Technical Note. Noise emission from Dehumidifier Type C65E TC Project no.: I Page 1 of July 2016

Size: px
Start display at page:

Download "Technical Note. Noise emission from Dehumidifier Type C65E TC Project no.: I Page 1 of July 2016"

Transcription

1 Technical Note Noise emission from Dehumidifier Type C65E-11.1 Performed for COTES A/S Project no.: I Page 1 of July 2016 DELTA Venlighedsvej Hørsholm Denmark Tel Fax VAT No The report must not be reproduced, except in full, without the written approval of DELTA.

2 Page 2 of 10 Title Noise emission from Dehumidifier Type C65E-11.1 Journal no. Project no. Our ref. I RUE/JEL/ilk Client COTES A/S Ndr. Ringgade 70c 4200 Slagelse Denmark Client ref. Rasmus Toftegaard Laboratory DELTA Agro Food Park Aarhus N Denmark Test conditions DS/EN ISO 11202:2010 DS/EN ISO 3744:2010 Results The dehumidifier type C65E-11.1 has been tested on 7 June 2016 and the sound pressure level was measured 1 metre from the dehumidifier in four positions. The maximum A-weighted sound pressure level, L pa at 1 metre distance was measured in position B (left side) at nominal flow mode: Standard deviation is σ tot = 1.6 db. Remarks 69.0 db re 20 µpa The results apply only to the object tested. Results are rounded to the nearest 0.5 db. DELTA, 1 July 2016 Rune Egedal Specialist, Acoustics Jens Elgaard Laursen Senior Specialist, Acoustics

3 Page 3 of 10 Contents 1. Introduction Test object Operating conditions during test Acoustic environment Measurement methods Sound pressure measurements and corrections Test results Sound pressure levels... 6 Annex 1 Measurement points... 8 Annex 2 Instrumentation... 9 Annex 3 Sound power levels for reference sound source B&K

4 Page 4 of Introduction On behalf of COTES A/S, DELTA has performed sound measurements on a dehumidifier type C65E The noise measurements were performed according to DS/EN ISO 11202: Test object Type: C65E-11.1 Make: COTES A/S Serial No.: Process Flow: 2600 m 3 /h Reg. Flow: 460 m 3 /h Power: 16.2 kw Dimensions: L: 820 mm / W: 1165 mm / H: 1615 mm Figure 1 Test set-up for the dehumidifier C65E The front here is Position A (see Annex 1).

5 Page 5 of Operating conditions during test The dehumidifier was tested operating at nominal flow mode. The noise emission was steady for the specified operating mode. 3. Acoustic environment The dehumidifier was placed indoor in a large workshop room at COTES, Rudolfgårdsvej 1A, 8260 Viby, Denmark (see Figure 1). On the ceiling of the workshop were mounted acoustic absorbing panels. The main dimensions of the room are 13.5 m 8 m 2.8 m (length width height). The acoustic quality of the test room was measured with a reference sound source from Brüel & Kjær type The measurements were performed by Rune Egedal, DELTA Acoustics, on 7 June 2016 and were performed according to ISO 3744 annex A2 in order to calculate the test rooms environmental correction factor K 2A. The results are listed in Table K 2A [db re 20 µpa] Table 1 Values of K 2A for the test room at COTES A/S, Viby J The K 2A values are all lower than 7 db, and the test room therefore qualifies for sound pressure measurements according to DS/EN ISO The sound power level values of the reference sound source are enclosed in Annex Measurement methods The measurements were performed according to standard DS/EN ISO The sound pressure level was measured in four positions at 1 metre distance from the test object and at a height of 1.55 metre as illustrated in Annex 1. A photo of the measuring set-up is shown in Figure 1. The measurements of the test object were performed on 7 June 2016 by Rune Egedal, DELTA Acoustics. The used instruments are listed in Annex 2. All measurements were performed with the test object in nominal flow mode.

6 Page 6 of Sound pressure measurements and corrections In each of the measurement positions the sound pressure level was measured for minimum 30 seconds. The background noise in the test room was measured while the dehumidifier was turned off. The measured time-averaged sound pressure levels L pa are corrected for each microphone position according to the following formula: Where L pa = L pa) - K 1A - K 3A. L pa is the energy A-weighted sound pressure level on the measuring surface, corrected for K 1A and K 3A. K 1A is the A-weighted correction for background noise level K 3A is an environmental correction depending of reflecting surroundings. The measurements were calculated and corrected in octave frequency bands before summing up. According to Annex A in DS/EN ISO 11202, the local environmental correction K 3A is dependent of the absorption area of the room surfaces: K 3A = 10 log (1 + 4S/A), where S is the area of a hemisphere with a radius of 1 metre: S = 2 π r 2 = 6.28 m 2. A is the total absorption area of the room: A = α S V, where α = 0.3 is an estimate of the mean absorption coefficient of the room surfaces. S V is the total area of the test room (walls, ceiling and floor), S V = 336 m 2. The value of K3A is determined to 1.0 db(a) 6. Test results 6.1 Sound pressure levels In Table 2 the measurement results are shown as the A-weighted sound pressure level in each of the four microphone positions: A-D (see illustration in Annex 1). C65E-11.1 Sound pressure levels, L pa in db re 20 µpa Measurement position A B C D Mean value Nominal flow mode Table 2 Type C65E-11.1.Measured and corrected, averaged, A-weighted sound pressure levels L, pa in db re 20 µpa corrected for background noise (K 1A ) and the environment correction (K 3A ). The highest value was found in position B on the left side of the test object: 69.1 db(a).

7 Page 7 of 10 The background noise was measured in all four position positions. The average background noise was 32.0 db(a). The standard deviation of the measurements is σ R0 = 1.5 db (accuracy grade 2). The operating and mounting conditions are σ omc = 0.5 db and the total standard deviation is σ tot = 1.6 db. The expanded uncertainty U for a one-sided confidence level of 95% is U = 2.5 db. The corrected, averaged (four positions), A-weighted sound pressure levels per 1/1-octave frequency band are shown in Table 3. Condition Nominal flow mode SUM Table 3 Type C65E Corrected, averaged, A-weighted sound pressure levels per 1/1-octave frequency band in db re 20 µpa.

8 Page 8 of 10 Annex 1 Measurement points The dashed lines show the measurement surface located at d = 1 metre from the reference box containing the test object. Four microphone positions were placed at height 1.55 m above the floor. B A C D Set-up for the sound pressure measurements (not in scale).

9 Page 9 of 10 Annex 2 Instrumentation Instruments and analysis software used for the sound measurements on 7 June 2016: No. Equipment Make Type Previous Calibration Next 02L019 Calibrator Brüel & Kjær Apr Oct L059 ½ Microphone G.R.A.S 40AE 22 Jan Jan L062 ½ Microphone G.R.A.S 40AE 30 Nov Nov L057 ½ Microphone G.R.A.S 40AE 7 Apr Apr L042 ½ Microphone G.R.A.S 40AE 21 Jan Jan L031 Preamplifier G.R.A.S 26CA 8 Apr Apr L043 Preamplifier G.R.A.S 26CA 21 Nov Nov L042 Preamplifier G.R.A.S 26CA 21 Nov Nov L039 Preamplifier G.R.A.S 26CA 21 Nov Nov L008 Ref. Sound Source Brüel & Kjær Apr Apr L002 Data aq. card National instruments NI Dec Dec Multimeter Fluke For recording and analysis the program noiselab 3.0 and noiselab Batch Processor from DELTA was used. The measurement set-up was calibrated before and after the measurements. All instruments are calibrated regularly in accordance with our DANAK guidelines.

10 Annex 3 Sound power levels for reference sound source B&K 4204 Page 10 of 10

Technical Note. Noise emission from Dehumidifier Type C35E-3.3 and Type C35E-5.6. TC Project no.: T Page 1 of 10.

Technical Note. Noise emission from Dehumidifier Type C35E-3.3 and Type C35E-5.6. TC Project no.: T Page 1 of 10. Technical Note Noise emission from Dehumidifier Type C35E-3.3 and Type C35E-5.6 Performed for COTES A/S TC-100902 Project no.: T211658 Page 1 of 10 15 January 2016 DELTA Venlighedsvej 4 2970 Hørsholm Denmark

More information

Technical Note. Noise emission from Dehumidifier Type C22/CR100. TC Project no.: T Page 1 of January 2016

Technical Note. Noise emission from Dehumidifier Type C22/CR100. TC Project no.: T Page 1 of January 2016 Technical Note Noise emission from Dehumidifier Type C22/CR100 Performed for COTES A/S TC-100899 Project no.: T211658 Page 1 of 9 15 January 2016 DELTA Venlighedsvej 4 2970 Hørsholm Denmark Tel. +45 72

More information

TEST REPORT No. EN-2160/057/15-098/15

TEST REPORT No. EN-2160/057/15-098/15 RN 72160821 Zagreb, 2015-12-21 TEST REPORT No. EN-2160/057/15-098/15 Building product: Leviter Shape 8 sound-absorption cladding Client: Sonitus d.o.o. Tina Ujevića 26 HR-48000 Koprivnica Croatia Contract/order:

More information

Sound Pressure Level Test Report Report No. : PH2_09_ Date : 2009/6/30

Sound Pressure Level Test Report Report No. : PH2_09_ Date : 2009/6/30 聲學測試實驗室 PAL Acoustics Technology Ltd. 4F, No, 388, Sec.1, Nei Hu Rd., Taipei, Taiwan. 114 Tel:886-2-2627-2515 Fax:886-2-2627-2295 www.pal-acoustics.com Sound Pressure Level Test Report Report No. : PH2_09_0227-1

More information

Supplementary type approval testing of Selco modules

Supplementary type approval testing of Selco modules We help ideas meet the real world DELTA Test Report DANAK TEST Reg. no. 19 Supplementary type approval testing of Selco modules Performed for Selco A/S DANAK-198611 Project no.: A504377-1 Page 1 of 20

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 18738-2 First edition 2012-10-15 Measurement of ride quality Part 2: Escalators and moving walks Mesure de la qualité de déplacement Partie 2: Escaliers mécaniques et trottoirs

More information

Test Report Nº B2016 LACUS IN 24

Test Report Nº B2016 LACUS IN 24 EMPLEGU ETA GIZARTE POLITIKETAKO SAILA Etxebizitza, Zuzendaritza DEPARTAMENTO DE EMPLEO Y POLÍTICAS SOCIALES Dirección de Vivienda AKUSTIKA ARLOA kudeatzailea: ACOUSTICS AREA managed by: Laboratory measurement

More information

DELTA Classification Report

DELTA Classification Report DELTA Classification Report TEST Reg. no. 19 Reaction to fire classification report for electric cables: Cat 6A U/FTP 500 MHz FRNC Performed for Caleb Cable Industrial Ltd. no.: Page 1 of 9 19 December

More information

Determination of air borne sound insulation According to ISO 140-3

Determination of air borne sound insulation According to ISO 140-3 Date : May 16, 2011 Door System Single leaf Fire Door Type 11 SHIRYONIT-HOSEM Determination of air borne sound insulation According to ISO 140- Test Report No. 116-1 Client: SHIRYONIT-HOSEM Security Products

More information

TNO report MON-RPT-033-DTS

TNO report MON-RPT-033-DTS Stieltjesweg 1 PO BOX 155 2600 AD Delft www.tno.nl Telephone +31 15 269 20 00 Fax +31 15 269 21 11 Info-IenT@tno.nl TNO report MON-RPT-033-DTS-2008-01823 Airborne sound insulation of the SGG Systems Clip-in

More information

ISO INTERNATIONAL STANDARD. Small craft Airborne sound emitted by powered recreational craft Part 1: Pass-by measurement procedures

ISO INTERNATIONAL STANDARD. Small craft Airborne sound emitted by powered recreational craft Part 1: Pass-by measurement procedures Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 14509-1 First edition 2008-10-01 Small craft Airborne sound emitted by powered recreational craft Part 1: Pass-by measurement procedures Petits

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 22868 Second edition 2011-03-01 Forestry and gardening machinery Noise test code for portable hand-held machines with internal combustion engine Engineering method (Grade 2 accuracy)

More information

Standard ECMA th Edition - December Declared Noise Emission Values of Information Technology and Telecommunications Equipment

Standard ECMA th Edition - December Declared Noise Emission Values of Information Technology and Telecommunications Equipment Standard ECMA-109 4 th Edition - December 1996 Standardizing Information and Communication Systems Declared Noise Emission Values of Information Technology and Telecommunications Equipment Phone: +41 22

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61400-11 Edition 2.1 2006-11 Edition 2:2002 consolidated with amendment 1:2006 Wind turbine generator systems Part 11: Acoustic noise measurement techniques Reference number

More information

PCT Workshop Before you leave the office

PCT Workshop Before you leave the office Before you leave the office Documentation Suitable Equipment Calibration Training Preparation Documentation Currently documentation for the scheme consists of: Association Of Noise Consultants PCT Registration

More information

Hemi Anechoic Chamber Number:

Hemi Anechoic Chamber Number: 1 of 6 Hemi Anechoic Chamber Architecture: 2 of 6 * Concrete floor and walls * Control room dimensions = 20 x 15 X 10 Feet. 3 of 6 Inner View / Features (not limited to below listing): * only a representative

More information

Consumer vacuum breast-pumps

Consumer vacuum breast-pumps Müller-BBM GmbH Robert-Koch-Str. 11 82152 Planegg bei München Telephone +49(89)85602 0 Telefax +49(89)85602 111 www.muellerbbm.de M.Eng. Philipp Meistring Telephone +49(89)85602 228 Philipp.Meistring@mbbm.com

More information

Report Number BTC 15450A

Report Number BTC 15450A Report Number BTC 15450A AN ACOUSTIC TEST REPORT COVERING LABORATORY SOUND INSULATION TESTS TO BS EN ISO 140-3:1995 ON A BRITISH GYPSUM GYPWALL AUDIO PARTITION WITH VARYING NUMBERS OF ELECTRICAL SOCKET

More information

AGREEMENT CONCERNING THE ADOPTION OF UNIFORM CONDITIONS OF APPROVAL AND RECIPROCAL RECOGNITION OF APPROVAL FOR MOTOR VEHICLE EQUIPMENT AND PARTS

AGREEMENT CONCERNING THE ADOPTION OF UNIFORM CONDITIONS OF APPROVAL AND RECIPROCAL RECOGNITION OF APPROVAL FOR MOTOR VEHICLE EQUIPMENT AND PARTS /Amend.1 E/ECE/TRANS/505A 21 February 1984 AGREEMENT CONCERNING THE ADOPTION OF UNIFORM CONDITIONS OF APPROVAL AND RECIPROCAL RECOGNITION OF APPROVAL FOR MOTOR VEHICLE EQUIPMENT AND PARTS done at Geneva

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60704-2-13 Edition 2.0 2011-01 Household and similar electrical appliances Test code for the determination of airborne acoustical noise Part 2-13: Particular requirements for

More information

1 Introduction - The rating level. 3 Subjective or objective analysis? 2 Determination of the adjustment for annoying tones

1 Introduction - The rating level. 3 Subjective or objective analysis? 2 Determination of the adjustment for annoying tones Noise can be said to be tonal if it contains a distinguishable, discrete, continuous note. This may include a whine, hiss, screech, hum, etc., and any such subjective finding is open to discussion when

More information

Bruksanvisning Directions for use

Bruksanvisning Directions for use Bruksanvisning Directions for use LPKB 125 B/B-r, LPKB 160 K/K-r, LPKB 200 B/B-r, LPKB 200 K/K-r LPKBI 125 B/B-r, LPKBI 160 K/K-r, LPKBI 200 B/B-r, LPKBI 200 K/K-r SVENSK/ENGLISH VERSION ENGLISH This directions

More information

o Rear HVAC columns (Priority 1: Item 3) the rear ceiling area: be more dead for the organ and traditional music. (Priority 2: Item A)

o Rear HVAC columns (Priority 1: Item 3) the rear ceiling area: be more dead for the organ and traditional music. (Priority 2: Item A) Table 2. Prioritized recommendations for sound system enhancements and acoustical finishes. PRIORITY SOUND SYSTEM ACOUSTICAL FINISHES Scheme 1: Priority 1 Priority 1: Rear Surface Treatment to Reduce Acoustical

More information

ISO 6393 INTERNATIONAL STANDARD. Earth-moving machinery Determination of sound power level Stationary test conditions

ISO 6393 INTERNATIONAL STANDARD. Earth-moving machinery Determination of sound power level Stationary test conditions INTERNATIONAL STANDARD ISO 6393 Third edition 2008-03-15 Earth-moving machinery Determination of sound power level Stationary test conditions Engins de terrassement Détermination du niveau de puissance

More information

Gern Glas Order no. 0302/ Industrivej 4 Page 1 of Sorring Appendicis 1 Danmark Initials MJLD/MFRI

Gern Glas Order no. 0302/ Industrivej 4 Page 1 of Sorring Appendicis 1 Danmark Initials MJLD/MFRI TEST Reg. No. 2 Gern Glas Order no. 0302/805637 Industrivej 4 Page 1 of 2 8641 Sorring Appendicis 1 Danmark Initials MJLD/MFRI Test report Teknologiparken Kongsvang Allé 29 8000 Aarhus C + 45 72 20 20

More information

Acoustical Test Methods and Sound Power Rating Procedures for Transport Refrigeration Equipment

Acoustical Test Methods and Sound Power Rating Procedures for Transport Refrigeration Equipment AHRI Standard 1120 (formerly ARI Standard 1120) 2007 Standard for Acoustical Test Methods and Sound Power Rating Procedures for Transport Refrigeration Equipment IMPORTANT SAFETY RECOMMENDATIONS It is

More information

According to the following European Regulations which come into force:

According to the following European Regulations which come into force: WHAT HAPPENS? From September 26th 2015, in order to be placed on the European market, all products and systems used for heating, production and storage of hot water must comply with the MINIMUM ENERGY

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 10302-1 First edition 2011-01-15 Acoustics Measurement of airborne noise emitted and structure-borne vibration induced by small air-moving devices Part 1: Airborne noise measurement

More information

Chillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to kw

Chillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to kw Chillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to 1.99 kw Centrifugal compressor with magnetic levitation This is a miniaturized, highly innovative

More information

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N E S A RE F R E IG RA N T G TECHNICAL MANUAL -FRIEND Y CONDENSING UNITS FOR OUTDOOR INSTALLATION O L CMA C 2 The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual,

More information

Brief Synopsis of the Japanese MOE Sponsored Evaluation of Wind Turbine Noise

Brief Synopsis of the Japanese MOE Sponsored Evaluation of Wind Turbine Noise Brief Synopsis of the Japanese MOE Sponsored Evaluation of Wind Turbine Noise Principal Investigator: Dr. Hideki Tachibana Presented by Mark Bastasch, PE, INCE Slides Courtesy of Dr. Tachibana Research

More information

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION ECO-FRIENDLY REFRIGERANT GAS INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years

More information

Room Acoustics, PA Systems and Speech Intelligibility for Voice Alarm Systems using the example of the Cruise Center Steinwerder

Room Acoustics, PA Systems and Speech Intelligibility for Voice Alarm Systems using the example of the Cruise Center Steinwerder Room Acoustics, PA Systems and Speech Intelligibility for Voice Alarm Systems using the example of the Cruise Center Steinwerder Anselm Goertz - IFAA Alfred Schmitz - IFAA TOA Partner Meeting September

More information

Heat Recovery Unit HERU. web-version

Heat Recovery Unit HERU. web-version Heat Recovery Unit HERU web-version HERU 50 and 75 Heat recovery unit HERU is designed to suit places like houses, offices and other buildings where there is a big demand for high temperature efficiency,

More information

Sound Performance Rating of Non-ducted Indoor Airconditioning

Sound Performance Rating of Non-ducted Indoor Airconditioning AHRI Standard 350 2015 Standard for Sound Performance Rating of Non-ducted Indoor Airconditioning and Heat Pump Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify

More information

Measuring Sound Pressure Level with APx

Measuring Sound Pressure Level with APx T E C H N O T E Application and Technical Support for Audio Precision Users TN113 Measuring Sound Pressure Level with APx By Joe Begin Introduction The level of acoustic noise or sound in the environment

More information

ROOFMASTER STEF-HT ROOF FAN

ROOFMASTER STEF-HT ROOF FAN fire safety Air movement Roof Fans ROOFMASTER STEF-HT ROOF FAN» Technical CATALOGuE Contents ROOFMASTER STEF-HT... 3 Performance Data... 4 Performance Table... 5 General description... 6 Fan Chart-explanation

More information

SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY

SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY PART A: CALCULATION METHODOLOGY FOR SOLAR WATER HEATERS AND HEAT PUMP WATER HEATERS WITH A VOLUMETRIC CAPACITY OF UP TO AND INCLUDING

More information

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEC exhaust FAN» Technical CATALOUGE Technical catalouge Exhaust Fan GLEC 2 Contents Exhaust fan - GLEC... 3 Performance Data...4 Fan chart-explanation and definitions...

More information

CASE STUDY. History. Testing Laboratories. GHSP Testing Laboratories A2LA Accredited Testing Laboratory. United States of America

CASE STUDY. History. Testing Laboratories. GHSP Testing Laboratories A2LA Accredited Testing Laboratory. United States of America CASE STUDY GHSP Testing Laboratories A2LA Accredited Testing Laboratory United States of America Automotive Components, NVH Consultancy PULSE, Sound Quality Software, Transducers GHSP is a world leader

More information

CNBOP-PIB Standard Fire Protection

CNBOP-PIB Standard Fire Protection Centrum Naukowo Badawcze Ochrony Przeciwpożarowej im. Józefa Tuliszkowskiego Państwowy Instytut Badawczy CNBOP-PIB-BA-01E:2014 Revision 1, February 2014 CNBOP-PIB Standard Fire Protection Laboratory Tests

More information

Handbook Qualification Quiet Room label

Handbook Qualification Quiet Room label Handbook Qualification Quiet Room label Version 1.0 2015 This publication is Copyright protected Content Contents 1 Introduction 5 Which sound levels must be determined? 5 What is the airborne sound insulation

More information

The Ed Roberts Campus Berkeley, CA

The Ed Roberts Campus Berkeley, CA The Ed Roberts Campus Berkeley, CA Anderson Clemenceau Mechanical Option Penn State A.E. Senior Thesis April 14, 2015 Leddy Maytum Stacy Architects, Photo by Tim Griffith ASHRAE Climate Zone 3C 99.6% Heating

More information

Installation, operation and maintenance guide for window models

Installation, operation and maintenance guide for window models Installation, operation and maintenance guide for window models Rev. 2014.06.25 Page 1 of 23 Table of content 2.0.0 GENERAL INFORMATION... 3 2.1.0 PREFACE... 3 2.2.0 AREAS OF USE... 3 2.3.0 INCORRECT USE...

More information

Daikin Altherma Selection Report

Daikin Altherma Selection Report Daikin Altherma Selection Report Produced on 20.10.2014 with Daikin Altherma Simulator V4.4.7 - database Central 9.7.9 Project name Energa Sistemi Reference Airabela Client name Energa Sistemi Revision

More information

CALIBRATION HOW IT WORKS

CALIBRATION HOW IT WORKS HIGH POWER SOLUTIONS POWER DETECTORS ENERGY DETECTORS At Gentec-EO, we understand that the essence of our business since over 45 years has been delivering accuracy. There are no half measures: it either

More information

> ENGLISH VERSION. Instructions HERU 50 HERU / utg 2

> ENGLISH VERSION. Instructions HERU 50 HERU / utg 2 > ENGLISH VERSION Instructions HERU 50 HERU 75 1270100/ utg 2 EC declaration of conformity (as defined by the Machinery Directive 98/37/EEC, appendix 2A) We hereby confirm that HERU 50 and HERU 75 comply

More information

Acoustics in open-plan offices A laboratory study

Acoustics in open-plan offices A laboratory study Acoustics in open-plan offices A laboratory study Petra Larm, Jukka Keränen, Riikka Helenius, Jarkko Hakala, Valtteri Hongisto Finnish Institute of Occupational Health, Lemminkäisenkatu 14-18 B, 20720

More information

Sound Performance Rating of Outdoor Unitary Equipment

Sound Performance Rating of Outdoor Unitary Equipment 2015 Standard for Sound Performance Rating of Outdoor Unitary Equipment AHRI Standard 270 WITH ADDENDUM 1, Sound Performance Rating of Outdoor Unitary Equipment March 2016 Note: This addendum is not ANSI

More information

Vibration tests on a TNAML Luminaire

Vibration tests on a TNAML Luminaire Sebert Trillingstechniek B.V. Report M13.001-P13.001 rev.01 Date 26 august 2013 Vibration tests on a TNAML Luminaire Client Technor Benelux B.V. Veersteeg 15 4212 LR Spijk The Netherlands Contact Person

More information

ISO 7183 INTERNATIONAL STANDARD. Compressed-air dryers Specifications and testing. Sécheurs à air comprimé Spécifications et essais

ISO 7183 INTERNATIONAL STANDARD. Compressed-air dryers Specifications and testing. Sécheurs à air comprimé Spécifications et essais INTERNATIONAL STANDARD ISO 7183 Second edition 2007-12-15 Compressed-air dryers Specifications and testing Sécheurs à air comprimé Spécifications et essais Reference number ISO 7183:2007(E) ISO 2007 PDF

More information

Specimen delivery date: Test date: Sampling: The test specimen sampled by customer. Order description N o 152/

Specimen delivery date: Test date: Sampling: The test specimen sampled by customer. Order description N o 152/ CONSTRUCTION OF KAUNAS UNIVERSITY OF TECHNOLOGY SCIENCE LABORATORY OF BUILDING THERMAL PHYSICS BANDYMAI ISO/IEC 17025 Nr. LA. 01.031 Date: 19 of November 2013 Page (pages) 1 (5) Test method: Specimen description:

More information

S TAR-ORION S OUTH D IAMOND P ROJECT E NVIRONMENTAL I MPACT S TATEMENT APPENDIX A FUNDAMENTALS OF ACOUSTICS

S TAR-ORION S OUTH D IAMOND P ROJECT E NVIRONMENTAL I MPACT S TATEMENT APPENDIX A FUNDAMENTALS OF ACOUSTICS APPENDIX 5.2.5-A FUNDAMENTALS OF ACOUSTICS Definition of Acoustical Terms Acoustics is the study of sound and noise is defined as unwanted sound. Airborne sound is a rapid fluctuation or oscillation of

More information

REPORT SUNDBYBERG KOMMUNHUS, MEASUREMENT OF SOUND PRESSURE LEVELS IN OPEN PLANE OFFICES STORKONOTOR

REPORT SUNDBYBERG KOMMUNHUS, MEASUREMENT OF SOUND PRESSURE LEVELS IN OPEN PLANE OFFICES STORKONOTOR REPORT SUNDBYBERG KOMMUNHUS, MEASUREMENT OF SOUND PRESSURE LEVELS IN OPEN PLANE OFFICES STORKONOTOR 2014-09-08 Project 253520, Sundbyberg, mätning av rumsakustiska parametrar enligt SS-EN 3382-3 Title:

More information

next DX.U.S* 052.Z2.H6.DC

next DX.U.S* 052.Z2.H6.DC next DX.U.S* 05.Z.H6.DC GENERAL CHARACTERISTICS Air conditioning unit with remote air cooled condenser, for computer rooms, any high-tech facility and offices. Units can run non-stop at 4x65 hours a year.

More information

Wayside horn noise investigation

Wayside horn noise investigation Wayside horn noise investigation Simon Moore AECOM, Level 28, 91 King William Road, Adelaide, Australia ABSTRACT Warning horns are used by trains and sounded when approaching a level to warn of its presence.

More information

CALIBRATION HOW IT WORKS

CALIBRATION HOW IT WORKS HIGH POWER SOLUTIONS POWER DETECTORS ENERGY DETECTORS At Gentec-EO, we understand that the essence of our business since 40 years has been delivering accuracy. There are no half measures: it either measures

More information

Air Conditioning. Technical Data. Ceiling suspended unit EEDEN AHQ-C

Air Conditioning. Technical Data. Ceiling suspended unit EEDEN AHQ-C Air Conditioning Technical Data Ceiling suspended unit EEDEN13-131 AHQ-C Indoor Unit AHQ-C TABLE OF CONTENTS AHQ-C 1 Features............................................................. 2 2 Specifications.......................................................

More information

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING Free cooling modules for 2 700V to 1100V POWER 1200V to 1800V Cooling capacity: 185 to 485 kw Cooling only Hydraulic module Free cooling ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY L'ENVIRONNEMENT

More information

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) www.blowtech.in we make air move Blowtech Air Devices Pvt. Ltd. was founded in 1988 and quickly established

More information

Krantz. Multifunction exposed ceiling AVACS. Cooling and heating systems

Krantz. Multifunction exposed ceiling AVACS. Cooling and heating systems Krantz Multifunction exposed ceiling AVACS Cooling and heating systems DS 4170 E 07.16 Preliminary remarks and construction design Preliminary remarks The multifunction exposed ceiling AVACS is designed

More information

EEDEN technical data ERHQ AA

EEDEN technical data ERHQ AA EEDEN08-70 technical data Altherma Outdoor units R-410A Altherma Outdoor units 34 1 Features 1 O u t d o o r u n i A l t h e r m a E R H Q 0 1 1-0 1 6 A A R - 4 1 0 A Cost effective alternative to a fossil

More information

Type approval testing of miscellaneous smoke and heat detectors for marine applications

Type approval testing of miscellaneous smoke and heat detectors for marine applications We help ideas meet the real world DELTA Test Report TEST Reg. no. 19 Type approval testing of miscellaneous smoke and heat detectors for marine applications Performed for Consilium Marine AB DANAK-199842

More information

Ceiling air diffuser INDULTHERM INDULTHERM-e

Ceiling air diffuser INDULTHERM INDULTHERM-e Technical Information Ceiling air diffuser INDULTHERM INDULTHERM-e Effective cooling and heating with a diffuser Thermomechanical or electrical switching Draught-free air distribution for cooling down

More information

WATER TO AIR DUCTABLE INDOOR HORIZONTAL HEAT PUMP

WATER TO AIR DUCTABLE INDOOR HORIZONTAL HEAT PUMP EVH R-407C WATER TO AIR DUCTABLE INDOOR HORIZONTAL HEAT PUMP Size Cooling Heating [kw] [kw] 7 2.0 1.9 11 2.6 2.5 15 3.9 3.3 5.2 5.5 25 7.3 6.7 31 8.9 8.4 41 10.7 9.8 REPLACE: BT02E009GB-01 The Versatemp

More information

Avicii 2014 Centennial Parklands, Sydney 25 th January 2014

Avicii 2014 Centennial Parklands, Sydney 25 th January 2014 Avicii 2014 Centennial Parklands, Sydney 25 th January 2014 Prepared for Centennial Parklands Centennial Park and Moore Park Trust by The P.A. People Pty Ltd A.C.N. 000 919 255 9 11 Leeds Street Rhodes

More information

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers Self-adjusting electronic control Cooling capacity: 35 to 700 kw 410A Cooling Operation DYNACIAT - DYNACIAT POWER

More information

MODEL: ACWD CEILING CONCEALED Chilled Water Fan Coils Unit

MODEL: ACWD CEILING CONCEALED Chilled Water Fan Coils Unit MODEL: ACW200D ACW300D ACW400D ACW500D ACW600D ACW800D ACW900D ACW1000D ACW1200D ACW1400D ACWD-2006 ACWD_2006_Cover.indd 1 CEILING CONCEALED Chilled Water Fan Coils Unit 2006-5-25 17:24:07 Contents Main

More information

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING Free cooling modules for 2 700V to 1100V POWER 1200V to 1800V Cooling capacity: 185 to 485 kw Cooling only Hydraulic module Free cooling ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY L'ENVIRONNEMENT

More information

Appendix 1 Reference HOB and boiler efficiency

Appendix 1 Reference HOB and boiler efficiency Appendix 1 Reference HOB and boiler efficiency 1. Methods and summary of researches Research on boilers has been conducted to identify reference HOB and set default values of energy efficiency for reference

More information

Do you want a versatile solution

Do you want a versatile solution Do you want a versatile solution to make significant savings? ESTIA TOSHIBA AIR CONDITIONING RESIDENTIAL HEATING AIR-TO-WATER HEAT PUMP ESTIA hatever you need ESTIA TO MAKE SIGNIFICANT SAVINGS Toshiba

More information

Test Report for the determination of Critical Fall Height for Under Playground Surfacing with Plants

Test Report for the determination of Critical Fall Height for Under Playground Surfacing with Plants Page: 1 of 6 ABN 36 062 949 973 20/109A Bonds Rd Punchbowl NSW 2196 Test Report for the determination of Critical Fall Height for Under Playground Surfacing with Plants Specification: Australian Standard

More information

PRODUCT DATA 2260 H, BZ Hand-held FFT System 2260 Investigator and FFT Software BZ7208 Type 2260 H

PRODUCT DATA 2260 H, BZ Hand-held FFT System 2260 Investigator and FFT Software BZ7208 Type 2260 H PRODUCT DATA Hand-held FFT System 2260 Investigator and FFT Software BZ7208 Type 2260 H With FFT Software BZ 7208, 2260 Investigator becomes a single-channel FFT analyzer. It is suitable for measuring

More information

DUST TEST REPORT. :Gold Apollo Co., Ltd. Company Model Name :A27. Date of Received :APR. 19, 2006 Date of Tested :APR. 19, 2006

DUST TEST REPORT. :Gold Apollo Co., Ltd. Company Model Name :A27. Date of Received :APR. 19, 2006 Date of Tested :APR. 19, 2006 Report No.:RA-S9504-0992 Reliability Engineering Division Page: 1 of 5 1F, No.22, Pu-ding Rd., Hsin - chu City, Taiwan, R.O.C. http://www.isti.com.tw Company Model Name :A27 DUST TEST REPORT :Gold Apollo

More information

CONDOR. Supply air ceiling QUICK FACTS

CONDOR. Supply air ceiling QUICK FACTS Supply air ceiling QUICK FACTS 00% flexible spread pattern High induction rate Can be cleaned Diffuser modules 595 x 595 mm Available in alternative colours VariZon air distribution system A I R F L O

More information

CERTIFICATE of Product Conformity (QAL1 )

CERTIFICATE of Product Conformity (QAL1 ) ATÜVRheinland`jR' Procis ly Right. CERTIFICATE of Product Conformity (QAL1 ) Certificate No.: 0000053816 AMs designation: Manufacturer: Test Laboratory: U3600-QALl for dust Auburn systems LLC S Electronics

More information

Determination of airborne sound insulation factor (designation of the test)

Determination of airborne sound insulation factor (designation of the test) Determination of airborne sound insulation factor (designation of the test) Test performed LST EN ISO 10140-2:2010 Acoustics. Laboratory measurement of sound insulation of building in accordance elements.

More information

INSPECTION REPORT Nr IDD/S-09/922

INSPECTION REPORT Nr IDD/S-09/922 Page: 1/7 PROJECT: TPI For Sheet Pile BV Client: Manufacturer: Nanjing Grand Steel Piling Co., Ltd. Inspection requested by: Ref: P/o nr: (client to BV) P/o nr: GP09111101 (client to Manufacturer) SUPPLY

More information

REPORT. Condensing air heaters. Technology evaluation. Project report Maj 2013

REPORT. Condensing air heaters. Technology evaluation. Project report Maj 2013 Condensing air heaters Technology evaluation Project report Maj 2013 REPORT Danish Gas Technology Centre Dr. Neergaards Vej 5B DK-2970 Hørsholm Tlf. +45 2016 9600 Fax +45 4516 11 99 www.dgc.dk Condensing

More information

CALIBRATION HOW IT WORKS

CALIBRATION HOW IT WORKS THZ DETECTORS PHOTO DETECTORS HIGH POWER DETECTORS POWER DETECTORS ENERGY DETECTORS MONITORS At Gentec-EO, we understand that the essence of our business since 40 years has been delivering accuracy. There

More information

ISO INTERNATIONAL STANDARD. Acoustics Measurement of sound pressure level from service equipment in buildings Engineering method

ISO INTERNATIONAL STANDARD. Acoustics Measurement of sound pressure level from service equipment in buildings Engineering method INTERNATIONAL STANDARD ISO 16032 First edition 2004-09-15 Acoustics Measurement of sound pressure level from service equipment in buildings Engineering method Acoustique Mesurage du niveau de pression

More information

HOTEL CHILLED BEAM IQ STAR SILENCIA

HOTEL CHILLED BEAM IQ STAR SILENCIA HOTEL CHILLED BEAM IQ STAR SILENCIA TECHNICAL CATALOGUE 2 IQ Star Silencia Hotel Chilled beam - Technical catalogue IQ STAR SILENCIA HOTEL CHILLED BEAM Silencia unit is designed for use in hotel bedrooms,

More information

This document is a preview generated by EVS

This document is a preview generated by EVS IEC 60942 Edition 4.0 2017-11 REDLINE VERSION colour inside Electroacoustics Sound calibrators IEC 60942:2017-11 RLV(en) THIS PUBLICATION IS COPYRIGHT PROTECTED Copyright 2017 IEC, Geneva, Switzerland

More information

European Technical Assessment ETA 17/1007 of 02/05/2018

European Technical Assessment ETA 17/1007 of 02/05/2018 RISE Research Institutes of Sweden AB RISE Certifiering Box 553 SE-371 23 Karlskrona Sweden Member of www.eota.eu Tel: +46 10 516 63 00 Web: www.ri.se/eta Mail: certifiering@ri.se European Technical Assessment

More information

E/ECE/324/Rev.1/Add.27/Amend.5 E/ECE/TRANS/505/Rev.1/Add.27/Amend.5

E/ECE/324/Rev.1/Add.27/Amend.5 E/ECE/TRANS/505/Rev.1/Add.27/Amend.5 7 February 2018 Agreement Concerning the Adoption of Harmonized Technical United Nations Regulations for Wheeled Vehicles, Equipment and Parts which can be Fitted and/or be Used on Wheeled Vehicles and

More information

PRODUCT CONFORMITY CERTIFICATE

PRODUCT CONFORMITY CERTIFICATE PRODUCT CONFORMITY CERTIFICATE This is to certify that the V-CEM5100 Flow Monitor Manufactured by: Codel International Ltd, Station Road Bakewell Great Britain Has been assessed by Sira Certification Service

More information

Refrigerating Appliance ErP Test Report

Refrigerating Appliance ErP Test Report Report Number Test Laboratory Name / Address Applicant Name / Address Manufacturing Name / Address Product Brand Name Description Model(s) (if applicable) Model Similarity Ratings Date of receipt of sample(s)

More information

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems . Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems PRESENTED BY NIRAJ MISTRY aircon@stroma.com Cooling Load The Refrigeration Load Cooling load on refrigeration system

More information

Sunlight Supply, Inc.

Sunlight Supply, Inc. FCC Part 18 Subpart C Consumer For RF Lighting Equipment Electromagnetic Compatibility Test Report Sunlight Supply, Inc. December 19, 2017 Tests Conducted by:, LLC 20811 NW Cornell Road, Suite 600, Hillsboro,

More information

Acoustic Verification Report

Acoustic Verification Report Acoustic Verification Report Invacare XPO 2 Portable Oxygen Concentrator Type XPO100B-EU for Date: 2013-12-10 Our reference: IS-ATC2-MUC/js Document: Report Invacare VR.600010074.002.12 - Revision 2.docx

More information

TEST REPORT: CHM14-05-CHY

TEST REPORT: CHM14-05-CHY A TEST REPORT: 7191100863-CHM14-05-CHY Date: Tel: +65 68851291 Fax: +65 67784301 Client s Ref: Email: huayi.chen@tuv-sud-psb.sg Note: This report is issued subject to the Testing and Certification Regulations

More information

INSTRUMENTATION FOR MARINE BLACK CARBON MEASUREMENTS

INSTRUMENTATION FOR MARINE BLACK CARBON MEASUREMENTS INSTRUMENTATION FOR MARINE BLACK CARBON MEASUREMENTS Workshop on Marine Black Carbon Emissions, Ottawa, 9-10 th of September 2014 1 Outline IMO Measurement Methods and Definitions for Black Carbon Selectivity

More information

Compact and silent Scroll compressors All-season operation

Compact and silent Scroll compressors All-season operation Compact and silent Scroll compressors All-season operation Cooling capacity: 40 to 161 kw 410a Cooling only Use The new generation of CONDENCIAT condensation units is the solution for all split-system

More information

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB R407C EASY_R Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans 5,2 41,5 kw T_ESY_R_0508_GB EASY_R R407C INDEX WORKING LIMITS... 3 SERIES IDENTIFICATION... 4 MODEL

More information

draft dated 9/17/2015 page 1

draft dated 9/17/2015 page 1 247-32 Glare, noise, odor and other nuisances B. Noise 1. Intent Town of Pendleton The Pendleton Town Board determines that the creation of unreasonable noise within the Town limits of Pendleton is detrimental

More information

Lawnmowers, pedestrian controlled (combustion engine powered)

Lawnmowers, pedestrian controlled (combustion engine powered) Compliance Guide Rev.1, 09/2016 Lawnmowers, pedestrian controlled (combustion engine powered) European Garden Machinery Federation EGMF Bd Reyers 80, 1030 Brussels, Belgium secretariat@egmf.org +32 2 206

More information

Ceiling Concealed High Volume Chilled Water Fan Coil Unit (50/60Hz)

Ceiling Concealed High Volume Chilled Water Fan Coil Unit (50/60Hz) Technical Manual Ceiling Concealed High Volume Chilled Water Fan Coil Unit (50/60Hz) Models: MCW1400 MCW1600 Air Flow: 2270-3020m3/h MCW1800 Engineered for flexibility and performance. TM MCW-C/F(High

More information

GLOSSARY OF ACOUSTICAL TERMS

GLOSSARY OF ACOUSTICAL TERMS GLOSSARY OF ACOUSTICAL TERMS Abnormal noise events Noises that are sufficiently infrequent as to be uncharacteristic of an area or that occur so close to the microphone as to dominate the measurements

More information

ISO INTERNATIONAL STANDARD. Acoustics Guidelines for noise control by silencers

ISO INTERNATIONAL STANDARD. Acoustics Guidelines for noise control by silencers INTERNATIONAL STANDARD ISO 14163 First edition 1998-10-15 Acoustics Guidelines for noise control by silencers Acoustique Lignes directrices pour la réduction du bruit au moyen de silencieux A Reference

More information

Listen Out 2016 Centennial Parklands, Sydney 1 st October 2016

Listen Out 2016 Centennial Parklands, Sydney 1 st October 2016 Final Environmental Noise Report Listen Out 2016 Centennial Parklands, Sydney 1 st October 2016 Prepared for Botanic Gardens & Centennial Parklands by The P.A. People Pty Ltd A.C.N. 000 919 255 9 11 Leeds

More information