FIRE STATION 55 June 14, 2010

Size: px
Start display at page:

Download "FIRE STATION 55 June 14, 2010"

Transcription

1 SECTION ELECTRICAL WIRING PART 1 - GENERAL 1.1 RELATED DOCUMENTS: 1.2 SUMMARY: The general provisions of the Contract and the requirements of Section apply to the Work specified in this Section. A. Power Wiring: 1. Provide all conductors for all electric service entrance, feeders, branch circuits and proper connections to serve all building electrical loads. 2. Make proper wiring connections to all electrical equipment and devices that require electrical connection, including all Owner-furnished equipment and all equipment furnished under other Divisions of the Specifications (mechanical, elevator, etc.). All electrical circuits and connections, disconnects, and starters shall be in accordance with this specification and with the specific equipment manufacturer's instructions. B. Control Wiring: 1. Provide a complete control wiring system for all electrical equipment and appliances, including all Owner-furnished equipment as shown on drawings. Equipment furnished under other Divisions of the Specifications (mechanical equipment, etc.) shall be properly installed with electrical circuits and connections, disconnects, starters, operator control pushbuttons, alarms, etc. as specified for each type of item. 2. Building Automation System and all BAS wiring is specified under Division 15. Provide line voltage branch circuits for control power where indicated on Electrical Drawings. Provide other line voltage HVAC control system wiring when shown on the Electrical Drawings. Control wiring not shown on the Electrical Drawings is provided under Division All domestic water pumps, house pumps, fire and jockey pumps, sewage ejector, surge tanks, sump pumps, surge tank water valve controllers, including all associated alarm circuits. 4. All switches for controls, signals, pilots, remote trip operators, raise/lower switches, remote start/stop motor control stations, and any other devices or system required. 5. Contactor, time switches, and photoelectric control systems. 6. Smoke Control Dampers: Provide fire alarm monitored relays and supervised wiring to provide signal of fire alarm condition to smoke control dampers. Refer to Section for additional requirements. 1.3 QUALITY ASSURANCE: A. Regulatory Requirements: Comply with provisions of NFPA 70 National Electrical Code: ELECTRICAL WIRING

2 B. Underwriters Laboratories: Provide components that are listed and labeled by UL. C. NEMA/ICEA: Provide components that comply with the following standards: 1.4 SUBMITTALS: 1. WC-5: Thermoplastic-Insulated Wire and Cable for the Transmission and Distribution of Electrical Energy. 2. WC-3: Rubber-insulated building wire. A. Provide submittals according to Section B. Product Data: 1. Submit manufacturer's published catalog pages and specification sheets for following products. 2. Each wire type. 3. Type MC cable fittings PART 2 - PRODUCTS VOLT WIRING SYSTEMS: A. Low Voltage: Refer to Article titled LOW VOLTAGE CLASS CIRCUITS in this Section for additional requirements. B. Wire Manufacturers: 1. Not all manufacturers listed make all types of wire specified or required. Contractor is responsible for verifying that all price quotes received and wire types submitted are from named manufacturers and also meet project specifications. 2. Aetna Insulated Wire Company, Alpha, Alflex Corp., AFC Cable Systems, Inc., American Insulated Wire, Anixter (distributor), AT&T Technologies, Belden, Berk-Tek, General Cable, CommScope, Inc., Encore Wire, Essex, General Cable, General Wire, Magnetek Universal, Manhattan Electric Cable, Mohawk/CDT, Montrose/CDT, NORDX/CDT, Rome Cable Corporation, Service Wire Co., Signal Cable Co., Southwire, West Penn Wire/CDT. C. Minimum Size: AWG #12 except control circuits operating at a maximum of up to 120 volts may be #14. Where wire is sized at the homerun only or if scheduled, then that size holds for the entire circuit. Where wire is not sized, and circuit protective device is rated at 20 amps, provide AWG #12 wire. If not shown on Drawings, in accordance with the National Electrical Code based on the requirements of the load served. D. Insulation: 1. Above Ground: THHN/THWN or THHN/THWN-2. ELECTRICAL WIRING

3 2. Underground: RHW, RHW-2, XHHW, or XHHW-2. Note that conduit sizes shown on Drawings are based on XHHW insulation. If Contractor proposes to use RHW, Contractor shall adjust conduit sizes as required for proper installation of the conductor with greater insulation O.D. 3. Sunlight: Insulated conductors and cables used where exposed to direct sunlight shall be listed or marked sunlight resistant. 4. Special: Where drawings indicate any other special type of insulation required by stating the Code letter type or if the application requires special insulation, then that type shall be provided. E. Conductors: 1. Soft drawn, annealed, bare (uncoated) copper, 98% conductivity. 2. All wire sizes on Drawings represent copper wire unless indicated to be aluminum by the abbreviation "AL" on the Drawings. 3. Contractor Aluminum Option: For copper conductors AWG #1/0 and larger, and "AL" is not indicated on Drawings, aluminum may be provided at the option of the Contractor if: a. the size of the feeder and conduit is increased to provide a NECacceptable installation of equal (or greater) ampacity and equal (or less) voltage drop to the copper sizes shown, and b. aluminum grounding conductors shall be sized per NEC Table , and c. aluminum wire shall not be terminated at fire pumps, generators, mechanical equipment, motor controllers or terminals of control circuit devices unless approved in written installation instructions by that equipment manufacturer, and d. all lugs shall be proper UL-listed dual-rated copper-aluminum lugs. 4. Aluminum conductors shall be Aluminum Association 8000 Series electricalgrade aluminum alloy. To wire manufacturers listed above, add Alcan Cable- Stabiloy brand aluminum conductor. 5. Aluminum conductor shall have compact stranding as defined in 1993 NEC Chapter Nine Tables 5A and 5B. 6. Install all aluminum conductor for phase, neutral and ground in each circuit and feeder for which aluminum conductor is used. Install all copper conductor for phase, neutral and ground in each circuit and feeder for which copper conductor is used. F. Conductor Makeup: 1. Solid: All wire sizes AWG #10 and smaller. 2. Stranded: All wire sizes AWG #8 and larger. G. Grounding Conductors: All grounding electrode conductors and equipment grounding conductors shall be insulated copper (as specified above) unless indicated otherwise. H. Special Purpose: Special purpose control wiring such as that used for packaged equipment, switchboards, etc., shall be a type specifically approved for the purpose and as recommended by the equipment manufacturer. ELECTRICAL WIRING

4 2.2 LOW-VOLTAGE CLASS CIRCUITS: A. General: Low-voltage class circuits are those as defined in NEC 725 Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits. For wiring to be installed as a part of an auxiliary system specified in another Section of this Specification, refer to that Section for additional requirements. B. Code Requirements: Article 725 of the National Electrical Code for the specific class circuit involved. C. Wire: 1. Minimum Size: AWG #16 minimum or larger size shown on the drawings or specified elsewhere. Where not shown or specified, provide the size required for the specific application. 2. Insulation: Thermoplastic unless required otherwise for application. In all cases, insulation shall be rated for 600 volts. 3. Conductor: Soft drawn, annealed, bare (uncoated) copper, 98% conductivity. 4. Fire Resistance of Cables: a. Class 2 and 3: All cables of Class 2 and 3 circuits shall be U.L. listed in product category QPTZ and marked as described in NEC , 51 and 53. All such cable shall be Type CL2 or CL3. In addition, riser cables shall be Type CL2R (or CL3R) and plenum cables shall be labeled Type CL2P (or CL3P). b. Communication Cable: Refer to Section TELECOMMUNICATIONS PATHWAYS. c. Fire Alarm Cable: Refer to Section FIRE ALARM SYSTEM. d. Optical Fiber Cable: Refer to Article in this Section. 5. Manufacturers: Same as manufacturers listed for 600 Volt wiring systems. PART 3 - EXECUTION 3.1 INSTALLATION: A. Wire Pull: 1. All wiring shall be installed in approved raceway and enclosures. Raceway run shall be completely installed and free of any foreign objects before pulling or installing wire. No wire shall be pulled into conduit which terminates in large distribution equipment until equipment has been anchored into place. Cleaning agents shall have no deleterious effect on conductor coverings. 2. Pulling Lubricants: All pulling lubricants shall be listed in UL Electrical Construction Materials Directory (Green Book) under category WIRE-PULLING COMPOUNDS (ZOKZ). Lubricants shall have no deleterious effects on physical and electrical properties of wire and cable jackets. Wire lube products of 3M, American Polywater Ideal or approved equal. 3. Rough-Ins for Future Connections: Where wire is indicated to be installed, but the connection is indicated "future" or "by others", Contractor shall leave a minimum of 3' of "pigtail" at a junction box, tape the ends of the conductors, ELECTRICAL WIRING

5 and cover the junction box, unless otherwise instructed on the drawings. B. Wire and Cable Terminations, Splices, and Taps: 1. General: Comply with NEC All materials used to terminate, splice or tap conductors shall be designed for, properly sized for, and U.L. listed for the specific application and conductors involved. Install in strict accordance with the manufacturer's recommendations, using the manufacturer's recommended tools. Where taps are required on conductors sized #6 and larger, Contractor shall not sever the "main" or "feed through" conductor, but shall provide "tee" or "parallel" type connectors for connection of the tapping conductor. 2. Junctions: All wire and cable in conduit shall be continuous without taps or splices. Install junctions for taps and splices only in approved boxes and enclosures and comply with NEC (a). Provide raceway systems so that the fewest possible junctions can be installed as is feasible and practical. 3. Wire Connectors in Corrosive Areas: Connectors shall be IDEAL Twister DB Plus brand, DryConn brand of King Innovation, or approved equal. Provide silicone grease filled wire connectors when wire connectors are installed on AWG #8 and smaller wire sizes in the following areas: a. All well-light luminaires installed flush in grade outdoors. b. All outdoor signs. c. All outdoor floodlights mounted at grade level. d. All lighting, switch outlets, and receptacle outlets in the pool area, pump room and other areas with chlorine air environment. 4. All Wires AWG #8 or Smaller: a. Power Circuits: Insulated thermoplastic body, solderless live-spring mechanical twist-on wire connectors. 3M Electrical Products 2-color "Scotchlok 2" and original "Scotchlok", Ideal Wing-Nut, Twister, Twister PRO and B-CAP brands, NSI Industries Easy-Twist Winged Wire Screw-On Connectors, or approved equal. b. Control Circuits: As described for power circuits above, except terminations at equipment shall be made on properly rated terminal blocks. 5. In-Line Reducer Splice: Cables may be shown on the Drawings or otherwise required to be over-sized to accommodate voltage drop. Where required to fit into circuit breaker, fused switch, or dimmer module, install in-line reducer on cable ends. Properly terminate cable into equipment lugs. Under no circumstances shall cable be reduced below protective rating of overcurrent device protecting the feeder or circuit. Maintain access to reducers. If necessary, install additional wireway or other junction box to supplement panelboard cabinet or switch enclosure. In-line reducer shall be ILSCO RocketSplice ( , ), MAC Products Concentric Reducing Connector MSSR Series Penn-Union Corp. Insulated Inline Reducer ( ), PT-R Series ReduceR adapter plug or Slip n Sleeve compression reducer by Greaves Electric ( ), or approved equal. 6. Any Wire AWG #6 or Larger: a. All Copper Cable Splices and Taps: High strength, high-copper alloy, corrosion resistant, solderless, mechanical set-screw connector or hydraulic-crimp copper compression connectors. Apply 3M Electrical ELECTRICAL WIRING

6 Products brand "Scotchfil" putty or 3M Electrical Products Brand No. 23 tape around the connector to form a rounded base free of irregular surfaces. Over this apply two half-lapped layers of 3M Electrical Products Brand No. 33+ Scotch vinyl plastic electrical tape. Contractor Option: As an alternate method of insulating wire splices and taps, install molded joint cover 3M 8420 Series Cold Shrink Connector Insulator, Greaves Corporation Polaris Series Pre-Insulated Splice, NSi Industries Inc. Polaris Insulated Connector ( ), GelWrap or GILS kit by Raychem brand of Tyco Electronics or acceptable equivalent. b. Motor Pigtails: Splice motor pigtails with pigtail kits, 3M Electrical Products Series 5300, T & B Motor Stub Splice Insulator, GelCap kit by Raychem brand of Tyco Electronics, or acceptable equivalent. Lugs shall be long barrel, hydraulic-crimp copper compression with 1-hole or 2-hole bolt tang. c. Copper Cable Lug Connections to Equipment: Lugs shall be solderless, mechanical set-screw aluminum (AL/CU dual-rated) lug or hydrauliccrimp copper compression lug. Secure lugs to equipment as recommended by the manufacturer of the specific piece of equipment. d. Manufacturers: Amp and Raychem brands from Tyco Electronics Buchanan, Burndy, Cutler- Hammer/Westinghouse, Woodhead Dossert, G.E., Greaves ( ), Hoffman, Homac, Ideal, Ilsco MAC Products NSi Industries Inc., O.Z./Gedney, Penn-Union Corp. Plymouth Rubber, 3M, Siemens, Square D, Steel City, Thomas and Betts Color- Keyed and Blackburn brands C. Power Distribution Blocks: 1. General: Provide power distribution blocks when multiple taps must be made to a single feeder. Install blocks in listed wireway, auxiliary gutter or junction box. 2. Listed: Power distribution blocks shall be UL listed. Manufacturer shall be named in Category (QPQS) or (ZMVV) of UL Electrical Construction Materials Directory (Green Book). 3. Construction: Blocks shall have mechanical bolt lugs for both incoming main feeder and outgoing feeder tap(s). Design shall permit inserting main feeder without severing conductor(s). Configurations shall be available for parallel main and tap conductors. Provide 3 or 4-wire assembly, as required. Each block shall have insulated base and clear cover. 4. Manufacturers: Burndy "Spec-Blok" or "Electro-Rail"; Greaves pre-insulated Polaris series ( ); Homac Multi-Seal ;Ilsco PDB-Series Lay-In Power Distribution Block, SnapBloc, and ClearTap ( , sales@ilsco.com ); NSi Industries Inc. Connector- Blocks ( ), Penn-Union Corp D. Circuitry: 1. General: Branch circuits may be grouped in single raceways and share common neutral provided the following guidelines are followed, unless the ELECTRICAL WIRING

7 Drawings indicate otherwise: 2. Dedicated Circuits: Provide a neutral per phase conductor for all dedicated circuits. 3. Voltage Separation: Branch circuit and feeder conductors operating at different voltages, e.g. 120V and 277V, shall not be grouped together and installed in the same raceway. 4. Three Phase, Four Wire, Wye Systems: Provide a neutral conductor for each group of two or three sequence phased line conductors. 5. Single Phase, Three Wire Systems: Provide a neutral conductor for each group of two sequenced line conductors. 6. Three Phase, Four Wire, Delta Systems: Provide a neutral conductor for each group of two sequence phased line conductors; the high leg phase (or line) shall not be used for phase to neutral wiring connections. 7. Dimmed Circuits: Provide a separate neutral conductor for each phase conductor on lighting circuits controlled with electronic dimming. This shall include both central packaged systems and wall box type. 8. Code Requirements: In grouping conductors in a single raceway, comply with Code requirements for ampacity derating of conductors and maximum capacities of raceways. Provide larger conductors as required to maintain full ampacity of circuits as indicated on Drawings. E. Conductor Labeling: 1. Conductors shall have insulation of the proper color as listed below: SYSTEM VOLTAGE A B C NEUTRAL 120/208 Volt 3PH/4W Black Red Blue White 277/480 Volt 3PH/4W Brown Purple Yellow Gray All Voltages: Green for Grounding Conductor IG receptacles shall have green wire with yellow stripe. 2. Alternative Color Marking for AWG No.1 and Larger: Contractor may use 3M Electrical Products Scotch #35 vinyl plastic electrical tape, wrapping two turns of the appropriate color tape around each cable at all termination points and junction and pull boxes. 3. Control Wiring Systems: All terminal blocks and wire terminals shall be properly numbered for identification with T & B "E-Z-Code" Vinyl Stick-On Markers or equivalent. 4. Dedicated Neutrals: a. General: Dedicated neutrals are required where multi-wire circuits are prohibited by specification, such as for dimmer circuits, computer circuits, and other dedicated circuits. Neutral labels will assist individual circuit tracing, isolation of circuit load voltages and currents, and verification of dedicated neutral. b. Neutral Tags: When a branch circuit is required to be installed with a dedicated neutral per phase conductor, the neutral wire shall be labeled or tagged with the associated branch circuit number at every junction box, wire termination and other points of access to circuit conductors. c. Neutral label not required at final wiring device termination unless more than one neutral is present in the outlet box. ELECTRICAL WIRING

8 d. Color-mark: Color-mark each neutral with tape to match the color of the associated phase conductor. Wrap tape on neutral at same points as branch circuit tags. e. All neutral identification shall comply with NEC (D) and (A). F. Record Posting for Control Power Branch Circuits: Prepare a schedule for each 120 Volt control power branch circuit. Refer to Part One for additional requirements of normal and emergency power dedicated control power branch circuits. List all smoke dampers and other items that get power from each circuit. Use the exact name for each device assigned by the Division 15 Mechanical equipment installer. Post the schedule under Lexan adjacent to the circuit junction box in the Air Handler Room or Mechanical Room. Include a copy of the schedule in the Operation & Maintenance Manual for the Building Automation System. Purpose of the schedule is to track every item that receives power from the 120 Volt branch circuit. 3.2 METAL-CLAD PRE MFG CABLE CONNECTOR SYSTEMS (RE-LOCK): A. Installation: 1. Installation Requirements: a. Routing: Generally, cable shall be routed parallel with or perpendicular to the building lines above corridors. Parallel runs shall be tied and routed together 6. Applications: a. Luminaires (Lighting Fixtures) and Switches. B. Support: 1. General: Cable shall be supported independently and not to or from other systems. Securing cables to water lines, electrical raceways, or any other mechanical system shall not be acceptable. Cables shall not be allowed to sag more than 8" below the support system, shall not rest or sag onto the suspended ceilings, shall not contact sharp objects, and shall maintain a 6" vertical and horizontal clearance from electrical fixtures. Installation shall be neat and orderly. 2. Support Methods: Cables shall be supported from building structure. Cable shall be supported from bar joists, unistrut trapeze hangers, drop rods, allthread rods, or other hangers installed and approved for this purpose. Hangers and supports shall be spaced as required, but in no case shall spacing exceed 6' on center (NEC ). 3. Support shall be dedicated to electrical conductors and not shared with ductwork, piping, or other equipment. 4. Raceways: Raceways shall not be used as a means of support.. 5. Fastening Devices: Cables shall be securely fastened to building structure by Caddy steel cable support clips, bridal rings with clips or clamps or similar approved equal devices. Tie wire, scrap wire and tape fasteners are prohibited from Work of this Project. Protect against physical damage as required by NEC (D). ELECTRICAL WIRING

9 3.4 TESTING: 6. Cable assemblies, boxes and fittings located above a nonfire-rated floor/ceiling or roof/ceiling assembly shall not be secured to, or supported by, the ceiling assembly, including the ceiling support wires. Provide an independent means of secure support. All attachment to support wires shall be with Caddy clips, or approved equal fasteners, and not bare wire ties. 3. Ceiling grid shall not support any cable or raceway. A. General: After installation of all conductors, and before final acceptance, make required tests to determine proper functioning of all circuits. Furnish all necessary instruments required to make tests, and correct any deficiencies found. Prior to energizing, circuits shall be "ringed-out" to verify continuity and detect short circuits. Contractor shall submit to Architect written test report certifying compliance with this requirement and stating that all deficiencies have been corrected. B. Procedure: 1. Insulation resistance of all feeder conductors and all conductors AWG #1 and larger shall be tested. Each conductor shall have its insulation resistance tested after the installation is completed and all splices, taps, and connections are made except connection to source and point of final termination at distribution or utilization equipment. 2. Insulation resistance of conductors that are to operate at 600 volts or less shall be tested by using AVO Biddle (or approved equal) Megger at not less than 1000 volts dc. Resistance shall be measured from conductor to conduit (ground), conductor to conductor and conductor to neutral. Testing methodology shall conform to short-time or spot-reading procedural recommendations of AVO Biddle Instruments for specific megger being used. Acceptable insulation resistance of conductors rated at 600 volts shall not be less than one (1) megohm. 3. Conductors that do not exceed one megohm resistance during the short-time test above shall be tested using the time-resistance method (two-time method). Calculate the dielectric absorption ratio from the two readings. Test shall be performed taking 60 second/30 second reading ratio for handcranked Meggers and 10 minutes/1 minute reading ratio for power-operated Meggers. Ratios shall be acceptable and considered as passing if ratio for 60/30 test is greater than 1.4 and ratio for 10/1 test greater than Conductors that do not satisfy test requirements in (b.) or (c.) above shall be removed, replaced, and testing repeated on new cable at no additional cost to the Owner. All tests shall be performed by licensed electrician trained in the use of test instruments. Contractor shall furnish all instruments and personnel required for tests, shall tabulate readings observed and shall forward six (6) copies of test readings to Engineer for review. Reports shall clearly indicate all test failures, locations, remedies, and re-test results. 5. These test reports shall identify each feeder conductor tested, date, time, and result of test, wet and dry bulb temperature, weather conditions, relative humidity and range, test voltage, and serial number of the megger instrument used. In addition provide insulation resistance values corrected for temperature. Any conductor or splice that is found defective shall be promptly ELECTRICAL WIRING

10 removed and replaced, and additional test shall be performed. C. Disconnect Surge Protective Devices (SPD): High potential testing is prohibited across any SPD, also know as Transient Voltage Surge Suppressors (TVSS). Disconnect SPD from any conductors or equipment to be tested by ac or dc high potential testing (hi-pot testing or Meggar testing). SPD are not designed for and may not withstand the high voltages applied for the duration of high potential testing. 3.5 LOW VOLTAGE CLASS CIRCUITS: A. Raceway Installation: Provide raceway for all circuits in accordance with the Section entitled RACEWAY SYSTEMS, except no raceway is required in the following areas: 1. Accessible air handling ceiling cavities, as described in NEC (C), where cable is used that is U.L. listed as having adequate fire-resistant and low-smoke producing characteristics, per U.L. Subject Accessible, non-air handling ceiling cavities, when wiring installed is same as wiring in accessible air handling ceiling cavities. 3. Provide raceway in walls even when it is not required in ceiling cavities as outlined above. 4. Provide raceway above accessible ceiling when ceiling is higher than 11'-0" above finished floor. B. Installation Where Raceway Not Required: 1. General: Cable shall be supported independently and not to or from other systems. Securing cables to water pipe, electrical raceways, ductwork or any other mechanical system shall not be acceptable. Cables shall not be allowed to sag more than 8" below the support system, shall not rest or sag onto the suspended ceilings, shall not contact sharp objects, and shall maintain a 6" vertical and horizontal clearance from electrical fixtures. Installation shall be neat and orderly. 2. Routing: Generally, cable shall be routed parallel with or perpendicular to the building lines above corridors. Parallel runs shall be tied and routed together. Cables leaving intermediate distribution points shall be routed only through building core rooms and spaces, corridors or other public spaces until they reach the specific area of outlets that they are intended to serve. 3. Support Methods: Cables shall be supported from building structure (NEC 725.6). Cable shall be supported from bar joists, unistrut trapeze hangers, drop rods, all-thread rods, or other hangers installed and approved for this purpose. Hangers and supports shall be spaced as required, but in no case shall spacing exceed 6' on center. 4. Raceways: Raceways shall not be used as a means of support for cables (NEC (B)). 5. Fastening Devices: Cables shall be securely fastened to building structure by Caddy steel cable support clips, bridal rings with clips or clamps, Caddy WMX3/6 Series J-hanger with attachment clip, Caddy CableCAT spring steel J- hook with rounded edges for Category 5, Caddy Cat-CM Cable Support System CADDY, B-Line bridal rings with plenumrated plastic insert to protect cables from kinking B- Line wide-body J-hooks or X-hooks with steel spring closure for re-usable cable ELECTRICAL WIRING

11 entry, or similar approved equal devices. Scrap wire or tape is not acceptable. Protect against physical damage as required by NEC (D). 3.7 BRANCH CIRCUIT LENGTH: A. 150 Volts or less: Install AWG #10 when the first outlet is over 100 feet from the panelboard. B. 150 to 300 Volts: Install AWG #10 when the first outlet is over 150 feet from the panelboard. C. Branch circuit voltage drop shall not exceed 3% of branch circuit voltage rating. END OF SECTION ELECTRICAL WIRING

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices. SECTION 16470 PANELBOARDS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 09900 - Painting. 2. 16120 - Wire and Cable. 3. 16475 - Overcurrent Protective Devices. 1.02 SYSTEM DESCRIPTION A. Performance

More information

E I Delmar Cobble MINOR ELECTRICAL DEMOLITION

E I Delmar Cobble MINOR ELECTRICAL DEMOLITION PART1 GENERAL 1.01 SECTION INCLUDES A. Electrical demolition. 1.02 RELATED REQUIREMENTS SECTION 26 0501 MINOR ELECTRICAL DEMOLITION A. Section 01 7000- Execution and Closeout Requirements: Additional requirements

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 220533 - HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes plumbing piping heat tracing for freeze prevention, domestic hot-water-temperature maintenance, and

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

SECTION ISOLATED POWER SYSTEMS

SECTION ISOLATED POWER SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR September 2012, rev. 00 26 0553 Identification for Electrical Systems PART 1. GENERAL 1.01 Summary A. Section Includes: 1.02 Submittals 1. Identification for raceways. 2. Identification of power and control

More information

MEDIUM, LOW AND CONTROL VOLTAGE CABLES

MEDIUM, LOW AND CONTROL VOLTAGE CABLES Related Sections U-M Design Guideline Sections: 260800 - Electrical Acceptance Tests Products Medium Voltage Primary Cables Primary power distribution cable shall be single conductor stranded copper, with

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 27 12 23 FIBER OPTIC DATA NETWORK A. Furnish, install, terminate, and test all fiber optic equipment and cabling necessary for a complete and functional data highway

More information

SECTION (16140) - WIRING DEVICES

SECTION (16140) - WIRING DEVICES SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -

More information

A. Shop Drawing submittals shall include, but not be limited to, the following:

A. Shop Drawing submittals shall include, but not be limited to, the following: SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods 1. BASIC ELECTRICAL MATERIALS 1. All conduit and raceway must be 3/4" or larger. Exposed raceway in finished areas shall be in 700 or larger wiremold. Exception: runs to individual devices 10 or less,

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS PART 1 GENERAL 1.01 SUMMARY SECTION 26 22 00 (16460) - LOW-VOLTAGE TRANSFORMERS A. Section Includes: 1. Dry-Type Distribution And Specialty Transformers Rated 1000 V And Less. a. General-Purpose Distribution

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA

SECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low voltage power panelboards 1.02 RELATED SECTIONS 1.03 REFERENCES

More information

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates.

B. Shop Drawings: List of legends and description of materials and process used for premarking wall plates. SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Nameplates and labels B. Wire and cable markers C. Conduit markers 1.2 REFERENCES A. NFPA 70 - National Electrical

More information

PANELBOARDS & BUILDING DISTRIBUTION

PANELBOARDS & BUILDING DISTRIBUTION 262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic

More information

Section Electical General Provision

Section Electical General Provision Section 26 05 00 Electical General Provision 26 05 00-1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Except as modified in this Section, General Conditions, Supplementary Conditions, applicable provisions

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less.

1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less. Copyright 2010 AlA MasterSpec Full Length 09/10 SECTION 260519- LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART I-GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wires and cables rated 600

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

5. Identification products.

5. Identification products. Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 [SECTION 260523- CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets

More information

PowerWave 2 Busway System

PowerWave 2 Busway System PowerWave 2 Busway System Guide Specifications (Revision 004, 11/17/2017) 1 GENERAL 1.1 Summary This specification covers the electrical characteristics and general requirements for a continuous opening,

More information

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch

More information

IN2 Lighting Control Devices

IN2 Lighting Control Devices Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Lighting Control Devices Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

DIVISION 16 ELECTRICAL

DIVISION 16 ELECTRICAL DIVISION 16 ELECTRICAL Saratoga Springs / standards / 02-2004 Page - 0 ELECTRICAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.01 SECTION INCLUDES A. Grounding electrodes and conductors, equipment

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section Wiring Devices for wall-box dimmers and manual light switches. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 2 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 3 1.7 COORDINATION... 3 1.8 DELIVERY, STORAGE, AND

More information

Division 26 ELECTRICAL TABLE OF CONTENTS

Division 26 ELECTRICAL TABLE OF CONTENTS Division 26 ELECTRICAL TABLE OF CONTENTS 26 1000 GENERAL... 33 A. CODE... 3 B. RELATED SECTIONS... 3 C. ABBREVIATIONS... 3 D. DEFINITIONS... 3 E. DRAWING REQUIREMENTS... 3 F. EQUIPMENT SERVICE ACCESS AND

More information

C. Pigtail: Short lead used to connect a device to a branch-circuit conductor.

C. Pigtail: Short lead used to connect a device to a branch-circuit conductor. SECTION 26 27 26 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS. A. This Section includes basic electrical materials and methods including:

SECTION BASIC ELECTRICAL MATERIALS AND METHODS. A. This Section includes basic electrical materials and methods including: SECTION 16050 BASIC ELECTRICAL MATERIALS AND METHODS PART 1 - GENERAL 1.01 SUMMARY A. This Section includes basic electrical materials and methods including: 1. Conduit, fittings and accessories. 2. Wire,

More information

Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.

Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends. SECTION 260500- COMMON WORK RESULTS FOR ELECTRICAL PART 1 - GENERAL 1.1 SUMMARY Section Includes: 1. Sleeves for raceways and cables. 2. Sleeve seals. 3. Grout. 4. Common electrical installation requirements.

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems SECTION 26 05 54 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Permanent Marking. 6. Underground

More information

SECTION SOLAR PHOTOVOLTAIC (PV) POWER GENERATION SYSTEM

SECTION SOLAR PHOTOVOLTAIC (PV) POWER GENERATION SYSTEM SECTION 48 14 14 SOLAR PHOTOVOLTAIC (PV) POWER GENERATION SYSTEM PART 1 GENERAL 1.1 SECTION INCLUDES The work of this section consists of furnishing a complete Solar Photovoltaic (PV) Power Generation

More information

CurrentGuard TM. Installation, Operation and Maintenance Manual. CurrentGuardTM. Flush Mount. Surge Protective Devices A00

CurrentGuard TM. Installation, Operation and Maintenance Manual. CurrentGuardTM. Flush Mount. Surge Protective Devices A00 TM CGFS u r g e P R O T E C T I O N CurrentGuardTM Installation, Operation and Maintenance Manual 750-0098-006 A00 Surge Protective Devices CurrentGuard TM Flush Mount Table of Contents Guide to Installation

More information

You work hard on your panel. we work hard in your panel. PRODUCTS FOR

You work hard on your panel. we work hard in your panel. PRODUCTS FOR You work hard on your panel we work hard in your panel. PRODUCTS FOR 2 PRODUCTS FOR You simply won t find better panel components. Thomas & Betts has everything you need to make your panel better than

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

Fire Alarm Systems ARTICLE. Introduction to Article 760 Fire Alarm Systems. Part I. General

Fire Alarm Systems ARTICLE. Introduction to Article 760 Fire Alarm Systems. Part I. General ARTICLE 760 Fire Alarm Systems Introduction to Article 760 Fire Alarm Systems Article 760 covers the installation of wiring and equipment for fire alarm systems, including all circuits controlled and powered

More information

Allegany College of Maryland ACM Welcome Center M&D Project No

Allegany College of Maryland ACM Welcome Center M&D Project No SECTION 26.010 GENERAL PROVISIONS PART 1 - GENERAL 1.1 SCOPE: A. Work under this section shall be subject to the GENERAL CONDITIONS hereinbefore written for the entire work, noting especially the reference

More information

B. Section Identification for Fire Suppression Piping and Equipment.

B. Section Identification for Fire Suppression Piping and Equipment. SECTION 211300 - FIRE SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION : MEPS IDENTIFICATION & LABELING

SECTION : MEPS IDENTIFICATION & LABELING SECTION 01 70 10: MEPS IDENTIFICATION & LABELING 1. GENERAL A. The intent of this section is to define the labeling and identification requirements for building mechanical, electrical, plumbing, and specialty

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

Flame Retardant EP/CPE POWER, CONTROL & INSTRUMENTATION CABLES

Flame Retardant EP/CPE POWER, CONTROL & INSTRUMENTATION CABLES Flame Retardant EP/CPE POWER, CONTROL & INSTRUMENTATION CABLES 37-754 FLAME RETARDANT EP/CPE TYPE TC OR TC-ER POWER CABLE Two Five Conductor + Ground (Two, Three & Four Conductor) 600 V Rated 90 C Conductor*

More information

2014 National Electrical Code & NFPA 70E/Arc Flash

2014 National Electrical Code & NFPA 70E/Arc Flash Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the

More information

SECTION LIGHTING CONTROL DEVICES

SECTION LIGHTING CONTROL DEVICES SECTION 16145 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION EXTERIOR LIGHTING

SECTION EXTERIOR LIGHTING SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26

More information

Department of General Services Real Estate Services Division Professional Services Branch Additional Detailed Instructions (ADI)

Department of General Services Real Estate Services Division Professional Services Branch Additional Detailed Instructions (ADI) Department of General Services Real Estate Services Division Professional Services Branch Additional Detailed Instructions (ADI) PJECT: Altaville Fire Station WORK ORDER NO. 125047 Automotive Shop Replacement

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: SECTION 26 09 23 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

BASIC ELECTRICAL REQUIREMENTS July Electrical Systems

BASIC ELECTRICAL REQUIREMENTS July Electrical Systems SECTION 26 05 02 - BASIC ELECTRICAL REQUIREMENTS PART 1 - GENERAL 1.1 SUMMARY A. Work Included: Furnish all labor, material, services and skilled supervision necessary for the construction, erection, installation,

More information

Incorporate as part of the Contract Documents, the following:

Incorporate as part of the Contract Documents, the following: March 21, 2014 SAS Job No. 1207R Addendum Number 3 to the Contract Documents for the Construction of: Bevill Biomedical Research Building Shared Equipment Room Package University of Alabama at Birmingham

More information

SECTION COMMERCIAL-KITCHEN HOODS

SECTION COMMERCIAL-KITCHEN HOODS SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber

More information

occurs and be cause for termination of the contract.

occurs and be cause for termination of the contract. 1.02 SUBMITTALS occurs and be cause for termination of the contract. CITY OF MIAMI CAPITAL IMPROVEMENTS PROGRAM A. Manufacturer s Data: 1. Complete list of materials to be furnished under this section.

More information

SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 0513 -CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 260923 - LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

DIVISION 16. ElECTRICAl

DIVISION 16. ElECTRICAl DIVISION 16 ElECTRICAl SECTION 16030 ELECTRICAL POWER SYSTEM STUDIES PART 1 -GENERAL 1.01 SUMMARY A. Section Includes: 1. Short circuit study, protective device evaluation study, protective device coordination

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 260501 - BASIC ELECTRICAL MATERIALS AND METHODS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

DIVISION 16 BASIC MATERIALS, METHODS, AND REQUIREMENTS SECTION 16A-1

DIVISION 16 BASIC MATERIALS, METHODS, AND REQUIREMENTS SECTION 16A-1 DIVISION 16 BASIC MATERIALS, METHODS, AND REQUIREMENTS SECTION 16A-1 PART 1: GENERAL 1.1 SUMMARY.1 This section covers materials, methods, and requirements common to all electrical work..2 When it becomes

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Coaxial cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control

More information

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120 LowProfile Series: 080 and 120 Surge Protective Devices Installation, Operation and Maintenance Manual P.O. Box 3760 Winter Park, FL 32790 USA 1.800.647.1911 www.tpssurge.com LOWPROFILE InstaLLatIOn, OPERatIOn

More information

SECTION INTERIOR LIGHTING

SECTION INTERIOR LIGHTING SECTION 26 51 00 INTERIOR LIGHTING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 2416 - PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Manufacturers Statement of Compliance with NFPA 70, National Electric Code,

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information