1 BY DAVE DEMMA PAYING THE PIPER This is the third and final installment explaining the conversion of a refrigeration system from an HCFC (R22) to an alternative, probably an HFC (R404A or R507). There are other refrigerants to choose from as well: specifically the family of R422 refrigerants. The intention is not to recommend one refrigerant over the other but rather to discuss the final considerations necessary to ensure the conversion is done properly. SEALS AND GASKETS Going back to the early years of converting systems using CFC refrigerants to HFC refrigerants, which also required removing the mineral oil and replacing it with POE (polyol ester) oil, it was commonplace to find multiple leaks in gasket/seal joints where there were none before. Since there were no leaks before the conversion, it was thought that the existing gaskets/seals were not compatible with the new refrigerants/oils. The fact is that there was another explanation for why these leaks were occurring. Let s take a look at the life of an elastomer seal such as an o-ring or quad-ring (tetra-seal), and how it prevents refrigerant from leaking out of the system. First, for a given application such as a common ME10S240 liquid line solenoid valve, the seal material is subjected to extensive testing for compatibility and performance prior to the first manufacturing production run. This testing is typically done by the valve manufacturer and verified by an independent lab before a decision to accept the material is made. In addition to selecting the proper seal material, a precisely sized groove is machined into one of the seal mating surfaces; this is where the seal will reside. During the production phase, the valve body, along with every other required part, is machined to its respective specifications. Final assembly includes fitting the specified seal into its groove, and tightening the joint to the specified torque setting. Prior to sending this valve out into the field, it TABLE 1 NEOPRENE TYPE W SWELL RATES is tested for operation and leakage. Once the valve is put into service, there are several factors that allow the seal to take a set, ensuring that it remains a good seal. These include the torque setting of the joint, the type of seal material, the size of the machined grove which the seal fits into, the pressure that the seal is subjected to (as a liquid line component in an R22 system it will regularly see pressures between 150 psi and 250 psi, perhaps more if the condenser is dirty), and the amount of swelling that the seal will EDITOR S NOTE: Parts I and II of this series ran in HPAC May/June and HPAC September/October. They can be found at Click DIGImag on the menu on the left to access HPAC s online magazine. experience when in contact with the refrigerant and oil. The elastomer swell rate, along with the pressure the seal is subjected to, are the variables which ultimately determine how effective an existing seal will remain after the conversion. In other words, will the conditions that the seal is subjected to before the conversion remain the same after the conversion? The answer is no. When the R22 is removed, the liquid pressure that would normally act against the seal is gone. When a vacuum pump is used to properly evacuate the system prior to adding the new refrigerant, a further reduction of the Neoprene Type W Seals Refrigerant & Oil Swell Rate Change in Swell Rate R22 with Mineral Oil 4.1% R404A with POE Oil 3.0% R22 with Mineral Oil initially; 4.1% to 2.6% -1.5% Converted to R404A with POE pressure acting against the seal occurs. Since the new refrigerant s pressuretemperature characteristics will be different than R22, the pressure acting against the seal is now different. With a conversion to R404A, it will go from the 150 to 250 psi range to the 175 to 300 psi range (for normal winter/summer condensing temperatures). The final variable is the swell rate (refer to Table 1). The swell rate for Neoprene Type W is greater when in the presence of R22 and mineral oil versus R404A and POE. If the original seal is reused, it actually experiences a net shrinkage of 1.5 per cent. This shrinkage, combined with temporarily relieving the pressure on the seal during CONTINUED ON PAGE HPAC 80 years NOVEMBER/DECEMBER 2006

2 St. Lawrence Chemical Inc. Exclusive distributor of Genetron refrigerants in Canada Ontario and Western Canada, Tel: Fax: Quebec and the Maritime Provinces, Tel: Fax: Circle #25

3 CONTINUED FROM PAGE 42 refrigerant removal/evacuation, then subjecting it to higher pressures with the new refrigerant, causes the seal set to be disturbed, resulting in a high leakage probability. Because of this situation, all elastomer seals must be replaced. In an effort to eliminate the swell factor, some manufacturers have changed to different (non-elastomer) seal types. Prior to January 1998, the FIGURE 1 ENCLOSING TUBE TORQUE SPEC. not essential that they be replaced during a conversion, but it is recommended. It is possible that some older vintages of ball valves will develop leaks after the conversion, particularly in the liquid applications. It may be prudent to replace liquid ball valves before the conversion. In addition, all access valve and seal caps, seals for the liquid level sensor in the receiver, EPR seals, and so on, should be replaced. If in doubt, any elastomer seal in the system should be replaced. TIGHTENING SEAL/GASKET JOINTS Typically, there is a specified torque setting for all seal joints. While it is recognized that most service trucks do not have a torque wrench on them, a technician should be able to feel the difference between a torque setting in the 10 to 15 ft/lb range and a 100 ft/lb setting. In today s climate of no leaks, some might think that a 16 crescent wrench with a three-foot cheater would be the best method for tightening all joints. But remember, it is not necessary to over tighten these joints. In fact over tightening may damage the elastomer seal and cause a leak. Additionally, over tightening some joints may cause valve damage. For example, the evaporator pressure regulator shown in Figure 2 has a very specific torque setting for the suction stop pilot solenoid enclosing the tube locknut; it is nine to 10 ft/lb. If over tightened, this may prevent the valve from opening. The enclosing tube plunger travels up and down in the enclosing tube as the coil is energized/de-energized. There is a small amount of clearance between the plunger and the opening in the lock nut. This allows the plunger to drop down and open the small suction stop pilot when de-energized. In this position, the suction stop pilot FIGURE 2 CUTAWAY VIEW OF PILOT ENCLOSING TUBE TORQUE SPEC: 9/10ft/lb Clearance Between The Enclosing Tube I.D. & Plunger Enclosing Tube Plunger Graphic Parker Hannifin Corporation above-mentioned ME10S240 solenoid valve used a tetra-seal (labelled enclosing tube gasket in Figure 1), set in a groove in the enclosing tube mating surface, to provide the seal between it and the valve body. The current seal is a rubberized metal flat gasket. It does not experience the same swell phenomenon as an elastomer, nor does it require a groove in the enclosing tube mating surface. Gaskets of this type are not subject to the disturbing the set issue that elastomer seals are. It is port is open, allowing high pressure vapour to pressurize the main piston chamber, forcing the valve closed. During the conversion, the enclosing tube seal would be replaced, and the lock nut re-tightened with the system shut down (coil de-energized). In the de-energized mode, the valve is in the suction stop mode. Over tightening the lock nut can cause deformation, changing the round hole into something more elliptical. This will constrict the plunger, preventing it from traveling up when the coil is energized. The result is a valve that is always in the suction stop mode (closed), even when the coil is energized. In most cases loosening the lock nut and re-tightening it to the specified torque setting will cause the hole to regain its original shape. 44 HPAC 80 years NOVEMBER/DECEMBER 2006

4 TEV PERFORMANCE It is the system conditions (evaporator temperature, liquid temperature, and P across the thermostatic expansion valve (TEV) port) that determine what the actual TEV capacity is. If a supermarket refrigeration rack is outfitted with a liquid subcooler, and the design calls for a 60F liquid refrigerant temperature, you can be assured that the original TEVs were selected based upon this fact. The new TEVs will also have been selected based upon the 60F liquid temperature. Therefore, for proper TEV operation, it is important to ensure that the subcooler circuit is supplying liquid refrigerant at the design condition. It goes without saying that every TEV should be checked to see if it is maintaining the proper superheat at the evaporator outlet. If the superheat is not correct, the TEV should be adjusted. will counterbalance the higher operating pressure of the refrigerant in the system. If the R404A element is used on an R22 system, the opening force would be much greater than required, due to the higher pressure fluid in the CONTINUED ON PAGE 46 R404A bulb. This would cause the TEV to open more than it should for a given condition. CONTROL SETTINGS Evaporator pressure regulating valves TIMEFRAME FOR REPLACEMENT There may be a desire to replace as many components as possible before the R22 is removed. The one component that cannot be replaced prior to the conversion is the TEV. There are two reasons for this: 1) A nominal one-ton R22 TEV will typically be replaced with a nominal one-ton R404A TEV. A given TEV port size will yield a greater capacity with R22 as opposed to R404A. So, the nominal one-ton R404A TEV, if installed before the refrigerant is replaced, becomes a nominal 1-1/2 ton TEV when used with R22 and it is oversized. 2) The thermostatic element on the R404A valve is designed to provide the correct pressure on the top of the element diaphragm to counteract the evaporator pressure of the refrigerant in use. For a 25F saturation temperature the corresponding pressure will be 49 psi for R22 and 62 psi for R404A. Therefore, the fluid charge in the sensing bulb of the R404A element would have to supply an additional 15 psi as compared to the R22 fluid, so that it Moving away from R-22 just got easier. Introducing DuPont ISCEON MO59 and ISCEON MO79. These non-ozone depleting refrigerants provide you with easy-to-use, cost-effective retrofit options to help your customers avoid costly equipment replacement or interruptions while reducing the use of ozone depleting substances. With over 75 years as a leader in the refrigerants industry, we re committed to providing you with reliable, proven and safe alternatives for CFC and HCFC systems. To find the right products, call your local DuPont Refrigerants distributor. DuPont Refrigerants. The Science of Cool. Copyright 2006 E.I. du Pont de Nemours and Company. All rights reserved. The DuPont Oval Logo, DuPont, The miracles of science, The Science of Cool and ISCEON are registered trademarks or trademarks of E.I. du Pont de Nemours and Company or its affiliates. Circle #26 NOVEMBER/DECEMBER years HPAC 45

5 CONTINUED FROM PAGE 45 (EPR valves) maintain fairly consistent fixture discharge air temperature by maintaining a constant refrigerant saturation temperature in the evaporator. For example, if the design condition for a particular system calls for a 17F refrigerant saturation temperature, and assuming a pressure loss in the piping is equivalent to a 2F change in saturation temperature, this will be maintained by an EPR setting of 38 psi for R22. After a conversion to R404A, the EPR setting will need to be raised to 49 psi. The rack controller, which attempts to maintain a fairly constant common suction pressure by cycling compressors on/off, will also require resetting. For example, the ice cream case lineup will typically be the lowest operating system on the low temperature rack. If the design calls for a -20F saturation temperature for this system, the corresponding pressure (allowing for a pressure drop equal to a 2F change in saturation temperature) would be nine psi for R22. After a conversion to R404A, this pressure will increase to 15 psi. The condenser fan cycling pressure controls and the head pressure control valves (holdback valve and receiver pressurization valve) are used to prevent the condensing temperature (pressure) from falling below a certain level. If, for example, the design minimum condensing temperature is 80F, the holdback valve would be set for 147 psi with R22. After the conversion to R404A, the holdback valve must be reset to 175 psi. If a split condenser valve is used, and is controlled by pressure, it will also need to be reset. Likewise, the highpressure cut-out controls will require resetting. It is likely that the high-pressure relief valves will also require replacing. FOOD FOR THOUGHT A deepening concern over how we treat our environment, our world, our home (specifically regarding the issues of global warming and ozone depletion) has elevated the topic of refrigerant conversions to the level of importance it now commands. Those of us earning a living in the HVAC/R industry who were less aware certainly now know the impact refrigerant leaks are having on our environment. At the very least government actions have forced us to face the monumentally negative impact refrigerant leaks and improper refrigerant management can have on cash flow. Does the average consumer care about this yet? Many companies seem to believe they do, as evidenced by the large budgetary expenditures devoted to green campaigns. It is my feeling that when Joe Couch-Potato wants a new big screen plasma television, it is the price that determines where he decides to make his purchase. I would be surprised if any variation of the following dialogue ever takes place: Say, I like the price on the plasma TV. I just have one final question; what refrigerant are you currently using in your store s cooling equipment? As if the sales attendant would even know, but the answer might be: Well, we are still using R22. Joe s reply is stunning: Well then, I m afraid I will not be able to support your business until you become a little more environmentally engaged. This scenario is not happening soon but we can hope that, at some point in time, consumer pressure will become a larger factor in the environmental equation. Dave Demma FILTER ISSUES All liquid filter driers, suction filters and oil filters should be replaced. Due to the affinity POE has for moisture, a high water capacity filter drier should be used. POE has the ability to scrub contaminants from the interior walls of the tubing, the compressor, components, and so on, and bring them back into circulation. Because of this, it should be anticipated that there might be contamination problems after the conversion. This should be monitored closely, with additional filter drier replacement as the required remedy. THE FINAL ACT A complete system evacuation must be done before adding the new refrigerant. After the conversion, a thorough leak check should be done. The last thing you want to tell your customer, after they have spent a small fortune on the conversion, is that there were a few leaks. A proper refrigerant conversion is no small task. Allow ample time for ordering parts and creating a plan of attack. Make sure that adequate manpower is available, as the refrigerated product has a limited life while the equipment is inoperative. If required, dry ice can be obtained to keep the product reasonably cold. While conversions seem to be a daunting challenge, like any difficult task they will get easier with repetition. Dave Demma holds a degree in refrigeration engineering and worked as a journeyman refrigeration technician before moving into the manufacturing sector where he regularly trains contractor and engineering groups. He can be reached at , ext RATE THE ARTICLE! Will this information be useful? Please circle the appropriate number on the Reader Postcard. Thank you. VERY USEFUL USEFUL NOT USEFUL HPAC 80 years NOVEMBER/DECEMBER 2006

6

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL BY DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL In the September/October 2005 issue of HPAC Magazine, the case was made for reducing head pressure to increase compressor efficiency, thereby lowering its

More information

DAVE DEMMA REDUCING ELECTRICAL CONSUMPTION

DAVE DEMMA REDUCING ELECTRICAL CONSUMPTION BY DAVE DEMMA REDUCING ELECTRICAL CONSUMPTION It is said that necessity becomes the mother of invention. As energy prices soared in the 1970s, supermarket owners sought ways to reduce their enormous utility

More information

DuPont ISCEON 9 Series Refrigerants

DuPont ISCEON 9 Series Refrigerants ISCEON 9 Series Refrigerants P R O D U C T I N F O R M A T I O N G U I D E Refrigerants. The Science of Cool. TM de Nemours International S.A. 2 Chemin du Pavillon P.O. Box 50 CH-1218 Le Grand-Saconnex

More information

DuPont Refrigerants. John McCormack Business Manager DuPont Chemicals and Fluoroproducts. R22 market and the ISCEON retrofit options

DuPont Refrigerants. John McCormack Business Manager DuPont Chemicals and Fluoroproducts. R22 market and the ISCEON retrofit options DuPont Refrigerants R22 market and the ISCEON retrofit options Airefrig November 2010 John McCormack Business Manager DuPont Chemicals and Fluoroproducts HCFC Regulations & ISCEON 3 Actions Impacting Fluorochemicals

More information

Sporlan Valve Division Parker Hannifan/CIC Group

Sporlan Valve Division Parker Hannifan/CIC Group www.parker.com/cic Sporlan Valve Division Parker Hannifan/CIC Group Matt McGrath, SW Regional Sales Manager Bob Dolan, Sales Engineer - Atlanta www.parker.com/cic Why Discuss TEVs Today? Expansion Valves

More information

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation Form 30-217 / January 2007 Heat Reclaim Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation While the vapor-compression cycle has

More information

refrigeration THE GOODS ON OIL FAILURE TRIPS

refrigeration THE GOODS ON OIL FAILURE TRIPS refrigeration BY DAVE DEMMA THE GOODS ON OIL FAILURE TRIPS Do you remember that service call you were dispatched to where the frozen food was melting in the display cases? Upon arrival you found the compressor

More information

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job. June 01 / BULLETIN - 3-Way Valves The right solenoid valve for any job. Page 2 / Bulletin - Advantages Sporlan 3-Way Valves 3-Way Pilot eliminates costly high- to low-side leaks. "B" reduces total installed

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

A Treatise on Liquid Subcooling

A Treatise on Liquid Subcooling A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance

More information

System Considerations for Refrigerant Blends with Temperature Glide

System Considerations for Refrigerant Blends with Temperature Glide System Considerations for Refrigerant Blends with Temperature Glide Theory and Practical Retrofit Guidance Table of Contents 1 2 3 4 5 Blend and Glide Basics... 3 1.1 Superheat and Subcooling of Refrigerant

More information

Bulletin , March Electric Hot Gas Bypass Valves

Bulletin , March Electric Hot Gas Bypass Valves Bulletin 100-60, March 2018 Electric Hot Gas Bypass Valves PAGE 2 / Bulletin 100-60 10 FEATURES AND BENEFITS SDR-4 Direct temperature control Tight shutoff when closed Can be interfaced with direct digital

More information

10/4/2013. The Changing State of Refrigerants

10/4/2013. The Changing State of Refrigerants 10/4/2013 The Changing State of Refrigerants Refrigerant Chemistry CFC = Chlorofluorocarbon Rapid phase-out Stopped U.S. production in 1996 R-11, R-12, R-113, R-114, R-500, R-502 HCFC = Hydrochlorofluorocarbon

More information

Capacity regulators, type CPCE and LG REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Capacity regulators, type CPCE and LG REFRIGERATION AND AIR CONDITIONING. Technical leaflet Capacity regulators, type CPCE and LG REFRIGERATION AND AIR CONDITIONING Technical leaflet Introduction CPCE capacity regulators adapt compressor capacity to actual evaporator load. They are designed for

More information

410AREFRIGERANTTRANSITIONGUIDE

410AREFRIGERANTTRANSITIONGUIDE Contactyourlocal ValueFirstrepresenta ve byvisi ng www.valuefirstonline.com/local 410AREFRIGERANTTRANSITIONGUIDE Replace-Retrofit-Repair (seenextpagefordetails) REPLACE OR REPAIR? OUR HVAC EVALUATION HELPS

More information

Refrigerant changeover guidelines

Refrigerant changeover guidelines Refrigerant changeover guidelines HCFC R-22 to HFC R-407A/F, R-448A or R-449A for medium and low temperature applications HCFC R-22 to HFC R-407C for high, medium and low temperature applications HCFC

More information

Technical Review. Remote Condenser Cuber. Enhanced Refrigeration and Water Systems. CM 3 Technology. of a. with. using. models included are:

Technical Review. Remote Condenser Cuber. Enhanced Refrigeration and Water Systems. CM 3 Technology. of a. with. using. models included are: Technical Review of a Remote Condenser Cuber with Enhanced Refrigeration and Water Systems using CM 3 Technology models included are: CME1356 shown on BH900 CME456, CME1056, CME1356, CME1656 and CME2006

More information

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES November 2006 / BULLETIN -60 ELECTRIC DISCHARGE BYPASS VALVES PAGE 2 / Bulletin -60 10 FEATURES AND BENEFITS Direct temperature control Tight shutoff when closed Can be interfaced with direct digital controls

More information

RDT Refrigeration Book

RDT Refrigeration Book RDT Refrigeration Book Indoor / Outdoor Air-Cooled Systems Indoor Air-Cooled Systems 1. Shorter line runs. 2. Systems located off roof or dock space. 3. Weather covers are not required (saves cost). 4.

More information

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During

More information

The Essentials Of Working With R-410A

The Essentials Of Working With R-410A The Essentials Of Working With R-410A By Norm Christopherson Several major manufacturers are producing comfort air conditioning equipment using refrigerant 410A. The trend towards the use of 410A continues

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

Gary Parker Refrigerants Product Manager

Gary Parker Refrigerants Product Manager Gary Parker Refrigerants Product Manager Refrigerant f i t History Status of the HCFC ( R22) Phase out Ozone Friendly Alternativesti Choosing the Best Retrofit Solution Lubricants and how they impact performance

More information

USING THE P-T CARD AS A SERVICE TOOL

USING THE P-T CARD AS A SERVICE TOOL Service Application Manual SAM Chapter 620-115 Section 2 USING THE P-T CARD AS A SERVICE TOOL Reprinted with permission from Sporlan Division, Parker Hannifin Corporation INTRODUCTION Manufacturers of

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012 SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate Technologies, Inc. does not advocate

More information

Air Conditioning Operation and Troubleshooting Matt Dunham

Air Conditioning Operation and Troubleshooting Matt Dunham Air Conditioning Operation and Troubleshooting Matt Dunham Major Components (10 Minutes) Compressor heart of the system, causes refrigerant to flow by increasing the pressure of the refrigerant Metering

More information

Gary Parker Refrigerants Product Manager

Gary Parker Refrigerants Product Manager Gary Parker Refrigerants Product Manager Refrigerant History Status of the HCFC ( R22) Phase out Ozone Friendly Alternatives Choosing the Best Retrofit Solution Lubricants and how they impact performance

More information

Webinar: HVAC Claims Repair versus Replace Presenter: Curtis VanNess, General Manager HVAC Forensics Webinar Questions & Answers

Webinar: HVAC Claims Repair versus Replace Presenter: Curtis VanNess, General Manager HVAC Forensics Webinar Questions & Answers Webinar: HVAC Claims Repair versus Replace Presenter: Curtis VanNess, General Manager HVAC Forensics Webinar Questions & Answers Q: Can you explain how a swamp cooler works and/or is different? A swamp

More information

Warm Case Troubleshooting Guide 9/18/2014

Warm Case Troubleshooting Guide 9/18/2014 Introduction Warm cases can be caused by various problems which require thorough troubleshooting. Begin the investigation with questions to store personnel asking for information such as when the last

More information

What Is Liquid Subcooling?

What Is Liquid Subcooling? VA Lake City Florida Rob, Though I still haven t received the information from the contractor for this project, I have done some preliminary work on it. One thing of concern to me is something that you

More information

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration

More information

EcoVision II Plus Door Upgrade for D6 Kysor Warren Multi-deck Merchandisers

EcoVision II Plus Door Upgrade for D6 Kysor Warren Multi-deck Merchandisers EcoVision II Plus Door Upgrade for D6 Kysor Warren Multi-deck Merchandisers IMPORTANT Keep in store for future reference! Installation & Operation Manual P/N 0537298_A July 2014 MANUAL- I/O ECOVISION II

More information

The Changing State of Refrigerants. Gary Parker Refrigerants Product Manager

The Changing State of Refrigerants. Gary Parker Refrigerants Product Manager The Changing State of Refrigerants Gary Parker Refrigerants Product Manager The Changing State of Refrigerants Acronyms you may want to know CARB California Air Resources Board GWP Global Warming Potential

More information

REFRIGERANT CHANGEOVER

REFRIGERANT CHANGEOVER Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants

More information

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the XSTREAM Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications. TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there

More information

PL Series Premier Indoor Plenum Coils

PL Series Premier Indoor Plenum Coils IM-PLC-0667392-04 April 2016 PL Series Premier Indoor Plenum Coils Installation Instructions GENERAL ADP evaporator coils are designed for use with condensing units or heat pump units. These instructions

More information

R.A.S.E.R.S System. Installation Guide

R.A.S.E.R.S System. Installation Guide R.A.S.E.R.S System Installation Guide Contents R.A.S.E.R.S System components... 1 Required components for heating, cooling, and hot water...1 Provided...1 Not provided...2 Optional components...3 R.A.S.E.R.S

More information

JEFFERSON COLLEGE COURSE SYLLABUS HRA125 REFRIGERATION AND A/C MECHANICAL SYSTEMS. 5 Credit Hours. Prepared by William Kaune November 30, 2010

JEFFERSON COLLEGE COURSE SYLLABUS HRA125 REFRIGERATION AND A/C MECHANICAL SYSTEMS. 5 Credit Hours. Prepared by William Kaune November 30, 2010 JEFFERSON COLLEGE COURSE SYLLABUS HRA125 REFRIGERATION AND A/C MECHANICAL SYSTEMS 5 Credit Hours Prepared by William Kaune November 30, 2010 Mary Beth Ottinger, Division Chair, Business & Technical Education

More information

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS INTRODUCTION Please note that HUD Manufactured Home Construction and Safety Standard Section 3280.714, paragraph (a) and subparagraph

More information

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane.

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane. 1/1/12 RS-45 (R434A): Q & A 1 Q: What is RS-44? 1.Q: What is RS-45 A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-45 contain? A: RS-45 is

More information

Refrigerants Management & Retrofits. Mike Saunders & Randy Tebbe Emerson Climate Technologies

Refrigerants Management & Retrofits. Mike Saunders & Randy Tebbe Emerson Climate Technologies Refrigerants Management & Retrofits Mike Saunders & Randy Tebbe Emerson Climate Technologies Agenda Refrigerant Landscape and Proposed Regulation Review Life Cycle Climate Performance Refrigerant Phase-Down

More information

HVAC Basics RESIDENTIAL AIR CONDITIONING

HVAC Basics RESIDENTIAL AIR CONDITIONING HVAC Basics RESIDENTIAL AIR CONDITIONING Introduction This Instructor s Guide provides information to help you get the most out of Residential Air Conditioning, part of the two-part series HVAC Basics.

More information

Energy Use in Refrigeration Systems

Energy Use in Refrigeration Systems 2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is

More information

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois Althouse Turnquist Bracciano PowerPoint Presentation by: Associated Technical Authors Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois Chapter 5 Explain the purpose and operation of

More information

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS English Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Instruction Manual

More information

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications: TECHNICAL DATA SHEET Features and uses of is a non-azeotropic blend of HFC with zero Ozone Depletion Potential et low Global Warming Potential (GWP), formulated to meet the requirements of the F-Gas Regulation

More information

Otherwise, you can continue reading the file on the following pages.

Otherwise, you can continue reading the file on the following pages. If you d like to be able to print this file out to study off-line or use on the job, a printable version is available for an administrative fee of $3.97 USD. To download the unlocked file, click here.

More information

Installation Instructions

Installation Instructions Installation Instructions THERMAL EXPANSION VALVE (TXV) KIT FOR HEAT PUMP AND AIR CONDITIONING SAFETY INFORMATION IMPORTANT: Please read all instructions before servicing this equipment. Pay attention

More information

A/C-HEATER SYSTEM - MANUAL

A/C-HEATER SYSTEM - MANUAL A/C-HEATER SYSTEM - MANUAL 1986 Isuzu Trooper II 1986 A/C-HEATER SYSTEM Isuzu A/C-Heater Systems - Manual P UP, Trooper II * PLEASE READ THIS FIRST * CAUTION: When discharging air conditioning system,

More information

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE INSTRUCTIONS AND COMPETITION DETAILS INSTRUCTIONS ET DÉTAILS DU CONCOURS REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE 1. Test Project Details This

More information

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA Daniel Giguère, Technology Expert Georgi Pajani, Engineer Sophie Hosatte, Section Head, Buildings CETC-Varennes, Natural

More information

Peachtree City is home office for America located about 30 miles south of the Atlanta airport this is were all KM cubers as well as Flakers are built.

Peachtree City is home office for America located about 30 miles south of the Atlanta airport this is were all KM cubers as well as Flakers are built. The following slides are designed to give you good understanding of the KM sequence of operation. You will find the sequence explained in two ways the first is a basic explanation that goes along with

More information

SERVICE ASSISTANT OVERVIEW FDSI Online Training

SERVICE ASSISTANT OVERVIEW FDSI Online Training Author: Dale T. Rossi Online Editor: Zachary Williams SERVICE ASSISTANT OVERVIEW FDSI Online Training May 5, 2009 Table Service Assistant Description... 2 Installing the Main Unit... 3 Ambient Temperature...

More information

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

AE October 1965 Reformatted October Hot Gas Bypass Control Systems Hot Gas Bypass Control Systems AE21-1160 AE21-1160 October 1965 Reformatted October 2010 On many refrigeration and air conditioning systems, the refrigeration load will vary over a wide range. This may

More information

R-407A R-448A R-449A

R-407A R-448A R-449A GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants

More information

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the MYSTICOOL Max Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

an ISO 9001:2015 Registered Company

an ISO 9001:2015 Registered Company an ISO 9001:2015 Registered Company Mark IV (672001-VHY) 18865 Goll St. San Antonio, TX 78266 Phone: 800-862-6658 Sales: sales@vintageair.com Tech Support: tech@vintageair.com www.vintageair.com 902001-VHY

More information

NZQA Expiring unit standard 3397 version 4 Page 1 of 5. Convert an automotive air conditioning system from R-12 to R-134a

NZQA Expiring unit standard 3397 version 4 Page 1 of 5. Convert an automotive air conditioning system from R-12 to R-134a Page 1 of 5 Title Convert an automotive air conditioning system from R-12 to R-134a Level 3 Credits 2 Purpose This unit standard is for people in the automotive repair industry. People credited with this

More information

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax: TECHNICAL MANUAL CX(E) SPLIT SYSTEMS CONTENTS INDEX PART NUMBERS, OPTIONS, UNIT COMBINATIONS, DIMENSIONS & WEIGHTS 3 PERFORMANCE DATA & AIR FLOW 4 SOUND POWER AND SOUND PRESSURE LEVELS 5 ELECTRICAL DATA

More information

Hot gas bypass regulator, type CPCE Liquid gas mixer, type LG (accessory)

Hot gas bypass regulator, type CPCE Liquid gas mixer, type LG (accessory) Data sheet Hot gas bypass regulator, type CPCE Liquid gas mixer, type LG (accessory) CPCE hot gas bypass regulator adapt compressor capacity to actual evaporator load. They are designed for installation

More information

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER Numbers of Abstract/Session (given by NOC) - 1 - DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER Richard W. Murphy Van D. Baxter Edward A. Vineyard Randall L.

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

THERMOSTATIC EXPANSION VALVES Part 2

THERMOSTATIC EXPANSION VALVES Part 2 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 THERMOSTATIC EXPANSION VALVES Part 2 Revised by Loren Shuck, CMS INTRODUCTION The previous chapter dealt briefly with

More information

Refrigerants. Retrofit Guideline. Commercial Refrigeration Systems Medium Temperature R-12, R-401A & R-409A to Solstice N13 (R-450A) & Genetron 134a

Refrigerants. Retrofit Guideline. Commercial Refrigeration Systems Medium Temperature R-12, R-401A & R-409A to Solstice N13 (R-450A) & Genetron 134a Refrigerants Retrofit Guideline Commercial Refrigeration Systems Medium Temperature R-12, R-401A & R-409A to Solstice N13 (R-450A) & Genetron 134a Table of Contents Introduction.... 1 Refrigerant Comparison...

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

HVAC/R Refrigerant Cycle Basics

HVAC/R Refrigerant Cycle Basics HVAC/R Refrigerant Cycle Basics This is a basic overview of the refrigeration circuit and how it works. It isn t a COMPLETE description by any means, but it is designed to assist a new technician or HVAC/R

More information

Before I start on this one At HVAC School we focus on a wide range of topics, many of them are very basic. My experience as a trainer for over 16

Before I start on this one At HVAC School we focus on a wide range of topics, many of them are very basic. My experience as a trainer for over 16 Refrigerant Charging Basics For Air Conditioning & Heat Pump Systems Before I start on this one At HVAC School we focus on a wide range of topics, many of them are very basic. My experience as a trainer

More information

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

Aspects of the. Following these key guidelines during a compressor changeout can ensure a successful, more efficient replacement.

Aspects of the. Following these key guidelines during a compressor changeout can ensure a successful, more efficient replacement. Aspects of the Compressor Retrofit Following these key guidelines during a compressor changeout can ensure a successful, more efficient replacement. B y J o h n P r a l l a n d D e n n y M a r t i n All

More information

Reducing Refrigerant Leakage

Reducing Refrigerant Leakage Reducing Refrigerant Leakage Mike Nankivell F.Inst.R Marketing Director Space Airconditioning plc President of HEVAC Chairman ACRIB F Gas Group An Introduction to Real Zero Information provided by Cool

More information

Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C

Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C McQuay International (A Member of the DAIKIN Group) Hydrofluorocarbon (HFC) refrigerants are critical to the safe and cost-effective phase-out

More information

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit

More information

Models Series Series

Models Series Series Models 31800-Series 31801-Series INDUSTRIAL DIAPHRAGM PUMPS 4 GPM/15 LPM FEATURES Self-Priming Easy Installation Can run dry without damage Low Amp Draw Flow to 4 GPM/15 LPM Compact Size Thermal Overload

More information

Chapter 2. Alternatives to HCFCs and their Characteristics

Chapter 2. Alternatives to HCFCs and their Characteristics Alternatives to HCFCs and their Characteristics Refrigerant - General Chemical used in a cooling system, such as an air conditioner or refrigerator, as the heat carrier which changes from vapour to liquid

More information

PULSE WIDTH MODULATING VALVES

PULSE WIDTH MODULATING VALVES PULSE WIDTH MODULATING VALVES PARKER PULSE WIDTH MODULATING VALVES MODEL HP P4144 MODELS CS & DS P4145 Features Long life (100 million cycles). Suitable for all common refrigerants except ammonia. Maximum

More information

DuPont Formacel Z-2. Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications FOAM EXPANSION AGENT TECHNICAL INFORMATION

DuPont Formacel Z-2. Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications FOAM EXPANSION AGENT TECHNICAL INFORMATION DuPont Formacel Z-2 FOAM EXPANSION AGENT TECHNICAL INFORMATION Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications Flammability of Formacel Z-2 and Other Alternative

More information

Models Series Series

Models Series Series Models 3180-Series 3181-Series INDUSTRIAL DIAPHRAGM PUMPS Commercial Duty, 3 GPM/1 LPM FEATURES Sealless Easy Installation Run Dry Ability Flow to 3 GPM/1 LPM Self-Priming Low Amp Draw Thermal Overload

More information

PRELIMINARY INSTALLATION. Operation & Service Manual. Carrier Transicold Europe 03/09/07 Viento - Installation/Rev- #1/56

PRELIMINARY INSTALLATION. Operation & Service Manual. Carrier Transicold Europe 03/09/07 Viento - Installation/Rev- #1/56 INSTALLATION Carrier Transicold Europe 03/09/07 Viento - Installation/Rev- #1/56 INSTALLATION Table of content Introduction...4 Preparation before installation...5 Vehicle partition... 6 Box preparation...7

More information

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold LOW VAC INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold REF HIGH SPECIAL FEATURES Low battery indicator Displays 63 refrigerants Displays corresponding saturation, dew or bubble point temperature

More information

EXPANSION VALVES. See Red Dot Catalog Also. * 2 ton valves - all other valves are 1 1/2 ton (1) Includes M1 Adapter 71R8050 EX02280

EXPANSION VALVES. See Red Dot Catalog Also. * 2 ton valves - all other valves are 1 1/2 ton (1) Includes M1 Adapter 71R8050 EX02280 EXPANSION VALVES See Red Dot Catalog Also PART NO. DESCRIPTION INLET OUTLET FITTING -- INTERNAL EQUALIZED 20359 INTERNAL EQUALIZED 38722 INTERNAL EQUALIZED FITTING -- EXTERNAL EQUALIZED 71R8050 EXTERNAL

More information

Refrigeration Systems and Accessories

Refrigeration Systems and Accessories As with the Chapter Review Tests and the Final Exam, the tests your understanding of the materials underlying the learning objectives. After you ve reviewed your answers to the Chapter Review Tests, try

More information

The rotary type compressor consists of an integrally formed rotor and shaft, five vanes, and a cylinder.

The rotary type compressor consists of an integrally formed rotor and shaft, five vanes, and a cylinder. W1860BE.book Page 12 Tuesday, January 28, 2003 11:01 PM 2. Cooling System A: COMPRESSOR The rotary type compressor consists of an integrally formed rotor and shaft, five vanes, and a cylinder. As the rotor

More information

DEEP VACUUM: ITS PRINCIPLE AND APPLICATION

DEEP VACUUM: ITS PRINCIPLE AND APPLICATION Service Application Manual SAM Chapter 630-158 Section 2C DEEP VACUUM: ITS PRINCIPLE AND APPLICATION Adapted from material provided by JB Industries. Reprinted with permission. INTRODUCTION With the deep

More information

Carwin COMPRESSOR SELECTION PROGRAM

Carwin COMPRESSOR SELECTION PROGRAM Carwin COMPRESSOR SELECTION PROGRAM IMPORTANT! READ CAREFULLY BEFORE USING By using this disk covering a software program entitled CARLYLE SELECTION PROGRAM WINDOWS (Software), you indicate your acceptance

More information

Fundamentals of Refrigeration Part 2 Refrigeration 1

Fundamentals of Refrigeration Part 2 Refrigeration 1 Fundamentals of Refrigeration Part 2 Refrigeration 1 We have established in the first part of this training session that cooling in a DX coil is the result of the latent heat of vapourisation which is

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

Q.: I liked our single stream recycling. It was easier and more convenient. This is a step backwards. Why?

Q.: I liked our single stream recycling. It was easier and more convenient. This is a step backwards. Why? FREQUENTLY ASKED QUESTIONS REGARDING THIS CHANGE: Q.: I liked our single stream recycling. It was easier and more convenient. This is a step backwards. Why? A.: This is not a change we wanted to make;

More information

4/19/2013. The Changing State of Refrigerants

4/19/2013. The Changing State of Refrigerants 4/19/2013 The Changing State of Refrigerants Refrigerant Chemistry CFC = Chlorofluorocarbon Rapid phase-out Stopped U.S. production in 1996 R-11, R-12, R-113, R-114, R-500, R-502 HCFC = Hydrochlorofluorocarbon

More information

The complete approach to the care and management of A/C & refrigeration systems

The complete approach to the care and management of A/C & refrigeration systems The complete approach to the care and management of A/C & refrigeration systems Testing oil with the Phase III Refrigeration Oil Acid Test Kit Flushing with OEM endorsed R x 11-flush Acid removal with

More information

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

SOLENOID VALVES FOR REFRIGERATING SYSTEMS SOLENOID VALVES FOR REFRIGERATING SYSTEMS APPLICATIONS The solenoid valves, shown in this chapter, are classified Pressure accessories in the sense of the Pressure Equipment Directive 97/23/EC, Article

More information

NORDYNE has received reports of malfunctioning TXV valves in ton split systems and package units.

NORDYNE has received reports of malfunctioning TXV valves in ton split systems and package units. To: Residential Distributors and Dealers Aftermarket Distributors and Dealers From: Technical Service Department Date: September 9, 2014 RE: POE Oil Contamination 1.5 3 Ton Split Systems and Package Units

More information

High Profile Evaporator

High Profile Evaporator PRODUCT DATA & INSTALLATION Bulletin K30-KHPA-PDI-5 Part # 1081585 PRODUCT SUPPORT web: k-rp.com/khp email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: High Profile Evaporator High & Medium Temperature

More information

How to Diagnose a TXV Failurek

How to Diagnose a TXV Failurek How to Diagnose a TXV Failurek There has been much written and many jokes made about the misdiagnosis of TXV (Thermostatic expansion valves) and rightly so. This article will cut straight to the point

More information

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the operation of reverse-cycle refrigeration (heat pumps) Explain

More information

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999 TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO. 8801469 EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999 THE MILK COOLING SYSTEMS SPECIALISTS TM FRE-HEATER Part No. 8801469 Table

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

MASS. MARITIME ACADEMY

MASS. MARITIME ACADEMY MASS. MARITIME ACADEMY REFRIGERATION LAB OUTLINE Rev.3 Fall 2015 Table of Content Page Lab #1: Introduction to refrigeration system components, tools and procedures 1 Lab #2: Familiarization, operation,

More information