TP48600B-N20B1 V500R002. User Manual. Issue 01. Date HUAWEI TECHNOLOGIES CO., LTD.

Size: px
Start display at page:

Download "TP48600B-N20B1 V500R002. User Manual. Issue 01. Date HUAWEI TECHNOLOGIES CO., LTD."

Transcription

1 V500R002 Issue 01 Date HUAWEI TECHNOLOGIES CO., LTD.

2 2015. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd. Trademarks and Permissions and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd. All other trademarks and trade names mentioned in this document are the property of their respective holders. Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied. The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute a warranty of any kind, express or implied. Huawei Technologies Co., Ltd. Address: Website: Huawei Industrial Base Bantian, Longgang Shenzhen People's Republic of China support@huawei.com i

3 About This Document About This Document Overview This document describes the DC power system in terms of product introduction, component introduction, and system maintenance. The figures of this document are for reference only. Intended Audience This document is intended for: Sales engineers Technical support engineers Maintenance engineers Symbol Conventions The symbols that may be found in this document are defined as follows. Symbol Description Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to personal injury. Calls attention to important information, best practices and tips. NOTE is used to address information not related to personal injury, equipment damage, and environment deterioration. ii

4 About This Document Change History Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues. This issue is the first official release. iii

5 Contents Contents About This Document... ii 1 Safety Precautions General Safety Precautions Electrical Safety Battery Safety Cable Layout Mechanical Safety Overview Introduction Features Working Principle System Configurations Components Interior PDU Rectifier SMU02B UIM02C (Optional) Communications Expansion Module NIM01C Battery Temperature Sensor Maintenance Routine Maintenance Rectifying Common Faults AC Failure AC Over Volt AC Under Volt Phase A/B/C Failure DC Over Volt DC Under Volt Batt Chg. Overcur LLVD Disconnected iv

6 Contents BLVD Disconnected Battery Fuse Break High Amb. Temp Low Amb. Temp High Amb. Humi Low Amb. Humi Batt. High Temp Batt. Low Temp Rectifier Missing Rect Fault Rect Protection Rect Comm Fault Load Fuse Break AC SPD Alarm DC SPD Alarm Identifying Component Faults Identifying AC SPD Faults Identifying Circuit Breaker Faults Identifying Rectifier Faults Identifying SMU Faults Parts Replacement Replacing a Rectifier Replacing an SMU Replacing an AC SPD Module Replacing a Circuit Breaker Replacing the PCB of UIM02C Replacing a Battery Temperature Sensor A Technical Specifications A.1 Environment Specifications A.2 Electrical Specifications A.3 EMC Specifications A.4 Cabinet Specifications A.5 Rectifier Specifications B Electrical Conceptual Diagram C Associations Between Dry Contacts and Alarms D Acronyms and Abbreviations v

7 1 Safety Precautions 1 Safety Precautions 1.1 General Safety Precautions Ensure that the product is used in environments that meet its design specifications to avoid damaging components and voiding the warranty. Ensure that only trained and qualified personnel install, operate, and maintain Huawei equipment. Comply with local laws and regulations. The safety instructions in this document are only supplements to local laws and regulations. Do not operate the device or cables during thunderstorms. Remove metal objects such as watches, bracelets, and rings when using the product. Use insulated tools on the product. Follow specified procedures during installation and maintenance. Measure contact point voltage with an electric meter before touching a conductor surface or terminal. Ensure that the contact point has no voltage or it is within the specified range. Note that the load may power off during maintenance or fault location if the power system is not connected to a battery or if battery capacity is insufficient. Store cables for at least 24 hours at room temperature before laying out them if they were previously stored at sub-0ºc. Routinely check installed equipment and perform maintenance according to the user manual; replace faulty components quickly to ensure that the device works properly. 1.2 Electrical Safety Grounding Requirements When installing a device, install the ground cable first. When removing a device, remove the ground cable last. Before operating a device, ensure that the device is properly grounded. AC and DC Operation Requirements 1

8 1 Safety Precautions ESD Requirements The power system is powered by high-voltage power sources. Direct or indirect contact (through damp objects) with high-voltage power sources may result in serious danger. Non-standard and improper operations may result in fire and electric shocks. Before electrical connections, turn off the upstream protection switch for the device. Before connecting the AC power supply, ensure that electrical connections are complete. Before you connect cables to loads or battery cables, check cable and terminal polarities, preventing reverse connections. To prevent electrostatic-sensitive components from being damaged by the static on human bodies, wear a well-grounded ESD wrist strap or gloves when touching circuit boards. When holding a board, hold its edge without components. Do not touch chips. Removed boards must be packaged with ESD packaging materials before storage and transportation. Liquid Prevention Requirements Place this product far away from areas with liquid. Do not place the product under positions prone to leakage, such as air conditioner vents, ventilation vents, and feeder windows of the equipment room. Prevent liquid from entering the inside of the device to avoid short circuits, and ensure that there is no condensation inside the equipment room or device. If detecting any liquid inside the device, immediately disconnect the power supply and contact the administrator. 1.3 Battery Safety Basic Requirements Before installing, operating, and maintaining batteries, read the instructions provided by the battery vendor. The safety precautions in this document are for special attention. For more safety precautions, see the instructions provided by the battery vendor. Before installation and maintenance, wear goggles, rubber gloves, and protective clothes to prevent injury caused by electrolyte overflow. When handling a battery, ensure that its electrodes are upward. Leaning or reversing batteries is prohibited. Keep the battery loop disconnected during installation and maintenance. Secure battery cables to a torque specified in battery documentation. Loose connections will result in excessive voltage drop or cause batteries to burn out when the current is large. 2

9 1 Safety Precautions Preventing Battery Short Circuit Preventing Flammable Gas Short circuits will generate high transient currents and release a great deal of energy, which may cause personal injury. If conditions permit, disconnect the batteries in use before performing any other operations. Preventing Battery Leakage Do not use unsealed lead-acid batteries. Place and secure lead-acid batteries horizontally to prevent device inflammation or corrosion due to flammable gas emitted from batteries. Lead-acid batteries in use emit flammable gas. Therefore, store the batteries in a place with good ventilation, and take measures against fire. High temperatures may result in battery distortion, damage, and electrolyte overflow. When the battery temperature is higher than 60 C, check the battery for electrolyte overflow. If the electrolyte overflows, absorb and counteract the electrolyte immediately. When moving or handling a battery whose electrolyte leaks, exercise caution because the leaking electrolyte may hurt human bodies. When you find electrolyte leaks, use sodium bicarbonate (NaHCO 3 ) or sodium carbonate (Na 2 CO 3 ) to counteract and absorb the leaking electrolyte. Preventing Battery Overdischarge After you connect batteries, ensure that the battery fuse is disconnected or the circuit breaker is OFF before powering on the power system. This prevents battery overdischarge, which damages batteries. 1.4 Cable Layout When cables are used in a high temperature environment, the insulation layer may age and be damaged. Ensure that a sufficient distance exists between the cables and the DC busbar, shunt, and fuse. 3

10 1 Safety Precautions Signal cables must be bound separately from strong-current cables and high-voltage cables. Cables prepared by the customer must have the fire resistance capability. Cables must not pass behind the air exhaust vents of rectifiers in the cabinet. 1.5 Mechanical Safety Hoisting Devices Using a Ladder Do not walk under cantilevers or raised objects. Only trained and qualified personnel are allowed to perform hoisting operations. Before hoisting objects, check that all hoisting tools are available and in good condition. Before hoisting objects, ensure that hoisting tools are firmly fixed onto a weight-bearing object or wall. Ensure that the angle formed by two cables is less than 90 degrees. Use only ladders that are in good condition. Find out and do not exceed the maximum weight capacity. The recommended angle for a ladder against another object is 75 degrees. Measure the gradient with a right angle or your arms, as shown in Figure 1-1. Ensure that the wider end of the frame is at the bottom, the base cannot slide, and that the ladder is securely positioned. Figure 1-1 Correct angle for ladders When climbing a ladder: Ensure that your body's center of gravity does not shift outside the legs of the ladder. 4

11 1 Safety Precautions To minimize the risk of falling, steady your balance on the ladder before performing any operation. Do not climb higher than the fourth rung from the top. To climb onto a roof, ensure that the ladder top is at least one meter higher than the roofline, as shown in Figure 1-2. Figure 1-2 One meter higher than the roofline Drilling Holes Moving Heavy Objects Do not drill holes into a cabinet without permission. Non-standard drilling may affect the electromagnetic shielding of the cabinet and damage interior cables. Metal shards generated during drilling may short-circuit circuit boards if they get into the cabinet. Before drilling holes into a cabinet, remove interior cables. Wear goggles and protective gloves when drilling holes. After drilling, clean up metal shards immediately. Be cautious to prevent injury when moving heavy objects. Wear protective gloves when moving heavy objects. 5

12 2 Overview 2 Overview 2.1 Introduction The TP48600B-N20B1 is an indoor telecom power system that converts AC power into stable DC power and supplies power to and backs up power for 48 V communications equipment with a maximum output current of 600 A. Figure 2-1 shows the exterior of the TP48600B-N20B1. 6

13 2 Overview Figure 2-1 Cabinet exterior 2.2 Features Wide range of AC input voltage from 85 V AC to 300 V AC Comprehensive battery management Comprehensive AC and DC surge protection design One fast Ethernet (FE) port and one RS485/RS232 port for network connections Huawei network management system (NMS) protocol and telecom protocol for communicating with HUAWEI Network Ecosystem (NetEco), M2000, and a third-party NMS; remote management and unattended operation A liquid crystal display (LCD) for display and buttons for user operations. A web user interface (WebUI) for user operations. Multiple display languages, such as English, Chinese, Spanish, Portuguese, Italian, French, and Russian Hot-swappable rectifiers and site monitoring unit (SMU) Rectifier power factor (PF) of 0.99 High-efficiency rectifier with a maximum efficiency of 96%, and standard-efficiency rectifier with a maximum efficiency of 94% 7

14 2 Overview 2.3 Working Principle Figure 2-2 shows the working principle of the power system. AC power enters rectifiers through the AC power distribution unit (PDU). Rectifiers convert the input AC power into 48 V DC power, and then the DC PDU supplies power to multiple routes of loads. If the AC power is normal, rectifiers power DC loads and charge batteries. If the AC power fails, rectifiers stop working and batteries start to power DC loads. After the AC power resumes, rectifiers power DC loads again and recharge batteries. The SMU monitors the operating status of each component in the power system in real time and performs appropriate intelligent control operations. If any abnormal cases occur, the SMU reports the alarm signals. Figure 2-2 Working principle of the power system 2.4 System Configurations Table 2-1 System configurations Item System Configurations PDU AC power distribution: AC input circuit breaker DC power distribution: battery low voltage disconnection (BLVD) circuit breaker, load low voltage disconnection (LLVD) circuit breaker and fuse, and battery fuse 8

15 2 Overview Item AC input system SMU User interface module (UIM) Rectifier Communications expansion module Battery AC SPD DC SPD Sensor System Configurations 220/380 V AC three-phase four-wire, compatible with 220 V AC three-phase three-wire SMU02B UIM02C A maximum of 12 R4850G2 or R4850N2 rectifiers A maximum of two NIM01Cs A maximum of three 150 Ah battery strings Nominal lightning strike discharge current: 20 ka (8/20 µs); maximum lightning strike discharge current: 40 ka (8/20 µs) Differential mode: 10 ka (8/20 μs); common mode: 20 ka (8/20 μs) One battery temperature sensor (mandatory) 9

16 3 Components 3 Components 3.1 Interior Figure 3-1 Cabinet interior 10

17 3 Components (1) Battery switch (2) Battery fuses (3) SMU (4) Space for the communications expansion module (5) Space for rectifiers (6) Space for batteries (7) RTN+ busbar (8) Load low voltage disconnection (LLVD) circuit breakers and fuses (10) AC SPD (11) AC input circuit breakers and terminals (9) Ground bar (12) Battery low voltage disconnection (BLVD) circuit breakers (13) User interface module (UIM) 3.2 PDU The TP48600B-N20B1 uses AC and DC PDUs. Table 3-1 lists PDU specifications. Table 3-1 TP48600B-N20B1 PDU specifications Item AC power distribution AC input circuit breaker AC input system Power Distribution Specifications One 3-pole 125 A circuit breaker 220/380 V AC three-phase four-wire, compatible with 220 V AC three-phase three-wire DC power distribution Load route BLVD: two 63 A circuit breakers, two 32 A circuit breakers, and two 10 A circuit breakers LLVD: two 63 A circuit breakers, six 32 A circuit breakers, and two 10 A circuit breakers LLVD: four 160 A fuses Battery route Four 250 A fuses 3.3 Rectifier Rectifiers convert AC input into stable DC output. 11

18 3 Components Figure 3-2 Rectifier (1) Power indicator (2) Alarm indicator (3) Fault indicator (4) Locking latch (5) Handle Table 3-2 Rectifier indicators Indicator Color Status Description Power indicator Green Steady on The rectifier has an AC power input. Off The rectifier has no AC power input. The rectifier is faulty. Blinking at 0.5 Hz Blinking at 4 Hz The rectifier is being queried. The rectifier is loading an application program. Alarm indicator Yellow Off No alarm is generated. Steady on The rectifier generates an alarm for power limiting due to ambient overtemperature. The rectifier generates an alarm for shutdown due to ambient overtemperature or undertemperature. The rectifier protects against AC input overvoltage or undervoltage. The rectifier is hibernating. Blinking at 0.5 Hz The communication between the rectifier and the SMU is interrupted. Fault indicator Red Off The rectifier is running properly. Steady on The rectifier locks out due to output overvoltage. The rectifier has no output due to an internal fault. 12

19 3 Components 3.4 SMU02B Appearance Figure 3-3 shows an SMU02B. Figure 3-3 SMU02B appearance Panel Figure 3-4 shows an SMU02B panel. Figure 3-4 SMU02B panel (1) Run indicator (2) Minor alarm indicator (3) Major alarm indicator (4) Buttons (5) USB port (reserved, the port is protected by a security mechanism.) (6) RS485/RS232 port (7) Handle (8) Locking latch (9) FE port (10) Liquid crystal display (LCD) 13

20 3 Components Indicators Table 3-3 describes the indicators on the SMU02B panel. Table 3-3 SMU02B indicator description Name Color Status Description Run indicator Green Off The SMU is faulty or has no DC input. Blinking at 0.5 Hz Blinking at 4 Hz The SMU is running properly and communicating with the host properly. The SMU is running properly but is not communicating with the host properly. Minor alarm indicator Yellow Off The SMU does not generate any minor alarms. Steady on The SMU generates a minor alarm. Major alarm indicator Red Off No critical or major alarm is generated. Steady on A critical or major alarm is generated. Buttons Table 3-4 describes the buttons on the SMU02B panel. Table 3-4 SMU02B button description Button Name Description Up Down Turns to the previous menu or sets parameter values. When setting parameter values, you can hold down quickly adjust values. Turns to the next menu or sets parameter values. When setting parameter values, you can hold down quickly adjust values. to to Back Returns to the previous menu without saving the settings. Confirm Enters the main menu from the standby screen. Enters a submenu from the main menu. Saves the menu settings. Communication Ports Table 3-5 describes the communication ports on the SMU02B panel. 14

21 3 Components Table 3-5 SMU02B communication port description Communication Port Communications Parameter Communications Protocol Function FE port 10/100 M auto-adaptation HTTPS, NetEco network management system (NMS), and SNMP protocols Connects to an upper-level NMS. RS485/RS232 port Baud rate: 9600 bit/s, bit/s NetEco NMS protocol, YDN protocol Connects to an upper-level device such as BBU. NOTE All the ports mentioned are protected by a security mechanism. Figure 3-5 Pins in the FE port and RS485/RS232 port Table 3-6 Pin definitions for the FE port Pin Signal Description 1 TX+ Sends data over FE. 2 TX- 3 RX+ Receives data over FE. 6 RX- 4, 5, 7, and 8 None N/A. Table 3-7 Pin definitions for the RS485/RS232 port Pin Signal Description 1 TX+ Sends data over RS TX- 4 RX+ Receives data over RS

22 3 Components Pin Signal Description 5 RX- 3 RX232 Receives data over RS TX232 Sends data over RS PGND Connects to the ground. 8 None N/A. 3.5 UIM02C Panel The user interface module (UIM02C) supports eight dry contact outputs, nine dry contact inputs (including six universal dry contact inputs, one smoke sensor input, one water sensor input, and one door status sensor input), and four analog parameter inputs (including one ambient temperature and humidity input, two ambient temperature inputs, and one battery temperature input). Figure 3-6 shows a UIM02C panel. Figure 3-6 UIM02C panel Ports Table 3-8 UIM02C ports Port Type Silk Screen Description Sensor ports TEM-HUM Ambient temperature and humidity sensor WATER Water sensor TEMP1 Ambient temperature sensor 1 TEMP2 Ambient temperature sensor 2 GATE SMOKE BTEMP Door status sensor Smoke sensor Battery temperature sensor 16

23 3 Components Port Type Silk Screen Description Dry contact input ports Dry contact output ports DIN1 DIN2 DIN3 DIN4 DIN5 DIN6 ALM1 ALM2 ALM3 ALM4 ALM5 ALM6 ALM7 ALM8 NOTE For the associations between the dry contact input ports and alarms, see the appendix. NOTE For the associations between the dry contact output ports and alarms, see the appendix. Communications port COM RS485 port Communication Port Table 3-9 COM communication port description Communication Port Communications Parameter Communications Protocol Function COM port Baud rate: 9600 bit/s, bit/s M/S and Modbus protocol Connects to lower-level devices such as the battery voltage detector, DC Air Conditioner. NOTE The COM port supports the security mechanism. 17

24 3 Components Figure 3-7 Pins in the COM port Table 3-10 Pin definitions for the COM port Pin Signal Description 1 RX+ Receives data over RS RX- 4 TX+ Sends data over RS TX- 6 PGND Connects to the ground. 3, 7, 8 None N/A Pins Figure 3-8 shows the pin numbers of the sensor ports. Table 3-11 defines the pins. Figure 3-8 UIM02C pin numbers 18

25 3 Components Table 3-11 UIM02C pin definitions Silkscreen No. Pin Definitions TEM-HUM 1 12 V 2 ENV_TEMP 3 12 V 4 ENV_HUM WATER 1 12 V 2 WATER 3 GND 4 Not defined TEMP1 1 GND 2 TEMP1 TEMP2 1 GND 2 TEMP2 GATE 1 GATE+ 2 GATE- SMOKE 1 SMOKE 2 12 V BTEMP 1 GND 2 BTEMP 3.6 (Optional) Communications Expansion Module NIM01C Panel Figure 3-9 shows a NIM01C panel. 19

26 3 Components Figure 3-9 NIM01C Panel (1) 3G indicator (unavailable if the module does not provide 3G functions) (4) ANT communications port (unavailable if the module does not provide 3G functions) (2) Alarm indicator (5) COM1 port (7) COM3/CAN port (8) COM4 port (3) Run indicator (6) COM2 port (9) Handle Indicators Table 3-12 describes the indicators on the NIM01C panel. Table 3-12 Indicator description Indicator Color Status Description 3G indicator Green Steady on The dial-up connection is in the data service state. Blinking at a period of 2s (on for 0.1s and then off for 1.9s) Blinking at a period of 2s (on for 0.1s, off for 0.1s, on for 0.1s and then off for 1.7s) The network has been registered. A network is in search, or no network is connected. Alarm indicator Run indicator Red Off No alarm is generated. Steady on An alarm is generated. Green Off The NIM01C is not running because it is faulty or has no DC input. Blinking at 0.5 Hz Blinking at 4 Hz The NIM01C is running and communicating with the host properly. The NIM01C is running properly, but fails to communicate with the host. 20

27 3 Components Communications Ports The NIM01C provides four communications ports, which are described in Table Table 3-13 Communications port description Communications Port Communications Parameter Description COM1 port COM2 port Baud rate: 9600 bit/s, 19,200 bit/s, or 115,200 bit/s Baud rate: 9600 bit/s, 19,200 bit/s, or 115,200 bit/s Supports master/slave protocols and Modbus. Supplies 12 V power. Supports master/slave protocols and Modbus. Supplies 12 V power. COM3/CAN port Baud rate: 9600 bit/s COM3: Supports master/slave protocols and Modbus. CAN: Supports CAN protocol. COM4 port Baud rate: 9600 bit/s, 19,200 bit/s, or 115,200 bit/s Supports Modbus. Figure 3-10 Pins in the COM1, COM2, and COM3 ports Table 3-14 Description for the pins in the COM1 and COM2 ports Pin Signal Description 1 RS485+ RS485 data + 2 RS485 RS485 data V Supply power 4 RS485+ RS485 data + 5 RS485 RS485 data - 6 Left blank N/A 7 Left blank N/A 8 GND Grounded 21

28 3 Components Table 3-15 Description for the COM3/CAN port pins Pin Signal Description 1 RX+ Receives data over RS RX 3 Left blank N/A 4 TX+ Sends data over RS TX 6 GND Grounded 7 CANH CAN data + 8 CANL CAN data - Table 3-16 Description for the COM4 port pins Silk Screen Signal Description R+ RS485+ RS485 data + R RS485 RS485 data Battery Temperature Sensor Figure 3-11 Battery temperature sensor 22

29 4 Maintenance 4 Maintenance 4.1 Routine Maintenance Routine maintenance is required periodically based on the site requirements. The recommended maintenance interval is six months. If any fault is detected, rectify it in time. Table 4-1 Routine maintenance checklist Maintenance Task Maintenance Item Check Whether Check Method Repair When Measures Cabinet door lock The door lock is damaged. Observing and using the lock. The door lock is too damaged to use. Replace the door lock. Electrical specifications Preventive maintenance inspection (PMI) The output voltage is normal. The fault indicator is normal and the LCD displays an alarm. Using a multimeter. Observing the indicators and the LCD. The output voltage exceeds the threshold. An alarm is generated. For details, see Rectifying Common Faults. Appearance The paint or electroplated coating on the cabinet flakes off or has scratches. Observing the appearance. The surface is damaged or distorted. Repaint or repair the shell. Grounding The ground point properly connects to the ground bar in the equipment room. Observing the grounding and using a screwdriver or wrench. The cable connecting the ground point and the ground bar in the equipment room is damaged or loose. Secure or replace the cable. 23

30 4 Maintenance 4.2 Rectifying Common Faults AC Failure Possible Causes The AC input power cable is faulty. The AC input circuit breaker is OFF. The mains grid is faulty. Measures 1. Check whether the AC input cable is loose. If yes, secure the AC input cable. 2. Check whether the AC input circuit breaker is OFF. If yes, handle the back-end circuit failure and then switch on the circuit breaker. 3. Check whether the AC input voltage is lower than 50 V AC. If yes, handle the mains grid fault AC Over Volt Possible Causes The AC overvoltage alarm threshold is not set properly on the SMU. The power grid is faulty. Measures 1. Check whether the AC overvoltage alarm threshold is properly set. If no, adjust it to a proper value. 2. Check whether the AC input voltage exceeds the AC overvoltage alarm threshold (280 V AC by default). If yes, handle the AC input fault AC Under Volt Possible Causes The AC undervoltage alarm threshold is not set properly on the SMU. The power grid is faulty. Measures 1. Check whether the AC undervoltage alarm threshold is properly set. If no, adjust it to a proper value. 2. Check whether the AC input voltage is below the AC undervoltage alarm threshold (180 V AC by default). If yes, handle the AC input fault Phase A/B/C Failure Possible Causes The AC input power cable is faulty. 24

31 4 Maintenance The rectifier is in poor contact. The monitoring unit is faulty. Measures 1. Check whether the AC input power cable is correctly and securely installed. If no, reinstall the cable. If the insulation layer deteriorates, replace the cable. 2. Check whether a short circuit occurs in the AC input power cable or the insulation layer is damaged. If yes, replace the cable. 3. If the AC input is normal and the Alarm indicators on certain rectifiers are steady yellow, reinstall the rectifiers. 4. If the alarm persists, replace the monitoring unit DC Over Volt Possible Causes The DC overvoltage alarm threshold is not set properly on the SMU. The power system voltage is set too high in manual mode. Rectifiers are faulty. Measures 1. Check whether the DC overvoltage alarm threshold (58 V DC by default) is properly set. If no, adjust it to a proper value. 2. Check whether the system voltage is set too high in manual mode. If yes, confirm the reason and adjust the voltage to normal after the operation. 3. Remove the rectifiers one by one and check whether the alarm is cleared. If the alarm still exists, reinstall the rectifier. If the alarm is cleared, replace the rectifier DC Under Volt Possible Causes An AC power failure occurs. The DC undervoltage alarm threshold is not set properly on the SMU. The system configuration is not proper. The power system voltage is set too low in manual mode. Rectifiers are faulty. Measures 1. Check whether an AC power failure occurs. If yes, resume the AC power supply. 2. Check whether the DC undervoltage alarm threshold (45 V DC by default) is properly set. If no, adjust it to a proper value. 3. Check whether the load current is greater than the current power system capacity. If yes, expand the power system capacity or reduce the load power. 4. Check whether the system voltage is set too low in manual mode. If yes, confirm the reason and adjust the voltage to a proper value after the operation. 25

32 4 Maintenance 5. Check whether the power system capacity is insufficient for the loads due to rectifier failures. If yes, replace the faulty rectifier Batt Chg. Overcur. Possible Causes The rectifier communication is interrupted. Poor contact of the SMU. The SMU is faulty. Measures 1. Check whether an alarm is generated for rectifier communication interruption. If yes, remove the rectifier and reinstall it to check whether the alarm is cleared. If the alarm still exists, replace the rectifier. 2. Remove the SMU and reinstall it to check whether the alarm is cleared. If the alarm still exists, replace the SMU LLVD Disconnected Possible Causes An AC power failure occurs. Loads are manually disconnected. The load disconnection voltage is set too high on the SMU. Rectifiers are faulty. The system configuration is not proper. Measures 1. Check whether an AC power failure occurs. If yes, resume the AC power supply. 2. Check whether loads are manually disconnected. If yes, confirm the reason of the manual disconnection, and reconnect the loads after the operation. 3. Check whether the load disconnection voltage (44 V DC by default) is set too high on the SMU. If yes, adjust it to a proper value. 4. Check whether the power system capacity is insufficient for the loads due to rectifier failures. If yes, replace the faulty rectifier. 5. Check whether the load current is greater than the current power system capacity. If yes, expand the power system capacity or reduce the load power BLVD Disconnected Possible Causes An AC power failure occurs. Batteries are manually disconnected. The battery disconnection voltage is set too high on the SMU. Rectifiers are faulty. The system configuration is not proper. 26

33 Measures 1. Check whether an AC power failure occurs. If yes, resume the AC power supply. 4 Maintenance 2. Check whether batteries are manually disconnected. If yes, confirm the reason of the manual disconnection, and reconnect the batteries after the operation. 3. Check whether the battery disconnection voltage (43.2 V DC by default) is set too high on the SMU. If yes, adjust it to a proper value. 4. Check whether the power system capacity is insufficient for the loads due to rectifier failures. If yes, replace the faulty rectifier. 5. Check whether the load current is greater than the current power system capacity. If yes, expand the power system capacity or reduce the load power Battery Fuse Break Possible Causes The battery fuse detection cable is disconnected. The battery circuit breaker trips or battery fuse is blown. Measures 1. Check whether the battery fuse detection cable is disconnected. If it is disconnected, reconnect it. 2. Check whether the battery circuit breaker is disconnected or the battery fuse is blown. If the battery breaker is disconnected or the battery fuse is blown, rectify the battery loop fault and then switch on the circuit breaker or replace the fuse High Amb. Temp. This alarm is generated only for the power system that has ambient temperature sensors installed. Possible Causes The ambient overtemperature alarm threshold is not set properly on the SMU. The indoor temperature control system is faulty. The ambient temperature sensor is faulty. Measures 1. Check whether the ambient temperature alarm threshold (55 C by default) is properly set on the SMU. If no, adjust it based on site requirements. 2. Check whether the indoor temperature control system is faulty. If yes, rectify the fault. The alarm is cleared when the cabinet temperature falls within the allowed range. 3. Check whether the ambient temperature sensor is faulty. If yes, replace the temperature sensor Low Amb. Temp. This alarm is generated only for the power system that has ambient temperature sensors installed. 27

34 4 Maintenance Possible Causes The ambient undertemperature alarm threshold is not set properly on the SMU. The indoor temperature control system is faulty. The ambient temperature sensor is faulty. Measures 1. Check whether the ambient undertemperature alarm threshold (-20 C by default) is properly set on the SMU. If no, adjust it based on site requirements. 2. Check whether the indoor temperature control system is faulty. If yes, rectify the fault. The alarm is cleared when the cabinet temperature falls within the allowed range. 3. Check whether the ambient temperature sensor is faulty. If yes, replace the ambient temperature sensor High Amb. Humi This alarm is generated only for the power system that has humidity sensors installed. Possible Causes The ambient overhumidity alarm threshold is not set properly on the SMU. The humidity is too high in the cabinet where the humidity sensor is located. The humidity sensor is faulty. Measures 1. Check whether the ambient overhumidity alarm threshold (95%RH by default) is properly set on the SMU. If no, adjust it based on site requirements. 2. Check whether the humidity is too high in the cabinet. If yes, wipe the water with dry cotton or other tools and rectify the fault. 3. Check whether the humidity sensor is faulty. If yes, replace the humidity sensor Low Amb. Humi. This alarm is generated only for the power system that has humidity sensors installed. Possible Causes The ambient underhumidity alarm threshold is not properly set on the SMU. The humidity is too low in the cabinet where the humidity sensor is located. The humidity sensor is faulty. Measures 1. Check whether the ambient underhumidity alarm threshold (5% RH by default) is properly set on the SMU. If no, adjust it based on site requirements. 2. Check whether the cabinet humidity is too low. If yes, adjust the cabinet humidity. The alarm is cleared when the humidity falls within the allowed range. 3. Check whether the humidity sensor is faulty. If yes, replace the humidity sensor. 28

35 4 Maintenance Batt. High Temp. This alarm is generated only for the power system that has battery temperature sensor installed. Possible Causes The battery overtemperature alarm threshold is not set properly on the SMU. The ambient temperature of batteries is too high. The battery temperature sensor is faulty. Measures 1. Check whether the battery overtemperature alarm threshold (50 C by default) is properly set. If no, adjust it to a proper value. 2. Check whether the indoor temperature control system is faulty. If yes, rectify the fault. The alarm is cleared when the battery temperature falls within the allowed range. 3. Check whether the battery temperature sensor is faulty. If yes, replace the temperature sensor Batt. Low Temp. This alarm is generated only for the power system that has battery temperature sensor installed. Possible Causes The battery undertemperature alarm threshold is not set properly on the SMU. The ambient temperature of batteries is too low. The battery temperature sensor is faulty. Measures 1. Check whether the battery undertemperature alarm threshold (-10 C by default) is properly set. If no, adjust it to a proper value. 2. Check whether the indoor temperature control system is faulty. If yes, rectify the fault. The alarm is cleared when the battery temperature falls within the allowed range. 3. Check whether the battery temperature sensor is faulty. If yes, replace the temperature sensor Rectifier Missing Possible Causes Certain rectifiers are not powered on. The rectifier is faulty. The subrack or slot connector is faulty. The monitoring unit is faulty. 29

36 Measures 4 Maintenance 1. Check whether the rectifier circuit breakers corresponding to undetected rectifiers are ON. If no, switch them on. 2. Check whether the rectifier is removed. If yes, find the cause and reinstall it. 3. Replace the rectifier if it is faulty. 4. Check whether certain rectifiers in the rectifier subrack do not work properly. If yes, remove the rectifiers that do not work and check whether their slot connectors are damaged or deformed. If yes, repair or replace the subrack or slot connectors. 5. If the alarm persists after the preceding measures are taken and the monitoring unit is restarted, replace the monitoring unit Rect Fault Possible Causes The rectifier is in poor contact. The rectifier is faulty. Measures 1. Check the Fault indicator on the rectifier panel. If it is steady red, remove the rectifier, and then reinstall it after the indicator turns off. 2. If the alarm still exists, replace the rectifier Rect Protection Possible Causes The rectifier input voltage is too high. The rectifier input voltage is too low. The ambient temperature is too high. The rectifier is abnormal. Measures 1. Check whether the AC input voltage exceeds the upper threshold of the rectifier working voltage. If yes, rectify the power supply fault and then resume the power supply. 2. Check whether the AC input voltage is below the lower threshold of the rectifier working voltage. If yes, rectify the power supply fault and then resume the power supply. 3. Check whether the ambient temperature is higher than the normal operating temperature of the rectifier. If yes, check and rectify the temperature unit fault. 4. Remove the rectifier that generates the alarm and reinstall it after the indicator turns off. If the alarm still exists, replace the rectifier Rect Comm Fault Possible Causes The rectifier is removed. The rectifier is in poor contact. 30

37 4 Maintenance The rectifier is faulty. Measures 1. Check whether the rectifier is removed. If yes, reinstall it. 2. If the rectifier is in position, remove the rectifier and reinstall it. 3. If the alarm still exists, replace the rectifier Load Fuse Break Possible Causes The load circuit breaker trips or fuse is blown. The load circuit breaker or fuse detection cable is disconnected. Measures 1. Check whether the load circuit breaker trips or fuse is blown. If yes, rectify the back-end circuit fault and then switch on the circuit breaker or replace the fuse. 2. Check whether the load circuit breaker or fuse detection cable is disconnected. If yes, reconnect the cable AC SPD Alarm Possible Causes The AC SPD is faulty. The AC SPD detection cable is disconnected. Measures 1. Check whether the AC SPD indication window turns red. If yes, replace the SPD. 2. Check whether the AC SPD detection cable is disconnected. If yes, reconnect the cable DC SPD Alarm Possible Causes The DC SPD detection cable is disconnected. The DC SPD is faulty. Measures 1. Check whether the DC SPD detection cable is disconnected. If yes, reconnect the cable. 2. Check whether the DC SPD detection cable is disconnected. If no, replace the DC SPD. 31

38 4 Maintenance 4.3 Identifying Component Faults Identifying AC SPD Faults Check the color of the AC SPD indication window. Green indicates that the AC SPD is normal. Red indicates the AC SPD is faulty Identifying Circuit Breaker Faults The following lists main circuit breaker faults: The circuit breaker cannot be switched to ON/OFF after the short circuit fault for its end circuit is rectified. When the circuit breaker is switched to ON and its input voltage is normal, the voltage between the two ends of the circuit breaker exceeds 1 V. The input voltage is normal, but the resistance between both ends of the circuit breaker is less than 1 kω when the circuit breaker is OFF Identifying Rectifier Faults If any of the following occurs, the rectifier is faulty: The AC input and slot connector are normal, but the Fault indicator (red) is steady on or all indicators are off. The slot connector and SMU are normal, but the Alarm indicator (yellow) still blinks after the rectifier is reseated. The AC input and SMU are normal, but the SMU cannot control the rectifier Identifying SMU Faults The following are the main symptoms of SMU faults: The DC output is normal while the green indicator on the SMU is off. The SMU breaks down or cannot be started. Its LCD has abnormal display or buttons cannot be operated. With the alarm reporting enabled, the SMU does not report alarms when the power system is faulty. The SMU reports an alarm while the power system does not experience the fault. The SMU fails to communicate with the connected lower-level devices while the communications cables are correctly connected. Communication between the SMU and all rectifiers fails while both the rectifiers and the communications cables are normal. The SMU cannot monitor AC or DC power distribution when communications cables are intact and AC and DC power distribution is normal. Parameters cannot be set or running information cannot be viewed on the SMU. 4.4 Parts Replacement 32

39 4 Maintenance Ensure that loads are powered on during replacement. For example, keep the circuit breakers for primary loads ON, and do not disconnect both the battery input and AC input from the loads. Seek the customer's prior consent if load disconnection is required. Rectifiers and the SMU are hot-swappable Replacing a Rectifier Prerequisites Prepare an ESD wrist strap, a pair of protective gloves, an ESD box or bag, and the cabinet door key. Check that the new rectifier is intact. Ensure that the AC input to the power system is normal and batteries are in float charging mode. Procedure Step 1 Put on protective gloves. Step 2 Push the locking latch on the right of the rectifier panel upwards. To avoid burns, exercise caution when removing a rectifier because it is hot during operation. Step 3 Gently draw the handle outwards, and then remove the rectifier from the slot, as shown in Figure 4-1. Figure 4-1 Removing the rectifier Step 4 Push the locking latch on the new rectifier upwards, and pull out the handle. Step 5 Place the new rectifier in the appropriate slot. Step 6 Slide the new rectifier gently along the guide rail, and push the locking latch downwards, as shown in Figure

40 4 Maintenance Figure 4-2 Installing a new rectifier Step 7 Take off protective gloves. ----End Follow-up Procedure Replacing an SMU Pack the removed component, and return it to Huawei local warehouse. Prerequisites You have obtained the cabinet door key. The new SMU is intact. Procedure Step 1 Push the locking latch towards the left. Step 2 Pull the handle outwards to remove the SMU, as shown in Figure 4-3. Figure 4-3 Removing an SMU Step 3 Insert a new SMU into the subrack, push the locking latch towards the left, and pull out the handle. Step 4 Slide the new SMU into the subrack slowly along the guide rail, pull in the handle, and then push the locking latch towards the right. Step 5 Reset parameters on the SMU. 34

41 4 Maintenance Figure 4-4 Installing an SMU ----End Follow-up Procedure Pack the removed component, and return it to Huawei local warehouse Replacing an AC SPD Module Prerequisites You have obtained an ESD wrist strap or a pair of ESD gloves, an ESD box or bag, and the cabinet door key. The new AC SPD module is intact and the indication window is green. Do not replace an AC SPD module during a thunderstorm. Procedure Step 1 Connect the ground cable to the ESD wrist strap and wear the ESD wrist strap and ESD gloves. Step 2 Hold down the faulty AC SPD module and pull it out, as shown in Figure 4-5. Step 3 Install a new AC SPD module, as shown in Figure

42 4 Maintenance Figure 4-5 Replacing an AC SPD module Step 4 Disconnect the ground cable from the ESD wrist strap and take off the ESD wrist strap and ESD gloves. ----End Follow-up Procedure Check that the alarm for the AC SPD is cleared Replacing a Circuit Breaker Prerequisites Procedure Before replacing an AC circuit breaker, switch off the upstream input circuit breaker. You have obtained the cabinet door key, insulation tape, and tool kit. The new circuit breaker is intact and has the same specifications as the old one. Step 1 Switch off the circuit breaker that is to be replaced. Step 2 Record the positions where the output cable and signal cable terminals connect to the circuit breaker. Step 3 Loosen the screw that secures the upper port of the circuit breaker by using a Phillips screwdriver, and remove the output power cable and signal cable terminals. Wrap the cable and terminals by using the insulation tape to prevent hazards. 36

43 4 Maintenance Step 4 Loosen the screw that secures the lower port of the circuit breaker by using a Phillips screwdriver, and loosen the buckle at the circuit breaker base by using an insulated flat-head screwdriver. Step 5 Remove the circuit breaker from the guide rail. Figure 4-6 shows how to remove the circuit breaker. Figure 4-6 Removing a circuit breaker Step 6 Switch off the new circuit breaker. Press the buckle at the circuit breaker base by using an insulated flat-head screwdriver and install the new circuit breaker. Then loosen the buckle and secure the circuit breaker to the guide rail. Step 7 Tighten the screw that secures the lower port of the circuit breaker. Step 8 Remove the insulation tape from the output power cable and signal cable terminals. Then connect the output power cable and signal cable terminals to the upper port of the circuit breaker and tighten the screw. Step 9 Switch on the circuit breaker. Figure 4-7 shows how to install the new circuit breaker. Figure 4-7 Installing a circuit breaker ----End 37

44 4 Maintenance Replacing the PCB of UIM02C Prerequisites You have obtained an ESD wrist strap, a pair of ESD gloves, an ESD box or bag, the cabinet door key, and tools. The new printed circuit board (PCB) of UIM02C is intact. Procedure Step 1 Connect the ground cable to the ESD wrist strap, and wear the ESD wrist strap and ESD gloves. Step 2 Record the positions on the UIM02C panel for connecting signal cables and disconnect the cables. Step 3 Unscrew the UIM02C panel and remove the UIM02C, as shown in Figure 4-8. Figure 4-8 Taking out the UIM02C Step 4 Record the positions where the PCB connects to all the cables, and then disconnect the cables. Step 5 Remove the PCB. 38

45 4 Maintenance Figure 4-9 Removing the PCB of UIM02C Step 6 Take out the new PCB and install it. Step 7 Connect all cables back to the new PCB based on the record made previously. Step 8 Push in the UIM02C and tighten the screws. Step 9 Reconnect signal cables to the UIM02C panel based on the records made previously. Step 10 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap or ESD gloves. ----End Follow-up Procedure Pack the removed component, and return it to Huawei local warehouse Replacing a Battery Temperature Sensor Prerequisites You have obtained an ESD wrist strap, a pair of ESD gloves, an ESD box or bag, the cabinet door key, and a tool kit. The new battery temperature sensor is intact. Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Step 2 Remove the battery temperature sensor cable from the UIM, as shown in Figure

46 4 Maintenance Figure 4-10 Removing a battery temperature sensor cable Step 3 Cut off the cable tie of the battery temperature sensor and remove the sensor. Figure 4-11 Position of a battery temperature sensor Step 4 Properly place the new battery temperature sensor and bind it securely with a cable tie. Step 5 Reconnect the battery temperature sensor cable to the UIM. Step 6 Disconnect the ground cable from the ESD wrist strap, and take off the ESD wrist strap and ESD gloves. ----End 40

47 A Technical Specifications A Technical Specifications A.1 Environment Specifications Table A-1 Environment specifications Item Operating temperature Transport temperature Storage temperature Operating humidity Storage humidity Altitude Noise level Specifications 10ºC to +45ºC (with built-in batteries); 10ºC to +50ºC (without built-in batteries) 40ºC to +70ºC 40ºC to +70ºC 5% 95% RH (non-condensing) 5% 95% RH (non-condensing) m When the altitude ranges from 2000 m to 4000 m, the operating temperature decreases by 1ºC for each additional 200 m. Complies with YD/T Acoustic pressure level < 60 dba A.2 Electrical Specifications Table A-2 Electrical specifications Item Specifications AC input Input system 220/380 V AC three-phase four-wire, compatible with 220 V AC three-phase three-wire Input voltage Input frequency V AC Frequency range: Hz; nominal 41

48 A Technical Specifications Item Specifications Power factor Total harmonic distortion (THD) frequency: 50 Hz or 60 Hz 0.99 (rated input and full load) 10% (50% 100% load) DC output Output voltage range 42 V DC to 58 V DC AC input protection Default output voltage Output power Regulated voltage precision Ripple and noise Psophometrically weighted noise Current imbalance AC input overvoltage protection threshold AC input overvoltage recovery threshold AC input undervoltage protection threshold AC input undervoltage recovery threshold 53.5 V DC Maximum output power = Output power of a single rectifier x Number of rectifiers ±1% 200 mvp-p 2 mv ±5% (20% 100% load) > 300 V AC When the voltage is restored to 290 V AC, the output resumes. < 85 V AC When the voltage is restored to 90 V AC, the output resumes. DC output protection AC surge protection DC surge protection DC output overvoltage protection threshold 58.5 V DC to 60.5 V DC 1. If overvoltage occurs inside a rectifier, the rectifier locks out. 2. If the external voltage is greater than 63 V for more than 500 ms, the rectifier locks out. Nominal lightning strike discharge current: ±20 ka (8/20 µs); maximum lightning strike discharge current: ±40 ka (8/20 µs) Differential mode: 10 ka (8/20 μs); common mode: 20 ka (8/20 μs) Safety compliance Complies with IEC Mean time between failures (MTBF) 200,000 hours 42

ETP4830-A1 V300R001. User Manual. Issue 09. Date HUAWEI TECHNOLOGIES CO., LTD.

ETP4830-A1 V300R001. User Manual. Issue 09. Date HUAWEI TECHNOLOGIES CO., LTD. V300R001 Issue 09 Date 2016-01-28 HUAWEI TECHNOLOGIES CO., LTD. 2016. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent

More information

LORAIN CIP 4890/48120 DC Power System

LORAIN CIP 4890/48120 DC Power System DC Power for Business-Critical Continuity Key Features Compact flexibility provides rectifiers, distribution, and controller in one shelf Constant power delivers more current at lower voltages to meet

More information

LORAIN CSP DC Power System

LORAIN CSP DC Power System DC Power for Business-Critical Continuity Key Features Compact flexibility provides more space for revenue generating equipment Constant power delivers more current at lower voltages to meet load or recharge

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

APC BC300 Series 40kW 208/450/480V User Guide

APC BC300 Series 40kW 208/450/480V User Guide APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Installing the Cisco ONS FAP-4 Fuse Alarm Panel Installing the Cisco ONS 15454-FAP-4 Fuse Alarm Panel Product Number: 15454-FAP-4= This document explains how to install, test, operate, and maintain the Cisco ONS 15454-FAP-4 fuse alarm panel. This document

More information

PDU Power Distribution Unit for IP-NINJAR. User s Guide Ver

PDU Power Distribution Unit for IP-NINJAR. User s Guide Ver Power Distribution Unit for IP-NINJAR PDU-1209 User s Guide Ver. 1.0.0 Thank you for choosing this IDK product. To ensure the best performance of this product, please read this User s Guide fully and carefully

More information

Utopian Split A/C. Thank you for purchasing this quality Split A/C system!

Utopian Split A/C. Thank you for purchasing this quality Split A/C system! Utopian Split A/C Thank you for purchasing this quality Split A/C system! Please read through this manual completely, and keep it in case you need to reference the information in the future. Any operation

More information

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand 5U Compact System Installation Manual V1.0 Manufactured by Enatel Ltd. 321 Tuam Street PO Box 22-333 Christchurch New Zealand Phone +64-3-366-4550 Fax +64-3-366-0884 Email sales@enatel.net www.enatel.net

More information

Galaxy Pulsar Plus Controller Family Troubleshooting Table with SMNP Traps

Galaxy Pulsar Plus Controller Family Troubleshooting Table with SMNP Traps Critical Power Product Manual Galaxy Pulsar Plus Controller Family Troubleshooting Table with SMNP s This document supplements CC848815341 Galaxy Pulsar Plus Controller Family Product Manual r07. Service

More information

NetSure 2100 A31-S1 Subrack Power System User Manual

NetSure 2100 A31-S1 Subrack Power System User Manual NetSure 100 A31-S1 Subrack Power System User Manual Version V1.1 Revision date December 31, 017 BOM 31013614 Vertiv provides customers with technical support. Users may contact the nearest Vertiv local

More information

Installation and Operation Manual Low Power (LP) DC Power System

Installation and Operation Manual Low Power (LP) DC Power System Installation and Operation Manual Low Power (LP) DC Power System LPS Power Enclosure LPB Battery Enclosure 2051259 R3 Information in this document is subject to change without notice and does not represent

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

ACQUITY UPLC HT Column Heater Instructions

ACQUITY UPLC HT Column Heater Instructions ACQUITY UPLC HT Column Heater Instructions Note: This document is an addendum to Revision C of the ACQUITY UPLC System Operator s Guide. Contents: Topic Page Overview 1 Connecting the cable 4 Installing

More information

1U ULTRA Compact System

1U ULTRA Compact System en atel Supervisory Module SM32 Load 60 00 A IE C60947-2 G B140 4 8.2 CHNT NB1-63 C32 23 0/40 0 V e NaT el OK enatel RM 1848 enatel RM 1848 Battery 60 00A IE C60947-2 G B1 4 04 8.2 CHNT NB 1-63 C32 23

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

General safety precautions English

General safety precautions English English A min (m 2 ) 550 530 540 510 520 490 500 470 480 450 460 430 440 410 420 390 400 370 380 350 360 330 340 310 320 290 300 270 280 250 260 230 240 210 220 190 200 170 180 150 160 130 140 110 120

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The nvent RAYCHEM NGC-40 is a multipoint

More information

User's Manual. Model VJQ8 Pulse to Analog Converter. (Multi-function) MODEL AND SUFFIX CODES CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT

User's Manual. Model VJQ8 Pulse to Analog Converter. (Multi-function) MODEL AND SUFFIX CODES CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT User's Manual Model VJQ8 Pulse to Analog Converter (Multi-function) (Isolated Single-output and Isolated Dualoutput Types) Thank you for purchasing the JUXTA Signal Conditioner. Please read through this

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic

More information

P4200PM / P5000PM Remote Air Dryer User s Guide

P4200PM / P5000PM Remote Air Dryer User s Guide P4200PM / P5000PM Remote Air Dryer User s Guide 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P4200PM / P5000PM Air Dryer! We here at PUREGAS are very proud of our products

More information

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE - SOLARE TERMICO Installation and operating instructions Temperature difference controller 6 inputs, 3 outputs, integrated data logger for

More information

OPERATING MANUAL. AIR CONDITIONER Duct Type. Indoor Unit ARTG36LH ARTG45LH ARTG54LH ARTG60LH PART NO KEEP THIS MANUAL FOR FUTURE REFERENCE

OPERATING MANUAL. AIR CONDITIONER Duct Type. Indoor Unit ARTG36LH ARTG45LH ARTG54LH ARTG60LH PART NO KEEP THIS MANUAL FOR FUTURE REFERENCE OPERATING MANUAL AIR CONDITIONER Duct Type Indoor Unit ARTG36LH ARTG45LH ARTG54LH ARTG60LH KEEP THIS MANUAL FOR FUTURE REFERENCE PART NO. 9374379583 CONTENTS SAFETY PRECAUTIONS... 2 FEATURES AND FUNCTIONS...

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1- DPR-45 User Manual V-2.0 (2..206) DPR-45 TEMPERATURE PROTECTION RELAY PT00 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT 9-50VDC SUPPLY DESCRIPTION DPR-45 is a precision unit designed for the temperature

More information

Installation and Operation Instructions ELECTRIC FIREPLACE X56WMEF1BLK X56WMEF1WHT

Installation and Operation Instructions ELECTRIC FIREPLACE X56WMEF1BLK X56WMEF1WHT Installation and Operation Instructions ELECTRIC FIREPLACE X56WMEF1BLK X56WMEF1WHT Tool list Assembly Instructions Important Safety Instructions Listing Approvals Glass Particles Installation Instructions

More information

Ultraviolet Systems UV-C 50 INSTALLATION INSTRUCTIONS & PRODUCT MANUAL

Ultraviolet Systems UV-C 50 INSTALLATION INSTRUCTIONS & PRODUCT MANUAL Ultraviolet Systems Inc. UV-C 50 INSTALLATION INSTRUCTIONS & PRODUCT MANUAL TABLE OF CONTENTS SECTION 1 General Information 1A. Description...1 1B. Specifications...1 SECTION 2 Installation 2A. Pool Preparation...

More information

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death.

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death. Please Read: Safety Precautions DC AC In order to ensure that this product is used safely, be sure that you read and understand the following precautions fully and use the product only as directed. Be

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

FLOOR CONSOLE/ UNDER CEILING DUAL TYPE. ABT Series FUJITSU GENERAL LIMITED AIR CONDITIONER OPERATING MANUAL P/N

FLOOR CONSOLE/ UNDER CEILING DUAL TYPE. ABT Series FUJITSU GENERAL LIMITED AIR CONDITIONER OPERATING MANUAL P/N OPERATING MANUAL AIR CONDITIONER FLOOR CONSOLE/ UNDER CEILING DUAL TYPE ABT Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N9375756024 CONTENTS SAFETY PRECAUTIONS... 1 NAME OF PARTS...

More information

Operating instructions

Operating instructions ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 793-0 Fax +49 (0) 793-0 info@de.ebmpapst.com www.ebmpapst.com CONTENTS. SAFETY REGULATIONS AND NOTES. Levels of hazard warnings.

More information

RAYCHEM NGC-30 COMPONENTS

RAYCHEM NGC-30 COMPONENTS PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM PRODUCT OVERVIEW CABLE DUCT Card Rack Modules TERMINAL STRIP PLINTH MAIN SWITCH 800 mm USER INTERFACE

More information

Safety Please be mindful of the following for the installation, maintenance, wiring, and related inspections:

Safety Please be mindful of the following for the installation, maintenance, wiring, and related inspections: Operation Instructions for T300 Thank you for choosing the ViewX human-machine interface. For more efficient use of the ViewX human- machine interface, please read the included quick startup guide before

More information

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number Innovation In and Out of Parlour Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual Version - 1.0 Date - June 2016 Part Number - 39-0038 Index Manual Version... 3 About the Remote Vacuum

More information

Axiom Technologies L.L.C Telephone: Pennbright Dr., Suite 220 Fax: XP7 USER S MANUAL

Axiom Technologies L.L.C Telephone: Pennbright Dr., Suite 220 Fax: XP7 USER S MANUAL L.L.C Telephone: 281 931 0907 255 Pennbright Dr., Suite 220 Fax: 281 931 6562 Houston, Texas 77090 www.axiomsafety.com XP7 USER S MANUAL COMPACT MULTI-CHANNEL ALARM & SHUTDOWN SYSTEM GENERAL The XP7 alarm

More information

2-inch HDCVI Speed Dome Installation Manual

2-inch HDCVI Speed Dome Installation Manual 2-inch HDCVI Speed Dome Installation Manual Version 1.0.1 Table of Contents 1 INSTALLATION PREPARATION... 1 1.1 Basic Requirements... 1 1.2 Installation Check... 1 1.3 Cable Preparation... 1 1.3.1 Cable

More information

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM Card Rack Modules CABLE DUCT MAIN SWITCH 800 mm USER INTERFACE TERMINAL PRODUCT OVERVIEW The nvent

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

Installation and user manual for the BiWire / Conventional Repeater Panel

Installation and user manual for the BiWire / Conventional Repeater Panel Panel EFBWCV-REPEATER Contents Introduction.... 3 Purpose... 3 The Panel.... 3 Indication Equipment (IE).... 3 Power Supply Equipment (PSE).... 4 System Wiring.... 5 Status Indications.... 5 Repeater I/O....

More information

FTTHARCFUSIONSPLICER AD620

FTTHARCFUSIONSPLICER AD620 FTTHARCFUSIONSPLICER AD620 Read this instruction manual carefully before operating the equipment. Adhere to all safety instructions and warnings contained in this manual. Keep this manual in a safe place.

More information

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000 SERVICE INSTRUCTIONS FOR Fire Alarm System MINI-2000 Version 1.3 02.04.1998 Jari Ollila Tom Brunberg Oy Esmi Ab Copyright Oy ESMI Ab, 1991... 1998 The copyright to the documentation herein is the property

More information

TECH SHEET DO NOT DISCARD PAGE 1. If unsuccessful entry into diagnostic mode, actions can be taken for specific indications:

TECH SHEET DO NOT DISCARD PAGE 1. If unsuccessful entry into diagnostic mode, actions can be taken for specific indications: TECH SHEET DO NOT DISCARD PAGE 1 WARNING Electrical Shock Hazard Disconnect power before servicing. Replace all parts and panels before operating. Failure to do so can result in death or electrical shock.

More information

T3/E3 Fiber Optic Line Drivers

T3/E3 Fiber Optic Line Drivers MT618A-ST-R3 January 2004 MT619A-ST-R2 MT620AE-R2 T3/E3 Fiber Optic Line Drivers CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500) FREE technical

More information

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions Description The NGC-UIT-ORD is a panel mounted display used in conjunction with other approved Raychem control and

More information

Portable Air Conditioner User Manual

Portable Air Conditioner User Manual Portable Air Conditioner User Manual Email: usinfo@jmatek.com Web: www.jmatek.com Model / Modèle / Modelo: MN09 Series / Série / Serie: MN09CES, MN09CESBB, MN09CESWW, MN09CHES, MN09CHESBB, MN09CHESWW MN10

More information

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX 2218 F/2TDH4P

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX 2218 F/2TDH4P Operating manual 2218 F/2TDH4P 1 SAFETY REGULATIONS AND INFORMATION Read the operating manual carefully before commencing work at the product. Pay attention to the following warnings to avoid risk to persons

More information

Intelligent Speed Dome Installation Manual. Version 1.0.0

Intelligent Speed Dome Installation Manual. Version 1.0.0 Intelligent Speed Dome Installation Manual Version 1.0.0 Table of Contents 1 INTELLIGENT SPEED DOME INSTALLATION... 1 1.1 Installation Environments... 1 1.2 Check installation space and installation location

More information

AIR CONDITIONER OPERATING MANUAL. Duct type. Indoor Unit ARTG45LDTA ARTG54LDTA ARTG60LDTA KEEP THIS MANUAL FOR FUTURE REFERENCE. PART No.

AIR CONDITIONER OPERATING MANUAL. Duct type. Indoor Unit ARTG45LDTA ARTG54LDTA ARTG60LDTA KEEP THIS MANUAL FOR FUTURE REFERENCE. PART No. AIR CONDITIONER OPERATING MANUAL Duct type Indoor Unit ARTG45LDTA ARTG54LDTA ARTG60LDTA KEEP THIS MANUAL FOR FUTURE REFERENCE PART No. 98067 98067_OM_EN.indd 07-Aug-5 :40:5 OPERATING MANUAL PART No. 98067

More information

Service Manual & Installation Manual

Service Manual & Installation Manual GE Consumer & Industrial Appliances Service Manual & Installation Manual Split System Air Conditioner Model numbers: GE AIR F24 GE AIR F34 GE AIR F41 1 2 3 Introduction and Features Model Remarks GE AIR

More information

OPERATING MANUAL AIR CONDITIONER CASSETTE TYPE. AUT Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N

OPERATING MANUAL AIR CONDITIONER CASSETTE TYPE. AUT Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N OPERATING MANUAL AIR CONDITIONER CASSETTE TYPE AUT Series KEEP THIS MANUAL FOR FUTURE REFERENCE FUJITSU GENERAL LIMITED P/N9378015029 CONTENTS SAFETY PRECAUTIONS... 1 NAME OF PARTS... 2 OPERATION... 2

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

SITESTAR CABINET DESCRIPTION

SITESTAR CABINET DESCRIPTION SITESTAR CABINET DESCRIPTION Product No: D000100/1 Revision: 03 SiteTel Sweden AB Haukadalsgatan 8A, SE-164 40 Kista, Sweden www.northbattery.com Contents 1 INTRODUCTION... 4 1.1 TARGET GROUP...5 1.2 DOCUMENTS...5

More information

Beacon 410A Gas Monitor Operator s Manual

Beacon 410A Gas Monitor Operator s Manual Beacon 410A Gas Monitor Operator s Manual Part Number: 71-0397 Revision: F Released: 12/5/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be

More information

IR Intelligent Speed Dome Installation Manual

IR Intelligent Speed Dome Installation Manual IR Intelligent Speed Dome Installation Manual Version 1.0.0 Table of Contents 1 INSTALLATION PREPARATION... 1 1.1 Basic Requirement... 1 1.2 Installation Check... 1 1.3 Cable Preparation... 1 1.3.1 The

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

SM Field Installed Electric Heat Kit

SM Field Installed Electric Heat Kit SM Field Installed Electric Heat Kit HK050 HK100 HK150 HK200 Installation Manual 8733822029 (2018/07) US 2 SM Series Electric Heat Installation Manual Data subject to change 07.2018 8733822029 Installation

More information

OWNER S MANUAL. FLAT PANEL FIREPLACE HEATER Model Number: Serena (EF202A) WARNING CAUTION

OWNER S MANUAL. FLAT PANEL FIREPLACE HEATER Model Number: Serena (EF202A) WARNING CAUTION FLAT PANEL FIREPLACE HEATER Model Number: Serena (EF202A) OWNER S MANUAL WARNING Read and understand this entire owner s manual, including all safety information, before plugging in or using this product.

More information

C-Bus Four Channel General Input Unit Installation Instructions

C-Bus Four Channel General Input Unit Installation Instructions C-Bus Four Channel General Input Unit Installation Instructions 5504GI Series REGISTERED DESIGN REGISTERED PATENT Table of Contents Section...Page 1.0 Product Range... 3 2.0 Description... 3 3.0 Capabilities...

More information

Dahua 2-inch HDCVI Speed Dome Installation Manual Version Dahua Technology CO., LTD

Dahua 2-inch HDCVI Speed Dome Installation Manual Version Dahua Technology CO., LTD Dahua 2-inch HDCVI Speed Dome Installation Manual Version 1.0.0 Dahua Technology CO., LTD Table of Contents 1 HDCVI SPEED DOME INSTALLATION... 1 1.1 Installation Environments... 1 1.2 Check installation

More information

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX. RG CPAP 24 V mit Powermodul 24V sensorless

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX. RG CPAP 24 V mit Powermodul 24V sensorless Operating manual RG CPAP 24 V mit Powermodul 24V sensorless 1 SAFETY REGULATIONS AND INFORMATION Read the operating manual carefully before commencing work at the product. Pay attention to the following

More information

INSTRUCTIONS Français 2 Nederlands 15 English 28 Italien

INSTRUCTIONS Français 2 Nederlands 15 English 28 Italien INSTRUCTIONS Français 2 Nederlands 15 English 28 Italien 41 INSTRUCTION BOOK Thank you for purchasing our product. Please read this owner s manual carefully before using the unit. It is important that

More information

P4200W2 Series Air Dryer

P4200W2 Series Air Dryer P4200W2 Series Air Dryer User s Guide Models covered: P4200W2 P4200W2LP P4202W2 P4202W2LP P4202W2H 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P4200W2 Series Air Dryer!

More information

Refrigerated Incubator Model and Operating Instructions

Refrigerated Incubator Model and Operating Instructions Refrigerated Incubator Model 165000 and 165000-2 Operating Instructions N2400379 - Rev. 1 08May2018 1 Contents 1. SAFETY...3 1.1. EMF INTERFERENCE...4 1. PRODUCT INFORMATION...5 1.1 INTRODUCTION...5 2.

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

HP Power Distribution Unit with Power Monitoring (Models S124 and S132) User Guide

HP Power Distribution Unit with Power Monitoring (Models S124 and S132) User Guide HP Power Distribution Unit with Power Monitoring (Models S124 and S132) User Guide March 2006 (First Edition) Part Number 413611-001 Copyright 2006 Hewlett-Packard Development Company, L.P. The information

More information

Intelligent Swing Gate Turnstile Operating Manual CPW-322CS

Intelligent Swing Gate Turnstile Operating Manual CPW-322CS Intelligent Swing Gate Turnstile Operating Manual CPW-322CS C O N T E N T S 1. General Descriptions...1 2. Definitions... 1 2.1 Swing Gate Turnstile... 1 2.2 Passing Modes... 2 3. Safety Precautions...3

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,

More information

TECH SHEET - DO NOT DISCARD PAGE

TECH SHEET - DO NOT DISCARD PAGE TECH SHEET - DO NOT DISCARD PAGE 1 3. If this test mode has been entered successfully, all indicators on the console are illuminated for 5 seconds with 8:88 showing in the Estimated Time Remaining three-digit

More information

General safety precautions English

General safety precautions English English 1 1 1.1 About the documentation The original documentation is written in English. All other languages are translations. The precautions described in this document cover very important topics, follow

More information

P550W Series Air Dryers

P550W Series Air Dryers P550W Series Air Dryers User s Guide Models covered: P550W P550WH P550WLP P552W P552WH P552WLP 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P550W Series Air Dryer! We

More information

NetSure -48 VDC Power System

NetSure -48 VDC Power System Specification Number: 582136600 Model Number: 211NGFB This page is intentionally blank. Table of Contents Admonishments Used In This Document... ii Important Safety Instructions... iii General Safety...iii

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,

More information

Installation & Operating Guide

Installation & Operating Guide 5-036 HOT WATER TANK Installation & Operating Guide Read all instructions thoroughly. Keep this guide for future reference. Proof of purchase is required for Warranty. Staple receipt or proof of purchase

More information

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use! Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 74363 Güglingen Telefon +49 7135-102-0 Service +49 7135-102-211 Telefax +49 7135-102-147 info@afriso.de

More information

Installation Guide. For Models: E-MLV36BNK4LK1 E-MLV36ESP4LK1 E-MLV36WW4LK1 READ THESE INSTRUCTIONS AND AND SAVE THEM FOR FUTURE USE

Installation Guide. For Models: E-MLV36BNK4LK1 E-MLV36ESP4LK1 E-MLV36WW4LK1 READ THESE INSTRUCTIONS AND AND SAVE THEM FOR FUTURE USE READ THESE INSTRUCTIONS AND AND SAVE THEM FOR FUTURE USE Federal regulations require ceiling fans with light kits manufactured or imported after January 1, 2009, to limit total wattage consumed by the

More information

IntelliDoX Operator Manual

IntelliDoX Operator Manual IntelliDoX Operator Manual OPERATOR MANUAL TABLE OF CONTENTS Table of Contents Table of Contents...1 About this Publication...3 Important Safety Information: Read First...4 Getting Started...5 About the

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

DRYTEK 1 - User Manual ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL

DRYTEK 1 - User Manual ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL DRYTEK 1 - User Manual ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL CONTENTS 1. INTRODUCTION... 5 2. WARNINGS... 6 3. GENERAL DESCRIPTION... 7 4. INSTALLATION... 8 5. CONTROL PANEL... 9 5.1

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

PowerLogic Branch Circuit Power Meter (BCPM)

PowerLogic Branch Circuit Power Meter (BCPM) PowerLogic Branch Circuit Power Meter (BCPM) Panel Board Monitoring System Installation Guide Branch Circuit Power Meter (BCPM) HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and

More information

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Australia Issue 01 April 2012 Contents 1 Introduction 3 2 Safety 3 3 Installation 4 3.1 Mounting the Cabinet 4 4 Specifications

More information

Installation instructions. For the competent person. Installation instructions VRT 350 VRT 350 GB, IE

Installation instructions. For the competent person. Installation instructions VRT 350 VRT 350 GB, IE Installation instructions For the competent person Installation instructions VRT 350 VRT 350 GB, IE Legal information Document type: Product: VRT 350 Target group: Language: Installation instructions Authorised

More information

1X-F Series Installation Manual

1X-F Series Installation Manual 1X-F Series Installation Manual P/N 501-415003-1-31 REV 03.10 ISS 13NOV13 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact information 2013 UTC Fire

More information

General safety precautions English

General safety precautions English General safety precautions General safety precautions English 1 General safety precautions 1 General safety precautions Units are marked with the following symbol: 1.1 About the documentation The original

More information

CONTENTS SAFETY PRECAUTIONS. En-1 DANGER! CAUTION!

CONTENTS SAFETY PRECAUTIONS. En-1 DANGER! CAUTION! CONTENTS SAFETY PRECAUTIONS... 1 NAME OF PARTS... 2 PREPARATORY OPERATION... 3 OPERATION... 3 TIMER FUNCTIONS... 5 ON/OFF TIMER... 5 WEEKLY TIMER... 6 TEMPERATURE SET BACK TIMER... 8 FILTER DISPLAY RESET...

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 3323 - CENTRAL BATTERY EQUIPMENT [for Evanston campus only] PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

EST User Manual. (Please read this manual carefully before using)

EST User Manual. (Please read this manual carefully before using) EST-1000 Handheld Intelligent Toxic Gas Detector User Manual (Please read this manual carefully before using) ENVIRONMENTAL SENSOR TECHNOLOGY CO.INC. Contents I. Product Overview...1 II. Product Description...1

More information

Installation & Operating Guide

Installation & Operating Guide HOT WATER DISPENSER Installation & Operating Guide Read all instructions thoroughly. Keep this guide for future reference. Proof of purchase is required for Warranty. Staple receipt or proof of purchase

More information

Galaxy Pulsar Plus Digital Battery Plant Controller

Galaxy Pulsar Plus Digital Battery Plant Controller Galaxy Pulsar Plus Digital Battery Plant Controller Features Supports up to 60 Power Modules rectifiers and converters Supports dual voltage plants, with rectifiers and converters Auto-sensing dual voltage

More information

IR Intelligent Positioning System Installation Manual

IR Intelligent Positioning System Installation Manual IR Intelligent Positioning System Installation Manual Version 1.0.0 Table of Contents 1 INSTALLATION PREPARATION... 1 1.1 Basic Requirement... 1 1.2 Installation Check... 1 1.3 Cable Preparation... 1 1.3.1

More information

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT CONTENTS Installation Instructions for Heating & Air Conditioning 1F79 n-programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information

P6500W Air Dryer User s Guide

P6500W Air Dryer User s Guide P6500W Air Dryer User s Guide 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P6500W Air Dryer! We here at PUREGAS are very proud of our products and we are committed to

More information

Installation and operation manual

Installation and operation manual Installation and operation manual - + BRC1HHDAW BRC1HHDAS BRC1HHDAK English Table of contents Table of contents 1 General safety precautions 2 1.1 For the user... 2 1.2 For the installer... 2 2 About this

More information

General safety precautions English

General safety precautions English English 1 1 Units are marked with the following symbol: 1.1 About the documentation The original documentation is written in English. All other languages are translations. The precautions described in

More information

WINDOW TYPE COOLING MODEL AKT7F AKT9F REVERSE CYCLE MODEL AKT7U AKT9U FUJITSU GENERAL LIMITED

WINDOW TYPE COOLING MODEL AKT7F AKT9F REVERSE CYCLE MODEL AKT7U AKT9U FUJITSU GENERAL LIMITED OPERATING MANUAL OPERATING MANUAL BEDIENUNGSANLEITUNG MODE D EMPLOI MANUAL DE FUNCIONAMIENTO MANUALE DI ISTRUZIONI ΕΓΧΕΙΡΙ ΙΟ ΛΕΙΤΟΥΡΓΙΑΣ MANUAL DE INSTRUÇÕES ROOM AIR CONDITIONER WINDOW TYPE COOLING MODEL

More information

FOR SERVICE TECHNICIAN ONLY DO NOT REMOVE OR DESTROY WARNING

FOR SERVICE TECHNICIAN ONLY DO NOT REMOVE OR DESTROY WARNING WARNING Electrical Shock Hazard Disconnect power before servicing. Replace all parts and panels before operating. Failure to do so can result in injury or death. IMPORTANT Electric Discharge (ESD) Sensitive

More information

Installer manual AG-WL10

Installer manual AG-WL10 LEK LED CLEAN TIMER OPERATION Installer manual Indoor unit air/air heat pump IHB GB 1637-1 331827 Table of Contents 1 Important information Safety information Read before starting the installation Electrical

More information