MUKWONAGO SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY
|
|
- Gavin Hopkins
- 5 years ago
- Views:
Transcription
1 MUKWONAGO SCHOOL DISTRICT ARCHITECTURE PARK VIEW MIDDLE SCHOOL The original school building was dedicated in 1954 as the High School, with an addition in 1959, a library addition in 1970, and an addition/renovation in The 1993 addition demolished the 1970 library addition as part of the renovation. The building currently contains approximately 114,000 gross square feet on the first floor, with a partial basement area of nearly 5,900 gross square feet. The exterior walls of the 1954 and 1959 buildings are load bearing masonry walls, while the 1993 buildings are load bearing masonry cavity walls. There appears to be no air space or insulation between the brick and block of the 1950 s era buildings. The roof structure for all of the additions consists of steel joist, metal deck, and a built-up roofing system. 1. SITE Condition of Asphalt Parking 1.1 The asphalt parking lot is in good condition and should be patched, resealed, and restriped. Condition of Asphalt Playgrounds 1.2 Basketball courts are in poor condition and should be replaced. Adequate Parking / Observed Traffic Flow 1.3 Parking appears to be adequate. Athletic Field Conditions 1.4 The running track is in poor condition and needs to be repaired and resurfaced. Condition of Landscaping 1.5 Landscaping around the perimeter of the building is in poor condition. Landscaping at the edge of the parking lot is in poor condition, where most of the grass has eroded away. ADA Access 1.6 From parking lot to front door: An ADA accessible route and accessible parking stalls are provided at the front entrance. 1.7 From building to playground: ADA access to the playground is provided through several doors throughout the building. 2. BUILDING - ROOF Roof Type and 1959 Roof - Built-up roof system Roof Ballasted rubber membrane. Lifespan / Age / Condition 2.3 Most of the original roof remains from the 1954 building and 1959 addition. New roofs were added to the areas covering the 1993 addition/renovation, but no replacement of the existing roof was implemented. Many of the roofs are beyond or getting near the end of their lifespan and should be replaced. Roof flashing repairs are also required. Roof repair replacement budget should be included. The budget of $818,000 should be inflated at 5% per year for two years. PRA Project No Park View Middle School Page 1
2 MUKWONAGO SCHOOL DISTRICT ARCHITECTURE 3. BUILDING EXTERIOR Condition of Brick / Tuck Pointing 3.1 Many of the exterior walls have large cracks, or in some cases, missing bricks. Most of this occurs in the original 1954 and 1959 building. Several repairs have been made around the building, but many of the problems are still evident. Tuck pointing and brick repair is needed on approximately 40% of the building perimeter. Block backup needs repair where cracked. 3.2 Various stone accents and sills around the building are in need of cleaning. Condition of Windows / Insulated Glass / Operation 3.3 All of the windows around the building were replaced in the 1993 addition/renovation and are in fair condition. However, 80% of the spandrel glass used above the operable windows have become discolored and will need to be replaced. Condition of Trim Work (Metal Coping, Trim Accent Pieces, Etc.) 3.4 Much of the original metal coping and trims from the 1954 and 1959 building is in poor condition and should be replaced. Condition of Exterior Doors (Store Front, Steel Doors, Etc.) 3.5 Existing steel doors from the 1954 and 1959 building are worn and should be replaced. Threshold repair or replacement and weatherstripping around doors is required. Condition of Exposed Foundations, Cracks 3.6 No work needed. Condition of Drainage System (Gutters, Downspouts, Scuppers) 3.7 Most of the roof is drained by internal roof drains. Some existing scuppers and downspouts remain from the building from the 1954 and 1959 building. They are worn and should be replaced. Caulking 3.8 Caulking appears to be in fair condition, but should be checked for replacement. 4. BUILDING INTERIOR ADA Access / Entrance 4.1 Most of the doors were replaced in the 1993 addition/renovation to provide ADA access to the building. ADA Bathrooms 4.2 All of the public bathrooms were updated in the 1993 addition/renovation to provide ADA accessibility for users, but current standards have rendered them inaccessible. Address accessibility by widening doorways, replace partitions, replace/relocate fixtures and replace finishes. 4.3 The rest of the single, private bathrooms around the building are not ADA accessible. PRA Project No Park View Middle School Page 2
3 MUKWONAGO SCHOOL DISTRICT ARCHITECTURE Asbestos Abatement 4.4 Report available at School and District offices. Interior Windows / Doors 4.5 Many of the doors were new, replaced, or redone in the 1993 addition/renovation and are in good condition. Provide security doors at science hallway as well as main office/guidance area for after hours security. Elevator 4.6 Lift to Band Room. Stairs 4.7 The stair to music area appears to be in fair condition, but metal railings/banister should be cleaned and repainted. Flooring / Carpet 4.8 The floor tile is in fair condition and approximately 20% should be replaced. These areas have tile cracking, lifting or discoloration. 4.9 The floor in both gyms is in good condition, but needs to be thoroughly cleaned and restriped The vinyl base throughout the building is in poor condition and should be replaced Several rooms in the southeast corner of the building are experiencing moisture problems in the floor. Several floors have been replaced due to this problem. Investigations will need to take place to determine the extents of this problem, which may include excavation of sub-grade soil. Ceilings 4.12 Most of the ceiling tiles were replaced in the 1993 addition/renovation and are in fair condition. General paint condition on walls 4.13 Painted walls around the building are in good condition The walls of Gym 85 should be painted to a height of seven feet (7'-0") as there are many scuffs and marks from gym use Paint all restrooms Paint locker room walls. Condition of woodwork / casework 4.17 Case work is in fair condition. Miscellaneous 4.18 A majority of the lockers in the halls and gym locker rooms are 1950 s vintage and should be replaced The bleachers in both gyms are worn and out-dated. Replace approximately 52- feet of bleachers in the Gym 85 and replace 1950 s era bleachers in Gym Soffits around the building are in poor condition and should be painted Install building security system Provide selective locker refinishing and repair in hallways and locker rooms Replace missing ceramic tiles in locker rooms. PRA Project No Park View Middle School Page 3
4 PLUMBING PARK VIEW MIDDLE SCHOOL Sanitary Drainage System: Sanitary waste is extended from the building below ground to the City sanitary sewer system. Storm Drainage System: Storm water from roof areas is collected at interior roof drains, routed down to below grade and extended to the City storm sewer system. Domestic Water System: Domestic water is supplied to the building from a water service main, connected to the City water main in the street. Domestic water is routed throughout the building above the ceiling. No water softener is provided for the building s domestic water system except a small water softener and brine tank is provided to soften the hot water to the kitchen dishwasher. Domestic hot water is provided by two (2) gas-fired, sealed combustion, 100-gallon tank type water heaters. Plumbing Fixtures: Water Closets: Urinals: Lavatories: Sinks: Mop Basins: Water Coolers: Floor outlet and wall-hung, manual flush valve, water closets, vitreous china units. Stall floor outlet, vitreous china urinals, sensor operated flush valve. Wall-hung, vitreous china units with deck mounted metering mixing faucet and push button operator. Countertop, self-rimming, single and double compartment stainless steel sinks, deck-mounted gooseneck spout, mixing faucet with wrist handles. Floor set, floor outlet, 36 x 24 x 10 fiberglass mop basin with wallmounted faucet with vacuum breaker. Wall-hung, standard height water coolers. PRA Project No Park View Middle School Page 4
5 PLUMBING General Comments: 1.1 The two (2) existing gas-fired water heaters are new, just installed, including two (2) circulating pumps. Heaters and pumps should be replaced when failure occurs. Estimated Cost $ 8,000. per heater 1.2 The existing horizontal hot water storage tank should be drained and the inside inspected to determine its condition whenever the school schedule permits. Tank should be replaced when failure occurs. Estimated Cost $ 12, The entire building s water distribution system should be softened except for the exterior hose bibbs. New water softening equipment should be provided and additional hard water piping extended through the building all exterior hose bibb locations. Estimated Cost $ 15, The old and poor condition plumbing fixtures in toilet rooms and classrooms should be replaced with new water-saving-type fixtures and trim. Estimated Cost $ 1,200. per fixture 1.5 The domestic hot water piping in the building is starting to show its age. Pipe leaks have been increasing and repairs are more difficult to fix. The existing piping should be replaced with new type L copper pipe and fittings with new fiberglass pipe insulation. Estimated Cost $ 80,000. PRA Project No Park View Middle School Page 5
6 HVAC PARK VIEW MIDDLE SCHOOL Heating: The building is heated by two (2) gas-fired, forced draft, low pressure fire tube steam boilers and one (1) gas-fired, forced draft, cast iron boiler located in the basement. The two steam boilers were installed in the 1950 s and the cast iron boiler was installed in The mechanical systems, with the exception of the steam boiler system, were replaced as part of the 1993 remodeling project. A steam-to-water heat exchanger is installed in the boiler room to provide hot water for the heating system. A piping loop is routed above the ceiling and in tunnels of the building. The piping loop is connected to radiation, unit ventilators, air handling units and reheat coils throughout the building. The piping system is part a two (2) pipe heating/cooling system which supplies hot water during the heating season and cold water during the cooling season. Portions of the piping loop are provided with two-position isolation valves to prevent flow to heating-only equipment with the system in the cooling mode. Ventilating: The classrooms are ventilated by vertical unit ventilators installed at the exterior walls. The library and interior classrooms are ventilated by horizontal unit ventilators suspended above the ceilings with supply and return ductwork routed to ceiling outlets. Indoor air handling units are provided for the following areas: Area Served Unit Location Type Music Area Basement Var. Vol. w/vav Reht. Units Old Gym Mezzanine Mech. Room Constant Vol. Single Zone New Gym First Floor Mech. Room Constant Vol. w/reheat Coils Art Rooms M.P. Storage Room Var. Vol. w/vav Reht. Units Multi Purpose Room M.R. Storage Room Constant Vol. w/reheat Coils Wood Shop Wood Shop Constant Vol. Single Zone Indoor fan coils suspended at or above the ceiling provide heating and ventilating for the Boys and Girls Locker Rooms and heating, ventilating and air conditioning for the corridors, Guidance Areas, Administration Offices and Health Room/Nurses Office. Economizer relief is provided by roof-mounted hoods located above the corridor ceiling and ducted to grilles in the corridor ceiling. Exhaust for toilet rooms, locker/shower rooms, kitchen hood, etc. is provided by roof-mounted exhaust fans. PRA Project No Park View Middle School Page 6
7 HVAC Air Conditioning: The building is air conditioned by a grade-mounted air cooled chiller. Chilled water piping is routed above the ceiling and connected to the two-pipe system which is each to unit ventilator, fan coil unit and air handling unit cooling coil. The chilled water system contains a glycol solution to eliminate the need to drain the chiller or cooling coils during the heating system. The Administration Office and Health/Nurses Office fan coil units are provided with direct expansion cooling coils with refrigerant piping routed to grade-mounted air cooled condensing units. Temperature Controls Automatic temperature controls for the HVAC systems in the building are pneumatic. An ATC air compressor and refrigerated air dryer are provided to supply compressed air to the system. HVAC Comments: 1.1 Remove steam boilers, heat exchanger and condensate return system and provide new high efficiency hot water boilers. Estimated Cost $210, Replace hot water circulating pumps. Estimated Cost $ 15, Replace unit ventilator outside air louvers with new and provide protection from playground damage. Estimated Cost $ 1,200. per louver 1.4 Replace pneumatic ATC system with DDC system compatible with other buildings. Estimated Cost $250,000. PRA Project No Park View Middle School Page 7
8 ELECTRICAL PARK VIEW MIDDLE SCHOOL ELECTRICAL SERVICE AND DISTRIBUTION The main electric service is 3000A, 120/208V 3-phase, 4-wire. The GE Spectra Series service entrance switchboard appears to have about half of its useful life remaining. The main service should be able to accommodate any lighting, bleacher, boiler and circulation pump, water heater, and elevator replacements that have been identified. 1.1 Minor power distribution modifications will be required for bleacher replacement. 1.2 Minor power distribution modifications will be required for (3) boiler and circulation pumps replacement. 1.3 Minor power distribution modifications will be required for (2) water heater replacement. 1.4 Minor power distribution modifications will be required for elevator replacement. SURGE SUPPRESSION The main service does have a TVSS unit to provide surge suppression. EMERGENCY GENERATOR AND TRANSFER SWITCH The emergency generator is a Kohler 135kW diesel set. It is located outside near the utility transformer with an above ground diesel storage tank. One 600A transfer switch that serves both the life-safety and non-life safety loads. This violates current Code, but this installation is grandfathered in so separating the loads is not required unless a new generator is installed. The generator and transfer switch both appear to have about half of their useful life remaining. They also appear to be in good operating condition. LIGHTING The majority of the lighting is T8 fluorescent. Typical classrooms have 2 x4 3-lamp acrylic lenses troffers on 8 x10 centers. 1.5 Corridors have 1 x4 2-lamp acrylic lenses troffers on 10 centers. Some corridors have 2-lamp 18 DTT compact fluorescent fixtures as well. Building staff indicated the desire to relight these corridors to provide better lighting. Exterior lighting is HPS. PRA Project No Park View Middle School Page 8
9 ELECTRICAL FIRE ALARM The existing fire alarm system in this building is an addressable Simplex 4100 type which was recently installed and can be assumed to comply with the current Code. 1.6 The only work which may be required if a new elevator is installed, is minor modifications for elevator recall. CLOCK SYSTEM A new Primex wireless clock system was installed in No work required. INTERCOM SYSTEM There is a Simplex intercom system with speakers in corridors, classrooms, and offices. It appears to be in good operating condition. Building staff has requested that volume control be provided for the speakers. There are two options for providing volume control on the existing system. They are as follows: DATA DISTRIBUTION 1.7 Option A: Provide attenuator at punchdown blocks in intercom rack. This would allow a one-time volume control adjustment, not daily adjustments. Estimate includes 75 rooms. $4,000 Option B: Provide volume control at individual rooms. This would allow volume adjustment at any time. However, pulling new cable from each room requiring volume control would likely be necessary. Estimate includes 75 rooms. $8,000 The data distribution was completed in the late 1990 s as part of the TEACH telecommunication systems program. Cat 5 outlets are provided in each classroom. TELEPHONE DISTRIBUTION The telephone distribution was completed in the late 1990 s as part of the TEACH telecommunication systems program. Cat 5 phone outlets are provided in each classroom. TELEVISION DISTRIBUTION The television distribution was completed in the late 1990 s as part of the TEACH telecommunication systems program. Television distribution outlets are provided in each classroom. PRA Project No Park View Middle School Page 9
10
11
12 PHOTOGRAPHS PARK VIEW MIDDLE SCHOOL Typical hallway Typical hallway Typical exterior Typical vent 1.1 Asphalt paving at parking lot 1.5 Landscaping at perimeter of the building PRA Project No Park View Middle School Page 10
13 PHOTOGRAPHS 2.3 Gym 7E roof leaks 3.1 Deteriorated brick 3.1 Tuck pointing 3.1 Tuck pointing 3.2 Stone trim to be cleaned 3.2 Stone trim to be cleaned PRA Project No Park View Middle School Page 11
14 PHOTOGRAPHS 3.3 Windows 3.3 Windows 3.3 Windows 3.7 Downspout 4.1 Exterior door 4.2 Typical bathroom PRA Project No Park View Middle School Page 12
15 PHOTOGRAPHS 4.2 Typical bathroom 4.2 Typical bathroom 4.3 Bathroom at teachers lounge 4.5 Typical classroom door 4.8 Typical staff lounge carpet 4.9 Floor tile PRA Project No Park View Middle School Page 13
16 PHOTOGRAPHS 4.9 Floor tile 4.9 Floor tile 4.9 Typical hallway floor 4.10 Gym 78 floor 4.11 Vinyl base at walls 4.12 Floor problem PRA Project No Park View Middle School Page 14
17 PHOTOGRAPHS 4.12 Floor problem 4.15 Gym 85 walls 4.17 Hallway lockers 4.18 Bleachers in gym Bleachers in gym Exterior soffits PRA Project No Park View Middle School Page 15
MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY
ARCHITECTURE ROLLING HILLS ELEMENTARY SCHOOL Rolling Hills Elementary was built in 1999 and is the newest addition to the Mukwonago Area School District. The building contains approximately 64,900 gross
More informationTighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance
Groton Heights School Mechanical Evaluation TO: FROM: Amy Vaillancourt, Project Manager Harley Langford, Project Manger Jason Curtis, P.E. DATE: February 24, 2016; Revised May 31, 2016 On Monday, December
More informationFlorence High School / Middle School Page 1 of 3 Florence, WI
Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October
More informationVOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED
Ashton Elementary School 1 Masonry Repair $ 42,781.50 2 Replace HVAC $ 375,000.00 3 Replace SAT @ Various Locations $ 92,364.00 3 Recoat & Resurface Exterior Paved Play Area $ 135,978.30 3 Various Technological
More informationSITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL)
SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL) Basketball Courts 15 25 Built Improvements Playgrounds, Site Furniture, etc. 20 20 Catch Basin 40 40 Cold Water Lines 40 40 Compactors DHW Supply
More informationMechanical Inspection Plumbing
0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,
More informationHOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District
HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the
More information2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect
1 Site Summary Address 7200 Bluff Springs Road Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 2014 Total Campus Building Area (combined) 25,314 SF Introduction The
More informationEdward Jenner Elementary Academy of the Arts
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#58619/Page 1/November 1, 2017 PLUMBING Executive Summary: Presently, the Plumbing Systems serving the building are cold water, hot water, sanitary, waste and vent system, storm drain piping, and natural
More informationPLATTEVILLE MIDDLE SCHOOL
Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle
More informationState College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT
State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the
More informationGenevieve Melody Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationChariho Regional School District Five-Year Capital Facilities Improvement Plan (2/10/15)
Chariho Regional School District Five-Year Capital Facilities Improvement Plan (2/10/15) School/Department FY 16 FY 17 FY18 FY19 FY20 Chariho Regional High School FY 16 FY 17 FY18 FY19 FY20 *Repair Bleachers
More informationSchool District of Milton 5- Year Capital Maintenance and Improvement Plan
Updated - 02/21/17 School District of Milton 5- Year Capital Maintenance and Improvement Plan 101 East Elementary 1 Parking Lot/Traffic Flow Project 615,175 Includes Construction and Engineering 2 Bathroom
More informationFacility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building
Facility Condition Assessment Summary Report British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Submitted by: VFA Canada Corp. Burnaby Centre 4211 Kingsway Burnaby, BC V5H 1Z6
More informationState College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT
State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the
More informationAgustin Lara Elementary Academy
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationJosefa Ortiz De Dominguez Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationCalmeca Academy of Fine Arts and Dual Language
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationResidential Construction and Remodeling Estimates. compliments of. pillartopost.com
Residential Construction and Remodeling Estimates compliments of STRUCTURE/EXTERIOR Structure > addition (foundation to roof) $95 $130/sq.ft. > basement entrance $5250 $10500 > basement main beam $2100
More informationDOCUMENT TABLE OF CONTENTS
DOCUMENT 00003 June 16, 2005 TABLE OF CONTENTS DOCUMENT NO. INTRODUCTORY INFORMATION DOCUMENT 00003 TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS SECTION 01011 SECTION 01025 SSP21.1-1 SECTION 01026
More informationRichard Henry Lee Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationJoseph Brennemann Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationMARY CRAPO CENTER Miller Road, Swartz Creek, Michigan
MARY CRAPO CENTER 8197 Miller Road, Swartz Creek, Michigan MARY CRAPO CENTER 8197 Miller Road, Swartz Creek General Information: - Instructional, Child Care Development Center (West Wing) o (2) Infant/Toddler
More informationJohn Palmer Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More information2014 Bond Project Guide
2014 Bond Project Guide Bush Elementary School Page 1 Instructional Technology Computers, Projectors, Mobile Carts, Document Cameras and Printers Wireless Connectivity New Construction New Tech Center
More informationDESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES
2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.
More informationCook - Wissahickon Elementary School
Cook - Wissahickon Elementary School 201 E. Salaignac St., Philadelphia, PA 19128 HVAC Replacement Project Scope Determination Report May 10, 2018 Prepared by: G.P. Lamina, Jr., P.E., MBA School District
More informationDEERFIELD SCHOOL DISTRICT REFERENDUM Committed to Excellence and Equity in Educating Our Students
DEERFIELD SCHOOL DISTRICT REFERENDUM Committed to Excellence and Equity in Educating Our Students FACILITY NEEDS THE CHALLENGE Deerfield Middle School/High School building has served the community for
More informationEstimated Repair, Replacement, and Upgrade Costs
Description Electrical Attic ventilator-mechanical $250 Baseboard heater (4') $150-$400 Ceiling fan $200 Doorbell system $80-$100 Dryer duct $100-$150 Hardwired smoke detector $60-$120 Exhaust Fan-Bathroom
More informationFrancis M McKay Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationGeorge B Swift Elementary Specialty School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationTillamook High School Bond Projects
Tillamook High School Bond Projects School Project Description All Buildings Upgrade fire alarm H&S All Buildings Add door lock capability from inside rooms Security All Buildings Install card lock entry
More informationBriar Crest Elementary
Promises Kept This document includes partial lists of major projects completed at Pattonville Schools since 1986 as part of past bond issues approved by the Pattonville community. Briar Crest Elementary
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton RCSSD #7 Bishop Savaryn Catholic Elementary School B58A Edmonton Report run on: July 10, 2008 3:31 PM Building Name: Address: Location: Building Id: Gross Area
More informationWashington Irving Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationExisting Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1
L21366/101 090 00.00/Page 1 HVAC EXECUTIVE SUMMARY The North Middlesex Regional High School has received average maintenance of the HVAC systems over its occupied years. Even with adequate maintenance,
More informationOscar DePriest Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationREPAIR ESTIMATE GUIDE
REPAIR ESTIMATE GUIDE STRUCTURE Foundation Addition (foundation to roof)... $125 - $170/sq.ft. Basement entrance... $6485 - $13690 Basement main beam... $2740 Basement support post/foundation... $650 -
More informationAlessandro Volta Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationInspecta-Homes 2469 University Avenue West St. Paul MN Ph#: (651)
Page 1 Doc #: Inspector: Date: Dwelling Address: Client Name: Client's Agent: Real Estate Company: Please refer to the General Home Inspection Contract. Thank you for using Minnesota and Western Wisconsin's
More informationMOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School
MOUNT PLEASANT MIDDLE SCHOOL HVAC M-01 Heating Plant: The existing boilers have recently been upgraded. (3) steam boilers (8660 mbh each) manufactured by Weil- McLain have been installed. Newer hot water
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Calgary RCSSD #1 Ecole St. Matthew Elementary / French Immersion Jr. High School B2614A Calgary Report run on: March 25, 2010 10:11 AM Building Name: Address: Location:
More information3. 21st Century Learning A. Districtwide Flexible Learning - Allowance for Flexible Furniture $600,000 Subtotal $600,000
1. Safety and Security A. Additional Cameras District Wide $382,000 B. Interior Locks Upgrades Allowance $300,000 C. Tilden Entrance Upgrades D. Door and Glass Improvements Allowance $500,000 E. Alert
More informationCharles W Earle Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationInspection Report. Prepared for: Tonia Mann. Property Address: 402 Leslie Court McDonough, GA Date: March 07, 2013
Inspection Report Prepared for: Tonia Mann Property Address: 402 Leslie Court McDonough, GA 30253 Date: March 07, 2013 Inspector: Charles Mann Edifice Inspections, Inc. (770) 594-2222 www.edificeinspections.com
More informationCAPITAL OUTLAY REQUEST - IDENTIFIED AND EMERGING PROJECTS - RANKED 3-Jun-14
2014-2015 CAPITAL OUTLAY REQUEST - IDENTIFIED AND EMERGING PROJECTS - RANKED 3-Jun-14 School Item Amount a. Classroom A/R (Increase CR capacity to 804, add l Resource and tutoring spaces needed. Teacher
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton RCSSD #7 Our Lady Of The Prairies Catholic Elementary School B3241A Edmonton Report run on: July 17, 2008 4:00 PM Building Name: Address: Location: Building Id:
More informationFAIRA TRANSPARENCY REPORTS S 236th St, 10-5, Kent, WA 98032
608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 5427 S 236th St, 10-5, Kent, WA 98032 Thank you for your interest in this Faira Certified
More informationSidney Sawyer Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Calgary School District #19 John G Diefenbaker High School B2686A Calgary Report run on: January 1, 28 9:31 AM Building Name: Address: Location: Building Id: Gross Area
More informationDESIGNER KITCHEN WITH PREMIUM APPLIANCES 1407 & 1409 Military Trail Features & Finishes 1. Open concept kitchen with NEFF designer cabinetry and Caesa
DESIGNER KITCHEN WITH PREMIUM APPLIANCES 1407 & 1409 Military Trail Features & Finishes 1. Open concept kitchen with NEFF designer cabinetry and Caesarstone countertop. 2. 4 x 16 ceramic tile backsplash.
More informationTIFT COUNTY SCHOOLS E-SPLOST HISTORY
TIFT COUNTY SCHOOLS E-SPLOST HISTORY July 1, 1997 June 30, 2002 $28,766,187.16 collected July 1, 2002 June 30, 2007 $39,025,830.10 collected July 1, 2007 June 30, 2012 $41,886,155.46 collected July 1,
More informationThe Ultimate Home Maintenance Schedule
The Ultimate Home Maintenance Schedule On-Going Quarterly Maintenance Schedule Check interior and exterior faucets for leaks. Clean aerators. Replace washers if Clean with baking soda. Pour water down
More informationFacilities Master Planning
Facilities Master Planning DeForest Area School District DeForest, WI PRA Project #130343-01 January 13, 2014 DRAFT Table of Contents DeForest Area School District PRA Project # 130217-01 Section 1 Existing
More informationGreenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111
Greenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111 Year Opened 1958 Current Square Footage 50,504 Site Acreage 8.53 greenwood.cherrycreekschools.org $220,720 Electrical
More informationNebraska Department of Correctional Services
Nebraska Department of Correctional Services Feasibility Study for the former Lancaster County Jail Facility Lincoln Air Park 4420 NW 41 st Street Lincoln, NE September 29, 2015 TABLE OF CONTENTS I. Introduction
More informationDeWitt Clinton Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Calgary School District #19 Queen Elizabeth Junior / Senior High School B2745A Calgary Report run on: March, 2010 10:02 AM Building Name: Address: Location: Building Id:
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Wild Rose School Div #66 Pioneer School B3972A Rocky Mountain House Report run on: March 26, 213 9:48 AM Building Name: Address: Location: Building Id: Gross Area (sq.
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton School District No. 7 Stratford Academic High School B3336A Edmonton Report run on: April 3, 29 1:6 AM Building Name: Address: Location: Building Id: Gross Area
More informationHVAC / Boilers / Hot Water. Expected Life Span. very rough estimates Condition/Issue Age. Athletics / Gyms
$4,013,500.00 $4,013,500.00 $ 1,155,000.00 $ 1,000,000.00 $ 205,000.00 $ 275,000.00 $ 300,000.00 $ 360,000.00 $ 438,500.00 $ 280,000.00 School Status Item HS Boilers boiler controls replaced 2017 2002
More informationNYACK PUBLIC SCHOOLS CAPITAL IMPROVEMENT PLANNING PROCESS
NYACK PUBLIC SCHOOLS CAPITAL IMPROVEMENT PLANNING PROCESS DECEMBER 3, 2013 KEY QUESTIONS 1. What is the time sequence for available funding? (In what years will the funding be available?) 2. What is the
More informationCLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN
CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN 04.13.2017 1 MONTICELLO INTERIOR FINISHES PAINT MOULDING WALLS ACCENT DOORS DOOR TRIM/STAIRS
More informationDOMESTIC WATER PACKAGED BOOSTER PUMPS
DIVISION 22 PLUMBING 22 11 16 DOMESTIC WATER PIPING 22 11 19 DOMESTIC WATER PIPING SPECIALTIES 1. To facilitate landscape and other maintenance operations, exterior hose bibs shall be provided at 150 foot
More informationCampus Middle School 4785 South Dayton Street Greenwood Village, Colorado 80111
Campus Middle School 4785 South Dayton Street Greenwood Village, Colorado 80111 Year Opened 1971 Current Square Footage 175,743 Site Acreage (included in CCHS) 87.22 campus.cherrycreekschools.org $2,441,170
More informationSpringpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp.
Volume 1 Bidding Requirements, Contract Forms, Conditions of the Contract, Division 1, Architectural and Site Specifications 000107 Certification Page 000110 Table of Contents DIV00 PROCUREMENT AND CONTRACTING
More informationNARRATIVE REPORT. Engineering Administration was originally constructed in 1965; the building has had no major renovations.
NARRATIVE REPORT 1.0 BUILDING INFORMATION Engineering Administration was originally constructed in 1965; the building has had no major renovations. Engineering Administration is a three-story, 9,579 ft
More informationAshland School District Facility & Capacity Assessment Report 2005
Ashland School District Facility & Capacity Assessment Report 2005 Briscoe Elementary School (Closed Facility) Address: 265 N Main Street Area: 33,980 square feet Buildings: Original Building 1948 Music
More informationCanadian Property Inspections
Cover Page Canadian Property Inspections Home Inspection Report L9Z-1K4 Inspection prepared for: K.C. Pitman Date of Inspection: 3/6/2017 Time: 3pm Age of Home: 42 Size: 500-1000 Weather: Cloudy, cool.
More informationDRAFT. Widen Elementary School Site Summary 74,523 SF. Introduction
1 Widen Elementary School Site Summary Address 5605 Nuckols Crossing Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 1986 Total Campus Building Area (combined) 74,523
More informationMassachusetts School Building Authority
Massachusetts School Building Authority School District Revere District Contact Paul Dakin TEL: (781) 286-8226 Name of School Submission Date 3/6/2007 The following Priorities have been included in the
More informationAsurity 1. Property Inspection Report S Gurd Rd., Hastings, MI Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski -
Cover Page Property Inspection Report Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski - Date of Inspection: 3/28/2017 Time: 2:00 Age of Home: Built 1999 Size: 2015 Weather: 50 Overcast.
More informationENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING
Mechanical Systems Information The mechanical system at Reed Middle School is comprised of seventy six Trane DX/Gas rooftop units (RTUs). The recommended useful life for DX equipment is 15 years. Seventy
More informationSagebrush Elementary School East Temple Place Aurora, Colorado 80015
Sagebrush Elementary School 14700 East Temple Place Aurora, Colorado 80015 Year Opened 1977 Current Square Footage 57,100 Site Acreage 7.66 sagebrush.cherrycreekschools.org Asphalt and concrete work; electrical
More informationDesign Standards Manual
Design Standards Manual Table of Contents: Part III (Divisions 1-32) Section No. Title Revision DIVISION 1: GENERAL REQUIREMENTS 01524 Construction Waste Management 05/07 01815 HVAC Commissioning Requirements
More informationDMTF: Specific Building Recommendations
DMTF: Specific Building Recommendations Asset Name Project Title Total Cost BLOCKER BUILDING 22,503,303 Capital Renewal 7,640,013 DOMESTIC WATER HEATER REPLACEMENT 16,374 EXTERIOR DOOR REPLACEMENT 133,623
More informationDESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.
PART 1 - GENERAL 1.1 Toilet rooms and utility rooms to have floor drains at lowest point. 1.2 Utilize Exposed Flushometers. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.
More informationNARRATIVE REPORT. Underlayment Paper for Linoleum. The Asbestos Bulk Sample Results Table includes asbestos sampling data.
NARRATIVE REPORT 1.0 BUILDING INFORMATION Engineering and Technology was originally constructed in 1913; although specific information is unavailable, several renovations are evident. Engineering and Technology
More informationMadeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)
Madeira City Schools Madeira, Ohio HVAC Assessment December 2011 (Revised February 2012) Prepared by: CMTA Engineering Consultants, Inc. 10411 Meeting Street Prospect, KY 40059 www.cmtaegrs.com (502) 326-3085
More informationStructural Guidelines. Food Service Establishments. Retail Food Stores
Structural Guidelines for Food Service Establishments and Retail Food Stores Jefferson County Department of Health Food & Lodging Protection Division 1 Before construction or remodeling of a food service
More informationNew High School Concept
Approved Bond Projects for Alamance-Burlington Schools In November 2018, Alamance County citizens approved a $150 million bond project proposal. Bond funds will pay to construct a new high school and provide
More informationFAIRA TRANSPARENCY REPORTS. July 6, 2016
608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 13301 NE 135 th St, Kirkland, WA 98034 July 6, 2016 Thank you for your interest in this Faira
More informationMaster Facility Planning Update School Board Meeting May 26, 2016
Master Facility Planning Update School Board Meeting May 26, 2016 Master Facilities Committee Overview Reflection of Committee Work Review of District Wide Facility Issues Identified District Wide Facility
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton RCSSD #7 Blessed Kateri School B36A Edmonton Report run on: April 3, 29 1:1 AM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement
More information2014 Bond District-wide Facility Repairs
Elementary Schools Aloha-Huber Park Fire Detector upgrade Replace electric backboard winches in gym Heating/cooling system controls upgrade Barnes Replace exterior windows Heating/cooling system and controls
More informationCanadian Property Inspections
Cover Page Canadian Property Inspections Home Inspection Report N6J-3A8 Inspection prepared for: Josh Baran Date of Inspection: 3/7/2017 Time: 9am Age of Home: 40 Size: 1500 Weather: Cloudy,cool,light
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Canadian Rockies Reg Div #12 Exshaw School B3390A Exshaw Report run on: March 26, 2010 9:29 AM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement
More informationSiemens Building Technology MEP Existing Conditions
Electrical Existing Conditions Report Executive Summary: The electrical systems for the are generally of the original vintage. The site is primary metered with the meter located in the main Electric Room.
More informationInspection Report 123 My Street Midland, GA
Buying, Selling or Building Your Home Inspection Company ROFESSIONAL INSPECTION SERVICES, LLC P.O. Box 9774 Columbus, GA 31908 706-565-0333 1-866-298-4251 Inspection Report 123 My Street Midland, GA This
More informationIchabod Crane Central School District 2018 Capital Project Preliminary Estimate
Health & Safety 1,399,000 Academics & Program 17,140,800 Physical Education & Athletics 5,922,000 Building Infrastructure 3,103,800 Site Infrastructure 1,049,600 TOTAL SCOPE OF WORK 28,615,200 PROPOSED
More informationPREPARED FOR: (Name of Client) CONCERNING: (Address of Property) BY: P Home. YOUR HOME CHECK 1305 FM 359, Suite G F
PREPARED FOR: l (Name of Client) CONCERNING: (Address of Property) BY: (Name of Technician) (Consultation Date) YOUR HOME CHECK 1305 FM 359, Suite G Richmond, TX 77469 P 281-342-Home F 281-342-4669 I.
More informationMontgomery County Land Bank PRE SALE INSPECTION REPORT
Montgomery County Land Bank 130 West 2nd Street, Suite 1425 Dayton, OH 45402 Address: 1517 PRINCETON Pre-Sale Number: City: DAYTON Location: Inspector: Sue Pratt Phone Number: PRE SALE INSPECTION REPORT
More informationNYC Department of Education
Asset: P.S. 128 - MANHATTAN, 560 WEST 169 STREET, New York, 10032 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-07 8:50 AM 2018-06-14 1:16 PM Asset Data Are there fuel tanks?
More informationMaster Project List Report
Blue Hills Elementary School 01-8215 Site Utilities Replacement $52,835 01-8502 Modernization $3,135,933 01-8525 Exterior Painting $181,478 01-8552 Kindergarden Fencing $13,180 Install new backflow preventer.
More informationMechanical System Description
1. Building Description: Mechanical System Description The building is a Type-1B construction, 9-levels, non-high rise building with 67 affordable family housing units. The first level of the structure
More informationThe following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on
HOME PROPERTY SCAN INSPECTIONS The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on January 11, 2010 and
More informationELECTRICAL SYSTEMS ASSESSMENT Hanover High School
ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,
More informationSUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM
SUMMARY 1234 Main St.Severn 21144 Buyer Name 07/18/2018 9:00AM Henry Toman MD License 32391 1st American Home Inspection, LLC 443-685-4062 henrytoman61@gmail.com The summary is meant to organize the defects
More information