7706-ULF Integrated Fire Monitoring System. Installation, Operation & Programming Manual

Size: px
Start display at page:

Download "7706-ULF Integrated Fire Monitoring System. Installation, Operation & Programming Manual"

Transcription

1 7706-ULF Integrated Fire Monitoring System Installation, Operation & Programming Manual AES Corporation 285 Newbury Street Peabody, MA USA Tel (978) Fax (978) Copyright 2015 All Rights Reserved

2 ULF Conventional Fire Monitoring System OWNER WARRANTY AES CORPORATION LIMITED PRODUCT WARRANTY AND TECHNOLOGY LICENSE LIMITED PRODUCT WARRANTY: AES Corporation ( AES ) warrants to the original purchaser that each AES Subscriber Product will be free from defects in material and workmanship for three (3) years from date of purchase and all other products purchased from AES including central station receivers and accessories will be warranted for one (1) year from the date of purchase. At no cost to the original purchaser for parts or labor, AES will repair or replace any AES Product or any, part or parts thereof which are judged defective under the terms of this Warranty. Defective AES Products must be returned to AES directly, provided they are properly packed, postage prepaid. Or exchange may be made through any authorized direct factory representative for any AES Products that are judged defective under the terms of this Warranty. Improper or incorrectly performed maintenance or repair voids this Warranty. This Warranty does not cover replacement parts that are not approved by AES. This Warranty does not apply to any AES Product or any part thereof that has been altered in any way to affect its stability or reliability, or that has been subjected to abuse, misuse, negligence, accident or act of God, or that has had the serial number effaced or removed. Certain AES Products are designed to operate and communicate with other specified AES Products and certain other specified products, systems or networks authorized or approved by AES, as identified in the applicable AES Product instructions. This Warranty does not apply to any AES Product that is used with any unauthorized or unapproved products, systems or networks, or that has been installed, applied or used in any manner, other than in strict accordance with AES instructions. AES makes no warranty, express or implied, other than what is expressly stated in this Warranty. If the law of your state provides that an implied warranty of merchantability, or an implied warranty of fitness for particular purpose, or any other implied warranty, applies to AES, then any such implied warranty is limited to the duration of this Warranty. AES cannot be aware of and is not responsible for the differing values of any property to be protected by its alarm reporting systems. This Warranty does not cover and AES shall not be liable for any defect, incidental or consequential, loss or damage arising out of the failure of any AES Product to operate. Some states do not allow the exclusion or limitation of the durations of implied warranties or the limitation on incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights and you may also have other rights that vary from state to state. TECHNOLOGY LICENSE: Certain AES Products include software, protocols and other proprietary and confidential technology and trade secrets of AES which are incorporated in or provided with AES Products solely for use in conjunction with and in order to operate AES Products ( Licensed Technology ). AES grants the original purchaser a non-exclusive license to use such Licensed Technology solely in connection with the use and operation of AES Products and for no other purpose or use whatsoever. No title or ownership in or to any such Licensed Technology is conveyed by the sale or delivery of any AES Products; all such rights are retained by AES. AES SERVICE PROCEDURE: Contact AES by phone (978) , fax (978) or (rma@aes-intellinet.com) to receive a Return Material Authorization Number. Have the AES part number and serial number ready. Repack equipment in original or equivalent packaging. Inside the box, please include a contact name, telephone number, address and a brief description of the reason for return. Ship items freight-prepaid to: Repair Services, RMA# AES Corporation 285 Newbury Street Peabody, MA USA (Contact AES for Return Material Authorization number.)

3 7706-ULF Integrated Fire Monitoring System 3 Table of Contents 1. Introduction Purpose of This Manual...7 System Overview...7 Communication Path Configuration...8 System Features...9 P-Link Accessories...10 How to Use this Manual...10 Common Terminology...10 Installation Tasks Overview Before You Start Installation System Specifications...12 Cabinet Description...12 Visual Indicators...12 LCD Description...12 Environmental Specifications...12 Model/Available Cabinet Colors...12 System Configurations/Appliances...13 Electrical Specifications...13 System Size Specifications...13 Mainboard Wiring Specifications...14 Circuit Separation...14 Wiring Types...14 Cabinet Dimensions Subscriber Antenna Planning and Installation Antenna Safety Considerations...17 Coaxial Cable Options...18 Coaxial Cable and Antenna Installation Tips...19 Transceiver Antenna...19 Antenna Grounding and Surge Protector Cabinet Mounting Subscriber and Mainboard Mounting and Wiring Instructions Cabinet Wiring Connections...26 Battery Circuit Calculations...27 Battery Calculation Worksheet...27 Main Supply Circuit...28 Battery Connections...28

4 ULF Integrated Fire Monitoring System 5. Control Panel Installation Input Circuits...29 Input Wiring Specifications...29 Input Circuit #1 Class A, Style D Wiring Configuration...30 Input Circuits #1-6 Class B, Style B Wiring Configuration...31 Notification Appliance Circuits Installation...32 NAC Wiring Characteristics...32 NAC Maximum Wiring Impedance Formula...33 NAC Wiring Configuration...33 P-Link Points...34 Configuration Characteristics...34 Maximum Wire Resistance Formula (Wire Length)...34 P-Link Addresses...35 Remote Annunciators Installation (RA-6075)...35 Setting Addresses...35 Auxiliary Power...36 Auxiliary Power Characteristics Control Panel Operation Control Panel Basic Operation...37 LCD Display...38 Menu Navigation Keys...38 Numeric Keypad...39 Function Keys...39 Status LEDs...40 Control Panel Menu Tree Subscriber Specifications Features...42 Optional Accessories...42 Subscriber Technical Specifications...42 Subscriber Local Trouble Output...42 Subscriber Programming...42 ID # and System Cipher Code...44 Timing Parameters...46 Modes...47 Time to Live...48 Account Override...50 User Codes...51 Report Account...52

5 7706-ULF Integrated Fire Monitoring System 5 Default PIC...53 Local Status Check (PIC Status)...54 Display Route Table...56 Self-Test Error Codes Status Error Codes...57 Status Indicators and Subscriber Reset Button Control Panel Programming Programming Options...60 Programming Overview...62 The Programming Cycle...62 Software Installation...63 LEARN Programming...63 Connecting the Computer and Panel...64 Connecting a Computer to the Panel via a Network...64 Transferring Data...66 Uploading from Panel to Computer...68 Downloading Configuration File to Panel...70 Enable Remote Access...70 File New...70 File Save / Save As...71 Audit Errors...72 Downloading a Configuration File...72 Uploading History Events Status Reports...73 History Reports...73 Printing Reports...75 Panel Software Overview...77 Window Regions / Areas...77 Program Icons...78 Programming Functions Overview...79 Remote Access Code...80 User Name / Password...80 General System Functions...81 Job Details...81 System Functions...82 P-Link Notification Requirements...83 Connecting the Panel to a Network Report Programming Sent from Panel Report Requested from PC...86

6 ULF Integrated Fire Monitoring System Receiving Status Reports...88 Creating Reminders...90 System Programming...91 Mapping Zones Overview...91 Single Zones...91 Multiple Zones...92 Mapping Terminology...93 Zone Types / Styles...93 Zone Attributes...94 Creating Zones...95 Configuring Zones...96 Configuring Points...97 Input Circuit Functions...97 NAC Functions...98 AUX Functions...98 Adding Points to Zones Group by Area Programming Points and Appliances Reporting Accounts Remote Annunciators Verify Input and Output Points Examine Firmware Versions LCD Control Firmware F Subscriber Firmware Mainboard and 7764 PIC Firmware A. Basic Operating Instructions B. System Maintenance and Testing C. Device Compatibilities D. Compatible Smoke Detectors Table E. Compatible Auxiliary Circuit Devices F. Control Panel Menu G. Verifying 7764 PIC Operation and Troubleshooting Steps H. PFC-6006 NAC Compatibility List

7 7706-ULF Integrated Fire Monitoring System 7 Section 1. Introduction The 7706-ULF Integrated Fire Monitoring System is a compact, simple panel designed to monitor all facets of a wet or dry fire sprinkler system and communicate the status to a monitoring station. The 7706-ULF System is a listed and approved microprocessor-based sprinkler monitoring panel and complies with UL-864, NFPA-70, and NFPA-72. The panel is provided with six (6) inputs and with one 24 VDC, 0.5A Notification Appliance Circuit (NAC) with strobe synchronization. The 2.0A power supply provides ample power to meet any jurisdictions requirements and will house and charge up to two (2) 18A/hour batteries. In addition, the panel has the Potter P-Link for connection to a remote annunciator. Purpose of This Manual This manual is intended to assist in installing and programming the 7706-ULF Integrated Fire Monitoring System. Refer to this manual to properly install and program the 7706-ULF System. It is recommended that the user follow the procedures as outlined in this manual to assist in the proper installation of, and prevent damage to, the control panel and associated equipment. System Overview The 7706-ULF Integrated Fire Monitoring System is designed for use as a sprinkler fire control panel for life safety applications. The system must be used with an AES-IntelliNet system, a two-way data radio network (see Figure 2), as alarm, supervisory, and trouble messages generated by the 7706-ULF system are transmitted to the AES- IntelliNet system's central receiver. The main components of the 7706-ULF System include a mainboard, an interface card, and a subscriber unit (see Figure 1). The 7706-ULF System is a single enclosure located at the protected premise. Data messages from the control panel (mainboard) are transferred through the AES 7764 Potter Interface Card (PIC) to the subscriber. Power 120V AC PFC-6006 Mainboard Backup Battery NAC Circuit Input Circuits AUX Power P-Link Bus Power Data 7764 Potter Interface Card Data Power 7706-ULF 7788F RF Subscriber D RA-6075 Remote Annunciator Figure ULF System Components The subscriber transfers the data messages to the AES RF mesh network as shown in Figure 2. The mesh network consists of a group of subscribers that provide a path for transmitting messages from the 7706-ULF System to the 7705i MultiNet central receiver. Subscribers in the mesh network automatically establish a path to the central receiver. The configuration is dynamic, so a path will be re-established if a subscriber in the route fails to function. Messages are passed between subscribers in a repeater fashion, allowing subscribers out of direct radio range to communicate with the central receiver.

8 ULF Integrated Fire Monitoring System Messages in the RF mesh network are passed between subscribers until received at the AES 7170 IP-Link. The 7170 IP-Link functions as a gateway between the AES RF mesh network and a TCP/IP network connection to the central receiver through direct Ethernet connection, LAN, WAN, or Internet. Messages terminate at the 7705i AES-MultiNet receiver. The receiver is capable of either sending the messages to automation software, displaying them on the receiver front panel LCD display, or printing them to the attached printer. AES RF Mesh Network 7170 IP-Link 7706-ULF Internet WAN/LAN D i MultiNet Central Receiver Figure 2. AES Intellinet System Diagram Communication Path Configuration The 7706-ULF Integrated Fire Monitoring System is designed to communicate with the 7705i MultiNet using the AES mesh radio network, eliminating the need for POTS telephone lines. The communication path is provided by the 7788F RF Subscriber which communicates via the mesh radio network. Alarm, trouble, and supervisory messages are delivered to automation as shown below when the 7706-ULF Integrated Fire Monitoring System is installed and configured according to installation instructions.

9 7706-ULF Integrated Fire Monitoring System 9 AES Radio Network PFC-6006 Mainboard 7764 Potter Interface Card 7788F RF Subscriber 7706-ULF 7170 IP Link D i MultiNet Automation Figure ULF Communication Path Overview System Features y Six (6) Programmable Input Circuits y One (1) Notification Appliance Circuit (NAC) rated at 0.5A maximum: Power Limited Built-in Sync Cadence and Temporal Patterns Programmable as Supervisory y Support for all major synchronization patterns: Potter/AMSECO Gentex CooperWheelock System Sensor y Auto Silence and Silence Inhibit y Built-in Ethernet Port (for programming and network connectivity) y P-Link RS-485 Bus (for system accessory support) y Dead-Front Cabinet Design

10 ULF Integrated Fire Monitoring System P-Link Accessories y Maximum of one (1) RA-6075 remote annunciator per system How to Use this Manual Refer to this manual before contacting Technical Support. The information in this manual is the key to a successful installation and will assist you in understanding proper wire routing, system requirements, and other guidelines specific to the 7706-ULF Integrated Fire Monitoring System y "Subscriber Programming" on page 42 contains instructions for configuring the AES radio subscriber used by the control panel to communicate with central monitoring stations. y "Section 8. Control Panel Programming" on page 60 contains instructions for configuration and operation of the fire alarm control panel. Common Terminology The following table provides you with a list of terms and definitions used with the PFC-6006 system: Term 7706-ULF Cabinet EOLR Remote Annunciator NAC P-Link PIC PFC-6006 Mainboard Subscriber Enclosure Table 1: Terminology End of Line Resistor Assembly LCD-type Remote Annunciator Notification Appliance Circuit Definition Proprietary RS-485 Communication Bus AES 7764 Potter Interface Card PCB Board Assembly containing LCD, keypad, terminal blocks, and alarm circuitry AES RF subscriber consisting of AES 7788F, 7764 PIC, and 7085UE5 transceiver Installation Tasks Overview Table 2 lists tasks to perform when installing the AES 7706-ULF Integrated Fire Monitoring System. Use the list to verify that installation tasks have been identified and completed. Tasks do not have to be performed in the order listed unless specifically identified. Important! Verify AES mesh network connectivity for the control cabinet before cabinet installation.

11 7706-ULF Integrated Fire Monitoring System 11 Table 2: Installation Tasks Page Control Cabinet Installation Tasks Reference Network Connectivity: Cabinet location and connectivity to AES mesh network 17 Select Antenna: Network connectivity and ability to mount on cabinet External Antenna: Safety, grounding, and surge Protection requirements 20 Environmental: Mounting location conditions meet Environmental Specifications 12 Mount Control Cabinet: Flush surface/recessed mount General cabinet wiring: Power limited/non-limited spacing requirements Subscriber Wiring: 7788F subscriber to 7764 PIC card wiring PIC P-Link address: Verification of DIP switch address Mainboard wiring: Mainboard to 7764 PIC card wiring 23 Input Circuit install: Connection of compatible listed devices and detectors NAC Circuit install: Connection of compatible listed strobe/horn/module appliances 32 Remote Annunciator Set P-Link address 35 Wiring - connect single remote annunciator 34 Connect AC main power 28 Connect batteries (usually the final step) F Subscriber Configuration Tasks Control Panel Operation: Using LCD/keypad for panel 37 Control Panel Menu Tree: LCD/keypad to change programmable settings/view info 41 Subscriber Programming Parameters: ID # and System Cipher Code 44 Timers: Checkin, NTR RPT DLY, Comm Timeout 46 Modes: Enable/Disable Repeating 47 Time to Live: Checkin, Alarm, Trouble, Restoral, Intellitap, Special 48 Account Override: Enable/Disable 50 User Codes: Enable/Disable 51 Report Account 52 Subscriber Self-Test: Power on self-test 57 Subscriber Network Status: LED for visual network connect status; LCD for messages 59 Subscriber Reset: Replace existing setting with factory default settings 53 Control Panel Programming Tasks System Software Configuration LEARN programming: Detect remote annunciator connection 63 Computer connection 64 Control Panel System Programming Zone type, Style, Attributes Programming Points & Appliances 105 Configuration file upload/download 68

12 ULF Integrated Fire Monitoring System Table 2: Installation Tasks Verify Input and Output Points 106 Examine Firmware Versions 107 Post Install Test 110 Section 2. Before You Start Installation This section addresses information that will help you in completing a successful installation such as the 7706-ULF cabinet layout, specifications, and environmental considerations. System Specifications Cabinet Description y Eighteen (18) gauge sheet steel with hinged, removable locked door y Enclosure dimensions 18-1/2" 14-1/4" 4-3/4" Visual Indicators y LCD (2 16 alphanumeric character display) y Mainboard LED indicators (red, green, amber) y Subscriber LED indicators (red, green, amber) y PIC LED indicators (green - viewable by installer only) LCD Description y Displays alarm, supervisory and trouble conditions, status and circuit for each correlating condition. Also displays subscriber configuration and status information. Environmental Specifications y Mount indoors only. y Temperature: 32 to 120 F, humidity: 93% non-condensing. y Verify panel is properly grounded. y Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides, bottom, or rear of the cabinet. Verify that they will not interfere with the batteries or other components. y The panel and system must be tested and maintained in accordance with all local and national codes and ordinances. y Panel shall be installed so that the display is easily readable and the door has adequate clearance to access the controls. Model/Available Cabinet Colors y 7706-ULF Integrated Fire Monitoring System Red

13 7706-ULF Integrated Fire Monitoring System 13 System Configurations/Appliances Table 3: System Configurations / Appliances Model Description Local Remote Station Central Station 7788F Subscriber Y Y Y Y PFC-6006 Mainboard/Panel Assembly Y Y Y Y RA-6075 LCD Remote Annunciator (UL) O O O O End of Line Resistor Assembly Y Y Y Y Y = Yes, required for applicable section N = No, not required for applicable section O = Optional, may or may not be used, has no affect on the applicable section. Electrical Specifications Please refer to the table below for electrical specifications: Table 4: System Panel Electrical Specifications Low Voltage Power Limited Circuit Panel - PFC 6006 Rating per Circuit NAC 0.5A B Conv. Input 1 2.5mA Normal Standby B Conv. Inputs 2, 3, 4, 5 & 6 2.5mA Normal Standby B Class Proprietary System Size Specifications Please refer to the table below for system size specifications: Accessories/Subassemblies PFC-6006 Table 5: System Size Specifications Maximum System Size Six (6) input circuits on the mainboard One (1) notification circuit on the mainboard One (1) P-Link connection* Auxiliary power output** *P-Link 24 VDC and auxiliary power combined are not to exceed 0.5A. P-Link is factory-wired with the option for additional field wiring of one (1) remote annunciator. **Auxiliary power output is dedicated and unavailable for external accessory use.

14 ULF Integrated Fire Monitoring System Mainboard Wiring Specifications There are several wiring requirements to consider before connecting circuits to the mainboard: (1) the circuit separation and (2) wiring types. All wiring should be sized and installed to comply with NFPA-70, NFPA-72, and local codes and ordinances. Circuit Separation Proper separation between the different types of circuits must be maintained between Power Limited, Non-Power Limited, and High Voltage wiring to reduce electrical interferences, transient voltage, or voltage ratings. Separations between the different wiring types must be maintained by at least ¼ inch and the wire insulation must be for the higher voltage. The control panel cabinet has sufficient knockouts located around the periphery allowing the installer to maintain separation between power limited and non-power limited connections. Wiring Types Wiring specifications must be followed to prevent damage or other consequences. Please refer to the wiring diagram in Figure 4 for proper wiring requirements.

15 7706-ULF Integrated Fire Monitoring System 15 Wire Routing for 7706-ULF (*Shown with false front removed) 1 Line2 In Line2 Out Line1 In Line1 Out F U SE Tip Ring Tip Ring Tip Ring Tip Ring FUSE A B A- A+ B- B BATTERY NAC AUX PLINK INPUT1 INPUT2 INPUT3 INPUT4 INPUT5 INPUT Power Inputs 3 DWG # Route all other wiring away from power input wiring. 2 Battery leads NOTICE Figure ULF Wire Routing Example

16 ULF Integrated Fire Monitoring System Refer to Table 6 below for a breakout of the different wiring requirements shown by circuit type: Table 6: Wiring Types Mainboard Circuit Voltage Power AC Connection High Voltage Non-Power Limited Battery Connection Low Voltage Non-Power Limited Input Circuits Low Voltage Power Limited Notification Device Circuit (NAC) Low Voltage Power Limited P-Link RS-485 Connections Low Voltage Power Limited AUX Power Low Voltage Power Limited 7788F/7764 Circuit Voltage Power Zone Input Low Voltage Power Limited Trouble Relay Low Voltage Power Limited DC Input Connection (battery leads) Low Voltage Power Limited Cabinet Dimensions Mounting Screws Figure 5. PFC-6006 Mainboard Module Shown Installed in Cabinet (shown with door removed)

17 7706-ULF Integrated Fire Monitoring System /4 (4) #6-32 X 1/4 MACHINE SCREWS AND NUTS 18 1/2 OPTIONAL TRIM DWG# Figure ULF Panel Showing Bezel Dimensions Section 3. Subscriber Antenna Planning and Installation Important! A UL fire compliant fire alarm installation for the 7706-ULF System needs to be in a location that has a NetCon of 5. Refer to "Table 12: PIC Menu Screen Displays" on page 55 for additional details. It is important to verify that a location is suitable before deciding on the antenna used and mounting the cabinet. A check of the location can be done with the AES Network Connectivity Tool (NCT). The AES NCT provides a quick means for verifying NetCon or finding suitable locations for installation. A tamper resistant rubber duck flexible antenna is part of the standard package for the 7706-ULF System and mounts on top of the steel cabinet. Depending on cabinet mounting, physical location, and mesh network connectivity, a remotely mounted antenna may be required. Antenna Safety Considerations Following is a list of important considerations as well as information on antenna and coaxial cable accessories available from AES. y If the antenna or cables connected to this equipment come in contact with electrical power lines, DEATH or SERIOUS INJURY may result. y It is unlawful to operate this equipment in the United States without a valid FCC radio station license. Other countries most likely require licensing through appropriate authorities as well.

18 ULF Integrated Fire Monitoring System y All equipment must be installed in accordance with National Electric Code, NFPA -70, National Fire Code NFPA-72 and local building codes. y Be certain to properly ground the antenna, enclosure and any surge protection devices to help dissipate surges away from the equipment and personnel. The grounding of the antenna and surge protector is for your safety and the safety of your equipment and should not be neglected. UHF antenna options are listed in Table 7. The frequency range is MHz. Contact factory at (800) or info@aes-intellinet.com for other frequencies. Table 7: UHF Antenna Options Antenna db Construction Usage Length P/N Notes 2.5-dB Case Top Flex Tamper Resistant Vinyl Clad Indoor 11 in , 2 3-dB Stealth Vinyl Clad Indoor 1.5 ft dB Standard Gain Steel Mast Indoor 1.5 ft UM 4, 5 5-dB High Gain Steel Mast Indoor 3 ft UM 4, 5 6-dB Rugged High Gain Fiberglass Mast In/Outdoor 4.5 ft UC 4 7-dB Rugged Higher Gain Fiberglass Mast In/Outdoor 6 ft US 4 9-dB Central Station High Gain Fiberglass Mast In/Outdoor 8 ft UC 4 Notes: 1. These alternate antennas may be used with the 7706-ULF Integrated Fire Monitoring System. 2. Included standard tamper-resistant antenna mounts on alarm unit s enclosure (includes cable). 3. Mounts in attics, vents, walls, behind drapes, etc. (includes 10-foot cable). 4. Requires coaxial cable. Usually requires user-supplied mounting hardware such as a pole with mounting brackets/hardware. 5. Antenna is intended for outdoor use. Supplied mount is intended for indoor use, as coaxial connection is exposed. To use outdoors, connection must be sealed with a suitable product such as a self-fusing tape to protect against moisture. The antenna must be installed in accordance with the National Electric Code and local electric code. NFPA-72 requires antenna cables to be protected in conduit. A surge protector must be installed in line with any type of remotely installed antenna. Refer to Remote Antenna Diagram in the Installation section for installation details. Coaxial Cable Options y Cables with connectors, BNC N, for all AES subscriber units, high performance, low-loss cables for all -UM, -UC and -US antennas above. y 10-foot RG-58 cable, Part No N. y 25-foot RG-58 cable, Part No N. y BNC plug/connector (male), crimp style for RG-58 coaxial, Part No

19 7706-ULF Integrated Fire Monitoring System 19 y 100-foot RG-8 W/1 N male (on spool), Part No (this coaxial cable is available for longer runs, cut to length and installer terminated). y Loose connectors required to complete RG-8 assembly, Part No y Crimp tool required for , Part No y Cable assembly; 18 RG-58 (N female, bulkhead BNC male) (used to connect RG-8 with N male to enclosure body), Part No Coaxial Cable and Antenna Installation Tips y Avoid using 25-foot coaxial cable length if a 10-foot length will be sufficient. y Never use more than 25 feet of RG-58 cable in any antenna installation. y Always use shortest length of coaxial cable possible. Longer than necessary coaxial cable lengths translate into greater signal loss. y Always use the straightest most direct routing possible in any coaxial cable installation. Unnecessary and tight bends add to potential signal loss. y Use 50-ohm impedance coaxial cable only. Do not use 75-ohm coaxial cable for the connection of remote antenna. RG-8, 9913, LMR-400, LMR-600, and RG-58 are among a list of acceptable 50-ohm coaxial cables. y RG-59 and RG-6 are 75-ohm coaxial cables and are NOT to be used. y Use the proper coaxial connectors and crimp tool for the coaxial selected. Incorrect or poorly installed connectors can have a significant effect on the performance of the RF. Transceiver Antenna y The supplied case top tamper resistant flexible 2.5 db antenna is mounted on the enclosure as shown in "Figure 7. Grounding and Surge Protector for Transceiver with Remote Antenna Installation" on page 20. y A separately purchased remote antenna may be used with the 7706-UL unit in UL installations. Contact AES at (800) or info@aes-intellinet.com for a selection of antennas suitable for use with your subscriber unit. Refer to "Table 7: UHF Antenna Options" on page 18 for information on antennas available from AES. y NFPA requires that coaxial cable to antenna be protected in conduit. y Mount antenna as high as possible, on or in the structure, with attics and rooftop locations preferred. Height need not be higher than is required to overcome nearby obstructions to the signal path if any additional height would use a longer coaxial cable length. Coaxial cable to antenna must be protected in conduit. y A remote antenna should be mounted in a location near the transceiver to minimize inherent signal loss due to unnecessary cable length. Do not use longer coaxial cable than is needed to reach the antenna. y Avoid installing the antenna in close proximity to other metal surfaces which may severely impact the performance of the radio communications due to the effects of signal reflections or detuning the antenna. Remember that pipes, conduit, wiring, ductwork, and other metal are commonly installed within walls and could affect antenna performance. Take into account foil-backed insulation and wallpaper. Metal objects may also be located in adjacent rooms or above ceilings. Metallic framing is in common use today. Antenna should not be mounted directly over, or in close proximity to, metal studding. Metallic supports are in common use today. Antenna should not be mounted in ceilings constructed of metal beams and supports that may interfere with the RF signal.

20 ULF Integrated Fire Monitoring System The antenna must be grounded properly to help reduce damage due to surges produced by lightning. Grounding must be done in accordance with local building codes as well as those in accordance with any other authority having jurisdiction. When needed, use higher gain antenna with rated cable and connectors. Mount antenna as high as possible. Attics that meet the temperature and humidity range specification can help to improve performance. See the UHF antenna options in "Table 7: UHF Antenna Options" on page 18 for available and approved options. y Antenna must be mounted in a vertical orientation. y Avoid tightly coiled or bunched coaxial cable, as this could also affect RF performance. Use coaxial cable length that best fits the installation. y The antenna must be installed in accordance with National Electric Code and local electric code. y A protective surge suppressor must be installed in line with any type of remotely installed antenna. Antenna Grounding and Surge Protector Figure 7 shows the grounding and surge protector for the transceiver with a remote antenna installation. Note that the coaxial cable must be protected in conduit. Remote Omni Directional Antenna RF Transceiver Coax Cable In Conduit Surge Protector D ai Earth Ground Figure 7. Grounding and Surge Protector for Transceiver with Remote Antenna Installation

21 7706-ULF Integrated Fire Monitoring System 21 Section 4. Cabinet Mounting Subscriber and Mainboard Mounting and Wiring Instructions To mount the cabinet: Important! The 7706-ULF System needs to be in a location that allows the subscriber to connect to the AES mesh network. It is important to verify that a location is suitable before deciding where the cabinet is mounted. A check of the location can be done with the AES Network Connectivity Tool (NCT). The AES NCT provides a quick means for verifying or finding suitable locations for installation. 1. Select a convenient location, approximately 5 feet from the floor, where it will be accessible for testing and servicing. Note: The system is supplied from the factory with the subscriber components mounted to the subscriber mounting and installed in the cabinet. The subscriber mounting plate must be removed before installing the cabinet. 2. Remove the panel motherboard from the cabinet by removing two screws mounting the black dead-front bezel, removing the bezel, and then removing the two screws mounting the panel motherboard. 3. Remove the two screws holding the mounting plate to the cabinet. See Figure 8 for screw location labeled mounting plate standoff. Lift the mounting plate upwards, approximately 1/2", in order to clear the crossbeam of the cabinet on which the mounting plate rests. Remove the mounting plate and set aside. Mounting Plate 7085UE5 7788F Subscriber Mounting Plate Standoff 7764 Mounting Plate Standoff A B + - D Figure 8. Subscriber Mounting Plate 4. The cabinet may be surface mounted or semi-flush mounted using the optional trim bezel (refer to Figure 5 and Figure 6).

22 ULF Integrated Fire Monitoring System Note: For semi-flush mounting the supplied rubber duck antenna cannot be used and a remote antenna will be required. For semi-flush installations, mount the housing so that the front edge protrudes 1" from the finished wall surface. After all conduits and wiring are in place and the wall surface is completely finished, insert the supplied plug in the case antenna mounting hole, slide the trim bezel in place and fasten with 4 #6-32 1/4" machine screws and nuts. 5. Install all required conduits, external wiring, and points and make all connections that are external to the panel. 6. Install the subscriber mounting plate first in the cabinet. Tilt the subscriber mounting plate so it slides in between the cross-beam and the two mounting tabs for the main circuit board panel. Use the nylon spacers and screws as shown in Figure 9 below to secure the subscriber mounting plate to the cabinet: Enclosure Nylon Spacer 6-32 screw Subscriber Mounting Plate D Figure 9. Subscriber Mounting Plate Standoff Hardware Assembly 7. Verify that the P-Link address on the 7764 PIC Card address is set to 1. Check the S1 DIP switch shown in Figure 10 below. Switches must be in positions shown. Panel Interface Card DIP Switch Setting S1 PLINK - + A B AUX IN - + VOUT D Figure PIC P-Link Bus Address Switch Setting

23 7706-ULF Integrated Fire Monitoring System Connect the interconnect cabling on the subscriber board as shown in Table 8 below. Table 8: Interconnections Cable/Wire Identification From To AES Part No J3 7788F J1 End of Line Resistor: EOL-2.2k 22 AWG Stranded Wire 7788F Battery Leads (Supplied) AES Part No P J4 - N.C J4 - C 7788F BAT ( - ) 7788F BAT ( + ) 7764 J1 PLINK V- (Black) V+ (Red) A (White) B (Green) V- (Brown) V+ (Blue) 7788F J2 - Z1 7788F J2 - G 7764 J5 (BLACK) 7764 J6 (RED) PFC-6006 J1 PLINK* - (Black) + (Red) A (White) B (Green) PFC-6006 J1 AUX* - (Brown) + (Blue) * Connect cable to PFC-6006 mainboard after installation. Notes: y Do not use 7764 connectors P1 and P2. y Switch S1 is factory set. Do not change the switch setting.

24 ULF Integrated Fire Monitoring System Radio Mounting Bracket 7085-UE5 Transceiver Radio 2.2K EOL Resistor Battery Input Subscriber Communications Cable 7788F NC NO C 7764 Panel Interface Card Battery Cable PLINK AUX IN 13V OUT - + A B BLK GRN Panel Interconnect Cable RED WHITE WHT BRN BLU D Figure ULF Cabinet Wiring Diagram Subscriber 9. Before proceeding, verify that the following items are complete. The wire terminal blocks and other connectors for the subscriber and PIC are not easily accessible with the mainboard installed. y Cables are connected to correct terminals on PIC and subscriber. y Antenna (case mounted) is installed, or coaxial cable is installed for external antenna. y P-Link bus address of 7764 PIC is set to 1.

25 7706-ULF Integrated Fire Monitoring System Replace the panel motherboard. Fasten using the two screws that hold the motherboard module to the cabinet. Panel Motherboard 7788F 16.5VAC NAC AUX PLI NK - + A B Panel Interface Card Programming Port Battery Battery PLINK Cable D Figure ULF Cabinet Wiring Diagram Panel Motherboard 11. Connect the AUX cable from the 7764 PIC to the AUX terminals on the mainboard. Connect the P-Link cable from the 7764 PIC to the P-Link terminals on the mainboard. 12. Check to see that the AC power is turned OFF at the circuit breaker panel. Connect the AC hot, neutral and ground wires to the mainboard terminal block TB5 as shown in Figure 12 above. 13. Connect all the other wiring to the terminals (refer to Figure 13). 14. Replace dead front panel and secure with mounting screws using care so as to not damage LED annunciator module cable. 15. Configure the system and verify the operation of the complete system as outlined in the test procedure section.

26 ULF Integrated Fire Monitoring System Cabinet Wiring Connections CAUTION: DE-ENERGIZE UNIT PRIOR TO SERVICING 120VAC 60Hz Connect to separate unswitched AC circuit Primary AC 120VAC, 60Hz,.75 AMP Min Low AC Detect 98VAC Use 14 AWG or heavier gauge wire with 600V insulation WARNING: RADIO FREQUENCY FROM TRANSMITTING DEVICES MAY IMPAIR INTENDED OPERATION OF THE CONTROL UNIT. MAINTAIN A MINIMUM OF 30 CM BETWEEN TRANSMITTING DEVICES AND CONTROL UNIT. All Circuit Impedance Values Short Circuit: 0 Ohms Open Circuit: >10K Earth Fault to any terminal: 0 Ohms Battery Charging Low Battery Main Fuse Specification Batt. Fuse Specification 1.6A-250VAC 2.5A-250VAC Onboard Transceiver Fuse: Self Resetting - Not User Serviceable Signaling Type - RF Type 6 Radio Test for Signal Strength, Ambient Noise: FUSE After Installation, observe "RX" Receive Light; o If RX Light is off or flashing intermittently, unit is OK Battery - o If RX Light is ON Steady for more than 20 seconds, do not use this unit. Contact Factory. Coax cable to antenna must be protected in conduit Battery connection (non-power limited). Use two (2) 12V batteries connected in series. F.C.C. This device has been verified to comply with FCC Rules Part 15, Class A Operation is subject to the following conditions: 1. This device may not cause radio interference. 2. This device must accept any interference received including any that may cause undesired operation. 285 Newbury Street Peabody, MA USA Acknowledgements Gentex, Cooper Wheelock, and System Sensor synchronization protocols used with permission. Cooper Wheelock Patent Nos. 5,400,009. P/N L1 Rev. 5 F US E F2 F1 TB5 TB4 - + BATTERY FIRE ALARM EQUIPMENT 35BP SIGNAL SYSTEM CONTROL UNIT OF Battery + BLACK WHITE - + GROUND POWER ON EARTH FAULT SILENCED SIGNAL SILENCE ACK NOWLEDGE A B NAC AUX PLINK E.O.L. 7788F 7706-ULF Integrated Fire Monitoring System ENTER TB3 J J1 G Z1 J1 ALARM SUPERVISORY TROUBLE RESET FIRE DRILL - + A B C N.C. 7085UE5 Potter RA-6075 Remote Annunciator E.O.L. Antenna 0 ESC Programming Connection A- A+ 9 E.O.L. E.O.L. TB2 E.O.L. 6 Conventional Inputs, fully programmable & supports 2-wire smoke detectors Requirements Install in accordance with Installation Manual, Part No ULF Rev and Operating Instructions, Part No PI Rev See Smoke Detector Compatibility Identifer "A". NFPA Commercial Protected Premises Control Unit for UL Installations: 13, 70, and NFPA 72. Alarm activation requiring activation of two or more automatic detection devices shall not utilize any time delay. Service Use for UL Installations: - Location - Remote Station - Proprietary - Central Station Line2 In Line2 Out Line1 In Line1 Out Tip Ring Tip Ring Tip Ring Tip Ring ALARM SIGNAL ACTIVATION PRESS LEFT & RIGHT ARROW KEYS AT SAME TIME TO TRIGGER ALARM SIGNAL ACTIVATION. LAMP TEST: PRESS [ENTER], [5], PASSWORD, [6]. PRESS THE [ESC] KEY WHEN DONE B- B INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 E.O.L. E.O.L. E.O.L. TB1 WARNING: DO NOT CONNECT. ONLY DETECTORS THAT ARE SHOWN IN THE COMPATIBILITY LIST ARE TO BE USED. System must be fully tested after installation. Intended for indoor use in dry locations only. Separation of power limited wiring from non-power limited wiring must be at least 1/4". Field wire size must be the same as factory wire size when connecting both wires to the same screw terminal. Do not mix use of solid and stranded wire on the same screw terminal. Place one wire on each side of the terminal screw head. Figure ULF Cabinet Wiring

27 7706-ULF Integrated Fire Monitoring System 27 Battery Circuit Calculations Before selecting the battery, it is important to determine the minimum size batteries for standby and alarm times desired for each application. If the wrong batteries are installed in a specific application or incorrect current draw is used, the proper standby and minimum alarm time will not be present. The battery circuit is rated for 8 to 18 AH batteries and will operate the panel alarm for at least 24 hours and 5 minutes. The cabinet will house up to two (2) 8 AH or two (2) 18 AH batteries. Please use the worksheet shown below to calculate the battery size and current draw required for each application: Battery Calculation Worksheet Description Quantity Standby (ma) Total Standby (ma) Alarm (ma) Total Alarm (ma) Mainboard (PFC-6006) Subscriber (7788F, 7764, and 7085UE5) LCD Remote RA Input Circuit #1 Input Circuit #2 Input Circuit #3 Input Circuit #4 Input Circuit #5 Input Circuit #6 NAC 1 Total (ma) Total (ma) Convert to Amps Convert to Amps (*Refer to maximum allowable standby current) Total A: Total A: 60 minutes per hour Multiply by standby hours Total Standby AH Alarm time (minutes) Example: 5 minute alarm: enter 12 Total Alarm AH +Total Standby AH Total AH Efficiency Factor 0.85 Required AH *Maximum Allowable Standby Current (UL 24-Hour standby time) 7 AH.244 A 12 AH.421 A 18 AH.634 A Important Notes: 1. FACP enclosure can house up to two (2) 18 AH batteries. 2. NFPA-72 requires 24 hours of standby power followed by 5 minutes of alarm activation. 3. LED/Relay current must be accounted for in the battery calculation for the supplying source. 4. Total current must not exceed power supply rating of 2A.

28 ULF Integrated Fire Monitoring System Main Supply Circuit The AC terminals are located in the upper left-hand portion of the mainboard. The mainboard supervises the main AC power and provides indication that the AC power is absent. The terminals are rated at 120 VAC 60 Hz and are marked accordingly on the board. 120VAC 60 Hz Connect to separate Unswitched AC circuit Use 14 AWg wire or Heavier with 600V Insulation Black White Ground L N AC POWER AC120V/AC230V,50/60Hz DWG # Figure ULF AC Terminals The earth ground connection is marked as " and is the furthest connection from the line voltage connection. The AC input power rating is a maximum of 0.75A at the nominal 120 VAC rating. Battery Connections The battery charging circuit is located on the main panel in the lower left portion of the board. The maximum battery charging current is 0.5A DC; the charging voltage is approximately 27.3 VDC and is supervised. Note: The battery should be clearly labeled as Sealed Lead Acid Battery or equivalent UL listed or UL recognized.

29 7706-ULF Integrated Fire Monitoring System 29 Connect the battery wire leads to the terminal connections, as shown in Figure 15 below. Batteries should be replaced every five (5) years or sooner depending on annual testing. - + BATTERY Panel Connec ons V Ba ery V Ba ery DWG # ULF Figure ULF Battery Connections Section 5. Control Panel Installation This section addresses installation procedures for Input Circuits 1 6, the NAC, and the optional RA-6075 remote annunciator. Wiring requirements and configuration examples are included throughout this section. Please read this section carefully before installing points and accessories to ensure proper installation. Input Circuits There are six (6) programmable Input or Initiating Device Circuits (IDC) provided on the PFC-6006, which are the same as an integrated fire system input. They are supervised and power-limited to protect 2-wire smoke detectors. Input Circuit #1 may be wired for either Class A, Style D or Class B, Style B, whereas Inputs #2-6 may be Class B, Style B only. All inputs are suitable for automatic, manual, waterflow or sprinkler supervisory service (refer to Figure 18 on page 33). Note: The panel has the intelligence to determine the applicable style for Input Circuit #1 based on the wiring configuration used. Input Wiring Specifications y Maximum short circuit current = 32 ma. y Maximum wiring resistance = 100 ohms. y Maximum wiring capacitance = 1 mf. y Maximum wire length in feet = 100/ohms per 1 foot of wire. y Normal standby current = 2.5 ma. y Operating voltage range = 15.1 VDC VDC.

30 ULF Integrated Fire Monitoring System Input Circuit #1 Class A, Style D Wiring Configuration L N G LINE 2 IN LINE 2 OUT LINE 1 IN LINE 1 OUT TIP RING TIP RING TIP RING TIP RING - + BATTERY - + NAC - AUX A B P-LINK A- A+ B- B ETHERNET INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 DWG #559-4 Figure 16. Example of Input 1, Class A, Style D WATERFLOW SWITCH NORMALLY OPEN CONTACTS CLASS A WIRING Notes: y Input Circuit #1 may be wired as either Class A or Class B. y All other inputs are Class B only. y Maximum wiring resistance must not exceed 100 ohms. y The input has ground fault detection with 0-ohm impedance to ground. y The EOL resistor assembly is a listed 5.1k ohm resistor.

31 7706-ULF Integrated Fire Monitoring System 31 Input Circuits #1-6 Class B, Style B Wiring Configuration L N G LINE 2 IN LINE 2 OUT LINE 1 IN LINE 1 OUT TIP RING TIP RING TIP RING TIP RING - + BATTERY - + NAC - AUX A B P-LINK A- A+ B- B ETHERNET INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 5.1K EOL DWG #559-5 COMM NO NC COMM NO NC SPRINKLER VALVE TAMPER SWITCH NORMALLY OPEN CONTACTS CLASS B WIRING Figure 17. Example of Inputs Wired as Class B, Style B Notes: y Maximum wiring resistance must not exceed 100 ohms. y The input has ground fault detection with 0-ohm impedance to ground. y The EOL resistor assembly is a listed 5.1k ohm resistor.

32 ULF Integrated Fire Monitoring System Notification Appliance Circuits Installation There is one (1) NAC circuit provided on the PFC-6006 rated as continuous 0.5A at 24 VDC. The NAC circuit is configurable as Class B, Style Y only. (Please refer to the wiring example located in this section.) NAC Wiring Characteristics y Output is supervised and regulated. y Circuit is power limited. y Normal standby supervisory current is approximately 1.2 ma y Low current trouble activation is 0.8 ma; high current trouble activation is 1.7 ma. y Maximum RMS current is 0.5A. Note: Type of NAC output is selectable, and may be configured for strobe synchronization with Potter/ AMSECO, Cooper Wheelock, Gentex, or System Sensor strobe points. Refer to the listing of compatible models located in "Appendix H. PFC-6006 NAC Compatibility List" on page 118.

33 7706-ULF Integrated Fire Monitoring System 33 NAC Maximum Wiring Impedance Formula The maximum impedance is a function of the load placed on the circuit. To calculate the maximum line current impedance, use the following formula: (Alarm Current of Notification Appliance) x (Wire Resistance) < 1.2 Volts NAC Wiring Configuration Notification Appliances - + NAC Note: The resistance of external wiring shall be determined using the following formula: (Alarm Current of Notification Appliance) x (Wire Resistance) < 1.2 Volts 5.1k EOL Potter Part # DWG #559-6A Figure 18. NAC Class B, Style Y Wiring Example Notes: y The EOL resistor assembly is a listed 5.1k ohm resistor. y The panel has ground fault detection on the NAC circuit. The impedance to ground for ground fault detection is 0 ohm. y The 1.2 volts is based on the worst case loading at the remote end of the NAC circuit (lump sum method). The total drop of 1.2 volts should be measured from the terminals to the most remote device.

34 ULF Integrated Fire Monitoring System P-Link Points Accessory points, such as the RA-6075 remote annunciator, are connected to the main control panel utilizing the fourwire P-Link bus for power and communication. This panel supports a single P-Link point, which can be connected using a Class B, Style 4 wiring style. Configuration Characteristics y P-Link current rating may not exceed 0.5A based on the total between auxiliary and P-Link. y P-Link maximum current is 500 ma. y P-Link voltage rating is 24 VDC. y Continuous DC frequency. y P-Link circuit is supervised and power-limited. Maximum Wire Resistance Formula (Wire Length) The maximum resistance is based on the load placed on the circuit. To calculate the maximum wire resistance, use the following formula: (Total Annunciator Alarm Current) x (Wire Resistance) < 6 Volts P Link - + A B 7706-ULF Panel Connection 7764 PIC - + A B - + A B RA-6075 Remote Annunciator Field wire size must be the same as factory wire size when connecting both wires to the same screw terminal. Do not mix use of solid and stranded wire on the same screw terminal. Place one wire on each side of the terminal screw head. Figure 19. P-Link Device Class B Wiring Example

35 7706-ULF Integrated Fire Monitoring System 35 P-Link Addresses Every P-Link device has a five-position DIP switch which is used to program the device address. The addresses range from one (1) to thirty-one (31). See the chart below to reference DIP switch settings: Annunciator Address DIP Switch Settings Annunciator DIP Switch Settings SW-1 SW-2 SW-3 SW-4 SW-5 Address SW-1 SW-2 SW-3 SW-4 SW-5 1 On Off Off Off Off 17 On Off Off Off On 2 Off On Off Off Off 18 Off On Off Off On 3 On On Off Off Off 19 On On Off Off On 4 Off Off On Off Off 20 Off Off On Off On 5 On Off On Off Off 21 On Off On Off On 6 Off On On Off Off 22 Off On On Off On 7 On On On Off Off 23 On On On Off On 8 Off Off Off On Off 24 Off Off Off On On 9 On Off Off On Off 25 On Off Off On On 10 Off On Off On Off 26 Off On Off On On 11 On On Off On Off 27 On On Off On On 12 Off Off On On Off 28 Off Off On On On 13 On Off On On Off 29 On Off On On On 14 Off On On On Off 30 Off On On On On 15 On On On On Off 31 On On On On On 16 Off Off Off Off On Remote Annunciators Installation (RA-6075) One (1) annunciator may be connected to the main sprinkler monitoring panel. The RA-6075 provides a 2 16 character LCD display, along with standard function and numeric keys. It is listed and designed to be mounted on a flat noncondensing surface or electrical box. Setting Addresses The annunciator's address is set by DIP switch S1, which is located on the back of the annunciator. The address must be set in the range of one to thirty-one (1 31) to be recognized by the panel.

36 ULF Integrated Fire Monitoring System Figure 20. Remote Annunciator Back Panel View Auxiliary Power The Auxiliary Power is a 24 VDC output rated at a maximum of 0.5A. The auxiliary power connection is dedicated for use with the AES 7764 PIC and 7788F subscriber and is not programmable. Do not connect auxiliary power to other external devices. Auxiliary Power Characteristics y The impedance to ground for ground fault detection is 0 ohm. y Supervised and power-limited. y Circuit is provided with battery back-up. y Special application. - + AUX Figure 21. Auxiliary Connections Example

37 7706-ULF Integrated Fire Monitoring System 37 Section 6. Control Panel Operation This section provides an overview of the control panel basic operations, which includes the status LEDs, function keys, and a quick reference sheet for the Control Panel Menu tree. The control panel is used for configuration of the 7788F subscriber and the alarm control panel. Control Panel Basic Operation The control panel is comprised of a two (2) line 16-character LCD display panel, arrow keys, function keys, status LEDs, and the numeric keypad. A description of each component is included in this section (refer to Figure 22 below). LCD Display 7706-ULF 11/11 21:20:AM Arrow Keys Status LEDs POWER ON EARTH FAULT SILENCED ALARM SUPERVISORY TROUBLE Function Keys SIG N A L SILENCE A C K N O W LEDGE R ESET FIR E D R ILL ENTER 0 ESC Numeric Keypad D Figure ULF Control Panel Display Note: Authorized system operators must use a key to open the outer door of the cabinet.

38 ULF Integrated Fire Monitoring System LCD Display The LCD panel displays the standard Start-up menu as shown in Figure 23 below. The LCD displays up to thirty-two (32) characters of information displays, providing important feedback to system users, i.e., system messages, status information, trouble conditions, or input changes. The LCD also provides access to the Main Menu for daily system operations and specific programming functions (refer to "Section 6. Control Panel Operation" on page 37 for details on these topics) ULF 11/11 21:20:00PM Figure 23. LCD Start-Up Screen Note: You may customize the Start-up screen to display a specific job site name or other relevant descriptive text. Menu Navigation Keys The arrow keys allow you to scroll or move through the control panel menus. The Enter and Esc keys may also be used to navigate through menus; they are located on the numeric keypad. Table 9 provides a summary of the navigation keys. Keys Table 9: Menu Navigation Keys Description Moves/scrolls up or down through menus. Scrolls to the left or right to display details, if any, of current menu item. Note: When the LCD panel displays a left and/or right arrow, this indicates more information may be viewed. Displays the Main Menu or selects the current menu option. Note: The blinking indicates the current menu option. Returns to previous menu or backs up to previous screen.

39 7706-ULF Integrated Fire Monitoring System 39 Numeric Keypad The numeric keypad allows you to enter user codes when required to access restricted functions. Alternatively, the numbers may be used to quickly select menu options, rather than using the arrow and Enter keys to select a function. Figure 24. Control Panel Numeric Keypad Function Keys The four (4) function keys are used when system alarm/trouble conditions occur or to perform a fire drill. Refer to Table 10 below for a brief summary of the function keys: Function Keys Table 10: Control Panel Function Keys Description Press to acknowledge the currently displayed condition. Press to silence all outputs programmed as silenceable and buzzer. Press to reset panel to normal condition. Press to begin a fire drill.

40 ULF Integrated Fire Monitoring System Status LEDs The control panel s LEDs communicate system conditions by illuminating and/or flashing the applicable green, red, or amber indicators. These are described in the table below. Figure 25. Control Panel Status LEDs Table 11: Status LEDs LED Type LED Color/Action Description POWER ON Steady Green Power is present. If power is absent for more than 5 seconds, LED will extinguish. ALARM Flashing Red An alarm device is active. ALARM Steady Red An alarm device is acknowledged. EARTH FAULT Flashing Amber A ground fault is present. SUPERVISORY Flashing Amber A supervisory condition is present. SILENCED Steady Amber A fault condition has been silenced. TROUBLE Flashing Amber A fault condition is present.

41 7706-ULF Integrated Fire Monitoring System 41 Control Panel Menu Tree Figure 26 displays the menu options as they appear on the LCD panel (see also Appendix G for the menu tree). Main Menu 1=View History 2=Enable/Disable 3=Set Date/Time 4=Walk Test 5=System Tools 6=Programming 7=Data Transfer Esc= Exit 7=PIC Config. 1=By Point Select Device Internal PWR 2=By Zone Zone (Enter Zone # and press Enter) 1=Disable Inputs 2=Disable Options Esc=Exit PIC Menu 1=PIC Status 2=Route Table Esc=Exit 1=Point Control 2=Ethernet Status 3=DACT Test 4=DACT Reset 5=Erase History 6=Lamp Test 7=App Revisions 8=PIC Status Esc=Exit 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit Select Data 1=Remote Access 2= History 3= Config 4= Test 5=Server Status Esc=Exit 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit System Setup 1=AC PWR Delay 2=DACT Setup 3=Display Mode Esc=Exit IP Settings 1=DHCP Settings 2=Default IP 3=Default Gatewy 4=Default Settings 5=Alternate IP 6=Alt. Gateway 7=Alt. Subnet Esc=Exit DACT Setup* 1=Line 1 Setup 2=Line 2 Setup 3=Acct 1 Setup 4=Acct 2 Setup 5=Acct 3 Setup 6=Acct 4 Setup 7=Acct 5 Setup Esc=Exit Display Mode 1=USA 2=Canada Esc=Exit Line Setup 1=Enable/Disable 2=Line Monitor 3=No. of Rings 4=Ans. Machine 5=Line Prefix 6=Dial Tone Det. Esc=Exit Account Setup 1=Report Event Type 2=Pri Acct ID 3=Pri Phone No. 4=Pri Rpt. Test 6=Sec Acct. ID 7=Sec Phone No. 8=Sec Rpt. Fmt. 9=Sec. Rpt. Test Esc=Exit Def. ID/Passwd 1=Username 2=Password Esc=Exit PIC Config. 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit * DACT not used in this product. TIP: To save time, enter the menu selection number on the keypad to select a function. For example, press 3 to select Set Date/Time from the Main Menu. Figure 26. Control Panel Menu Tree

42 ULF Integrated Fire Monitoring System Section 7. Subscriber Specifications Features This section is included for those customers familiar with other AES-IntelliNet UL Subscriber products. Listed below are the new features utilized with the unit as part of the 7706-ULF System. y Fail Secure Relay on board relay function is monitored through the 7764 PIC card. Connection to the relay is not required. The status of the 7788F is monitored by the PFC-6006 mainboard. y Transceiver power PTC is added. It is installed in series with the power line to the transceiver disconnecting power if the transceiver draws too much current. y Remote AES 7788F subscriber programming using software at the central station is disabled.this is to comply with UL/NFPA requirements. Optional Accessories No optional accessories are available with the 7788F used in the 7706-ULF Integrated Fire Monitoring System. Subscriber Technical Specifications y Voltage: 12 VDC nominal; power supplied from the PCF-6006 mainboard. y Current: 150 ma standby; 1.2A transmit y RESET button: Located on the PCB. y Transceiver: Standard UHF Frequency Ranges ( MHz, MHz, MHz) y Transceiver Fuse: 400 milliamp PTC, not serviceable y Standard RF Output Power: 2 Watts y Antenna Cut/Low Battery/Charger Fail Local Reporting: Controlled by the PFC-6006 mainboard. Subscriber Local Trouble Output y The control panel monitors the 7788F Trouble condition. y Do not connect to the J4 Trouble Output relay terminals. Subscriber Programming This section describes the configuration required for a subscriber to join the AES mesh network. Initial subscriber configuration must be performed on factory new units for the subscriber to join and communicate on the network properly. The subscriber is programmed through the AES 7764 PIC card. The keypad on the control panel display allows navigation of the LCD panel menu options (see "Figure 26. Control Panel Menu Tree" on page 41) and the ability to examine and change settings for the 7788F subscriber. Previously programmed information is stored in non-volatile memory, so the settings are not lost during power-down of the 7706 ULF or power failure. Important! The following 7788F subscriber features are not available in the 7706-ULF System. y Remote Programming (disabled to comply with UL/NFPA requirements) y Monitor Transmitter

43 7706-ULF Integrated Fire Monitoring System 43 ykey Transmitter y Display Zone Status y Text Messages y AC Fail, Charger Fault, Ground Fault: Not configurable on the 7788F when used in the 7706-ULF Integrated Fire Monitoring System. AC fail functionality is handled by the mainboard. y Zone Programming: Zone programming is fixed and cannot be changed for the 7788F when used as part of the 7706-ULF System. 1. Turn on the AC power to the system. 2. Connect the standby batteries with the cable provided to perform programming. Important! Battery polarity must be observed. Notes: y The panel will perform initialization and self-test after power is applied. A series of messages appear in the display. y The error message Trb-AES Comm in the display means the mainboard is unable to communicate with the 7788F subscriber (see "Appendix G. Verifying 7764 PIC Operation and Troubleshooting Steps").

44 ULF Integrated Fire Monitoring System ID # and System Cipher Code This function programs the unit ID# and the AES system cipher code. Access to view or change is available locally through the mainboard keypad or through the optional Potter Remote Annunciator. Menu location: Programming > PIC Config > PIC Options > 1=Setup 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit PIC Options 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit ID# Cphr Code Notes: y It is not possible to remotely program the unit ID# or system cipher code through the AES radio network. y The unit ID# must be unique and different from all other ID#'s in your network. y Entering new data overwrites (erases) any previously stored ID number and system cipher code. 1. From the control panel, press ENTER to display the Main Menu. 2. Press 6, then ENTER, to access the Programming menu. The Enter Code prompt displays. 3. Enter the user access code. 4. At the Programming menu: y Press 7 to select PIC Config. y From the PIC Options menu, press 1 to select Setup. The ID# prompt displays the current ID number. The subscriber ID# is four hexadecimal characters.

45 7706-ULF Integrated Fire Monitoring System To change the existing ID#, press the characters of the subscriber ID# on the keypad. Note: To enter characters A F, first press the up-arrow key. Then press the keypad number that corresponds to the hexadecimal character as shown in Figure 27. Keypad Number Hex Character 1 A 2 B 3 C 4 D 5 E 6 F Figure 27. Keypad Number to Hexadecimal Character Chart Example: To enter the ID# ABCD: 1. Press the up-arrow key once on the keypad. The word Shift appears in the LCD. 2. Press 1. The letter A appears in the ID#. 3. Continue by pressing the up-arrow key and then 2 for B. 4. Repeat the up-arrow and number key combination for the remaining characters until the full ID# has been entered. 6. Press ENTER after entering the ID#. The Cphr Code prompt displays with the current cipher code. Note: The actual characters of the current cipher code are not shown for security. Instead, four asterisks (****) are displayed. 7. Enter the 4-character hexadecimal cipher code as assigned by the system administrator. The cipher code must match the system cipher code. Only a correct cipher code will allow the subscriber to log on to the network to communicate. Note: To enter characters A F, first press the up-arrow key. Then press the keypad number that corresponds to the hexadecimal character as shown in Figure Press ENTER after entering the cipher code. The PIC Options display appears. ID# and cipher code programming is complete.

46 ULF Integrated Fire Monitoring System Timing Parameters This programming function is used to set timing parameters of Checkin Time, NTR RPT DLY, and Comm Timeout for the 7788F. Menu Location: Programming > PIC Config > PIC Options > 2=Timers 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit PIC Options 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit Checkin Time NTR RPT DLY Comm Timeout 1. From the control panel, press ENTER to display the Main Menu. 2. Press 6, then ENTER, to access the Programming menu. The Enter Code prompt displays. 3. Enter the user access code. 4. At the Programming menu, press 7 to select PIC Config. 5. At the PIC Options menu, press 2 to select Timers. The Checkin Time prompt displays with the subscriber check in time value. Note: Checkin Time default is 23:45 (23 hours and 45 minutes). This is also a recommended setting. Important! Short intervals between check-in times are a cause of more traffic on the radio network. Carefully consider the effect before implementing a short interval. 6. Enter the number of hours using the numeric keypad, or press ENTER to skip and go to the next parameter. Valid entries are between hours. 7. Press the right-arrow key to move the cursor to the minute position. 8. Enter the number of minutes using the numeric keypad. 00 hours, 00 minutes is an illegal entry and will not be accepted. 9. Press ENTER after entering the Checkin Time value. The NTR RPT DLY prompt displays. The Reporting Delay sets the rate at which a subscriber s own signals are transmitted. The initial alarm is sent immediately regardless of setting. Subsequent alarms are sent as specified by the delay setting. The

47 7706-ULF Integrated Fire Monitoring System 47 default value and recommended setting is 10 seconds; transmissions are sent at least 10 seconds apart (this helps to meter traffic on the system). The range is 0 80 seconds (no delay, not recommended). For all commercial fire alarms, the reporting interval must not exceed 20 seconds. After the reporting delay has expired, a new event will not have any delay, and the attempt to send a new message will begin immediately after activation. 10. Enter the number of seconds using the numeric keypad, or press ENTER to skip and go to the next parameter. Default Reporting Delay is 10 seconds. 11. Press ENTER after entering the delay value. The Comm Timeout prompt displays. 12. Enter the number of seconds using the numeric keypad, or press ENTER to skip. Valid entries are between 1 80 seconds. Modes Menu Location: Programming > PIC Config > PIC Options > 3=Modes 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit PIC Options 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit Enable Repeating 1. From the control panel, press ENTER to display the Main Menu. 2. Press 6, then ENTER, to access the Programming menu. The Enter Code prompt displays. 3. Enter the user access code. 4. At the Programming menu, press 7 to select PIC Config. 5. At the PIC Options menu, press 3 to select Modes. The Enable Repeating prompt displays. 6. To accept the default value of Yes, press ENTER. To change the value to No, press the left-arrow or rightarrow key, then press ENTER. 7. The 3=Mode prompt displays. Select the next parameter item to configure, or press ESC to exit the PIC Options menu.

48 ULF Integrated Fire Monitoring System Time to Live These settings are for the length of time that a packet message is retried for transmission by the subscriber to the AES mesh network. Menu Location: Programming > PIC Config > PIC Options > 4=Time to Live 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit PIC Options 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit Checkin TTL Status TTL Alarm TTL Trouble TTL Restoral TTL Intellitap TTL Special TTL 1. From the control panel, press ENTER to display the Main Menu. 2. Press 6, then ENTER, to access the Programming menu. The Enter Code prompt displays. 3. Enter the user access code. 4. At the Programming menu, press 7 to select PIC Config. 5. At the PIC Options menu, press 4 to select Time to Live. The Checkin TTL prompt displays. Note: The Checkin TTL value must be entered in hours and minutes. The Checkin TTL default is 00:10 (0 hours and 10 minutes). 6. Enter the number of hours using the numeric keypad, or press ENTER to skip and go to the next parameter. Valid entries are between hours. 7. Press the right-arrow key to move the cursor to the minute position. 8. Enter the number of minutes using the numeric keypad. 00 hours, 00 minutes is an illegal entry and will not be accepted. 9. Press ENTER after entering the Checkin TTL value. The Status TTL prompt displays. Note: The Status TTL value must be entered in hours and minutes. The Status TTL default is 00:10 (0 hours and 10 minutes). 10. Enter the number of hours using the numeric keypad, or press ENTER to skip and go to the next parameter. Valid entries are between hours.

49 7706-ULF Integrated Fire Monitoring System Press the right-arrow key to move cursor to the minute position. 12. Enter the number of minutes using the numeric keypad. 00 hours, 00 minutes is an illegal entry and will not be accepted. 13. Press ENTER after entering the Status TTL value. The Alarm TTL prompt displays. Note: The Alarm TTL value must be entered in hours and minutes. The Alarm TTL default is 03:00 (3 hours and 0 minutes) 14. Enter the number of hours using the numeric keypad, or press ENTER to skip and go to the next parameter. Valid entries are between hours. 15. Press the right-arrow key to move the cursor to the minute position. 16. Enter the number of minutes using the numeric keypad. 00 hours and 00 minutes is an illegal entry and will not be accepted. 17. Press ENTER after entering the Alarm TTL value. The Trouble TTL prompt displays. Note: The Trouble TTL value must be entered in hours and minutes. The Trouble TTL default is 03:00 (3 hours and 0 minutes). 18. Enter the number of hours using the numeric keypad, or press ENTER to skip and go to the next parameter. Valid entries are between hours. 19. Press the right-arrow key to move the cursor to the minute position. 20. Enter the number of minutes using the numeric keypad. 00 hours, 00 minutes is an illegal entry and will not be accepted. 21. Press ENTER after entering the Trouble TTL value. The Restoral TTL prompt displays. Note: The Restoral TTL value must be entered in hours and minutes. The Restoral TTL default is 03:00 (3 hours and 0 minutes). 22. Enter the number of hours using the numeric keypad, or press ENTER to skip and go to the next parameter. Valid entries are between hours. 23. Press the right-arrow key to move the cursor to the minute position. 24. Enter the number of minutes using the numeric keypad. 00 hours, 00 minutes is an illegal entry and will not be accepted. 25. Press ENTER after entering the Restoral TTL value. The IntelliTap TTL prompt displays. Note: The IntelliTap value must be entered in hours and minutes. The IntelliTap default is 00:10 (0 hours and 10 minutes) 26. Enter the number of hours using the numeric keypad, or press ENTER to skip and go to the next parameter. Valid entries are between hours. 27. Press the right-arrow key to move the cursor to the minute position. 28. Enter the number of minutes using the numeric keypad. 00 hours, 00 minutes is an illegal entry and will not be accepted.

50 ULF Integrated Fire Monitoring System 29. Press ENTER to go to the next parameter. The Special TTL prompt displays. Note: The Special TTL value is not used in this application. 30. Press ENTER. The 4=Time to Live prompt displays. Press ESC to exit the PIC Options menu. Account Override The Account Override option allows use of the subscriber ID# in place of the FACP identification number. Menu Location: Programming > PIC Config > PIC Options > 5=Acct Override 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit PIC Options 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit Acct Override 1. From the control panel, press ENTER to display the Main Menu. 2. Press 6, then ENTER, to access the Programming menu. The Enter Code prompt displays. 3. Enter the user access code. 4. At the Programming menu, press 7 to select PIC Config. The PIC Options prompt displays. 5. Press 5 to select Acct Override. The Acct Override prompt displays. Note: Acct Override default setting is No. 6. Press the up-arrow key to change the value, or press ENTER to skip and go to the next parameter. Press ESC to exit the PIC Options menu.

51 7706-ULF Integrated Fire Monitoring System 51 User Codes Menu Location: Programming > PIC Config > PIC Options > 6=User Codes 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit PIC Options 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit User Codes 1. From the control panel, press ENTER to display the Main Menu. 2. Press 6, then ENTER, to select Programming. The Enter Code prompt displays. 3. Enter the user access code. 4. At the Programming menu, press 7 to select PIC Config. The PIC Options prompt displays. 5. Press 6 to select User Codes. The User Codes prompt displays. Note: User Codes default setting is No. 6. Press the up-arrow key to change the value, or press ENTER to skip and go to the next parameter. 7. Press ESC to exit this menu.

52 ULF Integrated Fire Monitoring System Report Account Menu Location: Programming > PIC Config > PIC Options > 7=Report Acct 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit PIC Options 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit Rpt Alarms Rpt Troubles Rpt Supervisory Rpt By Rpt Acct 1. From the control panel, press ENTER to display the Main Menu. 2. Press 6, then ENTER, to select Programming. The Enter Code prompt displays. 3. Enter the user access code. 4. At the Programming menu, press 7 to select PIC Config. The PIC Options prompt displays. 5. Press 7 to select Report Acct. The Rpt Alarms prompt displays. Note: The default setting is Yes. 6. Press the up-arrow key to change the value, then press ENTER to go to the next parameter. The Rpt Troubles prompt displays. Note: The default setting is Yes. 7. Press the up-arrow key to change the value, then press ENTER to go to the next parameter. The Rpt Supervisory prompt displays. Note: The default setting is Yes. 8. Press the up-arrow key to change the value, then ESC to exit, or press ENTER to skip and go to the next parameter. The Rpt Test prompt displays. Note: The default setting is Yes.

53 7706-ULF Integrated Fire Monitoring System Press the up-arrow key to change the value, then ESC to exit, or press ENTER to skip and go to the next parameter. The Report By prompt displays. Note: The default setting is Zone. 10. Press the up-arrow key to change the value, then ESC to exit, or press ENTER to skip and go to the next parameter. The Report Account prompt displays. Note: The default setting is Press the up-arrow key to change the value. The left/right arrow key allows movement between digits to set them. Press ESC to exit after entering values, or press ENTER to skip and go to the next parameter. 12. Press ENTER to return to the Report Acct menu. Default PIC Menu Location: Programming > PIC Config > PIC Options > 8=Default PIC 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit PIC Options 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit Default PIC Important! This command functions the same as the 7788F Reset RAM function. It should be used only when a reset to factory settings of subscriber parameters is required. All existing parameters, except ID# and System Cipher Code, are reset back to factory default values. 1. From the control panel, press ENTER to display the Main Menu. 2. Press 6, then ENTER, to select Programming. The Enter Code prompt displays. 3. Enter the user access code. 4. At the Programming menu, press 7 to select PIC Config. The Default PIC prompt displays.

54 ULF Integrated Fire Monitoring System 5. Press 8 to select Default PIC. The Default PIC prompt displays. Note: Default PIC setting is No. 6. Press the up-arrow key to change the value to Yes (Note: Selecting Yes will reset all parameters back to factory default values), or press ENTER to return to the PIC Option menu. Local Status Check (PIC Status) This function performs a quick diagnostic check at any time and is shown across a set of four screens. Menu Location: System Tools > PIC Status > PIC Menu > 1= PIC Status 5=System Tools PIC Menu 1=PIC Status 2=Route Table Esc=Exit 1=Point Control 2=Ethernet Status 3=DACT Test* 4=DACT Reset 5=Erase History 6=Lamp Test 7=App Revisions 8=PIC Status Esc=Exit *DACT not used in this product. 1. From the control panel, press ENTER to display the Main Menu. 2. Press 5, then ENTER, to access the System Tools menu. The Enter Code prompt displays. 3. Enter the user access code. 4. At the System Tools menu, press 8 to select PIC Status. You are now in the PIC Menu. 5. Press 1 to select PIC Status. The PIC Menu prompt displays.

55 7706-ULF Integrated Fire Monitoring System 55 Type:SUB X.XXXX 7788F Second screen display: Table 12: PIC Menu Screen Displays Screen Display Meaning Required Action First screen display: Subscriber Model 7788F X.XXX is the FW Version Number ID:NNNN Route:NNNN ID: 4-digit ID number programmed into this unit. Route: The ID of the first subscriber or IP Link that will be attempted in route to the central station. Press the down-arrow on the keypad to move to the next screen, or press ESC to exit. Press the down-arrow key on the keypad to move to the next screen, the up-arrow to return to prior screen, or ESC to exit. Third screen display: Link Layer:N NetCon:N Fourth Screen display: Status:NNN If the letters XXXX appear in the display, then the unit is not on the network. Link Layer: Refers to the subscriber unit level" or "link layer," which suggests the expected number of hops the message packet might make to get to the IP-Link. In general, if the number is 1, then this unit is attempting communication directly with the IP-Link. If the number is 2, the unit expects to relay its message through one other subscriber unit to reach the IP-Link. If the number is 3, the message goes through 2 other subscribers... and so on. Also, the level number of subscriber with a weak signal to the unit on the top of its routing list will be incremented by 1. A unit level = 255 indicates that the unit is not on the network. NetCon: (NETwork CONnectivity) An internal rating used in the automatic positioning of this unit in the network. The possible values are 5, 6, or 7. A value of 5 indicates there are two or more paths available. A value of 6 indicates there is one path available. A value of 7 may indicate a problem with this unit or a unit in its path to the IP Link. Status: Status shows the subscriber self-test data. Refer to "Self-Test Error Codes Status Error Codes" on page 57 for explanations and resolution. Press the down-arrow key on keypad to move to next screen, the up-arrow key to return to prior screen, or ESC to exit. Press the up-arrow key to return to the prior screen, or ESC to exit.

56 ULF Integrated Fire Monitoring System Notes: All Fire Alarm installations require a NetCon value of 5. Minimum criteria for a "good" repeater are as follows: 1. The RF signal exceeds good threshold. 2. No faults are indicated in status (such as low battery). 3. Level/Link Layer of Subscriber/IP-Link is less than or equal to that of this unit. 4. The signal received from the Subscriber/IP-Link occurs at least once every 6 hours. Display Route Table Use this function to display the ID# s listed in this Subscriber s current Routing Table. Up to eight ID numbers may be available for display. A single ID in the Routing Table is displayed in the LCD display. Menu Location: System Tools > PIC Status > PIC Menu > 2=Route Table 5=System Tools PIC Menu 1=PIC Status 2=Route Table Esc=Exit 1=Point Control 2=Ethernet Status 3=DACT Test* 4=DACT Reset 5=Erase History 6=Lamp Test 7=App Revisions 8=PIC Status Esc=Exit *DACT not used in this product. 1. From the control panel, press ENTER to display the Main Menu. 2. Press 5, then ENTER, to select Programming. The Enter Code prompt displays. 3. Enter the user access code. The Programming menu will appear. 4. At the Programming menu, press 8 to select PIC Status. The PIC Status prompt displays. 5. Press 2 to select Route Table. The Route Table prompt displays. 6. Use the up-arrow/down-arrow keys to move to the next/previous screen. Fields displayed are as follows: Preference or sort order [1.- 8.] ID L: - Link Layer or Level:## N: NetCon:# (0-7)

57 7706-ULF Integrated Fire Monitoring System 57 Q: Signal Quality:## (03 = Best, 81 = worst) Screen Display 1.AA11 L:00,N:0,Q:03 2.BB12 L:00,N:0,Q: L:01,N:5,Q: L:02,N:5,Q:83 Table 13: Routing Table Display Examples Meaning/Definition An IP-Link AA11, top of the list = RT1 An IP-Link BB12, Good Signal (03) Unit 7107, Good Signal (03) Unit 5678, Weak signal (8x) y Routing Table A routing table is a list of up to eight IDs that a subscriber maintains for selecting the ID to pass its data packets on through. It is sorted so that the best ID is at Preference location 1. If no Packet Acknowledge is received after attempting transmissions to the #1 ID, then the #1 ID is removed from the table and all other preferences are incremented by 1. Transmission attempts resume using the new Preference 1 ID. y Link Layer or Level Link layer as reported by last transmission from ID. The value displayed in the table will be incremented by 1 if the signal quality is not good or if faults are reported by the ID. Link layer is the number of hops a data packet would need using the ID as first in the route, assuming all IDs in the route successfully used their Preference 1 IDs as well. y NetCon An internal rating used in the automatic positioning of this unit in the network. The possible values are 5, 6, or 7. A value of 5 indicates there are two or more paths available. A value of 6 indicates there is one path available. A value of 7 may indicate a problem with this unit or a unit in its path to the IP Link. y Signal Quality The first digit is either an 8 or a 0. 0 means that Carrier Detect (CD) was on during signal reception, while 8 means it was off. CD is related to signal strength where it is on when the strength of the signal is above a certain threshold. The second character is related to readability of the data. A value of 3 is the best, as it indicates that all three of the data repeats were properly read, and a value of 1 is the lowest, as it means that only one of the three was read. Therefore, a good signal would read 03, and a marginal would be 82 or 81. Self-Test Error Codes Status Error Codes A subscriber status error code is displayed in the LCD on the PIC Status screen when the subscriber unit fails the diagnostic self-test. Self-test is performed as part of the power-on sequence of the subscriber. When an error code appears, press the Reset button located on the subscriber board to see if the problem clears (refer to Figure 28 on page 58) for the Reset button location. If the error code does not clear, use the procedure below based on the error code that is displayed. Table 14: Status Error Codes Status Error Code Error Code Description Procedure 001 Battery power is low Check the battery. Press the subscriber RESET button. 002 RAM Checksum Failure Press the RESET button. See note below. 003 Problems 01 and 02 above 004, 006 EEPROM Failure Press the RESET button. See note below. 008 Analog Digital Converter/ADC Failure Same as 004/006 failure. See the procedure above for 004/006.

58 ULF Integrated Fire Monitoring System Table 14: Status Error Codes Status Error Code Error Code Description Procedure 080 Loopback Test Failure Press the RESET button. Unit will likely pass self-test when this is done. See note below. 100 AC Not Present Check AC power input and transformer. 200 Battery Charge Fail Unit may need servicing. 300 Combination of error code problems 100 and 200 Unit powered up by battery alone. If true, you may continue. 400 Ground Fault Ground Fault condition exists on a G terminal of the Zone input section. Other error code displayed. Error code is result of multiple error code numbers added together. Error code of 084 indicates a loopback failure and EEPROM fail ( ). AC fail and low battery would report error code 101. This example and other messages may indicate that the unit requires AES authorized servicing. See note below. Note: If unit passes, it must now be reprogrammed (see "Subscriber Programming"). If unit repeatedly fails the self-test with a message unrelated to AC fail or low battery, service may be required. If you are utilizing the assistance of AES Support, please report the error code to the AES service staff. As a general rule, if the self-test fail is not related to low battery, AC, battery charger, or ground fault, then verify that any ICs installed in sockets are properly seated. If the fault is still present, the subscriber will need to be returned to AES for service. Status Indicators and Subscriber Reset Button Four LED indicators are located on the circuit board of the 7788F. The LEDs are located near the top edge of the circuit board next to the J1/Programmer connector and the Reset button. The indicators are visible in the cabinet on the right side of the mainboard panel. The photograph in Figure 28 shows the location of the LEDs and Reset switch (Figure 29 shows a graphic representation of the Subscriber Status Indicator LEDs and Reset button). Figure 28. Subscriber Status Indicator LED and Reset Button Location

59 7706-ULF Integrated Fire Monitoring System 59 The function of each LED indicator is described below: Table 15: LED Indicators LED Color Function TX Yellow Illuminated indicates radio transmit. RX Green Illuminated indicates radio transceiver receiving RF signal. Steady on for 20 seconds or more indicates RF interference (includes any radio activity on this frequency strong enough to break squelch). WA Yellow Steady On = Waiting for acknowledgment of last transmission Steady Blinking = Not on Network; Off = Normal ALM Red Status/troubleshooting indicator; see Figure 18 for interpretation of blink patterns. Figure 29. LED Indicators Table 16 shows the various blink patterns utilized by the ALM LED and the status conditions indicated by the blink pattern. Blink Pattern 1 sec. Meaning Table 16: ALM LED Blink Patterns Steady blink system OK Short-short blink low battery Short-long blink an input zone is in alarm or trouble Short-short-long blink, low battery and zone in alarm/trouble Steady/no blink Self-test failure (excluding low battery) Symbols as follows: " " = short blink, " " = long blink Period between patterns is about 1 second with chart showing pattern repeated 3 times. Test for expected signals arrival at the monitoring system. Perform the tests below and confirm that the monitoring system and personnel received the correct messages and understand what they mean.

60 ULF Integrated Fire Monitoring System Section 8. Control Panel Programming This section addresses programming options and their parameters, provides an overview of the programming process, and addresses how to use the two programming methods: (1) the LEARN function and (2) the remote computer programming process. The LEARN function allows the addition and removal of remote annunciators. This section also includes procedures on uploading and downloading configuration data using the panel configuration software. Please refer to this section to learn how to navigate within the software, access and modify programming settings, such as the system clock, displaying events, and programming optional remote annunciators or the IP Communicator, if installed. Programming Options NOTICE To users, installers, authorities having jurisdiction, and other involved parties: This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below. Table 17: Programming Options Topic Feature or Option Permitted in UL (Y/N) Possible Settings Setting(s) Permitted in UL864? Comment Misc Idle LCD Message Y Yes/No All settings allowed Misc Misc Misc Misc Misc Misc Misc Display Events Waterflow Delay AC Report Delay DH Low AC Dropout Delay Auto Test Time Strobes Active When Silenced Display AM/ PM Misc Time Zone Y Y Initial Event Newest Event Initial Event Y seconds 0 90 seconds Y 0 30 hours 1 3 hours Y No delay, 15 seconds, 1 minute, 5 minutes All settings allowed Y Time of Day All settings allowed Y Yes/No All settings allowed Y AM/PM, 24 hour All settings allowed 24 Time Zone Selections All settings allowed Misc DST Enabled Y Yes/No All settings allowed Auto display of first event For UL864, use 1 3 hours Misc DST Start Y Month/Day All settings allowed Misc DST End Y Month/Day All settings allowed

61 7706-ULF Integrated Fire Monitoring System 61 Topic Feature or Option Permitted in UL (Y/N) Zone Zone Style Y Table 17: Programming Options Possible Settings Alarm Supervisory Auxiliary Fire Drill System Alarm System Supervisory Setting(s) Permitted in UL864? All settings allowed System Trouble Zone Silenceable Y Yes/No All settings allowed Comment Zone Silence Inhibit Y Yes/No All settings allowed Zone Auto Silence Y Yes/No All settings allowed Zone Auto Unsilence Y Yes/No All settings allowed Zone Restore Delay Y seconds Full range allowed Zone Latching Y Yes/No All settings allowed Zone Local Y Yes/No All settings allowed Zone Output Pattern Y Input Point Dry Contact Input Functions Y Constant ANSI Temp 3 March Code Double Time Water Flow, Pull Station, Supervisory, Tamper, Fire Drill, Trouble Monitor, General Alarm, Conventional Smoke, Conventional Heat All settings allowed Input Point Supervisory Y Yes/No All settings allowed NAC Function Y Potter/AMSECO Sync Gentex Sync System Sensor Sync Wheelock Sync General Purpose All settings allowed Applies to all input points and circuits. Specifies use of NAC circuit Subscriber Daily Test Call Y Any time of day All settings allowed Subscriber Subscriber Control Panel Daily Test Call Reporting Delay Y Any time of day All settings allowed Y 0 80 seconds seconds

62 ULF Integrated Fire Monitoring System Table 17: Programming Options Topic Subscriber Feature or Option Enable Repeating Status Reports Permitted in UL (Y/N) AUX Function Y Possible Settings Setting(s) Permitted in UL864? Y Y/N Y N Alarms, Troubles, Supervisory Test & History Constant* Y Comment * Default, fixed setting. AUX output is dedicated and unavailable for external accessory use. PIC Config Modes Y Y/N Y Programming Display Y USA/Canada USA Programming/ System Setup DACT Setup Y N/A Y This feature has been disabled. The DACT cannot be set up. Programming Overview Note: The configuration software below refers to the PFC-6006 which is the control panel portion of the 7706-ULF Integrated Fire Monitoring System. The LEARN function, available through the control panel, is an efficient way to automatically configure remote annunciators. LEARN detects all connected P-Link devices, assigns a name, and selects the applicable device type. The panel configuration software allows custom programming and configuration for all points via a network or remote computer. At the click of a mouse, you may fine-tune device behavior characteristics or create mapping zones for a more sophisticated fire protection system. By using the system software, you will realize the power and flexibility of the PFC-6006 system. (Refer to "Panel Software Overview" on page 77 and "Mapping Zones Overview" on page 91 for details on these procedures.) The Programming Cycle The following approach is recommended for programming the system, if not using the default setup: 1. Install software. 2. Connect Ethernet cable. 3. Upload data to the computer. 4. Program the system. 5. Download configuration file. Note: This approach may eliminate programming errors; however, these are only recommendations.

63 7706-ULF Integrated Fire Monitoring System 63 Software Installation It's easy to install the PFC-6006 software and requires only a few minutes to complete. Once done, the program automatically creates a shortcut icon on your desktop for easy access. The system software is compatible with Windows XP, Windows Vista, and Windows 7 Operating Systems, and it incorporates conventional shortcuts and features (i.e., right-click to display shortcut menus, drag and drop, etc.). The software s flexibility enables you to effectively program individual and/or groups of points. Several examples in configuring a basic fire system are provided in "System Programming" on page 91. Note: The latest version of Microsoft.NET Framework is required. To install the software: y Access the Potter website at and locate the appropriate link to begin the software download. y The default installation directory is C:\ProgramFiles\Potter\Potter Fire Panel Programmer. y You may change the location of the application files. LEARN Programming The LEARN mode enables you to efficiently configure all connected, addressed remote annunciators. Only authorized users may access this function. LEARN generates a list of all remote annunciators, which may be viewed on a remote computer. (Refer to "Configuring Points" on page 97 and "Mapping Zones Overview" on page 91 for details.) To run the LEARN mode: 1. From the control panel, press Enter to display the Main Menu. Press 6 to select Programming. The Enter Code prompt displays. Enter the user code as prompted. Press 2 to select LEARN. The P-Link Initializing prompt displays, and the system begins the initialization process. 2. Results are grouped by device type. If no changes are detected, the prompt No changes displays. Use the down-arrow key to scroll through the results by device type: 1=P-Link Found 2=P-Link Removed Esc=Exit Select Esc when finished reviewing results. The system prompts to save or discard file. 3. Press 1 to save changes; press 2 to discard changes. If option 1 is selected, the Accept confirmation prompt displays. Press Enter to accept or Esc to discard. 4. Press Esc to exit the Programming menu.

64 ULF Integrated Fire Monitoring System Connecting the Computer and Panel This section provides instructions on setting up connectivity between a laptop or networked computer and the control panel. Once this is achieved, you may program your system using the panel configuration software. Note: These instructions are relevant to all system configurations. If your PC connects directly to the panel, any procedural differences are noted throughout. Connecting a Computer to the Panel via a Network 1. Connect the cable to the Ethernet port on the network (or directly to the panel if not using a network). 2. Connect the Ethernet cable to the port as shown in Figure 30 on page 64. L N G LINE 2 IN LINE 2 OUT LINE 1 IN LINE 1 OUT TIP RING TIP RING TIP RING TIP RING - + BATTERY - + NAC - AUX A B P-LINK A- A+ B- B ETHERNET INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 DWG #559-7 Figure 30. Control Panel Showing Ethernet Port

65 7706-ULF Integrated Fire Monitoring System 65 The following series of messages display on the LCD: 7706-ULF Initializing IP 7706-ULF Obtaining IP Notes: y If the Ethernet cable is connected to a PC, you will see the Initializing IP message prior to the Obtaining IP message. y If your PC is connected directly to the panel, the Obtaining IP message displays for approximately 45 seconds, followed by the Private IP message (the Private IP message is not shown here). IP Address Note: The number shown above represents an example of a panel s IP address or identifier used for illustration purposes only. The panel s IP address is unique to each computer/network. Write down the IP address; it is required to transfer programming data between the panel and the computer. 3. The IP configured and IP address prompts alternatively display until configuration is completed ULF IP Configured Note: If Ethernet connectivity is lost, the message Ethernet Lost displays on the panel. This indicates that the Ethernet cable is disconnected at the panel or network (computer) port.

66 ULF Integrated Fire Monitoring System Transferring Data This section provides step-by-step instructions for uploading and downloading data transfers. The transfer icons are located at the top of the Programmer window and are briefly described below. Icons Table 18: Transfer Functions Description Downloads configuration file from the computer to the panel. Uploads the configuration file from the panel to the computer. Uploads the history events file from the panel to the computer. Prints the selected file. The Transfers region is located at the bottom of the Programmer window and lists all completed transfers. This area displays transfer details, including the date and time. You may also access the Transfer shortcut menu from this location to select any of the transfer functions.

67 7706-ULF Integrated Fire Monitoring System 67 The "Transfer" window displays all completed transfers. Figure 31. Example of Programming Window Showing Transfer Icons and Transfer Section Note: Double-click anywhere on the transfer record to view details.

68 ULF Integrated Fire Monitoring System Uploading from Panel to Computer The Upload Configuration File to Computer transfer icon is used to upload the configuration file from the panel to the computer once the LEARN function is completed or whenever points are added to or removed from the panel. To upload programming changes to computer: 1. Click the Upload Configuration File to Computer icon or right-click from the Transfers region as shown Figure 32: Right click anywhere in the transfer window to display the shortcut menu. Figure 32. Example of Transfer Shortcut Menu 2. Click the Add option from the shortcut menu to choose the transfer type. The Transfer dialog box displays. Figure 33. Example of Transfer Upload Dialog Box 3. Verify that Upload is selected in the Transfer Type field.

69 7706-ULF Integrated Fire Monitoring System Enter the configuration filename in the Filename field or leave blank to autoname. Figure 34. Example of Transfer Upload Window Notes: y If you do not name the file, the program automatically names it using the transfer type and date stamp as the file name. y Once the file has been saved, and additional programming changes are made at a later date, click the Browse button to locate the file name to replace the old file with the updated configuration changes. 5. Enter the IP address or panel name in the Transfer Via IP field. Notes: y To capture your panel s unique IP address, disconnect the Ethernet cable from the panel. The message Ethernet Lost displays, indicating connectivity is lost. Be prepared to write down the address, and reconnect the cable. 6. Click OK. The Transfers region displays the uploaded file. Figure 35. Example of Transfers Download Results y Double-click the transfer file to display results. y All points detected during the LEARN process have been uploaded to the panel configuration software. Note: y Details on viewing and configuring points are addressed in detail in "Configuring Points" on page 97.

70 ULF Integrated Fire Monitoring System Downloading Configuration File to Panel The Download Configuration File to Panel icon allows you to copy all programming changes to the panel. Notes: y Be sure to "Enable Remote Access" (Pages 70) at the panel before choosing this option. If your PC is directly connected to the panel versus a network, this step is not necessary. y Verify that the remote user name and password match the panel s user name and password. You will receive an error message when attempting to download data to the panel if they do not match. Enable Remote Access To enable remote access: 1. At the control panel, press ENTER to display the Main Menu. 2. Press 7 to select Data Transfer. 3. The Enter Code prompt displays. Enter the user code to continue. 4. The Select Data option displays. Press 1 to select Remote Access. 5. Press ESC to return to the Main Menu. Note: Once enabled, the remote access will time out after thirty (30) minutes if contact is not established. File New The File New menu option is used to complete all programming from scratch on the computer. You must select the correct panel model prior to programming. Note: It is imperative that you choose the correct panel model prior to programming or completing any data transfers; otherwise, you cannot complete a successful download to the panel. If this occurs, you will have to reprogram the entire panel.

71 7706-ULF Integrated Fire Monitoring System 71 Figure 36. Example of File New Dialog Box File Save / Save As Once programming has been completed, save your configuration file using either the File > Save or File > Save As function. An audit is performed that checks for rule violations; if errors are encountered, you may choose to either save with errors or cancel the save operation. Figure 37. Example of Save Panel Dialog Box Notes: y All site-specific configuration data is stored in the panel s non-volatile memory. y The next time you make programming changes, you may overwrite the original configuration file with changes. If you choose to do this, you will lose the original programming report information. y The panel configuration file has a.fpcf file extension.

72 ULF Integrated Fire Monitoring System Audit Errors The Audit Error - Save anyway? dialog box displays if programming errors are encountered when saving the configuration file. You may choose to save the file with errors; however, you cannot download the data until all errors have been corrected. Figure 38. Example of the "Save anyway?" Dialog Box Downloading a Configuration File To download the configuration file: 1. Click the Download Configuration File to Panel icon or right-click from the Transfers region, then click Add. The Transfer dialog box displays. Figure 39. Example of Transfer Download Dialog Box 2. Verify that Download is selected in the Transfer Type field. 3. Enter the file name in the Filename field or click the Browse button to select the file name. 4. Enter the IP address in the IP field (under Transfer Via).

73 7706-ULF Integrated Fire Monitoring System 73 Note: To capture the panel s unique IP address: 1. Disconnect the Ethernet cable from panel. 2. The message Ethernet Lost" displays indicating connectivity is lost. 3. Reconnect the cable, and write down the IP address shown. Figure 40. Transfer Download Dialog Box 5. Click OK. The Transfers window displays the transfer progress. Figure 41. Example of Transfers Window Showing Download Completed Uploading History Events Status Reports The Upload History File to Computer icon allows you to view valuable information that can be essential when analyzing system operations. You may choose to print the History reports by using the Print icon; reports can be scheduled to be automatically sent to authorized addresses. Refer to "System Functions" on page 82 for details on programming this reporting option. History Reports The Event History transfer option creates a report of all events held in the panel s buffer. Up to 1,000 events are held in the buffer at one time. This information may be used to troubleshoot errors or to assess ways to improve the system configuration. To transfer event history information: 1. Click the Upload History File to Computer icon or right-click from the Transfers area, and click Add. The Transfer dialog box displays. 2. Verify that History is selected in the Transfer Type field, and click OK to display the results.

74 ULF Integrated Fire Monitoring System Figure 42. Transfer Window Results 3. Double-click file to view results. Figure 43. Example of Transfer Results Window Note: Click the Print icon to print a copy of the report. Refer to "" on page 74 for more details. 4. Click the close button to close the report. Note: Refer to "Receiving Status Reports" on page 88 for a sample of a History Events Report sent via .

75 7706-ULF Integrated Fire Monitoring System 75 Printing Reports The Print icon allows you to print History reports. Double-click the History file listed in the Transfer window prior to clicking the Print icon. An example of the Report window, which displays a History report, is shown below: Move the mouse across the Print icons to display their descriptions. Figure 44. Example of the History Report (Print) Window

76 ULF Integrated Fire Monitoring System To print a History Report: 1. Double-click the History report listed in the Transfers window to display the report. 2. Adjust the width of the Event column to display the entire descriptions; otherwise, the Event information will be truncated on the printed report. Tip: Double-click on the Event column's border to automatically expand the width to accommodate the longest description. Refer to the example below. Double-click here to adjust the column width based on the longest event description. Figure 45. Example of the History Report 3. Click the Print icon, then click the Report Print icon or CTRL P to open the Print dialog box. 4. Click the Print button.

77 7706-ULF Integrated Fire Monitoring System 77 Panel Software Overview This section gives you an overview of the Panel Configuration Software. It addresses navigating through the program windows, understanding the purpose of icons and program features, and using Window s conventional editing techniques and other program shortcuts to efficiently configure your system. Window Regions / Areas When you select a function from the Panel window, the related information displays on the right. Additionally, the selected function is highlighted, which helps direct your eye to the function's related screen information. For example, when Remote Access Code is selected, the remote user name and password displays. Please refer to the examples shown in Figure 46 and Figure 47. Figure 46. Panel Menu Options Figure 47. Example of Remote Access Code

78 ULF Integrated Fire Monitoring System Program Icons The panel software uses several standard Windows icons, such as the close button and scroll bars. There are others that are unique to the panel software, such as auto hide and window position which are summarized in the table below: Name Icon Description/Function Table 19: Panel Configuration Icons Window Position Located in the upper right region of some windows. Click the icon to choose an option: Floating Window floats over other windows; right-click title bar to reselect dockable. Dockable Default window position; window is locked in place. Auto Hide Window is hidden when cursor is moved and tab displays as window placeholder; point to window tab to redisplay (window tab is explained below). Shortcut to hide a window. Auto-Hide Click to hide window. Icon changes to (insert window autohide if window is hidden. Click to unhide and dock window. Displays if window is hidden; available for specific windows only. Note: Tab name is specific to the hidden window. Point to tab to display window. Point or click in another window to hide. Window Tab Tab

79 7706-ULF Integrated Fire Monitoring System 79 Table 19: Panel Configuration Icons Name Icon Description/Function Available in Zones and Points windows only. Click the "plus" sign to expand. Click the "minus" sign to collapse. Expand/Collapse Programming Functions Overview The table below gives you a snapshot of the menu order along with a brief description of each. Details for these options are provided on the following pages. Table 20: Programming Menu Overview Menu Option Remote Access Code Job Details General Options Zones Points Reporting Reminders Users LAN Settings Dialer Annunciators Description Displays remote access User Name and Password. Allows site-specific information to be entered. Allows software s general panel settings to be customized. Define and configure zone s characteristics and mapping points. Define and view all addressable and non-addressable points. Schedule reports by day and time, set up addresses, and select type of report(s) to send to each addressee. Create and schedule customized daily, weekly, monthly, or yearly reminder s. Create up to ten (10) user codes and passwords, and set access rights. Configure Ethernet connectivity options. Note: The DACT is not used and this feature is not supported on the 7706-ULF Integrated Fire Monitoring System. Add or remove remote annunciators.

80 ULF Integrated Fire Monitoring System Remote Access Code The Panel Configuration window displays the remote access user name and password on the right section of the screen (refer to the example shown below). Figure 48. Example of the Panel Configuration Screen User Name / Password The default user name and password is Potter as shown below; they can be changed to ensure that only authorized personnel can transfer data to and from the panel. Figure 49. Remote Access Code Screen Notes: y The remote access user name and password may be changed to increase security on the system. y The remote user name and password must match the panel s user name and password.

81 7706-ULF Integrated Fire Monitoring System 81 General System Functions Job Details Site-specific information, such as company name, address, and phone numbers, may be entered in this window. This information is stored in the panel and is used to identify the panel when using reporting options. Please refer to the figure shown below. To enter site information: 1. Click the Job Details program option. The Job Details window displays. Figure 50. Job Details Window 2. Click in each applicable field to enter information. Note: You may also press the Tab key to move to the next field.

82 ULF Integrated Fire Monitoring System NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. System Functions The PFC-6006 comes with built-in capabilities. The panel automatically sends status s, including Alarms, Troubles, Supervisory, and Test events, to the addresses designated on the Reporting window as shown below. If selected, Event History Reports will be sent based on the weekly schedule, time and day of the month indicated here. Alarm, Trouble, Supervisory and Test Events are sent immediately as they occur! Figure 51. Reporting Window Event History reports may be scheduled to be sent on specific days of the week, time, or day of the month. Up to twenty (20) addresses may be programmed on this screen. After the Reporting section is completed and downloaded into the panel, the panel will start sending s according to programming. The panel is capable of sending automatic and on-demand reports because it has a designated outgoing address comprised of its model and serial numbers. On-demand reports can be requested directly from the panel's Data Transfer function or remotely from a PC, if the user has a valid address programmed on the Reporting window. The panel address is structured as PFC6XXXXXXXXXXX@potterlink.com, where PFC6XXXXXXXXXXX refers to the panel serial number. The serial number is the same as the NetBIOS name, and is located on the panel as shown below. Note: Outgoing panel s are routed through a dedicated Potter server. You must make a notation of your panel's outgoing address in order to send requests remotely.

83 7706-ULF Integrated Fire Monitoring System 83 NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. Panel Serial Number BAR CODE PFC6xxxxxxxxx DWG # Figure 52. Panel Serial Number Location P-Link Notification Requirements The following table lists the necessary hardware and Internet connectivity requirements to use P-Link functions, such as notification. Item Hardware IP Address Protocol Outbound Connectivity Inbound Connectivity Table 21: P-Link Notification Requirements Requirement 10/100 Mbps Ethernet Network DHCP or Static IP (factory default is DHCP) Must have outbound access to Internet (mail server connections only). Port for SMTP Port 110 for POP3 None required or utilized.

84 ULF Integrated Fire Monitoring System NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. Connecting the Panel to a Network In order to use the feature, the panel must be connected to a network with Internet connectivity. This is usually accomplished by installing an Ethernet drop near the panel. The IP address can be set one of two ways: y The panel has a built in DHCP (Dynamic Host Configuration Protocol) and will ask for an IP address from the host computer. y The installer or the Network Administrator may set the IP address using the software's Static IP function. Set the IP address using the DHCP function...or Set the IP address using the Static IP function Figure 53. Setting the IP Address Report Programming To set up History reports schedule: 1. Click on the Reporting option. The Reporting window displays. 2. Click in the reports on these days selection box to choose the days that the History report(s) will be sent. 3. Adjust time, if necessary. Select a day of the month if you wish reports to be sent on a specific day of each month. Note: Be sure to select each report type in the next section for each recipient you wish to send these reports.

85 7706-ULF Integrated Fire Monitoring System 85 NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. To set up addresses and select events and/or reports: 1. In the address section, as shown below, enter up to twenty (20) addresses, if needed. 2. Select the Enable Requests option if the addressee may request reports from the panel. Note: If Enable Requests is not selected, the panel will ignore request for an on-demand report. 3. Select each type of event(s) and/or report(s) you wish to send to the applicable address. 4. A checkmark displays in each selected report type. Important Note: The "Enable Requests" option must be selected in order for the panel to respond to an addressee requesting an ondemand report. Figure 54. Reporting showing Enable Request Sent from Panel To send a report from the panel: 1. Select Data Transfer (Menu Option 7) on the panel menu. 2. Select one of the transfer options as described below: Option 1=Remote Access 2= History 3= Config 4= Test 5=Server Status Table 22: Data Transfer Options Description Used to enable remote access Allows user to a history file Allows user to a panel configuration file (.fpcf) Allows user to send a test Allows server status to be verified

86 ULF Integrated Fire Monitoring System NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. 3. Select one or more addresses using one of the following options: y Choose Use Default to select the address entered in General Options (as shown below). y Choose Browse List to scroll through and select one or more addresses entered in Reporting. y Choose Specify New to enter additional addresses, if needed. Use the Default outgoing address. Figure 55. Example of the General Options Window - Default Outgoing Address Report Requested from PC To request a report from a remote PC: 1. Open or create a new In the To field, enter the panel's address as shown in Figure 56. (Refer also to "Figure 52. Panel Serial Number Location" on page 83.)

87 7706-ULF Integrated Fire Monitoring System 87 NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. Figure 56. Example of Keywords in Subject Field 3. In the Subject field, enter one or more of the following keywords: y History to send a current event history report back to sender. y Configuration to send a current configuration file back to sender. y Unsubscribe to stop the current settings for the sender until panel is reset or that address sends a Subscribe to the panel. y Subscribe to activate settings for the sender. Note: Keywords are NOT case sensitive, and more than one can be entered in the subject line of the There are no restrictions on contents entered into the body of the . Important! The person sending the must be added to the list in the Reporting section of the software as shown below. If the sender is not in the list, the panel will not respond.

88 ULF Integrated Fire Monitoring System NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. y The Enable Requests option must also be checked for the sender to receive s when requested from the panel or a remote PC. Note: You may choose not to select a specific event type or report for an address. If so, choose Browse List from the Data Transfer panel menu option. Then scroll through addresses and select one or more recipients. Sender's must be in the list and the Enable Requests box must be checked! Figure 57. Reporting Window Receiving Status Reports When a system status (Alarm, Supervisory, Trouble events) is received, the body of the contains the information entered in the Job Details section of the software (as shown below). If nothing is entered in the software, the body of the will indicate only the events that occurred. The events are listed after the Job Details information. They are formatted with a date/time stamp showing when the event occurred, event type, and the event description or the point information. Job Details display here Figure 58. Example of Job Details in System Status

89 7706-ULF Integrated Fire Monitoring System 89 NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. When a history status is received it contains two attachments: A text file (.txt) A comma separated values (.csv) file Figure 59. Examples of a History text file (.txt) & History Comma Separated Value file

90 ULF Integrated Fire Monitoring System NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. Creating Reminders reminders are fully customizable messages that may be sent based on a predefined schedule. The subject and body are defined by the installer, and they may choose to attach the History reports. Up to eight separate reminders can be created to be sent on a daily, weekly, monthly, or yearly schedule. Figure 60. Example of the Reminder Window To create Reminder s: 1. Select the Reminders option on the panel menu. 2. Click a Schedule option, i.e., Yearly, Monthly, Weekly, or Daily. 3. Select the specific scheduling frequency, i.e., "days to send" for a weekly reminder or "time" for a daily reminder. 4. Click the Attach History selection box, if needed. 5. Complete the following information: y In the To field, enter up to 20 addressees. y In the Subject field, enter an applicable subject. y In the Body field, enter up to 2000 characters, if needed.

91 7706-ULF Integrated Fire Monitoring System 91 NOTICE System communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. communications should NOT be used as a primary means of reporting emergency information. Figure 61. Example of Creating a Daily Reminder 6. Continue setting up additional reminders if needed. System Programming System programming involves defining the function of points and their relationships to each other, referred to as "mapping." You can define behavior characteristics of individual or groups of points, map points into zones, and further customize your system using the panel configuration software from a computer. The panel configuration software features include: y Easy-to-use Windows-based editing techniques, including drag and drop between windows. y Flexibility in configuring points into multiple zones, promoting sophisticated mapping relationships. y Simple sorting and grouping by select fields enhances viewing and analysis of data. y Options to view points by type, address, and function or description. Mapping Zones Overview Mapping is creating relationships between points, modules, and sensors and their behavior between each other. Whereas, the zone is the framework in which you group the points. These terms and other related mapping concepts are provided in this section. Single Zones The LEARN feature creates or maps a basic, one-to-one relationship where all points are automatically grouped into one zone. When all points are in the same zone, and an input device is activated, all output points will activate. An example of a one-to-one device relationship is shown in Figure 62:

92 ULF Integrated Fire Monitoring System Zone Symbol Legend: = Input Point = NAC = Panel Hardware Figure 62. Mapping all Points to One Zone Multiple Zones The panel configuration software allows you to customize the operational mode behavior of points by grouping them into a maximum of thirty (30) different zones. All input points, including the one (1) on-board NAC circuit (NAC 1), may be configured to behave in a specific manner. This flexibility enables you to configure system points to maximize protection throughout your site. By organizing points into different zones, you can create unique relationships between points for specific outputs or events. The panel configuration software allows you to efficiently group points to follow a sequence of events producing the same combination of outputs into different zones. This section addresses how to accomplish these tasks.

93 7706-ULF Integrated Fire Monitoring System 93 Mapping Terminology The table below provides mapping terms that may be helpful to you in understanding the mapping concept: Term Mapping Zone Table 23: Mapping Terminology Definition Creating relationships between points, modules, and sensors and defining their behavior. A group of points. Zones may represent a group of points located in a specific physical area at the site. Example: Zone 1 comprised of all alarm devices for a sprinkler system [i.e., pull station #1, one (1) water flow device, and one (1) strobe-nac]. Zones may represent a set of points configured for a specific function; their location may be scattered throughout the site. This group is a logical grouping or zone. Example: Zone 2 comprised of all points in Zone 1 as described above, plus a second pull station located at the end of a hallway and two (2) additional smoke detectors. Notes: y If all input/output points are grouped into one (1) zone, when any input is activated, all outputs activate. y A device or point may be mapped into more than one (1) zone. Point Latching Non-Latching Any specific initiating device circuit (IDC) or appliance connected to the panel. Device will not automatically reset; device must be reset at the keypad to remove condition. Device will automatically reset when trouble and supervisory condition is no longer present. Zone Types / Styles You may define or configure each zone to serve a specific purpose or to create specific output results. For procedures on how to select Zone styles, refer to the Configuring Zones section of this manual. The following zone styles are available: Alarm Zone Table 24: Zone Styles Description Default zone type; sets system into an Alarm condition when any input is activated. Supervisory Auxiliary Fire Drill System Alarm System Supervisory System Trouble Used for all Supervisory inputs. Used for all Aux inputs. Comprised of input / output points that will activate when running a Fire Drill. Used for outputs that will be activated upon any alarm. Used for outputs that will be activated upon any supervisory. Used for outputs that will be activated upon any trouble.

94 ULF Integrated Fire Monitoring System Zone Attributes Zone attributes are the settings that control the overall behavior of points within the zone. The zone may be configured as latching or non-latching, silenceable or non-silenceable, among other attributes. Tip: Double-click in a field to modify an applicable field, i.e., zone name or alarm count. Click in fields with a selection box to select or deselect the option, i.e., silenceable or latching. All zones default to an Alarm style or type when first created. The figure shown below is an example of the default attributes of an "Alarm" zone. Figure 63. Example of Zone Attributes (Fields 1 5) Refer to Table 25 for a brief explanation of zone attributes: Table 25: Zone Attributes Attribute Zone Name Default = Zone x (where x is a sequential number) Description Zone name may be up to sixteen (16) alphanumeric characters. Available for one (1) count zones only. Latching / Non-Latching Default = Latching Local / Non-Local Default = Non-Local Output Pattern Default = Constant Latching zone requires operator to press Reset. Non-latching zone will automatically turn off outputs when condition clears. Used only for the Report by Zone option. Allows a zone to be specified as a non-reporting zone. Defines the output pattern of general-purpose NAC circuit in the zone that occurs during alarm conditions. Click on the drop-down arrow to display and select an option: Constant ANSI Temp 3 March Code Double Time 24 VDC.5 sec on,.5 sec off,.5 sec on,.5 sec off, 5 sec on, 1.5 sec off 60 signals per minute 120 signals per minute Auto-Silence Timer Default = 0 minutes Range = minutes Defines the amount of time before silenceable NAC is automatically shut down.

95 7706-ULF Integrated Fire Monitoring System 95 Table 25: Zone Attributes Attribute Auto-Unsilence Timer Default = 0 minutes Range = 0 60 minutes Silence-Inhibit Timer Default = 0 minutes Range = 0 60 minutes Restore Delay Default = 0 seconds Range = seconds Description Defines the amount of time before any silenced NAC is reactivated; output only reactivate if panel is still in alarm. Defines the amount of time you may not silence an output when in alarm. Defines the amount of time before deactivating an output when the panel is reset. Creating Zones When creating zones, you may create one or more at a time. This section explains this process and includes examples for your convenience. To create a zone: 1. In the Zones window, right-click on any zone name. The shortcut menu displays. 2. Click Add Zones. The Add Multiple Zones dialog box displays. Figure 64. Examples of Adding Multiple Zones Dialog Box 3. In Number of Zones field, enter the number of zones to create. Note: You may enter up to thirty (30) zones. 4. In the Starting Zone Number field, enter the zone number to begin numbering zones, if different from default.

96 ULF Integrated Fire Monitoring System 5. Click OK or Cancel to exit the dialog box. The zones window lists all new zones. Figure 65. Zones Window 6. Go to the Zone Configuration window to view all available zones. Figure 66. Example of Configuring Multiple Zones Configuring Zones The next step is to customize a zone s attributes, which includes changing the name, selecting type of zone, and other characteristics (i.e., constant, double time output pattern, latching or non-latching, silenceable, auto-silence timer, etc.). To configure a zone: 1. Double-click in the zone s Name field to modify the default name. Note: Up to sixteen (16) alphanumeric characters may be entered. For example: Sprinkler Flow or Valve Tamper. 2. Click in the Style field. Click the drop-down arrow to display the zone styles. 3. Choose the applicable zone style (refer to Table 24 on page 93 for descriptions of zone styles). 4. Continue editing the zone s fields (refer to Table 25 on page 94 for field descriptions).

97 7706-ULF Integrated Fire Monitoring System 97 Configuring Points This section addresses how to define or configure points through the Points function. Each device may have a unique function in relation to the zone as well as the entire system. The user determines the Point's role, specific behavior characteristics, and customizes its name, if desired. Notes: y The list of available functions is associated with the device type. y Points may be configured from either the Zones or Points functions; however, for purposes of this manual, points are configured in the Points function. y Points can be configured individually, or by groups or ranges of points. An example of the Points window is shown below. Figure 67. Example of Points Window Input Circuit Functions The IDC's ("Conventional Inputs") default to specific functions as shown in Table 27; however, they may be reconfigured and renamed, based on the following configuration functions: Function Contact Input Pull Station Contact Input Water Flow Contact Input Supervisory Contact Input Tamper Contact Input Fire Drill Contact Input Trouble Monitor Contact Input Aux Table 26: Input Circuit Functions Description Pull station input. Water flow input obeys water flow delay as defined in General Options. Supervisory input. Tamper input reports as supervisory. Fire drill input activates a fire drill. Trouble input creates a trouble condition. Aux input reports as un-typed alarm.

98 ULF Integrated Fire Monitoring System The six (6) Input or Initiating Device Circuits (IDC) automatically default as follows: Table 27: Input Circuit's Default Configuration Input Circuit Default Function Input 1 Water Flow Input 2 Input 3 Inputs 4 and 5 Input 6 Smoke Detector Manual Pull Supervisory Valve Tamper NAC Functions The on-board NAC circuit (NAC 1) is automatically configured as Conv NAC General Purpose," but may be reconfigured to other functions, as described in Table 28. Function General Purpose Potter Sync Gentex Sync System Sensor Sync Wheelock Sync Table 28: NAC Circuit Configuration Functions Description General purpose NAC; obeys zone output pattern programming, and is the default. Drives Potter synchronized horns/strobes. Drives Gentex synchronized horns/strobes. Drives System Sensor synchronized horns/strobes. Drives Wheelock synchronized horns/strobes. AUX Functions The on-board AUX circuit in the 7706-ULF Integrated Fire Monitoring System is configured to Conv NAC Aux Constant." and cannot be changed. The AUX power circuit is unavailable for external accessory use. Refer to System Size Specifications section. Function Conv NAC Aux Constant Table 29: AUX Circuit Configuration Functions Description Constant DC power; this is the default configuration for the 7706-ULF Integrated Fire Monitoring System and cannot be changed.

99 7706-ULF Integrated Fire Monitoring System 99 To configure a single point: 1. Click on the Points function to display the Points Configuration window. Figure 68. Example of a Configuration Window Showing Conventional Input Functions Notes: y Points are listed by device addresses automatically. You may sort points by clicking on the column or field name, i.e., Name, Function, or Supervisory. Example: Click the Function field to sort points alphabetically by device function. y The list of available functions varies according to type of device(s) selected. y If you click the Supervisory field selection box, this designates that the contact will be a supervisory input versus an alarm input. 2. Click anywhere on the point you wish to configure. Tip: The selected point is highlighted in blue and is also designated with an arrow symbol at the beginning of the point's line, as shown below. 3. Double-click in the Name field to enter a descriptive name, if wanted. y Enter up to sixteen (16) alphanumeric characters.

100 ULF Integrated Fire Monitoring System 4. Click the drop-down arrow at the end of the Function field to display the list of options. Figure 69. Example of Configuring a Single Point 5. Continue configuring other points, as needed. To configure a range of points: 1. Click the first point to configure from the Function field. 2. Press and hold the SHIFT key, then click in the Function field of the last point. Figure 70. Example of Configuring a Range of Points 3. Right-click from the Function field to display the configuration options. Notes: y If you right-click outside of the Function field, the range is deselected, and only one (1) point will be configured. y You may alternatively use the CTRL key to select multiple, non-adjacent points. 4. Click on device function from the shortcut menu. 5. Continue configuring other points, as needed.

101 7706-ULF Integrated Fire Monitoring System 101 Adding Points to Zones This section provides procedures and examples of adding points to one or more zones. Points can be moved and deleted from zones through the Zones panel by dragging and dropping. The examples shown in Figure 71, Figure 72, and Figure 73 illustrate how to use shortcuts to expedite configuring zones and to also reinforce the interaction between the Zones and Points windows. To move one or more points into one zone: 1. Open the Zones configuration window and adjust the Points window to display full function name(s). Points 4, 6, and 7 are selected. Figure 71. Example of Resizing Points Window From Zone Screen 2. Click one or more points to select; use the SHIFT or CTRL keys to select a range or group of points. 3. Drag and drop the selected points from the Points window to the Device window. The selected points display in the Device window, as shown below. Points 4, 6, and 7 are configured into Zones 2 and 3. Figure 72. Example of Configuring Multiple Points into Multiple Zones

102 ULF Integrated Fire Monitoring System 4. Click + in the Points window to display point assignment by zone(s). Figure 73. Example of Expanding Point s Zone Assignment(s) Note: Click to collapse point assignments.

103 7706-ULF Integrated Fire Monitoring System 103 Group by Area You may group information by different fields in many of the program windows. This flexibility is helpful when configuring or viewing a large amount of information, such as all points, zones, or remote annunciators. Examples are included for illustration purposes only. To group by area (field): 1. Click on the Group bar located at the top of the window, if available. Click here to display "Group By Area". Figure 74. Example of Points Window The group by area prompt displays, as shown in Figure 75. Figure 75. "Group by Area" Prompt Note: Click the group by area" bar at any time to collapse region.

104 ULF Integrated Fire Monitoring System 2. Drag and drop one field into the group by area region. The information is displayed according to the selected field. Figure 76. Example of Points Grouped by Function Note: Click + next to the function to view a complete list of points. Click - to collapse the list of points, as needed. Figure 77. Example of Expanded List of Grouped Points Note: Click to collapse point assignments. 3. Drag the field out of the group by area region to redisplay items in original order.

105 7706-ULF Integrated Fire Monitoring System 105 Programming Points and Appliances This section addresses how to program the P-Link appliances and points, including the RA 6075 annunciators. Notes: y The 7706-ULF Integrated Fire Monitoring System does not support DACT communication. y A daily test is automatically sent to a remote monitoring location; the test time may be programmed through the General Options program window (in the Time to Send Autotest field). Reporting Accounts Note: The DACT feature is not supported on the 7706-ULF Integrated Fire Monitoring System. Remote Annunciators The 7706-ULF supports one (1) RA-6075 remote annunciator. To add and configure a remote annunciator: 1. Select Annunciators from the system panel. 2. Click the Add Device button to display the Add Device window. Figure 78. Example of Add Device Window 3. Double-click in the Name field to customize the name. 4. Double-click in the Address field to adjust the address, if needed. Note: Only one (1) annunciator may be connected to the system.

106 ULF Integrated Fire Monitoring System Verify Input and Output Points The 7706-ULF System input and output points can be verified using the keypad and LCD display after panel installation and configuration. Use the following instructions to access and view key information. 1. At the 7706 ULF Main menu screen, press 5, then press ENTER. The program access screen appears ULF 11/10 8:33:03AM Enter Code 2. Press 1111 as the access code. A series of * s display for each number pressed. Enter Code **** 3. From the Tools menu, press 1 for Point Control. Tools Menu 1=Point Control 4. From the Select Device screen, press ENTER. Select Device Internal PWR 5. Press ENTER at the Ckt (Circuit) screen (circuit 1 has been identified as the default point to examine). Enter Ckt: 1 The point detail appears for selection 1, which is shown configured for a NAC. NAC:GEN PURPOSE 001 NORMAL 6. Press ESC to return to the Enter Ckt screen, and enter the next point number to examine using the keypad. If no more points need examination, press ESC again to return to the Tools menu.

107 7706-ULF Integrated Fire Monitoring System 107 Examine Firmware Versions Firmware versions used in the 7706-ULF System are visible through the LCD on the keypad. LCD Control Firmware The LCD control firmware drives the LCD display on the keypad. To view the firmware version of the LCD control, power on the panel. The firmware version is visible on the first screen displayed after power-up self-test is complete: VX.XX where X.XX is the firmware version 7788F Subscriber Firmware To view the 7788F Subscriber firmware version: 1. From the Main Menu display, press 5, then press Enter to access the System Tools menu. The Enter Code prompt displays. 2. Enter the user access code (1111). 3. At the System Tools menu, press 8 to select PIC Status. You are now in the PIC Menu. 4. Press 1 to select PIC Status. The screen displays the firmware for the 7788F Subscriber: Type: SUB XX.XXXX 7788F where XX.XXXX is the firmware version Mainboard and 7764 PIC Firmware To view the mainboard and 7764 PIC firmware version: 1. From the Main menu display, press 5, then press ENTER to access the System Tools menu. The Enter Code prompt displays. 2. Enter the user access code (1111). 3. At the System Tools menu, press The screen displays the firmware version for the mainboard: Control VX.XX where VX.XX is the mainboard firmware version 5. Press the DOWN ARROW. The screen displays the firmware version for the AES 7764 PIC. AES PIC VX.XX where VX.XX is the AES 7764 PIC firmware version

108 ULF Integrated Fire Monitoring System Appendix A. Basic Operating Instructions These instructions must be framed and displayed next to the 7706-ULF panel in accordance with NFPA-72 fire code for Local Protected Fire Alarm Systems. Test the system in accordance with NFPA-72. Table A-1: Control Panel Function Keys Description Function Keys ACKNOWLEDGE ARROW KEYS FIRE DRILL ESC RESET SIGNAL SILENCE Table A-2: Operating Instructions Operation Task Silence Alarms, Troubles Press the SIGNAL SILENCE key. Acknowledge Alarms, Troubles Reset Alarms View Alarms, Troubles Press the ACKNOWLEDGE key after scrolling down to new event. Press the RESET key. Press the arrow key(s) to view alarms/troubles. Conduct a Fire Drill Press the FIRE DRILL key; press the RESET key to exit Drill mode. View Point s Status Press ENTER to display the Main Menu. Press 5 System Tools; enter the panel s code. Press 1 Point Control. Press ENTER to select Point. Enter Addr/Ckt No. and press ENTER. Press Up/Down to view previous/next points.

109 7706-ULF Integrated Fire Monitoring System 109 Table A-2: Operating Instructions Operation Set Date/Time Enable/Disable Point View Event History Press ENTER Main Menu. Press 3 Set Date/Time. Task Use the keypad to enter correct date; use right-arrow key to move through the date field and to display the time field. Press ENTER to save changes. Press ENTER Main Menu. Press 2 Enable/Disable; enter panel s code. Press 1 By Point. Enter Addr/Ckt No. and press ENTER. Press Up/Down to scroll. Point s current status displays Normal (if enabled) or Disabled. Press ENTER to change status; press ENTER to save or ESC to exit without saving. Press ENTER Main Menu. Press 1 View History. Press left/right arrow keys to view next/previous events. Press the up/down arrow keys for a list of events. Press ESC to exit. For Service Call:

110 ULF Integrated Fire Monitoring System Appendix B. System Maintenance and Testing Acceptance Test The control panel is required to be installed in accordance with local and state building codes and NFPA-72 (National Fire Alarm Code). At the conclusion of each original installation or modification of this system, the control panel and related system is required to be inspected and tested in accordance with NFPA-72 to verify compliance with the applicable standards. Testing should be conducted by trained fire alarm technician(s) from Potter factory in the presence of a representative of the Authority Having Jurisdiction (AHJ) and the building owners representative. Refer to NFPA-72 (National Fire Alarm Code), Inspection Testing and Maintenance code. Periodic Testing and Service Periodic testing and maintenance of the control panel, all initiating points, all notification appliances, and any other associated equipment is essential for ensuring that the system will operate as designed in emergency situations. Service and test the control panel according to the schedules and procedures outlined in the following documents: y NFPA-72, Inspection, Testing, and Maintenance. y All test and maintenance should be performed in accordance with any requirements of the local authority having jurisdiction. y Service manuals and instructions for any and all peripheral points installed in the system. It is very important that any and all trouble conditions (or faults) be corrected immediately. Operational Checks During interim periods between formal testing and at regular intervals, the control system should be subjected to the following operational performance checks. The Authority Having Jurisdiction (AHJ) should be consulted for requirements on frequency of system testing. y Check that the green AC power LED is lit. y Check that all amber LEDs are off. y Using the system menus, perform a Lamp Test function. Verify that all LEDs and LCD segments operate. y Before proceeding, (1) notify the fire department and the central alarm receiving station if transmitting alarm status conditions, (2) notify facility personnel of the test so that alarm-indicating points are disregarded during the test period, and (3) when necessary, bypass activation of alarm notification appliances and speakers (if installed) to prevent sounding of evacuation signals. y Activate an input device (i.e., manual station, heat, or smoke detector), and check that all notification appliances function. y Notify Fire Department, central alarm receiving station, and /or building personnel when finished with testing the system. y The test of ground fault must be measured below a 10-kohm impedance.

111 7706-ULF Integrated Fire Monitoring System 111 AC Fuse The control panel has one fuse on the board for the AC power over current protection. The AC fuse is rated at 1.6A to 250 VAC time lag and screened onto the mainboard as F2. Battery Fuse The battery fuse is rated at 2.5A to 250 VAC time lag and screened onto the mainboard as F1. Battery Maintenance The system has been designed to use maintenance-free sealed lead acid batteries. These sealed lead acid batteries do not require any additional water or electrolytes. The system will keep all batteries fully charged by the system's power supply modules float charger. A typical discharged battery will recharge at 0.5A and reaches the voltage of 27.3 VDC within 48 hours. The battery is to remain in the cabinet with nothing on or around the batteries. Replacement and Testing Recommendations The batteries are to be replaced at least once every four years, or more frequently if specified by local AHJ and manufacturer recommendations. Batteries should be dated at the installation. Minimal replacement battery capacity displays on the control panel marking label. The batteries are required to be UL-recognized batteries with a date of manufacture permanently marked on the battery. The battery is to be tested at least annually and if the battery is showing signs of failure, it should be replaced. Immediately replace a damaged or leaking battery, and always replace batteries in pairs. Proper Handling/First Aid Procedures y In the event a battery leaks and contact is made with the sulfuric acid, immediately wash skin with water for at least 15 minutes. Water and household baking soda provide a good neutralizing solution for sulfuric acid. y If sulfuric acid makes contact with eyes, flush with water for 15 minutes and seek immediate medical attention. y Ensure proper handling of the battery to prevent short circuits. y Take care to avoid accidental shorting of the leads from uninsulated work surfaces, tools, jewelry, and coins. y If a battery is shorted, the battery and any connected equipment may be damaged. Additionally, a short may injure personnel.

112 ULF Integrated Fire Monitoring System Appendix C. Device Compatibilities This section provides a listing of all NAC appliances, two-wire (2-wire) smoke detectors, and remote annunciator device compatibilities. Module/Device Compatibilities NAC Appliances Two-Wire (2-Wire) Smoke Detectors Refer to Potter document: NAC Compatibility Document Refer to "Appendix D. Compatible Smoke Detectors Table" for a complete listing of two-wire smoke detectors. Receivers AES Model 7705i and AES Model 7170 (AES RF Mesh Network) RS-485 Points Limited to a single RA-6075 LCD remote annunciator

113 7706-ULF Integrated Fire Monitoring System 113 Appendix D. Compatible Smoke Detectors Table Detector Model Identifier Base Model Identifier System Sensor (Brk) (Max. No. of Detectors Per Zone is 20) 1400* A N/A N/A 2400* A N/A N/A 2400TH* A N/A N/A 2W-B A N/A N/A 2WT-B A N/A N/A Detection System (Max. No. of Detectors Per Zone is 25) DS250 A MB2W/MB2WL A DS250TH A MB2W/MB2WL A ESL (Max. No. of Detectors Per Zone is 25) 611U S10 601U S00 611UD S10 601U S00 611UT S10 601U S00 612U S10 601U S00 612UD S10 601U S00 613U5 S10 601U S00 611UD S10 609U10 S00 612UD S10 609U10 S00 425C S10 N/A N/A 425CT S10 N/A N/A Hochiki (Max. No. of Detectors Per Zone is 25) SLR-24* HD-3 HSC-221R HB-71 HSB-221 HB-54 HSB-221N HB-54 NS6-221 NS4-221 NS6-220 HB-3 SLR-24H* HD-3 HSC-221R HB-71 HSB-221 HB-54 HSB-221N HB-54 NS6-221 NS4-221 SIJ-24* HD-3 HSC-221R HB-71 HSB-221 HB-54 HSB-221N HB-54 NS6-221 NS4-221 Detector Model Identifier Base Model Identifier

114 ULF Integrated Fire Monitoring System Fenwal (Max. No. of Detectors Per Zone is 25) CPD-7051* I51FE1 2-WIRE FE51A PSD-7155* P55FE1 2WRLT FE52A PSD-7156* P56FE1 2WRB FE55A All of the above Fenwal detectors and bases can be used in any combination. Retrofit Base Adaptor , Identifier MAFE1 (for series Bases, Models -001, -002, -003, and -005). Duct Housing with Detector Base DH-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only). Potter (Max. No. of Detectors Per Zone is 25) PS-24* HD-3 (HOCHIKI) SB-46 HB-71(HOCHIKI) SB-93 HB-54 (HOCHIKI) HB-3 (HOCHIKI) PS-24H HD-3 (HOCHIKI) SB-46 HB-71 (HOCHIKI) HB-54 (HOCHIKI) IS-24* HD-3 (HOCHIKI) SB-46 HB-71 (HOCHIKI) *UL listed. HB-54 (HOCHIKI) Note: If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.

115 7706-ULF Integrated Fire Monitoring System 115 Appendix E. Compatible Auxiliary Circuit Devices Model Description Flow Switches (UL listed devices by Potter Electric Signal Company, LLC) VSR-AT 2-inch Auto Test VSR-AT 3-inch Auto Test VSR-AT 4-inch Auto Test VSR-AT 5-inch Auto Test VSR-AT 6-inch Auto Test VSR-AT 8-inch Auto Test VSR-AT 2 1/2 inch Auto Test VSR-AT 3 1/2 inch Auto Test

116 ULF Integrated Fire Monitoring System Appendix F. Control Panel Menu Main Menu 1=View History 2=Enable/Disable 3=Set Date/Time 4=Walk Test 5=System Tools 6=Programming 7=Data Transfer Esc= Exit 7=PIC Config. 1=By Point Select Device Internal PWR 2=By Zone Zone (Enter Zone # and press Enter) 1=Disable Inputs 2=Disable Options Esc=Exit PIC Menu 1=PIC Status 2=Route Table Esc=Exit 1=Point Control 2=Ethernet Status 3=DACT Test 4=DACT Reset 5=Erase History 6=Lamp Test 7=App Revisions 8=PIC Status Esc=Exit 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit Select Data 1=Remote Access 2= History 3= Config 4= Test 5=Server Status Esc=Exit 6=Programming 1=System Setup 2=LEARN Mode 3=Panel Default 4=IP Settings 5=Def. ID/Passwd 6=Prog ID/Passwd 7=PIC Config. Esc=Exit System Setup 1=AC PWR Delay 2=DACT Setup 3=Display Mode Esc=Exit IP Settings 1=DHCP Settings 2=Default IP 3=Default Gatewy 4=Default Settings 5=Alternate IP 6=Alt. Gateway 7=Alt. Subnet Esc=Exit DACT Setup* 1=Line 1 Setup 2=Line 2 Setup 3=Acct 1 Setup 4=Acct 2 Setup 5=Acct 3 Setup 6=Acct 4 Setup 7=Acct 5 Setup Esc=Exit Display Mode 1=USA 2=Canada Esc=Exit Line Setup 1=Enable/Disable 2=Line Monitor 3=No. of Rings 4=Ans. Machine 5=Line Prefix 6=Dial Tone Det. Esc=Exit Account Setup 1=Report Event Type 2=Pri Acct ID 3=Pri Phone No. 4=Pri Rpt. Test 6=Sec Acct. ID 7=Sec Phone No. 8=Sec Rpt. Fmt. 9=Sec. Rpt. Test Esc=Exit Def. ID/Passwd 1=Username 2=Password Esc=Exit PIC Config. 1=Setup 2=Timers 3=Modes 4=Time to Live 5=Acct Override 6=User Codes 7=Report Acct. 8=Default PIC Esc=Exit * DACT not used in this product. TIP: To save time, enter the menu selection number on the keypad to select a function. For example, press 3 to select Set Date/Time from the Main Menu.

117 7706-ULF Integrated Fire Monitoring System 117 Appendix G. Verifying 7764 PIC Operation and Troubleshooting Steps Verifying 7764 PIC Operation and Troubleshooting Steps The 7764 PIC is operating normally when: yy No error message is on the LCD after the power-up self-test of the panel. yy The green Status heartbeat LED is blinking on and off. There is a short flash followed by approximately 2 seconds off before repeating. yy The green 12V Out LED is on continuously. A third diagnostic LED located on the board is for factory use only. See figure below for LED locations. Diagnostic LED - Factory Use Only Status Heartbeat LED 12V Out LED Troubleshooting If the following error message appears on the two-line LCD display Trb-AES COM [1] alternating with AES PIC 1,use the steps that follow to isolate the problem. To Isolate the Problem 1. Check the wiring between mainboard AUX ( - ) and ( + ) terminals and 7764 VAUX terminals (refer to "Table 8: Interconnections" for correct AUX wiring). Verify that there is DC voltage at the 7764 VAUX terminals. 2. Verify that the V Out LED is on. If the LED is not on and the VAUX terminals have DC voltage, then the 7764 requires service. Contact AES Technical Support for instructions. 3. Check wiring between PLINK on the 7764 and the mainboard (refer to "Table 8: Interconnections") for the correct PLINK wiring instructions). If the wiring is correct, perform a power reset by disconnecting the battery, removing and then reapplying AC power to the 7706-ULF. If the trouble error message still appears, the 7764 requires service. Contact AES Technical Support for instructions.

PFC-4064 Conventional Fire Alarm Panel

PFC-4064 Conventional Fire Alarm Panel PFC-4064 Conventional Fire Alarm Panel Installation, Operations & Programming Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

AES IntelliTAP. Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device. Version Installation Guide CONTENTS

AES IntelliTAP. Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device. Version Installation Guide CONTENTS AES IntelliTAP Satellite / Remote Dialer Data Receiver Page 1 AES IntelliTAP Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device Version 1.10 Installation Guide CONTENTS How it Works

More information

AHJ Resource Guide. Authority Having Jurisdiction (AHJ)

AHJ Resource Guide. Authority Having Jurisdiction (AHJ) AHJ Resource Guide Authority Having Jurisdiction (AHJ) R E S OU RCE G UI D E 1 AHJ Resource Guide 2 Purpose The purpose of this document is to provide the local Authority Having Jurisdiction (AHJ) information

More information

AHJ Resource Guide. Authority Having Jurisdiction (AHJ)

AHJ Resource Guide. Authority Having Jurisdiction (AHJ) AHJ Resource Guide Authority Having Jurisdiction (AHJ) R E S OU RCE G UI D E 1 AHJ Resource Guide 2 Purpose The purpose of this document is to provide the local Authority Having Jurisdiction (AHJ) information

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906 s Data Sheet Fire Safety & Security Products SXL-EX Fire Alarm Control Panel Conventional Zone Fire Alarm Control Panel ARCHITECT AND ENGINEER SPECIFICATIONS Four (4) zones expandable to eight (8) zones

More information

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA CONVENTIONAL FIRE ALARM CONTROL UNITS MR-2300 SERIES Fire Alarm Control Units Description Secutron s MR-2300 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual Replace the following pages of Document Number 50734 (I56-993-01/D770-19-00), Revision B with the corresponding revised

More information

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description CONVENTIONAL FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped with

More information

MR-2602 Two Zone Fire Alarm Control Panel

MR-2602 Two Zone Fire Alarm Control Panel MR-2602 Two Zone Fire Alarm Control Panel Installation Manual Secutron LT-2015 Rev.3 July 2010 Table of Contents 1 Introduction 1.1 The MR-2602 Fire Alarm Control Unit... 11 1.1.1 General features...

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

AL800ULADA. NAC Power Extender. Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi 50 (P/N 10-071) is a state-of-the-art true intelligent digital peer-to-peer modular suppression control system.

More information

Remote Relay Module (RRM)

Remote Relay Module (RRM) Remote Relay Module (RRM) Instruction Manual WARNING THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR INSTALLING, USING OR SERVICING THIS PRODUCT. Like

More information

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X AL1002ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.

More information

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated

More information

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014 January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,

More information

DS7400Xi Addressable Control/ Communicator

DS7400Xi Addressable Control/ Communicator DS7400Xi Addressable Control/ Communicator DS7400Xi DS7400Xi-EXP 110VAC operation 220VAC operation Remotely Programmable WDSRP (Windows Detection Systems Remote Programming Software), allows the systems

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

good things in small packages

good things in small packages FireShield Control Panels good things in small packages life safety for small buildings and shops A perfect arrangement FireShield offers the very best conventional fire alarm technology available, with

More information

Conventional Releasing Control Panel

Conventional Releasing Control Panel s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

EVO192 v3.0 Fire and Burglary What s New

EVO192 v3.0 Fire and Burglary What s New EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter TM Long Range Radio Alarm Transmitter INSTALLATION MANUAL Version 1.3W FEATURES Transmits alarm information to a long range radio network Varitech Transmission Format Note: If automatic SIA is used in

More information

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control File: S8485 Wiring Diagram This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control Panel. The operation of this product is intended for indoor

More information

AHJ Field Inspector Guide For: AES-IntelliNet Private Radio Network Installation Sites

AHJ Field Inspector Guide For: AES-IntelliNet Private Radio Network Installation Sites AHJ Field Inspector Guide For: AES-IntelliNet Private Radio Network Installation Sites Where to Find AES-IntelliNet in NFPA-72 Code Identifying UL Subscriber Model is UL 864, Ed 9 Listed for Fire Alarm

More information

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING MODEL ZAC-32 32 ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING 32 HARD WIRED ZONES CAN BE NORMALLY-OPEN OR NORMALLY-CLOSED ZONE WIRING RUNS CAN BE AS FAR AS 10,000 FEET FROM

More information

SC-6 Six Supervised Control Module

SC-6 Six Supervised Control Module INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) PATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262) NAC ETENDER SUPPLIES Installation Instructions 273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (800) 631-2148 Fax: (732) 222-8707 Web

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715 Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed

More information

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Fire Safety Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL THE GAMEWELL COMPANY PN: 71981 60 PLEASANT STREET ISSUE A ASHLAND, MA 01721 3/22/2001 This page intentionally blank ii

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED

More information

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep. 140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC

More information

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev Altronix Corp. 140 58th St. Brooklyn, NY AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 052313 Agency Listings: UL Listed for Control Units for

More information

RMS/RPX Reader. User Manual

RMS/RPX Reader. User Manual RMS/RPX Reader User Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security Inc. All rights reserved. This document may not be copied or otherwise reproduced,

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

Fire Control/Communicator

Fire Control/Communicator Operation and Installation Manual Fire Control/Communicator 1 2 3 4 5 12V AC,20V A, 60Hz or +24V DC 12V AC, 20V A, 60Hz or -24V DC EARTH GND BATTERY - BATTERY + 6 INITIATING A1-7 INITIATING A2-8 INITIATING

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X AL1042ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 071508X Agency Listings: UL Listed for Control Units for Fire Protective Signaling Systems (UL

More information

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs ACM Series Access Power Controllers with Power Supplies Installation Guide Models Include: AL400ULACM AL600ULACM - 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Fused Outputs - Fused Outputs

More information

Long Range Radio Alarm Transmitter

Long Range Radio Alarm Transmitter W A R N I N G Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. TM

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature AutoTest VSR (VSR-AT) (EU) Features Assembled in USA 0-30 second field replaceable electronic retard Two SPDT (Form C) switch contacts Weatherproof Easy to read wire terminal designations Easy to read

More information

KT-100 Door Controller

KT-100 Door Controller WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS SXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 4 Zones Expandable to 8 Zones Microprocessor Based Control Factory Programmed Field Configurable 2 Style Y Notification

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual P/N 315-049353-1 Siemens Building Technologies Fire Safety TABLE OF CONTENTS INTRODUCTION... 1 CONTROL PANEL

More information

AND ARCHITECT SPECIFICATIONS

AND ARCHITECT SPECIFICATIONS PXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 12 Zone System Expandable to 32 10 Amp Base Power Supply Multiple Power Supplies Available - Local or Remote 4 Notification

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0 CFP-105 Fire Alarm Control Panel Installation Manual Version 1.0 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..

More information

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays AEGIS Conventional Fire Alarm-Suppression Control Unit FEATURES Agency Approvals FM Approved FM Approved to ANSI/UL 864, 9th edition FM Approved to ULC-S527-99 Other domestic U.S. approvals/listings pending/

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow6na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow102na8d - 10A @ 12VDC - Eight

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS ECC-50/100(E) Emergency Command Center DF-60734:A4 General Firelite s ECC-50/100 and ECC-50/100E are multipurpose emergency voice evacuation panels for fire applications, mass notification applications,

More information

ECC-50/100C. Emergency Command Center

ECC-50/100C. Emergency Command Center ECC-50/100C Emergency Command Center Canadian DF-60815:B Emergency Communications General Fire-lite s ECC-50/100C is a multipurpose emergency voice evacuation panel for fire applications, mass notification

More information

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control Installation and Operation Manual Temperature and Pressure Monitoring for Heating and Cooling Applications Temperature Monitoring Control VALVE OPEN ALARM System= 128 o F Alarm At= 130 o F RESET /BACK

More information

Beacon 110 Gas Monitor Operator s Manual

Beacon 110 Gas Monitor Operator s Manual Beacon 110 Gas Monitor Operator s Manual Part Number: 71-0110RK Revision: H Released: 12/5/17 RKI Instruments, Inc. www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment

More information

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified

More information

20 Light Remote Annunciator

20 Light Remote Annunciator Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator

More information

Operation and Installation Guide. Fire Alarm Control Panel

Operation and Installation Guide. Fire Alarm Control Panel Operation and Installation Guide Fire Alarm Control Panel 2001 Radionics Page 2 P/N: 36958D Contents Contents 1.0 Notices... 5 1.1 FCC Compliance Notice... 5 1.2 Notice... 5 1.3 Installation Guidelines

More information

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note Product Overview: The Pertronic F4 Remote LED Mimic / Aux Relay Module F4-RMAX is an optional extra for the Pertronic F4 conventional 4-zone fire alarm panel. This board enables the fire alarm panel to

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D2 MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D2 GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

PERMACONN PM1030 Includes DI300. Installation Manual

PERMACONN PM1030 Includes DI300. Installation Manual PERMACONN PM1030 Includes DI300 Installation Manual Radio Data Comms Unit 5/20-30 Stubbs Street Silverwater NSW 2128 Telephone: 02 9352 1777 Facsimile: 02 9352 1700 Introduction The PERMACONN system provides

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

System Manual W A R N I N G. PC6O1O Software Version 2.1

System Manual W A R N I N G. PC6O1O Software Version 2.1 System Manual W A R N I N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

MODEL 5104B. Installation and Operation Manual. Fire Communicator. Part Number E, 09/04

MODEL 5104B. Installation and Operation Manual. Fire Communicator. Part Number E, 09/04 MODEL 5104B Fire Communicator Installation and Operation Manual Part Number 151053 E, 09/04 Content Section 1 Introduction... 1-1 1.1 Feature... 1-1 1.2 Accessory Devices... 1-2 1.3 About This Manual...

More information

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC. M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

INSTALLATION AND INSTRUCTION MANUAL

INSTALLATION AND INSTRUCTION MANUAL INSTALLATION AND INSTRUCTION MANUAL SS650-013 013 SIREN LCS652-013 SIREN and Light Controller PLITSTR247 REV. F 12/9/13 NOTICE Due to continuous product improvements, we must reserve the right to change

More information

Installation Guide. Control/Communicator

Installation Guide. Control/Communicator Installation Guide Control/Communicator 33120G Page 2 Copyright 2001 Radionics Contents 1.0 Introduction... 5 1.1 Listings and Approvals... 5 1.1.1 Fire... 5 1.1.2 Burglary... 5 1.2 FCC Notice... 5 1.2.1

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

SILENT KNIGHT. Model SK-2/E & SK-4/E. Installation and Operations Manual. Fire Alarm Control Panel. Part Number Rev. A ECN /08/05

SILENT KNIGHT. Model SK-2/E & SK-4/E. Installation and Operations Manual. Fire Alarm Control Panel. Part Number Rev. A ECN /08/05 SILENT KNIGHT Model SK-2/E & SK-4/E Fire Alarm Control Panel Installation and Operations Manual Part Number 52604 Rev. A ECN 05-276 08/08/05 Fire Alarm System Limitations An automatic fire alarm system

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

Fratech Multipath-IP

Fratech Multipath-IP Rev 2.0 (May 2013) Installer Manual 1 Current Part Numbers: Fratech Multipath-IP E-Link STU PCB & Accessory Kit only In Metal Enclosure with Power Supply 998325-PK 998325-XS Installer Manual This document

More information