INSTRUCTIONS FOR ASSEMBLY, OPERATION AND MAINTENANCE OF AIR HANDLING UNITS

Size: px
Start display at page:

Download "INSTRUCTIONS FOR ASSEMBLY, OPERATION AND MAINTENANCE OF AIR HANDLING UNITS"

Transcription

1 INSTRUCTIONS FOR ASSEMBLY, OPERATION AND MAINTENANCE OF AIR HANDLING UNITS ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 1 /40

2 Copyright Soko Inzinjering d.o.o. DDS January 2013 Information in this manual is subject to change or alterate without prior notice. Warning, Hazardous Voltage: All work to be performed by trained personnel only. All electrical installation and servicing of the electrical components of this unit to be performed by qualified electricians only. Disconnect power supply before installation and servicing! ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 2 /40

3 CONTENTS Table of contents INTRODUCTION General Safety Instructions Emergency Instructions Maintenance and Cleaning Instructions... 6 ASSEMBLY Delivery Unloading and Transport Unloading and Conveyance by Crane Unloading and Conveyance by Forklift Truck Assembly and Installation Installation of Section Connection of Sections Connection with Air Ducts Pipe Connectors of Heater and Cooler Connector for Condensate Drain Cleaning Electric Power Supply Protection of Motor MAINTENANCE Air Dampers Putting into operational mode Maintenance Fan and Motor Putting into operational mode Maintenance Determining the tensile force of V-Belt for V-Belt transmission Maintenance switch Filters Putting into operational mode Maintenance Silencers Putting into operational mode Maintenance Heater Heat Echanger (warm water /hot water, steam) Putting into operational mode ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 3 /40

4 12.2. Maintenance Electric Heater Putting into operational mode Maintenance Cooler Heat Echanger (cold water, direct epansion cooler) Putting into operational mode Maintenance CERTIFICATES - CONFIRMATION OF QUALITY Certificate CE mark GOST R Certificate GOST hygienic Certificate GOST ATEX Certificate EUROVENT CERTITA Certificate... Error! Bookmark not defined. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 4 /40

5 INTRODUCTION 1. General Attention This Instruction for assembly and maintenance should be read and observed by all persons having some influence on operation of Air Handling Unit. In case that some components are not described, individual instructions (require if necessary) shall be observed. Soko Inzinjering will not assume responsibility for any damage caused by nonobserving this Instruction. In case of illegal modifications or interventions on the Unit, the manufacturer s warranty will not be valid any more. Use for intended purposes Necessary space Storing Assembly Before commissioning The Air Handling Unit delivered by Soko Inzinjering is eclusively intended for air conditioning. Air conditioning means filtering, heating, cooling, humidifying, dehumidifying and transport of air. Soko Inzinjering epressly forbids any other type of use. Provide sufficient space for operation and maintenance of the Unit, in accordance with VDI The Air Handling Unit and all its parts must be stored in appropriate way, preventing damage or atmospheric influences. During the storage which eceeds 3 months, V-belt shall be removed and rotating parts of fan, motor, etc. shall be rotated once a month. If the Air Handling Unit is delivered in separate sections, they shall be assembled in accordance with this Instruction for assembly and all protective devices shall be efficiently mounted. A person trained for handling the Unit is responsible for assembly on the spot and replacement of fied parts, and shall also be responsible for issuance of the Certificate of Compliance. The Air Handling Unit can be set into operation only after the parts are assembled in compliance with this Instruction. All protective devices shall be mounted and checked Service switch must be mounted near the door of the ventilation section. Electric installation in accordance with regulations. 2. Safety Instructions Danger Serious injures and material losses can be caused if the following instructions are not observed, as well as applicable safety regulations. Access and work on the Unit is allowed only when the following requirements are met: All devices are disconnected from electric power supply. Minimum waiting period for frequency converter is 15 minutes (due to residual stress). Protection against subsequent switching in according to EN (e.g. block stop switch for repairs service switch.) ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 5 /40

6 Wait until all rotating parts are stopped, especially the fan impeller, V-belt, motor, etc. Heat echangers shall cool to room temperature. Protective clothing shall be worn. After the work is completed, the following requirements shall be met before setting the Air Handling Unit into operation: Protective devices must be mounted and efficient as per JUS EN 294 (e.g. protective network). Check that no person is present in dangerous zone (e.g. within the Unit). Only trained personnel shall operate the device. 3. Emergency Instructions Fire In case of fire, immediately disconnect all devices from electric power supply. Close air dampers and fire flaps in order to prevent oygen supply and prevent fire spreading. Carry out quickly antifire measures. Personal safety is more important than material safety. Danger Serious bodily injuries even loss of life can be caused by inhaling smoke (combustion products). Used construction materials can produce toic substances. Use protective breathing apparatus (gas mask or similar.)! Eplosion of high pressure vessels or pipelines caught by fire can cause serious bodily injuries and property damage. Do not approach dangerous (critical) area! 4. Maintenance and Cleaning Instructions Air Handling Units are devices which require regular maintenance. Maintenance is carried out periodically in approimate time intervals depending on air pollution in accordance with VDI If the air is more polluted, the intervals between two maintenance interventions shall be shorter accordingly. Regular maintenance does not release the operator from performing daily checks of the operation of the Air Handling Unit. Cleaning and maintenance Disinfection Commissioning Leak-proof test Casing Clean dry foulness with industrial aspirator. Use moistened cloth if cleaning agent with lubricant and oil solution is necessary. Treat galvanised parts with protective spray. Regularly treat all moving parts such as door handles, hinges with lubrication spray Use only alcohol based disinfecting agent. After maintenance and/or disinfecting measures, maintain sufficient cleanness before setting the Unit into operation again. Toic or offensive smelling substances shall not come in contact with inlet air by which air-conditioned space is supplied. In clean zones where, due to special circumstances, transmission from outlet to inlet air must not occur, all vital parts shall be leak-proof tested (e.g. using suitable test gas) once a year and after each servicing. Observe the manufacturer s safety instructions. When it ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 6 /40

7 is necessary, take measures in order to eliminate any leakage in consultation with the manufacturer. ASSEMBLY 5. Delivery Inspection of goods When goods are received, they must be inspected in order to ensure that the delivery is undamaged and complete. Missing or damaged parts shall be immediately recorded on consignment note and acknowledged by the driver. Detailed description in respect of the procedure when damage is discovered is given in dispatch note. If such procedure is not carried out, responsibility for deficiencies will not be considered. 6. Unloading and Transport The Air Handling Unit is delivered in individual sections which have their bases. Unloading and transport should be carried out by hoist or forklift truck. Danger Fall of weight can cause serious bodily injuries or damage. Follow safety instructions for means of transport. Do not stay under the load when it is in the stage of floating. 6.1 Unloading and Conveyance by Crane Attention Use only suitable and approved means for lifting (ropes, chains, wire cables, sheaves) according to national safety regulations for unloading and transport. 6.2 Unloading and Conveyance by Forklift Truck Attention When unloading and transporting the sections by forklift truck, the sections shall be transported either on their basic frames (bases) or on the pallet. 7. Assembly and Installation 7.1. Installation of Section Attention The Air Handling Unit shall not be used for fulfilling construction requirements. If the section is misused, e.g. so that the section base will replace a part of the construction structure or bad distribution will endanger the section statics, all warranty obligations will fail. See Note in VDI Base onto which the sections are placed Mount the section on even and hard foundation. Any unevenness leads to nonparallelism of the section frames which are to be connected; it must be corrected by adequate support. Maimum tolerance in horizontal direction is s=0.5% (0.3 0 ). ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 7 /40

8 Small floor unevenness (up to 50 mm) can be corrected by using the adjustable legs, which are an integral part of the AHU s stand. The foundation shall be adjusted to construction requirements from the viewpoint of statics, acoustics and water drain. Natural frequency of the support (bearing) structure, especially if it is of steel, must be adequately separated from the frequency of rotating parts such as fans, motors, compressors, etc. Mounting of the adjustable feet 1 2 Important Recommendation 1. Screw the adjustable feet 2. Adjust the height of legs in such a way that the distance from the floor to the stand is H = 250mm and secure by tightening the nut (4a) Check the arrangement of functional components and prepare drawings according to technical data before commencing the assembly. Use sound deadened construction bases. Neighbouring Unit which is of different weight can cause that the holes for connecting the sections are not aligned. In such case, align the holes during assembly by use of the hoist or other appropriate lifting equipment. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 8 /40

9 7.2. Connection of Sections All elements for connecting the sections, such as bolts, nuts, sealing tape, etc. are given as a part of the sections (usually in the fan section). Sections are connected by bolts passing through inner part of profiles which form the section frame. 1 Self-adhesive sealing tape 2 Housing profile 3 - Profile for interconnecting the AHU s sections with screw Important The following shall be done in order to connect the sections: Attach the self-adhesive sealing tape along the edges of the profiles which form the section frame. This is to be done on all joints of all sections being connected. Self-adhesive tape must be pressed between section profiles being connected. If necessary, fi mutually the sections by clamps, so that connecting holes are aligned. Connect the sections with bolts and nuts (mount the washers) Connection with Air Ducts Connection of air ducts with fleible connection on the sections of the Air Handling Unit must be realised so that it is free of any stresses. The length of fleible connection must not be used up to the maimum. The optimum length on which the fleible connection should be mounted is 115 mm. Fleible connection 1 Profile of the AHU 2 Fleible connection 3 Air duct which is connected to the AHU ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 9 /40

10 7.4. Pipe Connectors of Heater and Cooler When pipe water connections (inlet and outlet) of the heater and the cooler are close to each other, it must be provided that inlet and outlet connections are not mied up (take into account that the echangers are foreseen for counterdirectional water-air flow). Connection of echangers Attention Plan and adjust pipeline to be connected to echanger section so that the echanger be not eposed to pressure and stress due to large weight, vibrations, tensile forces, heat dilatation, etc. Use compensator if it is necessary. Provide couplings on service pipeline which will enable simple removal of the heat echanger for the purpose of maintenance or replacement. The pipeline should be eecuted so that it does not disturb servicing of the entire Air Handling Unit. When tightening the threaded connection on the coupling, it should be secured, e.g. by use of twist clamp so as to avoid pipe twisting or damaging. During the work, attention should be paid to connection with the coupling (flange) that the assembly be eecuted so that the echanger is not eposed to pressure or stress Connector for Condensate Drain Condensate drain is performed through the drain trap (U pipe) which is mounted on the very outlet of the Air Handling Unit. The height of U pipe must be appropriate in order to prevent suction of the drain condensate and its spraying in the air stream in the Air Handling Unit. Water must flow directly from the U pipe into side channel, and afterwards to the drains. Connection of drain trap ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 10 /40

11 Calculation of drain trap height The height of the drain trap is defined according to the following: In the zone of underpressure H 1 (mm) = p / 10 H S (mm) = p In the zone of overpressure H 1 (mm) = 35 mm Ptot 1000 Pa H 1 (mm) = 100 mm H S (mm) = 75 mm Ptot 1000 Pa H 1 (mm) = 35 mm H S (mm) = 150 mm p total drop of pressure at the point of condensate drain. Connect the drain trap to appropriate connection and charge it with water Cleaning When assembly is completed and before start-up (activation), check the cleanness of all components in accordance with VDI 6022 and clean them, if necessary. Special attention shall be paid to removal of metal chips (residues) since they can cause corrosion Electric Power Supply Equipotential Bonding Attention Installation, service and electric work to be performed only by skilled and qualified personnel! Protect against water ingress over electric junctions in the weather leak-proof units. Inlet of the cable should be near the bottom or through waterproof cable of sufficient crosssection (use at least protection class IP65). Check all electric junctions (switch case, frequency converter, motor, etc.) whether they are fied correctly and fi them if it is necessary (See DIN 46200). Connect all electric components (e.g. electric heater, electric motor, etc.) in accordance with the manufacturer s instructions, local electric regulations and general recommendations for protection against electromagnetic interference (earth work, cable length, cable protection). Electric heating coils must be equipped with safety switch. The safety switch must be inspected for proper operation after initial installation and after long periods of downtime. During maintenance of the air handling unit, the electric heating coil has to be checked for dirt and cleaned if necessary. Marking of junctions (e.g. electric heater, electric motor, etc.) is shown in the terminal bo. All electric nonconductive areas shall be jumper wire connected by same potential, e.g. separable section junctions, etc. Remove coating on the spots where ring eye meets equipotential bonding, so that the equipotential bonding is possible (metalic uninsulated surface). Do not use metal conduit gland screwing with plastic connector boes. Check every earthed cable, in order to make sure that they are correctly fied and fi them, if necessary. Check galvanised tape used for earth works. Test resistance of earth works in compliance with EN and take all necessary precautionary measures. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 11 /40

12 7.8. Protection of Motor Protection of the motor against overload is subjected to EN Provide motor safety switch and adjust the motor to rated current (see nameplate). Higher adjusted value is not acceptable! Motor to be wired according to wiring diagram in junction boes Electrical cables within the unit must be long enough that periodic tension adjustments to belt and pulleys will not be hampered The motor with nominal power up to ~ 5.5 KW can be connected directly (Note: power limitation is given by electric power distribution company, i.e. local supplier of electric power). Provide smooth commencement of operation when larger motors are used. Motor Protection: 1. Through thermal contact (thermal contact in winding) direct driven fans through speed controllable eternal rotor motors. The thermal contact used for motor protection, should be installed as to prevent a restart after a malfunction. 2. Through motor protection switch, with operation of fans with standard motor and beltdrive. The motor should be protected from overloading through a protection switch. The thermal relays in the unit should be set with +10% of measured current, after adjustment of the equipment, but not eceeding the rated current of the motor. Attention Damage caused by insufficient motor protection will not be covered with the manufacturer s warranty. MAINTENANCE 8. Air Dampers 8.1. Putting into operational mode Danger Pay attention to the instructions on page 5.! When the risk of pinning eists, do not approach the area within the reach of air damper blades! Protective devices such as duct connections, protective grid, etc. should be mounted according to EN 294! Attention Do not activate the fan before checking whether adequate air damper is open or the openness of the air damper is indicated by position switch. Provide control connection so when the air damper is close, adequate fan disengages immediately. Soko Inzinjering cannot assume responsibility for damage caused by irregular operation. Coupled air dampers If the air dampers are coupled, check synchronised movement and correct gear function, i.e. direction of rotation and final position of the air damper. Dampers with motor drive Check the tightness of all bolts and connections. In case of motor drive: Adjust linkage so that a 90 0 shutters reach end position when closed. swing angle is guaranteed and ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 12 /40

13 8.2. Maintenance Maintenance intervals Important Every three months. REGULARLY AS NECESSARY Check for operation of air damper, defects, damage and corrosion. Clean air damper, repair damage and remove corrosion. Check efficiency of protective device. Check for smooth moving of the blades. Check adjustments Do not lubricate air dampers with gear wheel drive. 9. Fan and Motor 9.1. Putting into operational mode Danger Pay attention to the instructions on page 5.! Serious bodily injuries and material damage can be caused by fracture of the impeller blade. Eceeding the fan maimum speed, as specified in technical data, is not allowed. Do not activate the fan if irregular vibrations are present. If the fan is started under free blow conditions, i.e. prior to connecting to ducting system, the current consumption may eceed the normal maimum (forbidden area of performance curve). The thermal protection of motor may be activated. Safety transport equipment Remove safety equipment mounted for transport (striking wedges or similar) from the fan base. Avoid damaging of vibration insulation. Attention Before the first activation, check whether it is necessary to clean the fan section, tubing system (is there pollution, tool, small parts, construction dust, etc.). Rotate the fan impeller to check for its smooth moving. Drive Check the connection of the pulleys with two V-belt slots (rim + elastic bush) together with motor and fan shafts. Check the drive of the pulleys, adjust if necessary: tension of V-belt whether the slots of the pulleys are aligned so that V-belt is not stressed. After 1 to 2 hours of continuous operation, repeat the above-said: retighten connection of the pulley with two V-belt slots (if necessary), retighten V-belt check if the slots of the pulleys are aligned. Direction of rotation Electric power consumption Activate the motor for short time, in order to check if rotation direction corresponds to the direction shown by an arrow on the fan casing. If the fan rotates in incorrect direction, reversed two phases in accordance with safety instructions (for three phase A.C. motor). After reaching operating speed of the fan, check the electric power consumption (with close inspection chamber). Measured values shall not eceed the nominal value on the ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 13 /40

14 nameplate. In case of eceeding, disengage immediately and check eternal pressure drop, airflows, rotation speed and direction of rotation. If phase currents are unequal, check motor power supply. Attention The fan must not be operated outside the operation scope limited by the manufacturer. The manufacturer s instructions shall be observed (take into account acceleration and deceleration). During assembly of motor fan, e.g. replacement of bearings, the manufacturer s specific assembly instruction must be observed. mark of the corresponding converter Installation of frequency converters Remove 1. Remove the upper two screws, and the lower two unscrew for about 5-6 mm. Unscrew 2. The corresponding frequency converter, which mark stands above, on the upper aluminum profile, set on the lower screws. Lean converter to the panel, return the top two screws and then all four screws firmly tighten. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 14 /40

15 Note: ALL frequency regulators are always installed/ mounted at the factory, but are disassembled for safe transportation. Electrical diagrams for connecting frequency regulators are attached to the panel (hatched area in the figure 1.) 9.2. Maintenance Maintenance intervals Every three months. Maintenance interval can be shorter, depending on whether the operation is continuous, or in some special conditions such as temperature eceeding 40 0 C, presence of dust, etc. Replacement, as well as adjustment of V-belts or pulleys should be performed without applying the force, since it can cause damaging. The fan motor bearings are permanently lubricated and cannot be lubricated subsequently. Standard greases used for lubrication are lithium-based greases and when they lose viscosity the bearing should be replaced. Remove V-belt in case of disengagement for a longer period (more than 3 months) in order to avoid load of bearings. Replace the fan motor bearing before use if disengagement lasts for longer period (a year or more). Pay attention to the manufacturer s instructions. FAN Check the fan for foulness, defects, damage, corrosion and couplings. REGULARLY Check bearings (noise). Lubricate bearings, observe the manufacturer s instructions. Check impeller blades for: balance and vibrations. Adjust if necessary. Check for fleible coupling (leak, joints, stress ) Check vibration absorbers for function (stiffness, connections, ) AS NECESSARY Check safety of protective frame Clean the fan, repair any damage and remove corrosion, fi connections. The fan motor bearings are permanently lubricated and cannot be lubricated subsequently (for motors with an ale height up to 160). Electrical motors with an ale height (180, 200, 225) are factory lubricated and it is impossible to further lubricate them without disassembling the motor, while electrical motors with an ale height 250 and above, have the option of lubrication. Standard greases used for lubrication are lithium-based greases and when they lose viscosity the bearing should be replaced. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 15 /40

16 ELECTRICAL MOTOR REGULARLY AS NECESSARY Check electric motor for defects, damage, corrosion, heating and the direction of rotation. Check motor bearings (noise). Clean motor, repair any damage and remove corrosion; fi couplings. Measure voltage, current, starting current and phase symmetricity. Check the tightness of joints, supports in the assembly with the fan, fi if necessary. V-belt transmission Check V-belt transmission for defect, damage, wear-out, tension, V-belt position (whether it is aligned), functioning and tightness. Replace a set of V-belts Adjust position of the fan and motor pulleys so that V-belt be aligned. Adjust V-belt tension Clean V-belt transmission 9.3. Determining the tensile force of V-Belt for V-Belt transmission according to DIN 7753 V-belt tension Tension of V-belt should be measured and adjusted in accordance to certain technical requirements, using adequate measuring instruments. Measure the distance A of the fan and motor pulleys aes (in meters) Deviation S = A 16 (mm) Apply sufficient force F on the V-belt in the middle of the distance A in order to obtain deviation S Measure the applied force F Compare deformation force F with the tabular values. Use higher values in the stage of commencing the operation of new V-belt. After a few hours of continuous operation, test again the deformation force F and adjust it if necessary. Force F [N] according to deviation S = 16 mm per 1 m of distance A ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 16 /40

17 TYPE OF PULLEY SPZ SPA SPB SPC DIAMETER OF SMALLER PULLEY ''d'' [mm] 67 to to to to to to to to 560 DEFORMATION FORCE F [N] 10 to to to to to to to to Maintenance switch Rukovanje servisnim prekidačim On all systems AHUs which have one operational and one reserve motor are mounted maintenance switches by type: 1-0-2, T /I1 for motors up to 5,5kW; 1-0-2, T /I2 - for motors from 5,5kW up to 11kW; 1-0-2, T5B /I4 - for motors from 11kW up to 18,5kW; 1-0-2, T B /I5 - for motors of 22kW These switches are designed to turn off the motor in case of any intervention on the fan motor in the fan section as well as a posibility for motor selection - Operating / reserve. It is envisaged that the motor which is closer to the fan be reserve, a motor which is further away from the fan motor to be operating. For the selection of the operating motor, set the switch to position 1. In the case of operating motor failure, set the switch to zero, wait for all moving parts to stop, take off the belt buckle of the operating motor, set the belt on the reserve motor, set the switch to position 2 - reserve motor. On systems where there is no reserve motor, the service switches type T /I1/SVB are mounted, which turns off the engine in case of any service intervention on the motor or inside of fan section. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 17 /40

18 10. Filters Putting into operational mode Danger Pay attention to the instructions on page 5.! Filter installation (in segments) Filters are fastened into a frame by tightening bolts. It is not allowed to destroy or damage filter segment. Check the position (seat) of filter in the frame. Supervision Final resistance of foul filter Roll filters Maintenance intervals It is necessary to monitor filter foulness; Adjustment of differential pressure switch on the side of servicing the Air Handling Unit is advisable. FILTER CLASS RECOMMENDED FINAL PRESSURE DROP ON FILTER BEFORE REPLACEMENT G1 G4 200 Pa F5-F7 400 Pa F8-F9 400 Pa H10-H Pa It is necessary to follow the instructions for maintenance provided by the manufacturer Maintenance Every three months. Danger Pay attention to the instructions on page 5.! Contact with foul filter (dust) can cause allergic reactions on skin, eyes or respiratory organs. When replacing filters, it is necessary to wear protective clothing, and if necessary protective mask. Avoid fouling of surrounding area and new filters when replacing the old ones. Spare filters Keep at least one set of spare filters in stock, and store them in a dry and dust-free area. Avoid fouling and possible damaging. Do not use filter after epiry of the life. Check filters for cleanness, odour, defects, damage and corrosion. Measure differential pressure drop on the filter. Check the filter seat, tightness, fastening. Replace filters in case of etreme foulness, odour or damage, in case of reaching final pressure drop, or after time interval: Replacement after 12 months Replacement after 24 months An earlier filter replacement can follow construction works or reconstruction measures or due to inspection. Replacement of single filter element in a set is acceptable in case of damage provided that the last replacement does not date back longer than 6 months. REGULARLY AS NECESSARY Pay attention to regulations related to environment protection when replacing the filter. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 18 /40

19 11. Silencers Putting into operational mode Danger Pay attention to the instructions on page 5.! Supervision Maintenance intervals It is necessary to check whether silencers are damaged or foul Maintenance Every three months. Danger Pay attention to the instructions on page 5.! The silencer largely requires low maintenance. Check silencers for: cleanness, defects, damage and corrosion. Clean silencers (see below), repair them and remove corrosion (if any), take contact samples if necessary. REGULARLY AS NECESSARY Cleaning Use vacuum cleaner for removal of surface dust particles. Attention When cleaning, do not damage absorption material. 12. Heater Heat Echanger (warm water /hot water, steam) Putting into operational mode Danger Pay attention to the instructions on page 5.! Do not use high temperature hot liquid when charging or bleeding, since there is a risk from burns. Do not touch very hot surfaces. Avoid contact with drained water when charging and bleeding for there is risk from poisoning and alkaline burns. Observe the manufacturer s instructions. Attention Do not eceed permissible nominal pressure (See design data sheet). In order to avoid freezing of heating coil: Add anti-freeze agents or fit safety frost thermostat on the side of air or water (depending on foreseen design of the Air Handling Unit). In order to avoid damaging of conditioning unit due to preheating, activate steam heater only when the fan is running. Provide protective sail switch ( air-prover ) and limit thermostat. Supervision Check correctness of inlet/outlet connections. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 19 /40

20 Charging After commissioning The system should be charged with the liquid intended for heating which by its composition corresponds to the design data sheet. Water quality shall be in accordance with JUS M.E Too high concentration of glycol leads to reduced heat echange, and too low concentration of glycol leads to possible damage due to freezing. When charging, pay attention to design technical specifications so that installation cleaning, bleeding and charging be performed correctly (residual air in the echanger can cause reduction of the capacity). After commissioning, check joints (connections) for leakage, and retighten them if necessary (See section 7.4). Maintenance intervals Maintenance Every three months. Danger Pay attention to the instructions on page 5.! To avoid any skin burns do not touch hot surfaces and prior to commencement of works allow the echanger to cool down to the surrounding temperature. Avoid any contact with discharged water when charging and bleeding, for there is a risk from poisoning and alkaline burns. Observe the manufacturer s instructions. Check the heater: hygienic conditions, defects on the air side, damage, leak-proof and corrosion. Clean the heater on the air side (see below), repair damage, leakage and remove corrosion. Check inlet/outlet connections for function. Check anti-frost protection for function. REGULARLY AS NECESSARY Cleaning Cleaning agents Clean the echanger already mounted; when not accessible pull it out. Removed foulness must not enter into other sections. Remove foulness and foul water very carefully. Pay attention to the following: Avoid bending and damaging of the echanger plate fins. Blow out the echanger with compressed air in direction opposite to air flow. Do not use high pressure steam cleaners. Clean with water and low pressure. Use cleaning agents with ph value between 6 and 8 (when required). Frost protection thermostats are easily accessible and can be adjusted via a maintenance door. If frost protection thermostats are mounted in frames those are withdrawable. Out of operation If the echanger is out of operation for some time and above all if there is a risk of freezing, the echanger must be emptied completely. Decontaminate discharged water in accordance with the manufacturer s instructions. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 20 /40

21 13. Electric Heater Putting into operational mode Danger Pay attention to the instructions on page 5.! Do not touch heating elements in order to avoid skin burns. Protection Recommendation Every electric heater must be fitted with safety thermostat with manual reset. Dual thermostat (protective and operating) mounted directly in the air stream behind the electric heater: Operating setting: 60 0 C Protective (safety) setting: 80 0 C. Do not change set values. Attention Electric heater can only be operated if airflow control is provided. Otherwise, due to insufficient cooling (preheating), electric heater, casing and other fied parts can be damaged. Flow control Electric power consumption Maintenance intervals Airflow must be monitored by measurements of differential pressure in the fan unit using differential pressure switch and sail switch. Functioning must be checked during commissioning (assembly). Electric power consumption of should be checked by measuring all phases. For nominal values, see nameplate (technical data). If the nominal values are eceeded, Sokoinžinjering After-Sale Service must be notified Maintenance Every three months. Danger Pay attention to the instructions on page 5.! To avoid any skin burns do not touch heating elements and prior to commencement of works allow the heater to cool down to the surrounding temperature. Check flow control, differential pressure switch and sail switch for function Check operation of electric heater, hygienic conditions, defects, damage, corrosion and tightness of joints. Clean electric heater, identify and repair damage and remove corrosion, tighten joints. Check safety and operating thermostat for function (See previous Commissioning ). REGULARLY AS NECESSARY ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 21 /40

22 14. Cooler Heat Echanger (cold water, direct epansion cooler) Putting into operational mode Danger Pay attention to the instructions on page 5.! Avoid any contact with discharged water; when charging and bleeding, there is a risk from poisoning and alkaline burns. Observe the manufacturer s instructions. Attention Do not eceed permissible nominal pressure (See the design data sheet). In order to avoid freezing of the echanger (if there is risk): Add anti-freeze agent or mount the echanger in air stream behind the heater. Supervision Charging Check inlet/outlet connections for function. The system cooler should be charged with liquid intended for cooling which by its composition corresponds to the design data sheet. Water quality shall be in accordance with JUS M.E Too high concentration of glycol leads to reduced heat echange, and too low concentration of glycol leads to possible damage due to freezing. When charging, pay attention to design technical specifications so that cleaning, bleeding and charging be performed correctly (residual air in the echanger can cause reduction of the capacity. After commissioning, check joints (connections) for leakage, and retighten them if necessary (See section 7.4). In case of with direct epansion cooler, cooling installation (including evaporator) is previously pressure tested by nitrogen to 25 bar, vacuumed and charged with cooling agent (Freon). Commissioning and maintenance of cooling installation are included in a specific instruction. Any intervention on the echanger is permissible only when cooling installation is out of operation. In case of some incorrectness, contact our service. Maintenance intervals Cleaning Maintenance Every three months. Danger Pay attention to the instructions on page 5.! Avoid any contact with discharged water; when charging and bleeding, there is a risk from poisoning and alkaline burns. Observe the manufacturer s instructions. Clean the echanger when already assembled or when not accessible, move it out. Removed foulness must not enter joining unit parts. Remove foulness and foul water very carefully. Important points to watch: Avoid bending and damaging the echanger plate fins. Blow out the echanger with compressed air in opposite direction to air flow. Do not use high-pressure steam cleaners Clean with water and low pressure. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 22 /40

23 MAINTENANCE REGULARLY AS NECESSARY Check the echanger: hygienic conditions, defects on air side, damage, leak-proof, and corrosion. Clean the echanger from air side (see below), repair damage, leakage and remove corrosion. Check and if necessary clean condensate drain pan (drop eliminator pan). Check and clean if necessary condensate drain and drain trap function. Check water level in drain trap, refill if necessary. Check inlet/outlet connections for function. Check anti-freeze protection for function Check direct epansion for icing. Drop eliminator Check drip eliminator for hygienic conditions, defects, damage, leak-proof and corrosion. Clean and service drop eliminator: Pull out cassette, disassemble and clean profiles separately, Repair damage and remove corrosion. Cleaning agents Use cleaning agents with ph value between 6 and 8 (when required). Out of operation If the echangers are out of operation for some time and above all if there is a risk of freezing, the echangers must be emptied completely. ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 23 /40

24 CERTIFICATES - CONFIRMATION OF QUALITY 15. Certificate CE mark ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 24 /40

25 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 25 /40

26 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 26 /40

27 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 27 /40

28 16. GOST R Certificate ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 28 /40

29 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 29 /40

30 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 30 /40

31 17. GOST Hygienic Certificate ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 31 /40

32 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 32 /40

33 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 33 /40

34 18. GOST ATEX Certificate ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 34 /40

35 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 35 /40

36 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 36 /40

37 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 37 /40

38 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 38 /40

39 ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 39 /40

40 «Soko Inzinjering» d.o.o. Office Bulevard A. Carnojevica New Belgrade, Serbia Phone +381(11) Fa +381(11) Factory Partizanska bb, Industrijska zona Krnjesevci, Stara Pazova, Serbia Phone +381(11) Fa +381(22) ASSEMBLY, OPERATION AND MAINTENANCE INSTRUCTIONS Page 40 /40

lindab we simplify construction Lindab Modular air handling units Service and maintenance manual

lindab we simplify construction Lindab Modular air handling units Service and maintenance manual Lindab Modular air handling units Service and maintenance manual Service and maintenance manual General... 3 2 Warnings and Tips... 3 3 Functional sections... 3 3.1 Fan section... 3 3.2 Heater section

More information

39 HQ Air Handling Units AiroVision

39 HQ Air Handling Units AiroVision VDI 6022 39 HQ Air Handling Units AiroVision Assembly/Installation, Commissioning, Maintenance Manual Type tested Production monitored AHU N : 08.02.251 Range: 39HQ DIN 1946-4 EN 13053 2 Code No: B.8.1.3i

More information

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL Indholdsfortegnelse Danvent Air Handling Units SERVICE MANUAL Service Servicing of the Air Handling Unit Your ventilation system is equipped with a Danvent Air Handling Unit (AHU) which will contribute

More information

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI500EN 09/2017

More information

English CNA-CNB. Centrifugal fans Installation and maintenance

English CNA-CNB. Centrifugal fans Installation and maintenance 916505-0 English CNA-CNB Centrifugal fans Installation and maintenance 916505-0 GB Centrifugal fans types CNA, CNB, CNA-M and CNB-M installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2

More information

lindab we simplify construction Lindab Compact air handling unit compair CF Transport, installation, start-up, maintenance and service

lindab we simplify construction Lindab Compact air handling unit compair CF Transport, installation, start-up, maintenance and service lindab we simplify construction Lindab Compact air handling unit compair CF Transport, installation, start-up, maintenance and service Transport, installation, start-up, maintenance and service manual

More information

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI100EN 09/2017

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT 90% EFFICIENCY HIGHEST EFFICIENCY AIR HANDLING UNIT Packaged energy recovery solutions for Green Buildings Integrated Accumulator, controls and DX Cooling System CLEAN AIR SINCE 1963 Euroclima is a company

More information

VETO CLEANER 500 FLUE GAS CLEANER

VETO CLEANER 500 FLUE GAS CLEANER As of serial number 3100 0001 VETO CLEANER 500 FLUE GAS CLEANER USER MANUAL SPARE PARTS LIST Manufacturer: ALA TALKKARI Veljekset Ala-Talkkari Oy FI-62130 HELLANMAA TEL. +358 6 433 6333 FAX +358 6 437

More information

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A CS 2 Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual Form No. 6120A TABLE OF CONTENTS Page Inspection... 2 Shipment of Units... 2 Handling... 2 Installation...

More information

MJC Cartridge Filter Unit Operation & Maintenance

MJC Cartridge Filter Unit Operation & Maintenance 1 of 19 Hodge Clemco Ltd MJC Cartridge Filter Unit Operation & Maintenance Owner s Manual Date of Issue: 19.07.04 TSSM536.1a Hodge Clemco Ltd Orgreave Drive Sheffield S13 9NR Tel: 0114 254 8811 Fax: 0114

More information

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI200EN 09/2017

More information

Chemical Motor Pump Unit BN

Chemical Motor Pump Unit BN Operating & Maintenance Instructions BW 5 02 01 / 1 The operating instructions of the centrifugal pump and the accessories should be located close to the pump. These instructions should be read carefully

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual DOMEKT ReGO 400VE(W)-B Series Air Handling Units EN Content Safety Requirements...3 Transportation...3 Brief Description of the Unit...5 Installation...6 Maintenance...11 Technical Information......13

More information

Technical instructions

Technical instructions Énergie Transfert Thermique Technical instructions A different climate Environmental control solutions Version IMPORTANT The warranty of ETT units depends on the respect of these technical instructions

More information

Oil burners fuel unit with solenoid valve

Oil burners fuel unit with solenoid valve Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Germany VM_e.pdf - 18.05.08 Page 1/6 Oil burners fuel unit with solenoid valve

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

SELF-PRIMING JET PUMPS

SELF-PRIMING JET PUMPS SS Anti-Rust SS Shaft Copper & Cold-rolled SELF-PRIMING JET PUMPS CONTENTS 1. Applications.... Model Description.... Technical Data... 4. Implementation Standards... 5. Safety Precautions... 6. Product

More information

Instructions for Operation and Maintenance of Containers

Instructions for Operation and Maintenance of Containers Instructions for Operation and Maintenance of Containers Container Handling 1. Containers are designed for transport on a flat loading area that is 2.5 m wide, which enables support of the load-bearing

More information

Operating instructions

Operating instructions ebm-papst Mulfingen GmbH & Co. KG Bachmühle D-74673 Mulfingen Phone +49 (0) 793-0 Fax +49 (0) 793-0 info@de.ebmpapst.com www.ebmpapst.com CONTENTS. SAFETY REGULATIONS AND NOTES. Levels of hazard warnings.

More information

Part 2: Installation Instructions cl

Part 2: Installation Instructions cl Contents Page: Part 2: Installation Instructions cl. 381-382 1. Delivery scope............................... 3 2. General and Transportation safety precautions........... 3 3. Stand installation 3.1 Installing

More information

Smoke extraction duct of sheet steel

Smoke extraction duct of sheet steel Smoke extraction duct of sheet steel The accessories that are available, as for example inspection openings, steel grilles, plenum boxes, ceiling diffusers, splitter attenuators, bends, tees and connecting

More information

Installation and Operating Instructions

Installation and Operating Instructions ELECTRICALLY OPERATED FOLDING STAIRS Installation and Operating Instructions Premier Loft Ladders ltd Registered Office: 2 Dawson Drive, Trimley St Mary, Felixstowe, Suffolk. IP11 0YW Registered in England

More information

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE ISO 9001 : 2000 STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE CUSTOMER : 1 CONTENTS 1 SAFETY... 5 1.1 General... 6 1.2 Description of symbols and pictograms... 6

More information

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original) Montageanleitung (Original) (Translation of the original) DE MA_ 1.0 06/2014 Taperlock Clamping-bush system _0 _1 Fixed hub Inlet nozzle with IMV 1. Revision index Revision Date MA_ 1.0 06/2014 2. Safety

More information

RS 6/C/ Published December RATING STANDARD for the CERTIFICATION of HYGIENIC AIR HANDLING UNITS

RS 6/C/ Published December RATING STANDARD for the CERTIFICATION of HYGIENIC AIR HANDLING UNITS RATING STANDARD for the CERTIFICATION of HYGIENIC AIR HANDLING UNITS Supersedes RS-6/C/011-2016 Editing (date): Anthony BAILLAU (January 2017) Checking (date): Jean FOURCROY (13th October 2017) Approval

More information

IEC- Direct-driven radial fans with IEC-Standardmotor

IEC- Direct-driven radial fans with IEC-Standardmotor EHND / ERND / ERNE / Contents. / Page 1. / Safety... 2 2. / Description... 4 3. / Condition of use... 4 4., / Storage, Transport... 5 5. / installation... 6 6. / operation... 8 7. / maintenance... 9 8.

More information

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2

Acquaer Ltd. H-4900, Fehérgyarmat, Szatmári út 11. CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 CENTRIFUGAL PUMP Instruction Manual ACm60 / ACm75 / ACm150 / ACm150B2 Congratulations on your purchase of a LEO Centrifugal Pump It is important that you read, fully understand and observe the following

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid

More information

Refrigerator KE T

Refrigerator KE T Refrigerator KE 680-1-3T Service Manual: H8-74-07 Responsible: U. Laarmann KÜPPERSBUSCH HAUSGERÄTE AG E-mail: uwe.laarmann@kueppersbusch.de Tel.: (0209) 401-732 Customer Service Fax: (0209) 401-743 Postfach

More information

A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513)

A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio Phone: (513) Fax: (513) A Fläkt Woods Company 2933 Symmes Road, Fairfield, Ohio 45014-2035 Phone: (513) 874-2400 Fax: (513) 870-6249 JM AEROFOIL FANS Installation, Operation and Maintenance Instructions Site Storage The fan must

More information

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

SMHA Hatch High temperature fan HT-fan Installation and Maintenance High temperature fan HT-fan Installation and Maintenance 22.8.2012 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

Installer manual GreenMaster-HP

Installer manual GreenMaster-HP Installer manual GreenMaster-HP Transport and installation Ventilation unit IHB EN 1747-2 8017172 2 GreenMaster-HP Transport and installation Introduction Here you can read about how best to handle the

More information

INSTALLATION & OPERATING INSTRUCTIONS

INSTALLATION & OPERATING INSTRUCTIONS INSTALLATION & OPERATING INSTRUCTIONS WARNING RISK OF ELECTRIC SHOCK. CONNECT ONLY TO A CIRCUIT PROTECTED BY A GROUND-FAULT CIRCUIT-INTERRUPTER. THE UNIT SHOULD BE INSTALLED BY A QUALIFIED SERVICE REPRESENTATIVE.

More information

This label warns for risk of electrical shock when failing to observe.

This label warns for risk of electrical shock when failing to observe. MANUAL horizontal centrifugal pumps MB series ic drive SB series mechanical seal 1. Introduction 2. Safety precautions 3. Receipt 4. Installation / Operation and Maintenance 4.1 Installation 4.2 Operation

More information

Installation and operating instructions. DK energy storage and DK energy buffer

Installation and operating instructions. DK energy storage and DK energy buffer Installation and operating instructions DK energy storage and DK energy buffer Edition: 08-2015 1 Preliminary note With this DK energy storage / DK energy buffer you purchased a DK quality product. The

More information

TopMaster Air Handling unit. Installation instructions

TopMaster Air Handling unit. Installation instructions Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into

More information

APW PSI PRESSURE WASHER

APW PSI PRESSURE WASHER APW5001 1300 PSI PRESSURE WASHER 1300 PSI PRESSURE WASHER Please carefully read this manual which has been specifically designed to provide all the necessary information for the correct use of the machine,

More information

Compact ventilation units Series SupraBox COMFORT

Compact ventilation units Series SupraBox COMFORT Betriebsanleitung Operating instruction EN Compact ventilation units Series SupraBox COMFORT SupraBox V BA113BB03/12/A/ SupraBox 1 Rosenberg Ventilatoren GmbH Maybachstraße 1 74653 Künzelsau-Gaisbach Tel.:

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RFEC/U/2017-1 (EN) (valid since 18.08.2017) ROOF FANS RF/EC...-... / RFV/EC...-... Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the

More information

Installation of Glass Lined Equipment

Installation of Glass Lined Equipment Installation of Glass Lined Equipment Information given herein is for guidance only and may not be complete. It is important that only trained and competent personnel are permitted to handle glass lined

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

Specifications. Vacuum motor power consumption(w/hp) 1200 / 1.6. Exhaust water pump power consumption(w/hp 800 / 1.1

Specifications. Vacuum motor power consumption(w/hp) 1200 / 1.6. Exhaust water pump power consumption(w/hp 800 / 1.1 Specifications Rated voltage (V) AC 110-120V or 220-240V / 50-60Hz Vacuum motor power consumption(w/hp) 1200 / 1.6 Exhaust water pump power consumption(w/hp 800 / 1.1 Exhaust water pump flow (GPH/LPH)

More information

Tornado Operations & Maintenance Manual

Tornado Operations & Maintenance Manual TORNADO INDUSTRIES 7401 W. LAWRENCE AVENUE CHICAGO, IL 60706 (708) 867-5100 FAX (708) 867-6968 www.tornadovac.com Tornado Operations & Maintenance Manual MODEL NO. 99690 BD 22/14, 99720 BD 26/14 L9722

More information

Oil burners fuel unit with solenoid valve

Oil burners fuel unit with solenoid valve Oil burners fuel unit with solenoid valve Type VM www.deltapumps.com VM1 - VM4U flanged Certified Quality System Printed in Italy - DE112/0404 Oil burners fuel unit with solenoid valve Type VM The DELTA

More information

ACN SMOKE INSTALLATION AND MAINTENANCE

ACN SMOKE INSTALLATION AND MAINTENANCE NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport

More information

INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS

INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS INSTALLATION MANUAL FOR ROTARY TWIN LOBE (ROOTS) BLOWERS / COMPRESSORS AIRVAC INDUSTRIES & PROJECTS CORPORATE OFFICE: H-2/111, SECTOR-16, ROHINI, DELHI-110 085 PHONE: +91-11-32958731, 27298061 FAX: +91-11-27298061

More information

CENTAFLEX Series A Assembly and operating instructions CF-AR M EN Rev. 2

CENTAFLEX Series A Assembly and operating instructions CF-AR M EN Rev. 2 Contents 1 General remarks... 5 2 Safety... 6 2.1 Safety remarks... 6 2.1.1 Signal words... 6 2.1.2 Pictograms... 7 2.2 Qualification of deployed personnel... 7 2.3 Intended application... 7 2.4 Application

More information

Ventilation and air conditioning QUALITY FOR LIFE. Refrigerating systems and heat pumps. Operating manual

Ventilation and air conditioning QUALITY FOR LIFE. Refrigerating systems and heat pumps. Operating manual Ventilation and air conditioning QUALITY FOR LIFE GB Refrigerating systems and heat pumps Operating manual Refrigerating systems and heat pumps 3052967 I 07/2010 Refrigerating systems and heat pumps Table

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RF/U/2017 (ENGLISH) (valid since 13.10.2017) ROOF FANS RF / RFV Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the right to modify this

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW)

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW) Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW) The contents of this publication are based on the latest information available and the materials that are used at the time of printing.

More information

CENTRIFUGAL AIR CONDENSERS

CENTRIFUGAL AIR CONDENSERS OPERATING INSTRUCTIONS INSTALLATION COMMISSIONING OPERATING MAINTENANCE (must be given to the end user in order to complete the operating manual during the equipment service life) CAC and SIROCCO CENTRIFUGAL

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

p Permanent magnet water cooled motors Additional manual

p Permanent magnet water cooled motors Additional manual p Permanent magnet water cooled motors Additional manual Safety Instructions 1 General General safety regulations, safety precautions and specific agreements made for each work site shown in this document

More information

XB-EFA-8L-BK & XB-EFA-8R-BK

XB-EFA-8L-BK & XB-EFA-8R-BK Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU The information contained in this document provides details of installation, operation

More information

lindab we simplify construction Lindab Compact air handling unit COMPAIR CF Transport, installation, start-up, maintenance and service manual

lindab we simplify construction Lindab Compact air handling unit COMPAIR CF Transport, installation, start-up, maintenance and service manual Lindab Compact air handling unit COMPAIR CF Transport, installation, start-up, maintenance and service manual CompAir CF 1 General 1.1 Types of functional sections 1.2 Functional elements 1.3 Housing checking

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) 52" Belt Drive, Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before

More information

290 on. 286 on. Comfortable climate with pre-heated, filtered supply air. Fresh air boxes ALB WW MODEL WITH WARM WATER HEATING

290 on. 286 on. Comfortable climate with pre-heated, filtered supply air. Fresh air boxes ALB WW MODEL WITH WARM WATER HEATING Fresh air boxes ALB Comfortable climate with pre-heated, filtered supply air. Ingeniously practical: Supply air, heating and filter in a single unit. For direct in-duct mounting. The fresh air boxes ALB

More information

USER S MANUAL ATH WH220

USER S MANUAL ATH WH220 USER S MANUAL ATH WH220 INDEX INTRODUCTION... - 3 - General information s... - 3 - Description of pneumatic jack... - 4 - Operation of jack... - 5 - Technical data... - 6 - Dimension drawing... - 6 - INSTALLATION...

More information

HEATING AND VENTILATION

HEATING AND VENTILATION SECTION 14-102.04 14-102.04/ 1 2007OC19 DESCRIPTION The heating, ventilation and air conditioning (HVAC) system is designed to optimize passenger comfort. The system regulates interior vehicle atmosphere,

More information

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 918149-0 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

EC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism

More information

AT4 Hygienic Application According to Guideline VDI 6022

AT4 Hygienic Application According to Guideline VDI 6022 Air-handling-units AT4 Hygienic Application According to Guideline VDI 6022 AT4 AHU for hygienic application The VDI guideline 6022, part 1 and 3 defines the hygienic requirements for AHU with regard to:

More information

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING USER S MANUAL VCU/ Series CENTRIFUGAL FAN IN SCROLL CASING 2 CONTENTS Introduction Use Delivery set Designation key Technical data Safety requirements Design and operating logic Mounting and set-up Connection

More information

CIRRUS AIRPLANE MAINTENANCE MANUAL

CIRRUS AIRPLANE MAINTENANCE MANUAL COOLING 1. DESCRIPTION On aircraft serials 183 and subsequent, an optional air condition system is available. This section contains the maintenance practices pertinent to this system. Cabin ventilation

More information

Decentralised ventilation units

Decentralised ventilation units Notes on installation Decentralised ventilation units FSL / SCHOOLAIR GB/en TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de

More information

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd 1 MJC Mini Cartridge Filters Owners Manual TSOM 556 Date of Issue: 13.07.04 Orgreave Drive, Sheffield South Yorkshire. S13 9NR Tel:0114 254 0600 Fax: 0114 2540250 Email:sales@hodgeclemco.co.uk www.hodgeclemco.co.uk

More information

Evaporative Cooling products

Evaporative Cooling products user manual Evaporative Cooling products OPERATION - MAINTENANCE Z0582995_A ISSUED 06/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT general information Note Recold

More information

Field Start-Up Sheet Direct Fired Gas Equipment

Field Start-Up Sheet Direct Fired Gas Equipment Customer: Sales Representative: Model Number: Serial Number: Field Start-Up Sheet Direct Fired Gas Equipment ***Please Print*** INITIAL INSPECTION I. Installer Responsibilities 1. Remote Panel: All interconnecting

More information

A/C-HEATER SYSTEM - MANUAL

A/C-HEATER SYSTEM - MANUAL A/C-HEATER SYSTEM - MANUAL 1986 Isuzu Trooper II 1986 A/C-HEATER SYSTEM Isuzu A/C-Heater Systems - Manual P UP, Trooper II * PLEASE READ THIS FIRST * CAUTION: When discharging air conditioning system,

More information

Hi-Pres. Self Contained A/C Unit HI-PRES MARINE & OFFSHORE

Hi-Pres. Self Contained A/C Unit HI-PRES MARINE & OFFSHORE Hi-Pres Self Contained A/C Unit TYPE SCU-C & SCU-W Product specifications HI-PRES MARINE & OFFSHORE Contents Introduction..................... 2 Type SCU-W.......................... 2 Type SCU-C...........................

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

LSM PUMPER Sigenvej 7 DK 9760 Vrå Tlf.: Fax USERS GUIDE FOR LSM PUMPS TYPE

LSM PUMPER Sigenvej 7 DK 9760 Vrå Tlf.: Fax USERS GUIDE FOR LSM PUMPS TYPE LSM PUMPER Sigenvej 7 DK 9760 Vrå Tlf.: +45 9898 1900 Fax. +45 9898 2440 USERS GUIDE FOR LSM PUMPS TYPE 10 15 19 25 32 40 50 65 80 100 125 150 200 Index Declaration of conformity 3 Conditions of usage

More information

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill of lading

More information

Pump WaterVISE, FloVISE

Pump WaterVISE, FloVISE General information It is important that this manual is read carefully by the user and the installer in order to ensure proper functioning and lifespan of the pump. Pahlen pumps are manufactured in accordance

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

BELT DRIVEN STATIONARY AGITATOR

BELT DRIVEN STATIONARY AGITATOR BELT DRIVEN STATIONARY AGITATOR INSTRUCTION MANUAL www.usfarmsystems.com 2955 S. K Street Tulare, CA. 93274 (559)685-0340 (800)811-9462 Fax (559)685-9160 Revision Date 9/7/2017 TABLE OF CONTENTS How to

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR MODEL RH REMOTE HORIZONTAL AIR COOLED HEAT EXCHANGERS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR MODEL RH REMOTE HORIZONTAL AIR COOLED HEAT EXCHANGERS INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR MODEL RH REMOTE HORIZONTAL AIR COOLED HEAT EXCHANGERS 9845 South 57 th Street Franklin, WI 53132 Telephone: (414) 421-4666 Fax: (414) 421-0712 MODEL RH

More information

Inverted Bucket Steam Traps

Inverted Bucket Steam Traps INSTALLATION AND MAINTENANCE INSTRUCTIONS IM-2-00-US December 201 Inverted Bucket Steam Traps Safety Information Safe operation of these products can only be guaranteed if they are properly installed,

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

SC250X FLOOR GRINDER OPERATIONS MANUAL

SC250X FLOOR GRINDER OPERATIONS MANUAL Unit 4/1 Rocklea Drive Port Melbourne Vic 3207 1300 109 108 www.traxxcp.com.au SC250X FLOOR GRINDER OPERATIONS MANUAL The contents of this Operations Manual are the copyright of the publisher and may not

More information

Enviro KES INSTALLATON MANUAL

Enviro KES INSTALLATON MANUAL Enviro KES INSTALLATON MANUAL Spring Air Systems Inc., Oakville, Ontario Phone (905) 338-2999, Fax (905) 338-0179, info@springairsystems.com www.springairsystems.com KES Installation Manual. This publication

More information

Installation and maintenance instructions

Installation and maintenance instructions Installation and maintenance instructions Air handling unit KG Standard (Translation of the original) Wolf GmbH D-84048 Mainburg Postfach 1380 Tel. +49 (0)8751/74-0 Fax +49 (0)8751/741600 Internet www.wolf-heiztechnik.de

More information

lindab we simplify construction Lindab Modular air handling units Connection, start-up and commissioning manual

lindab we simplify construction Lindab Modular air handling units Connection, start-up and commissioning manual Lindab Modular air handling units Connection, start-up and commissioning manual Connection, start-up and commissioning manual 1 General... 3 2 Warnings and Tips... 3 3 Functional sections... 3 3.1 Fan

More information

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2 Cleaning unit for coolant :_decftez`_>r_fr] Book No.: 1271526-02 V2 Alfa Laval Separation AB Separator Manuals, dept. SKEL S-147 80 Tumba, Sweden Telephone: +46 8 53 06 50 00 Telefax: +46 8 53 03 10 40

More information

EQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4

EQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4 EQGA AND EQGB HYGIENIC VERSION, CODE SUFFIX I = 3 AND 4 ASSEMBLY AND MAINTENANCE INSTRUCTIONS Contents Page Hygienic version..... 2 Delivery...... 2 Safety precautions...... 2 Mounting on the floor......

More information

CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015

CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015 INSTALLATION-OPERATION-MAINTENANCE CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015 TEFC 3 phase motor Outlet duct Fan wheel housing Inlet duct connection After filter transition Optional after filter unit

More information

AZN ATEX INSTALLATION AND MAINTENANCE

AZN ATEX INSTALLATION AND MAINTENANCE ZerAx AZN ATEX INSTALLATION AND MAINTENANCE 924714-0 English 924714-0 GB ZerAx axial flow fans type AZN ATEX Installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Temperature

More information

Air handling unit KG Standard (Translation of the original)

Air handling unit KG Standard (Translation of the original) Installation and Maintenance Instructions Air handling unit KG Standard (Translation of the original) Wolf GmbH Postfach 1380 D-84048 Mainburg Tel.+49 ( 0) 8751/74-0 Fax +49 (0) 8751/74-1600 Internet:

More information

Part No KEMPER Filter-Master XL

Part No KEMPER Filter-Master XL Part No. 150 0492 KEMPER Filter-Master XL 1. Application and Mode of Operation.... 2 2. Safety Instructions......... 2 3. Placing into Operation...... 3 4. Operation Elements and Function... 3-4 5. Installation

More information

INSTRUCTION MANUAL W-400

INSTRUCTION MANUAL W-400 USE and MAINTENANCE INSTRUCTION MANUAL Bellaria WBX WB GRAVITY SPRAY GUN Series LPH-400 WB en it fr es pt de se TECHNICAL DATA Classic Plus Series LPH-400 (LVLP) Classic Plus Nozzle_Needle set Combination

More information

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES Using the air handling unit... Free space for service and repair work... GENERAL INSTRUCTION Checking prior to commissioning...3

More information