Electrical Inspection Lighting & Power
|
|
- Mark Gregory
- 5 years ago
- Views:
Transcription
1 0921 Light Fixtures & Controls Fixtures, controls, conduit, wiring, etc. Interior classroom and corridor lighting consists of T12 fluorescent lamps with magnetic ballasts. In the classrooms the luminaires are suspended direct/indirect steel luminaires with prismatic acrylic diffusers and eight foot (8 ) HO lamps. Each individual luminaire consists of a single channel with a single lamp, supported two feet apart and hung approximately 7 6 above the floor. Most of the classrooms have some form of split switching with either two or three switches controlling the luminaires. There are three parallel runs of these in each classroom, 24 in overall length (40 in the kindergarten rooms). The library has two lamp wraparounds suspended in continuous rows while the corridor and toilet rooms have four lamp lensed troffers. The gymnasium is equipped with surface mounted louvered fluorescent luminaires, also with 8 T12 lamps. Emergency lighting was provided by a number of individual battery operated power stations located throughout the building and wired to specific luminaires. These are quite dated and do not appear to function at present. Wall bracket luminaires with emergency ballasts have been installed in the corridors to provide additional illumination and, more importantly, emergency egress lighting. These are a recent addition. The exit lights have been converted to luminous exit signs with 70 rated visibility. The condition of the lighting system, as with most of the other electrical systems, is dated but functional. All of the fluorescent lamps are T12 and all of the inspected ballasts are the electromagnetic type. These lamps and ballasts represent a former technology and have been superseded by T8 and T5 lamps with electronic ballasts. The classroom luminaires are unique and do a reasonable job of lighting the space. However, every room has at least one (very) noisy ballast and the energy costs are easily half again that current luminaire, lamp and ballast combinations. Again, the classroom fixtures are in pretty good physical shape, and possibly worth salvaging. The library, corridor, offices and toilets luminaires have broken and/or discolored lenses and poor technology electrical systems. Both the electromagnetic ballasts and especially the T12 lamps will become more difficult, and expensive, to replace in the future. T12 lamps are now only available for replacement use. Remaining life expectancy: Five to ten years. June 2005 Glacier Valley Elementary School Condition Survey Report Page 153 of 178
2 0921 1: Missing, Broken and Discolored Luminaire Diffusers Some of the library, toilet room and other luminaire diffusers and lenses are either missing, broken, discolored or both. Building wide. category: Renewal & Replacement RR. Provide new lenses or diffusers as necessary. Estimated Construction Cost: $25,800. June 2005 Glacier Valley Elementary School Condition Survey Report Page 154 of 178
3 0921 2: Lamps Out Some of the various luminaires throughout the building, especially in the gymnasium, have burned out or otherwise non functional lamps. Building wide. category: Renewal & Replacement RR. Provide new lamps or ballasts as necessary. Estimated Construction Cost: $18,200. June 2005 Glacier Valley Elementary School Condition Survey Report Page 155 of 178
4 0921 3: Under Illuminated Corridors Partly because of the surrounding wall and floor finishes and partly because of the electrical illumination, the corridors appear dimly lit and oppressive. Some of the luminaires have burned out or otherwise non functional lamps. category: Renewal & Replacement RR. Provide new luminaires, lamps and/or ballasts as necessary. Estimated Construction Cost: $69,800. June 2005 Glacier Valley Elementary School Condition Survey Report Page 156 of 178
5 0921 4: Light Switches on Hinge Side of Entry Door This is more of a convenience item as opposed to a code violation or operational deficiency. Some of the classrooms have the light switches on the hinge side of the entry door as opposed to the latch side. category: Functional F. Relocate the switches or rehang the door as necessary. Estimated Construction Cost: $6,100. June 2005 Glacier Valley Elementary School Condition Survey Report Page 157 of 178
6 0921 5: Emergency Lighting Systems Not Functional The various emergency lighting units throughout the building do not function. These should be removed, the wiring consolidated and the batteries properly disposed. Building wide. categories: Hazardous Material HM and Functional F. Remove emergency lighting systems, remedy wiring, dispose. Estimated Construction Cost: $15,200. June 2005 Glacier Valley Elementary School Condition Survey Report Page 158 of 178
7 0921 6: Upgrade or Replace Existing Luminaires The existing lighting systems are all older vintage T12 lamps with electromagnetic ballasts. These are both inefficient and generally noisy. A comprehensive replacement of all luminaires, lamps and ballasts will provide a quieter, energy saving environment with higher quality illumination for the occupants. category: Energy Conservation E. Provide a building wide replacement of all luminaires, including ballast and lamps. New equipment shall include electronic ballasts with T8 or T5 fluorescent lamps installed into energy efficient fixtures. Estimated Construction Cost: $185,000. June 2005 Glacier Valley Elementary School Condition Survey Report Page 159 of 178
8 0931 Devices & Connections Outlets, disconnects, equipment connections, wiring, etc. The branch circuit wiring appears to be mostly older type TW and THW with some THHN/THWN insulated copper conductors, nearly all in electrical metallic tubing (EMT). Some of the panelboards have correctly color coded circuit connections while most do not. A number of circuits have reduced neutrals. A few circuits are run in either MC cable or flexible metal conduit. All of the mechanical room motor connections are made with flexible metal conduit. Remaining life expectancy: 20 years. June 2005 Glacier Valley Elementary School Condition Survey Report Page 160 of 178
9 0931 1: Inaccessible Receptacle The terminus end of this cord is apparently attached to an inaccessible receptacle. category: Code (NEC) C, and Functional F. Extend electrical wiring to new wall and provide outlet. Estimated Construction Cost: $1,500. June 2005 Glacier Valley Elementary School Condition Survey Report Page 161 of 178
10 0931 2: Receptacles by Sinks are not Ground Fault Interrupter (GFI) Protected Existing receptacles adjacent to sinks are not GFI protected. category: Code (NEC) C. Replace the existing devices with GFI protected ones. Estimated Construction Cost: $16,000. June 2005 Glacier Valley Elementary School Condition Survey Report Page 162 of 178
11 0931 3: Broken Flexible Metal Conduit The flexible metal conduit is unraveling at the connector for this device. category: Code (NEC) C. Repair and/or replace this connection. Estimated Construction Cost: $1,000. June 2005 Glacier Valley Elementary School Condition Survey Report Page 163 of 178
12 0931 4: Accessible Power Receptacle and Wiring This power receptacle and its associated wiring are behind an unlocked panel cover providing access to the curious. This installation should be secured, particularly in an elementary school environment. category: Code (NEC) C. Provide a lockable cover to this device. Estimated Construction Cost: $1,000. June 2005 Glacier Valley Elementary School Condition Survey Report Page 164 of 178
13 0931 5: Overloaded Circuits In spite of the additional circuits and plugmold provided with Panels F and G, some of the existing rooms (specifically the kitchen, but also some of the offices and classrooms) still need more general use receptacles and circuits. category: Functional F. Provide additional receptacles and circuits in the kitchen, gymnasium, offices and classrooms to be fed from the new (replacement) panelboards. Estimated Construction Cost: $70,000. June 2005 Glacier Valley Elementary School Condition Survey Report Page 165 of 178
ELECTRICAL SYSTEMS ASSESSMENT Hanover High School
ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,
More informationElectrical Inspection Service & Distribution
0911 Distribution Panels & Switchgear Equipment, conduit, feeders, and grounding 480 Volt Switchboard: This switchboard contains the utility meter and two main, service, circuit breakers. One circuit breaker
More informationPLATTEVILLE MIDDLE SCHOOL
Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle
More informationHOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District
HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the
More informationAppendix B. Facilities Assessment Report
Mile Lane Army Reserve Center Redevelopment Plan September 2008 Appendix B Facilities Assessment Report RKG Associates, Inc. Mile Lane Army Reserve Base Middletown, CT MEP System Evaluation For RKG Associates
More informationIEC and NCCER Mapping for Year 1
Craft: 26102-14 Safety IEC and NCCER Mapping for Year 1 Perform a visual inspection on various types of ladders 102.4 STATE GENERAL SAFETY CONSIDERATIONS IN ELECTRICAL INSTALLATIONS (LADDER SAFETY, SLECTION
More informationFlorence High School / Middle School Page 1 of 3 Florence, WI
Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October
More informationCurrently, all electrical upgrades would be voluntary, but there are situations in which upgrades would be required.
Executive Summary The current electrical system is functional but requires some understanding in order to avoid overloading circuits. Certain outlets can be used for space heaters while others cannot and
More informationDISTRIBUTION PANEL BOARDS; NEW CONSTRUCTION. Subpart 1. Circuit index. All circuits in light and power
4658.4600 DISTRIBUTION PANEL BOARDS; NEW CONSTRUCTION. Subpart 1. Circuit index. All circuits in light and power panels must be identified with a typewritten index. Doors on electrical panel boards accessible
More informationNORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS. Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan
NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan PBA Project No. 2014.0137.00 Prepared By: Wayne Kerbelis Terry Cleis September
More informationRenovate MCRC Facilities Great Lakes, IL
6. ENGINEERING SYSTEMS REQUIREMENTS D50 ELECTRICAL SYSTEM DESCRIPTION The electrical repair work includes the design and construction of the electrical distribution system for the B3200 Marine Corps Reserve
More informationSiemens Building Technology MEP Existing Conditions
Electrical Existing Conditions Report Executive Summary: The electrical systems for the are generally of the original vintage. The site is primary metered with the meter located in the main Electric Room.
More informationInstallation Instructions
Installation Instructions Ordering Code: RF16UQT1XXC RF32UQT1XXC RF32UHT1XX RF45UQT1XXC RF45UHT1XX PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION OF THE FOLLOWING: 4 STRIP FIXTURES 8 STRIP FIXTURES
More informationM001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings
1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL
More informationMOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School
MOUNT PLEASANT MIDDLE SCHOOL HVAC M-01 Heating Plant: The existing boilers have recently been upgraded. (3) steam boilers (8660 mbh each) manufactured by Weil- McLain have been installed. Newer hot water
More informationELECTRIC SERVICE EVALUATIONS ELECTRICAL / BOILER REPLACEMENTS. Clarkstown Central School District. June Arch Proj. #
ELECTRICAL ELECTRIC SERVICE EVALUATIONS / BOILER REPLACEMENTS Clarkstown Central School District June 2015 CSArch Arch Proj. # 151-1501.00 151 Table of Contents SECTION 1 Executive Summary... 1 SECTION
More informationRelated Sections: TBD. Effective Date: January 1, 2016
Description: The purpose of the section is to highlight the current applicable UMCP Design Standards for the design, selection and, installation of lighting fixtures within buildings. Related Sections:
More informationCUSTOMIZED TEACHER ASSESSMENT BLUEPRINT ELECTRICAL POWER AND TRANSMISSION INSTALLERS. Test Code: 5922 Version: 01
CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT ELECTRICAL POWER AND TRANSMISSION INSTALLERS Test Code: 5922 Version: 01 Specific competencies and skills tested in this assessment: Basic Safety Identify career
More informationFIRE ALARM: BY OTHERS, IF REQUIRED.
x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT
More informationElectrical Design Guidelines Table of Contents
C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6
More information2015 Building Condition Survey Summary Mosaic Associates Architects 02/19/16
1. General: This summary is offered as a supplement to the 2015 Building Condition Survey being filed with SED on behalf of the District. All cost estimates are preliminary, and should be re-evaluated
More informationFIRE ALARM: BY OTHERS, IF REQUIRED.
x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,
More informationConnecting Lighting & Controls
Connecting Lighting & Controls The RELOC Advantage The RELOC Savings Pipe & wire and MC cable are antiquated and inefficient. Using such labor intensive methods results in longer projects, higher on-site
More informationWL24000 Series Reflectorized Troffer Luminaries
WL24000 Series Reflectorized Troffer Luminaries DESCRIPTION WL SERIES TROFFER LUMINARIES combines a highly reflective specular reflector and an electronic ballast. These premium quality energy saving fixtures
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as
More information1 x4 Dimmable LED RetroFits
1 x4 Dimmable LED RetroFits Installation Instructions Ordering Code: RF16UQT1XXCDL RF16UHT1XXDL RF32UQT1XXCDL RF32UHT1XXDL PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION OF THE FOLLOWING: 4 STRIP FIXTURES
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 131 - QUEENS, 170-45 84TH AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-18
More informationData Bulletin. Determining the Cause of AFCI Tripping Class 760
Data Bulletin 0760DB0204 06/2002 Cedar Rapids, IA, USA Determining the Cause of AFCI Tripping Class 760 Retain for future use. INTRODUCTION DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This document
More informationTHE COMPLETE GUIDE TO OUTDOOR WALL LIGHTS
THE COMPLETE GUIDE TO OUTDOOR WALL LIGHTS CONTENTS 1. INTRODUCTION 2. TYPES OF OUTDOOR WALL LIGHTS 3. LIGHT SOURCES IN OUTDOOR WALL LIGHTS 4. FACTORS IN SELECTING OUTDOOR WALL LIGHTS 5. SUMMARY lighting
More informationState College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT
State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Flow Lighting QuickLED NEW FIXTURE 2x4 2x2 1x4 Corporate 1240 Texan Trail, Suite 102 Grapevine, TX 76051 (817)435-8484 Office www.flowledlighting.com READ AND FOLLOW ALL SAFETY
More informationSECTION EXTERIOR LIGHTING
SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26
More informationElectricity Unit Notes. Agriculture Mechanics I
Electricity Unit Notes Agriculture Mechanics I Principles of Electricity Electricity is a form of energy that can produce light, heat, magnetism, chemical changes Resistance: tendency of a material to
More informationA. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.
DIVISION 26 ELECTRICAL SECTION 26 51 13 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire
More informationState College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT
State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the
More informationNEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015
NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized
More informationB. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.
PART 1 GENERAL 1.01 Lighting design: A. Reference UAF Facilities Services Guidelines for Average Illumination Levels. B. It is recognized that these standards are updated irregularly and lighting technology
More informationHMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3
HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California 95833 September 15, 2016 Woodland Joint Unified School District Spring Lake Area Elementary School HMC No. 3535003.000 DSA Appl.
More informationUBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical
More informationUltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW
12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes
More informationAshland School District Facility & Capacity Assessment Report 2005
Ashland School District Facility & Capacity Assessment Report 2005 Briscoe Elementary School (Closed Facility) Address: 265 N Main Street Area: 33,980 square feet Buildings: Original Building 1948 Music
More informationMARY CRAPO CENTER Miller Road, Swartz Creek, Michigan
MARY CRAPO CENTER 8197 Miller Road, Swartz Creek, Michigan MARY CRAPO CENTER 8197 Miller Road, Swartz Creek General Information: - Instructional, Child Care Development Center (West Wing) o (2) Infant/Toddler
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT HAN A HATS & CAPS LTD. ACCORD ID: 12339 DAG NO. CS &SA-115/117, RS-188/181, KHOTION NO. CS-128, SA-274, BAIPAIL, ASHULIA, SAVAR, DHAKA. OTHER FACTORIES: TEXTSTREAM FASHION
More informationAFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults?
RECEPTACLEFAQs AFCI 1 What is an arc fault? UL provides a definition for an arc fault in UL 1699 (Standard for Safety Arc Fault Circuit Interrupters). It is an unintentional arcing condition in a circuit.
More information2009 ELECTRICAL CODE REQUIREMENTS
2009 ELECTRICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Inspection Request Line (231) 533-3510 Electrical requirements
More informationSECTION INTERIOR LIGHTING
SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationBuilding Electrical System Overview
Philip Mackey L/E Dr. Mistrick Holy Cross Hospital North Addition Silver Spring, MD 0/3/05 Building Electrical System Overview Executive Summary: The following report describes the existing emergency power
More information13. ELECTRICAL - TECHNICAL
13. ELECTRICAL - TECHNICAL 13.1 GENERAL REQUIREMENTS 1. Base the electrical design on providing the following features at the most economical cost, considering both investment and operating expenditures:
More informationLord Stirling Community School Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004
Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004 Table of Content: Page 1 ~ Single Line Diagram 1 2 ~ Electrical System Narrative 2-3 3 ~ Lamp
More informationSCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003
SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved SCO # 1Punch listed items were noted below on
More informationI-320 SERIES AC EMERGENCY LIGHTING EQUIPMENT
P.O. BOX 84 TUCSON, AZ 85734 (520) 294-3292 FAX (520) 74-2837 www.iotaengineering.com INSTRUCTION MANUAL IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be
More informationMUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY
ARCHITECTURE ROLLING HILLS ELEMENTARY SCHOOL Rolling Hills Elementary was built in 1999 and is the newest addition to the Mukwonago Area School District. The building contains approximately 64,900 gross
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was
More informationInstallation Instructions
Installation Instructions Ordering Code: RF32UQT1XX PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION OF THE FOLLOWING: 4 STRIP FIXTURES 8 STRIP FIXTURES HARDWIRE 4 STRIP FIXTURES WRAP FIXTURES TROFFER
More informationAPPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL
This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with
More informationChapter 1 General... 5
About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of
More informationCONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA
American Electrical Institute 2014 PART 2 83 CONTINUING EDUCATION FOR OREGON ELECTRICIANS AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223 www.aeitraining.com 84 PART 3 American Electrical
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT N.A GARMENTS PLOT # 36, ROAD # 46, GULSHAN NORTH C/A, DHAKA OTHER FACTORIES: SIDKO LIMITED, SIDKO APPARELS LIMITED, DELTA TIES LIMITED April 17, 2014 Page 2 SUMMARY was surveyed
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 16 - BROOKLYN, 157 WILSON STREET, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-30
More informationMUKWONAGO SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY
MUKWONAGO SCHOOL DISTRICT ARCHITECTURE PARK VIEW MIDDLE SCHOOL The original school building was dedicated in 1954 as the High School, with an addition in 1959, a library addition in 1970, and an addition/renovation
More informationNYC Department of Education
Asset: LEARNING SUPPORT CENTER - K, 1665 ST. MARKS AVENUE, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-07 1:06 PM 2018-05-10 12:20 PM Asset Data Type of Service
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT AMITY DESIGNS LTD. HOUSE#7&9, ROAD#9 BLOCK D, SECTION #11MIRPUR DHAKA OTHER FACTORIES: NONE April 21, 2014 Page 2 SUMMARY was surveyed for fire safety on 4/21/2014 by Hughes
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT BEQ KNIT LTD. ZIRABO, ASHULIA, SAVAR, DHAKA Other Factories: Beq Sweaters Ltd., Tammam Design Ltd. April 22, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing
More informationFluorescence is the conversion of one frequency of electromagnetic radiation to another frequency by a material
Fluorescent Lighting Developed around turn of century Commercially available in 1938 by GE Presented at 1939 Worlds Fair Made efficient lighting possible during WWII in factories and warehouses Fluorescence
More informationDEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and
DEMOLITION GENERAL NOTES As-built conditions have been determined from Record Drawings (if they exist), field investigations (accessible areas and equipment), and discussions with maintenance personnel
More informationS AGE E NGINEERING A SSOCIATES, LLP
S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September
More informationEnvironmental Safety Risk Assessment Inpatient Behavioral Health Settings (Compiled from tools in the public domain)
Environmental Safety Risk Assessment Inpatient Behavioral Health Settings (Compiled from tools in the public domain) Location: Bedrooms Ceiling: non-accessible; solid gypsum board Flooring: wall to wall;
More informationMID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN
MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,
More informationE I Delmar Cobble MINOR ELECTRICAL DEMOLITION
PART1 GENERAL 1.01 SECTION INCLUDES A. Electrical demolition. 1.02 RELATED REQUIREMENTS SECTION 26 0501 MINOR ELECTRICAL DEMOLITION A. Section 01 7000- Execution and Closeout Requirements: Additional requirements
More informationNote: The office/work area is not in the scope of the PER. Existing Condition
ROBERT G. DASHIELL, JR., P.E., INC. Consulting Engineers 1225 West 26 th Street, Norfolk, Virginia 23508 (757) 623-5012 September 14, 2016 Draft Electrical Portion of the PER Petersburg Main Sanitary Sewage
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT YOUNG INTERNATIONAL PLOT NO. 32-36, SECTOR 5-CEPZ, CHITTAGONG OTHER FACTORIES: NONE July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by Hughes Associates,
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT TUBA GARMENTS LTD. PLOT # 1682, ANANDA NAGAR, MERUL BADDA, BADDA, DHAKA OTHER FACTORIES: NONE July 5, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/5/2014 by Hughes
More informationDIVISION 16 ELECTRICAL SYSTEMS
DESIGN AND CONSTRUCTION STANDARDS DIVISION 16 DIVISION 16 Division 16 of the Carnegie Mellon University Design and Construction Standards Manual addresses the following requirements for electrical systems
More informationCatalog Number. Notes
Catalog Number FEATURES & SPECIFICATIONS INTENDED USE Built on the compact, low-profile Z strip channel, this LED strip offers long maintenance-free life, several color s, lumen outputs and lengths. Ideal
More informationAppendix E: Photo Documentation
Appendix E: Photo Documentation Brown County Library Central Branch Building Assessment Appendix E: Photo Documentation Architectural and Structural Brown County Library Central Branch Building Assessment
More informationNATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY
A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -
More informationEmergency Lighting: what, when & how? Richard Caple MSc MSLL Lighting Applications Manager
Emergency Lighting: what, when & how? Richard Caple MSc MSLL Lighting Applications Manager What is emergency lighting? Legislation and standards Emergency lighting design Emergency lighting testing requirements
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed
More informationFacilities Master Planning
Facilities Master Planning DeForest Area School District DeForest, WI PRA Project #130343-01 January 13, 2014 DRAFT Table of Contents DeForest Area School District PRA Project # 130217-01 Section 1 Existing
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: PS 152 ANNEX -BROOKLYN, 1087 OCEAN AVENUE, New York, 11210 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20
More informationCOMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods
1. BASIC ELECTRICAL MATERIALS 1. All conduit and raceway must be 3/4" or larger. Exposed raceway in finished areas shall be in 700 or larger wiremold. Exception: runs to individual devices 10 or less,
More informationPage 1 of General
Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors
More informationEntry Level Assessment Blueprint Electrical Construction Technology
Entry Level Assessment Blueprint Electrical Construction Technology Test Code: 4130 / Version: 01 Specific Competencies and Skills Tested in this Assessment: Introduction to the Electrical Construction
More informationRESIDENTIAL OVER. 4. Would it be permissible to hard- wire the dishwasher in question 3? If so, under what conditions?
WELCOME TO THE EASTERN SECTION CODE BREAKFAST CODE BREAKFAST QUESTIONS FOR THE EASTERN SECTION ANNUAL MEETING 93 rd ANNUAL EASTERN SECTION MEETING, KING OF PRUSSIA, PA RESIDENTIAL ALL QUESTIONS BASED ON
More informationA. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationDivision 26 ELECTRICAL TABLE OF CONTENTS
Division 26 ELECTRICAL TABLE OF CONTENTS 26 1000 GENERAL... 33 A. CODE... 3 B. RELATED SECTIONS... 3 C. ABBREVIATIONS... 3 D. DEFINITIONS... 3 E. DRAWING REQUIREMENTS... 3 F. EQUIPMENT SERVICE ACCESS AND
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MAGPIE COMPOSITE TEXTILE LTD. 832/833, DEWAN IDRIS ROAD, AMTOLI, ASHULIA, SAVAR, DHAKA OTHER FACTORIES: NONE May 17, 2014 Page 2 SUMMARY was surveyed for fire safety on 5/17/2014
More informationMechanical Inspection Plumbing
0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,
More informationFIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH
FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH January 3, 2014 Redpoint Jackets Ltd. PAGE 1 SUMMARY The four story factory housing Redpoint Jackets Ltd. located in Dhaka Export Processing
More informationELECTRICAL REQUIREMENTS FOR HEALTH CARE FACILITIES
ELECTRICAL REQUIREMENTS FOR HEALTH CARE FACILITIES Review Guide for: Hospitals Nursing Facilities Clinics Office of Statewide Health Planning and Development Facilities Development Division www.oshpd.ca.gov
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 59 ANNEX - BRONX, 2120 QUARRY RD, New York, 10457 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-02-12
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 364 - BROOKLYN, 1426 FREEPORT LOOP, New York, 11239 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-16
More informationMASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 26 ELECTRICAL
SECTION 265100 - INTERIOR LIGHTING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Interior lighting fixtures, lamps, and ballasts. 2. Emergency lighting units. 3. Exit signs. 4.
More informationDirect Dim Microwave Presence/Absence Detector
Product Guide MWS3A-DD Direct Dim Microwave Presence/Absence Detector Contents Section Contents Page 1 Dimensional information 1 2 Description and operation 2 3 Wiring & Fixing 3 4 Installation 3 5 Fixing
More informationNational Electrical Code
National Electrical Code 409.30 Disconnecting Means Disconnecting means that supply motor loads shall comply with Part IX of Article 30. 410.81 Control (A) Disconnection Luminaires (fixtures) or lamp installation
More informationNYC Department of Education
NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-07
More informationCatalog Number. Notes. Type. FST Snap on frosted, diffuse L/LENS No diffuser
Catalog Number FEATURES & SPECIFICATIONS INTENDED USE Built on the compact, low-profile Z strip channel, this LED strip offers long maintenance-free life, several color s, lumen outputs and lengths. Ideal
More informationCT CABINET AND UTILITY METERING WELL AND BOOSTER PUMP CONTROL 12"x12" WIREWAY 200A MCB 200A, 120/208V, 3Ø, 4W BOARD TVSS CIA ALARM 400A, DOUBLE-THROW SWITCH PORTABLE GENERATOR CONNECTION ENCLOSURE EXISTING
More informationThaddeus Stevens College of Technology Mellor Building
Thaddeus Stevens College of Technology Mellor Building Energy Survey Report November 12, 2009 Prepared by: Energy Opportunities, Inc. 1200 East Camping Area Road Wellsville, PA 17365 717-292-2636 Energy
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February
More information