WATER INGRESS ALARM SYSTEM ON BULK CARRIERS ELECTRODE TYPE DETECTOR SUPER EYE
|
|
- Mary Lamb
- 6 years ago
- Views:
Transcription
1 SHEET NO A WATER INGRESS ALARM SYSTEM ON BULK CARRIERS TYPE DETECTOR SUPER EYE SUPER EYE water ingress alarm system is certified by every classification society for the ships (ABS, BV, DNV, LR, NK) in accordance with IACS SC180 (Sep.2003/Rev.1 May 2004) Hold. Ballast and dry space water level detectors (SOLAS chapter XII, Regulation 12 (IMO Resolution MSC. 134(76)) and Performance Standards for Water Level Detectors on Bulk Carriers (IMO Resolution MSC. 145(77)) 1 KC IDEAL TECHNOLOGY
2 WHEELHOUSE BOSUN STORE MAIN JUNCTION BOX BOX WHEELHOUSE ENGINE ROOM TYPE N0.9 CARGO HOLD TYPE N0.8 CARGO HOLD TYPE N0.2 CARGO HOLD TYPE N0.1 CARGO HOLD F. P. T. ALARM PANEL (IP23) (IN WHEELHOUSE) L-MPYC-37 L-MPYC-37 CONTROL PANEL (IP23) (IN AIR CONDITION ROOM) H-DPYC-1.5 H-DPYC-1.5 L-MPYC-19 MAIN ELECTRIC SOURCE AC100V 1Ø 60Hz EMERGENCY ELECTRIC SOURCE DC24V VDR OUTPUT L-MPYC-27 L-MPYC-27 MAIN JUNCTION BOX (IP23) PROVIDED BY SHIP YARD BOX2 (IP68) BOX1 (IP68) COMPANION ROOM (IP56) JUNCTION BOX (JB-1) ENGINE ROOM (IP56) BOX9 (IP68) BOX8 (IP68) BOX7 (IP68) BOX6 (IP68) BOX5 (IP68) BOX4 (IP68) BOX3 IN CARGO HOLD MAIN ALARM LEVEL PRE-ALARM LEVEL NO.9 CARGO HOLD NO.8 CARGO HOLD NO.7 CARGO HOLD NO.6 CARGO HOLD NO.5 CARGO HOLD NO.4 CARGO HOLD NO.3 CARGO HOLD MAIN MAIN PRE PRE NO.2 CARGO HOLD NO.1 CARGO HOLD * : MAKER SUPPLY WIRE BOSUN STORE F. T. P. 2
3 WHEELHOUSE CONTROL PANEL BOX BOX IN CRANE POST BOX IN CRANE POST BOX IN CRANE POST BOX IN CRANE POST BOSUN STORE ENGINE ROOM ENGINE ROOM TYPE N0.5 CARGO HOLD TYPE N0.4 CARGO HOLD TYPE N0.3 CARGO HOLD TYPE N0.2 CARGO HOLD TYPE N0.1 CARGO HOLD F. P. T. (IP23) ALARM PANEL (IN WHEEL HOUSE) L-MPYC-27 L-MPYC-27 CONTROL PANEL (IP23) L-DPYC-2.5 L-MPYC-2.5 MAIN ELECTRIC SOURCE AC100V 1Ø 60Hz EMERGENCY ELECTRIC SOURCE DC24V ACTUATOR OF EDUCATOR VALVE (IP56) IN ENGINE ROOM BOX5 KD-1019 IN CRANE POST (IP56) BOX4 KD-1019 IN CRANE POST (IP56) BOX3 KD-1019 IN CRANE POST (IP56) BOX2 KD-1019 IN CRANE POST (IP56) BOX1 KD-1019 (IP68) BOSUN STORE JUNCTION BOX JB300KZ HYDLAULICK CONTROL STAND BOSUN STORE IN HOLD MAIN ALARM LEVEL PRE-ALARM LEVEL F. P. T. NO.5 HOLD NO.4 HOLD NO.3 HOLD NO.2 HOLD NO.1 HOLD 3
4 Electric current + _ 4
5 + _ + 5
6 CABLE CABBLE GLAND IP68 AIR PRESSURE INSTALLATION PLATE TEST PORT PROVIDE BY SHIPYARD 1/4 ø (30) TERMINAL EPOXY RESIN ø64 90 ø115 SUS CABLE GLAND IP68 FLANGE WITH CABLE GLAND JIS 5K 32A FLANGE PROVIDED BY SHIPYARD 32A STPG370 SCH80 (GALVANIZE) PIPE SUPPORT CABLE GLAND IP68 JIS 5K 32A FLANGE TERMINAL Ti with Pt PLATING MAIN ALARM LEVEL 10% VOLUM OF F. P. T. SUS316 AIR PRESSURE TEST PORT & DRAIN PLUG WITH SEAL TAPE OR LIQUID SEALANT (30) 182 BASE LINE H SEPARATOR PVC 6
7 CARGO HOLD SIDE FLANGE PACKING 8-M16 BOLTS WELD BY SHIPYARD AIR PRESURE TEST PORT 1/4 CABLE GRAND IP68 ø165 ø120 MAIN ALARM LEVEL (30) S WELD BY SHIPYARD CABLE GRAND IP68 PRE-ALARM LEVEL BODY SCS13 DOUBLEING PLATE (SM490) ENGINE ROOM CARGO HOLD SIDE FLANGE PACKING PFTE 8-M16 BOLTS WELD BY SHIPYARD AIR PRESSURE TEST PORT 1/4 CABLE GLAND IP68 MAIN ALARM LEVEL TERMINAL DOUBLING PLATE (SM490) S (30) WELD BY SHIPYARD ø200 ø165 ø 52 ø 92 ø 120 ø 250 PRE-ALARM LEVEL DOUBLING PLATE (SM490) BOTTOM LINE 7
8 4-ø15 HOLES CABLE GLAND TERMINAL EPOXY RESIN AIR PRESUSURE TEST PORT 1/4 COVER SCS13 PLATINUM PLATING TITANUM ø115 ø90 ø16 ø64 90 SUS316 BODY SCS13 TERMINAL ARRANGEMENT T2 T1 S2 S1 (PLATINUM PLATING TITANUM) (SUS316) 8
9 ø15 HOLES FLANGE SUS13 ø115 ø90 ø16 ø64 90 CABLE GLAND TERMINAL EXPOXY RESIN AIR PRESSURE TEST PORT 1/4 DOUBLING PLATE SM490 or EQUIVALENT 20 8-ø19 HOLES COVER SCS13 Ti with Pt PLATING 40 ø200 ø ø52 ø BODY SCS13 SUS316 TERMINAL ARRANGEMENT T2 T1 S2 S1 (Ti with Pt PLATING) (SUS316) 9
10 a 20c 20c 4-ø9 SETTING HOLES ABT BODY 2 COVER 3 GASKET 4 CRAMPING SCREW 5 CABLE GLAND 6 NAME PLATE 7 HINGE 3.2 TERMINAL CABLE GLAND SKINDICHT M8X45 (SUS) ø10 AIR PRESSURE TEST PORT 1/4 10
11 8 20c 25a c ø9 SETTING HOLES ABT BODY 2 COVER 3 GASKET 4 CRAMPING SCREW 5 CABLE GLAND 6 NAME PLATE 7 HINGE 8 ZENER AIR PRESSURE TEST PORT 1/ (200) 47 PREPARED BY SIPYARD MOUNT 1 BODY 2 COVER 3 GASKET 4 CRAMPING SCREW 5 CABLE GLAND 6 NAME PLATE 7 ZENNER ø10 11
12 ELEC SOURCE ø15 HOLES 200 ELEC SOURCE ø15 HOLES
13 CAUTION PLATE FOR FRESH / SEA SWITCH ø CAUTION PLATE FOR FRESH / SEA SWITCH ø
14 400 4-ø CAUTION PLATE FOR FRESH / SEA SWITCH COAMING 40X M6 14
15 400 4-ø CAUTION PLATE FOR FRESH / SEA SWITCH COAMING 40X M6 15
16 16
***** 2. Rev.1 is to be uniformly implemented by IACS Members from 1 July 2004.
(Sept 2003) (Rev.1 May 2004) (Rev.2 Nov 2005) (Rev.3 Mar 2012) Hold, ballast and dry space water level detectors (Chapter II-1/25 and Chapter XII/12) and Performance Standards for Water Level Detectors
More informationRESOLUTION MSC.145(77) (adopted on 5 June 2003) PERFORMANCE STANDARDS FOR WATER LEVEL DETECTORS ON BULK CARRIERS
MSC 77/26/Add.1 RESOLUTION MSC.145(77) THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee, RECALLING
More informationRESOLUTION MSC.188(79) (adopted on 3 December 2004) PERFORMANCE STANDARDS FOR WATER LEVEL DETECTORS ON BULK CARRIERS AND SINGLE HOLD CARGO SHIPS
MSC 79/23/Add.2 RESOLUTION MSC.188(79) THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee, RECALLING
More informationTechnical Manual. Level Alarm Unit CARLA & WIDS
CARLA & WIDS Technical Manual SAS au Capital de 2 158 244-444 871 933 R.C.S. Bourges - APE : 2651B Headquarter : 9, rue Isaac Newton - 18000 Bourges - France Technical Manual CARLA for Tankers Cargo Tanks
More informationE-20 COMPARTMENT FLOODING WATER LEVEL DETECTORS (INCLUDING SENSORS)
Guideline No.: E-20(201510) E-20 COMPARTMENT FLOODING WATER LEVEL DETECTORS (INCLUDING Issued date: October 20,2015 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains
More informationMain changes in BV Rules for Steel Ships
Main changes in BV Rules for Steel Ships Main changes in Bureau Veritas Rules for the Classification of Steel Ships (January 2018 edition, into force on January 1st, 2018), regarding the previous edition
More informationFS-100 Series OUTLINE MAIN APPLICATIONS FEATURES LEVEL SWITCH
PERFECT ISOLATION BY MAGNET COUPLING COVERING HIGH TEMP., HIGH PRESS., AND VACUUM APPLICATIONS PRESSURE TIGHT FLAMEPROOF FOR HYDROGEN ATMOSPHERE READY SPRING BALANCED DISPLACER TYPE FS- Series LEVEL SWITCH
More informationSurvey of electrical equipment installed in hazardous areas on tankers
(June 2015) Survey of electrical equipment installed in hazardous areas on tankers 1. Application The recommendations in this document apply for survey of electrical installation in hazardous areas on
More informationIMO FP 53 Report. Lloyd s Register report on the 53 rd session of IMO Fire Protection Sub-Committee. 16 th March, 2009
IMO FP 53 Report Lloyd s Register report on the 53 rd session of IMO Fire Protection Sub-Committee 16 th March, 2009 Hot topics: Consideration continues on inerting to prevent fire and explosion on small
More informationVoid. Technical Information. Subject. Bulk Carrier Safety:Water Ingress Detection and Alarm System. No. TEC-0537 Date 3 July 2003
Subject Bulk Carrier Safety:Water Ingress Detection and Alarm System To whom it may concern Technical Information No. TEC-0537 Date 3 July 2003 As previously informed by ClassNK Technical Information No.
More informationClassNK Technical Information No. TEC-0453 Attachment (1) to ClassNK Technical Information No. TEC-0453 Guidance on SOLAS Chapter II-2 as amended in 2
Subject: Guidance on SOLAS chapter II-2 as amended in 2000 Technical Information No. TEC-0453 To whom it may concern Date 22 April 2002 As stated in ClassNK Technical Information No. 406, SOLAS as amended
More informationGeneral Specifications
General Specifications Model DM8 Vibration Type Liquid Density Meter Overview In 1967, YOKOGAWA developed the Model VD6 Vibration Type Liquid Density Meter in response to user requests for an online density
More informationNavigation Lights Signalling Lights Searchlights Whistles TECHNICAL DOCUMENT. DHR 230RCN 230 Remote Controlled Searchlight. Den Haan Rotterdam
Navigation Lights Signalling Lights Searchlights Whistles TECHNICAL DOCUMENT DHR 0RCN 0 Remote Controlled Searchlight Since 9 (Intentionally blank page) Version.0 October 08 ! Safety notes: Turn power
More informationDRY CHEMICAL POWDER SYSTEM REQUIREMENTS TO COMPLY WITH THE LATEST IMO IGC CODE AND EUROPEAN COUNCIL CLARIFICATIONS
DRY CHEMICAL POWDER SYSTEM REQUIREMENTS TO COMPLY WITH THE LATEST IMO IGC CODE AND EUROPEAN COUNCIL CLARIFICATIONS Tested down to Tested in long pipes 19 Published 18 November, 2016 Joe Blogs, Survitec
More informationFan Heaters Type VLEx
Fan Heaters Type VLEx Fan Heater type VLEx has been designed for Explosion Proof industrial applications. Our Fan Heaters are characterized mainly by their quality, both in used materials and design. Liquids
More informationCOMPANY INTRODUCTION
COMPANY INTRODUCTION Since 1971 COMPANY INTRODUCTION Company Name SAMGONG CO., LTD President & CEO J.S. Zong Head Office & Factory 135, Noksansandan 17Ro, Kangso-ku, Busan, Korea 46751 TEL +82-51-200-3040
More informationSCC 101 G Valid as of G11SE0404 up to G11SE... SCC 101 G
Gas unit Voltage 1NAC 230V 50-60Hz 1 1 Control panel 2 2 Electrical installation 3 3 Clima Plus 4 4 Steam generator, Bypass 5 5 Hot air heating 6 6 Motor and fan wheel 7 7 Interior cabinet 8 8 Door 9 9
More informationHoneywellmarine.com. Honeywell Proprietary
Systems Overview Cargo Level Gauging System for tankers and FPSO Integrated system measuring level, temperature, inert gas pressure, etc, for ballast and cargo tanks Inclinometers (Trim and list) Provides
More informationINERIS 01ATEX0060 (standard) TR CU (marking upon request, ordering code to be required)
FLUORESCENT LIGHTING RMS-560.. Series - Fluorescent lighting fixtures TECHNICAL FEATURES RMS.. series lighting fixtures are ideally suited for ON and OFF-SHORE applications and all kinds of industries
More informationNotice on the implementation of the amendments to the FSS Code in resolution MSC.339(91)
C C S 通函 Circular China Classification Society (2013) Circ.111 /Total No.397 25/07/2013 (total pages:18) To relevant departments of CCS Headquarters, Shanghai Rules and Research Institute, plan approval
More informationNotice No. 7. Rules and Regulations for the Classification of Ships, July Issue date: March Working together for a safer world
Notice No. 7 Rules and Regulations for the Classification of Ships, July 2014 The status of this Rule set is amended as shown and is now to be read in conjunction with this and prior Notices. Any corrigenda
More informationFlammable liquids, gasoline, oil etc. Advantages. 21 B. Ø 920 mm 21 B. Ø 920 mm
1370 14133 14133 Powder Wheeled Fire Extinguisher kg 25 Approved EN 166-1:200, Marina MED, higest rate achieved - A IVB C CSI Certificate MED/0497/126/09 Organic solid materials, wood rubber, textiles
More informationDisplay Cases Deli Cases Service Manual
Turbo Air Speed up the Pace of Innovation CAUTION! PLEASE KEEP POWER SWITCH ON BEFORE OPERATING THIS EQUIPMENT Display Cases Deli Cases Service Manual Please read this manual completely before attempting
More informationC e r t i f i c a t e
C e r t i f i c a t e of EC Type-examination (Module B) Certificate Nº: 09212007/AA/01 Product Category: A.1/5.13 With respect to Marine Equipment Directive 96/98/EC and the amending Directive 2008/67/EC,
More informationKUBOTA Double suction volute pump
PUMPS CATALOGUE KUBOTA Double suction volute pump DV-L type J series KUBOTA Corporation DOMESTIC OFFICES AND OVERSEAS OFFICE E-Mail:pump@kubota.co.jp http://www.kubota.co.jp/english KUBOTA Double suction
More informationIACS RESOLUTION CHANGES (GMO ) BEKİR SITKI TÜRKMEN
IACS RESOLUTION CHANGES (GMO - 10-12- 2015) BEKİR SITKI TÜRKMEN Resolution Changes January & July 2016 (UR, UI, PR, REC) 3+ 1 1 + 0 0 + 7-10 1 + 5 Total UR Changes = 9 (Jan 2016) + (28 10) (July 2016)
More informationMain changes in BV Rules for Steel Ships
Main changes in BV Rules for Steel Ships Main changes in Bureau Veritas Rules for the Classification of Steel Ships (January 2019 edition, into force on January 1 st, 2019), regarding the previous edition
More informationTemperature Measurement Transmitters for field mounting
Siemens AG 07 Overview Application The SITRANS TF can be used everywhere where temperatures need to be measured under particularly harsh conditions. For that reasons users from all industries have opted
More informationWaterproof TCW060 just light
Lighting Waterproof TCW060 just light TCW060 Designed for use in demanding environments, TCW060 is an economical, compact waterproof luminaire. Dedicated versions are available for TL-D and TL5 lamps.ingressprotected
More informationTechnical Data Sheet BNWAS. Bridge Navigational Watch Alarm System. Technical Data Sheet. General Features
Technical Data Sheet BNWAS Bridge Navigational Watch Alarm System Technical Data Sheet General Features Technical Data Sheet Bridge Navigational Watch Alarm System (BNWAS) New SOLAS regulations require
More informationSCC 61 E Valid as of E61SE0404 up to E61SE... SCC 61 E
Electrical unit Voltage 3NAC 400V 50-60Hz 1 1 Control panel 2 2 Electrical installation 3 3 Clima Plus 4 4 Steam generator, Bypass 5 5 Hot air heating 6 6 Motor and fan wheel 7 7 Interior cabinet 8 8 Door
More informationMSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017
Procedure Number: E1-03 Revision Date: 02/16/2017 References: S. T. Brady, CDR, Chief, Engineering Division a. National Fire Protection Association (NFPA) 750, 1996 Edition, Standard on Water Mist Fire
More informationDASPOS A/S Gammel Klausdalsbrovej Herlev Denmark Tel.: website: DASPOS USA, Inc NE 116th Street, PMB
LAS-10 - Leakage Alarm System Atmospheric oil mist and hydrocarbon detection Early warning system Your challenges Each year, there are several hundred fires recorded aboard merchant ships; 63% occur in
More informationCOMPANY PROFILE. Design, Development & Installation of Electrical & Automatic Control Systems
COMPANY PROFILE Design, Development & Installation of Electrical & Automatic Control Systems MSB/ESB Main & Emergency Switchboards PMS Power Management Systems Engine Room Alarm Monitoring Systems Engine
More informationCB IP40. Specification. Cold rolled steel sheet. Enclosure s body and mounting plate: 1 mm. Door panel: 1.5 mm.
CB IP40 CB IP40 Standard is an enclosure that protects electrical equipment from dust and water spray. It is suitable for indoor purposes. This enclosure is made of a cold rolled steel sheet and has a
More informationModel VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass
Project: Customer: Engineer: Pump Manufacturer: Submittal Document Model VPS Pressure Limiting (VFD) with Soft Start Bypass Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Note:
More informationIACS Unified Interpretations and Panel Responsible
UI CCx (concerning IMO Chemical Code) CC1 Interpretation of sub-section 3.9(b), BCH Code CC2 Interpretation of paragraph 4.9.2, BCH Code CC3 Interpretation of paragraph 4.11.2, BCH Code CC4 Interpretation
More information15-BER3. parts list as Excel-spreadsheet. Tsurumi Europe GmbH
5-BER3 data sheet parts list exploded view dimensional drawing free standing type dimensional drawing TOS-type sectional drawing free standing type sectional drawing TOS-type performance curve parts list
More informationTechnology. Drum H eaters ZIEGLER ENGINEERING. Metal drum heater design
Technology Metal drum heater design Drum H eaters Isopad offers a range of drum and base heaters that provide a reliable way to reduce viscosity, protect stored product from frost and enable product removal.
More informationManual. Simrad Panorama Mk2 Rudder Angle Indicator. English. A brand by Navico - Leader in Marine Electronics.
Manual Simrad Panorama Mk2 Rudder Angle Indicator English www.simrad-yachting.com A brand by Navico - Leader in Marine Electronics Manual Simrad Panorama Mk2 Rudder Angle Indicator English Document no:
More informationPLATE HEAT EXCHANGERS FOR MARINE APPLICATIONS
PLATE HEAT EXCHANGERS FOR MARINE APPLICATIONS www.tranter.com There are times when the reliability of your equipment is crucial! When conditions are tough, crew and equipment are really put to the test.
More informationGuideline No.: C-02(201510) C-02 FIRE DOORS. Issued date: October 20,2015. China Classification Society
Guideline No.: C-02(201510) C-02 FIRE DOORS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and
More informationRosemount TankRadar STaR
Technical Description Rosemount TankRadar STaR Tank Gauging, Alarm Handling and Cargo Control System The contents, descriptions and specifications within this document is subject to change without prior
More informationMarine Solutions. Honeywell s Solution for LNG Vessels
Marine Solutions Honeywell s Solution for LNG Vessels Integrated automation systems for LNG vessels. Honeywell is the leading supplier of Integrated Automation Systems (IAS) for LNG carriers and newer
More informationRESOLUTION MSC.217(82) (adopted on 8 December 2006) AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS
RESOLUTION MSC.217(82) AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning
More informationSPECIFICATION SHEET ORGANIC POLLUTION MONITOR. Model: OPM-410A - Organic Pollution Monitor - Issue: OPM-410A-0107-R0 Page 1 ISO ISO-9001
ISO-14001 ISO-9001 SPECIFICATION SHEET ORGANIC POLLUTION MONITOR Model: OPM-410A The Model OPM-410A monitors organic pollution in water from industrial effluent, rivers etc.. The design and construction
More informationAnalog Transmitter AT1000 AT1
Technical Information Analog Transmitter AT1000 AT1 Alarm Transmitter for Mechanical Level Gauges Application AT1 analog transmitter is designed to be installed to the LT, and LTC series float level gauge.
More informationPart 6 Additional class notations Chapter 6 Additional fire protection for passenger vessels
RULES FOR CLASSIFICATION Inland navigation vessels Edition December 2015 Part 6 Additional class notations Chapter 6 Additional fire protection for passenger vessels The content of this service document
More informationMSC Guidelines for Foam Fire Suppression Systems
References: S. T. Brady, CDR, Chief, Engineering Division a. 46 CFR 34.17, Tank Vessel Fixed Foam b. 46 CFR 34.20, Tank Vessel Deck Foam c. 46 CFR 76.17 Passenger Vessel Foam d. 46 CFR 95.17, Cargo Vessel
More informationAdditional Fire Protection (F-AMC)
RULES FOR CLASSIFICATION OF Ships PART 6 CHAPTER 4 NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS Additional Fire Protection (F-AMC) JANUARY 2011 This chapter has been amended since the main
More informationPersonal ph, ph/orp, Conductivity Meters
Personal ph, ph/orp, Meters PH71/PH72/SC72 Personal ph, ph/orp, Meters Bulletin 12B03D01-01E www.yokogawa.com/an/ Compact and lightweight 220g IP67 Waterproof CE,C-tick Compliance Various Convenient Functions
More informationElectromagnetic Flowmeter
LF654 /LF620 Field Intelligent Device Mount Anywhere Series - Flanged LF654 /LF622 Electromagnetic Flowmeter 1/2" to 18" (15 to 450 mm) Introduction The electromagnetic flowmeter uses Faraday s Law of
More informationPATROL BOATS HIGH SPEED, LIGHT CRAFT AND NAVAL SURFACE CRAFT RULES FOR CLASSIFICATION OF DET NORSKE VERITAS SPECIAL SERVICE AND TYPE ADDITIONAL CLASS
RULES FOR CLASSIFICATION OF HIGH SPEED, LIGHT CRAFT AND NAVAL SURFACE CRAFT SPECIAL SERVICE AND TYPE ADDITIONAL CLASS PART 5 CHAPTER 6 PATROL BOATS JULY 2009 This booklet includes the relevant amendments
More informationEJBX. Ex d. AISI 316L stainless steel. - Zone 1, 2, 21, 22 - Group IIB+H2 - Stainless steel junction boxes - Choice of 13 sizes - IP 66 / 67
Ex d EJBX AISI 316L stainless steel - Zone 1, 2, 21, 22 - Group IIB+H2 - Stainless steel junction boxes - Choice of 13 sizes - IP 66 / 67 Quartz sand blasting Warning labels Mounting bracket Silicone gasket
More informationRequirements for ships carrying hydrogen and compressed natural gas vehicles
Lloyd's Register briefing IMO FP 55 Summary report for clients Overview The 55 th session of the IMO Fire Protection Sub Committee (FP) was held from 25 th to 29 th July 2011, at the IMO headquarters in
More informationon board with solutions
ABOUT US Garant Safety is a part of Garant Group. Garant Safety is a safety and firefighting equipment supplier and service station, certified to conduct periodic equipment inspections and tests, as well
More informationConductive Leakage detectors of the Leckstar range
Conductive Leakage detectors of the Leckstar range with electrode and relay Jola Spezialschalter GmbH & Co. KG Klostergartenstr. 11 67466 Lambrecht (Germany) Tel. +49 6325 188-01 Fax +49 6325 6396 www.jola-info.de
More informationDNVGL-CP-0398 Edition December 2015
CLASS PROGRAMME Type approval DNVGL-CP-0398 Edition December 2015 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD
More informationINSTRUCTION MANUAL with Replacement Parts
INSTRUCTION MANUAL with Replacement Parts MODEL FD500 FOOD WASTE DISPOSERS (INCLUDES MOTOR PARTS) ML-18978 A product of HOBART CORPORATION 701 S. RIDGE AVENUE TROY, OHIO 45374-0001 FORM 11394 Rev. G (10-98)
More informationPersonal ph, ph/orp, Conductivity Meters
Personal ph, ph/orp, Meters PH71/PH72/SC72 Personal ph, ph/orp, Meters Bulletin 12B03D01-01E www.yokogawa.com Compact and lightweight 220g IP67 Waterproof CE,C-tick Compliance Various Convenient Functions
More informationProduct Catalog June 2012
Product Catalog Category Description Page Product Categories 1 Plastic Pipe Cements and Primers Oatey, Hercules and United Elchem solvent cements, primers, cleaners and related products 2 Thread Sealants
More informationC-01 FIRE DECKS AND BULKHEADS
Guideline No.: C-01(201510) C-01 FIRE DECKS AND BULKHEADS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection
More informationRECORD OF GARBAGE DISCHARGES PART II. For all cargo residues as defined in regulation 1.2 (Definitions) (Ships that carry solid bulk cargoes)
1 RECORD OF GARBAGE DISCHARGES PART II For all cargo residues as defined in regulation 1.2 (Definitions) (Ships that carry solid bulk cargoes) MU6654e - 12018 2 1 Introduction In accordance with regulation
More informationPersonal ph, ph/orp, Conductivity Meters PH71/PH72/SC72
Personal ph, ph/orp, Meters PH71/PH72/SC72 Personal ph, ph/orp, Meters Bulletin 12B03D01-01E www.yokogawa.com/ Compact and lightweight 220g IP67 Waterproof Various Convenient Functions Data memory Alarm
More informationROP-63 & ROP-63H MANUAL CALL POINTS
ROP-63 & ROP-63H MANUAL CALL POINTS Installation and Maintenance Manual IIA Issue 2 The ROP-63 and ROP-63H manual call points, covered by the present manual, complies with the requirements of the following
More informationComplete tank expertise. Marine tank management solutions for all ship types
Complete tank expertise Marine tank management solutions for all ship types understanding of the conditions of the marine market. You ll find we re unique in our in-depth understanding of the details of
More informationBevent Rasch BSKC6. - Fire /06/17
Bevent Rasch - Fire - BSKC6 19/06/17 Fire resistance class EI60/EI60S Sizes from 100 mm to 630 mm Prefitted safety actuator 24V or 230V Low weight Easy installation CE-marked building product according
More information2013Mexico USA Safety Seminar. Rapp Bomek AS Fire and Explosion Proof Doors
Rapp Bomek AS Fire and Explosion Proof Doors 2013Mexico USA Safety Seminar RAPP BOMEK AS Kvitberget 5, 8012 Bodø Norway Tel. +47 75 59 16 00 Fax. +47 75 59 16 10 office@rappbomek.com Presenting Rapp BomekAS
More informationBR
BR-500 www.furuno.com Monitor watch officer's presence and receive early warning detections in case of an emergency Flash Beacon Watertight Motion Detector Meets the IMO resolution MSC.128(75) for Bridge
More informationFirePro ANNEX 1 MARINE MANUAL. Version 1,
Marine Design Guide ANNEX 1 MARINE MANUAL To be read and used in conjunction with FirePro Information, Instruction & User Manual Version 4, 01-05-2010 FirePro Systems Ltd 6 Koumandarias & Spyrou Araouzou
More informationLEAKSTOPPER RANGE Multizone water leak detection systems
LEAKSTOPPER RANGE Multizone water leak detection systems WHAT DOES THE PRODUCT DO? The LeakStopper detects water leaks and instantly triggers an alarm to warn you. It is capable of monitoring between 2
More informationIMO CCC1 Summary Report on the developments of the IGF Code
IMO CCC1 Summary Report on the developments of the IGF Code London, 08-12 September 2014 BUREAU VERITAS Marine & Offshore Division Compliance & Regulations Contents Introduction Item: Development of international
More informationGuidance on the construction of CO 2 systems
Translation. Only the Danish document has legal validity. Guidance no. 9515 of 9 July 2014 issued by the Danish Maritime Authority Guidance on the construction of CO 2 systems 1. Introduction Notice B
More informationGAS COMPONENTS ELECTRIC COMPONENTS WATER TECHNOLOGY MECHANICAL COMPONENTS TOOLS. Spare parts suitable for MIWE
GAS COMPONENTS ELECTRIC COMPONENTS WATER TECHNOLOGY MECHANICAL COMPONENTS TOOLS Spare parts suitable for MIWE MIWE heating elements/thermostats heating elements heating elements for ovens safety thermostats
More informationPRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM
ANNEXUREIII D: FIRE PROTECTION SYSTEM SECTION ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Supply, Installation, testing and commissioning of Analogue Addressable Fire Alarm Control panel with battery backup
More informationCONTROL NARRATIVE. Ammonia Tank Farm Aqueous Ammonia Truck Unloading, Storage Tanks, Forwarding, Vaporizer & Dilution Air Package
CONTROL NARRATIVE Ammonia Tank Farm Aqueous Ammonia Truck Unloading, Storage Tanks, Forwarding, Vaporizer & Dilution Air Package ABOVE: Exmple of an Ammonia Tank Farm built by IFS. Document Number: CN-24729-01-3
More informationSOLAREKS - ELECTRIC WATER HEATER
SOLAREKS ELECTRIC WATER HEATER We want every product which we manufacture to be the best quality...i put my name on it SOLAREKS ALPER UYSAL SI UNIT CATALOGUE THREEPHASE INSTANT ELECTRIC WATER HEATER FOR
More informationInstruction Manual April sitrans AS 100
Instruction Manual April 2005 sitrans AS 100 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment.
More informationPOINT HELIDECK LIGHTS PRL-LSM LED v4 LOW SURFACE MOUNT LIGHT
Compliances: ETL Listed to UL 1598A Marine Vessels at -40 deg C to +55 deg C ETL Listed to CSA C22.2 No. 137-M1981 & No. 250.0-08 Canada ETL Listed to UL 1598 at -40 deg C to +55 deg C IMO 2009 MODU Code
More informationPOINT HELIDECK LIGHTS PRL-LSM LED v4 LOW SURFACE MOUNT LIGHT
Compliances: ETL Listed to UL 1598A Marine Vessels at -40 deg C to +55 deg C, IP66 & IP67 ETL Listed to CSA C22.2 No. 137-M1981 & No. 250.0-08 Canada ETL Listed to UL 1598 at -40 deg C to +55 deg C IMO
More informationFAN SEPARATOR. Fan / Separator H2SO4 (Sulfuric Acid) is Designed to Remove Fume and Other Contaminants from the Air Stream.
FAN SEPARATOR Fan / Separator H2SO4 (Sulfuric Acid) is Designed to Remove Fume and Other Contaminants from the Air Stream. FAN / SEPARATOR SPECIFICATIONS Various materials of construction may be used to
More informationAUDIBLE SIGNALIZATION
01 SIGNALIZATION AUDIBLE SIGNALIZATION PROGRAMMABLE ELECTRONIC MULTITONE SIRENS WITH TWO INPUTS Specially designed for marine application With two inputs where using each one, different tones and frequency
More informationIN-SITU ZIRCONIA OXYGEN ANALYZER <HART communication>
DATA SHEET IN-SITU ZIRCONIA OXYGEN ANALYZER ZFK8, ZKM-2, ZTA This oxygen analyzer is used to continuously measure oxygen concentration in combustion exhaust gas of industrial boilers
More informationControl unit PPT/RS,, Controls the functions of the conveyor. Fully pneumatic. The maximum recommended distance between the conveyor and contr
Control unit PPT/RS,, 0111636 Controls the functions of the conveyor. Fully pneumatic. The maximum recommended distance between the conveyor and control unit is 10 metres when feed pressure is 0.6 MPa.
More informationDOO IK ENG PRODUCT CATALOG DOO IK ENG TEMPERATURE SENSOR PRESSURE SWITCH NON FLOW SWITCH THERMOMETER
DOO IK ENG PRODUCT CATALOG DOO IK ENG TEMPERATURE SENSOR PRESSURE SWITCH NON FLOW SWITCH THERMOMETER COMPANY HISTORY & CERTIFICATE COMPANY HISTORY 2004. 06 DOOSAN ENGINE PART SALES AGENT 2005. 01 DSEC
More informationFIRE SAFETY SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS MACHINERY AND SYSTEMS MAIN CLASS PART 4 CHAPTER 10 JULY 2006
RULES FOR CLASSIFICATION OF SHIPS NEWBUILDINGS MACHINERY AND SYSTEMS MAIN CLASS PART 4 CHAPTER 10 FIRE SAFETY JULY 2006 CONTENTS PAGE Sec. 1 General Requirements... 5 Sec. 2 Fire Safety Measures for Cargo
More informationADDITIONAL FIRE PROTECTION (F-AMC)
RULES FOR CLASSIFICATION OF SHIPS NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 4 ADDITIONAL FIRE PROTECTION (F-AMC) JULY 2006 CONTENTS PAGE Sec. 1 General Requirements...
More informationRESOLUTION MSC.291(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFE AT SEA, 1974, AS
RESOLUTION MSC.291(87) THE MARITIME SAFETY COMMITIEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee, RECALLING FURTHER article
More informationACCESSORIES ITEM NUMBER. Digital timer, burning and ventilating. RT1, RT2, RT3 IT1 DA1 Thermostat for CH 12/18. fault detector.
ACCESSORIES RT1, RT2, RT3 IT1 DA1 Thermostat for CH 12/18. Digital timer, burning and ventilating. Fault detector GSM. GSM temperature fault detector. THERMOSTATS RT1, room thermostat -10/+40 C with 5
More informationBevent Rasch RABC-VAV. - Fire /03/2018
Bevent Rasch - Fire - RABC-VAV 26/03/2018 Fire damper and VAV-damper combined RABC-VAV Fire resistance class E60 Sizes from 100 mm to 630 mm Prefitted safety actuator 24V Installation in ducts Available
More informationSIMPLIFIED VOYAGE DATA RECORDER (S-VDR)
STANDARD FOR CERTIFICATION No. 2.9 SIMPLIFIED VOYAGE DATA RECORDER (S-VDR) APRIL 2009 Veritasveien 1, NO-1322 Høvik, Norway Tel.: +47 67 57 99 00 Fax: +47 67 57 99 11 FOREWORD (DNV) is an autonomous and
More informationREPUBLIC OF LIBERIA BUREAU OF MARITIME AFFAIRS
REPUBLIC OF LIBERIA BUREAU OF MARITIME AFFAIRS Marine Notice INS-004 Rev. 4/05 TO: SUBJECT: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT SHIPS, AND AUTHORIZED CLASSIFICATION SOCIETIES Operational/Safety
More informationSpecifications. Table of contents. 2:Specification. 3:Composition. 4:Instruments outside figure
DUST DENSITY METER (DDM-2001) Specifications Table of contents 1:Outline 2:Specification 3:Composition 4:Instruments outside figure 1) Main body control box 2) Detector 3) Optical fiber cable 4) Purge
More informationAdvanced tank technology
Advanced tank technology Sensors and Automation systems 2 API MARINE / ADVANCED TANK TECHNOLOGY Contents Introduction.... 5 Integrated Automation System Solution for Tankers... 8 Integrated Automation
More informationPOINT ROLLOVER LIGHTS PRL LED HELIDECK SEMIFLUSH LIGHT
Compliances: ETL Listed to UL 98 & UL 98A Marine Vessels USA CSA C22.2 No..-4 Canada FAA AC /39-2B Heliport Design Guide ICAO Annex 14, Volume II UK CAA CAP 437, Chapter 4, paragraph 3.1 IMO 9 MODU Code
More informationMOBILE OFFSHORE DRILLING UNITS 2012
Part 5: Fire and Safety Measures and Features RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS 2012 PART 5 FIRE AND SAFETY MEASURES AND FEATURES American Bureau of Shipping Incorporated by
More informationScrew plug immersion heaters
Screw plug HEATING GASES HEATING LIQUIDS MAINTAINING A CONTINUOUS TEMPERATURE The screw plug by CETAL are designed and manufactured as a standard range or according to customer specifications. Reliability
More informationInstallation Instructions
Condensing Heat Exchanger Kit Cancels: IIK 8A-- IIK 8A--7 -- Installation Instructions Part No. 171-7 through -7 NOTE: Read the entire instruction before starting the installation. INTRODUCTION This instruction
More informationTHE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY
Office of Deputy Commissioner of Maritime Affairs THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY Marine Notice INS-004 Rev. 06/12 TO: SUBJECT: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT
More informationFire. IMO fire control signs - according to IMO Resolution A.654 (16) (mm) 150x x200
IMO fire control signs - according to IMO Resolution A.654 (16) Safety and operating instructions for trained personnel (SIS) - As per ISO 24409, SIS signs are safety-related signs that replicate the symbols
More information