1 Urbana Free Library HVAC Analysis Prepared for the Urbana Free Library Prepared by Paul Boland, P.E., and Nathan Alderman, E.I.T. Report Dated August 8, Introduction The Urbana Free Library is a three-story building, and its loads are served by two large air handling units, one packaged air-cooled chiller, and one boiler in the basement. The building was expanded to the west in 2002, in an expansion project that nearly doubled the size of the library and its footprint. Cooling is provided to the original portion of the building by two directexpansion air-cooled condensing units mounted on the roof and a main air handling unit in the east penthouse, while cooling is provided to the 2002 addition by a packaged air-cooled chiller serving chilled water to a main air handling unit in the west penthouse. Neither air handling unit has a heating coil installed in its enclosure; heating is distributed to the space by means of reheat coils at each variable air volume box throughout the library, and the hot water that serves these boxes is produced by the boiler in the basement. The Urbana Free Library has requested an analysis of these heating, cooling, and air conditioning (HVAC) systems, including their performance, construction, controls, and potential repairs needed. In addition to the analysis, the Library staff has requested that HEI provide an analysis of the HVAC systems that serve the Archives on the second floor and a schematic design of a new independent HVAC system that only serves the Archives. 2. Existing Boiler Hot water is provided to the building as it is generated by a Cleaver-Brooks model 3 packaged condensing boiler. The boiler s catalog number is WTW-7A-1500, serial number is 635, and unit number is G M3. The faceplate input and output capacities are 1,500,000 BTUH input and 1,400,000 BTUH output, indicating that this boiler is operating at 93% efficiency. This type of boiler uses low return water temperatures to recover heat from the combustion air stream; typically a steam or hot water boiler cannot exceed 83% efficiency as heat is exhausted through the combustion air stream. Page 1 of 5
2 The boiler s faceplate indicates that it was installed in Hot water boilers typically have an expected life of 30 years; this boiler is past its life expectancy, and will need to be repaired or replaced soon. HEI contacted Cleaver-Brooks to ascertain the availability of parts to replace inside the boiler in lieu of a more expensive boiler replacement; unfortunately, due to the age of the boiler, parts are no longer available for this model. When the parts begin to fail the boiler will need to be replaced in its entirety. HEI s correspondence with Cleaver-Brooks was conducted through Michelle Frye on May 24, 2016, who can be reached at (309) or by at MFrye@cbservice.com. The current boiler is having no trouble managing the heating loads in the building, and if it is to be replaced the heating capacity should remain the same. HEI would recommend that two separate boilers sized for half the load (700,000 BTUH output) be installed for better turndown at part-load conditions and as insurance in case one boiler fails or needs to be taken offline for maintenance. The new boilers should also be the modular condensing type as is currently installed, to maintain the increased efficiency that this type of boiler offers. A preliminary estimate of probable construction cost for the replacement of the boiler in this manner would fall around $93,150, which includes a 15% markup for contingencies and the contractor s overhead and profit. 3. Existing Air Handling Units The library is served by two air handling units located in separate penthouses on the roof. Both units are variable air volume cooling-only units with economizers to take advantage of free cooling, and heat is provided to the spaces through reheat coils in the terminal boxes on each system. The east half of the library is served by a Trane type M-63 air handling unit, serial number K2L228866, which is original to the building. Cooling is provided to this air handling unit by two air cooled condensing units placed on the roof directly west of the east penthouse, each with a cooling capacity of 40 tons, with four fans and two compressors in each unit. At the time of investigation, one condensing unit was in operation with three of the four fans running, and the other condensing unit was not operating. Outdoor air is drawn in through a 10 x6 louver on the west face of the penthouse, and building air is relieved through a second 10 x6 louver on the east face of the penthouse. This unit has an economizer to make use of free cooling when the outdoor air temperature falls between 50 F and 60 F. The supply fan motor in the east penthouse air handling unit was rattling during operation, suggesting that a fan bearing must be nearing the end of its life. This is a common maintenance item, and should be addressed as soon as possible. The west half of the library is a new addition to the building that was constructed in 2002, and is served by a new air handling unit in the west penthouse. This unit is a York model AP660, serial number CGMM18527D, sales order and is tagged AHU-1. Cooling is provided to this unit through a chilled water coil, and chilled water is provided by a packaged air-cooled chiller located directly east of the west penthouse. The chiller is tagged C-1 and is a Page 2 of 5
3 York model YCAS, serial number RFMM Chilled water is circulated through the chiller and AHU-1 cooling coil by an Armstrong model 4030 pump with 287 gallons per minute (GPM) capacity at 70 feet of head, with a 10 horsepower motor. The air handling unit AHU-1 has an economizer to make use of free cooling when the outdoor air temperature falls below 60 F. The chiller tag indicates that it uses R-22 refrigerant, which is under phase-out at the moment and will be expensive to replace. It is recommended to upgrade the chiller to R-410a as soon as possible. In addition to the refrigerant, HEI notes that the insulation on the chilled water supply and return piping and the condensing unit refrigerant piping has deteriorated significantly and is cracking, which will allow moisture to gather in the insulation. HEI recommends that this insulation be replaced to maintain the vapor barrier around the piping and to improve the efficiency of the chilled water system. HEI s preliminary cost estimates indicate a total cost of $468,082 including 15% markup to replace the chiller, two air handling units, and two condensing units, not counting the cost of the controls upgrade from pneumatic to direct digital controls discussed in the next section. This cost may be broken down into the replacement cost based on system. The following is a list of HEI s estimates of probable construction cost for each piece of equipment on this system, each line including the 15% markup: 4. Controls Chiller C-1 Insulation Repairs: $1,196 Chiller C-1 Replacement: $144,578 Air Handling Unit AHU-1 Replacement: $122,668 Air Handling Unit Trane M-63 and Condensing Units replacement: $199,640 The building is served by two separate controls systems, divided between the original section of the building and the addition. The control panels serving each section are located in the penthouse mechanical spaces, mounted near the coil connection side of each air handling unit. The controls system serving the original section of the building is a pneumatic system tied to the Trane M-63 air handling unit and its associated air-cooled condensing units. The controls system serving the addition is a direct digital control (DDC) system tied to AHU-1, chiller C-1, and associated equipment throughout the building. The equipment controllers serving the building addition are mounted at the west end of the west mechanical penthouse. The controllers are Invensys model PXP-100 controllers, used to control equipment on the system other than AHU-1. The controls diagrams are present on the inside of the controls box. These controllers serve the variable air volume boxes, reheat coils, pumps, and unit heaters throughout the addition. During observation, HEI observed that the control panel serving AHU-1 indicated a mixed air temperature of 73.0 F and a leaving air temperature of 53.6 F; however, it also indicated that the chilled water valve was 0% open. The control panel is showing that the air passing through the chilled water coil is being cooled somehow, but it also shows that the cooling coil is shut Page 3 of 5
4 down. Since the building return, mixed, and supply air temperatures are in line with how the unit would be expected to operate at the outdoor air temperature observed at the time of the walkthrough, it is likely that the reading from the chilled water coil valve position may be inaccurate. The controls systems serving both portions of the building are in good working order. The DDC system serving AHU-1 is anticipated to last at least another 10 years before replacement will be necessary, and the pneumatic system serving the original building is anticipated to last another 5 years. When the pneumatic control system begins to fail and need to be replaced, a full replacement of the pneumatic system with matching DDC system would be estimated to cost roughly $159,045 including the 15% markup discussed above. 5. Archive Storage During our initial site visit and investigation, HEI interviewed the Director of Champaign County Historical Archives Anke Voss. Anke reported that the library archives are used to store several fragile artifacts on paper, microfilm, cassette tapes, photographs, and print negatives. Currently, 1500 linear feet of artifacts are stored in the space. The Society of American Archivists Standards state that the environment in which these artifacts are stored shall be held to the median temperature and humidity required to preserve all the different types of artifacts; in this case, the environment will need to be held at 70 F dry bulb and 40% relative humidity. The library archives are currently heated, cooled, and ventilated by air handler AHU-1, which also serves the rest of the west addition to the library. Due to this, when the air handling unit is set to shutdown mode every night when the library closes, the archives are not adequately conditioned to maintain the required temperature and humidity. In order to maintain the required conditions in the archives, a separate unit will need to be installed that only serves the archives, and is indexed to maintain 70 F and 40% relative humidity at all times with no night setback. The library archives consist of three separate rooms. Room 204 Archives is the main section of the archive storage, measures 2,200 square feet, and has desk and table space in the center and east ends as well as shelf storage on the west end. Room 205 Archives Office measures 450 square feet, and holds office space for the archive employees. Room 206 Archive Storage measures 600 square feet, and contains high-density storage shelves for the majority of the artifacts stored. Per ASHRAE 62.1, this space will need to be provided with 560 cubic feet per minute (CFM) of outdoor air to meet the ventilation requirements. Preliminary load calculations show that to maintain this amount of outdoor air and condition the space to the required set point, a new 2,600 CFM unit with cooling capacity of 7 tons and heating capacity of 115 MBH will need to be added to serve the archive space alone. This unit should be direct expansion cooled with a new dedicated condensing unit on the roof of the library rather than making use of the chilled water system, as the chiller will be deactivated when the outdoor air temperature drops below a certain point. This new cooling coil shall also be provided with digital scroll compressors for capacity control, which will allow the system to continue to cool and dehumidify at part load. Page 4 of 5
5 Humidity controls will be required with this new unit as well. Dehumidification will be provided by the cooling coil during normal operation, but due to the relatively low relative humidity setpoint a reheat coil will be required as well to prevent space over-cooling. Humidification may be provided through a small infrared pan humidifier inside the unit itself, and in order to maintain 40% relative humidity at 70 F this humidifier will need to have a rated capacity of pounds per hour. An electric humidifier may also be used, but since steam, softened water, or reverse osmosis water are not available on site the infrared humidifier will operate more reliably and responsively than an electric humidifier. While HEI would recommend that an airside economizer be provided with this new unit to take advantage of energy savings in cooler weather, an economizer is not strictly required by International Energy Conservation Code (IECC, 2015 edition) for this unit. Exception 3 in section C403.3 states that economizers are not required [w]here more than 25 percent of the air designed to be supplied by the system is to spaces that are designed to be humidified above 35 F (1.7 C) dewpoint temperature to satisfy process needs. This unit supplies all of its air to the Archives, which need to be held at 44.6 F dewpoint; therefore, an economizer will not be required. The unit will need to have a new mechanical room or other location set aside where it may be located. Since the archives are on the top floor of the library, the unit may be located on the roof directly above; however, if the unit is to be installed exposed to outdoors the infrared humidifier may not be used due to freezing concerns. An electric steam-generating humidifier will need to be mounted inside the building to provide humidity in the winter. If part of the Archives can be sectioned off as a new mechanical room for the air handling unit, the infrared humidifier may be used. The small section of the Archives just south of the Office 205 would be the best location for the unit, as it allows a portion of the archives to be set aside with minimal impact on the floor plans. Based on the requirements of the new system, HEI s opinion of probable cost for this installation would be $46,827. This is based on installation of a new direct-expansion cooled furnace with reheat coil and infrared humidifier, along with associated ductwork, grilles, electrical connections, and unitary controls. Page 5 of 5
AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University
AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort
More informationRedesign of Bennett Hall HVAC System
MEE 488 April 18, 2006 Redesign of Bennett Hall HVAC System Greg Andreasen Michael Chicoine Florent Hohxa Jason Jacobe Mechanical Engineering, University of Maine, Orono ME 04473, USA ABSTRACT Our task
More informationASHRAE Illinois Chapter 2015 Excellence in Engineering Awards
ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards PROJECT Chicago Vocational Career Academy Chicago, Illinois OWNER Chicago Public Schools PREPARED FOR American Society of Heating Refrigerating
More informationDescription of All Alternatives Considered-
Description of All Alternatives Considered- Energy efficiency is an area where the Tubman design can be improved. The design heating load is 1807.8 MBH and the design cooling load is 1702.2 MBH or 142
More informationOSU Alumni Center Phase I Implementation Review. Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon
OSU Alumni Center Phase I Implementation Review Prepared for Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon 97331 October 31, 2011 Job No. 02.11.00113 Introduction: Glumac was engaged by
More informationTopic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline
ME 414/514 HVAC Systems Overview Equipment Outline 2-1 The Complete System 2-2 The Air-Conditioning and Distribution System 2-3 Mechanical Equipment Air-handling Equipment Heating Equipment Boilers Furnaces
More informationSubmitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas
More information4. OVERVIEW OF MECHANICAL SYSTEM
4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in
More informationINTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings
INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,
More informationTechnical Assignment 3
0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Technical Assignment 3 Mechanical Systems and Existing Conditions Report David H. Koch Institute for Integrative
More informationAppendix 13. Categories of Cooling and Heating systems
EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01
More informationThe Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and
More informationBOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:
4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This
More informationSECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof
More informationDehumidifying with Dedicated Outdoor Air
Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,
More informationBOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:
4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XIN INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This
More information2009 IECC Commercial Mechanical Requirements
BUILDING ENERGY CODES UNIVERSITY 2009 IECC Commercial Mechanical Requirements Ken Baker PNNL-SA-66171 Learning(Objec-ves(( ( 1. Find(minimum(equipment(efficiency(requirements( and(recite(at(least(3(common(terms(for(measuring(
More informationHVAC 101. The Basics of Heating, Ventilation and Air Conditioning
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning HVAC Heating, Ventilation and Air Conditioning Provides comfort for people Allows humans to exist under adverse conditions. Comfort Comfort
More informationCHAPTER 4. HVAC DELIVERY SYSTEMS
CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer
More informationEarthWise System Seminar
EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States
More informationVH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control
VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Unit with Enhanced Humidity Control Motorized Bypass Damper Temperature and Humidity Controller Reheat Control Elastomeric Foam Insulation High Efficiency,
More informationAHRI Certification Program Scopes - COOLING
Air-to-Air Energy Recovery Ventilators (AHRI Std. 1060) Automatic Commercial Ice-Cube Machines and Ice Storage Bins (AHRI Stds. 810 & 820) Central Station Air-Handling Units (AHRI Std. 430) Commercial
More informationAugust 15, 2013 Page 1 of 19
Section C401 Application Compliance with C402, C403, C404 and C405 AND (either C406.2, C406.3 or C406.4) Compliance with C402, C403, C404 or C405 Section C402 Building Envelope (Climate Zone 5A) Space-Conditioning
More information1 - This title will copy onto other forms Date
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 Mechanical Summary MECH-SUM Project Title: 1 - This title will copy onto other forms Date 1/1/2015
More informationAndrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3
Existing System Evaluation Executive Summary The MBNA Career Services Center is a 44,000 square foot, 4-story office type building at Penn State University, University Park Campus. The building is located
More information1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT
Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#56566/Page 1/May 23, 2017 HVAC Heating Plant The original Town Hall building and Addition building are primarily heated by a gas fired hot water plant that is located in the basement. The boiler plant
More informationSubmitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University
More informationMuseum Archive Dehumidification in Hot & Humid Climates
Museum Archive Dehumidification in Hot & Humid Climates B. K. Browning, PE Principal Engineer KWR Services Austin, Texas ABSTRACT This paper discusses some of the difficulties found with a desiccant dehumidification
More informationBy Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE
By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE T he advent of the small scroll or screw chiller, capable of producing condenser water as high as 140
More informationThe ultimate fresh air solution.
Fresh Access The ultimate fresh air solution. Introducing Fresh Access TM. Expertly designed, our innovative energy recovery ventilator (ERV) unit, split dedicated outside air system (DOAS), and packaged
More informationDehumidification: Energy Efficiency Comparisons
Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,
More informationMECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY
MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY 2018 57 MECHANICAL ASSESSMENT MECHANICAL ASSESSMENT This report section includes an overview of the existing
More informationHVAC Mandatory Provisions Part II, Page 1
HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency
More informationTechnical Assignment 3 11/15/04. Executive Summary
Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria
More informationThe Temperature and Relative Humidity Control in Cushing Library
The Temperature and Relative Humidity Control in Cushing Library Chenggang Liu Research Associate Song Deng Assistant Director Homer L. Bruner, Jr., CEM Mechanical Systems Specialist Utilities Office of
More informationSECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...
SECTION 230001 TABLE OF CONTENTS SECTION 230001 PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS... 1 1.00 FILED SUB BID... 1 1.01 PROJECT OVERVIEW... 2 1.02 DESIGN CRITERIA... 4 1.03 CODE ISSUES...
More informationChilled Water system
Chilled Water system Introduction For large installations the Condenser, Evaporator, Compressor and Expansion device can be purchased as a package unit, known as a Chiller. The usual package consists of
More informationTrane CDQ Desiccant Dehumidification
Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features
More informationDIVISION 15 MECHANICAL
DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with
More informationAHRI Product Section and Subsection Scopes
Air Control and Distribution Devices Product Section Air-Cooled and Evaporative Condensers Subsection Air-Cooling and Air Heating Coils Subsection Air-to-Air Energy Recovery Ventilation Product Section
More informationUNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationA. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.
SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate
More informationHVAC 101. H V A C S y s t e m s
H V A C 1 0 1 S y s t e m s Introduction & Overview Should you care? Mechanical System Types Components & operation Popular Application Key Issues and Design Considerations System Comparisons First Cost
More informationNYC Department of Education
Asset: P.S. 22 - STATEN ISLAND, 1860 FOREST AVENUE, New York, 10303 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-08 8:51 AM 2017-12-18 4:14 PM Asset Data Are there fuel tanks?
More informationMT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS
CARROLL COUNTY PUBLIC SCHOOLS LIFE CYCLE COST ANALYSIS SUMMARY DGS PROCEDURES FOR THE IMPLEMENTATION OF LIFE CYCLE COST ANALYSIS AND ENERGY CONSERVATION OCTOBER, 2010 G.A.I.#09090 GIPE ASSOCIATES, INC.
More informationNational Institutes of Health Building 37 Modernization Bethesda, Maryland MECHANICAL DEPTH EXISTING MECHANICAL SYSTEM
MECHANICAL DEPTH EXISTING MECHANICAL SYSTEM The need to maintain occupancy during the renovation and the strict NIH Design Guidelines were the main driving forces behind the design. The mechanical engineering
More informationImproving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks
Improving Performance with a Building Tune-Up Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks How much is too much? Most buildings can cut total energy use by 5-30% while
More informationNYC Department of Education
Asset: LIBERTY HS - MANHATTAN, 250 WEST 18 STREET, New York, 10011 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-29 11:32 AM 2018-02-01 10:16 AM Asset Data Are there fuel tanks?
More informationENGINEERING. Edition No. 13 October 2002
Edition No. 13 October 2002 ENGINEERING S Y S T E M S O L U T I O N S W e at McQuay are very proud of our tradition of producing industry leading water source heat pumps. Our heritage stretches back more
More informationTechnical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer
Technical Development Program PRESENTED BY: COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems Ray Chow Sales Engineer TDP Updates Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section
More informationTechnical Report #3 Mechanical Systems Existing Conditions Evaluation
Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents
More informationPINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION
ENERGY EFFICIENT DEHUMIDIFICATION PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM Provides a very high degree of latent cooling using only a minimal amount of conventional cooling input Substantial energy
More informationRN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.
RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities
More informationCustom Air Handler Solutions Custom Units to Meet Your Unique Design Needs
Custom Units to Meet Your Unique Design Needs Engineered for flexibility and performance Contents Horizontal Configuration....1 Horizontal with Standard Economizer Configuration...2 Stacked Configuration...3
More informationInspection Phase Three. Mechanical, Electrical & Plumbing Section 503
Inspection Phase Three Mechanical, Electrical & Plumbing Section 503 COMCheck Mechanical Field Inspection Checklist Mechanical Mechanical, Electrical & Plumbing Equipment Efficiencies But a lot ore too
More informationHumidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President
Humidity Control Design Tips R. Mark Nunnelly, PE, CxA, LEED AP President AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationCOMcheck Software Version Review Mechanical Compliance Certificate
COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project
More informationCARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems
Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.
More informationSubmitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner
ESL-TR-99/12-09 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Commerce (TAMU-Commerce) Commerce, Texas Submitted to Texas
More informationCOMcheck Software Version Mechanical Compliance Certificate
COMcheck Software Version 3.8.2 Mechanical Compliance Certificate 90.1 (2007) Standard Section 1: Project Information Project Type: New Construction Project Title : Rudy's Star Motors Construction Site:
More informationASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee
ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique CTTC
More information60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES
60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#57295/Page 1/July 21, 2017 HVAC SYSTEMS NARRATIVE REPORT The following is the HVAC system narrative, which defines the scope of work and capacities of the HVAC system as well as the Basis of Design.
More informationJob Name Control Systems Description Date
Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In
More informationEnergy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE
This article was published in ASHRAE Journal, March 20145 Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationDEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks
DEHUMIDIFICATION: Ice Arena Application & Product Guide Design, construct and operate to control indoor humidity in ice rinks Munters is the world leader in dehumidification Munters is the largest manufacturer
More informationTable of Contents. List of Figures and Tables. Executive Summary: 3 ASHRAE Standard 62.1 Section 6 Analysis 7
Army Reserve Center Newport, Rhode Island Technical Report One: ASHRAE Standard 62.1 Ventilat tion and Standard 90.1 Energy Design Evaluations October 4, 2010 2 Table of Contents Executive Summary: 3 ASHRAE
More information"This is only the scope of work for the project. For more information, interested parties should contact Procurement at
"This is only the scope of work for the project. For more information, interested parties should contact Procurement at purchasing@stpgov.org to ensure receipt of a full bid package, to be listed as a
More informationChallenges and Methods of Estimating a Conceptual HVAC Design
Challenges and Methods of Estimating a Conceptual HVAC Design ABSTRACT In any conceptual HVAC design, estimators are faced with the challenge of trying to capture all of the pieces that complete a system.
More informationHigh Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO
High Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO 2012 1 Learning Objectives for this Session Get acquainted with typical systems used in the
More informationS.A. Klein and G.F. Nellis Cambridge University Press, 2011
12.A-1 A mixture of helium and water vapor is flowing through a pipe at T= 90 C and P = 150 kpa. The mole fraction of helium is y He = 0.80. a.) What is the relative humidity of the mixture? b.) What is
More informationAir-Handling System Cooling Options
Air-Handling System Cooling Options High-Capacity, Economical Evaporative Cooling High-Efficiency, DX & CW Mechanical Cooling Pure and Simple Solutions AbsolutAire Air-Handling System Cooling Options Economical
More informationREPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop
Energy-Savings Strategies for Rooftop VAV Systems Occupied set-point temperature Unoccupied set-point temperature Rooftop variable-air-volume (VAV) s are used to provide comfort in a wide range of building
More informationEADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option
EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationTechnical Report Three
Technical Report Three Existing Conditions for Mechanical Systems Contents Executive Summary...2 Building Overview...2 Mechanical Systems Overview...2 Mechanical System...3 Outdoor & Indoor Design Conditions...3
More informationDX Units. Ranging from 15 to 750 tons and 1,000 to 300,000+ CFM
D Units Ranging from 15 to 750 tons and 1,000 to 300,000+ CFM INDUSTRY-LEADING HVAC MANUFACTURER Nortek Air Solutions is the largest custom HVAC manufacturer in North America, with a combined total of
More informationFAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney
FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1
More informationFLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK
FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated
More informationIntroduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN
Introduction to HVAC Agenda Psychrometrics Human Comfort Heat Transfer Refrigeration Cycle HVAC Terminology HVAC Systems Introduction to HVAC Psychrometrics 2000 TRG-TRC002-EN Properties of Air Dry-bulb
More informationMechanical Systems Thesis Proposal: Calvert Memorial Hospital Prince Frederick, MD Holly Mawritz
: Holly Mawritz Senior Thesis Project Proposal Penn State University Department of Architectural Engineering Mechanical Emphasis Faculty Consultant: Dr. Jim Freihaut 12-10-04 Table of Contents: Executive
More informationHeat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features:
Heat Pumps M2 SERIES Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features: Water-source and geothermal heat pump self-contained units with capacities from 3-70 tons 10%-100% variable
More informationExplanation of Cooling and Air Conditioning Terminology for IT Professionals
Explanation of Cooling and Air Conditioning Terminology for IT Professionals White Paper #11 Revision 1 Executive Summary As power densities continue to increase in today s data centers, heat removal is
More informationRoofPak Applied Rooftop Systems
RoofPak Applied Rooftop Systems RoofPak Applied Rooftop Systems Design flexibility, energy efficiency, system performance and reliability make Daikin RoofPak applied rooftop systems the ideal solution
More informationVapor-Compression Refrigeration
Vapor-Compression Refrigeration condenser D C expansion device compressor A B evaporator Types of Heat Pumps water-source heat pumps water-to-water heat pump air-source heat pumps Cooling Heating
More informationterminal units only provide sensible cooling, a separate dehumidification system is usually needed.
providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can
More informationStrategies for Building Energy Efficiency
Strategies for Building Energy Efficiency Ben Sliwinski Technical Director SEDAC University of Illinois at Urbana-Champaign How Buildings Use Energy Building Envelope (Walls, Roof, Windows, Floors) Lighting
More informationGil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee
Gil Rossmiller In the construction industry for over 30 years ICC IRC Plumbing & Mechanical Code Development Committee ICC- IECC Commercial Energy Code Development Committee Building Official Parker, Colorado
More informationMadeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)
Madeira City Schools Madeira, Ohio HVAC Assessment December 2011 (Revised February 2012) Prepared by: CMTA Engineering Consultants, Inc. 10411 Meeting Street Prospect, KY 40059 www.cmtaegrs.com (502) 326-3085
More informationExisting Mechanical System Operation
majority of the air handlers. There are louvers along the north side of the building that allow for outdoor air to come in and feed the air handlers. On levels 4-8 the research laboratories are variable
More informationNYC Department of Education
Asset: I.S. 45 - BRONX, 2502 LORILLARD PLACE, New York, 10458 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-05 9:14 AM 2017-12-20 11:42 AM Asset Data Are there fuel tanks? Total
More informationAHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency
Application Note 24 AHRI 920 Performance Rating and Comparisons I NTRODUCTION In 2015, the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) introduced a performance rating for dedicated outside
More informationProblems Air and Water Distribution Systems
Problems Air and Water Distribution Systems ME419 D. Abata 1. Cooled air at 1 atm, 50 F, and 10% relative humidity is transported in a 600 ft long circular sheet metal duct at a rate of 800 cfm. If the
More informationNYC Department of Education
Asset: MID MAN ADULT LRNG CTR (81) - M, 212 W 120TH ST, New York, 10027 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-17 8:16 AM 2018-01-17 8:17 PM Asset Data Are there fuel
More informationChristopher Kelly Technical Report Three
Christopher Kelly Technical Report Three Mechanical Systems and Existing Conditions Evaluation SALK HALL ADDITION The University of Pittsburgh, Pittsburgh Christopher Kelly, Mechanical Option Professor
More informationCOMMERCIAL HVAC EQUIPMENT Indoor Self-Contained Units
COMMERCIAL HVAC EQUIPMENT Indoor Self-Contained Units Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection
More informationPRODUCT SERIES. VPR Series VPRX Series VPRE Series VPRP Series VPRC Series
PRODUCT SERIES VPR Series VPRX Series VPRE Series VPRP Series VPRC Series Valent Air Management Products Valent Air Management Systems designs and manufactures reliable, high-outdoor-air ventilators. Our
More information