FIRE RISK ASSESSMENT REVIEW
|
|
- Lewis Morgan
- 5 years ago
- Views:
Transcription
1 COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Director of Estates in conjunction with Council & the Vice Chancellor Brotherhood Boiler House, University of Kent, Canterbury CT2 7NZ Estates, contractor and Security staff Andrew Briggs, MIFSM, MIIRSM Date of Fire Risk Assessment: 24th August 2010 Note: various inspections/surveys conducted in the course of this exercise were non-invasive and/or sampling exercises, and therefore not fully conclusive. Date of Previous Fire Risk Assessment: 9th June 2004 Suggested Date for Review: August 2012, or as per UoK SHEU official schedule, or in event of significant change Document dated 24th August 2010 Fire Risk Assessment in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with various additions)
2 COVER SHEET
3 GENERAL BUILDING DESCRIPTION 1.0 The Building 1.1 Number of floors Approximate floor area: Not reviewed at this time 1.3 Construction Details: Brick & block walls, Thermolite decking supported by steel beams, asphalted felt roofing. 1.4 Occupancy: Usually unoccupied, or one member of contractor's staff present. Security and other Estates functions occasionally use the first floor rooms. 2.0 The Occupants 2.1 Approximate maximum number: Not reviewed at this time 2.2 Maximum number of staff at any one time: Unlikely to be more than Maximum number of members of public: Nil, restricted area (Add more detail by area or room as appropriate) 3.0 Occupants at Special Risk 3.1 Sleeping occupants: Nil 3.2 Occupants with disabilities: None at time of assessment, but possible subject to specific assessment 3.3 Occupants in remote areas: Occasional on boiler room elevated gangways (see 17.2 vii) 3.4 Others: N/A 4.0 Fire Loss Experience 4.1 Fires in past 10 years: Nil 4.2 Cost of fire losses: N/A
4 GENERAL BUILDING DESCRIPTION 5.0 Other Relevant Information 5.1 Detail: N/A 6.0 Relevant Fire Safety Legislation 6.1 Primary statutory provisions etc: Regulatory Reform (Fire Safety) Order 2005, referred Official Guidance & related British Standards/Euro Norms 6.2 Enforced by: Kent Fire & Rescue Service 6.3 Other legislation significant to fire safety Fire Safety (Employees' Capabilities) (England) Regulations 2010 provisions in this building: 6.4 Enforced by: Kent Fire & Rescue Service
5 The following is based on BS 9999 concepts and principles, which may be used in conjunction with official guidance in assessing risks. Categories relevant to the building are highlighted. Assessment of risk is on a "probable" basis, recognising the degree to which this Fire Risk Assessment is based on sampling; undetected risks may exist. Occupant risk categories Risk category Description Comments A Occupants who are awake and Local staff; visiting contractors etc. briefed and familiarised familiar with the building B Occupants who are awake and unfamiliar with the building C Occupants who are likely to be asleep: Ci long-term individual occupancy Cii long-term managed occupancy Ciii short-term occupancy D Occupants receiving medical care E Occupants in transit Fire growth rate(s) Category Fire growth rate Typical fire growth parameter, kj/s3 1 Slow Most locations 2 Medium Fast Ultra-fast Locations (where specific) & categories Risk profile: A1 Management level therefore required: 2 (3 according to BS 9999) 1 = fully proactive; optimally staffed, controlled & resourced etc. See BS 9999:2008 section = reliably reactive; compliant with legislation & direct requirements ( 3 = N/A, less than compliant with legislation ) Environmental risks Fire-fighting water runoff and temporary release of combustion products to atmosphere only; no other environmental impact likely Heritage aspects Building does not have Listed status.
6 Business continuity (University) Business continuity (department) Considerable effect on University as a whole due to function (especially winter months). Serious effect.
7 FIRE HAZARDS INDE DETAIL ES NO N/A COMMENTS, CONTROL MEASURES REQUIRED ETC. FURTHER COMMENTS, DETAIL, CLARIFICATION ETC 7.0 Electrical Sources of Ignition Continue insofar as possible to maintain safe separation distance of ½ metre between appliances and combustible materials in all areas, to ensure that sources of heat do not arise from faulty or overloaded electrical equipment, to ensure that all electrical fuses and circuit breakers etc are of the correct rating and suitable for the purpose, and to switch equipment off at the end of the working day. 7.1 Reasonable measures taken to prevent fires of electrical origin? 7.2 Fixed installation periodically inspected and tested? Portable appliance testing carried out? Suitable policy regarding use of personal electrical appliances? Suitable limitation of trailing leads and adaptors? Continue to ensure PAT and fixed installation testing is carried out regularly. 8.0 Smoking 8.1, 2 Reasonable measures taken to prevent fires as a Provide statutory No Smoking sign at main entrance. Ensure University smoking policy continues to be implemented, result of smoking? Prohibited where appropriate? Arrangements for smokers? No evidence of breaches? publicised and enforced insofar as possible. 9.0 Arson 9.1, 2 Does basic security against arson by outsiders appear reasonable? Absence of fire load available for ignition by outsiders? (Proximity to or presence within building) CCTV in use. See also Portable Heaters & Heating Installations 10.1 Is the use of portable heaters avoided as far as practicable? 10.2 If portable heaters are used: is the use of the more hazardous type (e.g. radiant bar fires or lpg appliances) avoided? Are suitable measures taken to minimize the hazard of ignition of combustible materials? 10.3 Are fixed heating installations subject to regular maintenance? Continue to ensure that additional appliances are used only where strictly necessary and with management knowledge and control. Portable electrical heaters with open elements, such as fan or radiant heaters, must not be used Cooking 11.1 Are reasonable measures taken to prevent fires as a result of cooking? Is all essential maintenance up to date and recorded? 11.2 Are filters changed and ductwork cleaned regularly? Are suitable extinguishing appliances available? 12.0 Lightning 12.1 Does the building have a lightning protection system?
8 FIRE HAZARDS 13.0 Housekeeping 13.1 Is the standard of housekeeping adequate? Ensure a programme is introduced to improve housekeeping. Ensure that housekeeping programme continues to include prompt removal of combustible or hazardous materials and waste Are combustible materials separated from ignition Continue to maintain safe separation distance of ½ metre between sources of sources? heat and combustible materials throughout building Is there an avoidance of unnecessary accumulation of combustible materials or waste? 13.4 Is there appropriate storage of combustible materials? 13.5 Is there avoidance of inappropriate storage of combustible materials? Continue to ensure that combustible items are not present in the main entrance, being the sole escape route from the office and from the first floor. N Timber pallets and any other combustibles should be stored at least 8 metres from the fabric of the building. Escape routes should be maintained as fire-sterile as possible; this is especially critical in staircases and where there is no alternative direction of escape Outside Contractor, Building Works and Maintenance Hazards 14.1 Is there satisfactory control over works carried out in the building by maintenance personnel and outside contractors? 14.2, 3 Are adequate fire safety conditions imposed on outside contractors? As Appropriate control (including Permits To work where appropriate) administered by Estates Dangerous Substances 15.1 Have the hazardous properties of dangerous substances been considered? If relevant, has a risk assessment been carried out according to the Dangerous Substances and Explosive Atmospheres Regulations 2002? 15.2 Is there adequate information on safety provided by the supplier on any relevant safety data sheet? 15.3 Has account been taken regarding: the special, technical and organisational measures and the substances used and their possible interactions. the amount of the substance involved where the work will involve more than one dangerous substance, the risk presented by such substances in combination the arrangements for the safe handling, storage and transport of dangerous substances and of waste containing dangerous substances N (1) Cylinder of compressed Propane and carbuoy of 28% Hydrochloric Acid should be removed to suitable storage elsewhere or disposed of. (2) Risk assessment under DSEAR 2002 will be required if Propane is to be stored or used on these premises again. Not checked. (a) No other flammables are present. Other hazardous materials are compressed nitrogen and sodium hydroxide based corrosives, BW40 and BW50 (up to a dozen 25 litre containers in entrance lobby); otherwise small quantities of maintenance fluids etc. (b) Continue to ensure that any dangerous substances temporarily introduced (e.g. by contractors) are known and logged, that appropriate controls are in place, and that all relevant information can be made immediately available to the Fire & Rescue Service in the event of an emergency.
9 FIRE HAZARDS any other measures introduced as a result of the RRO 15.4 Are there safe systems of work for maintenance, where there is the potential for a high level of risk? 15.5 Are sufficient control measures in place to counter the likelihood that an explosive atmosphere will occur and its persistence including adjacent areas? 15.6 Are sufficient control measures in place to counter the likelihood that ignition sources, including electrostatic discharges, will be present and become active and effective 15.7 Has account been taken regarding the scale of the anticipated effects? 15.8 Is sufficient additional safety information available to enable the assessment to be completed? Outline plans should be drawn up of the locations and hazard classifications of dangerous substances (e.g. corrosives) that may pose a health risk to firefighters Other Significant Risks 16.1 Are there other significant ignition sources present? 16.2 Are there other significant fuels present? As Boilers and ancillary equipment have numerous faisafe controls applied in respect of fire and gas leakage.
10 FIRE PROTECTION INDE DETAIL ES NO N/A COMMENTS, CONTROL MEASURES REQUIRED ETC. FURTHER COMMENTS, DETAIL, CLARIFICATION ETC 17.0 Means of Escape from Fire Dead end conditions exist in all locations except the floor level of the boiler room itself Is it considered that the building is provided with reasonable means of escape in case of fire? Management should ensure that all room doors are routinely closed at all times when there is no person present in the room i Adequate design of escape routes? (Calculate for room and premises occupancy numbers & types, where relevant.) 17.2 i Is a suitable assembly point specified? Boiler House car park, no. 25. suppl ii Adequate provision of exits? (Calculate for room and premises occupancy numbers & types, where relevant.) 17.2 iii Are exits easily and immediately openable where necessary? (Alarm-linked features such as electronic door release mechanisms to be verified as compliant, functional and suitably failsafe) 17.2 iv Do escape exits open in the direction of escape where necessary? 17.2 v Avoidance of sliding or revolving doors as fire exits where necessary? 17.2 vi Are there satisfactory means for securing exits? The main entrance must remain unlocked at all times when any person is present vii Are there reasonable travel distances where Extended travel distance on boiler room high level gantry, but acceptable. there is a single direction of travel? 17.2 viii Are there reasonable travel distances where there is an alternative means of escape? 17.2 ix Is there suitable protection of escape routes? N (1) Fire doors protecting the entrance lobby should be suitably adjusted, upgraded and kept closed (unless automated) (see also 20.1 (2)). (2) Recommendation to fit automatic device (Dorgard permissible) to office door (see 17.2 ix suppl.) ix suppl Where automatic devices are fitted to designated fire doors, is appropriate automatic fire detection fitted? As proposed at 17.2 ix (2) above - no detection in room, but smoke detection several feet away in corridor so tolerable on a fire risk assessed basis x Suitable fire precautions for all inner rooms? 17.2 xi Are all escape routes unobstructed? N Clear obstructions from alternative exit from boiler room Is the building provided with reasonable arrangements for means of escape for occupants with disabilities? N Should any person with a disability need to enter the building, a prior assessment of means of escape, possible adjustments, and therefore accessibility or otherwise, must be made and strictly adhered to Measures to Limit Fire Spread and Development
11 FIRE PROTECTION 18.1 i Is it considered that there is compartmentation of a reasonable standard? (Including e.g. firestopping of service penetrations) 18.1 i Is there potential for fire spread between suppl. compartments through void spaces? 18.1 ii Is it considered that there is reasonable limitation of linings that may promote fire spread? N (1) Fire stopping of holes, gaps, service penetrations etc through fire resisting construction was noted as deficient in numerous locations (e.g. gaps around service penetrations through walls of entrance lobby) - remedial fire stopping should be undertaken throughout. (2) Designated fire doors must not be propped or wedged open at any time. Where there is an operational need, or where management cannot ensure that these doors remain closed at all times, automatic devices should be considered (e.g. office door, 17.2 ix (2) - but subject to specific fire risk assessment) ii Are escape routes suitably/tolerably fire sterile? N Very old noticeboard with combustible postings serves no current purpose and suppl. should be removed from staircase As far as can be reasonably ascertained, are fire dampers provided as necessary to prevent critical means of escape against passage of fire, smoke and combustion products in the early stages of a fire? 19.0 Escape Lighting 19.1 Is a reasonable standard of escape lighting provided? 20.0 Fire Safety Signs and Notices 20.1 Does the building have a reasonable standard of fire safety signs and notices? Not exhaustively verified. Subject to ongoing verification by Estates. (1) Fire action notices do not reflect University policy in respect of fire extinguisher use and should be amended (and a number of unnecessary duplicated signs reduced). (2) Fit "Fire Door Keep Closed" signs to all doors off entrance lobby and first floor landing. (3) Provide additional directional sign to boiler room alternative exit (adjacent to pump/high level warning bell) Means of Giving Warning in Case of Fire 21.1 Is a reasonable manually operated electrical fire alarm system provided? 21.2, 3 Is automatic fire detection provided in building? (Throughout building? Part(s) of building only?) Is the extent of automatic fire detection generally suitable for the occupancy and risk? Smoke detection in escape routes; some heat detection elsewhere Is there a remote transmission of alarm signal? N But alarm signal within building can be expected to be audible in Campus Watch offices. 21 suppl. Is the fire alarm system audible or perceptible 1 throughout the building? Appears adequate, subject to ongoing verification by Estates that 65dB is attained throughtout. 21 suppl. If unwanted fire alarm signals occur, are they 2 acceptably infrequent? Nil or negligible Portable Fire Extinguishing Appliances
12 FIRE PROTECTION 22.1 Is the provision of portable fire extinguishers reasonable? 22.2 Are hose reels provided? N Hose reel on back wall of boiler room is not for firefighting purposes Are all fire extinguishing appliances readily accessible? 23.0 Automatic Fixed Systems 23.1 Is there a suitable sprinkler or water based system, gaseous local application or total flooding provided that is adequate for the risk present? 24.0 Other Fixed Systems and Equipment 24.1 Are there suitable smoke control facilities for the risk present? 24 suppl. Is there suitable provision of a fire-fighters' switch(es) for high voltage luminous discharge tube signs etc? Has suitable notice of these been given to the Fire & Rescue Authority, including switch colouring and marking? N N
13 MANAGING FIRE SAFET INDE DETAIL ES NO N/A COMMENTS, CONTROL MEASURES REQUIRED ETC. FURTHER COMMENTS, DETAIL, CLARIFICATION ETC 25.0 Procedures and Arrangements 25.1 Fire safety is managed by: Director of Estates Are suitably and sufficiently competent persons appointed to assist in undertaking and ensuring the preventive and protective measures (i.e. relevant general fire precautions)? 25.3, 4 Is there a suitable record of fire safety arrangements? Procedures properly documented? Suitable arrangements for summoning the Fire & Rescue Service, meeting them on arrival and providing relevant information including that relating to hazards to fire-fighters? Suitable arrangements for ensuring that the premises have been evacuated? Suitable fire assemply point(s)? Adequate procedures for evacuation of persons with disabilities? N Provide, resource and implement a written Fire Emergency Plan covering all appropriate procedures, responsibilities and features of the building Are persons nominated and trained to use fire extinguishing appliances? 25.6 Are persons nominated and trained to assist with evacuation, including evacuation of persons with disabilities? 25.7 Is there appropriate liaison with the Fire & Rescue Service (e.g. any relevant notifications, familiarization visits etc) 25.8 Is a system of routine in-house, local inspections of fire precautions implemented? Only Campus Watch are nominated (completion of training currently pending). It is unlikely that any building occupants will require full training but consideration should be given to maintenance staff, contractors and the fire risks they are exposed to. Not applicable; minimal specialist staff; could be expected to account for each other reliably in the event of an evacuation. N Ensure that a system of local checks and inspections of fire safety features is implemented throughout all locations. Under BS5306-3:2009, fire extinguishers should be checked at least monthly and the results recorded. See also Training and Drills Appropriate fire safety training of contractors' staff should be verified Are all staff given adequate fire safety instruction and training on induction? 26.1 Are all students and/or visitors given adequate fire Continue to provide adequate fire safety information and instruction and suppl. safety information and instruction at an training to visitors/contractors at the earliest opportunity appropriate time?
14 MANAGING FIRE SAFET 26.2 Are all staff given adequate periodic fire safety refresher instruction and training at suitable intervals? 26.3 Does all staff training provide information, instruction or training on the following: fire risks in the building, fire safety measures, action in the event of fire and on hearing the alarm signal, operation of manual call points, location and use of fire extinguishers, means of summoning the Fire & Rescue Service, identity of persons nominated to assist with evacuation, identity of persons nominated to use fire extinguishing appliances? 26.4 Are staff with special responsibilities (e.g. fire marshals) given additional training? 26.5 Are fire drills carried out at appropriate intervals, and in accordance with official guidance? Repeat basic fire safety information at not less than yearly intervals, and provide full refresher training at not less than 3 yearly intervals. But see requirement at 26.0 above. Not appropriate for this building due to nil or minimal staffing When the employees or visitors of another employer work or are accommodated in the premises: 26.6 i Is the employer given appropriate information (e.g. on fire risks and general fire precautions)? 26.6 ii Is it ensured that the employees and visitors are provided with adequate instructions and information? 27.0 Inspection, Testing and Maintenance 27.1 Adequate maintenance and inspection of premises ~ It is suggested that condition and suitability of fire doors should be by competent persons? assessed at least every 5 years, and of fire stopping at least every 10 years Weekly testing and periodic servicing of fire detection and alarm system? 27.3 Monthly and annual testing routines for emergency lighting? 27.4 Annual maintenance of fire extinguishing appliances? 27.5 Periodic inspection of external escape staircases and gangways? 27.6 Six-monthly testing and annual inspection of rising mains and/or hydrants?
15 MANAGING FIRE SAFET 27.7 Weekly and monthly testing, six monthly inspection and annual testing of evacuation and/or fire-fighting lifts? 27.8 Weekly testing and periodic inspection of sprinkler installations? 27.9 Routine checks of final exit doors and/or security fastening? Annual inspection and test of lightning protection systems? Other relevant inspections or tests: (including e.g. ductwork dampers, fire shutters, venting systems, door holdback devices, electronic door release systems)? Implement regular routine checks of alternative exit door (under 25.8) Records 28.1 Are appropriate records kept for: 28.1 i Fire drills? 28.1 ii Fire training?? Provide and maintain records of fire safety training iii Fire alarm tests? 28.1 iv Emergency escape lighting tests? 28.1 v Maintenance and testing of other fire protection systems? 29.0 oung Persons Have the following matters been taken into particular account in risk assessment in respect 29.1 of young persons: the inexperience, lack of awareness of risks and 29.2 immaturity of young persons 29.3 the fitting-out and layout of the premises the nature, degree and duration of exposure to 29.4 physical and chemical agents the form, range, and use of work equipment and 29.5 the way in which it is handled; 29.6 the organisation of processes and activities the extent of the safety training provided or to be 29.7 provided to young persons risks from agents, processes and work listed in the Annex to Council Directive 94/33/EC on the 29.8 protection of young people at work 30.0 Behavioural Aspects
16 MANAGING FIRE SAFET Is there evidence from previous fire drills and other emergencies indicating that some occupants may be unaware, unwilling or fail to 30.1 evacuate? (Aside from disability-related) Is there evidence of disregard of fire safety provisions amongst building occupancy and/or 30.2 management? Is there evidence of significant human 30.3 interference with fire safety provisions? N N N
17 INDE DETAIL DESCRIPTION 31.0 Fire Strategy - building design/layout 31.1 The ground floor is divided into two fire compartments (boiler room and office suite, separated by entrance lobby and staircase); the first floor is a single fire compartment not separated from the entrance lobby The evacuation strategy is simultaneous and immediate for the entire building and all occupants The building is well provided with access routes for firefighting by the Fire & Rescue Service - a main access road and two dedicated fire roads provide approach on three sides of the building. Fire hydrants are available next to two adjacent buildings (Ingram and Library) and are maintained in an operational state Fire Strategy - systems 32.1 The fire alarm system provides for manual operation and automatic detection in order to give sufficiently early warning of fire to occupants Fire Strategy - particular risks 33.1 Aside from the boiler machinery which operates with various fire-related safeguard controls, the building presents a very low fire loading except in some areas of offices and stores Compressed nitrogen is present in the boiler room and stored against the oil tank bund wall. Alkaline corrosives are stored at the foot of the staircase (up to a dozen 25 litre kegs) No persons with disabilities are ever present (at time of writing). Thorough individual assessment will be required before any individual with a relevant disability accesses the building.
18 This simple risk level estimator is based on a more general health and safety risk level estimator in BS Assessment of risk is on a "probable" basis, recognising the degree to which this Fire Risk Assessment is based on sampling; undetected risks may exist. Potential consequences of fire Slight harm Moderate harm Extreme harm Fire hazard Low Trivial OR tolerable risk * Tolerable risk Moderate risk Medium Tolerable risk Moderate risk Substantial risk High Moderate risk Substantial risk Intolerable risk * at discretion of Fire Risk Assessor Taking into account the fire prevention measures observed at the time of this risk assessment, it is considered that the hazard from fire (probability of ignition) at this building is: Low / highly unlikely Medium / unlikely High / likely Taking into account the nature of the building and the occupants, as well as the fire protection and procedural arrangements observed at the time of this risk assessment, it is considered that the consequences for life safety in the event of fire would be: Slight harm - following completion of recommendations of this fire risk assessment Moderate harm Extreme harm In this context, a definition of the above terms is as follows: Slight harm: Moderate harm: Outbreak of fire unlikely to result in serious injury or death of any occupant (other than an occupant sleeping in a bedroom in which a fire occurs). Outbreak of fire could result in injury of one or more occupants, but it is unlikely to involve multiple
19 Extreme harm: fatalities. Significant potential for serious injury or death of one or more occupants. Accordingly, it is considered that the risk to life from fire at this building is: Trivial Tolerable - following completion of recommendations of this fire risk assessment Moderate Substantial Intolerable A suitable risk-based control plan should involve effort and urgency that is proportional to risk. The following risk-based control plan is based on one advocated by BS 8800 for general health and safety risks: Trivial Tolerable Moderate Risk Level Action and Timescale No action is required and no additional detailed records need be kept. No major additional controls required. However, there may be a need for consideration of improvements that involve minor or limited cost, and various corrective actions may be required. It is essential that efforts are made to reduce the risk. Risk reduction measures should be implemented within a defined time period. Where moderate risk is associated with consequences that constitute extreme harm, further assessment may be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures. Substantial Considerable resources may have to be allocated to reduce the risk. If the building is unoccupied, it should not be occupied until the risk has been reduced. If the building is occupied, urgent action should be taken.
20 Intolerable Building (or relevant area) should not be occupied until the risk is reduced. Any significant change, occurrence, finding or development should be reported immediately to the University s Safety, Health & Environment Unit so that mitigating action can be taken and this Fire Risk Assessment reviewed and updated. Important note: this assessment of risk is made on a probable or 'best endeavour' basis, since this report is based on a sampling exercise. It is possible that greater risks remain undetected in areas or aspects that have not yet been accessed or addressed.
21 ACTION PLAN ORGANISATION: University of Kent ASSESSOR: Andrew Briggs BUILDING: Boiler House DATE: 24th August 2010 ACTION PLAN It is considered that the following recommendations should be implemented in order to reduce fire risk to, or maintain it at, the following level: TOLERABLE Note - only acute/remedial/salient/particular items appear below. Various standard/general requirements relating to e.g. training, records and maintenance have not been carried forward to the Action Plan, but are nevertheless necessary - see previous worksheets. REFERENCE ACTION REQUIRED TO ELIMINATE OR CONTROL SIGNIFICANT HAZARDS PRIORIT * RESPONSIBILIT TARGET DATE COMPLETE See also Further Comments/Detail/Clarification etc. in previous worksheets, where relevant 6 figure numbers are Estates Helpdesk Work Requests or carried forward to: ( = Estates spreadsheet) 8.0 Smoking 8.1, 2 Provide statutory No Smoking sign at main entrance. 2A/B Housekeeping 13.4 Timber pallets and any other combustibles should be stored at least 8 metres from the fabric of the building. 2A/B Estates & contractor Immediate & ongoing 15.0 Dangerous Substances 15.1 (1) Cylinder of compressed Propane and carbuoy of 28% Hydrochloric Acid should be removed to suitable storage elsewhere or disposed of. (2) Risk assessment under DSEAR 2002 will be required if Propane is to be stored or used on these premises again Outline plans should be drawn up of the locations and hazard classifications of dangerous substances (e.g. corrosives) that may pose a health risk to firefighters. 2A/B 3A (1) Estates local management (2) Estates Estates local management Immediate & potential/ ongoing Short term 17.0 Means of Escape from Fire 17.2 ix (1) Fire doors protecting the entrance lobby should be suitably adjusted, upgraded and kept closed (unless automated) (see also 20.1 (2)). (2) Recommendation to fit automatic device (Dorgard permissible) to office door (see 17.2 ix suppl.). (1) 2A/B (2) 3A/B (1) Partly , also Estates & Contractor (2) Estates 17.2 xi Clear obstructions from alternative exit from boiler room. 1A Estates local management 18.0 Measures to Limit Fire Spread and Development Ongoing Immediate (2)
22 ACTION PLAN 18.1 i (1) Fire stopping of holes, gaps, service penetrations etc through fire resisting construction was noted as deficient in numerous locations (e.g. gaps around service penetrations through walls of entrance lobby) - remedial fire stopping should be undertaken throughout. (2) Designated fire doors must not be propped or wedged open at any time. Where there is an operational need, or where management cannot ensure that these doors remain closed at all times, automatic devices should be considered (e.g. office door, 17.2 ix (2) - but subject to specific fire risk assessment) ii suppl. Very old noticeboard with combustible postings serves no current purpose and should be removed from staircase. 2A/B (1) (2) Estates local management and Contractor 2A/B Estates local management (2) Ongoing Immediate to short term 20.0 Fire Safety Signs and Notices 20.1 (1) Fire action notices do not reflect University policy in respect of fire extinguisher use and should be amended (and a number of unnecessary duplicated signs reduced). (2) Fit "Fire Door Keep Closed" signs to all doors off entrance lobby and first floor landing. (3) Provide additional directional sign to boiler room alternative exit (adjacent to pump/high level warning bell). 2A/B (1) Estates (2), (3) (1) Short to medium term (1) 25.0 Procedures and Arrangements 25.3, 4 Provide, resource and implement a written Fire Emergency Plan covering all appropriate procedures, responsibilities and features of the building Ensure that a system of local checks and inspections of fire safety features is implemented throughout all locations. Under BS5306-3:2009, fire extinguishers should be checked at least monthly and the results recorded. See also A/B 2A/B Safety Unit & Estates Estates local management Short term Ongoing 26.0 Training and Drills 26.0 Appropriate fire safety training of contractors' staff should be verified. 3A/B Estates Short term * PRIORIT (N.B. to Fire Service College Fire Safety Engineering Division scale, not PAS 79) Category A. Fire Risk to Persons: 1A - A serious life safety risk and/or a major or serious contravention of current fire safety legislation. This matter requires immediate attention and must be given high priority. 2A - An important life safety issue and/or a contravention of current fire safety legislation and/or official guidance, that may lead to enforcement action if not addressed. This matter requires attention with the minimum of delay.
FIRE RISK ASSESSMENT review
COVER SHEET review in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) Employer or other
More informationFIRE RISK ASSESSMENT REVIEW
COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Director of Kent Business School in conjunction with Council & the Vice Chancellor Kent Business
More informationFIRE RISK ASSESSMENT REVIEW
COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Council & Vice Chancellor; Director of Estates East Oast, University of
More informationSlight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk
Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action
More informationCo-Director, Tizard Centre (P. McGill) in conjunction with Council & the Vice Chancellor
COVER SHEET in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) Responsible Person:
More informationAFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT
AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff
More informationFire Risk Assessment. ABC Car Workshop. Prepared for. Redacted
Fire Risk Assessment Prepared for ABC Car Workshop Assessor: (Assessor s Name) Date of Assessment: 24/07/17 Date of Next Assessment Review: Upon occupation Introduction and Scope This Fire Risk Assessment
More informationFIRE RISK ASSESSMENT REVIEW
COVER SHEET REVIEW in accordance with Publicly Available Standard PAS 79:2011 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) IFSM-accredited
More informationUniversity of Kent; Vice Chancellor; Director of Kent Hospitality
COVER SHEET Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Vice Chancellor; Director of Kent Hospitality Rutherford College (excludes Extension)
More informationOperations, contents etc: Managing Director of Kent Union. Locke Building, University of Kent, Canterbury CT2 7UG
COVER SHEET in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with extensive additions) Employer or
More informationFire Risk Assessment Keys Meadow Primary School
Fire Risk Assessment Keys Meadow Primary School Issue Date: Issued To: Version Number: Approved By: 19 th May 2016 Jane Jenner 1 CS Fire Risk Assessment - Company Name XXX REGULATORY REFORM (FIRE SAFETY)
More informationFire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA
Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Assessment prepared by - Chris Caton MIFireE Pennine Fire & Safety Limited Pleasington Street Blackburn BB2 1UF info@penninefire.co.uk
More informationRegulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation
FIRE RISK ASSESSMENT Retirement Housing (Independent Living) Developed in conjunction with Cambridge shire Fire and Rescue Service, Housing and Care 21 s primary authority (v3.november 2016) Regulatory
More informationByker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014
Type of Property Owner Address of Properties Responsible Person (s) consulted Multi- occupied housing referred to as the Byker Wall Ground floor and varying upper levels with open deck assess to all areas.
More informationFIRE RISK ASSESSMENT REVIEW
COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Head of School of Physical Sciences in conjunction with Council & the Vice Chancellor Ingram
More informationFIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)
FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation The purpose
More informationFIRE RISK ASSESSMENT
FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Rodwell House
More informationTYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)
TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May
More informationFIRE RISK ASSESSMENT Waterstones High Street, Solihull, West Midlands, B91 3SW.
Waterstones 69-71 High Street, Solihull, West Midlands, B91 3SW. BAFE Certificate Number: 0040921 CONTENTS: BAFE SP205 Certificate of Compliance 3 Introduction 5 Risk Assessment Methodology 6 PAS 79 Fire
More informationFIRE RISK ASSESSMENT REVIEW
COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Council & Vice Chancellor; Director of Estates CORNWALLIS BUILDING, University
More informationFIRE RISK ASSESSMENT Self Assessment
FIRE RISK ASSESSMENT Self Assessment Important! This fire risk assessment form is to be filled in by the responsible person within a business or organisation. As this is a free download for the use of
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Hazeldene House
More informationS12 Fire Safety Risk Assessment H&SFS01-1 / 9
S12 Fire Safety Risk Assessment H&SFS01 Risk ratings The following risk ratings are based on two factors: The overall fire risk rating for the site The risk rating for the individual recommendations /control
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Harpwood Care
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the
More informationFIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)
FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning
More informationFire Risk Assessment 2017
Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless
More information1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.
Record of significant findings Risk assessment for : Assessment undertaken by : 71a The Close Nigel Billing CMIOSH Date: 21/3/17 Overview of Premises: 1970s building housing main school reception and support
More informationMillfield Schools Fire Risk Prevention Policy
Millfield Schools Fire Risk Prevention Policy This policy refers to the Senior School, Preparatory School, Pre-Preparatory School and EYFS 1. Introduction This policy sets out the approach that the school
More informationWell managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.
Record of significant findings Risk assessment for : Assessment undertaken by : Horsefair House Nigel Billing CMIOSH Date: 28/3/17 Overview of Premises: 2 buildings on 3 stories in an L shaped configuration,
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT
OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible
More informationManagement Standard: Fire Safety
OHSS: H&S Management 201 Fire Safety Management : Fire Safety 1. Legal framework This standard is produced to comply with the following legislation in respect to fire safety: 1.1. Regulatory Reform (Fire
More informationFire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT
Fire Risk Assessment Report - Initial Prepared by Your Company Name This report took 5 SECONDS to produce & a few MINUTES to collect the data on site! Download the app for FREE at www.pocketsurvey.com
More informationfire risk assessment For use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
More informationFire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes
Fire Assessment Location details Company Name Site address Site contact name Phone Guidance Notes looking at the workplace to identify potential A hazard is something that has the potential to cause harm;
More informationFire Safety Protocol
CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford
More informationHealth and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014
Fire Safety Policy Originator name: Section / Dept: Implementation date: Clive Parkinson Health & Safety March 2014 Date of next review: March 2017 Related policies: Health and Safety Policy Policy history:
More informationFire Risk Assessment Report
Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Science Block Hillcrest Rd, London W5 2JL 020 8997 2022 Bursar J Powell
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE
FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification
More informationISLE OF WIGHT FIRE & RESCUE SERVICE
ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS
More informationHealth & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome
Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome 1.0 Draft 07.03.2016 David Maine 1 st Draft for consultation/review 1.1 Approved 22.12.2016 David Maine 1
More informationThe Regulatory Reform (Fire Safety) Order Fire Risk Assessment Report
42 Haslucks Croft, Shirley, Solihull, B90 2EQ (t) 0121 249 1281 (m) 07814 203 977 www.veritas-consulting.co.uk The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Report Client The Company
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE
FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)
FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS
FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber
More informationSandwell Valley School and Sandwell Community Care Trust Training. 150 Birmingham Road, West Bromwich, B70 6QT
Fire Risk Assessment Company ame Address of premises (premises being assessed) Sandwell Valley School and Sandwell Community Care Trust Training 150 Birmingham Road, West Bromwich, B70 6QT ame of Responsible
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:
More informationFire Risk Assessment Report
Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Clockhouse Nursery and Early ears Hillcrest Rd, London W5 2JL 020 8997
More informationFIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre
FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job
More informationFire Risk Assessment Safety Checklist
Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory
More informationH&S Forum. Fire Safety Policy Glascote Academy
Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford
More informationFollowing a near miss (after a fire or where evidence suggests that a fire could have occurred).
Contents: This is your Fire Risk Assessment Revision of this risk assessment Scope of assessment and methodology Executive Summary Risk Rating Assessment Overview The Responsible Person/Duty Holder Persons
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the
More information5 Key Stages to Risk Assessment
5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking
More informationFIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017
Date: March 2017 Page 1 of 12 FIRE SAFETY POLICY Approval Approved by: University Court Date: March 28 th 2017 Page 1 of 12 Date: March 2017 Page 2 of 12 UNIVERSITY OF ABERDEEN FIRE SAFETY POLICY Contents
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:
More informationFire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1
Billy Hanafin H & S and Operations Officer Version 1.0 October 2013 Page 1 1. General The Trust is a responsible employer that takes its Fire Safety duties seriously. For that reason, this policy has been
More informationFire Risk Management Policy. UK September 2017
UK September 2017 5 & 7 Diamond Court, Opal Drive, Eastlake Park, Fox Milne, Milton Keynes MK15 0DU, T: 01908 396250, F: 01908 396251, www.cognitaschools.co.uk Registered in England Cognita Limited No
More informationFIRE PROCEDURES 1. APPOINTMENTS
12b FIRE PROCEDURES 1. APPOINTMENTS Responsible Person In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO), the School s Head, Mrs C Cameron is appointed as the Responsible Person for
More informationLYHA Fire Safety Policy
LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with
More informationFire Risk Assessment Case Study
Appendix B Fire Risk Assessment Case Study The purpose of this case study is to illustrate one practical approach to conducting a fire risk assessment. The checklist and proformas used in this case study
More informationFIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY
FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY Under the terms of the Regulatory Reform (Fire Safety) Order 2005, and subsequent regulations, Seaford College must ensure the safety from fire of all staff,
More informationFire Risk Assessment 2016
Fire Risk Assessment 2016 Elleray Campus Windermere School Author Paul Brownless Date 07 December 2016 Reviewed Reviewer 20 November 2017 Richard Hennah Reference FRA_EC_07122016 1 AUTHOR CLIENT Paul Brownless
More informationA basic guide to... Fire Safety for Scout Premises
A basic guide to... Fire Safety for Scout Premises A basic guide to Fire Safety for Scout Premises This Guide has been designed and produced by Chubb Fire to assist persons responsible for fire safety
More informationNOTTINGHAM CITY HOMES
APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes
More informationGlenmere Primary School Fire Safety Policy FIRE SAFETY POLICY. Revised on April Sam Conlon. Created by S.Conlon 1
FIRE SAFETY POLICY Revised on April 2018 By Sam Conlon Created by S.Conlon 1 Legal framework Contents Responsibilities of local governing body Responsibilities of Headteacher Responsibilities of premises
More informationGDST Fire Safety Strategy March 2016
GDST Fire Safety Strategy March 2016 GDST Fire Safety Strategy v1.0 March 2016 Page 1 of 17 Contents 1. Introduction 3 2. Compliance Statement 3 3. Fire Safety Strategy Aims and Objectives 3 Strategic
More informationSOUTHERN HEALTH NHS FOUNDATION TRUST
SOUTERN EALT NS FOUNDATION TRUST REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Address of Property: Person(s) consulted: Parklands ospital, Aldermaston Road Basingstoke
More informationHealth, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service
Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in
More informationKRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer
KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY Last Review Date 30 June 2015 Policy endorsed by Policy is maintained by ISI reference Trustees Co-Principals/Directors A9, B6, B9 Next review date 30 August
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More informationTo: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard
SOCIAL ACCOUNTABILITY ACCREDITATION SERVICES To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard Background: After an
More informationFire risk management plan. MH/05/Revised/06/17
Fire risk management plan MH/05/Revised/06/17 1 1. Scope This policy applies to fire safety arrangements in all workplaces, common areas of residential premises and any other premises managed and/or owned
More informationFire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy
Holme Grange School Whole School Policy Including EYFS Fire Safety Policy This document details the school s policy on fire safety in operation at Holme Grange School. The document is split into a number
More informationEMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be
EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety
More informationFire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD
Fire Safety Policy Somerville College Woodstock Road Oxford OX2 6HD Table of Contents 1.0 Introduction... 2 2.0 Legislative Requirements... 2 3.0 Fire Risk Assessment... 3 4.0 Management of Fire Safety...
More informationWellsprings Primary School. Fire Emergency Evacuation Plan
Wellsprings Primary School Fire Emergency Evacuation Plan This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the plan is: To ensure the safety
More informationFire Risk Assessment DURSTON HOUSE SCHOOL Castlebar Road, Ealing, London, W5 2DR. Prepared by: Steven Cox BA(Hons), ACII, AIOSH
Fire Risk Assessment DURSTON HOUSE SCHOOL 12-14 Castlebar Road, Ealing, London, W5 2DR Prepared by: Steven Cox BA(Hons), ACII, AIOSH Hettle Andrews & Associates Limited Eleven Brindleyplace 2 Brunswick
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationFire Risk Assessment
Fire Risk Assessment Department The Cockpit Risk Assessment number PM/06/2015 Date. 17 th June 2015 Review due date 17 th June 2016 Activity: Fire safety risk assessment Location: The Cockpit Name of Assessors:
More informationFIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY
FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY Under the terms of the Box Hill School must ensure the safety from fire of all staff, pupils, contractors and visitors. In order to do this the school
More informationLocal Rules: Fire Safety
1. Potential Effects of a Fire A small fire is most likely to cause damage to equipment and furniture, with the potential to cause additional smoke damage to the room of origin. A large and protracted
More informationFire Safety Management Audit Specification August 2017
Fire Safety Management Audit Specification August 2017 Membership Training Qualifications Audit and Consultancy Policy and Opinion Awards Contents Page 1 Introduction to the Fire Safety Management Audit
More informationFire Safety Policy 2018/19
Fire Safety Policy 2018/19 Reviewed: March 2016 Next Review: March 2019 1. Policy Statement The School is committed to ensuring, so far as is reasonably practicable, the health, safety and welfare of all
More informationUNIVERSITY COLLEGE LONDON REGULATORY REFORM (FIRE SAFETY) ORDER 2005
UNIVERSITY COLLEGE LONDON REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Responsible Person (e.g. employer) or person having control of the premises: University College London Address
More informationFire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019
Fire Safety Policy (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January 2018 Next Review: January 2019 Person Responsible: School Business Manager 1 P age 1. INTRODUCTION a) King Fahad
More informationFire Risk Assessment Guidance
Fire Risk Assessment Guidance This document is a guidance note to accompany the example fire risk assessment template. The example fire risk assessment template has been designed with small to medium domestic
More informationFIRE SAFETY POLICY. Health and Safety. Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018)
FIRE SAFETY POLICY Owner: Health and Safety Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018) Review due date: May 2019 Update history: Approved by Council 8 March
More informationKings Fire Safety Policy
Kings Fire Safety Policy All Kings policies will be ratified by the Board of Directors and signed by the Chairperson. Each policy will be co-signed by the principal of each school. Review dates will be
More informationSt Edward s Oxford FIRE SAFETY POLICY
FIRE SAFETY POLICY 1 CONTENTS Section Page No.(s) 1. Policy Statement 3-5 2. Organisation and Responsibilities 6 3. Responsibilities of Responsible Person 7-8 4. Responsibilities of Senior Management 9
More informationFire Risk Assessment Guide
Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are
More informationUCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES
Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments
More informationWILTSHIRE POLICE FORCE PROCEDURE. Fire Safety Management
WILTSHIRE POLICE FORCE PROCEDURE Fire Safety Management Date of Publication: May 2018 Version: 8.0 Next Review Date: May 2019 TABLE OF CONTENTS PROCEDURE OVERVIEW... 3 GLOSSARY OF TERMS... 3 RELATED POLICIES,
More informationFIRE RISK ASSESSMENT. Hatton House. Page 1 of 21
FIRE RISK ASSESSMENT Hatton House Page 1 of 21 CONTENTS Page 1 Introduction 3-6 2 Premises Particulars 7 3 General Statement Of Policy 7 4 Management Systems 7 5 General Description Of Premises 9 6 Fire
More informationFIRE SAFETY POLICY. This policy document replaces any previously published documents and comes into effect September 2018.
FIRE SAFETY POLICY This policy document replaces any previously published documents and comes into effect September 2018. 1.0 Fire Safety: The priority of Shrewsbury School is to minimise the risk to life
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the
More information