidisation inside the tubing. Dry nitrogen is preferred. Use only copper phosphorous brazing alloys containing at least 5% silver on copper to copper pipe joints. Where one component is other than copper, i.e. brass use a silver solder. AIR COOLED CONDENSER INSTALLATION The air cooled condenser should be installed on a level base. For roof installations, condensers should be mounted on steel supports. For ground installations, a level concrete base is sufficient to provide adequate support. The condenser mounting legs have mounting holes for securing the condenser. Care should be exercised to provide a minimum clearance of 900mm from the nearest obstruction to the coil face and fan. In addition the air inlet should face towards the prevailing winds. AIR COOLED CONDENSER ELECTRICAL CONNECTIONS In most cases the condenser power is fed from the indoor unit. Please check the unit electrical drawing. If this is not the case a separate electrical supply is required for the condensers. This power supply can either be single phase or three phase depending on the fans supplied. A low voltage control interlock between the indoor unit and the air cooled condenser is required. This interlock is connected between terminals 27 & 28 located within the indoor unit electric panel and in the control package electric box of the air cooled condenser. REFRIGERANT PIPING (AIR COOLED UNITS) As a general principle the refrigerant piping and associated components should be considered, selected and installed to ensure: 1) There is an adequate supply of liquid refrigerant to evaporator/s and an unrestricted return of the resulting vapour to the compressor. 2) A positive and continuous return of carry-over oil back to the compressor crankcase. 3) A minimum pressure drop to avoid unnecessary reduction in system capacity and overall efficiency. 4) Liquid refrigerant is prevented from entering the compressor during either running or idle time. 5) There is no possibility of oil binding or logging in sections of the discharge and suction line. LIQUID LINE The liquid line delivers a stream of liquid refrigerant to the control valve at a sufficiently high pressure to permit the control device (i.e. Thermal Expansion Valve) to operate with its intended efficiency. Since the refrigerant leaves the condenser under the influence of condensing pressure any carry-over oil that is present will also be carried along so that it passes through the control device and into the evaporator. However, excessive pressure drop should not be overlooked. This can cause the liquid refrigerant to flash or boil off before it reaches the Thermal Expansion Valve. Flash gas (as this condition is called) in the liquid line will have several undesirable effects on plant performance including reduction of the capacity of the flow control device and consequent reduction of system capacity. Also, because of intermittent flow between liquid and liquid rich vapour, erratic operation of the valve will occur and the needle & seat will eventually erode and not able to seal properly when in the closed position. This allows the evaporator to become flooded during idle periods and increases the risk of liquid refrigerant entering the compressor at start-up. Since the liquid leaving the condenser will normally be sub-cooled by about 5 C, liquid flashing would not normally occur unless the overall pressure drop across this part of the system exceeded around 40 kpa(5-6 psi), provided there is no extra heat picked up by the liquid line from some other external source. If the pressure drop is allowed to become greater than the value above, or if the temperature becomes higher than its sub-cooled temperature, then some flashing will occur due to the pressure on the liquid through the last part of the liquid line is below the pressure corresponding to its saturation temperature. 5

6 The same situation can also occur at times of low ambient/low condensing pressure, particularly if the condenser is oversized (which automatically happens with improper or insufficient fan cycling control on the condensers) or the liquid line picks up excessive heat from passing through a warm area. It should be noted that liquid line pressure drop is the sum of liquid flow resistance (frictional loss) from the tubing and all intermediate fittings (including the drier) plus loss of head pressure that may result due to vertical lift or elevation above the condenser which is a direct ratio of the refrigerant weight. At average liquid temperature of around 38 C the static pressure loss applied to elevation is approximately equal to 11.2 kpa (1.6 psi) per metre of lift for R407C. This must be considered when designing the system. R407C Recommended Liquid Line Sizes - O.D. Copper Model kw 10m 15m 20m 25m 30m mm 12 mm 16 mm 16 mm 16 mm mm 16 mm 16 mm 16 mm 16 mm mm 16 mm 16 mm 16 mm 18 mm mm 16 mm 16 mm 18 mm 18 mm mm 16 mm 18 mm 18 mm 22 mm mm 18 mm 18 mm 22 mm 22 mm mm 18 mm 22 mm 22 mm 22 mm Capacities for the various sizes of liquid lines are included in the Pipe Size Table. The table indicates the unit type and the refrigerant circuit size in the unit. There are two refrigerant circuits per unit It should be remembered that all on-site aspects are to be taken into account in final piping selection. The fitting of a pressure relief valve & liquid receiver near the condenser is required for correct unit operation.. DISCHARGE (HOT GAS) PIPING Discharge piping is sized to maintain minimum velocities to ensure oil entrainment and acceptable pressure drop. Pipework should be sized to give a pressure drop which should not exceed 6 psi and to maintain velocities of not less than 2.54m/s in horizontal runs and down runs and not less than 5.1m/s in vertical risers. R407C Recommended Discharge Line Sizes - O.D. Copper Model kw 10m 15m 20m 25m 30m mm 22 mm 22 mm 22 mm 28 mm mm 22 mm 28 mm 28 mm 28 mm mm 28 mm 28 mm 28 mm 35 mm mm 28 mm 35 mm 35 mm 35 mm mm 28 mm 35 mm 35 mm 35 mm mm 35 mm 35 mm 35 mm 35 mm mm 35 mm 35 mm 42 mm 42 mm Linear lengths, including any vertical runs should be kept to a minimum and should not normally exceed 45 metres. Vertical risers should be fitted with oil traps at every 5 metres rise. When running liquid and discharge lines together, they should be separated by at least 50 mm and on horizontal runs, the discharge line should be located above the liquid line. EVACUATION AND LEAK TESTING After completion of pipework and leak testing, evacuation of the system is next. For satisfactory operation, the system must be leak tight, dry and free of non-condensable gases. The process for leak check and system evacuation are as follows: 1) Connect gauges to the compressor service valve ports. 2) Pressurise the system with R407C refrigerant vapour until the system and the refrigerant drum have equalised. Carry out a preliminary leak test and repair any leaks found. Using dry nitrogen increase the system pressure to 350 p.s.i. Check system for leaks. If any are found release pressure and repair. When the system is leak free release the charge. Always discharge Freon into appropriate vessels or reclaim units. Do not release Freon into the atmosphere. 3) Using a suitable vacuum pump, pull a vacuum on the system to about 20 mbar. If the moisture indicator is reluctant to show dry break the vacuum with a dry gas such as nitrogen and repeat the process. 4) Close manifold valves and switch off the vacuum pump. CHARGING THE SYSTEM (FULL CHARGE) Use only R407C Refrigerant unless otherwise stated. Isolate the system from the vacuum pump and purge connection lines to prevent air from entering the system. Open the service valves to allow refrigerant to flow into the evacuated system. 6

7 Charge system with liquid through the high side only. To allow for correct charging use the tables below. It maybe necessary to complete the charging of the unit when the compressor is running by observing the sight glass, pressures and amperage. Then pipe runs exceed 20m add refrigerant oils for tube wetting and oil level in the compressor. For each 3m of pipework over 20m add 90ml of oil and 40ml per kg of refrigerant. R407C System Charges Indoor Unit Outdoor Unit Model Charge (kg) Model Charge (kg) DTA/FTA AGS DTA/FTA AGS DTA/FTA AGS DTA/FTA AGS DTA/FTA AGS DTA/FTA AGS DTA/FTA AGS AGS R407C Approximate operating charge per 30m length Copper Tube O.D. (in) Liquid Line (kg) Discharge Line (kg) Notes: 1. The indoor unit system change is per circuit. 2. The outdoor unit system change is per condenser. If you have a split circuit condenser, use half the tabulated changer per circuit. GENERAL ARRANGEMENT DRAWING SYSTEM COMPONENTS 1) Evaporator Coil. 2) Liquid Distributor. 3) Thermostatic Expansion Valve (externally equalised). 4) Liquid Line Solenoid Valve (optional). 5) Liquid Sight Glass (include. moisture indicator). 6) Filter Drier 7) Hermetic Compressor. 8) Compressor Service Valves. 9) High Pressure Switch (man. reset). 10) Low Pressure Switch (auto. reset). 11) Check Valve (See Note). 12) Fan speed Controller (pressure operated head pressure control). 13) Pressure relief Valve (See Note). 14) Air Cooled Condenser. 15) Liquid Receiver (See Note). Note: Items 11, 13 and 15 are field fitted by others. Suction Line M Discharge Line Liquid Line SETTING THE THERMOSTATIC EXPANSION VALVE The thermostatic expansion valve is factory-set but if for some reason, the superheat needs to be adjusted, use the following procedure. 1) Have the unit running as near as possible to design conditions. The compressor should be running for a period of at least 30 mins. before any adjustment should be undertaken. 2) Measure the superheat as follows: a) Measure temperature at the point where the expansion valve sensing bulb is located. A contact thermometer can be used for this purpose. b) Obtain suction pressure at the compressor suction rotolock valve and convert by use of a temp/press chart. c) The superheat value is the difference between the two readings. 3) The superheat value must be 7-8 o C; if not, set the expansion valve as follows: a) Remove the protective cover. b) As the thermostatic exp. valve is a finely balanced regulator it is strongly advised that the stem is adjusted only half a turn at a time. c) Wait for 30 mins. d) Measure the superheat again and repeat the operation, if necessary. To reduce the superheat adjust stem anticlockwise. To increase the superheat adjust stem clockwise. 7

8 WATER AND DRAIN CONNECTIONS ELECTRODE BOILER STEAM HUMIDIFIER Water is fed from the mains supply to the humidifier inlet solenoid valve. The connection to the solenoid valve is a 3/4 male connection. The feed water characteristics should comply with the following values: Characteristic Minimum Maximum Feed Water Pressure 1 bar 10 bar Electric Conductivity at 25 o C 400 µs/cm 800 µs/cm Impurity Size mm Feed Water Hardness French Degrees In the case of high water pressure, a pressure reducing valve calibrated to between 3-4 bar should be fitted. Inlet water temperature must not exceed 50 o C. It is recommended to install a shut-off valve and a mechanical filter with the wire mesh size less than 50µm. The humidifier pan drain connection is a 22 mm female connection. The humidifier drain can be discharged into the standard drainage system via a rubber or plastic hose suitable for temperatures up to 100 o C. The hose should have a minimum internal diameter of 22mm. A trap or vertical loop should be fitted in the tubing to prevent blow back or odours and ensure that the drain has a fall of not less than 1:50. Note: Do not feed demineralised water into the humidifier. CONDENSATE DRAIN Install a drain pipe from the base of the drainpan (typically a 1" female B.S.P. fitting). Insulating this drain pipe is not necessary. It is advised to fit a trap in this drainpipe. Copper pipe should be used for drains on units with humidifiers. If the system is equipped with a condensate pump, install a check valve on the discharge line of the pump to prevent backfilling the pump reservoir. 8

9 GENERAL ENGINEERING DETAILS DOWNFLOW OR UPFLOW UNITS Unit Size Coil Data Coil Face Area - DX type m Circuit Quantity No Rows Coil Drain Connection BSPF inch ¾ ¾ ¾ ¾ ¾ ¾ ¾ Air Side Data Air Volume m 3 /hr External Static Pressure ESP Pa Standard FC Centrifugal Fan Quantity Fan Motor kw Motor Quantity Optional EC Plug Fan Quantity Fan Diameter Fan Motor kw Fan Absorbed Power kw Filter Data Downflow Filter Size Code Downflow Filter Quantity No Upflow Filter Size Code Upflow Filter Quantity No Humidifier Data Inlet Connection BSPM inch Drain Connection BSPF inch Water Feed Pressure Bar French Degrees Water Hardness Noise Data Freefield SPL dba Compressor Data Scroll Compressor 50Hz - ZR72 ZR94 ZR108 ZR144 ZR160 ZR190 ZR250 Compressor Quantity No Scroll Compressor 60Hz - ZR61 ZR81 ZR94 ZR108 ZR144 ZR160 ZR190 Compressor Quantity No Piping Data Discharge Connection Size mm Liquid Connection Size mm Condenser Connections Inlet/Outlet 30 C mm 28/22 28/22 35/28 35/28 35/28 35/28 35/28 Condenser Connections Inlet/Outlet 35 C mm 28/22 35/28 35/28 35/28 35/28 35/28 35/28 Condenser Connections Inlet/Outlet 40 C mm 35/28 35/28 35/28 35/28 35/28 35/28 42/35 Condenser Connections Inlet/Outlet 45 C mm 35/28 35/28 35/28 42/35 42/35 42/35 28/22 Condenser Connections Inlet/Outlet 50 C mm 35/28 35/28 42/35 28/22 28/22 28/22 35/28 Dual Cool Chilled Water Data Coil Face Area m Chilled Water F&R Pipe Size mm Control Valve Size mm Control Valve Kv Notes: 1. Indoor unit Freefield SPL dba levels are measured at 3m. 2. Downflow Filter Size Code: 1 = 495mm x 545mm, 2 = 545mm x 622mm, 3 = 545mm x 595mm. 3. Upflow Filter Size Code: 1 = 445mm x 622mm, 2 = 545mm x 622mm, 3 = 545mm x 895mm. 4. All filters are 100mm thick and have an efficiency rating of G4 in accordance with EU Standard EN Water feed electrical conductivity for the humidifier should be in the range of microsiemens. 6. For correct installation pipe sizes refer to Refrigerant pipe sizing tables. 9

10 ELECTRICAL CONNECTIONS A correct electrical connection carried out accurately and in compliance with local regulations, is extremely important in order to prevent accidents and ensure long troublefree operation of the equipment. Before working on the electric parts of the unit, ensure that the power is off and that the main power disconnect switch on the front pillar is open. The first step is to ensure that the supply voltage corresponds to the nominal data o the unit (voltage, phase, frequency) shown on the unit nameplate. The location of the unit nameplate is above the electric panel on the Downflow Units and the fan blower housing on the Upflow Units. The electrical supply cable is passed through the knockout provided in the unit base or alternatively through one of the other knockouts provided on the unit panels. The cable should be properly glanded at this point and the flying leads run to the main power disconnect switch. Fix the ends of the supply cable to the switch terminals and tighten the terminal screws. The following charts outline the main electrical loadings for each model to be used when calculating the unit full load amps (FLA). The following values indicated are at various nominal supply characteristic of 400V/3Ph/50Hz, 220V/3Ph/60Hz, 380v/3Ph/60Hz, 460V/3Ph/60Hz 10

11 ELECTRICAL DETAILS 400V/3PH/50Hz Fans FLA Reheat FLA Humidifier FLA Scroll Compressor FLA Condenser 30 C Condenser 35 C Condenser 40 C Condenser 45 C Condenser 50 C V/3PH/60Hz Fans FLA Reheat FLA Humidifier FLA Scroll Compressor FLA Condenser 30 C Condenser 35 C Condenser 40 C Condenser 45 C Condenser 50 C V/3PH/60Hz Fans FLA Reheat FLA Humidifier FLA Scroll Compressor FLA Condenser 30 C Condenser 35 C Condenser 40 C Condenser 45 C Condenser 50 C V/3PH/60Hz Fans FLA Reheat FLA Humidifier FLA Scroll Compressor FLA Condenser 30 C Condenser 35 C Condenser 40 C Condenser 45 C Condenser 50 C Notes: 1. FLA = Full Load Amps. 2. Unit maximum FLA is the total of the components, which operate during maximum electrical load conditions. For full function units with humidifier & electric reheat the maximum FLA would be in dehumidification mode ie. cooling + reheat or in cooling and humidification mode ie. cooling + humidifier. 3. In dehumidification mode, calculate the max FLA based on single compressor FLA as only one compressor operates in this mode. Tabulated values for compressors above are for two compressors. 4. In cooling and humidification mode, calculate the max FLA based on dual compressor FLA as both compressors and the humidifier operate in this mode. 11

12 OPERATION GENERAL MICROPROCESSOR CONTROLS All Units shall be fitted as standard with the latest Delta range of DIN rail mounted Microprocessor Controls. The Control System utilises a main Microprocessor Interface Board equipped with a set of terminals necessary to connect the Board to the controlled devices.all software is permanently stored in flash RAM and is therefore protected even in the event of a power failure. Unit software is uploaded to the Microprocessor using a RAM key. On multi unit sites, this quickens unit commissioning. The software can also easily be changed or upgraded on site by qualified service personnel. Note: For more detailed information refer to Detailed Controls Manuals. 1) DELTA2 RANGE MICROPROCESSOR CONTROLLER SYSTEM PROGRAMMING MANUAL. GENERAL SYSTEM OPERATION Unit operation is completely automatic. The sequence below explains how the unit operates: The air, drawn in by the fan(s), enters the unit through top of the unit or the inlet grille. The air is immediately filtered. The temperature & relative humidity sensor verifies the condition of the inlet air and relays this to the microprocessor controller. The controller compares this information to the set point and proportional band values programmed into its memory. it then commands the air conditioner to treat the air as appropriate. CUSTOMER CONNECTIONS Power cables to the load break switch should be sized in compliance with local codes (see electrical data for permissible fuse size). Power cables required are 3 phase and a neutral (2.5mm minimum size neutral) and appropriately sized ground. The ground connection is vital. External device power / control connections are as follows: a) Connections to the condenser b) Connection to the remote shutdown feature is via terminals 15 & 16. Normally Closed N/C Unit On, Normally Open N/O Unit Off by Remote. A relay is required for this option. c) Connections for the external alarm relay's are via terminals 18, 19 & 20, (250 VAC rated - 10 Amps). Volt Free Contacts. d) Externally required A.C. voltage supplies are not to be taken from the unit, interface relays are to be utilised for these applications. INITIAL START UP a) On initial start-up, the crankcase heaters must be energised for 3 hours before starting the compressor. Do not engage the `On/Off' button on the keypad or run the compressor through the `Service Access' level during this period. The controller will display the following message: SYSTEM BOOT PLEASE WAIT. b) After a 5 second delay the controller will display the following: AIRFLOW OPERATION 13:58 12/02/97 MOI Temperature: 23.4 deg.c Humidity: 37.7 RH% UNIT ON a) When the electrical power has been energised for at least 3 hours, the unit may be energised by pressing the "On/Off" key on the keypad. The fan contactor KM1 will energise establishing airflow. 12

13 POWER FAILURE, INTERRUPTION OR SYSTEM RESET a) Should a `brownout' (where voltage is low enough to cause the electronics to fail) or electrical power failure occur, the controller will be alerted as the voltage begins to drop. It will then de-energise all contactors. b) During power failure all data entered through the keypad will be held in a memory back-up which is supported by an Eprom. The Eprom will retain data indefinitely without external power. c) If a unit is in the "RUN" mode when a power failure occurs, then, upon power restoration the unit will automatically commence "RUN" operation. The settle timer will count down to zero and at zero the unit will then continue as outlined in the Airflow, Temperature Control and Humidity Control sections. EC FAN OPERATION GENERAL The EC plug fan is a backward curved fan with an integrated EC electrically commutated motor which is controlled directly from the microprocessor using a 0-10V output. Options on setup are: Strategy 1: Fixed speed Strategy 2: Track temperature band Strategy 3: Maintain pressure setpoint Strategy 4: Control from BMS Strategy 5: Maintain airflow setpoint Dehumidification control mode FIXED SPEED A fixed 0-10V signal is set through the user display to operate the fan at a constant speed. TRACK TEMPERATURE BAND The unit is set up to track the heating and cooling bands with set voltage limits. Max voltage / fan air volume is at set point plus control band & min voltage / fan air volume at set point Max voltage / air volume is typically design air volume and min air volume is typically around 60% for chilled water units. Minimum value needs to insure that there are no hot spots due to lack of airflow and that there is no loss of sensible cooling capacity to latent cooling capacity at the cooling coil. MAINTAIN PRESSURE SETPOINT The microprocessor reads the underfloor pressure via a pressure transducer. The fan speed is then controlled to maintain a fixed underfloor pressure at all times. Pressure setpoint and min & max voltages are input through the user display. A reading of the underfloor pressure can also be viewed. CONTROL FROM BMS The speed of the fan can be controlled directly from a BMS if one of the optional BMS interface cards are installed in the unit. The BMS writes a value of between 0 & 100.0% to an analog BMS address. The fan then operates to this speed. Min and max voltage can be input through the user display to insure the fan operates within acceptable limits. MAINTAIN AIRFLOW SETPOINT The microprocessor calculates the airflow through the unit with the use of a pressure transducer and a special inlet ring across one of the fans designed for measuring airflow. PID control in then utilized to control the speed of the fans to insure a steady supply air volume. Airflow setpoint and min & max voltages are input through the user display. A reading of the total airflow through the unit can also be viewed. DEHUMIDIFICATION CONTROL MODE Unit set up to give a reduced fan air volume in dehumidification mode to conserve energy in dehumidification while quickly achieving the dehumidification effect at the cooling coil. This output voltage is again user selectable. 13

14 HEATING OPERATION GENERAL This can take one of two forms: Electrical heating: The electric elements heat the air passing over them. Heating is supplied by 3 elements configured to support 2 stages of heating. Airflow has to be established before the elements are energised. The heaters are protected by a manual reset thermostats. This thermostat is a capillary type stat positioned across the coil near the elements. Hot Water Heating (optional): If hot water is available this flows through the hot water coil thus heating the air passing over it. The hot water flow is controlled by an on-off (2 or 3-way) valve. ELECTRIC HEATING CAUTION: When commissioning the heater stage, be aware that the electric heater elements may at first give off smoke and may cause smoke detectors on site to alarm, e.g. Halon System. When the supply airflow is established, a drop in return air temperature below the return air setpoint (default 22.0 Deg. C) will cause the controller to call for Heating Stage 1. The contactor KM6 will energise. If the return air temperature falls (default 1.0 Deg. C) below the return air setpoint, the controller will call for Heating Stage 2. The contactor KM7 will energise. A rise in return air temperature below the return air temperature setpoint will cancel heating stage 2. Contactor KM7 wills de-energise. As the return air temperature rises still further, Heating Stage 1 will be cancelled above the return air temperature setpoint, contactor KM6 will de-energise. ELECTRIC HEATER PROTECTION & ALARMS a) The electric heaters are protected by one high temperature stats (RS1) which is fitted in the heater termination box. b) RS1 is a capillary type temperature stat. This capillary wrapped around the electric heater elements. If the temperature of the heater elements rises above 145 Deg. C the stat contacts will open and electric heating will be terminated. c) When the return air temperature drops sufficiently RS1 can be manually reset. Electric heating will continue as normal. HOT WATER REHEAT a) Hot Water Heating occurs when the return air temperature falls below the return air temperature setpoint. The solenoid valve or modulating valve will energise. b) As the return air temperature rises above the return air setpoint the controller will cancel the heating process by deenergising the solenoid valve or modulating valve. Note: Heating can occur when compressor 1 is operating in the dehumidification mode and the return air temperature is below the return air temperature setpoint by the appropriate amount. COOLING OPERATION COOLING FOR AIR COOLED UNITS A winter start timer is activated when cooling is required. The low pressure switch is by-passed to allow the suction pressure to stabilise at start up. It is preset for 5 minutes. If after the 5 minutes has timed out the low pressure switch has not made, then the display will indicate a "Low Compressor" alarm. COOLING OPERATION 1 st CIRCUIT a) Mechanical cooling can only occur when airflow has been established. b) After the initial switch on period the refrigeration circuit should be in a pumped down status, ready for commencement of cooling stages. Contactor KM3 de-energised. c) When the return air temperature rises above the return air temperature setpoint, plus control band, the controller will activate the cooling process. The winter start timer (KT1) will by pass the low pressure switch for a set period of time and energise the compressor contactor (KM3). d) After the time-out period of the timer (KT1-default 3 min.) the evaporator pressure will have stabilised allowing the compressor contactor (KM3) to be fed through the low pressure switch (LP1). e) When the return air temperature decreases above the return air temperature setpoint the controller will cancel the cooling stage. When the low pressure switch (LP1) opens the compressor will de-energise. 14

15 COOLING OPERATION - BOTH CIRCUITS a) Mechanical cooling can only occur when airflow has been established. After the initial switch on period both refrigeration circuits should be in a finished pumped down status ready for a commencement of cooling. Contactors KM3 & KM4 will be de-energised. b) When the return air temperature rises above the return air temperature setpoint (default 22.0 Deg. C) the controller will activate one stage of cooling. The refrigeration circuits work on an auto rotating, lead/lag compressor basis. c) If the return air temperature rises further above the return air temperature setpoint the controller will activate the second stage of cooling. d) If the return air temperature decreases above the return air temperature setpoint the controller will revert to one stage of cooling. e) If the return air temperature decreases further above the return air temperature setpoint the controller will cause the unit to stop cooling. COMPRESSOR PROTECTION All compressors are protected by low and high pressure switches. When a Cooling Stage is energised, the low pressure switch is ignored by the controller for the first three minutes. After this period the refrigerant evaporator pressure should have stabilised. The high pressure stat HP1 is monitored from commencement of the cooling process. Should a high or low pressure alarm be detected by the controller, the affected cooling stage will be de-energised. The other cooling stage (Duplex/Twin Circuit) will be energised if not already energised. DEHUMIDIFICATION CONTROL Dehumidification is provided by the cooling mode of the unit. In air, glycol or water cooled units the compressor provides the dehumidification operation. On chilled water units dehumidification is provided by having the modulating valve fully open. On Duplex/Twin Circuit models dehumidification is handled by the master module. Dehumidification only takes place when airflow is established. a) With the airflow established, an increase in return air relative humidity above the return air relative humidity setpoint (default 50.0%) will prompt the controller to call for dehumidification. The winter start timer (KT1) will by-pass the low pressure switch (LP1) for 3 minutes and feed the compressor contactor b) Should the return air relative humidity drop above the return air relative humidity setpoint, the controller will cancel the dehumidification stage. c) Heating can only occur when compressor 1 is operating in the dehumidification mode and the return air temperature is below the return air temperature setpoint by the appropriate amount. DEHUMIDIFICATION OVER-RIDE a) During dehumidification, should the return air temperature drop below temperature setpoints then the controller will override the call for dehumidification until the heaters cause the return air temperature to be within setpoint tolerances and will then re-energise the dehumidification stage if it is required HUMIDIFICATION CYCLE When a call for humidification exists, the microprocessor controller sends a 24V ac signal to the humidifier contactor supplying power to the boiler cylinder electrodes. The electric power dissipated in the boiler is kept constant by measuring the amount of current flow on phase (L3) via a current transformer. As evaporation proceeds, the controller opens the fill valve allowing water to enter the cylinder via a filter and a capacity regulator to the filling cup, and from there, by gravity, to the boiler. When the water level is so high that it touches the electrodes at the top of the boiler, the fill valve is closed and the excess water is drained through overflow tube. The drain valve opens periodically to drain water and reduce salt concentration in the boiler. It is also used to drain the humidifier completely under alarm conditions. SYSTEM OPERATION The humidifier interface PCB maintains the electric current dissipated in the boiler at the programmed set point The PCB therefore changes the immersion level of the electrodes by adding or draining water from the boiler through the respective valves. The operating current may be programmed on the front display panel between 30% and 100% of the rated value of the equipment. The functions of the equipment are described below: 15

16 FILL VALVE - maintains absorbed current between -10% and +10% of set point (percentages refer to rated current) by opening or closing respectively, with the first or second thresholds. The fill valve is automatically closed when: The drain valve is opened The free surface of the water reaches the level electrodes The system is in a state of alarm DRAIN VALVE - this is opened when: The absorbed electrical current reaches set point +30% (it closes as soon as current falls set point +10%) The washing cycle (initial or periodic) is activated The system is in a state of alarm TOP LEVEL ELECTRODES - these prevent water overflowing from the boiler. When they are covered with water for approx. three seconds the valve is closed. After the level electrodes have been out of water for approx. 25 seconds, the fill valve opens again. The level electrodes also controls topping-up when absorbed current does not reach the programmed threshold because: The water conductivity is too low The electrodes are partially or totally encrusted WASHING CYCLE - this prevents excessive salt build-up inside the boiler. It is activated as follows: At regular intervals, programmable according to the size of the equipment on the basis of cumulative time of humidification, memorised while the equipment is supplied with power. Every time the electrical supply is applied or restored ALARM CONDITION - The red ALARM button on the front display panel lights up, the drain valve opens and electrical supply to the boiler is cut off when: Absorbed current exceeds 1.8 times the rated current (generally due to the fill valve overload) The valve remains open for more than 10 minutes without the threshold of current set point +10% being reached and without the level electrodes intervening (e.g., due to failure in the water supply, blocked intake filter, defective fill valve, power probe current transformer, contactor, blown fuses, encrusted electrodes, etc.). 16

17 PGD DISPLAY + Turning the unit On/Off : Pressing the ESC & the Enter / Return arrow buttons together turns on and off the unit at the display. Pressing the up arrow button followed by the Enter / Return arrow button also turns unit on/off. Follow on screen instruction. Alarm button: By pressing this button you can display the alarm that has occurred & reset it manually. When the red led indicator lights up, at least one alarm condition has occurred. If there are multiple alarms then using the arrow up & down buttons lets you scroll through them. Up arrow button: Displays the program windows and allows the user to set the value of the control parameter Down arrow button: Displays the program windows and allows the user to set the value of the control parameter. In default menu, pressing down arrow button displays unit operating mode. Enter / Return arrow button: Confirms the set data. Escape button: By pressing this button, you go back one level from where you are. Program button: By pressing this button, you get a range of sub-menu s. 17

18 ALARMS The following alarms can be activated in an alarm condition & displayed on the display screen. All alarms can be set as serious or non-serious through the keypad AL 01 AL 02 AL 03 AL 04 AL 05 AL 06 AL 07 AL 08 AL 09 AL 10 AL 11 AL 12 AL 13 AL 14 AL 15 AL 16 AL 17 AL 18 AL 19 AL 20 AL 21 AL 22 AL 23 AL 24 AL 25 AL 26 AL 27 AL 28 AL 29 AL 30 AL 31 AL 32 AL 33 AL 34 AL 35 AL 36 ALARM LIST Compressor 1 HP / Thermal Overload Compressor 2 HP / Thermal Overload Compressor 1 LP Compressor 2 LP Air Flow Alarm (Serious Alarm) Air Flow Alarm Slave Alarm Electric Reheat High Temp Trip Condensate Pump / High Water Level Smoke/Fire (Serious Alarm) Alarm Air Filter High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm High Entering Water Temperature Low Entering Water Temperature Compressor 1 Run Hours Compressor 2 Run Hours Fan Run Hours Return Air Temperature Probe Fault Or Offline Entering Water Temperature Probe Fault Or Offline External Air Temperature Probe Fault Or Offline Supply Air Temperature Probe Fault Or Offline Return Air Humidity Probe Fault Or Offline Leaving Water Temperature Probe Fault Or Offline High Leaving Water Temperature Low Leaving Water Temperature High Current Into Humidifier Lack Of Water Into Humidifier Lack Of Current Into Humidifier Alarm Clock Spare / Custom Spare / Custom Spare / Custom Water Under Floor Loss of Water Flow Alarm Default List : Actual Alarms Model Dependant 18

19 ALARMS Default List : AL 37 Alarms Probe B00 Air pressure fault or disconnected AL 38 Alarms Probe B00 fault Head press. circuit 1 AL 39 Alarms Probe B00 fault Head press. circuit 2 AL 40 Desiccant Dryer Alarm AL 41 Alarm clock AL 42 Permanent memory Read/Write error Contact factory AL 43 EC Fan Fault or Offline AL 44 Alarms EVO n1 - EEV Motor Error AL 45 Alarms EVO n1 - MOP (high temperature of evaporation) AL 46 Alarms EVO n1 - LOP (low temperature of evaporation) AL 47 Alarms EVO n1 - Low superheat alarm AL 48 Alarms EVO n1 - Low suction temperature AL 49 Alarms EVO n1 - High condensing temperature AL 50 Alarms EVO n1 - EEPROM error alarm AL 51 Alarms EVO n1 - EEV probe S1 fault AL 52 Alarms EVO n1 - EEV probe S2 fault AL 53 Alarms EVO n1 - EEV probe S3 fault AL 54 Alarms EVO n1 - EEV probe S4 fault AL 55 Alarms EVO n1 - EEV driver offline AL 56 Alarms EVO n1 - EEV driver battery discharged AL 57 Alarms EVO n2 - EEV Motor Error AL 58 Alarms EVO n2 - MOP (high temperature of evaporation) AL 59 Alarms EVO n2 - LOP (low temperature of evaporation) AL60 Alarms EVO n2 - Low superheat alarm AL 61 Alarms EVO n2 - Low suction temperature AL 62 Alarms EVO n2 - High condensing temperature AL 63 Alarms EVO n2 - EEPROM error alarm AL 64 Alarms EVO n2 - EEV probe S1 fault AL 65 Alarms EVO n2 - EEV probe S2 fault AL 66 Alarms EVO n2 - EEV probe S3 fault AL 67 Alarms EVO n2 - EEV probe S4 fault AL 68 Alarms EVO n2 - EEV driver offline AL 69 Alarms EVO n2 - EEV driver battery discharged AL 70 Alarm Compressor 1 VSD Model Dependant Actual Alarms 19

20 ALARMS AL 71 Alarm Compressor 2 VSD AL 72 Alarms Probe B00 External humidity fault AL 73 Alarm External smoke alarm (Freecooling disabled) AL 74 Alarm Ziehl-Abegg fan n1 AL 75 Warning Ziehl-Abegg fan n1 AL 76 Alarm Ziehl-Abegg fan n1 Offline AL 77 Alarm Ziehl-Abegg fan n2 AL 78 Warning Ziehl-Abegg fan n2 AL 79 Alarm Ziehl-Abegg fan n2 Offline AL 80 Alarm Ziehl-Abegg fan n3 AL 81 Warning Ziehl-Abegg fan n3 AL 82 Alarm Ziehl-Abegg fan n3 Offline AL 83 Alarm Ziehl-Abegg fan n4 AL 84 Warning Ziehl-Abegg fan n4 AL 85 Alarm Ziehl-Abegg fan n4 Offline AL 86 Alarm Ebmpapst fan n1 AL 87 Warning Ebmpapst fan n1 AL 88 Alarm Ebmpapst fan n1 Offline AL 89 Alarm Ebmpapst fan n2 AL 90 Warning Ebmpapst fan n2 AL 91 Alarm Ebmpapst fan n2 Offline AL 92 Alarm Ebmpapst fan n3 AL 93 Warning Ebmpapst fan n3 AL 94 Alarm Ebmpapst fan n3 Offline AL 95 Alarm Ebmpapst fan n4 AL 96 Warning Ebmpapst fan n4 AL 97 Alarm Ebmpapst fan n4 Offline AL 98 Analog outputs incorrectly configured check unit config. AL 99 Alarm Refrigerant leak AL 100 Low pressure circuit 1 (transducer) AL 101 Low pressure circuit 2 (transducer) AL 102 Phase rotation alarm Default List : AL 103 High pressure prevent active. Compressor capacity reduced Alarms Model Dependant Actual 20

21 MAINTENANCE GENERAL CHECKLIST SAFETY NOTE This equipment is designed for safe operation provided it is installed, maintained and serviced in accordance with the guidelines laid down in this section of the manual. They should therefore be studied in advance by any person wishing to work on the equipment The equipment contains electrical components at high voltage. The main power isolation switch should therefore be opened before access is gained to the equipment Care should be taken to avoid hands and clothing becoming entangled in the rotating parts. Care should be taken when working near the steam outlet pipe. This can remain hot for some time after the unit is shut down. Any service and maintenance operations requiring access to the inside of the equipment while in operation should be carried out by an appropriately qualified or experienced person who is fully aware of the potential dangers and precautions to be taken. The following should be incorporated in a planned maintenance schedule to ensure that the equipment is well maintained. In all cases the various sections of the equipment should be examined and any defects logged for replacement/repair. For performance analysis a detailed service/maintenance log book should be kept outlining problems encountered and defects found during routine maintenance. Examples can be found at the end of this section. COMMON COMPONENTS CABINET AND FRAME - EXAMINE 1) Examine the cabinet exterior for any obvious defects or damage and repair as necessary. 2) Remove the front, side and rear panels and examine the cabinet interior for signs of damage or corrosion. Repair any damage found and restore the surface finish where corrosion has occurred. 3) Refit the front, side and rear panels and restore the electrical supply to the unit. 4) Record and report any defects found during the inspection. DRIVE PACKAGE 1) Remove the unit front panels and inspect the fan motor for any loose electrical connections and retighten as necessary. 2) Inspect the fan impellers and remove any debris. 3) Check that the fan impellers are securely mounted on the fan shaft. Rotate the impellers and ensure freedom of movement. 4) Inspect the bearings for signs of wear. If any excessive movement is noticed the bearings must be renewed. 5) Check the drive belts monthly for signs of wear and proper tension. Pressing on the belts midway between the sheave and pulley should produce approx. 12.5mm DRIVE BELT RE-TENSIONING 1) Correctly tension the belts by adjusting the fan motor slide base as necessary. NOTE: IF BELTS APPEAR CRACKED OR WORN, THEY SHOULD BE RENEWED WITH MATCHED BELTS (IDENTICALLY SIZED). ON UNITS WITH TWIN BELT DRIVES BOTH BELTS SHOULD BE RENEWED AT THE SAME TIME. WITH PROPER CARE, BELTS SHOULD PROVIDE A LONG SERVICE LIFE. 2) After adjusting or renewing the belts, always check that the motor mounts are tight. Loose mounts will produce vibration that may damage the unit. AIRFLOW SWITCH 1) Open the unit front panel and inspect the airflow switch located below the electric panel for any loose electrical connections and retighten as necessary. 2) Examine the pressure sensing tube between the switch and the fan casing for defects, damage and loose connections. Renew the tube if necessary. 3) Refit the unit front panel and restore the electrical supply to the unit. 4) Record and report any defects found during the inspection. 21

22 AIR FILTERS To maintain efficient operation, the air filters should be checked monthly and renewed as required. Because renewal intervals may vary with environmental conditions and filter type, each unit is equipped with a filter clog switch which warns of restricted air flow through the filter compartment by activating the 'Change Filter' alarm. 1) On downflow models the filters can be removed from the top of the unit, whereas on upflow units the bottom front panel contains the filters. 2) Fit new filters, refit the unit front panel on upflow units and restore the power supply. STEAM GENERATING HUMIDIFIER Remove the unit front panels and examine the humidifier for any loose electrical connections. Retighten any loose connections. Examine all pipes and connections for defects, damage and security of attachment. Ensure that the steam generating canister is properly secured to the unit frame. Refit the unit front and side panels and restore the electrical supply to the unit. Record and report any defects found during the inspection. REFRIGERATION COMPONENTS COMPRESSOR 1) Remove the front panel and examine the compressor for any obvious defects. Correct any defects found. 2) Examine the compressor vibration isolation mounts for defects and security. Retighten the mounts if necessary. 3) Inspect the refrigerant pipework connections for signs of oil leaks. 4) Examine the service valves for defects and signs of oil leaks. 5) Remove the compressor terminal cover and examine the electrical connections for damaged insulation. Retighten any loose connections. 6) Refit the compressor terminal cover and refit the unit front panel. 7) Restore the electrical supply to the unit. 8) Record and report any defects found during the inspection. REFRIGERANT LINES 1) Remove the unit front panel. 2) As far as possible, examine the refrigerant pipework for defects, damage and signs of oil leaks. 3) Examine the pipework for frictional or mechanical damage, particularly where pipes pass through the frame structure. 4) Check pipe brackets/clamps to ensure that they are properly secured. 5) Ensure that the insulation is sound and properly secured around the pipes. 6) Refit the unit front panel. 7) Restore the electrical supply to the unit. 8) Record and report any defects found during the inspection. EVAPORATOR COIL 1) Remove the unit front panels and inspect the coil for defects, damage and corrosion. 2) Check that the coil fins are in good condition. If they are found to be bent, they should be carefully straightened using a proprietary fin comb. 3) Inspect the refrigerant pipework connections for signs of oil leaks 4) Refit the unit front panels and restore the electrical supply to the unit. 5) Record and report any defects found during the inspection. LIQUID LINE SIGHT GLASS 1) Check the sight glass moisture indicator. If moisture is shown to be present in the system a new filter dryer must be fitted. 2) Refit the unit front panels and restore the electrical supply to the unit. 3) Record and report any defects found during the inspection. FILTER-DRYER 1) Open the unit front panels and locate the filter-dryer. 2) Examine the filter-dryer canister for defects or damage. Correct any defects found. 3) Inspect the refrigerant sight glass for dirt particles. If present, renew the filter-dryer. 4) Inspect the refrigerant pipework connections for signs of oil leaks. 5) Refit the unit front panels and restore the electrical supply to the unit. 6) Record and report any defects found during the inspection. 22

23 AIR COOLED UNITS AIR COOLED CONDENSER Restricted airflow through the condenser coil will reduce the unit operating efficiency and can result in high compressor head pressure and loss of cooling. 1) Clean the condenser coil of all debris that will inhibit air flow. This can be done with compressed air or commercial coil cleaner. 2) Check for bent or damaged coil fins and repair as necessary. If the fins are found to be bent, they should be carefully straightened using a proprietary fin comb. 3) Check all refrigerant lines and capillaries for vibration isolation and support as necessary. 4) Visually inspect all refrigerant lines for signs of oil leaks. 5) Record and report any defects found during the inspection. ELECTRIC PANEL INSPECTION AND FUNCTIONAL CHECKS GENERAL Open the unit front, inspect the electric panel for any damage or loose electrical connections and re-tighten as necessary. NOTE: -THE FUNCTIONING OF ALL CONTROL CIRCUITS CAN BE TESTED BY ACTUATING EACH OF THE MAIN FUNCTIONS, BY ADJUSTING THE SET POINTS. COOLING FUNCTIONAL TEST Select a set point for a temperature of 6 o C below room temperature. a) A call for cooling should be observed. b) The compressor contactor should energise, and the equipment should begin to cool. c) A high temperature alarm may enunciate. Disregard it. Return the set point to the room temperature. REHEAT FUNCTIONAL TEST Select a temperature set point for 6 o C above the room temperature. a) A call for heating should be observed. b) Both heating contactors should energise, and the heating elements should begin to heat. c) Disregard the low temperature alarm. Return the set point to the desired temperature. HUMIDIFICATION FUNCTIONAL CHECK Set the humidification to 10%RH above the room humidity reading. a) For a steam generating humidifier, you will immediately hear clicks as it energises. After a short delay, the canister will fill with water. The water will heat and steam will be produced. Return the humidity setting to the desired room relative humidity setting. DEHUMIDIFICATION FUNCTIONAL CHECK Set the humidification setpoint to 10%RH below the room humidity reading. Make sure that the temperature set point is at or above room temperature. a) The compressor contactor should energise and the system should begin to cool/dehumidify. Return the humidity setting to the desired room relative humidity setting. NOTE: - IN CHILLED WATER SYSTEMS THE VALVE OPENS PROPORTIONALLY. THE BASIC CONTROL CHECKS ARE NOW COMPLETED. 1) Replace the unit front panels and restore the electrical supply to the unit. 2) Record and report any defects found during the inspection. 23

24 STEAM GENERATING HUMIDIFIER CLEANING AND RENEWAL NOTE: REGULAR MAINTENANCE IS LIMITED TO DESCALING OR RENEWING THE BOILER. THIS IS NECESSARY WHEN SCALE ON THE ACTIVE SURFACES OF THE ELECTRODES PREVENTS SUFFICIENT PASSAGE OF ELECTRICAL CURRENT. 1) Drain the water completely. (See Controls Manual for details on drain procedure). 2) Disconnect the power supply to the equipment. 3) Unscrew the steam pipe from the boiler. 4) Disconnect the wiring to the main electrodes and the level electrodes. 5) Unhook the holding spring and unscrew the humidifier bottle by rotating it anti-clockwise on its axis. 6) Remove the bottle. NOTE: - THE BOILER MAY GENERALLY BE USED AGAIN AFTER DESCALING. 7) Unscrew the ring nut and extract the bottom filter. Remove any scale and deposits under a jet of water and clean the grids mechanically or chemically with a commercially available cleaner. NOTE: WHEN ELECTRODE WEAR IS SUCH THAT REGENERATION IS INSUFFICIENT, THE BOILER MUST BE RENEWED. 8) Reassemble the boiler in the reverse sequence after checking and if necessary, renewing the washer between the threaded connection and the discharge outlet. In the case of serviceable humidifiers the bottle can be dismantled and thoroughly cleaned. THERMOSTATIC EXPANSION VALVE - CALIBRATION SUPERHEAT - CALCULATION AND ADJUSTMENT CALCULATION 1) Measure the temperature of the suction line at the point where the TEV bulb is clamped. 2) Obtain the gauge pressure at the compressor suction valve. 3) Convert the sum of the two pressures to the equivalent temperature. 4) Subtract this temperature from the actual suction line temperature obtained in Step 1. The difference is the superheat value. ADJUSTMENT 1) Remove the cap at the bottom of the thermostatic expansion valve. NOTE: - MAKE NO MORE THAN A 1/4 TURN OF THE STEM AT A TIME. AS LONG AS 15 MINUTES MAY BE REQUIRED FOR THE NEW BALANCE TO TAKE PLACE. 2) Turn the adjusting stem counter-clockwise to lower the superheat. 3) Turn the adjusting stem clockwise to increase the superheat. REFRIGERANT CONTROL SETTINGS The pressure switches fitted are of the encapsulated type and are set and tested by the manufacturer prior to despatch. Switch settings are as indicated in the chart opposite: OPENS CLOSES LOW PRESSURE SWITCH 36 PSI 50 PSI HIGH PRESSURE SWITCH 400 PSI MANUAL 24

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax: TECHNICAL MANUAL CX(E) SPLIT SYSTEMS CONTENTS INDEX PART NUMBERS, OPTIONS, UNIT COMBINATIONS, DIMENSIONS & WEIGHTS 3 PERFORMANCE DATA & AIR FLOW 4 SOUND POWER AND SOUND PRESSURE LEVELS 5 ELECTRICAL DATA

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies Pakistan s Largest Manufacturers of Air-Conditioners PACKAGE TYPE UNIT FOR MOBILE APPLICATIONS Provides Turnkey Projects Conceptual Planning to Commissioning of HVACR Projects THE LARGEST MANUFACTURER

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Close Control Air Cooled Twin Circuit Range

Close Control Air Cooled Twin Circuit Range Close Control Air Cooled Twin Circuit Range Engineering Data Manual 50/60Hz ENGINEERING DATA MANUAL 50/60Hz Index Description Page YORK Company Profile 3 This Product Range 3 Other YORK Close Control Product

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

FULLY SELF-CONTAINED AIR CONDITIONING WITH INDUSTRIAL DURABILITY

FULLY SELF-CONTAINED AIR CONDITIONING WITH INDUSTRIAL DURABILITY C A P A C I T Y R U G G E D, I N D O O R/ R E A D Y T O T O T A L L O C A L M A T C H E D O U T D O O R D E S I G N I N S T A L L S U P P O R T E N V I R O N M E N T A L C O N T R O L Liebert Industrial

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

ENVIRONMENTAL CONTROL. Installation Operation and Maintenance Manual SLC-ES4-3E System 4. Liebert We won t let you down

ENVIRONMENTAL CONTROL. Installation Operation and Maintenance Manual SLC-ES4-3E System 4. Liebert We won t let you down Installation Operation and Maintenance Manual System 4 SLC-ES4-3E- - 271622-07.94 ENVIRONMENTAL CONTROL System 4 Liebert We won t let you down List of Contents Introduction 1 Installation 2 Operating

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS TC SERIES OPTIONS TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15,, 5 AIR COOLED PACKAGED WATER CHILLERS CONTENTS EQUIPMENT AND COMPONENT DETAILS PERFORMANCE AND TECHNICAL DATA SCHEMATIC FLOW & SYSTEM

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

VariCool VAV Engineering Guide

VariCool VAV Engineering Guide Engineering Guide Effective September 2017 Water-Cooled and Chilled Water, Variable Air Volume Contents Product Features... 3 UNIT FEATURES... 3 Product Features... 4 Marvel Plus Microprocessor Control

More information

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL WM150 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an

More information

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB Next P 6 112 kw COOLING 5 93 kw HEATING Heat pump air conditioners with upflow air delivery technicalcatalogue T_NXTP_0411_GB INDEX GENERAL CHARACTERISTICS... 3 SERIES IDENTIFICATION... 4 MODEL IDENTIFICATION...

More information

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) CONTENTS GENERAL................................... 5 SAFETY CONSIDERATIONS.................... 5 AGENCY APPROVALS.........................

More information

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION Environment IMPORTANT INFORMATION It is not anticipated that this equipment will be exposed to adverse environmental conditions without additional protection. Site the equipment in a frost free area. Ensure

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

INSTALLATION MANUAL - 50 Hz

INSTALLATION MANUAL - 50 Hz INSTALLATION MANUAL - 50 Hz SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) CONTENTS GENERAL................................... 5 SAFETY CONSIDERATIONS.................... 5 AGENCY APPROVALS.........................

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

Series 8. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 8. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 8 Guide Specification 60 Hz S8-GS-602017.doc 2014 ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 Series 8 Guide Specification-60

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

Container Refrigeration

Container Refrigeration Container Refrigeration OPERATION AND SERVICE for 69NT40-561-019 Evergreen Container Refrigeration Units Table 3 6 Controller Alarm Indications (Sheet 1 of 8) AL03 Loss of Superheat Control AL05 Manual

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES 11-AC11D2-5 INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: Condensing Units 2A7A5024-048, 2A7A4018-060, 2A7A2018-060 & 2A7A1018-060 IMPORTANT

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 9 Commissioning Checklist S9-CL2017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 S9-CL2017.doc Commissioning

More information

Series 6. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 6. Guide Specification 60 Hz. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 6 Guide Specification 60 Hz S6-GS-602017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 Series 6 Guide Specification-60

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET General Piping Recommendations and Refrigerant Line Length for Split-System Air Conditioners and Heat Pumps GENERAL GUIDELINES This Split-System (Air Conditioning Condensing/Heat

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems 12 In Row Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents Table of Contents... 3 Site

More information

VertiCool Aurora Engineering Guide

VertiCool Aurora Engineering Guide Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8

More information

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804 INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON CONTENTS GENERAL................................. 3 REFERENCE............................... 3 INSPECTION...............................

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Split System Cooling Condensers Model CTA 7 1/2 to 15 Tons Models A and later Design Sequence CTA 090A***A 60 HZ 120A***A 60 HZ 120B***A 60 HZ 180B***A 60 HZ SS-SVN11A-EN

More information

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED EQV R-407C WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED Size Cooling Heating [kw] [kw] 5 1,9 2,2 7 2,4 2,5 9 2,6 2,5 15 3,3 3,2 17 3,7 3,7 REPLACE: BT02E008GB-01 The Versatemp EQV units

More information

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F Temperature Control Units Water & Oil - F Portable Chillers Air & Water-Cooled - 7 F Central Chillers Air & Water-Cooled Packages & Modules - 7 F Pump Tank Stations Chilled or Tower Water - gallons Cooling

More information

REDI CONTROLS, INC. Installation, Operation & Maintenance Manual

REDI CONTROLS, INC. Installation, Operation & Maintenance Manual REDI CONTROLS, INC. Installation, Operation & Maintenance Manual Literature File No. 1151-00.113 Redi-Purge Microprocessor Controlled Ultra-High Efficiency Gravity Flow Non-Condensable Purge Unit For Use

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL BERG TEMPERATURE CONTROL UNIT

INSTALLATION, OPERATION & MAINTENANCE MANUAL BERG TEMPERATURE CONTROL UNIT INSTALLATION, OPERATION & MAINTENANCE MANUAL BERG TEMPERATURE CONTROL UNIT TABLE OF CONTENTS Description Page # Introduction 3 Customer Support 3 Model Number Nomenclature 4 Control Panel 5 Display Panel

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

40 RM/RMS Packaged Air-Handling Units

40 RM/RMS Packaged Air-Handling Units ConcepcionCarrier Air conditioning Company Philippines 40 RM/RMS 008034 Packaged AirHandling Units INSTALLATION MANUAL, STARTUP & SERVICE INSTRUCTIONS Contents Page Page Safety Considerations 1 40RM Physical

More information

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only Marvel S MICROPROCESSOR CONTROLLER Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED For Reference Only ***Interactive PDF*** Contents General Purpose...3 Standard And

More information

Daikin Direct Expansion (DX) Cooling Coils

Daikin Direct Expansion (DX) Cooling Coils Installation and Maintenance Manual IM 902 Daikin Direct Expansion (DX) Cooling Coils Group: Applied Air Part Number: IM 902 Date: February 2008 Types EN, EF, ER, EJ, EK 2008 Daikin Applied Contents Introduction...

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Liebert Challenger 3000/Liebert Challenger ITR with Liebert icom Control. Operation & Maintenance Manual - 50 & 60Hz

Liebert Challenger 3000/Liebert Challenger ITR with Liebert icom Control. Operation & Maintenance Manual - 50 & 60Hz Liebert Challenger 3000/Liebert Challenger ITR with Liebert icom Control Operation & Maintenance Manual - 50 & 60Hz TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................ INSIDE

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Next MTR kw. technicalcatalogue. Air conditioners for Metrology Labs with upflow air delivery T_NXTMTR_0511_GB

Next MTR kw. technicalcatalogue. Air conditioners for Metrology Labs with upflow air delivery T_NXTMTR_0511_GB 6 15 kw Next MTR Air conditioners for Metrology Labs with upflow air delivery technicalcatalogue T_NXTMTR_0511_GB INDEX GENERAL CHARACTERISTICS... 3 SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS 3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: 32305600 OPERATION & MAINTENANCE INSTRUCTIONS 0304 Parts List Item Part No Description Qty 1 FT900001 Top Cover 1 2 FT900002 Filter

More information

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified Shelf Units 2, 3, and 4 ton R-407C ISO 9001 Certified the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first precision cooling system was developed by data processing

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT: GENERAL SPECIFICATIONS OUTDOOR UNIT: TECHNICAL GUIDE COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM MODELS HB 180 & HB 240 MODELS LB 180 & LB 240 15 & 20 NOMINAL TONS 9.7 EER Two independent refrigerant

More information

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-410A. 6, 8, 10, and 13 ton. ISO 9001 Certified Data Aire LCS TM (Large Ceiling System) 6, 8, 10, and 13 ton ISO 9001 Certified LCS TM (LARGE CEILING SYSTEMS) DX Product Description Performance and Electrical Data 3 the pioneer and builder of the most

More information

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB

4,5 22,5 kw. technicalcatalogue. Air-conditioned server-racks for direct installation into the room T_CLSEVO_0113_GB 4,5 22,5 kw Air-conditioned server-racks for direct installation into the room technicalcatalogue T_CLSEVO_0113_GB INDEX HIGHLIGHTS... 3 PLANT TYPE... 3 GENERAL CHARACTERISTICS... 5 SERIES IDENTIFICATION...

More information

MISSION CRITICAL Air Conditioning Systems. Maintenance Guide. ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4

MISSION CRITICAL Air Conditioning Systems. Maintenance Guide. ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 MISSION CRITICAL Air Conditioning Systems Maintenance Guide ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 Vertical Floor /Wall /Ceiling Mount - Maintenance Manual 2

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw Multifunction chillers for indoor installation. Cooling Capacity: 22 222 Heating Capacity: 25 236 Scroll compressors EC Plug Fans Plate type heat exchangers EER up to 3,12 COP up to 3,84 ESEER up to 4,01

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental TECAM S.A. Tecnología Ambiental R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz harmony 5PZA Direct Expansion Registration No.: SC 4696-1 Registration No.: CO-SC 4696-1 Air Conditioning Equipment Manufacturer

More information

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING Emerson Inspire 1HDEZ-1521 Installation Instructions Thermostat/Interface Equipment Control TROUBLESHOOTING FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 1 Contents INTRODUCTION... 3 WARNING LABELS AND SAFETY INSTRUCTIONS... 4 PARALLEL RACK NOMENCLATURE... 5 GENERAL RACK DESCRIPTION...

More information

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers.

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers. Issued 2006/08/01 Section 15751 Humidifiers Page 1 of 7 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section 01810 Commissioning..4 Section

More information

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT Concepcion Carrier Air conditioning Company Philippines INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT CONTENTS Safety Considerations 1 Complete

More information

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH 33-44-50 CAH 49-54-70 CAH VARIABLE SPEED AIR HANDLERS DIMENSIONS... 3 TECHNICAL SPECS... 4 INSTALLATION DON TS... 5 INSTALLATION DO S... 6 FREEZE STAT REQUIRED

More information

Data Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified

Data Aire LCS TM (Large Ceiling System) R-407C. 6, 8, 10, and 13 ton. ISO 9001 Certified Data Aire LCS TM (Large Ceiling System) 6, 8, 10, and 13 ton ISO 9001 Certified LCS TM (LARGE CEILING SYSTEMS) with refrigerant Product Description Performance and Electrical Data Dimensional Data Guide

More information

38XTZ ABZ 007, 008, 016, 020 and ALZ 011 and 014. Split system air-cooled air conditioners. Models 38XTZ 016 to 024 MASTER LINK I

38XTZ ABZ 007, 008, 016, 020 and ALZ 011 and 014. Split system air-cooled air conditioners. Models 38XTZ 016 to 024 MASTER LINK I 38XTZ 007-024 40ABZ 007, 008, 016, 020 and 024 40ALZ 011 and 014 Split system -cooled conditioners MASTER LINK I Models 38XTZ 016 to 024 40ABZ/ALZ Carier is participating in the Eurovent Certification

More information

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB Summary 1 CONNECTIONS... 3 1.1 TEMPERATURE PROBES...3 1.2 LOW VOLTAGE DIGITAL INPUTS...3 1.3 LIVE DIGITAL INPUTS...4 1.4 RELAY OUTPUTS...5 2 POWER SUPPLY... 6 3 SERIAL CONNECTIONS... 6 4 SOFTWARE... 7

More information

P-Series, Vertical Floor-Mount Units

P-Series, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems P-Series, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 - 2 - SP-IM2018 Table

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning

NEXT EVO DXR410A NEXT EVO DX NEW SOFTWARE. rcgroupairconditioning : Direct expansion close control air conditioners with up-flow or down-flow air delivery. Cooling Capacity: 7 102 NEW SOFTWARE R410A rcgroupairconditioning E C A C UP FLOW DOWN FLOW MAIN FEATURES Precision

More information

EHH SERIES DRAW THROUGH FAN COILS CFM

EHH SERIES DRAW THROUGH FAN COILS CFM EHH SERIES DRAW THROUGH FAN COILS 400-5000 CFM TABLE OF CONTENTS TABLE OF CONTENTS 2 INTRODUCTION 3 GUIDE SPECIFICATIONS 4 UNIT OVERVIEW 6 TECHNICAL DATA 8 DIMENSIONS 10 COMPUTER SELECTION 11 GEMCOOL PROFILE

More information

Installation Instructions

Installation Instructions 8GXM / 0GXM Multi---Split High---Wall Duct Free Split System 8GXM --- Size 18k, k, and 0k 0GXM --- Size 9k, 1k, and 18k Installation Instructions NOTE: Read the entire instruction manual before starting

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18

NetworkAIR AFX. Operation and Maintenance AFX65 AFX18 NetworkAIR AFX Operation and Maintenance AFX65 AFX18 Contents Operation... 1 Display Interface.......................................... 1 Using the Display......................................... 3

More information

OWNER S MANUAL. R 410A Ductless Split System Air Conditioner and Heat Pump

OWNER S MANUAL. R 410A Ductless Split System Air Conditioner and Heat Pump R 410A Ductless Split System Air Conditioner and Heat Pump Models DLC4(A/H) Outdoor Unit, DLF4(A/H) Indoor Unit Sizes 9K, 12K, 18K, 24K, 30K and 36K Please read the operating instructions and safety precautions

More information

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T15 Model INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A ISO 9001 Certified Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aire s first

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

T-Series Air Conditioner T20 Model

T-Series Air Conditioner T20 Model INSTRUCTION MANUAL T-Series Air Conditioner T20 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information