IEC Type Test Report Report No. EU1515-H-00.3 Type PVI-LP Polymer Arrester 10,000 A Line Discharge Class 2

Size: px
Start display at page:

Download "IEC Type Test Report Report No. EU1515-H-00.3 Type PVI-LP Polymer Arrester 10,000 A Line Discharge Class 2"

Transcription

1 IEC Type Test Report Report No. EU1515-H-00.3 Type PVI-LP Polymer Arrester 10,000 A Line Discharge Class 2 This report records the results of this type test made on 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. Type tests performed on 10 ka Class 2 arresters demonstrate full compliance with the relevant clauses of the referenced standard and apply to all Hubbell 10 ka Class 2 arresters of this design manufactured and assembled at the following ISO 9001:2008 certified Hubbell locations: Hubbell Power Systems Hubbell Electric (Wuhu) Company, Ltd Richland Avenue, East Exports Processing Zone, No 68 Aiken, South Carolina North Jiuhua Road, Wuhu City Anhui Province, PR China The above locations manufacture, assemble, and test utilizing manufacturing, quality, and calibration procedures developed from Hubbell Engineering Department Specifications. Engineering Department Specifications are controlled by Arrester Business Unit design engineering in the USA. D. W. Lenk Principal Engineer Date 8/27/2012 Separate reports provide details of each test, according to the following table: Report No. Description Clause Issue date EU1515-H-01.1 Insulation Withstand Test on Arrester Housing 8.2 8/27/2012 EU1515-H-02.1 Residual Voltage 8.3 8/27/2012 EU1515-H-03.1 Long Duration Current Withstand 8.4 8/27/2012 EU1515-H-04.1 Accelerated Aging Procedure /27/2012 EU1515-H-05.1 Heat Dissipation Behavior of Test Section /27/2012 EU1515-H-06.1 Switching Surge Operating Duty /27/2012 EU1515-H-07.1 Partial Discharge 8.8 8/27/2012 EU1515-H-08.1 Power Frequency Voltage Versus Time Annex D 8/27/2012 EU1515-H-09.1 Short Circuit Annex N 8/27/2012 EU1515-H-10.2 Bending Moment /30/2012 EU1515-H-11.1 Moisture Ingress /27/2012 EU1515-H Hour Weather Aging Test /27/2012 EU1515-H Hour Salt Fog /27/2012

2 IEC Type Test Report Report No. EU1515-H-01.1 Polymer Arrester 10,000 A Line Discharge Class 2 INSULATION WITHSTAND TESTS ON THE ARRESTER HOUSING IEC CLAUSE 8.2 This report records the results of this type test made on IEC 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005, and Amendment 2 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. Dennis W. Lenk Principal Engineer Date: 8/27/2012

3 IEC Type Test Report INSULATION WITHSTAND TESTS ON THE ARRESTER HOUSING IEC CLAUSE 8.2 Table 1 summarizes polymer housing minimum leakage and strike distances for each arrester rating, and 60 Hz and impulse withstand requirements for each housing size. In all cases, the actual withstand values of each arrester housing exceed the minimum values specified in the Standard. Table 1. Insulation Withstand Voltage Requirements of IEC 10 ka Class 2 Arresters. Rating (kv rms) COV (kv rms) Minimum Leakage Distance (mm) Minimum Strike Distance (mm) BIL Withstand Required (kvc) Power Frequency 1 Minute Wet Withstand Required (kvc, peak) EU1515-H

4 IEC Type Test Report Report No. EU1515-H-02.1 Polymer Arrester 10,000 A Line Discharge Class 2 Residual Voltage IEC Clause 8.3 This report records the results of type tests made on IEC 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. D. W. Lenk Principal Engineer Date: 8/27/2012

5 TITLE: Residual-voltage characteristic IEC TYPE TEST REPORT Residual Voltage IEC Clause ka Class 2 Surge Arrester TEST OBJECTIVE: These measurements are used to obtain the maximum discharge voltages at various current magnitudes and waveshapes. TEST PROCEDURE: Discharge voltage tests were performed on three single disc test samples. Tests were conducted in accordance with clause 8.3 of IEC Standard. Test samples were subjected to 8/20 current waves with magnitudes ranging from 1.5 ka through 20 ka. In addition, Front-of-wave and switching surge discharge voltage tests were performed. TEST SAMPLES: Arresters are assembled from discs accumulated within 10 ka IR ranges as specified for each arrester rating. To verify catalog maximum IR levels were not exceeded, a discharge voltage ratio was established at each current level based on the test sections 10 ka IR (Table 1). That ratio was multiplied by the maximum allowed 10 ka IR accumulation specified for each rating. As summarized on Table 2, the IR calculated based on the prorated test sections do not exceed the maximum declared catalog levels for the current levels specified in clause 7.3. TEST RESULTS: Figures 1-12 contain oscillograms for test section 1 at each current and wave shape. Figure 1 125A, 9.950, 56/99 Waveshape Oscillogram not available Figure 2 500A, , 56/99 Waveshape EU1515-H

6 Figure 3 1 ka, kV, 56/99 Waveshape Figure ka, kv, 8.4/18.4 Waveshape Figure 5 3 ka, kv, 8.4/18.4 Waveshape EU1515-H

7 Figure 6 5 ka, kv, 8.4/18.4 Waveshape Figure 7 10 ka, kv, 8.7/19.0 Waveshape Figure 8 20 ka, kv, 8.2/18.7 Waveshape EU1515-H

8 Figure 9 40 ka, kv, 8.5/19.4 Waveshape Figure ka FOW, to voltage crest Figure ka FOW, microseconds to voltage crest EU1515-H

9 Figure ka FOW, microseconds to voltage crest Impulse Current (A) Wave Shape Table 1 Sample Discharge Voltage Data Summary Discharge Voltage (kv) Discharge Voltage Ratio Sample 1 Sample 2 Sample 3 Sample 1 Sample 2 Sample / / / ,500 8/ ,000 8/ ,000 8/ ,000 8/ ,000 8/ ,000 8/ ,000 ½ ,000 2/ Time to Crest Voltage (µs) 10,000 8/ ,000 ½ ,000 2/ EU1515-H

10 Table 2 IEC 10 ka Class 2 Arrester Discharge Voltage Summary IR Multipliers Impulse Wave 60/100 60/100 8/20 8/20 8/20 0.5usec MCOV Rating I Magnitude (A) Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR Specimen Measured IR Catalog Maximum IR EU1515-H

11 IEC Type Test Report Report No. EU1515-H-03.1 Polymer Arrester 10,000 A Line Discharge Class 2 LONG DURATION CURRENT IMPULSE WITHSTAND TESTS IEC CLAUSE 8.4 This report records the results of this type test made on 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. D. W. Lenk Principal Engineer Date: 8/27/2012

12 IEC Type Test Report LONG DURATION CURRENT IMPULSE WITHSTAND TESTS IEC CLAUSE 7.4 Sample Preparation Long duration current impulse withstand tests were performed on three test samples. MOV discs for each test sample were selected to represent the lowest acceptable reference voltage level. Test Parameters and Procedure Three samples were subjected to line discharge tests in accordance with line discharge Class 2 in Table 5 of Clause 8.4. All generator parameters conformed to Class 2 line discharge requirements. Prior to the transmission line discharge tests, 10 ka, 8/20 µs discharge voltage and reference voltage of the test samples were measured. Initial measurements and associated parameters for the three samples are given in Table 1. Table 1. Parameters for Line Discharge Tests on 10 ka Line Discharge Class 2 Arrester Samples. Test Parameters Sample 1 Sample 2 Sample 3 Initial Residual Voltage 10 ka, 8/20 µs Reference Current (ma) I ref Reference Voltage (kv c ) V ref COV ( kv rms) U c Rating (kv rms) U r Arrester Classification (ka) Line Discharge Class Virtual Duration of Peak (µs, 90-90%) Max. Generator Impedance (Ω) Z g Min. Generator Charging Voltage (kv) U L The transmission line discharge tests defined by IEC Standard , 1998, consisted of subjecting each test sample with eighteen rectangular waveshape discharges. The eighteen discharges were of six groups with three consecutive operations at a time interval of 50 to 60 seconds between the consecutive operations. The samples were allowed to cool to ambient temperature between groups of discharges. Test Results EU1515-H

13 Figure 1 shows the surge impedance of the transmission line generator and confirms the virtual duration of the generator. The samples were exposed to still air at ambient temperature of 21 C during the test. A summary of the test results is shown in Table 2. Figure 1. Z g = 11,090 V / A = Ω, Virtual Peak Duration = 2146 µs. Table 2. Transmission Line Discharge Tests Impulse Sample 1 Sample 2 Sample 3 I (A) V (kv) E (kj) I (A) V (kv) E (kj) I (A) V (kv) E (kj) Figure 2 shows oscillograms of the first and eighteenth transmission line discharges of sample 1. EU1515-H

14 Sample 1, Shot 1, Discharge Current = 588A Discharge Voltage = kv, Energy under V-I Curve = kj Sample 1, Shot 18, Discharge Current = 556A Discharge Voltage = kv, Energy Under V-I Curve = kj Figure 2. Transmission line discharges of sample 1. EU1515-H

15 Figure 3 shows oscillograms of the first and eighteenth transmission line discharges of sample 2. Sample 1, Shot 1, Discharge Current 588A Discharge Voltage = kv, Energy under V-I Curve = kj Sample 2, Shot 18, Discharge Current = 556A Discharge Voltage = kv, Energy Under V-I Curve = kj Figure 3. Transmission line discharges of sample 2. EU1515-H

16 Figure 4 shows oscillograms of the first and eighteenth transmission line discharges of sample 3. Sample 3, Shot 1, Discharge Current = 588A Discharge Voltage = kv, Energy under V-I Curve = kj Sample 3, Shot 18, Discharge Current = 560A Discharge Voltage = kv, Energy Under V-I Curve = kj Figure 4. Transmission line discharges of sample 3. EU1515-H

17 Subsequent to the completion of the transmission line discharges, 10 ka, 8/20 µs discharge voltage of the three test samples was measured. Results of the residual voltage measurements are summarized in Table 3. The maximum change of residual voltage of the three samples is less than the permissible change of 5 % defined by IEC Standard , Test Summary Table 3. Residual Voltage (10 ka, 8/20 µs) Measurements Before and After Long Duration Current Impulse Withstand Test. RESIDUAL VOLTAGE (kv) CHANGE SAMPLE Before After (%) The three test samples successfully passed the transmission line discharge tests per Section 8.4 of IEC Standard , For all three samples, the change of 10 ka, 8/20 µs residual voltage measured before and after the transmission line discharges is less than 1%, below the allowed 10%. Disassembly revealed no evidence of physical damage to the three test samples. Each of the three test samples has successfully fulfilled the long duration current impulse withstand requirements of IEC Class 2 arresters. EU1515-H

18 IEC Type Test Report Report No. EU1515-H-04.1 Polymer Arrester 10,000 A Line Discharge Class 2 ACCELERATED AGEING PROCEDURE IEC CLAUSE This report records the results of this type test made on 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. D. W. Lenk Principal Engineer Date: 8/27/2012

19 IEC Type Test Report ACCELERATED AGEING PROCEDURE IEC CLAUSE Tests were performed to measure the MOV disc aging characteristics. Measured watts loss values are used to develop an elevated voltage ratio K ct that is used in the operating duty test to simulate the performance of an arrester with service life equivalent to 1000 hours at 115 C. Sample Preparation Three arrester modules were prepared. The (3) modules consisted of the longest 50 mm diameter MOV disc, spring, end terminals, barrier film and fiberglass/epoxy wrap using standard module construction. Test Procedure Accelerated aging tests were performed per Section of IEC Standard , Test samples were energized by a voltage equal to the corrected maximum continuous operating voltage U ct of the three test samples for 1000 hours at 115 C ± 2 C. Individual watts loss and temperature were measured at U ct at the start (2 hours) and at the end (1000 hours) of the aging tests after energization. The initial watts loss is designated as P 1ct while the final watts loss is P 2ct. Table 1 summarizes the results of the 1000 hour accelerated aging tests. The watts loss values were measured at 115 C ± 2 C. Watts Loss at 2 Table 1. Accelerated Aging Tests. Watts Loss at 1000 Watts Loss at 2 Watts Loss at 1000 Elevation Factors Sample Number P 1c (w) P 2c (w) P 1r (w) P 2r (w) K c K r Test Summary For each sample, the final watts loss value at U ct is less than the initial watts loss value measured. Therefore, no elevation factors were required to apply to COV (U c ) or Rating (U r ) during the operating duty tests. EU1515-H

20 IEC Type Test Report Report No. EU1515-H-05.1 Polymer Arrester 10,000 A Line Discharge Class 2 HEAT DISSIPATION BEHAVIOUR OF TEST SAMPLES IEC CLAUSE This report records the results of this type test made on IEC 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. Dennis. W. Lenk Principal Engineer Date: 8/27/2012

21 IEC Type Test Report HEAT DISSIPATION BEHAVIOUR OF IEC 10KA CLASS 2 12 KV RATED ARRESTER AND 12 KV RATED ARRESTER SECTION Introduction IEC CLAUSE Tests were performed in accordance with clause and Annex B of IEC Standard , The purpose of this test was to verify that the thermal cooling curve of the 12 kv rated arrester prorated section, when internally heated, cools slower than that of a similarly heated 72 kv rated arrester. To achieve the same cooling rate for both samples, external insulation is attached between the polymer housing sheds on the 12 kv arrester section. Sample Preparation The 72 kv rated arrester was assembled without external insulation. The 12 kv rated prorated arrester section was assembled with external insulation located between arrester housing sheds. Each sample was assembled with a thermocouple located in the middle of the arrester module, between mov discs. Test Procedure The test units were placed in still air at ambient temperature. Both arresters were heated using a 60 Hz source. The targeted final heating temperature was C with the test lab ambient temperature at 23+/-2 C. The duration of the applied voltage was 10 minutes. The magnitude of the applied voltage was adjusted so that each arrester was heated to the same final temperature at the completion of the heating test. Upon achieving the desired disc temperature, thermocouples were attached to a data logger and temperature was monitored continuously for 2 hours. Test Results Figure 1 displays the cooling curves for the 10 KA Class 2 72 kv rated arrester and the 12 kv rated arrester prorated section. Examination of the cooling curves for the 12 kv rated prorated arrester section and the 72 kv rated arrester confirms that the cooling rate for the externally insulated section is slower than that of the 12 kv rated arrester, and durability tests performed on the 12 kv rated arrester section will simulate durability and thermal conditions for the 12 kv rated arrester. EU1515-H

22 Figure 1 Comparison of Cooling Curves for Prorated Section Versus 57 kv MCOV Arrester Cooling Time- Minutes Prorated Section 57 kv MCOV Arrester EU1515-H

23 IEC Type Test Report Report No. EU1515-H-06.1 Polymer Arrester 10,000 A Line Discharge Class 2 SWITCHING SURGE OPERATING DUTY TEST IEC CLAUSE This report records the results of this type test made on 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. D. W. Lenk Principal Engineer Date: 8/27/2012

24 Sample Preparation IEC Type Test Report SWITCHING SURGE OPERATING DUTY TEST IEC CLAUSE Switching surge operating duty tests were performed on three prorated test sections prepared based on the thermal equivalency test results. Each section consisted of two (2) 50 mm diameter, 40mm long MOV discs. The MOV discs for each sample were selected to represent the lowest acceptable reference voltage level. Test Procedure Prior to the conditioning series, reference voltage of each section was measured at 7 ma reference current and room temperature. Initial 10 ka, 8/20 µs residual voltage of each section was also measured. Conditioning tests consisted of two test series. The first conditioning test series subjects each test section to (20) 10 ka, 8/20 µs lightning current impulses, divided into four groups of five impulses. The interval between impulses was between 50 and 60 seconds and the interval between groups was between 25 and 30 minutes. Test sections were energized at 60 Hz voltage of 1.2 U c during each group testing. The impulses were timed to occur 60 before the crest of the 60 Hz voltage with the same polarity of the impulse. The second conditioning test series consisted of subjecting each test section to (2) 100 ka 4/10 surges, with the section allowed to cool to ambient temperature between discharges. Tests were performed in still air at ambient temperature of 20 C. During the operating duty test, each section was subjected to two (2) long duration current discharges. Prior to the second discharge, each prorated section was placed in an oven and heated overnight to 60 ± 3 C. Within 100 milliseconds of the second long duration current impulse, rated voltage (U r ) was applied to each section for 10 seconds immediately followed by U c for 30 minutes. During the recovery period, power dissipation of each section was monitored to demonstrate thermal stability. After this test sequence, each section was allowed to cool to ambient temperature and then its 10 ka, 8/20 µs discharge voltage was measured. EU1515-H

25 Test Results Initial measurements and parameters of the prorated sections are shown in Table 1. Table 1. Initial Measurements and Parameters of Prorated Sections. Test Parameters Section 1 Section 2 Section 3 Initial Residual Voltage 10 ka, 8/20 µs Reference Current (ma) I ref Reference Voltage (kv peak) U ref Maximum COV (kv rms): U c Maximum Rating (kv rms): U r A summary of results of the three sections for the 20-shot conditioning test is shown in Table 2. The sections were exposed to still air at ambient temperature of 20 C during the test. Table Shot Conditioning Test. IMPULSE NUMBER SECTION 1 I (ka) SECTION 2 I (ka) SECTION 3 I (ka) Cool Cool Cool Subsequent to the completion of the 20 shot test, each section was subjected to two (2) 100 ka nominal 4/10 µs conditioning impulses. Table 3 shows test results of the first and EU1515-H

26 second 100 ka impulses for the three sections. Figure 1 shows oscillograms of the test for the three sections. Table ka, 4/10 µs Conditioning Test. IMPULSE SECTION 1 I (ka) SECTION 2 I (ka) SECTION 3 I (ka) Section 1, Shot 1, Discharge Current = ka Section 1, Shot 2, Discharge Current = ka EU1515-H

27 Section 2, Shot 1, Discharge Current = ka Section 2, Shot 2, Discharge Current = ka Section 3, Shot 1, Discharge Current = ka EU1515-H

28 Section 3, Shot 2, Discharge Current = ka Figure ka nominal 4/10 µs impulses. Prior to the switching surge portion of the operating duty test, the test sections were preheated to 60 deg C. Immediately after removal from the oven, the prorated sections were subjected to two long duration discharges spaced one minute apart. Table 4 summarizes the 2-shot discharge duty on the three test sections. Table 4 #1 #2 #3 Shot # Current Amps Volts kv Energ y kj Current Amps Volts kv Energ y kj Current Amps Volts kv Energy kj Table 5 summarizes the results of the 10 second rated portion of the operating duty test. Time (Second) Table Second Rated Voltage Test. Section 1 Section 2 Section 3 Rated Current Time Rated Current Time Rated Ur I (Second) Ur I (Second) Ur (kvc) (ma) (kvc) (ma) (kvc) Current I (ma) EU1515-H

29 Figure 2 shows a typical oscillogram of the long duration current discharged thru the prorated test sections during the switching surge operating duty portion of the ODC test. The time sweep on the upper long duration trace is.60 milliseconds per major division. The middle trace displays the 10 rated voltage portion of the test while the bottom trace integrates the energy absorbed during the 10 second test. Figure 2 Thermal stability defined by Section of the Standard was verified during the recovery period by continuous monitoring of power dissipation of the test sections. Results are summarized in Table 6. Typical recovery voltage and current oscillograms for each section are shown in Figure 3. The results indicated that all three sections demonstrated thermal stability. RECOVERY TIME (Min) Table 6. Power Dissipation in Thermal Models during Recovery. SECTION 1 SECTION 2 WATTS LOSS WATTS LOSS (W) (W) SECTION 3 WATTS LOSS (W) EU1515-H

30 Results of the residual voltages measured before and after the operating duty test are summarized in Table 7. The maximum change of the residual voltages of the three sections is less than the permissible value of 5 %. Table 6. Summary of Residual Voltage Measurements. SECTION RESIDUAL VOLTAGE (kv) Change Before After (%) Test Summary The three prorated sections successfully passed the switching surge operating duty test per Section of IEC Standard , Disassembly revealed no evidence of puncture, flashover or cracking of the non-linear metal oxide resistors in any of the three sections. All three sections demonstrated thermal stability. The change of residual voltage measured before and after the test is less than 1 %, below the allowed 10% limit. The three test sections have successfully fulfilled the operating duty test requirements for the 10 ka Class 2 arrester. EU1515-H

31 IEC Type Test Report Report No. EU1515-H-07.1 Polymer Arrester 10,000 A Line Discharge Class 2 PARTIAL DISCHARGE IEC CLAUSE 8.8 This report records the results of this type test made on 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard Surge Arresters- Part 4: Metal oxide surge arresters without gaps for ac systems Dennis W. Lenk Principal Engineer Date: 8/27/2012

32 TITLE: Internal Partial Discharge IEC Type Test Report PARTIAL DISCHARGE IEC CLAUSE 8.8 TEST OBJECTIVE: Measure internal partial discharge of longest 10 ka Class 2 polymer-housed arrester. TEST SAMPLES: Testing was performed on the largest electrical unit (72 kv rated). TEST PROCEDURE: Per the specified test procedure, the arrester was energized at rated voltage for 2-10 minutes and then the voltage was reduced to 1.05 times COV. At this voltage, the arrester partial discharge was measured TEST RESULTS: The 57 kv COV arrester was energized at 59.9 kvrms and had a measured partial discharge of 2 picocoulomb, below the allowed 10 picocoulomb limit. Background PD was 1-2 picocoulomb. CONCLUSION: The 72 kv rated arrester passed the specified partial discharge testing, validating the 10 ka Class 2 design meets the IEC partial discharge requirements. EU1515-H

33 IEC Type Test Report Report No. EU1515-H-08.1 Polymer Arrester 10,000 A Line Discharge Class 2 POWER FREQUENCY VOLTAGE VERSUS TIME CHARACTERISTIC IEC ANNEX D This report records the results of this type test made on 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. D. W. Lenk Principal Engineer Date: 8/27/2012

34 IEC Type Test Report POWER FREQUENCY VOLTAGE VERSUS TIME CHARACTERISTICS IEC ANNEX D The claimed power frequency voltage capability for the IEC 10 ka Class 2 design is summarized in Figure 1. The test procedure is listed below: 1. Preheat to 60 ± 3 C; 2. Apply two long duration discharge spaced 60 seconds apart; 3. Within 100 ms of the second discharge, apply the selected p. u. of voltage for a time greater than the abscissa value on Figure 1; 4. Apply the recovery voltage (U c ) for 30 minutes and monitor the power loss to confirm stability. The 10 ka Class 2 arrester data points met the claimed TOV requirements specified by the TOV withstand curve. IEC Class 2 Arrester Power Frequency Voltage versus Time Characteristic Per Unit times Uc Time- Seconds Data Points IEC Class 2 Power Frequency Curve Figure 1. Power frequency voltage versus time characteristic EU1515-H

35 IEC Type Test Report Report No. EU1515-H-09.1 Polymer Arrester 10,000 A Line Discharge Class 2 SHORT CIRCUIT TEST ANNEX N This report records the results of this type test made on 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. D. W. Lenk Principal Engineer Date: 8/27/2012

36 IEC Type Test Report SHORT CIRCUIT TESTS ANNEX N TITLE: Short Circuit Test For Polymer Housed Station Class Arrester: TEST OBJECTIVE: Short Circuit tests were performed on the 10 ka Class 2 polymerhoused Station Class arrester per ANNEX N of IEC standard. TEST SAMPLES: Tests were performed on fusewire shorted and overvoltage failed arresters as defined in Table N.2 of the referenced standard. Pressure relief tests were performed on the longest mechanical section, as required in Clause N of the standard. TEST PROCEDURE: As required, two test samples for the high current test were assembled with a fuse wire oriented axially between the mov disc stack and the fiberglass-epoxy wrap. These samples were subjected to the full offset current test. In addition, six samples represented standard production arresters. These samples were failed using the specified 2-source failure mode procedure. All tests were performed at full voltage. Therefore, the prospective fault current, as measured during the bolted fault test on the generator, is the claimable pressure relief current capability of the design. It should be noted that the IEEE test is similar to that defined in Annex N of new IEC standard, except reduced level high current testing was performed only at 20 ka, instead of 25 and 12kA as required in the IEC standard. Also note that the IEEE testing is performed on (8) total arresters versus only (4) per IEC. TEST RESULTS: The following table summarizes the results these tests which validated the claimed maximum 40 ka rms symmetrical, 12 cycle fault current withstand capability of this design, with an applied ratio of 1.55 between total asymmetrical to symmetrical rms currents. This corresponds to a 2.6 ratio, in the first half loop of fault current, between the crest asymmetrical to rms symmetrical current, i.e., full offset. In addition to testing at the claimed maximum capability, tests were also performed, using the 2-source procedure, at half the claimed capability and at 600 amps as specified in Table 14 of the standard. Calibration Test 41.0 ka rms Symmetrical 107 ka peak Asymmetrical EU1515-H

37 Sample # Failure Mode Minimum Test Duration-seconds Condition of Module/Polymer Housing After Test 1 Fuse Wire.21 Module Intact/Housing Separated 2 Fuse Wire.21 Module Intact/Housing Separated 3 2-Source.21 Module Intact/Hsg Torn but in Place 4 2-Source.21 Module Intact/Hsg Torn but in Place Calibration Test 19.9 ka rms Symmetrical No Asymmetrical Requirement Sample # Failure Mode Minimum Test Duration-seconds Condition of Module/Polymer Housing After Test 5 2-Source.2 Module Intact/Hsg Torn but in Place 6 2-Source.2 Module Intact/Hsg Torn but in Place Calibration Test 600 A rms Symmetrical No Asymmetrical Requirement Sample # Failure Mode Minimum Test Duration-seconds Condition of Module/Polymer Housing After Test 7 2-Source 1.0 Module Intact/Hsg Torn but in Place 8 2-Source 1.0 Module Intact/Hsg Torn but in Place CONCLUSION: The eight test arresters assembled with the longest mechanical unit met the test evaluation criteria as specified in Clause N In all tests, the arrester module remained intact after the completion of each test. The flexible polymer housing wall section split, as intended, on all samples to allow venting of internal arcing gases to the outside of the arrester. In all cases, flames associated with the fault current test extinguished immediately after completion of the test, well within the allowed 2 minute duration. These tests have demonstrated the capability of the IEC 10 ka Class 2 arrester design to successfully discharge a maximum claimable 40 ka rms symmetrical fault current. EU1515-H

38 IEC Type Test Report Report No. EU1515-H-10.2 PVI-LP Base Mounted Polymer Arrester 10,000 A Line Discharge Class 2 Bending Moment This report records the results of type tests made on 10 ka Line Discharge Class 2 Type PVI-LP arresters, rated up to 72 kv. Tests were performed in accordance with procedures of IEC Standard , Ed. 2.2, , Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. Dennis Lenk Principal Engineer Chris Kulig Product Engineer Date: 11/30/2012

39 IEC TYPE TEST REPORT Bending Moment TESTS PERFORMED: The bending moment test was performed on three test samples as described in Clause of IEC , for polymer-housed arresters without enclosed gas volume. Prior to the mechanical testing, the test samples were subjected to electrical tests to establish initial watts loss, partial discharge, and residual voltage values. Tests were performed per Attachment A, Chart M6 of the standard. Per Section a), after electrical testing, each of the three test samples was subjected to 1000 cycles of bending moment load. Each cycle consisted of loading the samples from zero to the arrester s specified long-term load (SLL), followed by loading to the SLL in the opposite direction, then returning to zero load. This procedure was repeated 1000 times on each arrester at an approximate frequency of 3 Hz. The maximum deflection (for each sample during the test) and the un-loaded residual deflection (at the completion of the test) were recorded. Per the M6 Chart, after the three samples completed the 1000 cycle test, two of the samples were subjected per Section a) to the specified short-term load (SSL) bending moment test. Each of these two test units was securely mounted to the horizontal base of the test equipment and lateral (horizontal) loading was applied to the free end of the unit, in a direction perpendicular to the axis of the unit, at a rate necessary to reach the bending moment corresponding to the specified short-term load (SSL) in approximately 50 s. The load was then maintained at this level for about 90 s. Deflection was measured prior to release of the load. After release of load, the test sample was inspected to verify that no mechanical damage had occurred, and the load-deflection curve was examined to verify that there was no discontinuity which might indicate mechanical damage. As with the 1000 cycle test, the unloaded residual deflection was measured on each sample. The third sample from the 1000 cycle test was subjected to mechanical/thermal preconditioning per Section This test procedure loads the test sample to its specified long-term load (SLL) while the arrester is being thermally cycled from -40 to +60 degree C. The final stage of the Bending Moment test (section ) consisted of submersing the three test samples under boiling salt water for 42 hours. At the conclusion of the boiling water test, electrical tests were repeated on each sample (per section ) to verify that any changes were within allowed limits, and a visual inspection was made to verify that no mechanical damage had occurred. TEST RESULTS: Per Clause of IEC Ed Standard, preliminary electrical tests were performed on the three PVI-LP 24.4 kv Uc arrester samples. Table 1 summarizes the results of these preliminary electrical tests. EU1515-H

40 Table 1 Test Parameter Sample #1 Results Sample #2 Results Sample #3 Results Initial Watts Loss at Uc Residual Voltage at 10 ka kvc Partial Discharge at 1.05*Uc- pc <2 <2 <2 Next, per Clause a), each test sample was subjected to the 1000 cycles of bending moment test. Each cycle consists of loading the arrester from zero to its specified long-term load (SLL) in one direction, followed by loading to SSL in the opposite direction, then returning to zero load. The tested SLL load applied to each test sample was 180 Nt-M (1,600 in-lb). Figure #1 plots the deflection versus time characteristic curve for the required 1000 test cycles on sample #1. This plot is typical of those recorded on the samples # 1 and 3. There was no recordable residual deflection on the three test samples after release of the top end applied load. Figure 1 Per step 2.1 of Clause a), test samples # 1 and 2 were rigidly base mounted in a cantilever fixture and loaded within 30 to 90 seconds to the arresters claimed specified 340 Nt-M (3010 in-lb) short-term load (SSL) and maintained at this moment load for 60 to 90 seconds, after which the applied load was slowly removed. Figure #2 shows the test sample s top end deflection as plotted against time for test sample #2, typical of that measured on sample #1. The maximum recorded top end deflection under load was.073 inches while the recorded residual deflection was.05 inches. Figure 2 EU1515-H

41 Figure 3 shows moment applied to the top end of arrester #1 during the SSL loading cycle. Figure 3 EU1515-H

42 Per step 2.2 of Clause a), test sample #3 was subjected to thermo-mechanical preconditioning as specified in Clause During this test, the test sample is placed inside a thermal cycling oven which loads the top end of the sample to its claimed 180 Nt-M SLL. Figure 4 shows the sample s load and temperature cycle. At the completion of the specified mechanical loading, samples 1, 2, and 3 were placed into boiling NaCl water for 42 hours, as specified in Clause After 42 hours exposure, the water bath temperature was reduced to 50 deg C. After stabilizing in 50 deg C water bath, the test samples were dried off and 60 Hz electrical tests were repeated per Clause Table 2 Test Parameter Sample #1 Sample #2 Sample #3 Final Watts Loss at Uc Watts Loss % Increase Final PD at 1.05*Uc-pC EU1515-H

43 Figure 4 As specified in Clause , to further confirm the electrical integrity, each test sample was subjected to the following test sequence Final Test Steps Test Description Test Sample #1 Test Sample #1 Test Sample #1 1 7 ma Uref kvc /20 10 ka IR-kVc /20 10 ka IR-kVc ma Uref kvc Figures 4 thru 9 show oscillograms of the 10 ka residual measured during steps 2 and 3 for each test sample. Figure 4 Sample 1 Residual Voltage Shot 1 EU1515-H

44 Figure 5 Sample 1 Residual Voltage Shot 2 Figure 6 Sample 2 Residual Voltage Shot 1 EU1515-H

45 Figure 7 Sample 2 Residual Voltage Shot 2 Figure 8 Sample 3 Residual Voltage Shot 1 EU1515-H

46 Figure 9 Sample 3 Residual Voltage Shot 2 EU1515-H

47 CONCLUSION: Three Type PVI-LP 24.4 kv Uc arresters were subjected to bending moment tests as defined in Clause of IEC Ed Standard. Specified short-term load (SSL) testing was successfully completed at 340 Nt-M, while specified long-term load (SLL) testing was successfully completed at 180 Nt-M. 60 HZ electrical tests, performed on each arrester prior to and after the mechanical and moisture ingress tests, confirmed arrester PD levels below the allowed 10 pc and watts loss was <1%, well below the allowed 20% change. 10 ka residual voltage tests also confirmed the electrical integrity of the three test arresters. In summary, the three 10 ka Class 2 type PVI-LP test arresters successfully passed the bending moment test at the designated SLL and SSL levels. Attachment A EU1515-H

48 EU1515-H

49 IEC Type Test Report Report No. EU1515-H-11.1 Base Mounted Polymer Arrester 10,000 A Line Discharge Class 2 MOISTURE INGRESS This report records the results of this type test made on IEC 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. Dennis. W. Lenk Principal Engineer Date: 8/27/2012

50 IEC Type Test Report MOISTURE INGRESS TEST Introduction IEC CLAUSE Tests were performed in accordance with clause of IEC Standard The purpose of this test was to verify the seal integrity of the arrester polymer housing after being subjected to a terminal torque and thermomechanical test, followed by the boiling water immersion test. Sample Preparation A 19.5 kv MCOV Class 2 arrester was assembled for this test. Test Procedure The test arrester was subjected to PD, watts loss, and discharge voltage tests prior to the bending moment and boiling water immersion test. The mechanical portion of the test consisted of first applying a 40 ft-lb torque to the arrester end terminals for 30 second duration. The test arrester was then placed inside a thermal cycling oven and mechanically loaded to its 1,600 in-lb continuous cantilever rating. The load application and test temperature is shown on the attached figure. After completion of the mechanically loading portion of the test procedure, the water immersion portion of the bending moment test was performed per para and EU1515-H

51 consists of placing the mechanically stressed arrester into a boiling salt water bath for 42 hours, after which the same is cooled to room temperature and electrical tests are repeated. Test Results Subsequent to the bending moment test, the test arrester was subjected to 42 hours immersion in the specified salt water bath. After removal from the bath, the arrester was electrically tested. The following table shows the results of the final electrical testing, compared with initial measurements. Sample No. Initial Uc Final Uc Initial 1.05 times Uc (pc) Final 1.05 times Uc (pc Initial 10 ka Residual Voltage kvc Final 10 ka Residual Voltage kvc <1 < Test Conclusions Visual inspection confirmed that there was no damage to the arrester as a result of the 1,600 in-lb thermomechanical conditioning, followed by the water immersion test. Electrical tests performed before and after testing also confirmed the electrical integrity of the test arrester. The 15% watts loss increase was below the allowed 20% limit. Partial discharge was unchanged at less than 1 pc, below the allowed 10 pc limit. The measured 10 ka residual voltage was almost unchanged, below the allowed 5% limit. Therefore, the IEC Class 2 base mounted arrester design successfully passed the moisture ingress test, as defined in IEC standard. EU1515-H

52 IEC Type Test Report Report No. EU1515-H-12.1 Base Mounted Polymer Arrester 10,000 A Line Discharge Class HOUR WEATHER AGING TEST This report records the results of this type test made on IEC 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2001 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. Dennis. W. Lenk Principal Engineer Date: 8/27/2012

53 IEC Type Test Report 5000 HOUR WEATHER AGING TEST Introduction IEC CLAUSE Tests were performed in accordance with clause of IEC Standard , The purpose of this test was to verify the electrical integrity of the arrester polymer housing after being subjected to 5000 hours in a weathering chamber. Sample Preparation A 29 kv MCOV IEC base mounted Class 2 arrester was assembled for this test. Test Procedure The 5000 hour weathering test was performed per IEC test procedure with the arrester energized at 30.6 kv rms over the entire 24 hour test cycle. Salt fog salinity was 7 kg per cubic meter. Test Results The test arrester successfully withstood the 5000 hour aging test with no evidence of surface tracking, erosion, or puncturing. In addition, electrical reference voltage changed from 57.0 to kvc, well within the allowed 5% variation. Finally, partial discharge measured less than 3 picofarad, well below the allowed 10 pc limit. Test Conclusions The IEC Class 2 base mounted arrester design successfully passed the 5000 hour weathering test, as defined in IEC standard. EU1515-H

54 IEC Type Test Report Report No. EU Base Mounted Polymer Arrester 10,000 A Line Discharge Class HOUR SALT FOG TEST This report records the results of this type test made on IEC 10 ka Class 2 arresters rated 3 thru 72 kv in accordance with IEC Standard , 2005 Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. Dennis. W. Lenk Principal Engineer Date: 8/27/2012

55 IEC Type Test Report 1000 HOUR SALT FOG TEST Introduction IEC CLAUSE Tests were performed in accordance with clause of IEC Standard , The purpose of this test was to verify the electrical integrity of the arrester polymer housing after being subjected to 1000 hours in a salt fog environment. Sample Preparation A 24.4 kv MCOV IEC Class 2 arrester was assembled for this test. Test Procedure The 1000 hour weathering test was performed per clause of IEC Salt fog salinity was 10 kg per cubic meter. Test Results The test arrester successfully withstood the 1000 hour salt fog exposure test with no evidence of surface tracking, erosion, or puncturing. The following table summarizes the results of electrical tests performed on the arrester before and after the salt fog exposure. Sample No. Initial 1.05 times Uc (pc) Final 1.05 times Uc (pc Initial 7 ma reference voltage kvc Final 7 ma reference voltage kvc 1 <1 < Test Conclusions Reference voltage changed less than 1% as a result of salt fog exposure. No tracking, shed puncture or significant erosions were evidenced by visual inspection carried out at the end of the test. The IEC Class 2 arrester design successfully passed the 1000 hour salt fog test, as defined in IEC standard. For details of test report, reference CESI AT-A3/ test report. EU

IEC Type Test Report Report No. EU1120-HR Type PDV 100 Polymer Arrester 10,000 A Line Discharge Class 1

IEC Type Test Report Report No. EU1120-HR Type PDV 100 Polymer Arrester 10,000 A Line Discharge Class 1 IEC Type Test Report Report No. EU1120-HR2-00.6 Type PDV 100 Polymer Arrester 10,000 A Line Discharge Class 1 This report records the results of this type test made on 10 ka Class 1 arresters rated 3 thru

More information

SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING

SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING Page 1 of 10 CONTENTS 1 SCOPE 2 DEFINITIONS 2.1 SURGE ARRESTER 2.2 GAPLESS METAL-OXIDE SURGE ARRESTERS 2.3

More information

Bowthorpe EMP surge arrester Distribution metal oxide surge arrester DA0 Series, (IEC)

Bowthorpe EMP surge arrester Distribution metal oxide surge arrester DA0 Series, (IEC) Energy Division Bowthorpe EMP surge arrester Distribution metal oxide surge arrester DA0 Series, (IEC) Bowthorpe EMP distribution metal oxide surge arrester DA0 series Tyco Electronics Bowthorpe EMP business

More information

Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series. Energy Division

Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series. Energy Division Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series Energy Division http://energy.tycoelectronics.com Bowthorpe Surge Arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development

More information

Qualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49. Report Number: EDR-5391 Rev. 0 06/15/05. Approved by: Signature: Date:

Qualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49. Report Number: EDR-5391 Rev. 0 06/15/05. Approved by: Signature: Date: Energy Report EDR-5391 Qualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49 Qualification Testing of Nuclear High Voltage Splice (NHVS) Enclosures: Report Number: Date: EDR-5391

More information

Energy Division. Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series

Energy Division. Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series Energy Division Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series At the core of the Bowthorpe OCP design is our improved ZnO varistor disk, which has superior thermal and electrical characteristics

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Integrally Mounted Medium and High Exposure Surge Protective Devices

More information

Table of Contents. Section Title Page 1.0 SUMMARY TEST SPECIMEN Materials and Construction 3.0 TEST PROGRAM 2

Table of Contents. Section Title Page 1.0 SUMMARY TEST SPECIMEN Materials and Construction 3.0 TEST PROGRAM 2 EDR-5210 01/07/92 Table of Contents Section Title Page 1.0 SUMMARY 1 2.0 TEST SPECIMEN 2 3.0 2.1 Materials and Construction 3.0 TEST PROGRAM 2 3.1 Test Sequence 3.2 Functional Test Procedures 3.3 Specimen

More information

Qualification Test Report. AMP-TWIST Series Jacks for Class EA systems

Qualification Test Report. AMP-TWIST Series Jacks for Class EA systems Qualification Test Report 501-93032 14/April/2011 Rev A AMP-TWIST Series Jacks for Class EA systems 1. INTRODUCTION 1.1 Purpose Qualification testing on AMP-TWIST* Series Jacks for Class E A Systems, to

More information

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear IEC/PAS 62271-109 Edition 1.0 2002-07 High-voltage switchgear and controlgear Part 109: Alternating-current series capacitor by-pass switches PUBLICLY AVAILABLE SPECIFICATION INTERNATIONAL ELECTROTECHNICAL

More information

PRODUCT SPECIFICATION. 0.5mm Fine Stacking. Hermaphroditic Type BTB Connector

PRODUCT SPECIFICATION. 0.5mm Fine Stacking. Hermaphroditic Type BTB Connector PRODUCT SPECIFICATION 108-115057 29OCT13 Rev. A1 0.5mm Fine Stacking Hermaphroditic Type BTB Connector 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for 0.5mm

More information

Energy Division. DAH series (IEEE) Distribution metal oxide surge arrester

Energy Division. DAH series (IEEE) Distribution metal oxide surge arrester Energy Division DAH series (IEEE) Distribution metal oxide surge arrester Bowthorpe EMP distribution surge arresters DAH series Tyco Electronics Bowthorpe EMP pioneered the development of polymeric composite

More information

ENERGY PRODUCTS DIVISION. Polymeric Surge Arresters Reliable protection for power equipment upto 800kV

ENERGY PRODUCTS DIVISION. Polymeric Surge Arresters Reliable protection for power equipment upto 800kV ENERGY PRODUCTS DIVISION LV MV HV Polymeric Reliable protection for power equipment upto 800kV Raychem Polymeric Surge Arrester Safety and reliability are vital in energy industry and Raychem RPG's Energy

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

/Mar/2014 Rev A

/Mar/2014 Rev A Qualification Test Report 501-93038 21/Mar/2014 Rev A MPOptimate FO Microcassette 12 fiber MPO-12xLC/PC 1. INTRODUCTION 1.1 Purpose Tests performed on MPOptimate FO Microcassette 12 fiber MPO-12xLC/PC,

More information

Jun08 Rev A

Jun08 Rev A Product Specification Terminal Block Crimp Snap Plug Assembly 108-2319 09Jun08 Rev A 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the Tyco Electronics

More information

TABLE OF CONTENTS. Section Title Page 1.0 SUMMARY TEST SPECIMEN Materials and Construction TEST PROGRAM 4

TABLE OF CONTENTS. Section Title Page 1.0 SUMMARY TEST SPECIMEN Materials and Construction TEST PROGRAM 4 TABLE OF CONTENTS Section Title Page 1.0 SUMMARY 1 2.0 TEST SPECIMEN 2 2.1 Materials and Construction 2 3.0 TEST PROGRAM 4 3.1 Test Sequence 4 3.2 Functional Test Procedures 5 3.3 Specimen Preconditioning

More information

Nuclear Products Requalification Testing Phase 2. Title Pages: 113. Report Number: EDR-5389 Rev. 0 12/10/2004. Approved by: Signature: Date:

Nuclear Products Requalification Testing Phase 2. Title Pages: 113. Report Number: EDR-5389 Rev. 0 12/10/2004. Approved by: Signature: Date: Energy Report EDR-5389 Nuclear Products Requalification Testing Phase 2 Title Pages: 113 Nuclear Products Requalification Testing Phase 2 Enclosures: Report Number: Date: EDR-5389 Rev. 0 12/10/2004 Prepared

More information

Bowthorpe EMP surge arrester Distribution metal oxide surge arrester DA1 Series, (IEC)

Bowthorpe EMP surge arrester Distribution metal oxide surge arrester DA1 Series, (IEC) Energy Division Bowthorpe EMP surge arrester Distribution metal oxide surge arrester DA1 Series, (IEC) Bowthorpe EMP distribution metal oxide surge arrester DA1 series Tyco Electronics Bowthorpe EMP business

More information

Product Specification EMI Shielded Duplex LC Sealed Receptacle (ODVA Conforming)

Product Specification EMI Shielded Duplex LC Sealed Receptacle (ODVA Conforming) Product Specification EMI Shielded Duplex LC Sealed Receptacle (ODVA Conforming) 02Oct08 Rev A 1. SCOPE 1.1. Content This specification, based on IEC 61753-1 Edition 1.0 tests for Category E (Extreme Environment),

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

ETSI TS V1.2.1 ( )

ETSI TS V1.2.1 ( ) TS 100 783 V1.2.1 (2004-08) Technical Specification Transmission and Multiplexing (TM); Passive optical components; Fibre optic fusion splices for single-mode optical fibre transmission systems for indoor

More information

Energy Star Directional Luminaire Test Report ELEC-TECH INTERNATIONAL CO LTD. LED Downlight

Energy Star Directional Luminaire Test Report ELEC-TECH INTERNATIONAL CO LTD. LED Downlight Directional Luminaire Test Report For ELEC-TECH INTERNATIONAL CO LTD No. 1 Jinfeng Road, Tangjiawan Town, Xiangzhou District, Zhuhai City, Guangdong Province, P.R.China 519085 LED Downlight Model name(s):

More information

1. PURPOSE. This advisory circular (AC) contains the Federal Aviation Administration (FAA) specification for obstruction lighting equipment.

1. PURPOSE. This advisory circular (AC) contains the Federal Aviation Administration (FAA) specification for obstruction lighting equipment. U.S. Department of Transportation Federal Aviation Administration Advisory Circular Subject: SPECIFICATION FOR OBSTRUCTION LIGHTING EQUIPMENT Date: 10/19/95 Initiated by: AAS-200 AC No:150/5345-43E Change:

More information

Independent, accredited testing station Member laboratory of STL and LOVAG

Independent, accredited testing station Member laboratory of STL and LOVAG Independent, accredited testing station Member laboratory of STL and LOVAG TYPE TEST REPORT NO. 3096.2081034.859 GSAB Elektrotechnik GmbH Lindenstraße 23 99718 Greußen GERMANY GSAB Elektrotechnik GmbH

More information

Page 2 of 14 Report Ref. No

Page 2 of 14 Report Ref. No age 2 of 14 Summary of testing: Tests performed (name of test and test clause): Clause 6.1, Initial measurements: - MST 01: Visual inspection - 10.2: Maximum power determination - MST 16: Dielectric withstand

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Mar11 Rev C

Mar11 Rev C Product Specification 108-1441 11Mar11 Rev C Connector, Z-PACK*, 2 mm FB, Signal and Power 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the Z-PACK* 2mm

More information

Side Entry Insulation Damage Repair Sleeve (SEIDRS) Raychem Devices Products

Side Entry Insulation Damage Repair Sleeve (SEIDRS) Raychem Devices Products 1.0 Scope This specification covers the design, performance and qualification requirements for Raychem Side Entry Insulation Damage Repair Sleeve. 1.1 Description. Raychem SEIDRS covered by this specification

More information

FT702LT Turbine control wind sensor gives durability a new meaning FT702LT. series

FT702LT Turbine control wind sensor gives durability a new meaning FT702LT. series FT702LT Turbine control wind sensor......gives durability a new meaning FT702LT series Proven High Availability The FT702LT ultrasonic anemometer is the result of FT Technologies 10 years of experience

More information

Rules for Classification and Construction Additional Rules and Guidelines

Rules for Classification and Construction Additional Rules and Guidelines VI Rules for Classification and Construction Additional Rules and Guidelines 7 Guidelines for the Performance of Type Approvals 7 Test Requirements for Statical Converters with Semi-Conductors Edition

More information

RAYCHEM MEDIUM VOLTAGE

RAYCHEM MEDIUM VOLTAGE ENERGY /// RAYCHEM MV OUTDOOR SURGE ARRESTERS RAYCHEM MEDIUM VOTAGE Surge Arresters for special applications Raychem MV Indoor Surge Arresters Raychem MV Surge Arresters MPA for Indoor Applications For

More information

Rules for Intruder Alarm Systems

Rules for Intruder Alarm Systems Rules for Intruder Alarm Systems Opening detectors (Magnetic contacts) Part 1: Requirements VdS 2120en 03/96 (03) Subject 44 1 General; 2 Terms and definitions; 3 Classification 1 General 1.1 Scope These

More information

SPECIFICATION AND PERFORMANCE MDP CONNECTOR SERIES

SPECIFICATION AND PERFORMANCE MDP CONNECTOR SERIES SPECIFICATION AND PERFORMANCE OF MDP CONNECTOR SERIES CIRCUIT ASSEMBLY CORP. 18 THOMAS STREET, IRVINE, CA 92618-2777 Page No. 1 of 16 CLAUSE CONTENTS PAGE 1.0 SCOPE... 3 2.0 APPLICABLE DOCUMENTS... 3 3.0

More information

Accumulated Battery JULY The electronic pdf version of this document found through is the officially binding version

Accumulated Battery JULY The electronic pdf version of this document found through   is the officially binding version p pproval roramms for U rcos orasato Mutual coto (M)No. 2.9 STANDARD FOR CERTIFICATION Approval Programmes Type Approval Programmes for EU recognised organisation Mutual Recognition (MR) No. MR-E008 Accumulated

More information

NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES

NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES Javier CORMENZANA Ormazabal Spain jco@orrmazabal.com Sergio SEBASTIAN Ormazabal -

More information

23" PANEL MOUNT INDUSTRIAL MONITOR REVISION C PRODUCT RELIABILITY TEST REPORT

23 PANEL MOUNT INDUSTRIAL MONITOR REVISION C PRODUCT RELIABILITY TEST REPORT 23" PANEL MOUNT INDUSTRIAL MONITOR REVISION C PRODUCT RELIABILITY TEST REPORT Model No. HIS-ML23- _ C Table of Contents Test Report Overview... 3 Testing Rationale...3 Test Plan...4 Test 1 Cold (Steady

More information

Plug shell and receptacle, single cavity, floating, EN Application of modular rectangular modules and shells per EN4165

Plug shell and receptacle, single cavity, floating, EN Application of modular rectangular modules and shells per EN4165 PRODUCT SPECIFICATION Sep 22, 29 Rev. B CONNECTOR, SINGLE CAVITY, AEROSPACE, PANEL MOUNT, FLOATING, EN416 1 - SCOPE 1.1. Content This document covers the performances, tests, and quality requirements of

More information

Free Height 0.8 mm Pitch Board-to-Board Connector (SMT)

Free Height 0.8 mm Pitch Board-to-Board Connector (SMT) Product 108-5390 Specification 31 OCT 17 Rev.F1 Free Height 0.8 mm Pitch Board-to-Board Connector (SMT) 1. SCOPE 1.1. Contents This specification covers the requirements for product performance, test methods

More information

Product Tests Report

Product Tests Report TO WHOM IT MAY CONCERN Page: 1 of 5 Product name: Model number and description: MIC IP starlight 7000i Product Tests Report MIC-7502-Z30B, PTZ camera 2MP HDR 30x IP68 IK10, black MIC-7502-Z30W, PTZ camera

More information

17" UNIVERSAL MOUNT INDUSTRIAL MONITOR REVISION E, F & G PRODUCT RELIABILITY TEST REPORT

17 UNIVERSAL MOUNT INDUSTRIAL MONITOR REVISION E, F & G PRODUCT RELIABILITY TEST REPORT 17" UNIVERSAL MOUNT INDUSTRIAL MONITOR REVISION E, F & G PRODUCT RELIABILITY TEST REPORT Model No. HIS-UM17- _ E, HIS-UM17- _ F and HIS-UM17- _ G Table of Contents Test Report Overview... 3 Testing Rationale...3

More information

POINT ROLLOVER LIGHTS PRL LED HELIDECK SEMIFLUSH LIGHT

POINT ROLLOVER LIGHTS PRL LED HELIDECK SEMIFLUSH LIGHT Compliances: ETL Listed to UL 98 & UL 98A Marine Vessels USA CSA C22.2 No..-4 Canada FAA AC /39-2B Heliport Design Guide ICAO Annex 14, Volume II UK CAA CAP 437, Chapter 4, paragraph 3.1 IMO 9 MODU Code

More information

Electric radiator tests

Electric radiator tests Electric radiator tests Carried out for Haverland By P Stonard 16 July 2010 Electric radiator tests Carried out for: Haverland Avda San Martin De Valdeigiesias Km-2,200 Alcorcon MADRID 28925 Spain Contract:

More information

Qualification Test Report LC Duplex Adapter For LC Cutouts

Qualification Test Report LC Duplex Adapter For LC Cutouts Qualification Test Report LC Duplex Adapter For LC Cutouts 501-683 09Mar09 Rev B 1. INTRODUCTION 1.1. Purpose Testing was performed on Tyco Electronics LC Duplex Adapters for LC Cutouts, to determine their

More information

Qualification Test Report 1/Jul/2005 Rev. A

Qualification Test Report 1/Jul/2005 Rev. A Qualification Test 501-93013 Report 1/Jul/2005 Rev. A AMP CO 10 Gigabit/s Insert PN 1711188-X 1. INTRODUCTION 1.1 Purpose Testing was performed on AMP* CO 10 Gigabit/s Insert, to determine its conformance

More information

Gardian W51. Approvals

Gardian W51. Approvals Gardian W51 120 V pre-assembled electric heating cables for pipe freeze protection and roof & gutter de-icing Installation Instructions Description Gardian W51 120 V pre-assembled self-regulating heating

More information

Speed and Frequency Seite 1 von 7

Speed and Frequency Seite 1 von 7 Speed and Frequency Seite 1 von 7 E16 Systems for High Safety Speed ing, all with Triple Modular Redundancy. A choice of versions to meet various demands. Compliant with SIL3 / IEC 61508 and/or API 670.

More information

VDE-QT-PV001:2012/01

VDE-QT-PV001:2012/01 1 VDE-QT-PV001:2012/01 VDE-QT-PV001:2012/01 Combined IEC 61215 ed.2, IEC 61730-1 ed. 1, IEC 61730-2 ed.2 plus VDE addendums 2 VDE-QT-PV001:2012/01 CONTENTS 1 Scope and object 5 2 Normative references 5

More information

Two Circuit Heavy Duty Burner Connector

Two Circuit Heavy Duty Burner Connector Product 108-1056 11 Oct.16 Rev B Specification EC 0990-0059-05 Two Circuit Heavy Duty Burner Connector 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the

More information

A three-pole dead-tank SF 6 circuit-breaker incorporating one interrupter per pole in single-pole enclosures with a common operating mechanism

A three-pole dead-tank SF 6 circuit-breaker incorporating one interrupter per pole in single-pole enclosures with a common operating mechanism Object A three-pole dead-tank SF 6 circuit-breaker incorporating one interrupter per pole in single-pole enclosures with a common operating mechanism 2153-16 Type TCB 145-40-31 Serial No. 16000702, 16000703

More information

IR1xxx Series 1, IR2xxx Series 1 Miniature Infrared Gas Sensors for Hazardous Areas and Intrinsic Safety in Mining

IR1xxx Series 1, IR2xxx Series 1 Miniature Infrared Gas Sensors for Hazardous Areas and Intrinsic Safety in Mining IR1xxx Series 1, IR2xxx Series 1 Miniature Infrared Gas Sensors for Hazardous Areas and Intrinsic Safety in Mining FEATURES * Configured for carbon dioxide (IR11BD, IR21BD), hydrocarbons (,,, ) or acetylene

More information

FALCON SERIES 12 METAL CLAD

FALCON SERIES 12 METAL CLAD We engineer, we assure. FALCON SERIES 12 METAL CLAD Until 11kV - 31,5 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel Saudi Cable Company REF: EMCF-EN-16-03 2 www.elimsan.com FALCON

More information

Test Methods for Consideration Into Radio Standard

Test Methods for Consideration Into Radio Standard Test Methods for Consideration Into Radio Standard Jason Allen March 20,2013 Test Methods for Consideration Into Radio Standard Reviewed many current NFPA standards including: NFPA 1971- Structural and

More information

Standard PRC Transmission Relay Loadability

Standard PRC Transmission Relay Loadability A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-2 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability

More information

Cat 6 Shielded Patch cords

Cat 6 Shielded Patch cords Product Specification 108-93010 14/Oct/2009 Rev E Cat 6 Shielded Patch cords 1. SCOPE 1.1 Content This specification describes performance and material requirements and tests procedures for AMP NETCONNECT*

More information

MAR2 LED SERIES M A R 2 L E D. Linear LED Lighting for Hazardous Locations

MAR2 LED SERIES M A R 2 L E D. Linear LED Lighting for Hazardous Locations MAR2 LED SERIES Linear LED Lighting for Hazardous Locations Class I, Division 2, Groups A, B, C & D UL 844 Hazardous Locations UL 1598A Marine Outside Type UL 8750 LED Safety CSA C22.2 #250.0-08; CSA C22.2

More information

POINT HELIDECK LIGHTS PRL-LSM LED LOW SURFACE MOUNT LIGHT

POINT HELIDECK LIGHTS PRL-LSM LED LOW SURFACE MOUNT LIGHT Compliances: ETL Listed to UL 98 US & CSA C22.2 No..-4 Canada ETL Listed to UL 98A Marine Vessels IMO 9 MODU Code () paragraph 13.. FAA AC /39-2B Heliport Design Guide ICAO Annex 14, Volume II UK CAA CAP

More information

SolderSleeve Insulated Electrical Termination Devices

SolderSleeve Insulated Electrical Termination Devices Tyco Electronics Corporation 300 Constitutional Drive Menlo Park, CA 94025 USA Specification This Issue: Date: Replaces: RT-1404 ISSUE 9 April 20, 2000 ISSUE 8 1.0 INTRODUCTION SolderSleeve Insulated Electrical

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

/Oct/2014 Rev E

/Oct/2014 Rev E Product Specification 108-93017 14/Oct/2014 Rev E Cat 6 Unshielded Patch Cords 1. SCOPE 1.1 Content This specification describes performance and material requirements and tests procedures for TE Connectivity

More information

AA-480-XX OUTDOOR THERMOELECTRIC COOLER ASSEMBLY USER S MANUAL

AA-480-XX OUTDOOR THERMOELECTRIC COOLER ASSEMBLY USER S MANUAL AA-480-XX OUTDOOR THERMOELECTRIC COOLER ASSEMBLY USER S MANUAL Table of Contents Introduction 3 Incoming Inspection 3 General Safety & Warnings 3 Technical Specifications 4 Installation and Operation Instructions

More information

HMN-D2 Insert Series

HMN-D2 Insert Series HMN-D2 Insert Series Table of contents 1. SCOPE... 2 1.1. Content... 2 1.2. Qualification... 2 2. APPLICABLE DOCUMENTS... 2 2.1. TE Connectivity Documents... 2 2.2. Other Documents... 2 3. REQUIREMENTS...

More information

FALCON SERIES 12 METAL CLAD

FALCON SERIES 12 METAL CLAD We engineer, we assure. FALCON SERIES 12 METAL CLAD Until 11kV - 31,5 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel Saudi Cable Company REF: EMCF-EN-16-02 2 www.elimsan.com 3 FALCON

More information

Electric radiator test

Electric radiator test Electric radiator test Final Report 56161/1 Carried out for Cornwall Heating Solutions Ltd & Bright Heating By Calum Maclean 27 June 2012 Electric radiator test Carried out for: Cornwall Heating Solutions

More information

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045 FOR THE SCOPE OF ACCREDITATION UNDER NVLAP LAB CODE 100402-0. Project No. G101030158 Date: February 26, 2013 REPORT NO. 101030158CRT-001 TEST OF ONE LED

More information

Vibration tests on a TNAML Luminaire

Vibration tests on a TNAML Luminaire Sebert Trillingstechniek B.V. Report M13.001-P13.001 rev.01 Date 26 august 2013 Vibration tests on a TNAML Luminaire Client Technor Benelux B.V. Veersteeg 15 4212 LR Spijk The Netherlands Contact Person

More information

38-SDMS-01 SPECIFICATIONS FOR FAULT INDICATORS FOR UNDERGROUND DISTRIBUTION NETWORKS

38-SDMS-01 SPECIFICATIONS FOR FAULT INDICATORS FOR UNDERGROUND DISTRIBUTION NETWORKS SPECIFICATIONS FOR FAULT INDICATORS FOR UNDERGROUND DISTRIBUTION NETWORKS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3

More information

COMITÉ EUROPÉEN DES ASSURANCES

COMITÉ EUROPÉEN DES ASSURANCES COMITÉ EUROPÉEN DES ASSURANCES SECRETARIAT GENERAL 3bis, rue de la Chaussée d'antin F 75009 Paris Tél. : +33 1 44 83 11 73 Fax : +33 1 44 83 11 85 Web : cea.assur.org DELEGATION A BRUXELLES Square de Meeûs,

More information

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division 7 418 ISO 9001 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of low to medium capacity, without fan assistance, in intermittent operation. The

More information

PQS Independent type-testing protocol

PQS Independent type-testing protocol PQS Independent type-testing protocol WHO/XXX Original: English Distribution: General TITLE: Wall-mounted pen recording thermometer Product verification protocol: E06/TR04VP Applies to specification ref(s):

More information

Technical Specification for the Mastic-Sealed Fiber-Optic Closure System (FOSC 300C)

Technical Specification for the Mastic-Sealed Fiber-Optic Closure System (FOSC 300C) Page 1 of 24 Prepared by: Chris Radelet R&D Department Manager Approved by: Pieter De Coster Product Manager for the Mastic-Sealed Fiber-Optic Closure System (FOSC 300C) The FOSC 300C closure system is

More information

Type approval qualification of Photovoltaic Modules Procedures and test experiences

Type approval qualification of Photovoltaic Modules Procedures and test experiences Type approval qualification of Photovoltaic Modules Procedures and test experiences We Advise. Develop. Facilitate. Inspect. Certificate. Precisely Right. For You. 1 Type approval qualification of Photovoltaic

More information

M7100 Pressure Transducer

M7100 Pressure Transducer SPECIFICATIONS Performance standard on and off highway engine and vehicle OEMs Rugged for heavy equipment and outdoor use Designed specifically for high volume applications Stainless steel wetted surfaces

More information

Jan05 Rev A EC

Jan05 Rev A EC Product Specification Two Circuit Heavy Duty Burner Connector 108-1056 12Jan05 Rev A EC 0990-0059-05 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the

More information

USB 3.0 Plug & Receptacle

USB 3.0 Plug & Receptacle US 3.0 Plug & Receptacle 1. Scope: 1.1 Contents: This specification covers the requirements for product performance, test methods and quality requirements of Tyco Electronics Universal Serial us (US) consortium

More information

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE / 3 GM20 Digital Ground Continuity Relay For AC Systems Technical Bulletin NAE03230 / 0.20 GM20 Ground continuity monitor For AC systems Description The GM20 monitors the loop resistance of ground conductors

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60076-11 First edition 2004-05 Power transformers Part 11: Dry-type transformers This English-language version is derived from the original bilingual publication by leaving out

More information

PolyGarde Metal-Oxide Surge Arresters

PolyGarde Metal-Oxide Surge Arresters PolyGarde Metal-Oxide Surge Arresters R Metal-Oxide Surge Arresters Based on over twenty years of experience in the field of crosslinked polymers for medium and high-voltage applications, Raychem has

More information

POINT ROLLOVER LIGHTS PRL LED HELIPORT INSET LIGHT

POINT ROLLOVER LIGHTS PRL LED HELIPORT INSET LIGHT Compliances: ETL Listed to UL 98 ETL Listed to UL 98A Marine Vessels ETL Listed to CSA C22.2 No..-4 Canada FAA AC /39-2B Heliport Design Guide ICAO Annex 14, Volume II UK CAA CAP 437, Chapter 4, paragraph

More information

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13 Test Report No. AJHG1501000530FB Date: FEB.17, 2015 Page 1 of 13 ZHEJIANG TERASUN AIR DUCT CO., LTD MAREN VILLAGE, CHONGREN INDUSTRIAL ZONE, CHONGREN TOWN, SHENGZHOU CITY, ZHEJIANG PROVINCE, CHINA The

More information

POINT FLASHING BEACON PFB EX LED HAZARDOUS AREA CLASS I, DIVISION 2

POINT FLASHING BEACON PFB EX LED HAZARDOUS AREA CLASS I, DIVISION 2 Compliances: Class I, Division 2, Groups A B C D, T6 Class I, Zone 2, Groups IIA IIB+H2 IIC, T6 ETL Verified FAA L-864 to FAA Advisory Circular 150/5345-43G Compliance to ICAO Annex 14 Medium Intensity

More information

Table of Contents FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS...

Table of Contents FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS... TITLE SPECIFICATION FOR PHOTOELECTRIC CONTROL UNITS (PECUs) REFERENCE REV DATE: JUNE 2017 PAGE: 1 OF 16 REVISION DATE: Table of Contents FOREWORD... 3 INTRODUCTION... 4 1 SCOPE... 4 2 NORMATIVE REFERENCES...

More information

IR15TT-R Miniature Infrared Gas Sensor for Monitoring Carbon Dioxide and Methane up to 100% Vol.

IR15TT-R Miniature Infrared Gas Sensor for Monitoring Carbon Dioxide and Methane up to 100% Vol. IR15TT-R Miniature Infrared Gas Sensor for Monitoring Carbon Dioxide and Methane up to 100% Vol. FEATURES Two active gas channels for simultaneous detection of carbon dioxide and methane (or other hydrocarbons)

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK Langer Road Contact: Mr I Frost Felixstowe Tel: +44 (0)1394 694000 Suffolk Fax: +44 (0)1394 276030 IP11 2ER E-Mail: ian.frost@itron.com Website:

More information

Substation Monitoring System

Substation Monitoring System Substation Monitoring System UHF Partial Discharge Monitoring System Description Introduction The UHF PDM System is the third generation, spanning 20 years, of monitoring systems developed for GIS partial

More information

TOCOS. Guidelines & Precautions. For Using Trimmer Potentiometers. Guidelines for Circuit Design. Guidelines for Production Processes

TOCOS. Guidelines & Precautions. For Using Trimmer Potentiometers. Guidelines for Circuit Design. Guidelines for Production Processes TOCOS Trimmer Potentiometers are designed and manufactured with emphasis on dependability and costeffectiveness. For reliable performance and general safety, follow these guidelines and precautions for

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61400-24 Edition 1.0 2010-06 Wind turbines Part 24: Lightning protection INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XG ICS 27.180 ISBN 978-2-88910-969-2 Registered

More information

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products 7 418 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of small to medium capacity (without fan) in intermittent operation. The LGA... and this

More information

Color Mark Sensor. Sensing gdsa distance Spot diameter e. Possible to switch between vertical or horizontal connection using the M12 rotary connector.

Color Mark Sensor. Sensing gdsa distance Spot diameter e. Possible to switch between vertical or horizontal connection using the M12 rotary connector. Color Mark Sensor Detects laminated or light-dispersing objects in stable operation without being influenced by mirror reflection. Double indication of the detection level and threshold level allows easy

More information

Thick-Film Heater achieves Superior Performance in Thermal Response, Uniformity and Efficiency.

Thick-Film Heater achieves Superior Performance in Thermal Response, Uniformity and Efficiency. Thick-Film Heater achieves Superior Performance in Thermal Response, Uniformity and Efficiency. by Mary Ruggiero, P.Eng., PhD and John Stockton, P.Eng Abstract IntegrAL thick-film heaters by Datec Corporation

More information

SP METHOD 5320 Issue No: Test method for fire detection systems installed in engine compartments of heavy vehicles

SP METHOD 5320 Issue No: Test method for fire detection systems installed in engine compartments of heavy vehicles SP METHOD 5320 Test method for fire detection systems installed in engine compartments of heavy vehicles Page 1(17) Copyright This test method is copyrighted by SP. Neither a printed nor electronic copy

More information

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60539-1 QC 430000 First edition 2002-02 Directly heated negative temperature coefficient thermistors Part 1: Generic specification Thermistors à coefficient de température négatif

More information

Draft ES V1.1.1 ( )

Draft ES V1.1.1 ( ) Standard Transmission and Multiplexing (TM); Passive optical components; Fibre optic mechanical splices for single-mode optical fibre communications systems; Common requirements and conformance testing

More information

POWDER GUIDE. Trouble shooting tips to maximise the benefits of Apcoshield Powder Coatings

POWDER GUIDE. Trouble shooting tips to maximise the benefits of Apcoshield Powder Coatings POWDER GUIDE From ASIAN PAINTS (I) LTD Trouble shooting tips to maximise the benefits of Apcoshield Powder Coatings Section A : Powder Application Problems Trouble Possible Causes Solutions 1. Poor charging

More information

PolySwitch TS600 Overcurrent Protection Devices

PolySwitch TS600 Overcurrent Protection Devices R PolySwitch TS600 Overcurrent Protection Devices New surface-mount products for overcurrent protection Raychem introduces the PolySwitch TS600 series to protect sensitive telecommunications equipment

More information

Energy Division. Raychem Insulation Enhancement Systems

Energy Division. Raychem Insulation Enhancement Systems Energy Division Raychem Insulation Enhancement Systems Raychem Insulation Enhancement System Based on Tyco Electronics Raychem long experience in polymer technology and sealing systems for energy networks

More information

POINT HELIDECK LIGHTS PRL-EX-LSM LED v4 CLASS I, DIVISION 2 & ZONE 2

POINT HELIDECK LIGHTS PRL-EX-LSM LED v4 CLASS I, DIVISION 2 & ZONE 2 Compliances: ETL Listed Class I, Division 2, Groups A B C D, T6 at -40 deg C to +55 deg C ETL Listed Class I, Zone 2, Groups IIA, IIB+H2, IIC T6 at -40 deg C to +55 deg C ETL Listed to UL 844 & UL 1598

More information

Technical Specification for the Gel-Sealed Fiber-Optic Closure System (FOSC 450)

Technical Specification for the Gel-Sealed Fiber-Optic Closure System (FOSC 450) Page 1 of 26 Prepared by: Daniel Daems R&D Department Manager Approved by: P. De Coster Product Manager for the Gel-Sealed Fiber-Optic Closure System (FOSC 450) The FOSC 450 system is a fully mechanical

More information