1 ARTICLE 760 Fire Alarm Systems Introduction to Article 760 Fire Alarm Systems Article 760 covers the installation of wiring and equipment for fire alarm systems, including all circuits controlled and powered by the fire alarm system. These include fire detection and alarm notification, voice communications, guard s tour, sprinkler waterflow, and sprinkler supervisory systems. NFPA 72, National Fire Alarm Code provides other fire alarm system requirements. Since many people have difficulty understanding this article from the text alone, pay close attention to the illustrations as you study this material. The figures highlight important requirements and common Article 760 violations. Part I. General Scope. Article 760 covers the installation of wiring and equipment for fire alarm systems, including all circuits controlled and powered by the fire alarm system. Figure FPN No. 1: Fire alarm systems include fire detection and alarm notification, voice communications, guard s tour, sprinkler waterflow, and sprinkler supervisory systems. Other circuits that might be controlled or powered by the fire alarm system include elevator capture, elevator shutdown, door release, smoke door and damper control, fire door and damper control, and fan shutdown. NFPA 72, National Fire Alarm Code provides the requirements for the selection, installation, performance, use, testing, and maintenance of fire alarm systems. Author s Comments: Building control circuits associated with the fire alarm system, such as elevator capture and fan shutdown, must comply with Article 725 [760.3(E)]. Article 760 applies if these components are powered and directly controlled by the fire alarm system. NFPA 101 Life Safety Code or the local building code specifies when and where a fire alarm system is required. Figure Author s Comment: Residential smoke alarm systems, including interconnecting wiring, aren t covered by Article 760, because they aren t powered by a fire alarm system as defined in NFPA Definitions. Abandoned Cable. A cable that isn t terminated to equipment and not identified for future use with a tag. Author s Comment: Section requires the accessible portion of abandoned cables to be removed. Fire Alarm Circuit. The portion of the wiring system and connected equipment powered and controlled by the fire 226 Mike Holt s Illustrated Guide to Understanding the National Electrical Code, Volume 2

2 Fire Alarm Systems alarm system. Fire alarm circuits are classified as either nonpower-limited or power-limited. Power-Limited Fire Alarm Circuit. A power-limited fire alarm circuit must have the voltage and power limited by a listed power supply that complies with as follows: Figure Inherently Limited (ac) [Chapter 9, Table 12(A)] Voltage Power 0 to 20V 5.00 x V 21V to 100V 100 VA Not Inherently Limited [Chapter 9, Table 12(A)] Overcurrent Voltage Power Protection 0 to 20V 5.00 x V 5A 21 to 100V 100 VA 100/V 101 to 150V 100 VA 1A Figure Author s Comment: Inherently limited power supplies are designed to burn out if overloaded. Nonpower-Limited Fire Alarm Circuit. A nonpower-limited fire alarm circuit can operate at up to 600V, and the power output isn t limited [ and ]. Figure Other Articles. Only those sections of Article 300 specifically referenced in this section apply to fire alarm circuits and equipment and complies with (A) through (G) as follows. (A) Spread of Fire or Products of Combustion. Fire alarm circuits installed through fire-resistant-rated walls, partitions, Figure Figure Mike Holt Enterprises, Inc NEC.CODE ( ) 227

3 Fire Alarm Systems floors, or ceilings must be firestopped to limit the possible spread of fire or products of combustion in accordance with the instructions supplied by the manufacturer for the specific type of cable and construction material (drywall, brick, etc.), as required by Figure (B) Ducts, Plenums, and Other Spaces Used for Environmental (C) Hazardous (Classified) Locations. Fire alarm circuits installed in any hazardous location must be installed in accordance with Articles 500 through 516, specifically and (D) Corrosive, Damp, or Wet Locations. Fire alarm circuits installed in corrosive, damp, or wet locations must be identified for use in the operating environment [110.11]; must be of materials suitable for the environment in which they are to be installed [300.6]; and must be of a type suitable for the application [310.9]. (E) Building Control Circuits. Class 1, 2, and 3 circuits used for building controls (elevator capture, fan shutdown, etc.), associated with the fire alarm system, but not controlled and powered by the fire alarm system, must be installed in accordance with Article 725 [760.1]. (F) Optical Fiber Cables. Optical fiber cables utilized for fire alarm circuits must be installed in accordance with Article Access to Electrical Equipment Behind Panels Designed to Allow Access. Access to equipment must not be prohibited by an accumulation of cables that prevent the removal of suspended-ceiling panels. Cables must be located so that the suspended-ceiling panels can be moved to provide access to electrical equipment. Figure Air-Handling Purposes. Where necessary for direct action upon, or sensing of the contained air, fire alarm cables are permitted to be installed in ducts or plenums if they are installed in a metal raceway as required by (B). Figure Exception: Plenum-rated fire alarm cables are permitted above a suspended ceiling or below a raised floor used for environmental air [760.30(B)(1) and (2), (A), and (A)]. Nonplenum-rated fire alarm cables are permitted to be installed above a suspended ceiling or below a raised floor used for environmental air, if the cable is installed in a metal raceway [300.22(C)(1)]. Figure Mike Holt s Illustrated Guide to Understanding the National Electrical Code, Volume 2

4 Fire Alarm Systems Mechanical Execution of Work. Equipment and cabling must be installed in a neat and workmanlike manner. Author s Comment: Raceways and cables are permitted to be supported by independent support wires attached to the suspended ceiling [300.11(A) and ]. Figure Figure Exposed cables must be supported by the structural components of the building so that the cable will not be damaged by normal building use. Cables must be secured by straps, staples, hangers, cable ties, or similar fittings designed and installed in a manner that will not damage the cable. Figure Figure Cables run through or parallel to framing members or furring strips must be protected where they are likely to be penetrated by nails or screws, by installing the wiring method so Figure Figure Mike Holt Enterprises, Inc NEC.CODE ( ) 229

5 Fire Alarm Systems it isn t less than 11 4 in. from the nearest edge of the framing member or furring strips, or by protecting them with a 1 16 in. thick steel plate or equivalent [300.4(D)]. Figure Abandoned Cable. To limit the spread of fire or products of combustion within a building, the accessible portion of cable that isn t terminated at equipment and not identified for future use with a tag must be removed [760.2]. Figure circuit conductors extend beyond a building, they must be installed in accordance with Article 800, or they must be installed in accordance with Part I of Article Fire Alarm Circuit Requirements. (A) Nonpower-Limited Fire Alarm Circuits. Nonpowerlimited fire alarm (NPLFA) circuits must comply with Parts I and II of this article. Cables identified for future use must be with a tag that can Figure Figure withstand the environment involved. Figure Author s Comment: Cables installed in concealed raceways aren t considered accessible, therefore they re not required to be removed Fire Alarm Circuit Identification. Fire alarm circuits must be identified at all terminal and junction locations. The identification must be in such a manner that will help to prevent unintentional signals on the fire alarm system circuits during testing and servicing of other systems. Figure Author s Comment: The marking of raceways and cables isn t required by this section [ ] Fire Alarm Circuit Cables Extending Beyond a Building. Where twisted-pair power-limited fire alarm (B) Power-Limited Fire Alarm Circuits. Power-limited fire alarm (PLFA) circuits must comply with Parts I and III of this article. Part III. Power-Limited Fire Alarm (PLFA) Circuits Power Sources for Power-Limited Fire Alarm Circuits. (B) Branch Circuit. Power-limited fire alarm equipment must be supplied by an individual branch circuit that is not GFCI or AFCI protected. Figure Equipment Marking. Fire alarm equipment supplying power-limited fire alarm cable circuits must be 230 Mike Holt s Illustrated Guide to Understanding the National Electrical Code, Volume 2

6 Fire Alarm Systems durably marked to indicate each circuit that is a power-limited fire alarm circuit. Author s Comment: Fire alarm circuits must be marked at all terminal and junction locations [760.30] Wiring Methods on Load Side of Power- Limited Fire Alarm Power Source. (B) PLFA Wiring Methods and Materials. Power-limited fire alarm conductors and cables described in must be installed as detailed in (1), (2), or (3). (1) Exposed or Fished in Concealed Spaces. Power-limited fire alarm circuits installed exposed must be adequately supported and protected against physical damage, or be installed must be protected by a 1 16 in. thick steel plate or the equivalent [760.8]. Cable splices or terminations must be made in listed fittings, boxes, enclosures, fire alarm devices, or utilization equipment. Figure Separation from Power Conductors. (A) General. Power-limited fire alarm conductors must not be placed in any enclosure, raceway, or cable with conductors of electric light, power, or Class 1 circuits. (B) Separated by Barriers. Where separated by a barrier, power-limited fire alarm circuits are permitted with electric power conductors. Author s Comment: Separation is required to prevent a fire or Figure Figure in a raceway. Author s Comment: Exposed cables must be supported by the structural components of the building so the cable won t be damaged by normal building use. Cables must be secured by straps, staples, hangers, or similar fittings designed and installed in a manner that won t damage the cable. Cables run through or parallel to framing members or furring strips must be protected where they re likely to be penetrated by nails or screws, by installing the wiring method so it isn t less than 11 4 in. from the nearest edge of the framing member or furring strips, or it shock hazard that can occur from a short between the fire alarm circuit and the higher-voltage circuits. (D) Associated Systems Within Enclosures. Power-limited fire alarm conductors are permitted to be mixed with electric light, power, and Class 1 circuit conductors in enclosures where these other conductors are introduced solely for connection to the same equipment, and: (1) A minimum of 1 4 in. separation is maintained from the power-limited fire alarm cable conductors. Mike Holt Enterprises, Inc NEC.CODE ( ) 231

7 Fire Alarm Systems Figure (G) Other Applications. Power-limited fire alarm circuit conductors must be separated by not less than 2 in. from insulated conductors of electric light, power, or Class 1 circuits unless: (1) All of the electric light, power, and Class 1 circuit conductors, or all of the power-limited fire alarm circuit conductors, are in a raceway or in metal-sheathed, metalclad, nonmetallic-sheathed, or underground feeder cables. Figure Power-Limited Fire Alarm Circuits, Class 2, Class 3, and Communications Circuits. (A) Two or More Circuits. Power-limited fire alarm circuits, communications circuits, or Class 3 circuits are permitted to be in the same cable, enclosure, cable tray, or raceway. Figure (B) PLFA and Class 2 Circuits. Class 2 circuits are permitted to be within the same cable, enclosure, cable tray, or raceway as conductors of power-limited fire alarm circuits provided the Class 2 circuit conductor insulation isn t less than that required for the power-limited fire alarm circuit. Author s Comment: Listed Class 2 cables have a voltage rating of 150V [ (G)], whereas listed power-limited fire alarm cables have a voltage rating of 300V [ (C)]. (D) Audio System Circuits and Power-Limited Fire Alarm Circuits. Audio system circuits [640.9(C)] using Class 2 or Class 3 wiring methods must not be installed in the same Figure Figure cable, cable tray, or raceway with power-limited fire alarm conductors or cables. Author s Comment: The concern is that a fault from audio amplifier circuits to fire alarm circuits has the potential to create a hazard by disrupting the operation of fire alarm systems. However, this new restriction doesn t apply to the voice annunciation audio circuits supplied and controlled from a fire alarm 232 Mike Holt s Illustrated Guide to Understanding the National Electrical Code, Volume 2

8 Fire Alarm Systems panel and commonly required in high-rise buildings and similar applications Support. Power-limited fire alarm cables are not permitted to be strapped, taped, or attached to the exterior of any raceway as a means of support. Figure Author s Comment: Power-limited fire alarm cables identified as suitable for plenum or riser use are not required in one- or two-family dwellings Applications of Power-Limited Fire Alarm Cables (PLFA). (A) Ducts, Plenums, and Other Space Used for Environ mental Air. Where necessary for direct action upon, or sensing of the contained air, power-limited fire alarm cables are permitted to be installed in ducts or plenums if installed in a metal raceway [300.22(B)]. Power-limited fire alarm cables identified as suitable for plenum use can be installed above a suspended ceiling or below a raised floor used for environmental air. Figure Author s Comments: Power-limited fire alarm cables not identified as suitable for plenum use can be installed above a suspended ceiling or below a raised floor used for environmental air, but only if the power-limited fire alarm cables not identified as suitable for plenum use are installed in a metal raceway [300.22(C)(1)]. Fire alarm cables installed beneath a raised floor in an information technology equipment room (computer room) aren t required to be plenum-rated [300.22(D) and 645.5(D)(6)(c)]. (B) Riser. (1) Power-limited fire alarm cables installed in vertical runs penetrating more than one floor must be riser-rated Types FPLR or FPLP [ (E)]. Listed riser raceways and listed plenum signaling raceways are permitted to be installed in vertical riser runs, but only if the cables contained in these raceways are riser- or plenum-rated Types CL2R, CL3R, CL2P, or CL3P. (2) Power-limited fire alarm cables installed in vertical runs penetrating more than one floor aren t required to be riser-rated if installed within a metal raceway. Author s Comment: Metal raceways containing circuit conductors from a power-supply system that operates below 50V generally aren t required to be connected to an equipment grounding conductor [ and (I)]. (3) FPL cable is permitted for all applications in one- and two-family dwellings. Figure (C) Other Wiring Within Buildings. (1) General. Type FPL cable is permitted. (2) In Raceways. Cables are permitted to be installed in raceways. (3) Nonconcealed Spaces. Chapter 3 cables meeting the requirements of (A) and (B) can be installed in noncon cealed spaces where the exposed length of cable doesn t exceed 10 ft. (D) Cable Substitutions. Power-limited fire alarm circuit cables are permitted to be substituted in accordance with Table Part IV. Listing Requirements Listing and Marking Requirements of Power-Limited Fire Alarm Cables (PLFA). Power-limited fire alarm cable installed within buildings must be listed in accordance with (A) through (H) and must be marked in accordance with (I). Power-limited fire alarm cable used in a wet location must be listed for use in wet locations or have a moisture-impervious metal sheath. Figure Mike Holt Enterprises, Inc NEC.CODE ( ) 233

9 Fire Alarm Systems (A) Conductor Materials. Conductors must be solid or stranded copper. (B) Conductor Size. The size of conductors in a multiconductor cable must not be smaller than 26 AWG. Single conductors must not be smaller than 18 AWG. (C) Cable Voltage Rating. Power-limited fire alarm cable must have a voltage rating of 300V and this rating must not be marked on the cable [ (I)]. (D) Type FPLP. Power-limited fire alarm plenum cables (FPLP) are listed for use in ducts, plenums, and other environmental air spaces [ (A)]. Figure Figure Author s Comment: Cables identified as suitable for plenum use can be installed in environmental air spaces, but they are not permitted to be installed in ducts or plenums! See 760.3(B) in this textbook for details. (E) Type FPLR. Power-limited fire alarm riser cables (FPLR) are listed for use in a vertical run in a shaft, or from floor to floor [ (B)]. (F) Type FPL. Power-limited fire alarm cables (FPL) are listed for general-purpose use [ (C)]. (H) Coaxial Cables. Coaxial cables are listed as FPLP, FPLR, or FPL. (I) Cable Marking. The 300V rating of power-limited fire alarm cable must not be marked on the cable [ (C)]. FPN: Voltage markings on cables may suggest that the cables are suitable for Class 1, or electrical power applications, which they re not. 234 Mike Holt s Illustrated Guide to Understanding the National Electrical Code, Volume 2

10 Practice Questions Article 760 ARTICLE 760 Practice Questions Article 760 Fire Alarm Systems Practice Questions 1. Fire alarm cables that are not terminated at equipment and not identified for future use with a tag are considered abandoned. (a) True (b) False 2. Fire alarm cables identified for future use shall be marked with a tag of sufficient durability to withstand. (a) moisture (b) humidity (c) the environment involved (d) none of these 3. The power source for a nonpower-limited fire alarm circuit shall not be supplied through a(n). (a) ground-fault circuit interrupter (b) arc-fault circuit interrupter (c) inverse time circuit breaker (d) a or b 4. The number of nonpower-limited fire alarm conductors in a raceway shall not be required to comply with the fill requirements contained in (a) True (b) False 5. Cable splices or terminations in power-limited fire alarm systems shall be made in listed or utilization equipment. (a) fittings (b) boxes or enclosures (c) fire alarm devices (d) all of these 6. Audio system circuits using Class 2 or Class 3 wiring methods shall not be installed in the same cable or raceway with. (a) other audio system circuits (b) power-limited fire alarm conductors or cables (c) a or b (d) none of these 7. Power-limited fire alarm cables installed within buildings shall be as being resistant to the spread of fire. (a) marked FR (b) listed (c) identified (d) color-coded Mike Holt Enterprises, Inc NEC.CODE ( ) 235

I dedicate this book to the Lord Jesus Christ, my mentor and teacher. Proverbs 16:3 NOTICE TO THE READER ABOUT THE AUTHOR

I dedicate this book to the Lord Jesus Christ, my mentor and teacher. Proverbs 16:3 NOTICE TO THE READER ABOUT THE AUTHOR NOTICE TO THE READER The publisher does not warrant or guarantee any of the products described herein or perform any independent analysis in connection with any of the product information contained herein.

More information

ARTICLE 760 FIRE ALARM SYSTEMS

ARTICLE 760 FIRE ALARM SYSTEMS Mike Holt s Illustrated Guide to ARTICLE 760 FIRE ALARM SYSTEMS Based on the 2014 NEC Extracted from Mike Holt s Illustrated Guide to Understanding the National Electrical Code Volume 2 For more information

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xiii How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations... Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

Genesis Series Cable THE POWER OF CHOICE. Cables for Silent Knight

Genesis Series Cable THE POWER OF CHOICE. Cables for Silent Knight Genesis Series Cable THE POWER OF CHOICE Cables for Silent Knight Cable for That! Genesis Series Cables for Silent Knight 5600 5700 5808 5820XL IFP-25 IFP-50 IFP-100 IFP-1000 IFP-2000 SK-5208 DIRECTORY

More information

NFPA Changes

NFPA Changes Chapter 12, Circuits and Pathways Summary. Chapter 12, Circuits and Pathways, is a new chapter. It brings together requirements that were formerly found in SIG-FUN, Fundamentals of Fire Alarm Systems regarding

More information

Second Revision No. 601 NFPA [ Section No [Excluding

Second Revision No. 601 NFPA [ Section No [Excluding Second Revision No. 601 NFPA 70 2015 [ Section No. 300.4 [Excluding any Sub Sections] ] Where subject to physical damage, conductors, raceways, and cables shall be protected. Informational Note: Minor

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch

More information

Product Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables.

Product Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables. Fire Alarm Cables Initiating Device, SLC Lines, and NAC Cables Product Guide STANDARDS Fire Alarm Systems A fire alarm system is number of devices working together to detect and warn people through visual

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Fire Alarm Cables. Features: Countdown. New Labeling System on box. Color Coded Boxes. Zone and Room Markings

Fire Alarm Cables. Features: Countdown. New Labeling System on box. Color Coded Boxes. Zone and Room Markings Fire Alarm Cables Our Fire Alarm Cables are manufactured in a wide variety of gauge sizes, shielding configurations and jacketing materials including plenum, riser and general purpose. Genesis also manufactures

More information

Fee $15 Course: NEC Changes 5 This course is valid for these credentials: Credential Description Cred Code Credit Hours

Fee $15 Course: NEC Changes 5 This course is valid for these credentials: Credential Description Cred Code Credit Hours www.garyklinka.com Page 1 of 9 Instructions: Fee $15 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Spring Test 6 due 04/26/2013

Spring Test 6 due 04/26/2013 Spring Test 6 due 04/26/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. The article that covers TV wiring installations in residences

More information

Session: Fire Alarm Installation

Session: Fire Alarm Installation Session: Fire Alarm Installation PRESENTED BY: MICHAEL L. SAVAGE, L. LLC. SAVAGE, LLC. 2 About the speaker Director of Building Safety in Marion County, Florida Licensed Inspector in Maryland for 23 years.

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities

More information

NEC, NFPA 70, NFPA 70E and National Electrical Code are registered trademarks of the National Fire Protection Association. September 20, 2017

NEC, NFPA 70, NFPA 70E and National Electrical Code are registered trademarks of the National Fire Protection Association. September 20, 2017 2017 NEC INDEX NEC, NFPA 70, NFPA 70E and National Electrical Code are registered trademarks of the National Fire Protection Association. September 20, 2017 NOTICE TO THE READER The publisher does not

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Is low voltage cable allowed to be run through drilled

More information

NEC 2017 Changes and Their Effect Upon the ICT Industry

NEC 2017 Changes and Their Effect Upon the ICT Industry NEC 2017 Changes and Their Effect Upon the ICT Industry Today s Presenters John Kacperski, RCDD, OSP, CDT Chair of BICSI Standards BICSI Representative on NFPA 70-CMP 16 Richard S. Anderson, RCDD, CDT,

More information

PAIRED UNJACKETED. Insulation Nominal Anixter. Paired Conductors Thickness O.D. Number AWG Strand No. IN IN

PAIRED UNJACKETED. Insulation Nominal Anixter. Paired Conductors Thickness O.D. Number AWG Strand No. IN IN PVC Stranded and Solid Conductors Listed as Misc. Wire PAIRED UNJACKETED Burglar alarm systems wiring; to sensors, control. BURGLAR ALARM 1. CONDUCTOR: Stranded copper conductors (1/c tinned + 1/c bare)

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 The City of Portsmouth adopts the State Building Code, which adopts by reference The National Electrical Code, 2017(NEC), as Chapter 15, Part IV, of the

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire.

Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire. Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire. Installs fast and easy Lowers labor costs Replaces conduit and wire Provides superior grounding UL Listed Corra/Clad MC

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod Journeyman and Master Common Exam 2 1 The grounding terminal of a grounding-type receptacle installed in a metal box shall be? A. Connected to the equipment ground B. Bonded to the box C. Connected to

More information

Electrical Tech Note 107

Electrical Tech Note 107 Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State

More information

2011 and 2014 National Electrical Code Changes Residential Only

2011 and 2014 National Electrical Code Changes Residential Only 2011 and 2014 National Electrical Code Changes Residential Only Sponsored By: and.net Instructor: Fritz Gunther, Chief Electrical Inspector 585-436-4460 www.nyeia.com NEW YORK ELECTRICAL INSPECTION AGENCY

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

Revisions for the 2011 National Electrical Code - Part 4

Revisions for the 2011 National Electrical Code - Part 4 PDHonline Course E358 (3 PDH) Revisions for the 2011 National Electrical Code - Part 4 Instructor: Patrick Ouillette 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone &

More information

Applying the NEC to Telecom Design Morning Session. By Tim Kuhlman, PE RCDD CDT TEECOM

Applying the NEC to Telecom Design Morning Session. By Tim Kuhlman, PE RCDD CDT TEECOM Applying the NEC to Telecom Design Morning Session By Tim Kuhlman, PE RCDD CDT TEECOM Safety Moment Schedule 9:00am to 10:15am 10:15am 15 minute break 10:30am to 12:00pm 12:00pm to 1:30pm - Lunch 1:30pm

More information

J-PRO TM Cable Support System

J-PRO TM Cable Support System Frequently Asked Questions Cable Support System What references define how and where J-hooks are used? J-hooks are a horizontal pathway promoted in the BICSI TDM manual as a means to route small to medium

More information

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Manufacturers Statement of Compliance with NFPA 70, National Electric Code,

More information

IN2 Lighting Control Devices

IN2 Lighting Control Devices Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Lighting Control Devices Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

2017 NEC Presented by: Russ LeBlanc

2017 NEC Presented by: Russ LeBlanc 2017 NEC Presented by: Russ LeBlanc 1. 90.2(A)-installation and removal 2. 90.3-code layout 3. 100-readily accessible 4. 100-field evaluation body (FEB) 5. 100-field labeled 6. 100-receptacle 7. 100-structure

More information

BUILDER S PRE-INSPECTION CHECKLIST

BUILDER S PRE-INSPECTION CHECKLIST Warrenton Fire Protection District 606 Fairgrounds Rd. Warrenton, MO 63383 Ph: 636-456-8935 Fax: 636-456-7764 www.warrenton-fire.org BUILDER S PRE-INSPECTION CHECKLIST This checklist is designed as a general

More information

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 1. Is a standard wire-nut approved for a wet location as in an outside j-box? Is there a listed

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter except as otherwise

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

SECTION LIGHTING CONTROL DEVICES

SECTION LIGHTING CONTROL DEVICES SECTION 16145 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

BUILDER S PRE-INSPECTION CHECKLIST

BUILDER S PRE-INSPECTION CHECKLIST Warrenton Fire Protection District 606 Fairgrounds Rd. Warrenton, MO 63383 Ph: 636-456-8935 Fax: 636-456-7764 www.warrenton-fire.org BUILDER S PRE-INSPECTION CHECKLIST This checklist is designed as a general

More information

Labeling to Article 690 of the National Electrical Code Routing and Protecting PV Cables

Labeling to Article 690 of the National Electrical Code Routing and Protecting PV Cables Labeling to Article 690 of the National Electrical Code Routing and Protecting PV Cables Article 690 labeling requirements from the NEC 2011 Edition General overview of industry labeling Labeling updates

More information

Report on Proposals June 2010 NFPA 70

Report on Proposals June 2010 NFPA 70 16-1 Log #4917o NEC-P16 Caleb M. Ferris, Chadwick Electric Add a diagram table after the scope of each article similar to the one in Article 430. For NEC user cost make the table layout diagram in 430.8

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

Fire alarm system specification for multiple tenant retail buildings

Fire alarm system specification for multiple tenant retail buildings Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE 2003 IAEI 75 th JUBILEE MEETING

REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE 2003 IAEI 75 th JUBILEE MEETING REPORT ON DISCUSSIONS DURING UL MEETINGS WITH ELECTRICAL INSPECTORS AT THE IAEI 75 th JUBILEE MEETING September 1, 2004 TO: SUBJECT: Attendees of Underwriters Laboratories Inc. Meetings with Electrical

More information

WIRE & CABLE. Wire & Cable... Wire Accessories...

WIRE & CABLE. Wire & Cable... Wire Accessories... Wire &... Wire Accessories... LINE CARD (9N) Arlington (GI) GRI (WG) Genesis (H2) ICC (Int l Conn & Corp) (RM) Remee (0E) W Box Technologies (WP) West Penn 1.800.233.6261 adiglobal.com/us New Vendor *

More information

WIRE & CABLE. Wire & Cable... Wire Accessories...

WIRE & CABLE. Wire & Cable... Wire Accessories... Wire &... Wire Accessories... LINE CARD (9N) Arlington (GI) GRI (WG) Honeywell Cabling / Genesis (H2) ICC (Int l Conn & Corp) (RM) Remee (0E) W Box Technologies (WP) West Penn 1.800.233.6261 adiglobal.com/us

More information

SIGA-CC1 Single Input Signal Module Installation Sheet

SIGA-CC1 Single Input Signal Module Installation Sheet SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality

More information

Town of Cicero Local Code Amendments

Town of Cicero Local Code Amendments Town of Cicero Local Code Amendments 2009 International Residential Code Local Amendments: DELETE Table R302.1 (Exterior Walls), see Attachment A. DELETE Exception for Subsection R313.2 (One and Two-Family

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Coaxial cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control

More information

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007 BUILDING CODE OF THE CITY OF NEW YORK New York City Department of Buildings 4 June 2007 Fatma Amer, PE, Deputy Commissioner, Technical Affairs James Colgate, RA, Executive Architect John Lee, RA Keith

More information

TOM BURNS, PLANNING DIRECTOR

TOM BURNS, PLANNING DIRECTOR ~~ 0 173 COUNTY OF SANTA CRUZ August 4,2005 PLANNING DEPARTMENT 701 OCEAN STREET, qth FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 TOM BURNS, PLANNING DIRECTOR Agenda:

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Print Specification. Publication. Instructions. Specific requirements. General requirements

Print Specification. Publication. Instructions. Specific requirements. General requirements Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

S U B S T I T U T E O R D I N A N C E BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF CHICAGO: ARTICLE I ELECTRICAL CODE

S U B S T I T U T E O R D I N A N C E BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF CHICAGO: ARTICLE I ELECTRICAL CODE S U B S T I T U T E O R D I N A N C E BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF CHICAGO: This ordinance is organized into eight Articles, as follows: Article I. Article II. Article III. Article

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc. Chapter 1 GROUNDING AND BONDING 1 Proper grounding practices protect people from the hazards of electric shock and ensure the correct operation of overcurrent protection devices. Grounding is the intentional

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

TECHNICAL ARTICLE. Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009

TECHNICAL ARTICLE. Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009 TECHNICAL ARTICLE Inspecting Existing Dwelling Electrical Systems Using NFPA 73 by Skip Walker September 2009 Many inspectors were contractors in some prior life. The progression from contractor to inspecting

More information

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates. SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

TABLE 1-E (2017) Effective July 1, 2017

TABLE 1-E (2017) Effective July 1, 2017 TABLE 1-E (2017) Effective July 1, 2017 Oregon Amendments to the 2017edition of the National Fire Protection Association (NFPA) 70, National Electrical Code (NEC) for the 2017 Oregon Electrical Specialty

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

NewGeneration Cables. BELDENCable TM

NewGeneration Cables. BELDENCable TM NewGeneration Cables BELDENCable TM Table of Contents New Generation Cables Page No. Introduction 13.2 New Generation Cable Finder Guide 13.3 13.6 Security and Alarm Cable 13.7 13.26 Unshielded Multi-conductor:

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

5. Identification products.

5. Identification products. Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 [SECTION 260523- CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

Overview of Significant 2017 NEC Changes

Overview of Significant 2017 NEC Changes Overview of Significant 2017 NEC Changes National Fire Protection Association. All rights reserved. Five New NEC Articles Article 426 Fixed Resistance and Electrode Industrial Heating Equipment Article

More information

CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST

CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST Plan Check No. Plan Check Expiration Date Job Address: Square Footage Use Zone Fire Zone Occ. Group Type of Construction No. of Stories Applicant Phone

More information

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR September 2012, rev. 00 26 0553 Identification for Electrical Systems PART 1. GENERAL 1.01 Summary A. Section Includes: 1.02 Submittals 1. Identification for raceways. 2. Identification of power and control

More information

2014 National Electrical Code & NFPA 70E/Arc Flash

2014 National Electrical Code & NFPA 70E/Arc Flash Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 3 From: Kimberly Shea, Project Administrator

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 27 COMMUNICATIONS SECTION PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS SECTION 275116 - PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Preamplifiers. 2. Power amplifiers. 3. Microphones. 4. Control console. 5. Loudspeakers.

More information

Understanding Your Options: AFCI Protection and the 2015 CE Code

Understanding Your Options: AFCI Protection and the 2015 CE Code Understanding Your Options: AFCI Protection and the 2015 CE Code November 25, 2014 Eaton 2008 Eaton Corporation. All rights reserved. Classifying An Arc Fault Operational Arcs - occur in a properly functioning

More information

EXTINGUISHING SYSTEM DETECTION AND CONTROL

EXTINGUISHING SYSTEM DETECTION AND CONTROL GAP.13.0.1 A Publication of Global Asset Protection Services LLC EXTINGUISHING SYSTEM DETECTION AND CONTROL INTRODUCTION Extinguishing systems require prompt detection systems so they operate quickly and

More information