FIRE RISK ASSESSMENT REVIEW

Size: px
Start display at page:

Download "FIRE RISK ASSESSMENT REVIEW"

Transcription

1 COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Council & Vice Chancellor; Director of Estates East Oast, University of Kent, Canterbury Sports & SDFVA management; Georgia Wright, fine art technician; Estates staff Andrew Briggs, TechIFSM, MIIRSM Date of Fire Risk Assessment: 6th to 10th October 2008 Date of Previous Fire Risk Assessment: Suggested Date for Review: 15th June SHOULD BE READ IN CONJUNCTION WITH THIS REVIEW. October 2010, or as per UoK SHEU official schedule, or in event of significant change Document dated 10th October 2008 Correction 28/10/08: 4 above (incorrectly read 'Director of Kent Hospitality') Fire Risk Assessment in accordance with Publicly Available Standard PAS 79 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology

2 COVER SHEET

3 GENERAL BUILDING DESCRIPTION 1.0 The Building 1.1 Number of floors Approximate floor area: Not reviewed at this time 1.3 Construction Details: Traditional brick; timber upper structure & roof including traditional square oast 1.4 Occupancy: Ground floor - sports changing facility in poor condition, currently used only once a week First floor - fine art studio 2.0 The Occupants 2.1 Approximate maximum number: Estimate 10 (first floor) 2.2 Maximum number of staff at any one time: 1 or 2 regularly/occasionally 2.3 Maximum number of members of public: Currently N/A 3.0 Occupants at Special Risk 3.1 Sleeping occupants: Nil 3.2 Occupants with disabilities: According to practicable/stated accessibility - see Occupants in remote areas: Occasional brief presence in oast store 3.4 Others: Nil 4.0 Fire Loss Experience 4.1 Fires in past 10 years: Nil

4 GENERAL BUILDING DESCRIPTION 4.2 Cost of fire losses: Nil 5.0 Other Relevant Information 5.1 Detail: N/A 6.0 Relevant Fire Safety Legislation 6.1 Statutory provisions etc: Regulatory Reform (Fire Safety) Order 2005, referred Official Guidance & related British Standards/Euro Norms etc.

5 The following is based on BS9999 concepts and principles, which may be used in conjunction with official guidance in assessing risks. Categories relevant to the building are highlighted. Occupant risk categories Risk category Description Comments A Occupants who are awake and Staff; students familiar with the building B Occupants who are awake and unfamiliar with the building C Occupants who are likely to be asleep: Ci long-term individual occupancy Cii long-term managed occupancy Ciii short-term occupancy D Occupants receiving medical care E Occupants in transit Fire growth rate(s) Category Fire growth rate Typical fire growth parameter, kj/s3 Locations (where specific) & categories 1 Slow Ground floor 2 Medium First floor 3 Fast First floor (especially contents of oast store) 4 Ultra-fast Risk profiles: Range A1 to A3 Management level required: 1 Written explanation of BS9999 management levels pending. Environmental risks Heritage aspects Fire-fighting water runoff and temporary release of combustion products to atmosphere only; no other significant environmental impact likely Contrary to previous FRA, East Oast is not a Listed building.

6 FIRE HAZARDS INDE DETAIL ES NO N/A COMMENTS, CONTROL MEASURES REQUIRED ETC FURTHER COMMENTS, DETAIL, CLARIFICATION ETC DESCRIPTIONS, JUSTIFICATIONS ETC 7.0 Electrical Sources of Ignition Continue to maintain safe separation distance of ½ metre between appliances and combustible materials in all areas, to ensure that sources of heat do not arise from faulty or overloaded electrical equipment, to ensure that all electrical fuses and circuit breakers etc of the correct rating and suitable for the purpose, and to switch equipment off at the end of the working day wherever possible. 7.1 Reasonable measures taken to prevent fires of electrical origin? 7.2 Fixed installation periodically inspected and tested? Portable appliance testing carried out? Suitable policy regarding use of personal electrical appliances? Suitable limitation of trailing leads and adaptors? First floor intruder alarm should be hard-wired to the electrical supply. Electrical intake (domestic type circuit breaker board) on ground floor is not in a fire resisting enclosure, but entire ground floor is currently relatively fire sterile.? (1) Management should verify/ensure that testing of electrical installations and portable appliances is implemented on an appropriate scheduled basis. (2) The electrical circuit to the oast store lighting may require investigation and repair (fizzled and tripped out during visit). 8.0 Smoking Ensure University smoking policy continues to be implemented and enforced insofar as possible. 8.1 Reasonable measures taken to prevent fires as a Provide statutory No Smoking signs at building entrance(s). result of smoking? Prohibited where appropriate? Arrangements for smokers? Evidence of breaches? 9.0 Arson Continue to ensure that no combustible materials are left immediately outside building at any time. 9.1 Does basic security against arson by outsiders Minor combustible items under external escape staircase at time of visit must be appear reasonable? Fire load available for removed. ignition by outsiders? Timber structure of building is vulnerable to any fire Cooking & Heating 10.1 Are reasonable measures taken to prevent fires as a result of cooking & heating? Is all essential maintenance up to date and recorded? Strictly no portable electrical heaters with bare elements (e.g. convector, fan, Strict control of electrical heaters is all the more important since the radiant) should be used on the first floor; this information must be conveyed to all subdivision of the studio space will render the heating installation users of the building. much less effective Are filters changed and ductwork cleaned regularly? 10.3 Are suitable extinguishing appliances available? 11.0 Lightning 11.1 Does the building have a lightning protection system?? Ensure building has been or is risk assessed for lightning strike, and appropriate action taken Other Significant Ignition Sources 12.1 Are there other significant ignition sources present? Continue to maintain safe separation distance of ½ metre between appliances and combustible materials. Switch equipment off at the end of the working day. Ensure ban on candles, joss sticks etc continues to be enforced insofar as possible Housekeeping 13.1 Is the standard of housekeeping adequate? Largely adequate - continued active vigilance is likely to be necessary by management/supervision (see also 16.9). Ensure that housekeeping programme continues to include prompt and appropriate removal of combustible materials and waste Are combustible materials separated from ignition Continue to maintain safe separation distance of ½ metre between appliances sources? and combustible materials throughout building Is there an avoidance of unnecessary accumulation of combustible materials or waste? Management should ensure that combustible materials in use (including works of art themselves) are kept at all times in an orderly manner so as to minimise flame spread in the event of a fire. Ensure that combustible items are not present in escape routes at any time.

7 FIRE HAZARDS 13.4 Is there appropriate storage of combustible materials? 13.5 Is there avoidance of inappropriate storage of combustibles materials? 14.0 Outside Contractor and Building Works Hazards 14.1 Is there satisfactory control over works carried out in the building by outside contractors? 14.2 Are adequate fire safety conditions imposed on outside contractors? Management should ensure that combustible materials in storage (especially including works of art) are kept at all times to a reasonable minimum and stored in an orderly manner so as to minimise flame spread in the event of a fire. Flammables cabinet should be repaired/adjusted/replaced so as to close fully, easily and reliably (there is some damage/distortion to the doors). Appropriate control (including Permits To work where appropriate) administered by Estates. Local department(s) should however ensure that contractors are briefed on, and accounted for, under building Fire Emergency Plan (also that contractors' dangerous substances are known & logged - see 15) Dangerous Substances 15.1 Have the hazardous properties of dangerous substances been considered? 15.2 Is there adequate information on safety provided by the supplier on any relevant safety data sheet? 15.3 Has account been taken regarding: the special, technical and organisational measures and the substances used and their possible interactions. the amount of the substance involved where the work will involve more than one dangerous substance, the risk presented by such substances in combination the arrangements for the safe handling, storage and transport of dangerous substances and of waste containing dangerous substances any other measures introduced as a result of the RRO 15.4 Are there safe systems of work for maintenance, where there is the potential for a high level of risk? 15.5 Are sufficient control measures in place to counter the likelihood that an explosive atmosphere will occur and its persistence including adjacent areas? 15.6 Are sufficient control measures in place to counter the likelihood that ignition sources, including electrostatic discharges, will be present and become active and effective 15.7 Has account been taken regarding the scale of the anticipated effects? 15.8 Is sufficient additional safety information available to enable the assessment to be completed? Continue to keep the quantities of flammable and readily combustible substances to a minimum. MSDSs available. N First floor: the premises are of poor fire resistance, especially in relation to the present use (in particular, the flammable and readily combustible materials present). Management and users of the facilities must continue to be made highly aware of risks, precautions and emergency procedures. Continue to inform and instruct all building users in precautions regarding autoignition risks associated with vegetable oils. Fire fighting equipment training referred to at 25.3.

8 FIRE PROTECTION INDE DETAIL ES NO N/A CONTROL MEASURES FURTHER COMMENTS, DETAIL, CLARIFICATION ETC DESCRIPTIONS, JUSTIFICATIONS ETC 16.0 Means of Escape 16.1 Is it considered that the building is provided with reasonable means of escape in case of fire? 16.2 Is there adequate provision of exits? (Calculate for room and premises occupancy numbers & types, where relevant.) 16.3 Are exits easily and immediately openable where necessary? (Alarm-linked features such as electronic door release mechanisms to be verified as compliant, functional and suitably failsafe) 16.4 Do escape exits open in the direction of escape where necessary? 16.5 Are there satisfactory means for securing exits? Glass tube and hammer should be replaced at first floor alternative exit (plastic tube inserted, but door remains easily openable) Are there reasonable travel distances where there is a single direction of travel? 16.7 Are there reasonable travel distances where there is an alternative means of escape? 16.8 Is there suitable protection of escape routes? Half-hour separation of internal staircase may be slightly compromised but appears acceptable in view of premises size, occupancy, alternative route and available escape time - despite risks present Are all escape routes unobstructed? N Alternative first floor exit found blocked by large easel and fire extinguisher. All escape routes must be maintained unobstructed at all times. Management must ensure that all users of the building are suitably informed, instructed and trained and act accordingly at all times - especially in view of risks present and likely fire growth rate on first floor Is the building provided with reasonable arrangements for means of escape for occupants with disabilities? N (1) Types of disability that cannot be accommodated must be established in detail; the building Fire Emergency Plan and other University information should specify accordingly. (2) For any disabled persons that can be accommodated, a system of generic and specific Personal Emergency Evacuation Plans must be provided. SDFVA suggestion to demarcate escape route gangway in studio space, with floor tape, would be a significant improvement. Greater provision of technical, physical, organisational and human resources is being developed on a campus-wide basis to provide comprehensive systems for disabled evacuation. Local departments and building occupants may be required to assist with implementing such plans Fire Spread and Development Limitation 17.1 Is it considered that there is compartmentation of a reasonable standard? (Including e.g. dampers in ductwork; fire-stopping of service penetrations) 17.2 Is it considered that there is reasonable limitation of linings that may promote fire spread?? Integrity and effectiveness of fire resisting construction appears mostly acceptable but should be thoroughly checked/audited throughout - especially in view of risks present, and especially with regard to fire separation of the oast store. Continue to ensure that there no combustible items are posted on the internal staircase Escape Lighting 18.1 Is a reasonable standard of escape lighting provided? Emergency lighting should be provided outside all final exits unless/except where street lighting etc. is adequate for this purpose. Premises are used until 9pm Fire Safety Signs and Notices 19.1 Does the building have a reasonable standard of fire safety signs and notices? (1) Fit "fire escape keep clear" sign to interior of first floor alternative exit door and outside all final exits. (2) Provide suitable Fire Action Notices at all final exits and storey exit Fire Warning Arrangements

9 FIRE PROTECTION 20.1 Is a reasonable manually operated electrical fire alarm system provided? N Strict prescription according to forthcoming BS9999 would require the installation of an electrical fire alarm system complying to BS 5839, L2, preferably linked to Security. However, the ground floor is particularly fire-sterile; the current use of the first floor is temporary; and the layout and occupancy of the first floor is such that shouting would be sufficient for a manual alarm. See recommendation at Is automatic fire detection provided in building? N Automatic fire detection must be fitted to the studio space and store rooms (see 20.1) Is the fire alarm system audible or perceptible throughout the building? 20.4 Is there a remote transmission of alarm signal? Requirements as above (20.1 & 3) Portable Fire Extinguishing Appliances 21.1 Is the provision of portable fire extinguishers reasonable? 21.2 Are hose reels provided? N Management must ensure that a robust and effective system is implemented for immediately making all occupants aware of a fire emergency, and for summoning Campus Watch. Re-mount extinguisher at first floor alternative exit. Continue to ensure that extinguishers remain unobstructed at all times Automatic Fixed Systems 22.1 Is there a suitable sprinkler or water based system that is adequate for the risk present? 22.2 Is there a suitable gaseous local application or total flooding provided that is adequate for the risk? Other Fixed Systems 22.3 Are there suitable smoke control facilities for the risk present? 23.0 Luminous Discharge Tubes 23.1 Has notice been given to the Fire & Rescue Authority regarding luminous discharge tubes cutoff switch, its colouring and marking.

10 MANAGING FIRE SAFET INDE DETAIL ES NO N/A CONTROL MEASURES FURTHER COMMENTS, DETAIL, CLARIFICATION ETC DESCRIPTIONS, JUSTIFICATIONS ETC 24.0 Procedures and Arrangements 24.1 Appropriate fire procedures in place (including calling the fire service)? N Provide, resource and implement a written Fire Emergency Plan covering all appropriate procedures, responsibilities and features of the building. The Plan should include for academic staff etc to take responsibility for the evacuation of students in their presence; to positively confirm full evacuation of the building or otherwise; and to provide clear instructions for liaising with the fire brigade on arrival and notifying them of any special risks or conditions. A diagrammatic plan of the building, escape routes, and other fire safety features should be provided Training and drills Are all staff given instruction on induction, and periodic refresher training at suitable intervals? Are all students and visitors given suitable suppl. information and instruction? Are fire emergency evacuation drills suitably suppl. conducted? 25.3 Do key staff have suitable competence & training? (Responsible & competent persons, fire marshals etc, nominated fire extinguisher users, academic staff, etc) > > > [Continue to] ensure full & appropriate induction information and training is provided to all employees, with suitable refresher information and training at not less than three year intervals. Especially critical for this building is familiarity with the current means of raising the alarm to ensure all present evacuate immediately, along with the potential for rapid fire spread on the upper floor. Cannot generalise - may be variable by department Continue to ensure adequate fire safety information and briefing is given to all students and visitors. Fire safety awareness and behaviour should be enhanced by any available means. Basic information on the use of fire extinguishers should be included. Especially critical for this building is familiarity with the current means of raising the alarm to ensure all present evacuate immediately, along with the potential for rapid fire spread on the upper floor. N Conduct fire drills in accordance with official guidance. For the purposes of fire drills, a main circulation route should be blocked to simulate the conditions of a real fire. N Appropriate persons should be nominated and trained as appropriate for fire safety requirements such as regular inspections and coordinating evacuations. Full fire extinguisher training is not deemed necessary in view of the size, use and occupnacy of the premises: Security officers will respond; for occupants, basic information/instruction will suffice for emergency use only if necessary to effect an escape Inspection, Testing and Maintenance 26.1 Adequate maintenance and checking of workplace and fire safety features? N Ensure that a system of checks and inspections of fire safety features is implemented throughout all locations. Checks should take account of behavioural aspects such as abuse of fire safety provisions. Fire extinguishers should be checked at least monthly and the results recorded Weekly testing and periodic servicing of fire detection and alarm system? 26.3 Monthly, six-monthly and annual testing routines for emergency lighting? 26.4 Annual maintenance of fire extinguishing appliances? 26.6 Weekly testing and periodic inspection of sprinkler installations? 26.7 Other relevant inspections or tests: (including e.g. ductwork dampers, fire shutters, venting systems, door holdback devices, electronic door release systems) N Implement appropriate maintenance and testing of emergency lighting Records

11 MANAGING FIRE SAFET 27.1 Are appropriate records kept for fire training? > > > Provide/maintain records of fire safety training, if/where not currently recorded Are appropriate records kept for fire alarm tests? Response field left blank - mostly 'yes' but inevitably variable by department 27.3 Are appropriate records kept for escape lighting tests? 27.4 Are appropriate records kept for the maintenance and testing of other fire protection systems? Provide and maintain a register of fire safety records including escape lighting tests (when implemented - see 26.3) oung Persons Have the following matters been taken into particular account in risk assessment in respect of 28.1 young persons: the inexperience, lack of awareness of risks and 28.2 immaturity of young persons 28.3 the fitting-out and layout of the premises the nature, degree and duration of exposure to 28.4 physical and chemical agents the form, range, and use of work equipment and 28.5 the way in which it is handled; 28.6 the organisation of processes and activities the extent of the safety training provided or to be 28.7 provided to young persons risks from agents, processes and work listed in the Annex to Council Directive 94/33/EC on the 28.8 protection of young people at work Confirmed that no young persons are present at any time on the upper floor. The lower floor is particularly fire sterile and well provided with final exits Behavioural Aspects Is there evidence from previous fire drills and other emergencies indicating that some occupants may be unaware, unwilling or fail to 29.1 evacuate? (Aside from disability-related) Is there evidence of disregard of fire safety provisions amongst building occupancy and management? 29.2 Is there evidence of significant human 29.3 interference with fire safety provisions? N Re first floor - change of use to fine art studio was not fire risk assessed, premises are relatively unsuitable for the inherent fire loading and risks, and suitable arrangements have not yet been made (e.g. automatic fire detection).

12 This simple risk level estimator is based on a more general health and safety risk level estimator in BS 8800: Potential consequences of fire Slight harm Moderate harm Extreme harm Fire hazard Low Trivial risk Tolerable risk Moderate risk Medium Tolerable risk Moderate risk Substantial risk High Moderate risk Substantial risk Intolerable risk Taking into account the fire prevention measures observed at the time of this risk assessment, it is considered that the hazard from fire (probability of ignition) at this building is: Low / highly unlikely Medium / unlikely High / likely Taking into account the nature of the building and the occupants, as well as the fire protection and procedural arrangements observed at the time of this risk assessment, it is considered that the consequences for life safety in the event of fire would be: Slight harm - following completion of recommendations of this fire risk assessment Moderate harm Extreme harm - OR - - prior to completion of recommendations of this fire risk assessment In this context, a definition of the above terms is as follows: Slight harm: Moderate harm: Extreme harm: Outbreak of fire unlikely to result in serious injury or death of any occupant (other than an occupant sleeping in a bedroom in which a fire occurs). Outbreak of fire could result in injury of one or more occupants, but it is unlikely to involve multiple fatalities. Significant potential for serious injury or death of one or more occupants.

13 Accordingly, it is considered that the risk to life from fire at this building is: Trivial Tolerable - following completion of recommendations of this fire risk assessment Moderate Substantial - prior to completion of recommendations of this fire risk assessment Intolerable A suitable risk-based control plan should involve effort and urgency that is proportional to risk. The following risk-based control plan is based on one advocated by BS 8800 for general health and safety risks: Trivial Tolerable Moderate Risk Level Action and Timescale No action is required and no additional detailed records need be kept. No major additional controls required. However, there may be a need for consideration of improvements that involve minor or limited cost, and various corrective actions may be required. It is essential that efforts are made to reduce the risk. Risk reduction measures should be implemented within a defined time period. Where moderate risk is associated with consequences that constitute extreme harm, further assessment may be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures. Substantial Intolerable Considerable resources may have to be allocated to reduce the risk. If the building is unoccupied, it should not be occupied until the risk has been reduced. If the building is occupied, urgent action should be taken. Building (or relevant area) should not be occupied until the risk is reduced.

14 Any significant change, occurrence, finding or development should be reported immediately to the University s Safety, Health & Environment Unit so that mitigating action can be taken and this Fire Risk Assessment reviewed and updated.

15 ACTION PLAN ORGANISATION: University of Kent BUILDING: East Oast ASSESSOR: Andrew Briggs DATE: 10th October 2008 ACTION PLAN It is considered that the following recommendations should be implemented in order to reduce fire risk to, or maintain it at, the following level: TOLERABLE REFERENCE ACTION REQUIRED TO ELIMINATE OR CONTROL SIGNIFICANT HAZARDS PRIORIT * RESPONSIBILIT TARGET DATE COMPLETE 6 figure numbers See also Further Comments/Detail/Clarification etc. in previous worksheets, where relevant are Estates Helpdesk Work Requests or carried forward to: 7.0 Electrical Sources of Ignition 7.1 First floor intruder alarm should be hard-wired to the electrical supply. 3A/B Estates 7.2 (1) Management should verify/ensure that testing of electrical installations and portable appliances is implemented on an appropriate scheduled basis. (2) The electrical circuit to the oast store lighting may require investigation and repair (fizzled and tripped out during visit). (1) 1A/B (2) 3A/B Estates 8.0 Smoking 8.1 Provide statutory No Smoking signs at building entrance(s). 2A/B Lightning 11.1 Ensure building has been or is risk assessed for lightning strike, and appropriate action taken Housekeeping 13.5 Flammables cabinet should be repaired/adjusted/replaced so as to close fully, easily and reliably (there is some damage/distortion to the doors) Means of Escape (1) Types of disability that cannot be accommodated must be established in detail; the building Fire Emergency Plan and other University information should specify accordingly. (2) For any disabled persons that can be accommodated, a system of generic and specific Personal Emergency Evacuation Plans must be provided. 2A/B 1A/B (1) 4A (2) 1A Estates SDFVA SDFVA, Estates & Safety Unit 17.0 Fire Spread and Development Limitation

16 ACTION PLAN 17.1 Integrity and effectiveness of fire resisting construction appears mostly acceptable but should be thoroughly checked/audited throughout - especially in view of risks present, and especially with regard to fire separation of the oast store. 2A/B Estates 18.0 Escape Lighting 18.1 Emergency lighting should be provided outside all final exits unless/except where street lighting etc. is adequate for this purpose Fire Safety Signs and Notices 19.1 (1) Fit "fire escape keep clear" sign to interior of first floor alternative exit door and outside all final exits. (2) Provide suitable Fire Action Notices at all final exits and storey exit Fire Warning Arrangements 20.2 Automatic fire detection must be fitted to the studio space and store rooms (see 20.1) Management must ensure that a robust and effective system is implemented for immediately making all occupants aware of a fire emergency, and for summoning Campus Watch. 2A 1A/B 1A 1A SDFVA to determine and report (1) Estates (2) Safety Unit & SDFVA Estates SDFVA (& Sports Centre) 21.0 Portable Fire Extinguishing Appliances 21.1 Re-mount extinguisher at first floor alternative exit. 2A/B Procedures and Arrangements 24.1 Provide, resource and implement a written Fire Emergency Plan covering all appropriate procedures, responsibilities and features of the building. The Plan should include for academic staff etc to take responsibility for the evacuation of students in their presence; to positively confirm full evacuation of the building or otherwise; and to provide clear instructions for liaising with the fire brigade on arrival and notifying them of any special risks or conditions. A diagrammatic plan of the building, escape routes, and other fire safety features should be provided. 1A/B Estates, Safety Unit, SDFVA & Sports Centre 25.0 Training and drills [Continue to] ensure full & appropriate induction information and training is provided to all employees, with suitable refresher information and training at not less than three year intervals. Especially critical for this building is familiarity with the current means of raising the alarm to ensure all present evacuate immediately, along with the potential for rapid fire spread on the upper floor. 1A All departments, especially SDFVA

17 ACTION PLAN suppl. Continue to ensure adequate fire safety information and briefing is given to all students and visitors. Fire safety awareness and behaviour should be enhanced by any available means. Basic information on the use of fire extinguishers should be included. Especially critical for this building is familiarity with the current means of raising the alarm to ensure all present evacuate immediately, along with the potential for rapid fire spread on the upper floor suppl. Conduct fire drills in accordance with official guidance. For the purposes of fire drills, a main circulation route should be blocked to simulate the conditions of a real fire Appropriate persons should be nominated and trained as appropriate for fire safety requirements such as regular inspections and coordinating evacuations. 1A 1A 2A/B SDFVA Estates (with SDFVA & Sports Centre) SDFVA & Sports Centre, or by mutual arrangement 26.0 Inspection, Testing and Maintenance 26.1 Ensure that a system of checks and inspections of fire safety features is implemented throughout all locations. Checks should take account of behavioural aspects such as abuse of fire safety provisions. Fire extinguishers should be checked at least monthly and the results recorded. 2A/B SDFVA & Sports Centre, or by mutual arrangement 26.3 Implement appropriate maintenance and testing of emergency lighting. 2A Estates 27.0 Records 27.1 Provide/maintain records of fire safety training, if/where not currently recorded. 2A/B All departments * PRIORIT (N.B. to Fire Service College Fire Safety Engineering Division scale, not PAS 79) Category A. Fire Risk to Persons: 1A - A serious life safety risk and/or a major or serious contravention of current fire safety legislation. This matter requires immediate attention and must be given high priority. 2A - An important life safety issue and/or a contravention of current fire safety legislation and/or official guidance, that may lead to enforcement action if not addressed. This matter requires attention with the minimum of delay. 3A - A significant life safety issue which, in combination with other significant findings, may result in an increased risk to persons. Advised to implement programme of work or action in accordance with good fire safety practice.

18 ACTION PLAN 4A - A life safety issue recommended for consideration in accordance with good fire safety practice. Advised to implement action or programme of work as appropriate. Category B. Fire Risk to Property, Business Continuity, Environment, Amenity, Heritage etc. 1B - A serious risk of damage by fire (with possible legal implications, depending on the enforcing authority involved). This matter requires immediate attention and must be given high priority. 2B - An important potential fire damage issue (with possible legal implications, depending on the enforcing authority involved). This matter requires attention with the minimum of delay. 3B - A significant potential fire damage issue which, in combination with other significant findings,may result in an increased risk to the property. Advised to implement programme of work or action in accordance with good fire protection/prevention practice. 4B - A property protection issue recommended for consideration as a medium of longer term objective in accordance with good fire prevention/protection practice. Advised to implement action or programme of work as appropriate.

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Director of Kent Business School in conjunction with Council & the Vice Chancellor Kent Business

More information

FIRE RISK ASSESSMENT review

FIRE RISK ASSESSMENT review COVER SHEET review in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) Employer or other

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Director of Estates in conjunction with Council & the Vice Chancellor Brotherhood Boiler House,

More information

University of Kent; Vice Chancellor; Director of Kent Hospitality

University of Kent; Vice Chancellor; Director of Kent Hospitality COVER SHEET Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Vice Chancellor; Director of Kent Hospitality Rutherford College (excludes Extension)

More information

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action

More information

Co-Director, Tizard Centre (P. McGill) in conjunction with Council & the Vice Chancellor

Co-Director, Tizard Centre (P. McGill) in conjunction with Council & the Vice Chancellor COVER SHEET in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) Responsible Person:

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW in accordance with Publicly Available Standard PAS 79:2011 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with additions) IFSM-accredited

More information

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted Fire Risk Assessment Prepared for ABC Car Workshop Assessor: (Assessor s Name) Date of Assessment: 24/07/17 Date of Next Assessment Review: Upon occupation Introduction and Scope This Fire Risk Assessment

More information

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation FIRE RISK ASSESSMENT Retirement Housing (Independent Living) Developed in conjunction with Cambridge shire Fire and Rescue Service, Housing and Care 21 s primary authority (v3.november 2016) Regulatory

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: University of Kent; Council & Vice Chancellor; Director of Estates CORNWALLIS BUILDING, University

More information

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May

More information

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation The purpose

More information

Operations, contents etc: Managing Director of Kent Union. Locke Building, University of Kent, Canterbury CT2 7UG

Operations, contents etc: Managing Director of Kent Union. Locke Building, University of Kent, Canterbury CT2 7UG COVER SHEET in accordance with Publicly Available Standard PAS 79:2007 (British Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology (with extensive additions) Employer or

More information

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Assessment prepared by - Chris Caton MIFireE Pennine Fire & Safety Limited Pleasington Street Blackburn BB2 1UF info@penninefire.co.uk

More information

Fire Risk Assessment Keys Meadow Primary School

Fire Risk Assessment Keys Meadow Primary School Fire Risk Assessment Keys Meadow Primary School Issue Date: Issued To: Version Number: Approved By: 19 th May 2016 Jane Jenner 1 CS Fire Risk Assessment - Company Name XXX REGULATORY REFORM (FIRE SAFETY)

More information

FIRE RISK ASSESSMENT REVIEW

FIRE RISK ASSESSMENT REVIEW COVER SHEET REVIEW Employer or other Responsible Person: Address of Property: Person(s) Consulted: Assessor: Head of School of Physical Sciences in conjunction with Council & the Vice Chancellor Ingram

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

S12 Fire Safety Risk Assessment H&SFS01-1 / 9

S12 Fire Safety Risk Assessment H&SFS01-1 / 9 S12 Fire Safety Risk Assessment H&SFS01 Risk ratings The following risk ratings are based on two factors: The overall fire risk rating for the site The risk rating for the individual recommendations /control

More information

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014 Type of Property Owner Address of Properties Responsible Person (s) consulted Multi- occupied housing referred to as the Byker Wall Ground floor and varying upper levels with open deck assess to all areas.

More information

FIRE RISK ASSESSMENT Self Assessment

FIRE RISK ASSESSMENT Self Assessment FIRE RISK ASSESSMENT Self Assessment Important! This fire risk assessment form is to be filled in by the responsible person within a business or organisation. As this is a free download for the use of

More information

Management Standard: Fire Safety

Management Standard: Fire Safety OHSS: H&S Management 201 Fire Safety Management : Fire Safety 1. Legal framework This standard is produced to comply with the following legislation in respect to fire safety: 1.1. Regulatory Reform (Fire

More information

Health and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014

Health and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014 Fire Safety Policy Originator name: Section / Dept: Implementation date: Clive Parkinson Health & Safety March 2014 Date of next review: March 2017 Related policies: Health and Safety Policy Policy history:

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Rodwell House

More information

FIRE RISK ASSESSMENT Waterstones High Street, Solihull, West Midlands, B91 3SW.

FIRE RISK ASSESSMENT Waterstones High Street, Solihull, West Midlands, B91 3SW. Waterstones 69-71 High Street, Solihull, West Midlands, B91 3SW. BAFE Certificate Number: 0040921 CONTENTS: BAFE SP205 Certificate of Compliance 3 Introduction 5 Risk Assessment Methodology 6 PAS 79 Fire

More information

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT Fire Risk Assessment Report - Initial Prepared by Your Company Name This report took 5 SECONDS to produce & a few MINUTES to collect the data on site! Download the app for FREE at www.pocketsurvey.com

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Hazeldene House

More information

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes Fire Assessment Location details Company Name Site address Site contact name Phone Guidance Notes looking at the workplace to identify potential A hazard is something that has the potential to cause harm;

More information

Millfield Schools Fire Risk Prevention Policy

Millfield Schools Fire Risk Prevention Policy Millfield Schools Fire Risk Prevention Policy This policy refers to the Senior School, Preparatory School, Pre-Preparatory School and EYFS 1. Introduction This policy sets out the approach that the school

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Science Block Hillcrest Rd, London W5 2JL 020 8997 2022 Bursar J Powell

More information

Fire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1

Fire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1 Billy Hanafin H & S and Operations Officer Version 1.0 October 2013 Page 1 1. General The Trust is a responsible employer that takes its Fire Safety duties seriously. For that reason, this policy has been

More information

Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome

Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome 1.0 Draft 07.03.2016 David Maine 1 st Draft for consultation/review 1.1 Approved 22.12.2016 David Maine 1

More information

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy Holme Grange School Whole School Policy Including EYFS Fire Safety Policy This document details the school s policy on fire safety in operation at Holme Grange School. The document is split into a number

More information

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Harpwood Care

More information

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing) FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford

More information

Fire Risk Assessment Safety Checklist

Fire Risk Assessment Safety Checklist Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory

More information

Fire Risk Management Policy. UK September 2017

Fire Risk Management Policy. UK September 2017 UK September 2017 5 & 7 Diamond Court, Opal Drive, Eastlake Park, Fox Milne, Milton Keynes MK15 0DU, T: 01908 396250, F: 01908 396251, www.cognitaschools.co.uk Registered in England Cognita Limited No

More information

Fire Safety Policy 2018/19

Fire Safety Policy 2018/19 Fire Safety Policy 2018/19 Reviewed: March 2016 Next Review: March 2019 1. Policy Statement The School is committed to ensuring, so far as is reasonably practicable, the health, safety and welfare of all

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Clockhouse Nursery and Early ears Hillcrest Rd, London W5 2JL 020 8997

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

NOTTINGHAM CITY HOMES

NOTTINGHAM CITY HOMES APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes

More information

Fire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD

Fire Safety Policy. Somerville College Woodstock Road Oxford OX2 6HD Fire Safety Policy Somerville College Woodstock Road Oxford OX2 6HD Table of Contents 1.0 Introduction... 2 2.0 Legislative Requirements... 2 3.0 Fire Risk Assessment... 3 4.0 Management of Fire Safety...

More information

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in

More information

Fire Safety Protocol

Fire Safety Protocol CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents

More information

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points. Record of significant findings Risk assessment for : Assessment undertaken by : Horsefair House Nigel Billing CMIOSH Date: 28/3/17 Overview of Premises: 2 buildings on 3 stories in an L shaped configuration,

More information

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019 Fire Safety Policy (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January 2018 Next Review: January 2019 Person Responsible: School Business Manager 1 P age 1. INTRODUCTION a) King Fahad

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

FIRE SAFETY AND PREVENTION POLICY

FIRE SAFETY AND PREVENTION POLICY Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford

More information

Wellsprings Primary School. Fire Emergency Evacuation Plan

Wellsprings Primary School. Fire Emergency Evacuation Plan Wellsprings Primary School Fire Emergency Evacuation Plan This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the plan is: To ensure the safety

More information

H&S Forum. Fire Safety Policy Glascote Academy

H&S Forum. Fire Safety Policy Glascote Academy Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote

More information

Glenmere Primary School Fire Safety Policy FIRE SAFETY POLICY. Revised on April Sam Conlon. Created by S.Conlon 1

Glenmere Primary School Fire Safety Policy FIRE SAFETY POLICY. Revised on April Sam Conlon. Created by S.Conlon 1 FIRE SAFETY POLICY Revised on April 2018 By Sam Conlon Created by S.Conlon 1 Legal framework Contents Responsibilities of local governing body Responsibilities of Headteacher Responsibilities of premises

More information

Fire Policy and Procedures. Cañada Blanch Spanish School

Fire Policy and Procedures. Cañada Blanch Spanish School Fire Policy and Procedures Cañada Blanch Spanish School SUMMARY 1. Introduction (p. 3) 2. Roles and responsibilities (p. 3) -- Headteacher -- Fire Team -- All staff -- Contractors 3. Fire procedures (p.

More information

WILTSHIRE POLICE FORCE PROCEDURE. Fire Safety Management

WILTSHIRE POLICE FORCE PROCEDURE. Fire Safety Management WILTSHIRE POLICE FORCE PROCEDURE Fire Safety Management Date of Publication: May 2018 Version: 8.0 Next Review Date: May 2019 TABLE OF CONTENTS PROCEDURE OVERVIEW... 3 GLOSSARY OF TERMS... 3 RELATED POLICIES,

More information

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring. Record of significant findings Risk assessment for : Assessment undertaken by : 71a The Close Nigel Billing CMIOSH Date: 21/3/17 Overview of Premises: 1970s building housing main school reception and support

More information

St Edward s Oxford FIRE SAFETY POLICY

St Edward s Oxford FIRE SAFETY POLICY FIRE SAFETY POLICY 1 CONTENTS Section Page No.(s) 1. Policy Statement 3-5 2. Organisation and Responsibilities 6 3. Responsibilities of Responsible Person 7-8 4. Responsibilities of Senior Management 9

More information

Fire Safety Policy. Investing in success. Dukes Centre Dukes Avenue Kingston KT2 5QY 1. Policy

Fire Safety Policy. Investing in success. Dukes Centre Dukes Avenue Kingston KT2 5QY   1. Policy Fire Safety Policy 1. Policy It is the policy of Malden Oaks to minimise the risks to students, staff and others which may arise from fire. This is achieved by ensuring precautions are taken to avoid fires

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:

More information

LYHA Fire Safety Policy

LYHA Fire Safety Policy LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with

More information

FIRE SAFETY LOG BOOK

FIRE SAFETY LOG BOOK FIRE SAFETY LOG BOOK Regulatory Reform (Fire Safety) Order 2005 If you own, manage or operate a business, you will need to comply with fire safety law. The main law is the Regulatory Reform (Fire Safety)

More information

NOT PROTECTIVELY MARKED. Fire Legislation

NOT PROTECTIVELY MARKED. Fire Legislation Fire Legislation Contents Policy Statement... 2 Legislation... 2 Fire Extinguisher Usage... 2 Fire Evacuation Procedure... 3... 4 Line Managers/Supervisors... 4 Business Support Officer... 5 Driver/Handy

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY Last Review Date 30 June 2015 Policy endorsed by Policy is maintained by ISI reference Trustees Co-Principals/Directors A9, B6, B9 Next review date 30 August

More information

ISLE OF WIGHT FIRE & RESCUE SERVICE

ISLE OF WIGHT FIRE & RESCUE SERVICE ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS

More information

Arbour House. Fire Policy and Procedures

Arbour House. Fire Policy and Procedures Arbour House Fire Policy and Procedures Policy Review Date: May 2017 Introduction Arbour House School endeavours to ensure that risks from fire are identified and that arrangements are in place to control

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:

More information

Fire Safety Management Audit Specification August 2017

Fire Safety Management Audit Specification August 2017 Fire Safety Management Audit Specification August 2017 Membership Training Qualifications Audit and Consultancy Policy and Opinion Awards Contents Page 1 Introduction to the Fire Safety Management Audit

More information

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma Reference Number: This risk assessment and ALL associated documents must be retained. Date : Sept 17 The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma This Fire Risk Assessment

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Premises Description Address Area Post Code Tel no. Num of Employees Normal Occupancy Max Allowed Use of Premises Building Length Building Breadth Area 0.00 M² Floors Storeys Below

More information

FIRE SAFETY POLICY. Health and Safety. Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018)

FIRE SAFETY POLICY. Health and Safety. Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018) FIRE SAFETY POLICY Owner: Health and Safety Reviewed by: Health & Safety Committee (2 May 2018) Approved by: Council (25 June 2018) Review due date: May 2019 Update history: Approved by Council 8 March

More information

Fire Safety Policy Date: 0

Fire Safety Policy Date: 0 Fire Safety Policy Date: 0 Policy Preparation & Introduction This document format has been produced by Firesafe Solutions (UK) Ltd to aid managers, tenants and others responsible for fire safety in their

More information

Charlotte Building, 17 Gresse Street, London W1T 1QL

Charlotte Building, 17 Gresse Street, London W1T 1QL Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of

More information

FIRE SAFETY POLICY. This policy refers to both Wellington Senior School and Wellington Prep School

FIRE SAFETY POLICY. This policy refers to both Wellington Senior School and Wellington Prep School FIRE SAFETY POLICY This policy refers to both Wellington Senior School and Wellington Prep School Headmaster Henry Price Author Bursar Date Reviewed 27.06.2017 for implementation on 25.07.2017 Date of

More information

Fire Procedures. April 2016

Fire Procedures. April 2016 Estates Department Fire Procedures April 2016 Author Robert Hardman Estates Manager Last Policy Review Date 1/04/16 Next policy Review Date 1/04/17 Reviewed by The Laurus Trust School Fire Procedures Contents

More information

FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY

FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY Under the terms of the Regulatory Reform (Fire Safety) Order 2005, and subsequent regulations, Seaford College must ensure the safety from fire of all staff,

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

FIRE PROCEDURES 1. APPOINTMENTS

FIRE PROCEDURES 1. APPOINTMENTS 12b FIRE PROCEDURES 1. APPOINTMENTS Responsible Person In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO), the School s Head, Mrs C Cameron is appointed as the Responsible Person for

More information

GDST Fire Safety Strategy March 2016

GDST Fire Safety Strategy March 2016 GDST Fire Safety Strategy March 2016 GDST Fire Safety Strategy v1.0 March 2016 Page 1 of 17 Contents 1. Introduction 3 2. Compliance Statement 3 3. Fire Safety Strategy Aims and Objectives 3 Strategic

More information

A basic guide to... Fire Safety for Scout Premises

A basic guide to... Fire Safety for Scout Premises A basic guide to... Fire Safety for Scout Premises A basic guide to Fire Safety for Scout Premises This Guide has been designed and produced by Chubb Fire to assist persons responsible for fire safety

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

Fire risk management plan. MH/05/Revised/06/17

Fire risk management plan. MH/05/Revised/06/17 Fire risk management plan MH/05/Revised/06/17 1 1. Scope This policy applies to fire safety arrangements in all workplaces, common areas of residential premises and any other premises managed and/or owned

More information

Fire Risk Assessment 2016

Fire Risk Assessment 2016 Fire Risk Assessment 2016 Elleray Campus Windermere School Author Paul Brownless Date 07 December 2016 Reviewed Reviewer 20 November 2017 Richard Hennah Reference FRA_EC_07122016 1 AUTHOR CLIENT Paul Brownless

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Local Rules: Fire Safety

Local Rules: Fire Safety 1. Potential Effects of a Fire A small fire is most likely to cause damage to equipment and furniture, with the potential to cause additional smoke damage to the room of origin. A large and protracted

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Fire Risk Assessment Case Study

Fire Risk Assessment Case Study Appendix B Fire Risk Assessment Case Study The purpose of this case study is to illustrate one practical approach to conducting a fire risk assessment. The checklist and proformas used in this case study

More information

Fire Risk Assessment 69-77A Black Lion Lane South Hammersmith, Ravenscourt Park W6 9BG 25/07/2017

Fire Risk Assessment 69-77A Black Lion Lane South Hammersmith, Ravenscourt Park W6 9BG 25/07/2017 Fire Risk Assessment 69-77A Black Lion Lane South Hammersmith, Ravenscourt Park W6 9BG 25/07/2017 Page 1 of 23 Section 1: Details of Premises all questions on this page are compulsory LBHF Ward UPRN Name

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY

HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY INTRODUCTION Cwmni CYNNAL recognises its duty of care to employees and all reasonable steps will be taken to secure the health and safety of employees.

More information

Fire Safety. A TUC guide for trade union activists

Fire Safety. A TUC guide for trade union activists Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement

More information

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY Under the terms of the Box Hill School must ensure the safety from fire of all staff, pupils, contractors and visitors. In order to do this the school

More information