General RATIONALE services. dedicated. utility. that do not. sized. The. over the selection of the. equipment. Voltage.
|
|
- Oscar Eaton
- 5 years ago
- Views:
Transcription
1 Section Section 10.9 General This section describes additional requirements for BSL33 and ABSL3 facilities. These additional requirements provide greater level of safety and reliability of operation. BSL3 Laboratory Power a) Electrical Servicee (1) Buildings other than NIH Bethesda campus shall have minimum two dedicated utility services, physicallyy separated in different duct banks and different manholes. Thesee dedicatedd services shall be fed by different primary substations or by one double endedd utility substation, which is fed by two dedicated utility service lines that do not servee any other facility. Each required electric service to the facility shall be sized to handle 100% of the design load (i.e. 2N redundancy). The customer rather than the utility company should own the onsite mediumm voltage distribution including Medium Voltage (MV) / Low Voltage (LV) transformers. When customer owned distribution system installation is not possible, coordinate with the local utility company to ensure that they provide electrical distribution system that meets the facility s requirements. (2) For non-nih Bethesda, Maryland campus BSL3/ABSL3 projects with low voltage double ended switchgear, an automatic main-tie-main breakerr configuration is acceptable. The switchgear shall be metal clad compartmentalized type with each breaker capable of being racked out and replaced with the switchgear energized. BSL3 & ABSL3 Biocontainment This is to increase reliability of electrical services. This provides the owner greater control over the selection of the equipment and aids maintenance of the equipment. Electrical demand of the facility may considerably exceed the utility s own engineering and construction standards. As a result, coordination with utility company is critical in providing reliable electrical service. This is to increase reliability of electrical services as tie breakerr closes to allow transfer of electric power to other available electrical service when one of the main circuit breakers opens. 1
2 (3) The preferred method of installation for the electric utility services is underground; overhead lines may be used only within the secure perimeter of the facility. (4) Locate distribution equipment, such as MV switches and transformers, in a secure location. (5) Reliability: The A/E shall evaluate and minimize single points of failure for all projects. (6) Downstream electrical distribution from switchgear to critical areas, such as mechanical support rooms with redundant motors in each set, shall comprise pairs of distribution switchboards/panelboards, each fed from a separate side of the switchgear, to supply approximately half of each set of motors. Where possible, provide separate feeders to packaged units with multiple motors, i.e. a separate feeder for each motor This is to protect electrical service feeders from vandalism and natural disasters such as high winds, thunderstorms and falling tree branches. This is to ensure electrical service equipment is protected from physical damage, vandalism or compromise. This is to preclude outage due to a single point of failure. This is to ensure that critical equipment remains operational when one of the service feeders fail. b) Standby Power Requirements (1) In addition to the loads listed in Section Emergency Power, connect the following loads to the standby electrical systems: i) Critical support fan coil units. ii) Receptacles serving selected equipment. iii) Environmental rooms. iv) General lighting. v) Laboratory air compressors. vi) Sterilizers. vii) Supplemental heating/cooling. viii) Water heaters. (2) As determined per program basis, recommend connecting the following loads to the standby electrical system: i) Freezers/Refrigerators/Environmental rooms, other than high value specimen units. ii) Distilled water systems. iii) General laboratory receptacles. iv) Heat-reclaim systems. v) Imaging equipment. vi) Task lighting. vii) Vacuum pumps. 2
3 (3) Consider providing 100% generator back-up for facilities where the loads mandated to be connected to a generator comprise the majority of load of the facility. (4) Provide a local generator dedicated to the facilityy to provide emergency/standby power; however, a remote generatorr farm (with redundant feeders) may also be acceptable. (5) Provide a load bank (including a connection point suitable for use for a portable generator) for all BSL3 facilities for periodic testing of generator. c) Uninterruptible Power Supply (UPS) (1) A central UPS system or a number of local UPSs may be required to back-up all building wide low voltage systems that are essential for containmen operation and for critical BSL3/ABSL3 specific loads. Perform an economic analysis to select the appropriate UPS system. (2) A central UPS shall be of the double-conversion on-line type; wet cell type batteries are recommended. (3) Recommend connecting the following systems to thee UPS: i) Building automation systems (BAS). ii) Select light fixtures in lieu of emergency battery packs. iii) Communications and PA systems. iv) Fire alarm systems. v) Lab equipment monitoring systems. vi) Mechanical controls. vii) Security, CCTV and access control systems BSL3 Laboratory Conductors, Cables, and Boxes a) Power Wiring Insulationn shall be compatible with sealing compound (sealing compound non- deleterious to insulation), using THW, THWN, THHN/THWN N, or XHHW. b) Other System Wiring Voice/Data, fire alarm, control, and security system wiring shall follow the same sealing requirements as that of the power wiring. Cable types shall be determinedd by NIH IT and manufacturer s recommendations for voice/data wiring and by respective system manufacturer for other systems. The A/E shall coordinate exact requirements for security wiring with Division of Physical Security Management (DPSM) Thiss is to protect insulationn of the electrical wiree from damage from sealing compound. Thiss is to protect the low voltage cable from damage from sealing compound. 3
4 c) Sealing Requirements (1) Provide silicon based caulk in all areas. See Chapter 4, Exhibit X4-2-A for additional information. Provide a 25 mmm (1 in.) barrier of silicone caulk around the wire within a devicee box hub. Provide a continuous bead of caulk between the device box and the adjacent surface. Provide a continuous bead of caulk around the device cover plate and the adjacent surface. d) Boxes for All Systems (1) Provide cast boxes with external mounting provisions, external hub, and gasketed devicee cover plates. Provide sealing as mentioned paragraph (c). (2) All boxes shall be double gang type; the box depth shall be at least the next size larger than the minimum size required per code. e) Conduits for Alll Systems Use RGS conduit with threaded fittings in all BSL3 areas. Provide seal-off fittings when conduits exit defined BSL3/ABSL3 perimeter. Use of surface metal raceway systems is NOT allowed in BSL3/ABSL3 areas BSL3 Area Lighting Requirements Thiss is to require use of approved sealing compounds, specify required sealing and provide a gas-tight electrical distribution system to facilitate decontamination, and prevent vermin harborage and transmission through the electrical raceway system. Thiss is to provide for a gas-tight electrical installation for decontamination, and to prevent vermin harborage and transmission through the electrical raceway system. Thiss is to provide added device box volume for wiring and required sealing within device boxes. Thiss is to provide a gas-tight electrical distribution system to facilitate decontamination, and prevent vermin harborage and transmission throughh the electrical raceway system. Surface metal raceway is not available with manufactured approved gasketing to eliminate vermin harborage and transmission. a) Lighting Control Laboratories shall utilize line voltage toggle switches. Occupancy sensors may be used in lab support and other areas. In addition, specialized lightingg controls (such as dimming systemss and DC lighting controls) shall be provided per specific program requirements. b) Containment The lighting systemss shall be designed to ensure that biohazards are contained within the BSL3 lab area. Lighting fixtures shall allow full decontamination with ease of effort, and permit easy re-lamping and access to ballasts. 4
5 c) BSL3 Laboratory Lighting Fixtures Lighting fixtures in BSL3 area shall comply with the following requirements: (1) Provide fixtures with stainless steel housings, glass or heavy duty acrylic prismatic lens and stainless steel door with tool-less fasteners. (2) Fixtures shall be UL listed for damp location and provided with a continuous bead of sealant around its perimeter to seal housing to ceiling. (3) Use surface mounted, fully sealed, enclosed and gasketed fluorescent fixture. Lighting fixtures may be pendant mounted only in an open ceiling. Pendant mounted lighting fixtures shall be fully sealed and gasketed with same features as those of surface mounted fixtures. (4) Install fixtures in continuous rows and aligned with edge of laboratory bench in laboratories and lab support areas. Install lighting fixtures in a symmetrical pattern. (5) Imaging Laboratory: Provide surface mounted lighting fixtures. In specific imaging modalities, such as MRI, fixtures shall be made of non-ferrous materials; use DC rated incandescent lamps and use dimming controls. All special requirements shall be coordinated with the manufacturer of each modality. d) Emergency Lighting (1) Connect 50% of light fixtures in the BSL3 laboratories to the emergency power source. (2) Provide at least one lighting fixture per room in BSL3 laboratory areas with selftesting emergency battery ballast. Connect the lighting fixtures with emergency ballasts to un-switched local emergency generator circuits This is to allow cleaning of lighting fixture and decontamination by gaseous means. This is required for strict moisture and vermin control required within the space. This is required for strict moisture and vermin control required within the space. This is to provide uniform level of lighting at work surfaces. This to specify unique requirements of the imaging laboratories. This allows for continuation of laboratory function in case of loss of normal power. This allows continuous illumination in case of loss of power and during transfer from once source to other. 5
6 NIH Desiggn Requireme ents Manual Section ABSL3 A An nimal Res search Fa acility a) Anima al Research h Facility Standby Pow wer Requirem ments (1) In ad ddition to th he equipmen nt required to be conn nected to th he standby power in B BSL laborratory, conne ect the follow wing equipm ment to the lo ocal generato or: 434 i) Aniimal Waterin ng Systems. 435 ii) An nimal Caging g and Ventila ation System ms. 436 (2) The following f loa ad is recom mmended to be conneccted to the local generrator per sp pecific 437 progrram requirem ments. 438 i) Cag ge Wash eq quipment al Research h Facility Lighting b) Anima 441 (1) Lightting Fixture es: Lighting fixtures for ABSL3 anim mal research h facilities sshall meet a all the 442 requirements of lighting fixtu ures of BSL L3 research h laboratorie es. In additio on, the follo owing 443 requirement appllies: 444 i) Sellf-testingGeneral em mergency batttery ballasts in make ABSL3sure a areas shall h have visual iindication on nly. Comment: Needsto electrical items related to controls/bas 445 reliability is covered either here or in another section. For example, monitoring 446 of UPS, standby power, and the avoidance of single point failure scenarios in 447 BAS; as well as appropriate alert (telemetry) to responsible party (responsible 448 with BSL-3), arrangement and confirmation of any hardwire interlocks etc Add: 451 -Testing Requirements (expectations that the A/E would mandate in their specs that may be unique to a BSL-3). For example: "Systems shall be verified for proper operation and integrated performance with 454other building utility systems in accordance with the design intent. Component installations shall be 455verified so as to maintain proper response in the event of malfunction and to preclude loss of 456containment. 457Add additional "General Requirements" to beginning of this section: 458-a) Penetrations through the containment barrier shall be gas tight, non-porous, smooth and cleanable; and readily 459visible for routine inspection, cleaning, and maintenance. Penetrating components shall be sufficiently rigid in 460 construction and adequately braced to structure to maintain the long term integrity of the penetration. The result 461 shall be free of sharp edges or similar hazards b) Penetrations into the containment barrier of BSL-3 (including mounting of electrical boxes) shall be detailed in 463 the construction documents, and shall require mock-ups to be constructed and tested prior to installation. 464 Penetration details for equipment shall be coordinated with the equipment manufacturers. Rationale: Provision of mockups allows for confirmation of acceptable construction, rigidity of mounting, and understanding of requirements prior to undergoing expensive construction. -c) All penetrations shall be durable, sealed, and tested to meet the room tightness criteria for BSL-3 laboratories. Add: -Electrical systems and equipment not serving BSL-3 shall not be located within containment areas. Add: -Where conduits or components must be surface mounted, consideration shall be applied to selection of support and mounting means so as to stand away from finished surfaces at least 25 mm (1 in.) to promote cleanability, decontamination, minimize concealed spaces, and so as not present sharp or protruding surfaces. 6
General RATIONALE services. dedicated. utility. that do not. sized. The. over the selection of the. equipment. Voltage.
Section 10 9 6 14 12 1 2 3 4 5 6 8 9 0 11 14 15 16 17 18 19 10 11 12 23 24 25 26 25 20 21 22 23 24 31 37 38 39 340 341 342 38 347 348 49 40 41 42 43 44 45 48 49 40 Section 10.9 General 10.9.0. This section
More informationElectrical Design Guidelines Table of Contents
C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6
More informationPage 1 of General
Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors
More informationNEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015
NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized
More informationELECTRICAL SYSTEMS ASSESSMENT Hanover High School
ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,
More informationElement D Services Electrical
PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as
More informationNATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY
A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -
More informationSECTION ELECTRICAL IDENTIFICATION
SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationTechnical Report 2: Electrical Systems Criteria and Existing Conditions
Technical Report 2: Electrical Systems Criteria and Existing Conditions Princeton Theological Seminary Library Princeton, NJ Stephanie Deckard Lighting Electrical Faculty Advisor Dr. Kevin Houser 10/12/2012
More informationSECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)
SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill
More informationSTATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES
STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES Articulation Agreement Identifier: ELT 118 (2005-1) Identifier is the postsecondary course prefix followed by Plan-of-Instruction
More informationChapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...
Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6
More information5.0 Installation Instructions
5.0 Installation Instructions 5.1 Location Within the laboratory, pharmacy, etc., the ideal location of the biological safety cabinet is away from personnel traffic lanes, air vents (in or out), doors
More informationSERIES & NO. SMI SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF SPECIAL ELECTRICAL SYSTEMS
1 of 4 SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF I. PURPOSE To provide basic guidelines for identifying electrical systems required for special installations. II. REFERENCES National Electric
More informationWINDSOR FOREST HIGH SCHOOL HVAC REPLACEMENT ADDENDUM #2 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM FEBRUARY 18, 2016
SECTION 26 2030 - LIGHTING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Special Conditions and Division 1 Specification Sections,
More informationChapter 1 General... 5
About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of
More informationDEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and
DEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and equipment), and discussions with maintenance personnel
More informationNATIONAL TRAINING BOARD (ELECTRICIAN) REGULATIONS 2008 BR 54/2008 NATIONAL OCCUPATIONAL CERTIFICATION ACT :38
BR 54/ NATIONAL OCCUPATIONAL CERTIFICATION ACT 2004 2004 :38 The National Training Board, with the approval of the Minister responsible for the National Training Board, in exercise of the powers conferred
More informationBrown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA
PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities
More informationTABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51
TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...
More informationSECTION EMERGENCY POWER SYSTEMS
SECTION 16620 EMERGENCY POWER SYSTEMS A. Standby Engine/Generator Systems 1. Installations of stationary engine/generator (e/g) systems shall be designed in strict accordance with ANSI/NFPA 70 - National
More informationElectrical Safety Requirements
Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system
More informationRelated Sections: TBD. Effective Date: January 1, 2016
Description: The purpose of the section is to highlight the current applicable UMCP Design Standards for the design, selection and, installation of lighting fixtures within buildings. Related Sections:
More informationM001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings
1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL
More informationELECTRICAL POWER SYSTEMS
Scope The various Codes applicable to the University's electrical power system are mainly based upon a model of a single utility service, connected to a single premise. The University s electrical system,
More informationFIRE ALARM: BY OTHERS, IF REQUIRED.
x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT
More information2009 ELECTRICAL CODE REQUIREMENTS
2009 ELECTRICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Inspection Request Line (231) 533-3510 Electrical requirements
More informationA. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
More informationSECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35
SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4
More informationUNC Chapel Hill Design Requirements for Level 3 Biological Safety Laboratories & Animals
UNC Chapel Hill Design Requirements for Level 3 Biological Safety Laboratories & nimals I General Criteria The purpose of this Guideline is to establish the criteria for Design and Construction of Level
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationFIRE ALARM: BY OTHERS, IF REQUIRED.
x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,
More informationChang Liu Lighting + Electrical M.A.E./B.A.E. Integrated Degree. Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson
M.A.E./B.A.E. Integrated Degree Technical Assignment 2 October 12, 2012 Faculty Consultants: Ron Dodson Renzo Museum of American Art Executive Summary This report provides an analysis of the electrical
More informationTABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19
TABLE OF CONTENTS About This Textbook...xiii How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...
More informationDESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES
2.07 ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.07 It is expected that the electrical design professional will conform to accepted good engineering design practices.
More informationMEDIUM, LOW AND CONTROL VOLTAGE CABLES
Related Sections U-M Design Guideline Sections: 260800 - Electrical Acceptance Tests Products Medium Voltage Primary Cables Primary power distribution cable shall be single conductor stranded copper, with
More informationSECTION (16140) - WIRING DEVICES
SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -
More informationAPPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL
This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with
More information.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.
Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code
More informationProduct Specifications Dialog Room Controller* (*patent pending)
1 Product Specifications Dialog Room Controller* (*patent pending) 1. GENERAL 1.1. OVERVIEW 1.1.1. Provide a complete stand-alone, decentralized, low voltage, digital lighting control system for classrooms,
More informationLindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2
Lindsay Frederick Lighting + Electrical Ron Dodson Faculty Advisor Native American Cultural Center Arizona Technical Report 2 Native American Cultural Center Technical Report 2 p. 2 Executive Summary The
More informationSUBJECT: Effective Date: Procedure Number:
SUBJECT: Effective Date: Procedure Number: Facilities Operations/ Utilities and Energy 9/1/2015 FS 2015 UES0002 Services Division of Responsibility Procedure APPLICABILITY/ACCOUNTABILITY: Supersedes: Page
More informationSECTION INTRUSION DETECTION SYSTEM
SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing
More informationConstruction Management at Risk Services. New North East Branch Library Project. August 3, 2018
Construction Management at Risk Services New North East Branch Library Project ADDENDUM 01 August 3, 2018 1. The attendance sheets (4 pages) from the Pre-Bid Conference are attached. 2. The proposals may
More informationUBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical
More informationSECTION ISOLATED POWER SYSTEMS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationA. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.
DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets
More informationINSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY
RV Products Division INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY DESIGNED AND MANUFACTURED BY THE MAKERS
More informationDIVISION 28 ELECTRONIC SAFETY AND SECURITY
DESIGN CONSIDERATIONS DIVISION 28 ELECTRONIC SAFETY AND SECURITY The Consultant shall provide a written description of how the entire system is designed to operate. This Basis of Design (BOD) narrative
More informationBuilding Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationBuilding Electrical System Overview
Philip Mackey L/E Dr. Mistrick Holy Cross Hospital North Addition Silver Spring, MD 0/3/05 Building Electrical System Overview Executive Summary: The following report describes the existing emergency power
More informationElectrical Program. Electrical Laws & Rules. Electrical RCW WAC B. Permits Inspections Access Description Directions Comments.
Electrical Laws & Rules Licensing Electrical Work Scope Administrator Duties Certification Supervision RCW 19.28 WAC 296-46B Permits Inspections Access Description Directions Comments Electrical Program
More informationThe following is a University standard specification and shall be reviewed and edited by the Design Professional to be project specific.
DIVISION 13 21 00 CONTROLLED ENVIRONMENT ROOMS The following is a University standard specification and shall be reviewed and edited by the Design Professional to be project specific. GENERAL REQUIREMENTS
More informationA. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR
September 2012, rev. 00 26 0553 Identification for Electrical Systems PART 1. GENERAL 1.01 Summary A. Section Includes: 1.02 Submittals 1. Identification for raceways. 2. Identification of power and control
More informationINSTALLATION INSTRUCTIONS - POWER SENTRY CONTROL POWER SENTRY CONTROL UNIT PSBCEB2 INSTALLATION INSTRUCTIONS
POWER SENTRY CONTROL UNIT PSBCEB2 INSTALLATION INSTRUCTIONS READ AND FOLLOW THESE INSTRUCTIONS BEFORE INSTALLATION TO ENSURE PROPER AND SAFE OPERATION SAVE THESE INSTRUCTIONS READ AND FOLLOW ALL SAFETY
More informationCITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST
CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST Plan Check No. Plan Check Expiration Date Job Address: Square Footage Use Zone Fire Zone Occ. Group Type of Construction No. of Stories Applicant Phone
More informationProject Description Clinical Research Building (CRB) Animal Area Renovation
Table of Contents INTRODUCTION... 3 PROJECT OVERVIEW... 4 CONSTRUCTION SYSTEMS AND ASSEMBLIES... 10 SPECIAL ISSUES AND CONSIDERATIONS... 19 PRODUCTS... 20 Issued: June 22, 2012 1 OF 24 Issued: June 22,
More informationDivision 26 ELECTRICAL TABLE OF CONTENTS
Division 26 ELECTRICAL TABLE OF CONTENTS 26 1000 GENERAL... 33 A. CODE... 3 B. RELATED SECTIONS... 3 C. ABBREVIATIONS... 3 D. DEFINITIONS... 3 E. DRAWING REQUIREMENTS... 3 F. EQUIPMENT SERVICE ACCESS AND
More informationReplacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus
ADDENDUM FORM INVITATION TO TENDER: 2016-067 ADDENDUM NO: 1 DATE ISSUED: June 23, 2016 ISSUED BY: Monty Thibeault DESCRIPTION: Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus
More information3. Provide revised typed circuit directory in panelboards that have circuits removed.
DIVISION 26 - ELECTRICAL 26 0501 MINOR ELECTRICAL DEMOLITION A. Coordinate utility service outages with the UND Electrical Department. B. Verify the abandoned wiring and equipment serve only abandoned
More informationMichigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1
Page 1 TABLE OF CONTENTS 1 ELECTRICAL 2 Summary Sustainability Electrical Distribution Lighting Detection and Alarm Communication Systems Lightning Protection Clock Systems Access Control Housekeeping
More informationTOM BURNS, PLANNING DIRECTOR
~~ 0 173 COUNTY OF SANTA CRUZ August 4,2005 PLANNING DEPARTMENT 701 OCEAN STREET, qth FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 TOM BURNS, PLANNING DIRECTOR Agenda:
More information2011 and 2014 National Electrical Code Changes Residential Only
2011 and 2014 National Electrical Code Changes Residential Only Sponsored By: and.net Instructor: Fritz Gunther, Chief Electrical Inspector 585-436-4460 www.nyeia.com NEW YORK ELECTRICAL INSPECTION AGENCY
More informationESTIMATE SET-UP PACKAGE BID SCHEDULE ENTRY AND MAINTENANCE
BIDDING INFORMATION BID DATE: PROJECT NAME: ADDRESS: ESTIMATE SET-UP PACKAGE BID SCHEDULE ENTRY AND MAINTENANCE ESTIMATE NO.: CITY: STATE: ZIP: PRIME: PROJECT MANAGER: PROJECT TYPE: SUB: $ SIZE: BID TIME:
More informationApplications. Standard Materials
Mercmaster III Low Profile Compact Fluorescent Luminaires Compact Fluorescent listed for simultaneous exposure to combustible dusts and flammable gases or vapors. Applications Enclosed and gasketed fixtures
More informationSECTION INTERIOR LIGHTING
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationAssessing Your Airfield Electrical Distribution System
Assessing Your Airfield Electrical Distribution System PRESENTED AT The 2017 Airports Conference March 30, 2017 Hershey, PA PRESENTED BY Samuel Mullen, III - Burns Engineering, Inc. 1 Presentation Objective
More informationElectrical Inspection Lighting & Power
0921 Light Fixtures & Controls Fixtures, controls, conduit, wiring, etc. Interior classroom and corridor lighting consists of T12 fluorescent lamps with magnetic ballasts. In the classrooms the luminaires
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Flow Lighting QuickLED NEW FIXTURE 2x4 2x2 1x4 Corporate 1240 Texan Trail, Suite 102 Grapevine, TX 76051 (817)435-8484 Office www.flowledlighting.com READ AND FOLLOW ALL SAFETY
More informationExplosion Proof Exit Sign - Class I, Division I - IP65-120V/277VAC - Emergency Battery Back-Up
Explosion Proof Exit Sign - Class I, Division I - IP65-120V/277VAC - Emergency Battery Back-Up Part #: EPL-EMG-EXT-3W Page: 1 Made in the USA The EPL-EMG-EXT-3W Explosion Proof LED Exit Sign with back
More informationSECTION INTERIOR LIGHTING
SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationFOUNTAINS UGA DESIGN & CONSTRUCTION SUPPLEMENTAL GENERAL REQUIREMENTS & STANDARDS APRIL 30,
13 12 00 FOUNTAINS A. Due to water conservation efforts and the high maintenance requirements of fountains, new interior and / or exterior fountains are not allowed. B. If a variance is granted for a fountain,
More informationAir Flow Diagram. Orange County Sanitation District SP-194 Section 05 Conceptual Design
Orange County Sanitation District SP-194 Section 05 Conceptual Design Air Flow Diagram Two options are being analyzed for air distribution and temperature control within the building: Conditioned air shall
More informationBdl60u Fluorescent Emergency Ballast
A Division Of Philips Electronics North America Corporation One- or two-lamp emergency; Universal input voltage: 120 through 277 V, 50 or 60 Hz; Replaces B60U Bdl60u Fluorescent Emergency Ballast Product
More informationDESIGN & CONSTRUCTION GUIDELINES
ADMINISTRATIVE SERVICES 4202 E. FOWLER AVENUE, FPC110 PHONE: (813) 974-2625 FACILITIES PLANNING & CONSTRUCTION TAMPA, FLORIDA 33620-7550 WEBSITE: USF.EDU/FPC DESIGN & CONSTRUCTION GUIDELINES DIVISION 21
More informationINSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY
RV Products Division INSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY DESIGNED AND MANUFACTURED BY THE MAKERS OF COLEMAN -MACH AIR CONDITIONERS TABLE OF CONTENTS
More informationMANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)
MANDATORY MEASURES INDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130.1) MANDATORY LIGHTING CONTROLS 1. Area Controls: Manual controls that control lighting in each area separately 2. Multi-level
More informationELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING
SEMINAR 301 Part 1: Changes in the 2005 NEC SEMINAR RULES: There are no Rules All Questions need to be asked Stop at any time for an explanation SEMINAR PARTS: ELECTRIC and NEON SIGN STANDARDS By Randy
More informationAdv. 8.4 Guidelines for Biosafety Cabinets Rev
UNIVERSITY OF CINCINNATI Environmental University Health Services 556-4968 Health and Safety ADVISORY NO. 8.4: GUIDELINES FOR THE SELECTION, INSTALLATION AND USE OF BIOSAFETY CABINETS (INCLUDING ISSUES
More informationMODULAR INTEGRATION OF PROCESS EQUIPMENT PACKAGES FOR OIL AND GAS FACILITIES
MODULAR INTEGRATION OF PROCESS EQUIPMENT PACKAGES FOR OIL AND GAS FACILITIES Copyright Material PCIC Europe Paper No. PCIC Europe LO-70 Allan Bozek EngWorks, Inc. 1620 49 th Avenue, SW Calgary, AB T2T
More informationKidde Nitrogen Inert Gas Clean Agent Fire Suppression System
1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering
More informationTABLE OF CONTENTS. Part I Administrative... 1
Part I Administrative............................ 1 CHAPTER 1 ADMINISTRATION............... 1 R101 Title, Scope and Purpose.................... 1 R102 Applicability.............................. 1 R103
More informationTHAILAND REGULATORY BODY LEGISLATIVE FRAMEWORK RATIONALE FOR REGULATION. Consumer Protection.
THAILAND I. RATIONALE FOR REGULATION COUNTRY RATIONALE FOR REGULATION Thailand Consumer Protection. II. REGULATION BODY COUNTRY Thailand REGULATORY BODY Thai Industrial tandards Institute (TII) under the
More informationIMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016
IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS June 17th, 2016 RE: City Council Adopts 2014 National Electrical Code with Pool Alarm Requirements On April 25th, 2016 the
More informationSECTION ELECTRICAL GENERAL PROVISIONS
PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling
More informationHoneywell Durafit LED Retrofit Kit
Honeywell Durafit LED Retrofit Kit INSTALLATION INSTRUCTIONS LED RETROFIT LUMINAIRE CONVERSION FOR USE ONLY WITH PRODUCTS DESCRIBED AND INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS PROVIDED WITH THIS
More informationPOINT ROLLOVER LIGHTS PRL LED HELIDECK SEMIFLUSH LIGHT
Compliances: ETL Listed to UL 98 & UL 98A Marine Vessels USA CSA C22.2 No..-4 Canada FAA AC /39-2B Heliport Design Guide ICAO Annex 14, Volume II UK CAA CAP 437, Chapter 4, paragraph 3.1 IMO 9 MODU Code
More informationIDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems
SECTION 26 05 54 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Permanent Marking. 6. Underground
More informationRecommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.
SMOKE GUARD SYSTEM MODEL 600 REV. 3 SPECIFICATION Smoke Guard, Inc 287 Maple Grove Boise, ID 83704 Toll Free: 800.574.0330 Fax: 208.639.7851 e-mail: info@smokeguard.com website: http://www.smokeguard.com/
More informationExecutive Summary. CNBC Global Headquarters Christine Cajilig
Executive Summary This report contains an analysis and description of the existing electrical distribution of the including the distribution type, emergency power, uninterruptible power system, over current
More informationSECTION GENERATOR PARALLELING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationSECTION LIGHTING
SECTION 26 50 00 LIGHTING PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and required to furnish and install
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards
Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44
More information80W C1D2 Hazardous Location Integrated LED - Corrosion Resistant for Marine - Emergency Backup
80W C1D2 Hazardous Location Integrated LED - Corrosion Resistant for Marine - Emergency Backup Part #: HALP-EMG-48-2L-ITG-LED-V2 Page: 1 Made in Texas The Larson Electronics HALP-EMG-48-2L-ITG-LED-V2 Hazardous
More informationDOMESTIC WATER PACKAGED BOOSTER PUMPS
DIVISION 22 PLUMBING 22 11 16 DOMESTIC WATER PIPING 22 11 19 DOMESTIC WATER PIPING SPECIALTIES 1. To facilitate landscape and other maintenance operations, exterior hose bibs shall be provided at 150 foot
More informationElement D Services Electrical ODG010107
Element D Services Electrical ODG010107 D5090 Other Electrical Systems Part 1. General This section includes design standards and requirements for other electrical systems. This is a design standard and
More informationSECTION LIGHTING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationA. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.
DIVISION 26 ELECTRICAL SECTION 26 51 13 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire
More information