+ + CHECKFIRE MARINE ELECTRIC DETECTION AND CONTROL SYSTEM. CHECKFIRE Marine Electric Detection and Control System (Part No.

Size: px
Start display at page:

Download "+ + CHECKFIRE MARINE ELECTRIC DETECTION AND CONTROL SYSTEM. CHECKFIRE Marine Electric Detection and Control System (Part No."

Transcription

1 CHECKFIRE Marine Electric CHECKFIRE MARINE ELECTRIC DETECTION AND CONTROL SYSTEM NAME 2016-JAN-30 REV. 03 PAGE 1 Installation, Inspection, and Maintenance Manual One Stanton Street / Marinette, WI , USA / / Copyright 2016 Tyco Fire Products LP. / All rights reserved. / Part No

2

3 CHECKFIRE Marine Electric FOREWORD 2016-JAN-30 REV. 03 This manual is intended for use with the CHECKFIRE Marine Electric. Those who install, operate, inspect, or maintain this system should read this entire manual. Specific sections will be of par ticular interest depending upon one s responsibilities. As with all electrical equipment, the electric detection and control system needs periodic care to provide maximum assurance that it will operate effectively and safely. This ANSUL systems manual is limited to the uses herein described. For other applications, contact your local Authorized ANSUL Distributor, Domestic District Manager, International Area Manager, or Tyco Fire Protection Products Technical Services Department, Marinette, Wisconsin Note: The converted metric values in this manual are provided for dimensional reference only and do not reflect an actual measurement. Part Number: Date: 2016-JAN-30 LEXAN is a trademark of its respective owner. ANSUL, CHECKFIRE, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.

4 EXPLANATION OF SAFETY ALERTS REV JAN-30 CHECKFIRE Marine Electric p! DANGER Indicates a hazardous situation in which a person will experience serious personal injury or death if the situation is not avoided.! WARNING Indicates a hazardous situation in which a person could experience serious personal injury or death if the situation is not avoided.! CAUTION Indicates a hazardous situation in which a person could experience minor or moderate personal injury if the situation is not avoided. CAUTION Addresses practices not related to personal injury, such as a system part malfunctioning, property damage, or system failure. NOTICE Addresses general practices or observations related to system function that are not related to personal injury.

5 CHECKFIRE Marine Electric REVISION RECORD 2016-JAN-30 REV. 02 PAGE R-1 DATE PAGE REV. NO. DATE PAGE REV. NO SEP SEP SEP SEP SEP SEP SEP SEP SEP SEP DEC DEC DEC DEC JAN-30 2 New 2016-JAN JAN-30 4 New 2016-JAN JAN JAN-30 8 New 2016-JAN JAN New 2016-JAN JAN New 2016-JAN New 2016-JAN Legend for Manual Page Revision Indicators: Indicates revised information. Indicates no change to text change in page sequence only.

6 REVISION RECORD PAGE R-2 REV JAN-30 CHECKFIRE Marine Electric NOTES:

7 CHECKFIRE Marine Electric TABLE OF CONTENTS 2016-JAN-30 REV. 03 PAGE TOC-1 SECTION SAFETY PRECAUTIONS 1 PAGE SYSTEM APPLICATION AND DESCRIPTION 3 4 SYSTEM COMPONENTS 5 8 Control Module 5 Mounting Bracket 5 Vertical Rate Compensated Thermal Detector 5 End-of-Line Module 6 Battery 6 Remote High Level Alarm 6 Alarm Bell 6 or 10 Inch 6 Detection Circuit Test Module 7 Manual Fire Alarm Station 7 USER INTERFACE 9 12 Field Terminations 9 Front Panel Indicators 9 10 Power Connections 10 Front Panel Buttons 11 Battery Replacement 11 Enclosure 11 Cover Removal 11 Strain Relief Installation 11 Mounting 11 SECTION PAGE INSPECTION AND MAINTENANCE Daily Inspections 21 Detection Circuit Test 21 Maintenance 21 Detection Circuit Check 21 External Power Test 21 Yearly 21 Set-In Service 21 TROUBLESHOOTING Diagnostics 23 Troubleshooting Table 24 PROGRAMMING Manual Programming Switch 25 APPENDIX 27 Component Index 27 SYSTEM PLANNING Hazard Identification 13 Pre-installation Guidelines INSTALLATION Mounting Bracket Installation 15 Mounting the Control Module 15 Audible Alarm Installation Auxiliary Control Relay 17 Detection Wire Installation Wiring Manual Fire Alarm Station 18 Thermal Detector Installation 18 End-of-Line Module Installation 19 Detection Circuit Test Module 19 External Power Connection 19 Function Test 20 Placing the System into Service 20

8 TABLE OF CONTENTS PAGE TOC-2 REV JAN-30 CHECKFIRE Marine Electric NOTES:

9 CHECKFIRE Marine Electric SAFETY PRECAUTIONS 1998-SEP-01 REV. 0 PAGE 1 SAFETY PRECAUTIONS For the protection of personnel and equipment being installed, this manual contains WARNING and CAUTION statements which are listed in the steps which they apply. These warnings and cautions are also listed here so that the manual user can become familiar with them before performing any procedures.! WARNING In case of fire, evacuate area to lessen the risk of injury from flames, heat, hazardous vapors, explosions, or other hazards that may be created.! CAUTION Operation of the Test Module will simulate an alarm condition. The control relays will operate as if in a real alarm condition and any equipment connected to the Auxiliary Control Relay or Alarm Relay will be affected as it would in an actual alarm condition. Measures should be taken to ensure that this does not affect the safety of the vessel or the personnel on board.! CAUTION Contact your local waste management company for information concerning the correct disposal of lithium batteries.! CAUTION Discharged lithium batteries may contain significant amounts of unused energy and should be handled with care. Do not compact for disposal. Before disposal, each battery must be fully discharged and electrically isolated by enclosing in a plastic bag and sealing the bag. Do not dispose of in fire. Check applicable solid waste disposal regulations for proper disposal of more than one battery.

10 SAFETY PRECAUTIONS PAGE 2 REV JAN-30 CHECKFIRE Marine Electric NOTES:

11 CHECKFIRE Marine Electric SYSTEM APPLICATION AND DESCRIPTION 2016-JAN-30 REV. 02 PAGE 3 APPLICATION The CHECKFIRE Marine Electric Detection and Control System has been designed to be used in conjunction with an ANSUL fire suppression system requiring manual input as a means of actuation to meet the fire protection requirements of 46 CFR Subchapter T Small Passenger Vessels (Under 100 Gross Tons). Its unique low voltage low power operating system, designed to operate from a 12 or 24 VDC power input, makes the CHECKFIRE Marine detection system an ideal fire detection controller in applications where accessibility to standard 115 VAC power is either impractical or not available. The CHECKFIRE Marine system is primarily used for automatic fire detection in machinery spaces where an automatic fire detection system is required to accompany a manual fire suppression system; it may also be used for other shipboard hazard areas. Because of its rugged construction it is especially suited for protection of equipment that is subjected to extreme environmental and physical conditions. The CHECKFIRE Marine Electric is USCG approved under No /40/1. DESCRIPTION The complete CHECKFIRE Marine system is composed of components which are combined to provide automatic fire detection and control. Input Power The CHECKFIRE Marine control unit will accept an external 12 or 24 VDC regulated power source as its primary power. The control module uses an internal long life Lithium battery to provide a secondary supply in the event the external 12/24 VDC primary power source is interrupted. The internal battery has the capacity to perform all of the detection and control functions in the absence of primary power. Under quiescent load (system operating in a non-alarm condition), the secondary supply has the capacity to operate the system for a period of up to one year, and at the end of that period is capable of operating the system in a full alarm condition for 72 hours. Audible Alarms The control module provides an internal high pitch audible alarm that sounds whenever an alarm or trouble condition exists. Additionally, an alarm relay with a set of normally open/ normally closed (NO/NC) contacts is available for connection of an auxiliary high level alarm; and a trouble relay with a set of normally open contacts is available for remote trouble annunciation. Auxiliary Control Relay An auxiliary control relay with one set of 3 amp rated NO/ NC contacts is provided for auxiliary shutdown and control functions. This relay will transfer upon an alarm condition and is non-silenceable. Operator Interface Panel Operator interface is provided by a front panel mylar overlay containing four visual status LEDs, a silence switch and a reset switch. The status LEDs include: Green Power LED: Indicates a power normal condition when pulsing. Yellow Battery (Power) Fault LED: Pulses when an off normal condition exists with either the external or internal power source. Red Alarm LED: Pulses when an alarm condition is present. Yellow Detection Fault LED: Pulses when an off normal condition exists in either initiating circuit. The Silence and Reset switches allow silencing of the audible alarms and reset of the control panel respectively. The internal audible alarm is always silenceable, while the audible alarm relay is field selectable for either silenceable or non-silenceable operation. Operation of the reset switch will allow resetting of the control panel after alarm conditions have been cleared. Initiating Circuits The control module contains two supervised detection initiating input circuits that are designed to be connected to contact closure type thermal detectors. The initiating circuits are identical, and detection wiring can be connected to either one or both circuits. An environmentally sealed End-of-Line Module (Part No ) is used to terminate the detection circuit after the last detector in line. If only one detection circuit is used the unused circuit can be terminated inside the enclosure with a 4.7K ohm resistor that is provided with the control module. The initiating circuits are also designed to eliminate nuisance alarms associated with contact bounce in high vibration environments.

12 SYSTEM APPLICATION AND DESCRIPTION PAGE 4 REV JAN-30 CHECKFIRE Marine Electric NOTES:

13 CHECKFIRE Marine Electric SYSTEM COMPONENTS 1998-SEP-01 REV. 0 PAGE 5 CONTROL MODULE The Control Module is the basis of the CHECKFIRE Marine detection system. See Figure 1. The module cover and back box are made of durable Noryl SE1gfN3 material with a flammability rating of UL94 V-1. The back box contains the field interface terminal block, battery, and field wiring entrance ports. The cover assembly contains the control PC board assembly, sounder, operator interface panel, and environmental seal. The enclosure meets IEC 529 requirements for dust and water spray in all directions. Mounting feet allow mounting to any suitable flat surface. A steel mounting bracket is also available. All circuitry, relays, switches, and LED s are contained on a single PC board. A board mounted receptacle mates with the plug-in terminal block mounted in the back box. A high pitch sounder is threaded into the cover and plugged into the PC board. The PC board is encapsulated to provide added protection against moisture and dust. The PC board assembly contains a switch for optional manual programming functions. VERTICAL RATE COMPENSATED THERMAL DETECTOR The Vertical Rate Compensating Thermal Detectors are factory preset. They are normally open, mechanical contact closure switches designed to operate at the set temperature rating or when the surrounding air temperature increases in excess of 40 /min. The detectors have an electrical rating (resistive) of VAC, VDC, 2 24 VDC, and 1 48 VDC. See Figure 3. Temperature Setting and Color Coding Part No. F ( C) Color (60.0) Yellow (71.7) Yellow (87.8) White (107.2) White Electrical Wire Leads 6 in. (15 cm) 1/2-14 NPT Color-Coded Tip Temperature Stamping Figure FIGURE MOUNTING BRACKETS The CHECKFIRE Marine control module has four mounting feet for direct mounting to a suitable flat surface. An optional steel bracket is also available for mounting. The bracket (Part No ) is painted red and is fastened by either bolting or welding. See Figure 2. The outer shell is made of a rapidly expanding alloy which closely follows changes in surrounding air temperature. The inner struts are made of a lower expanding alloy. A slow rate fire will heat the shell and struts together. At the set point, the unit will trigger, sending a signal to the CHECKFIRE control module. If a fast rate fire starts, the shell will expand rapidly and the struts will close signaling the control module. See Figure 4. Braze Sealed End Adjusting Screws Low Expansion Struts Contact Points Electrical Insulation Expanding Outer Shell Braze Sealed Head Glass Beads Hermetic Seal Electrical Leads Figure Module Bracket Part No FIGURE

14 SYSTEM COMPONENTS PAGE 6 REV JAN-30 CHECKFIRE Marine Electric END-OF-LINE MODULE The End-of-Line Module Resistor Assembly (Part No ) includes the terminal block with 4.7K ohm resistor, strain relief, and EOL cap. The module is installed on the end of the detection wire after the last detector. See Figure 5. LOCK NUT EOL CAP 1/4 IN. 1 IN. TERMINAL BLOCK WITH 4.7K OHM RESISTOR STRAIN RELIEF CONNECTOR INSTALLED DETECTION WIRE Figure BATTERY The CHECKFIRE Marine Control Module uses one 3.6 VDC lithium battery (Part No ). All power required to run the detection system can be provided from this battery. The battery is supplied with two separate plug-in connectors. One connector is used for plugging into SC-N modules and the other connector is used for plugging into MP-N/ Marine modules. CAUTION: Do not cut off unused connector assembly. It must remain on battery module even though it is not used. Simply tuck the extra connector assembly along side the battery module when installing the cover. The battery must be replaced annually, after discharge, or when the YELLOW Battery LED and the Audio Alarm are pulsing. See Figure 6. FIGURE ALARM BELL 6 OR 10 INCH The ANSUL motor driven alarm bell is designed to meet the special requirements of fire alarm systems where low power consumption and high sound output is essential. The sound output level is 92 dba. Both 6 and 10 inch bells are 24 volt models. The current draw of the 24 volt model is.030 A. 6 in. Alarm Bell 10 in. Alarm Bell 24 VDC Part No Part No The basic mechanism, gong and accessories have a baked, red enamel finish. Holes are located to mount to a standard 4 in. (102 mm) square outlet box. Screw terminals permit fast in-out wiring of 16 AWG wire. The operating temperature rating for either bell is 31 F to 150 F (-35 C to 66 C). A weatherproof back box (Part No ) is available for outdoor use. See Figure 8. 6 INCH BELL 3 3/8 IN. (86 mm) 6 IN. (152 mm) 10 INCH BELL 10 IN. (254 mm) 3 3/8 IN. (86 mm) 3 3/8 IN. (86 mm) SC-N Connector (BLACK) MP-N Connector (WHITE) 2 3/4 IN. (70 mm) 2 3/4 IN. (70 mm) 3 3/8 IN. (86 mm) NOTE: Do not cut off unused wire assembly WBB Weatherproof Back BoX 4.20 IN. ( mm) IN. (50.8 mm) FIGURE IN. ( mm) REMOTE HIGH LEVEL ALARM The remote high level alarm (Part No ) is intended for those installations where the noise level or operating conditions may prevent the operator from recognizing the control module alarm condition. This device is connected through the auxiliary alarm relay of the control module to a separately fused power source. It is capable of 102 decibels at 6 to 30 volts, 0.3 amp maximum at a temperature range of 40 F to 170 F ( 40 C to 76.7 C). See Figure Figure 8

15 CHECKFIRE Marine Electric SYSTEM COMPONENTS 2016-JAN-30 REV. 02 PAGE 7 DETECTION CIRCUIT TEST MODULE The Detection Circuit Test Module (Part No ) meets the USCG requirements to provide a simple and convenient means at the control module to individually test each fire detecting circuit by simulating an alarm and trouble condition. The test module is housed in a polycarbonate enclosure that conforms to IEC/EN60947 with protection to IP66. The enclosure contains knockouts on four sides for field wiring. The module contains two 3-position momentary contact selector switches for manually simulating a trouble and an alarm condition in each of the two detection circuits. One switch is designated Alarm Test 1 & 2, and the other switch is designated Trouble Test 1 & 2. See Figure 9. MANUAL FIRE ALARM STATION The non-coded, dual action Manual Fire Alarm Station (Part No ) provides a convenient means to manually initiate a fire alarm. Pulling the handle down causes it to latch in the down position and to close the normally-open switch. The handle is restored manually by unscrewing the allen-head screw so the top of the case can pivot forward, allowing the spring-loaded handle to return to its normal position. The case can then be pivoted back to its normal position and secured with the allen-head screw. The shell, door and handle are molded of red colored LEXAN material (or polycarbonate equivalent) with a textured finish and white lettering. The back plate is 16 gauge steel. Switch contacts are normally open. A weatherproof surface back box (model WP-10) should be used for installation. See Figure in. (80 mm) 4 1/8 IN. (104 mm) TOP 1 3/8 IN. (35 mm) 1 3/8 IN. (35 mm) SIDE VIEW SURFACE BACK BOX 4.73 in. (120 mm) 2.21 in. (56 mm) 5 1/2 IN. (139 mm) FIGURE FIGURE

16 SYSTEM COMPONENTS PAGE 8 REV JAN-30 CHECKFIRE Marine Electric NOTES:

17 CHECKFIRE Marine Electric USER INTERFACE 2007-DEC-01 REV. 01 PAGE 9 USER INTERFACE This section is designed to give the user overall information on all features and components pertaining to the CHECKFIRE Marine Control Module itself. FIELD TERMINATIONS External Power Circuit (Terminals No. 1 and No. 2) 12 to 24 VDC Polarity must be considered Terminal No. 1 (+), Terminal No. 2 ( ) 5 amp inline fuse must be used in the positive side Cable should be round jacketed, with an O.D. of 0.13 in. to 0.25 in., suitable for the intended usage Detection Circuit #1 (Terminal No. 3 and No. 4) Cable from splicing device should be round jacketed, with an O.D. of 0.13 in. to 0.25 in., suitable for the intended usage Polarity need not be considered Detection Circuit #2 (Terminals No. 5 and No. 6) Cable from splicing device should be round jacketed, with an O.D. of 0.13 in. to 0.25 in., suitable for the intended usage Polarity need not be considered Circuit Terminals No. 7 and No. 8 Not Used (10 ohm resistor required across these terminals) Trouble Relay Circuit (Terminals No. 9 and No. 10) Cable should be round jacketed, with an O.D. of 0.13 in. to 0.25 in., suitable for the intended usage 3 amp maximum load Contacts are normally open in the powered, non-trouble condition. Contacts close upon trouble Relay specification: 4A 250VAC, 3A 30VDC resistive Auxiliary Alarm Relay Circuit (Terminals No. 11, No. 12, and No. 13) Cable should be round jacketed, with an O.D. of 0.13 in. to 0.25 in., suitable for the intended usage 3 amp maximum load Relay specification: 4A 250VAC, 3A 30VDC resistive Normally open, normally closed set of contacts Form C contact arrangement Contacts shown in non-alarm condition No. 11 (N.O.), No. 12 (Common), No. 13 (N.C.) Auxiliary Control Relay Circuit (Terminals No. 14, No. 15, and No. 16) Cable should be round jacketed, with an O.D. of 0.13 in. to 0.25 in., suitable for the intended usage 3 amp maximum load Relay specification: 4A 250VAC, 3A 30VDC resistive Normally open, normally closed set of contacts Form C contact arrangement Contacts shown in normal condition No. 14 (N.O.), No. 15 (Common), No. 16 (N.C.) Terminal Block Terminal connections are sized for AWG Terminal is labeled from left to right, No. 1 through No. 16 The terminals are designed as follows: 1. + Ext. 12/24 VDC Battery 2. Ext. 12/24 VDC Battery 3. + Detection CKT 1 4. Detection CKT Detection CKT 2 6. Detection CKT 2 7. Not Used 8. Not Used 9. Trouble Common 10. Trouble N.O. 11. Alarm N.O. 12. Alarm Common 13. Alarm N.C. 14. Auxiliary Relay N.O. 15. Auxiliary Relay Common 16. Auxiliary Relay N.C. FRONT PANEL INDICATORS (See Figure 11) Power Normal (Green) LED pulses once every 3 seconds when indicating normal power The green Power Normal LED pulses on once every 3 seconds indicating power is normal from both sources of input power. If the power drops below an acceptable level from either the internal or external source of input power, the green Power LED will be extinguished. If only one source of power is used, the green Power LED will extinguish when the voltage level drops below an acceptable level. Battery Trouble (Yellow) LED pulses once every 10 seconds when indicating battery trouble The yellow battery trouble LED will pulse when a low power condition is detected in either of the connected supplies (internal or external). If only one power source is used, the control module will automatically ignore the unconnected circuit upon resetting the control module. If a power source is once connected and recognized, a subsequent loss of that power source will be recognized as a Battery Trouble condition. If a power source is once connected, recognized, and then disconnected, the disconnected supply can be ignored by operating the RESET button. Alarm (Red) The Alarm LED will flash if an alarm condition exists. An alarm condition is caused by operation of a detection circuit. The alarm condition will continue until the source of the alarm is removed and the control module is reset.

18 USER INTERFACE PAGE 10 REV JAN-30 CHECKFIRE Marine Electric FRONT PANEL INDICATORS (Continued) DETECTION CIRCUIT ACTIVATION MODE Upon receiving an input signal from a thermal detector, the following functions will be performed automatically: 1. The Alarm LED will flash, the internal sounder will pulse, the alarm relay will transfer resulting in remote alarm operation if connected, and the auxiliary control relay will transfer to operate auxiliary functions if connected. 2. If the silence button is operated during an alarm condition the internal sounder is silenced and, if programmed to do so, the auxiliary alarm relay is also silenced. 3. Operating the Reset button returns the control panel to a fire ready monitoring state providing all alarm and trouble conditions have cleared. Detection Trouble (Yellow) The Yellow Detection Trouble LED and the audio pulse once every 10 seconds when the control module detects a trouble in the detection circuit. The control module will automatically return to normal when the trouble is cleared. Sounder (Audio) The sounder gives a pulsing audio indication for all alarm and trouble outputs. When an alarm condition is initiated, the sounder will pulse at a rate of approximately 2 pulses per second (slow pulse). If the alarm condition is allowed to continue (not removed or reset) for more than 30 seconds, the pulse rate will increase to approximately 4 pulses per second (fast pulse). The sounder gives the audio indications of the various outputs. The sounder is rated at 85 dba at 10 ft (3 m). The pulse rates are as follows: Alarm Slow pulse 2 pulses per second Fast pulse 4 pulses per second Trouble 1 pulse per 10 seconds POWER CONNECTIONS Internal The 3.6 VDC internal lithium battery is connected to the control module by a removable type plug. The battery must be replaced annually. A label is attached near the battery mounting location for recording the installation date.! CAUTION Discharged lithium batteries may contain significant amounts of unused energy and should be handled with care. Do not compact for disposal. Before disposal, each battery must be fully discharged and electrically isolated by enclosing in a plastic bag and sealing the bag. Do not dispose of in fire. Check applicable solid waste disposal regulations for proper disposal of more than one battery. External The external power circuit can be between 12 to 24 VDC. The circuit must be fused at the source on the positive line. The external power source is connected to the module terminal block on terminals No. 1 and No. 2. Both power sources, internal and external, must be utilized. This will always give the fire suppression system a battery back-up when one of the sources are removed for whatever reason. Sounder Yellow Red Yellow Battery Alarm Detection Power Green FIGURE

19 CHECKFIRE Marine Electric USER INTERFACE 2006-SEP-01 REV. 01 PAGE 11 FRONT PANEL BUTTONS (See Figure 12) Silence Pressing the SILENCE button will silence the internal sounder. Pressing the SILENCE button will also silence the alarm relay if the alarm relay has been programmed to silence. The alarm relay silence function is inhibited (locked out) for one minute after an alarm condition is initiated. If an alarm condition is initiated, the operator must wait one minute before silencing. Resetting the panel with an alarm source still present will reinitiate the one minute silence lockout timer. Reset The RESET button is used to re-initialize the control panel. When depressed, it provides an indication that all LEDs and the sounder are functional. It is used to upload the manual programming into the control module. If trouble(s) has not been cleared, the trouble indication will reappear after the RESET button is pressed. When the RESET button is pressed, three short audio and visual indications will acknowledge the switch has been depressed properly. BATTERY REPLACEMENT While in use, the battery requires replacement every year. The shelf life of the battery is 8 years. Control Module contains a label for recording battery replacement date. Make certain used battery is disposed of properly. ENCLOSURE The enclosure is watertight. It meets the requirements of Standard IEC 529, Degrees of Protection Provided by Enclosures for an IP 66 rating. COVER REMOVAL The cover is attached with 4, captive, slotted screws. When removing and installing cover, make certain seal is always correctly in place and not twisted. Seal should always be kept clean. A small amount of silicone lubricant will improve the seals effectiveness. STRAIN RELIEF INSTALLATION Always use Dow Corning 737 RTV Sealant or equal on all strain relief and plug male threads. MOUNTING Control Module can be mounted without a bracket. It has molded-in mounting tabs on the back box. Control Module can be mounted on a bracket, Part No The Control Module should never be mounted in an area which is subject to pressure washing or stream cleaning. Silence Button Silence Reset Reset Button Figure

20 USER INTERFACE PAGE 12 REV JAN-30 CHECKFIRE Marine Electric NOTES:

21 CHECKFIRE Marine Electric SYSTEM PLANNING 2006-SEP-01 REV. 01 PAGE 13 HAZARD IDENTIFICATION Before the CHECKFIRE Marine Electric Detection and Control System is installed, the hazards to be protected must be identified. These hazard locations determine where the detection wire or thermal detectors and the fire suppression system nozzles are required. While the agent nozzles in existing fire suppression systems will point out the hazard areas, the following information should still be reviewed to best determine detection requirements. If an entire fire suppression/ detection system is to be installed, this information is vital in determining proper placement of discharge nozzles and detection devices. Fire Hazard Definition A fire hazard is any area where an ignition source (high temperature or sparks) and fuel (flammable materials) may be found in close proximity. Examples of ignition sources are engines, exhaust piping, turbochargers, battery compartments, electrical system equipment, torque converters, transmissions, hydraulic pumps, and friction from debris packed around parts. Occasionally other components may reach high temperatures due to malfunction. The potential danger from these components must also be examined during hazard identification. Temperatures in excess of the thermal detector ratings will cause the detection system to activate thereby actuating the alarm system. The above mentioned heat sources can cause fire when they come in contact with flammable materials such as leaking fuel: either broken fuel lines, slow leaks, broken hydraulic lines, or a ruptured fuel tank. Type of Class A materials are part of the vessel itself such as electric wiring insulation, padding, plastic parts, the packages on the vessel, or debris due to poor maintenance. These materials can contribute to the rapid buildup or spreading of fire. Other Considerations Be aware that the propagation of fire from one area to another may cause a hazard to be larger than originally determined. Liquid fuel may spray, splash, or flow carrying the fire some distance from the starting point. Radiation, sparks, or conduction through metal can carry heat to an area where the danger of fire wouldn t normally exist. Also, consider the fire history of the equipment being protected or of similar equipment. Each hazard that is identified should have both fire suppression system fixed nozzles and thermal detectors. Equipment Shutdown Another factor to examine is equipment shutdown. Provisions should be made to shut down any components that could possibly add to the intensity of the fire (fuel pumps, hydraulic pumps, engine, etc.) or any components that could possibly re-ignite the fire once it has been suppressed (battery, electrical system). Although a properly installed fire suppression/detection system is the primary means of protecting equipment from fire, an effective fire protection package also includes provisions for equipment shutdown. The CHECKFIRE Marine control module contains 3 amp 30VDC auxiliary control relay contacts to facilitate connection of shutdown devices. Alarm Application Some areas on a vessel tend to be very noisy. In such cases, a high decibel alarm or bell is available to signal that the control module has received a detection signal. PRE-INSTALLATION GUIDELINES Before actually installing the CHECKFIRE Marine Electric, review all of the following information and plan (sketch) the system layout. This will help to avoid any unforeseen installation problems. Once an acceptable layout has been determined, record and keep it for future reference. Control Module and Actuator Location 1. The control system can be surface mounted. The preferable location is in a clean, dry area with minimum shock and vibration. The control system should be completely visible and accessible for maintenance. Avoid confined areas such as storage closets. If the panel is installed in such an area, personnel will not be aware of a trouble condition, should one develop. 2. The location must be suitable for bolting or welding if bolting is impractical. The mounting surface must be flat to avoid strain on the mounting bracket. 3. There must be room enough to allow for proper wiring connection to the control module. Also, the module should be accessible for periodic inspection and maintenance. The components should be mounted in a location that will not interfere with normal equipment maintenance. NOTICE The ambient temperature in the mounting environment must not fall below 40 F ( 40 C) nor exceed 140 F (60 C). General Wiring The installation of wiring and equipment shall be in accordance with Article 760, Fire Protective Systems, of the National Electric Code (NFPA 70) and with Subchapter J of Title 46 of the Code of Federal Regulations (46 CFR ). Wiring must be marine wiring in accordance with 46 CFR 111. Unless otherwise specified by the authority having jurisdiction, local codes, or on the wiring diagrams supplied for the specific installation, No. 18 AWG, color coded wire is recommended for the detector circuits. Use No. 16 AWG wire for the alarm signaling circuits. Use No. 14 AWG wire for power circuits. All wiring should be multi-conductor jacketed cable with an outer jacket OD of.13 to.25 in. to maintain the watertight integrity of the strain relief at the control module.

22 SYSTEM PLANNING PAGE 14 REV SEP-01 CHECKFIRE Marine Electric Pre-Installation Guidelines (Continued) Thermal Detector Selection Placement Thermal detectors are selected by temperature range relative to the hazard temperature. The table below indicates the thermal detector rated operating temperature and part number. Operating Temperature Detector F ( C) Part No. 140 (60) (71) (88) (107) The placement and selection of thermal detectors should be based on the following requirements: 1. For overheads up to 15 ft (4.6 m), a spacing of 15 ft (4.6 m) between detectors is utilized. 2. Locations with overhead heights greater than 15 ft (4.6 m) require reduced spacing. Contact ANSUL Applications Engineering for assistance in locating detectors in high overhead applications. 3. A minimum setting of 100 F (37.7 C) above ambient temperature is recommended. Detection Circuit Test Switch Module Mount module in a location adjacent to control module which is not subject to damage.

23 CHECKFIRE Marine Electric INSTALLATION 1998-SEP-01 REV. 0 PAGE 15 MOUNTING BRACKET INSTALLATION Bolting 1. Using the bracket as a template, carefully mark the location of the bracket mounting holes. 2. Center punch the premarked hole locations and drill 3/8 in. (10 mm) holes through the mounting surface. 3. Secure the bracket to the mounting surface using appropriate length of 5/16 in. (8 mm) bolts with flat washers, lockwashers, and nuts. See Figure 13. MOUNTING THE CONTROL MODULE The CHECKFIRE Marine Control Module can be mounted to either a flat, rigid surface or the optional bracket. If mounting the control module to a flat, rigid surface, use the appropriate fasteners. See Figure IN. (107 mm) 2.54 IN. (64.5 mm) 7.68 IN. (195 mm) 7.05 IN. (179 mm) Nut Lockwasher Welding Flatwasher Module Bracket, Part No NOTICE Never weld on the vessel without first consulting the owner. Bolt FIGURE Carefully mark the location of the bracket. 2. Clean the mounting bracket and mounting surface using a wire brush until clean steel surfaces are available for welding. 3. Secure the bracket to the mounting surface using 1/8 in. (3 mm) fillet welds at the top, bottom, and both sides. See Figure Remove all weld spatter from the bracket and mounting surface. 5. Prime and paint the exposed bare metal of the bracket and mounting surface. Weld 3 IN. (76 mm) Figure If mounting the control module to the bracket, complete the following: With the bracket securely mounted, position the holes in the control module mounting flanges over the holes on the bracket. Using the supplied mounting hardware, securely fasten the control module to the bracket with four flat washers, lockwashers and screws. Remove the cover from the control module. If the internal 3.6 VDC battery is in place, disconnect the wire plug until the field wiring is complete. If the strain relief(s) and plug(s) are not in place, coat the male threads with Dow Corning 737 RTV Sealant or equal and install in holes of module back box. At this point, the external field wiring can be installed. AUDIBLE ALARM INSTALLATION A high pitch audible sounding device is an integral part of the control module for the CHECKFIRE Marine detection and control system. However, for applications where high background noise is prevalent it may be necessary to install a remote high level alarm or bell. A silenceable auxiliary alarm relay is provided in the control module for this purpose. The specifications for the alarm relay are described under the User Interface section of this manual. Note: Use 0.13 to 0.25 in. diameter round jacketed cable to maintain water tight integrity of control module strain reliefs. Weld Module Bracket, Part No FIGURE

24 INSTALLATION CHECKFIRE Marine Electric AUDIBLE ALARM INSTALLATION (Continued) Remote High Level Alarm 1. Using the alarm as a template, carefully mark the location of the mounting holes. Use either the bottom or rear set of mounting holes depending on the mounting location. Secure the alarm using appropriate length of 5/16 in. bolts with lock washers and nuts. See Figure 16. Alarm Bell 6 or 10 Inch 1. The alarm bell is a 24 VDC device. Use the application design to select the correct version. See Figure INCH BELL 6 IN. (152 mm) 10 INCH BELL 10 IN. (254 mm) 3 3/8 IN. (86 mm) 3 3/8 IN. (86 mm) 3 3/8 IN. (86 mm) 2 3/4 IN. (70 mm) 2 3/4 IN. (70 mm) 3 3/8 IN. (86 mm) VDC Part No VDC Part No Figure Wire the alarm to the control module in accordance with the diagram in Figure 19 using 20 AWG wire. On the terminal block at the control module, install the wires to Terminals 11 (NO) and 12 (C). FIGURE Wire the alarm to the control module in accordance with the diagram in Figure 17 using 20 AWG wire. Make certain the jumper is installed between the HI and LO terminals on the alarm terminal block. Certain alarm models may have only one positive terminal in which case a jumper is not used. The ends of stranded wire must be tinned with 60/40 rosin core solder, using a low wattage soldering pencil, before installation. On the terminal block at the control module, install the wires to Terminals 11 (NO) and 12 (C). Alarm Relay NO C NC Jacketed Cable Fused Lead on Non-Chassis side (Fuse at Load X 1.25, not to exceed 3 amps) Alarm Bell Terminal Block Vessel Power Source 12/24 VDC Chassis Ground* Alarm Relay NO C NC Jacketed Cable Fused Lead on Non-Chassis Side (Fuse at Load X 1.25, Not to Exceed 3 Amps) Alarm Terminal Block Vessel Power Source Chassis Ground* * Grounding to be in accordance with 46 CFR Subchapter J Parts Figure The alarm bell is mounted to a back box that is part of the CHECKFIRE Marine system wiring. Remove bell to attach alarm base to the back box. Replace bell when alarm base is secure. Three options are available for mounting as shown in Figure 20. Semi-Flush Surface Outdoor Leave Jumper in Place (When Equipped) * Grounding to be in accordance with 46 CFR Subchapter J Parts FIGURE Figure 20

25 CHECKFIRE Marine Electric INSTALLATION 2006-SEP-01 REV. 01 PAGE 17 Auxiliary Control Relay 1. Install the auxiliary device in accordance with manufacturer s instructions. The device must not exceed the relay contract rating of 3 30VDC resistive. 2. Terminals 14 (NO), 15 (C), and 16 (NC), are the auxiliary relay terminals on the control module. Figure 21 illustrates a typical wiring diagram for a normally closed circuit. Figure 22 shows a typical normally open circuit. Note: Use 0.13 to 0.25 in. diameter round jacketed cable to maintain water tight integrity. Auxiliary Control Relay NO C NC Fused Lead on Non-Chassis Side (Fuse at Load X 1.25, Not to Exceed 3 Amps) DETECTION WIRE INSTALLATION! CAUTION When screw-type terminals are not provided for wiring connections, the use of insulated screw-type, or crimp-type wire nuts is recommended. Soldering will transfer its high heat to the device and possible damage to the device could occur. Use heat resistant wire nuts on thermal (heat) detector connections. Run all circuit wiring as shown in Figure 23 and 24. All detection circuit wires are continuously supervised through an end-of-line resistor. In order to keep supervision complete, parallel branching is not allowed. Every detector must have one set of incoming and one set of outgoing wires. Use only Approved initiating devices. See System Components Section in this manual. Jacketed Cable Auxiliary Device (By Others) Vessel Power Source 12/24 VDC Chassis Ground* Circuit Tester * Grounding to be in accordance with 46 CFR Subchapter J Parts FIGURE Circuit Tester Auxiliary Control Relay NO C NC Fused Lead on Non-Chassis Side (Fuse at Load X 1.25, Not to Exceed 3 Amps) Figure Jacketed Cable Auxiliary Device (By Others) Vessel Power Source 12/24 VDC EOL Module Manual FIRE ALARM Station Circuit Tester Chassis Ground* * Grounding to be in accordance with 46 CFR Subchapter J Parts FIGURE Thermal Detector Control Module Terminals Figure

26 INSTALLATION PAGE 18 REV SEP-01 CHECKFIRE Marine Electric DETECTION WIRE INSTALLATION (Continued) Route detector wiring through the strain reliefs provided in the control module. Connect the detector wiring to either detection circuit 1 (terminals 3 and 4) or detection circuit 2 (terminals 5 and 6). Allow one cable per strain relief. If only one detection circuit is connected the unused detection circuit must be terminated with a 4.7K ohm resistor. See Figure 25. It is not necessary to be concerned with polarity when installing the detector wiring. Detection Circuit Detection Circuit k 1/4 w THERMAL DETECTOR INSTALLATION The detectors may be mounted to any approved junction box with 7/8 in. (22 mm) diameter opening by using 1/2 14 NPT mounting nuts. Four lead wires are provided to facilitate supervision of system wiring. On units up to 375 F (190.5 C) No. 18 AWG Teflon insulated wire is supplied. For overhead height up to 15 ft (4.6 m), a spacing of 15 ft (4.6 m) between detectors is utilized. Locations with overhead heights greater than 15 ft (4.6 m) require reduced spacing. Contact Ansul Applications Engineering for assistance in locating detectors in high overhead applications. A minimum setting of 100 F (37.7 C) above ambient temperatures is recommended. See Figure 27. Maximum Torque Tolerance: Without thread lubricant...20 Ft. lbs. With Teflon tape lubricant...3 Ft. lbs. 4 IN. Octagonal Outlet Box 4 IN. Round Box Cover Figure Install EOL module, Part No , to end of detection wire. WIRING MANUAL FIRE ALARM STATION The fire alarm station has one set of incoming and one set of outgoing wires. Terminal block screws allow quick installation of detection wiring. See Figure 26. 1/2 14 NPT REtainer Nuts 7/8 IN. (22 mm) Diameter Hole 1/2 14 NPT Detector Figure TO CONTROL MODULE TO NEXT DETECTOR OR EOL MODULE Figure

27 CHECKFIRE Marine Electric INSTALLATION 2007-DEC-01 REV. 02 PAGE 19 END-OF-LINE MODULE INSTALLATION CHECKFIRE Marine Detection circuits require an End-of-Line Module Resistor Assembly, Part No , to be installed on the end of the detection wire after the last detector. To properly attach the EOL Resistor assembly, complete the following steps: See Figure Strip 1 in. of outer jacket off the detection wire. 2. Strip 1/4 in. of insulation off the two internal wires. 3. Loosen the lock nut on the strain relief connector and slide both lock nut and connector over end of wire. 4. Loosen screws on terminal block, insert bare wires, and securely tighten screws. 5. Apply a small amount of Dow Corning 737 Sealant or equal on male threads of strain relief connector. 6. Screw EOL cap to strain relief connector. 7. Tighten lock nut onto detection wire. The Detection Circuit Test Module enclosure contains knockouts on four sides for field wiring. The detection circuit wiring from the control module is first routed and connected to the Detection Circuit Test Module where connections are made on the test switch contact blocks. Field wiring to detectors is continued from the switch contact blocks. See Figure 30. Top of Module NO NO NC NC + TO TERMINAL 3 Detection TO TERMINAL 4} CKT 1 + TO TERMINAL 5 Detection TO TERMINAL 6} CKT 2 1/4 IN. 1 IN. STRAIN RELIEF CONNECTOR LOCK NUT INSTALLED DETECTION WIRE To First Detector CKT 1 To First Detector CKT 2 Figure EOL CAP TERMINAL BLOCK WITH 4.7 K OHM RESISTOR Figure DETECTION CIRCUIT TEST MODULE The Detection Circuit Test Module uses four mounting holes for mounting to a suitable surface. The holes will accept up to a #8 machine screw with a maximum head diameter of See Figure 29 for hole pattern. EXTERNAL POWER CONNECTION The external power is wired into the control module terminal strip on Terminals No. 1 (+) and 2 ( ). See Figure 31. External power must be fused with a 5 amp fuse at the power source on the positive (+) side of the circuit. External 12/24 VDC Circuit Terminals 1 (+) and 2 ( ) in. (106.5 mm) 2.62 in. (66.5 mm) Figure To vehicle Battery (5 Amp Fused AT Source) Figure After all wiring has been properly installed, press the RESET button on the control module. This will set the module to normal. Note: Reset will be acknowledged by controller with short pulses from sounder. After all wiring is properly installed, make certain terminal strip is securely in place in control module. All incoming wires should be secured as they enter the terminal strip and then should be secured to a rigid support on the vessel within 12 in. (305 mm) of the control module. Finally check monitoring of external power by disconnecting the fuse and checking to see that a power trouble is present. Replace the fuse and check to see that the panel returns to normal.

28 INSTALLATION PAGE 20 REV DEC-01 CHECKFIRE Marine Electric FUNCTION TEST The following tests will verify that the system will operate upon receiving an electrical signal from a detection device (simulated fire condition). If the system is connected to available equipment the test should verify that the auxiliary device functions properly. If noted results are not attained, refer to the Troubleshooting Section of this manual for corrective action. Use Extender Test Cable, Part No , and battery extender cable, Part No , to conduct functional test. The Extender Test Cables allow separation of the cover from the enclosure while maintaining circuit integrity. See Figure 32. Extender BATTERY Cable Extender Test Cable Figure Detection Circuit Functional Test 1. Using a short length of insulated wire stripped at both ends, hold one end of the wire to Terminal 3 and hold the other end to Terminal 4. See Figure 33. Detection Circuit NO. 1 Terminals 3 and Jumper The following will take place while the jumper wire is being held on the terminals: The RED Alarm LED and sounder will pulse at a rate of two times per second for 30 seconds, then increase to four times per second The alarm relay will activate (non-latching) After verifying the above, remove the jumper wire and reset the module. The controller should return to Normal. Normal is when only the GREEN Power LED is pulsing and no other LEDs or the Audio Alarm are operating. Also, the alarm relay will return to normal. Repeat this test for detection circuit 2 by jumpering terminals 5 and If the unit has been programmed to silence the Alarm Relay, repeat test 1 for detection circuit 1 and 2 and test silence function for Alarm Relay. A silence lockout timer will prevent silencing the Alarm Relay for one minute after initiating an alarm. 3. Repeat test 1 for detection circuits 1 and 2 to test Auxiliary Control Relay function. The Auxiliary Control Relay is non-silenceable. PLACING THE SYSTEM INTO SERVICE After all testing has been successfully completed, the system may be placed in service. To place in service, press the reset button. The controller should return to a Normal condition with no alarms or troubles present and the only LED pulsing will be the green LED. Otherwise consult Troubleshooting Section. Detection Circuit Wiring Figure

29 CHECKFIRE Marine Electric INSPECTION AND MAINTENANCE 1998-SEP-01 REV. 0 PAGE 21 To ensure the CHECKFIRE Marine Electric Detection and Actuation System will operate as intended, proper inspection and maintenance procedures must be performed at the specified intervals. DAILY INSPECTIONS The vessel operator must check the system daily by visually verifying that the GREEN power LED is flashing and no other LED is illuminated. Also, no audio alarm should be sounding. If any other conditions exist, contact the local authorized Ansul distributor or whoever has been trained and authorized by Ansul to perform inspection and maintenance checks. DETECTION CIRCUIT TEST The detection circuitry of the control unit can be tested on a daily basis by operating the Detection Circuit Test Module. Prior to testing, all shipboard personnel should be given notice that a test is to take place. The Detection Circuit Test Module tests only the functional integrity of the control module. Periodic tests of the detectors are also required in accordance with the U.S. Coast Guard, National, State, and Local codes and/or the Authority Having Jurisdiction.! CAUTION Operation of the Test Module will simulate an alarm condition. The control relays will operate as if in a real alarm condition and any equipment connected to the Auxiliary Control Relay or Alarm Relay will be affected as it would in an actual alarm condition. Measures should be taken to ensure that this does not affect the safety of the vessel or the personnel on board. To conduct an alarm test for detection circuit No. 1 move the Alarm Test lever to the left, then release lever once the alarms have sounded. Reset the control panel when satisfactory operation of the system has been confirmed. To test detection circuit No. 2 repeat the test by moving the Alarm Test lever to the right. Reset the control panel after successful operation of the system has been confirmed. To conduct a detection circuit trouble test on detection circuit No. 1 move the Trouble Test lever to the left, then release lever after confirming that a detection trouble appears on the control module. Once the lever is released, the control unit should return to normal. Repeat the test for detection circuit No. 2 by moving the lever to the right. MAINTENANCE To give maximum assurance that the system will operate as intended, maintenance must be performed at six-month intervals or sooner depending on the operating environment or maintenance schedule. Maintenance should be performed by an authorized Ansul distributor or whoever has been trained and authorized by Ansul to perform maintenance checks. Visually check components and wiring for wear and damage. DETECTION CIRCUIT CHECK Each detector should be activated one at a time to ensure proper operation. The alarm LED should be checked to ensure proper operation. The control system must be reset after each detector is operated. Verify that the alarm relay (check audibles) operates as well as the auxiliary control relay. EXTERNAL POWER TEST To ensure presence of external power measure the voltage at terminals 1 and 2 for the presence of 12/24 VDC. Check monitoring of external power by removing the fuse and checking to see that a power trouble condition is indicated. YEARLY Remove control module cover screws and replace internal 3.6 VDC lithium battery, Part No Record date of new battery installation on label located near battery. Reinstall control module cover and depress RESET button.! CAUTION Contact your local waste management company for information concerning the correct disposal of lithium batteries. SET-IN SERVICE Reconnect any circuits which may have been disconnected to enable system check out. Reset system to normal supervisory condition.

CHECKFIRE 210 Detection and Actuation System

CHECKFIRE 210 Detection and Actuation System DATA SHEET CHECKFIRE 210 Detection and Actuation System Features Supervised power, detection, release, and communication circuits Display module with LED system status indicators Adjustable mounting bracket

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM

CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM CHECKFIRE 110 DETECTION AND ACTUATION SYSTEM PLANNING, INSTALLATION, Operation, and Maintenance Manual One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 / www.ansul.com Copyright 2014

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE ANSUL INSTALLATION OPERATION AND MAINTENANCE MANUAL ANSUL AUTOMAN II-C RELEASING DEVICE 001799 This manual is intended for use with the ANSUL AUTOMAN II-C Releasing Device. Those who install, inspect,

More information

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

SS90 SERIES CONTROLS MODEL C INSTALLATION MANUAL S S S SS O L I D S S90 TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U L 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. "SS90" SERIES CONTROLS MADE IN THE U.S.A. MODEL

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating

More information

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE SAFE A N D SECURE Cornell 100 Elmwood Ave. Crestwood Industrial Park Mountaintop, PA 18707 Tel 800.233.8366 Fax 800.526.0841 Email: cornell@cornelliron.com O W N E R S M A N U A L M O D E L F I R E G A

More information

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual 001799 This manual is intended for use with the ANSUL AUTOMAN Il-C Explosion-Proof Releasing Device.

More information

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices DAF DETECT-A-FIRE DAF DETECT-A-FIRE Detection and Release Devices FEATURES Repeatable - resets itself, nothing to replace, testable Rugged - withstands shock and vibration Versatile - offers various temperature

More information

Installation Requirements for Models:

Installation Requirements for Models: 900 & 9100 Series Refrigerators Installation Requirements for Models: 9162 9163 9182 9183 962 963 982 983 WARNING Improper installation, adjustment, alteration, service, or maintenance can cause injury

More information

MODELS 304GC, 304GCX, 314GC, and 314GCX

MODELS 304GC, 304GCX, 314GC, and 314GCX 2562109A REV. A1 0317 Printed in U.S.A. MODELS 304GC, 304GCX, 314GC, and 314GCX INSTALLATION AND SERVICE INSTRUCTIONS FOR SELECTONE Limited Warranty This product is subject to and covered by a limited

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS INDEECO Circulation Heaters are designed to provide years of trouble free operation if properly installed and maintained. Please read and follow these instructions for installing and maintaining the heater.

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone: Cookson Company 1901 South Litchfield Road Goodyear, AZ 85338 Phone: 800-294-4358 www.cooksondoor.com O W N E R S M A N U A L MODEL FIREFLY III EXTENDED PERFORMANCE RELEASE DEVICE TABLE OF CONTENTS INTRODUCTION

More information

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION: RELEASE DEVICES MADE IN THE U.S.A. RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: The "WPS" World Power Series, Time Delay Release

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Basic Vehicle Fire Protection Manual

Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual TABLE OF CONTENTS Introduction... 3 System Operation...... 5 Component Overview.... 7 Operator Controls Control Panel.........

More information

MODELS ASHP, ASHH, ASUP, and ASUH

MODELS ASHP, ASHH, ASUP, and ASUH 2562229A REV. A 1210 Printed in U.S.A. MODELS ASHP, ASHH, ASUP, and ASUH INSTALLATION AND SERVICE INSTRUCTIONS blank page INSTALLATION AND SERVICE INSTRUCTIONS FOR MODELS ASHP, ASHH, ASUP, AND ASUH SAFETY

More information

Check It Panel. 1 Phase Simplex Demand Dose Operation, Maintenance & Installation Manual. Introduction. Safety Guidelines

Check It Panel. 1 Phase Simplex Demand Dose Operation, Maintenance & Installation Manual. Introduction. Safety Guidelines Introduction Before proceeding with the installation or operation of the control panel read all instructions thoroughly, as well as comply with all Federal, State and Local Codes, Regulations and Practices.

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

SAFETY INFORMATION AND WARNINGS

SAFETY INFORMATION AND WARNINGS This manual refers to the Model SST-3 control panel manufactured since October 31, 2013, which uses a universal (100 277 VAC; 50/60 Hz) power supply. Older units use a voltage-specific power supply and

More information

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL Firefly II Multi Voltage RELEASE DEVICES Firefly II & IIB-MV INSTALLATION MANUAL GENERAL DESCRIPTION: S/N The The Cookson Company Firefly II-MV time delay release devices are designed for use on rolling

More information

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

SOLID STATE SECURITIES, INC. THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL S S S S S S LISTED L * PATENT PENDING S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT U 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors Hinge Edge of Door Hinge Edge of Door Wiring Instructions for the Sargent 0 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL

More information

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL S S S S S S OLID TATE ECURITIES, INC S S 90 SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED 99Y9 RESET U L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: These Time Delay Release Devices are U.L. Listed, Canadian Listed,

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

Axiom Technologies L.L.C Telephone: Pennbright Dr., Suite 220 Fax: XP7 USER S MANUAL

Axiom Technologies L.L.C Telephone: Pennbright Dr., Suite 220 Fax: XP7 USER S MANUAL L.L.C Telephone: 281 931 0907 255 Pennbright Dr., Suite 220 Fax: 281 931 6562 Houston, Texas 77090 www.axiomsafety.com XP7 USER S MANUAL COMPACT MULTI-CHANNEL ALARM & SHUTDOWN SYSTEM GENERAL The XP7 alarm

More information

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS Fire Control Panel Installation & Programming Manual TBLE OF CONTENTS Page Getting Started 2 Power Supply Unit 3 Inputs 4 Outputs 4 LED Indications 4 User Keypad Functions 5 Engineer Keypad Functions 6

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

DETECT-A-FIRE Heat Detectors

DETECT-A-FIRE Heat Detectors DETECT-A-FIRE Heat Detectors DETECT-A-FIRE thermal detectors are detection and release devices used for fire detection systems to activate alarms and actuate extinguishing systems. This rate compensated

More information

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM 216279-000 rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM IDENTIFYING YOUR SYSTEM IOM216279-000 The HOTSTART heating system is designed to heat fluids for use in marine

More information

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description. Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description The TYCO RAPID RESPONSE Model RCP-1 Residential

More information

Conventional Releasing Control Panel

Conventional Releasing Control Panel s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device

More information

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE Cookson 100 Elmwood Avenue Crestwood Industrial Park Mountaintop, PA 18707 Phone: 800-233-8366 Fax: 800-526-0841 CornellCookson.com O W N E R S M A N U A L M O D E L S F I R E G A R D M C F I R E G A R

More information

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) SECTIONS General Description.... 1 Warnings.... 2 Technical

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector Wiring Instructions for the 900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

Installation Instructions

Installation Instructions 50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions

More information

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

12.0 cu.ft., 2 way, 4-door, R.V. refrigerator with ice maker.

12.0 cu.ft., 2 way, 4-door, R.V. refrigerator with ice maker. Installation Manual For 1200ACXX models: For 120XAC-IMXX models: 12.0 cu.ft., 2-way, 4-door, R.V. refrigerator. 12.0 cu.ft., 2 way, 4-door, R.V. refrigerator with ice maker. The letter X, in the model

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

FLCH4R Garage and Utility Electric Heater

FLCH4R Garage and Utility Electric Heater FLCH4R Garage and Utility Electric Heater Installation, Operation & Maintenance Instructions Model No. Volts Amps Watts BTU/HR Phase High Low High Low High Low Min Fuse Size* FLCH4R 208 17.3 8.66 3600

More information

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control

More information

ANNUNCIATOR FIXED MODULE

ANNUNCIATOR FIXED MODULE 12 Clintonville Road Northford, CT 06472 Phone: 203-484-7161 Fax: 203-484-7118 THE ANNUNCIATOR FIXED MODULE Installation Manual for the AFM-16ATF and AFM-32AF Annunciator Modules Document # 15970 3/27/95

More information

Model 17A00 Expansion Enclosure

Model 17A00 Expansion Enclosure HOME AUTOMATION, INC. Model 17A00 Expansion Enclosure Installation Manual Document Number 17I00-1 Rev A March, 2002 Home Automation, Inc. Model 17A00 Expansion Enclosure Installation Manual Document Number

More information

Installation Instructions Dual Fuel Ranges

Installation Instructions Dual Fuel Ranges Installation Instructions Dual Fuel Ranges E30DF74EPS E36DF76EPS E48DF76EPS 5995447082 2 Safety IMPORTANT SAFETY INSTRUCTIONS Safety Precautions Do not attempt to install or operate your unit until you

More information

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

ELECTRONIC FLAME SUPERVISION MULTI-BURNER MULTI-BURNER MODEL: SENS-A-FLAME II Revision: 0 7112 DESCRIPTION Model 7112 Sens-A-Flame II is a second generation solid-state programmable combustion safeguard for supervising multiple burner ovens, furnaces,

More information

30.45 Electric Release PDRP-2001

30.45 Electric Release PDRP-2001 The PDRP-2001 Fire Alarm Control Panel (FACP) is a six-zone control panel for single and dual hazard deluge and preaction applications. The FACP is compatible with conventional input devices (2-wire or

More information

Installation Instructions

Installation Instructions Electric Heaters 5 --- 20 kw SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters For 13 SEER, R---410A Manufactured Home Installation Instructions NOTE: The Dual Point Kit can only be installed on

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

Installation Manual. For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC )

Installation Manual. For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC ) Installation Manual For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC ) N404M.3 (128 liter 3-way operation with LP gas, 240 volts AC, or 12

More information

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM TTC-1 TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION The nvent RAYCHEM TraceTek TTC-1 sensing module is used with TraceTek sensing cables to detect liquid leaks.

More information

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature AutoTest VSR (VSR-AT) (EU) Features Assembled in USA 0-30 second field replaceable electronic retard Two SPDT (Form C) switch contacts Weatherproof Easy to read wire terminal designations Easy to read

More information

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg. WARD OXYGEN Installation, Operation, and Maintenance Instructions MEGA medical electronic gas alarm MEGA WARD MEGA medical electronic gas alarm WARD POWER SUPPLY Medical Electronic Gas Alarm OXYGEN SYSTEM

More information

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715 Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed

More information

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door CAUTION Hinge Edge of Door Wiring Instructions Checkmate Series with Single Point Hold-Open Combination Door Closer-Holder and Releasing Device with or without Integral Smoke Detector INSTALLER: LEAVE

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where

More information

Installation Instructions

Installation Instructions 50ES--A, 50EZ--A, 50VG--A, B, 50VL--A, B, 50VR--A, 50VT--A, B 604D-- --A, 607C-- --A, B, 607E-- --A, 704D-- --A, 707C-- --A, B, 707E-- --A PA3G -- -- A, PH3G -- -- A, PA4G, PH4G PAD3, PHD3, PAD4, PHD4,

More information

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps TT-1023 1/97 INSTALLATION INSTRUCTIONS Original Issue Date: 2/94 Model: 6-2000 kw Market: Industrial Subject: Flush- or Surface-Mount Remote Annunciator Kits PA-293991 and PA-293991-SD The remote annunciator

More information

AlarmLine Addressable Linear Heat Detector

AlarmLine Addressable Linear Heat Detector Line Addressable Linear Heat Detector P/N 7-0001-00 Effective: March 2008 K-7-02 FEATURES UL Listed FM Approved CSFM MEA (pending) Low-cost interface between Line sensor cable and control panel accepting

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

LifeAlarm Fire Alarm Controls

LifeAlarm Fire Alarm Controls UL, ULC Approved* LifeAlarm Fire Alarm Controls 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Features Provides additional notification appliance circuit (NAC) capacity

More information

User s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151

User s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151 User s Manual For the SHORE POWER CONNECTION MONITOR MODEL 9151 Table of Contents: Product Description... 3 Installation... 4 Optional Remote Alarm Installation... 7 Operator Test... 8 Alarms... 9 Figures...

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D2 MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D2 GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel 12 Clintonville Road Northford, CT. 06472 (203) 484-7161 FAX:(203) 484-7118 The TC-4F Time Control Module For the Sensican 2000 Fire Alarm Control Panel Document # 15972 3/27/95 Revision C P/N 15972:C

More information

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening. DIVISION 8 OPENINGS SECTION 08 33 23 PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead coiling counter fire doors. 1.2 RELATED SECTIONS A. Section 05500 - Metal Fabrications: Support framing and framed opening.

More information

Installation Instructions for the LatitudeTM Solaris Stick Light Models SL8C-xxx

Installation Instructions for the LatitudeTM Solaris Stick Light Models SL8C-xxx 25500298 Rev. A0 1215 Installation Instructions for the LatitudeTM Solaris Stick Light Safety Message to Installers and Operators of Warning Lights People s lives depend on your proper installation and

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent

More information

DE5300 Delayed Egress System. General Information

DE5300 Delayed Egress System. General Information *911031-00* 911031-00 Wiring and Configuration DE5300 Delayed Egress System Installation Instructions General Information The Von Duprin DE5300 is designed for controlled egress applications when used

More information

AlarmLine Linear Heat Detector

AlarmLine Linear Heat Detector 7.01 7/11/2000 8:1 AM Page 1 CP Scan#1:Desktop Folder:hold:90 Catalog:7.01.job: 7.01 AlarmLine Linear Heat Detector FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm

More information

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE Cornell 100 Elmwood Ave. Crestwood Industrial Park Mountaintop, PA 18707 tel 800.233.8366 fax 800.526.0841 cornell@cornelliron.com O W N E R S M A N U A L M O D E L S F I R E G A R D B B FIREGARD BV EXTENDED

More information