HVAC Clinic. Helical Rotary & Centrifugal Water Chillers

Size: px
Start display at page:

Download "HVAC Clinic. Helical Rotary & Centrifugal Water Chillers"

Transcription

1 HVAC Clinic Helical Rotary & Centrifugal Water Chillers

2 Table Of Contents Introduction... 3 Chiller Types... 3 Chiller Components... 4 Refrigeration Cycle Application Considerations... 19

3 Introduction Two types of chiller technologies dominate the large chiller landscape. For the purposes of this discussion, large tonnage chillers will be chillers with a nominal capacity rating greater than 200 tons. The two dominant technologies utilized in large tonnage chillers are helical rotary chillers and centrifugal compression chillers. A third chiller technology, absorption refrigeration chillers, comprises a small percentage of the North American chiller market. Absorption chiller technologies will not be discussed in this clinic. Figure 1. Helical Rotary and Centrifugal Chillers Chiller Types Types Of Helical Rotary Chillers Helical rotary chillers can be either water cooled or air cooled (figure 2). Air cooled chillers are typically available from 150 to 500 ton at efficiencies from 1.0 kw/ton to 1.3 kw/ton. Water cooled helical rotary chillers are typically available from 100 to 675 tons at efficiencies from 0.55 kw/ton to 0.7 kw/ton at ARI conditions. Helical rotary chillers, either air or water cooled, are ideally suited for small to medium sized applied systems. Air cooled systems are less costly to install and require less maintenance, largely due to the lack of water treatment, compared to equivalent water cooled systems. However, air cooled systems operate at lower efficiencies compared to comparably sized water cooled systems. In addition, water cooled systems may employ a waterside economizers, a feature that is relatively expensive to employ with air cooled systems. Figure 2. Helical Rotary Chillers WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 3 of 25

4 Types Of Centrifugal Chillers Centrifugal chillers, due to their larger inherent size and lower head generating capabilities, are generally limited to water cooled and evaporative condensed applications (figure 3). However, with the advent of smaller magnetic levitation machines, some air cooled magnetic levitation centrifugal chillers are produced by a few select manufacturers. Water cooled centrifugal chillers are typically available from 100 tons to 6000 tons. Efficiencies, for water cooled machines, range from 0.45 kw/ton to 0.6 kw/ton. Magnetic levitation air cooled centrifugal chillers can operate at efficiencies as low as 0.9 kw/ton at full load and 0.45 kw/ton at 50% load. Figure 3. Centrifugal Chillers Chiller Components Helical Rotary Compressors Helical rotary chillers are generally comprised of an evaporator, one or multiple twin rotary compressors, a motor (either open or suction gas cooled), an oil separator, condenser, an electronic expansion device, evaporator, starter and control panel (figure 4). Each of these components will be explored in detail. Figure 4. Helical Rotary Chiller Components Two general types of vapor compression compressors are predominantly used in the HVAC industry. Those types are positive displacement compressors and dynamic compression compressors. Positive displacement compressors reduce the amount of refrigerant volume within the compression chamber, thus increasing its pressure. Dynamic compression cycles utilize the principle of static regain (as discussed in the duct clinic) to increase static pressure through changes in velocity pressure. Helical rotary compressors are positive displacement type compressors. A helical rotary compressor traps the refrigerant vapor between a male and female rotor and compresses it by decreasing the volume of the refrigerant (figure 5). WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 4 of 25

5 Figure 5. Male and Female Rotors The majority of helical rotary compressor designs use two mating screw rotors to perform the compression process. The male rotor is driven by the compressor motor. The lobes of the male rotor make contact and drive the female rotor, causing the two rotors to counter rotate. Refrigerant vapor enters the compressor housing through the intake port and fills the pockets formed by the lobes of the rotors (figure 6). As the rotors turn, they push these pockets of refrigerant toward the discharge end of the compressor. The continued rotation of the rotors forces the refrigerant to meshing point. It is at this point that the refrigerant begins to compress (point D). Finally, when the pockets of refrigerant reach the discharge port, the compressed vapor is released. Figure 6. Compression Process Centrifugal Compressors Unlike helical rotary compressors, which work on the principle of positive displacement compression, centrifugal compressors operate on the principle of dynamic compression. Dynamic compression involves the conversion of energy, from one form to another. In the case of a centrifugal compressor, kinetic energy is converted to static energy. The main component of a centrifugal compressor is the impeller. In a closed face impeller, relatively low pressure refrigerant vapor is drawn into the eye of the impeller. Within the impeller body are blades that are fitted between two enclosed surfaces (for closed faced impellers). The rotation of the impeller causes the refrigerant vapor to accelerate within the blades (impeller passages), thus increasing its velocity. As the refrigerant velocity is increased, its kinetic energy is increased. Figure 7. Centrifugal Impeller WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 5 of 25

6 After exiting the impeller, high velocity, high kinetic energy refrigerant enters the diffuser passages (figure 8). These passages initially match the outlet area of impeller outlet. However, as the refrigerant passes down the length of the diffuser, the passages gradually increase in size. As the passages increase in size, the refrigerant velocity decreases. Following the first law of thermodynamics, which states energy cannot be destroyed, only converted from one form to another; the refrigerant energy is converted from kinetic to static energy. This employs the same phenomenon employed with duct static regain, as discussed in previous clinics. Figure 8. Diffuser & Volute The higher pressure refrigerant, as it exits the diffuser, collects in the volute. Like the diffuser, the volute increases in volume as the refrigerant travels through its passages which further converts kinetic or velocity energy to static energy. Finally, the refrigerant exits the compressor and travels to the condenser (figure 9). Figure 9. Compression Cycle A centrifugal compressors part load capacity can be modulated with inlet guide vanes, a variable frequency drive, or a combination of both. Traditionally, inlet guide vanes were used to control chiller capacity. Inlet guide vanes prespin the refrigerant before it enters the impeller passages. This pre-spinning of refrigerant reduces the grab or dynamic energy the impeller can impart on the incoming refrigerant stream (figure 10). Figure 10. Inlet Guide Vanes WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 6 of 25

7 Newer centrifugal compressor designs have incorporated variable frequency drives (VFD) to modulate the compressor speed at part load. Centrifugal compressors utilize dynamic compression which lends itself very well to the use of VFD s. In the past, the cost of VFD s made them prohibitively expensive to utilize in centrifugal compressor designs. In recent years, the cost of VFD s has been reduced substantially. While variable frequency drives present a slight penalty at full load performance, they offer substantial energy savings at part load. At part load, the variable frequency drive is modulated in conjunction with the inlet guide vanes in order to optimize efficiency and chiller operation. A recent technological advancement to centrifugal compressors involves the use of magnetic levitation bearings. Within a magnetic levitation centrifugal, the main drive shaft and impeller are magnetically levitated through the use of specially designed magnetic bearings (figure 11). Much like a magnetic levitation high speed train, the shaft and impeller float within a magnetic cushion, eliminating any contact friction. Implementing magnetic bearings can dramatically improve efficiency, reduce noise and improve reliability. In addition, systems that utilize magnetic drives do not require oil. The oil in a system acts as an added barrier to heat transfer. Oil coats heat exchange surfaces, both the evaporator and condenser, decreasing efficiency. In addition, oil-less systems simplify the machine design (the oil management system is removed) and reduces maintenance. Inlet guide vanes are generally not used in magnetic bearing designs. Furthermore, magnetic bearing machines often operate at motor speeds well above 3600 RPM (generally between 20,000 and 45,000 RPM), requiring the use of frequency drives in order to achieve the required motor speed (figure 11). Figure 11. Magnetic Levitation Compressor Magnetic drive machines may use multiple smaller open faced impellers which rotate at very high speeds (>40,000 RPM) or a single larger closed faced impeller which rotates at a slower speed (20,000 RPM). Generally speaking, a larger closed face impeller will offer better aerodynamics compared to a similar capacity machine utilizing multiple open faced impellers. The aerodynamics of an impeller is directly related to the chillers efficiency. Oil Management Following the compressor, the refrigerant may be fed into an oil separator. Oil separators are utilized is most helical rotary and many centrifugal chiller designs. The oil separator is a centrifugal device that separates the oil from refrigerant vapor (figure 12). The centrifugal motion of the refrigerant vapor forces the oil outward to the walls of the cylinder. The oil collects on the walls, eventually draining to the bottom of the device and collects in the oil sump and is recycled through the system. Generally, the oil sump is heated in order to ensure proper lubrication and to minimize condensation. The oil free refrigerant discharges through the top of the oil separator and passes to the condenser. A chillers oil separator is generally capable of separating more than 99% of the systems oil from the refrigerant vapor. Figure 12. Oil Separator WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 7 of 25

8 The oil that discharges the compressor is at condensing pressure. At this higher pressure, the oil is always trying to flow to the lower pressure components of the system. After the oil discharges the oil separator, it passes through an oil management system. The first component of the oil management system is generally the oil reservoir. Here the oil collects before being distributed to the gears (if machine is gear driven), bearings and shaft seal (if open drive). The oil reservoir is often located above the compressor such that oil can be gravity fed to the system in case of power failure. After the oil is delivered to the critical components, it collects in the oil sump. Within the sump, some manufacturers utilize an oil pump to maintain oil pressure. Other manufacturers choose to use the difference in pressure between the condenser and evaporator to create the differential pressure required to adequately deliver oil to critical components. Generally speaking, chillers which employ oil pumps are able to run at lower condenser pressures as they do not require differential pressure to move oil. This enables these machines to run at lower entering condenser water temperatures, without the use of head pressure control. Finally, the oil passes through an oil filter before completing the cycle (figure 13). Figure 13. Oil Management System While oil separators are very efficient, they are not 100% efficient. Thus, the refrigeration system must be designed to adequately move the oil throughout the entire system. This includes the condenser, evaporator and refrigerant connections. Condensers After the refrigerant vapor discharges the oil separator, it is directed to the condenser. Both helical rotary and centrifugal water cooled chillers generally utilize a shell and tube condenser. In a shell and tube condenser, water is allowed to run through the interior of the tubes that form the heat exchanger while refrigerant vapor fills the shell space surrounding the tubes (figure 14). By allowing the condenser water to run through the tubes, maintenance personnel can clean the tubes in the event of scale formation. Alternately, if the refrigerant was to run through the tubes, the heat exchanger would not be cleanable. As heat is absorbed by the cooler condenser water, the refrigerant vapor condenses on the tube surfaces. The condensed refrigerant liquid then falls to the bottom on the shell. At the bottom on the shell, additional tubes called the subcooler further cool the liquid refrigerant. The subcooler prevents liquid refrigerant from flashing before it enters the expansion device. As the refrigerant vapor condenses, the condenser water temperature will be increased and returned to the heat rejection device. Figure 14. Condenser WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 8 of 25

9 Alternately, an air cooled chiller employs an air cooled condenser in lieu of a water cooled condenser. Air cooled condensers generally use propeller-type fans to draw outdoor air over a finned-tube heat transfer surface. The temperature difference between the hot refrigerant vapor that is flowing through the tubes and the cooler outdoor ambient air induces heat transfer. The resulting reduction in the heat content of the refrigerant vapor causes it to condense into liquid. Located in the bottom, last few rows of condenser tubing is the subcooler. In the subcooler, the refrigerant is cooled below the saturation temperature or subcooled (figure 15). Figure 15. Air Cooled Condenser Evaporative condensers provide many of the energy advantages of water cooled systems while simplifying the design of the system. An evaporative condensers efficiency is a function of the ambient wet bulb temperature. Thus, in drier climates, machines with evaporative condensers can provide tremendous energy efficiency gains (figure 16). In addition, due to the reduced condenser pressures experienced with evaporative condensing machines, centrifugal compressors (including magnetic levitation) can be utilized. Figure 16. Evaporative Condensed Magnetic Levitation Chiller An evaporative condenser functions by evaporating water as it is transferred across a warm heat exchanger (condenser). As discussed in previous clinics, the heat of vaporization is much higher than typical sensible only cooling. Hence, an evaporative condensed heat exchanger can function much more efficiently that a comparable dry heat exchanger. However, one of the inherent disadvantages to any evaporative process is the deposition of solids that occurs as water evaporates. Some manufacturers utilize a dry sensible pre-cooler to pre-cool the hot discharge refrigerant before it enters the wet evaporative condensed heat exchanger (figure 17). The formation of solids is decreased as the approach temperature between the two fluid streams is decreased. When utilized, a dry pre-cooled can virtually eliminate most scale formation. Water treatment may still however be required, depending on the quality of water being used in the evaporative condenser. WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 9 of 25

10 Figure 17. Evaporative Condenser Refrigerant Metering Device After the liquid refrigerant exits the condenser subcooler, it passes through some type of expansion device. The expansion device maintains the pressure difference between the low side and the high side of the machine. This device is commonly either an orifice type expansion device or an electronic expansion device. Both modulating orifice and electronic expansion devices are common to helical rotary chillers. Conversely, fixed orifice expansion devices are typically employed with centrifugal chillers. The expansion device controls the refrigerant flow in order to maintain a fixed amount of superheat exiting the evaporator. Without proper superheat, liquid may enter the compressor, causing the potential for premature failure. Figure 18. Expansion Device Evaporator Saturated refrigerant exits the expansion device and enters the evaporator. The evaporator in a helical rotary chiller may be either a direct expansion or flooded type evaporator. Centrifugal chillers, in contrast, generally utilize flooded evaporators. In a direct expansion type evaporators, the refrigerant flows through the tubes while the water flows over the outside of the tubes. Conversely, in a flooded type evaporator, the water flows through the tubes and the refrigerant is distributed in a uniform manner over the outside of the tubes (figure 19). WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 10 of 25

11 Figure 19. Evaporator Most contemporary water and air cooled helical rotary compressors utilize flooded type evaporators. Flooded evaporators offer the advantage of being both cleanable and offering a smaller capacity and efficiency degradation when operating with glycol. Air cooled chillers utilizing flooded evaporators becomes especially important when in colder climates. In colder climates, glycol is often an operating requirement in order to prevent freezing of components and ultimately damage to the system. Air cooled machines employing direct expansion type evaporators will experience a significant capacity and energy efficiency reduction when running glycol. A variation of the flooded evaporator is the falling film type evaporator (figure 20). In a typical flooded evaporator, the refrigerant enters at the bottom shell (figure 19). In contrast, in a falling film flooded evaporator, the refrigerant is sprayed over the top of the tube bundle rather than entering through the bottom of the heat exchanger. The evaporator contains two tube bundles. The first, the falling film tube bundle, contains the first tubes that make contact with the refrigerant which is distributed by means of the spray header. After the refrigerant passes over the falling film tube bundle, any remaining liquid refrigerant settles to the bottom of the heat exchanger and transfers heat to the flooded tube bundle. Refrigerant vapor passes through the suction slot and finally passes through the suction flange and on to the compressor. Figure 20. Falling Film Evaporator A falling film evaporator, compared to a traditional flooded evaporator, generally reduce the total refrigerant charge by as much as 40%. In addition, the improved heat exchanger characteristics of a falling film evaporator will generally improve the efficiency characteristics of the chiller. If air cooled machines with direct expansion type evaporators are used, the designer should consider locating the evaporator inside the conditioned building so as to avoid the use of glycol. This option, known as a remote evaporator, is available with several manufacturers of air cooled helical rotary chillers (figure 21). While this type of WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 11 of 25

12 installation may increase the installation cost, due to the cost of the added refrigerant piping, the payback on investment achieved by avoiding the use of glycol should be significant. Figure 21. Remote Evaporator Starters Chillers cause large electrical loads with a large instantaneous inrush current. Because of this instantaneous electrical load, helical rotary and centrifugal chillers cannot be started and stopped using a contact closure. A starter s primary function is to connect and disconnect the chiller from the incoming line. Three types of starters are common with helical rotary and centrifugal chillers. These are: Electro Mechanical Starters o Wye-Delta closed transition starter Electronic Starters o Solid State Starter o Variable Frequency Drive Figure 22. Starter Types In a typical across the line starter, the jobsite full load amps (FLA) are the same as the motor full load amps (figure 23). WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 12 of 25

13 Figure 23. Across The Line Starter The amp draw during startup, for the first few fractions of a second, is very large. This is due to the energy required to overcome static friction at startup. This large amp draw condition is referred to as locked rotor amps (figure 24). Figure 24. Amp Draw of Across the Line Starter A wye-delta starter is type of reduced voltage starter that makes use of the characteristics of wye and delta connections to reduce voltage without lowering current (figure 25). A wye-delta starter reduces inrush current by 66% compared to an across the line starter. Star-Delta starters require a special six lead motor which allows connection of the three phase windings in a Star connection or Delta connection. Figure 25. Star-Delta Starter WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 13 of 25

14 During starting, the motor is connected in a Star or Wye configuration. This reduces the voltage to the motor stator by a factor of three. This 1/3 voltage results in 1/3 current into the motor at start and 1/3 torque to the shaft. Centrifugal compressor starting torque requirements are low enough to allow the motor to start at 1/3 of full load torque. If line voltage is low as in a brown-out condition, the motor may not have sufficient starting torque to reach full speed until the delta transition occurs, resulting in a large current spike and mechanical torque shock to the driveline. Essentially, this condition causes the motor to start across the line after pulling 1/3 LRA from the line for 40 seconds. Obviously, this is less than desirable condition. Star-Delta starting creates stresses for the starter's switchgear, building electrical system, power grid, and chiller mechanical driveline. Although these stresses are 1/3 of the stresses generated by an ACL starter, they cause wear on the system. Star-Delta starters require periodic maintenance and are only available for low voltage motors. Solid state starters utilize silicone controlled rectifiers (SCR s) to control current levels at startup. This method is more expensive than across the line or wye-delta starters, but offers variable voltage and torque. Solid state starters reduce motor stress by softly ramping inrush current. The solid state starter provides a soft continuous current to the chiller motor during motor starting, limiting the inrush of current to a programmed starting value, by reducing the voltage to the motor during startup. This reduced voltage is accomplished when the silicone controlled rectifiers (SCRs) are turned on in a phased back mode during motor acceleration. As the motor accelerates and the inrush of current begins to drop, the SCR devices are fired with less delay time so that more of the AC main voltage is conducted. Once the motor is up to speed there is no longer any delay applied to the firing signals. The SCR devices are turned on full voltage is applied the motor. Figure 26. Solid State Starter Finally, variable frequency drives are becoming relatively prevalent in the design of helical rotary drives. Variable frequency drives modulate the incoming frequency in order to softly start the machine. Power is directly related to frequency in a linear fashion. For example, if we cut the frequency in half, the power delivered to the motor is cut in half. Thus, by modulating the frequency, a variable frequency drive can vary the power and torque delivered to a motor (figure 27). Figure 27. Variable Speed Drive WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 14 of 25

15 Variable frequency drives have the added benefit of being able to help control the part load capacity of the machine. Additionally, the starting current profile for a VSD shows a smooth increase in current as power is applied to the motor (this is similar to, but better than a solid state starter). Because the VSD supplies power at variable frequencies, starting power is applied at very low frequency yielding much higher torque than with a solid state starter. Therefore, the starting current does not exceed the full load value for the motor. This profile is the least stressful to the motor, drive line, and electrical system. Figure 28. VSD Starting Profile Control Panel The last component common to all helical rotary and centrifugal chillers is the unit control panel. The control panel is the brain that operates the chiller. The control panel governs the operation of the compressor in coordination with the expansion device and condenser fans (if air cooled) in order to maintain the leaving chilled water temperature. In addition, the control panel monitors the chillers operation and prevents it from operating outside of its limits. Finally, the chiller control panel should provide a simple means by which building operators can diagnose and troubleshoot the machine. Most modern chillers utilize a large easily read display, some of which utilize touchscreen technology, to present the information to the building operator (figure 28). Figure 29. Control Panel Refrigeration Cycle A typical vapor compression refrigeration cycle as it applies to a typical helical rotary or centrifugal chiller is demonstrated in figure 30. First, cool, low pressure saturated liquid (A) plus vapor enters the evaporator. The evaporator absorbs heat from the warmer the conditioned fluid, superheating the refrigerant. The superheated refrigerant vapor is then drawn in to the suction side of the helical rotary compressor (B). The compressor draws in the superheated refrigerant vapor (B) and compresses it to a higher pressure and temperature (C) such that it can reject heat to another fluid. This hot, high-pressure refrigerant vapor then travels to the condenser. As the refrigerant passes through the condenser, heat is transferred from the hot refrigerant vapor to relatively cool heat rejection fluid (water if water cooled or air if air cooled). This reduction in the heat content of the refrigerant vapor causes it to desuperheat, condense into a liquid, and finally subcool before leaving the condenser (D) for the expansion device. WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 15 of 25

16 Finally, the high-pressure liquid refrigerant (D) flows through the expansion device. The flow through the expansion devices causes a large pressure drop that reduces the pressure of the refrigerant to that of the evaporator. This pressure reduction causes a small portion of the liquid to boil off, or flash, cooling the remaining refrigerant to the desired evaporator temperature. The cooled mixture of liquid and vapor refrigerant then enters the evaporator (A) ad repeats the cycle (figure 30). Figure 30. Vapor Compression Refrigeration Cycle The vapor compression refrigeration cycle described in figure X is common to a large percentage of helical rotary chiller designs. However, adaptations to the cycle have been incorporated by some manufacturers in order to improve the efficiency of the cycle. A shortcoming to the vapor compression refrigeration cycle described in the pressure enthalpy chart of figure 30 is that some refrigeration effect is lost due to flashing of liquid refrigerant within the saturation dome. This flashing occurs due to the nature and slope of the saturated liquid line curve. Any degree of subcooling prior to the expansion device will cause an excess of saturated vapor prior to the evaporator. This shortcoming can be alleviated by installing a refrigeration economizer cycle (figure 31). Figure 31. Economizer Cycle Before refrigerant enters the expansion device, any refrigerant vapor is allowed to separate from liquid refrigerant in an economizer flash tank. As the chiller loads, the economizer feed valve opens, allowing the medium pressure vapor part way through the compressor rotors. Viewed on a pressure-enthalpy chart, subcooled liquid refrigerant exits the condenser (1). The subcooled liquid refrigerant experiences a pressure drop as it passes through the refrigerant piping and feed valve, causing some refrigerant to flash into vapor (point 1 to 2). Medium pressure vapor is fed to the compressor rotors (point 2 to 6) while liquid refrigerant is allowed fall to the bottom of the economizer flash tank (point 2 to 3). The liquid refrigerant passes WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 16 of 25

17 through the expansion device before entering the evaporator (point 3 to 4). The difference in refrigeration effect, due to the implementation of the economizer cycle, is shown by R. This added refrigeration effect increases the capacity and efficiency of the helical rotary chiller. Figure 32. Helical Rotary Economizer PH Cycle Similarly, an economizer cycle if often utilized with Centrifugal chiller applications. In order to utilize an economizer cycle within a centrifugal chiller, the chiller must either implement multiple impellers or multiple compressors. Much like a helical rotary machine, a centrifugal chiller economizer cycle will flash some degree of refrigerant vapor during the expansion process (point 1-2). This flashed refrigerant vapor is then fed to the compression cycle (figure 33). This lower energy vapor is fed at some intermediary point in the compression cycle, lowering the heat of compression during the compression cycle (point 6-7). Figure 33. Centrifugal Economizer PH Cycle This lowered heat of compression further increases the efficiency of the refrigerant cycle. It is at this point that economizer designs may vary slightly among the manufactures which employ centrifugal chillers with economizer cycles. Much like a helical rotary chiller, the vapor which is flashed during the expansion process WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 17 of 25

18 should be introduced at an equal pressure point during the compression cycle. In a helical rotary chiller, that involves introducing the refrigerant vapor at some intermediary point along the length of the rotary compressors. However, the inherent design of a centrifugal compressor does not allow for a means of introducing refrigerant vapor at an intermediary compression point. Thus, economizers utilized with centrifugal chiller designs require multiple stages of compression. This can be accomplished with either multiple impellers connected to a single motor or multiple impeller and motor combinations (figure 34). Figure 34. Centrifugal Economizer Cycle In either scenario, both the refrigeration effect is increased and the heat of compression is effectively decreased. This has the effect of both increasing the capacity and efficiency of the chiller. Thus, if multiple stages of compression are available, an economizer cycle is an effective means of increasing chiller capacity and efficiency. Helical Rotary Compressor Modulation Helical rotary compressor can be modulated with either a slide valve or a variable frequency drive. The position of the slide valve along the rotors controls the volume of refrigerant vapor delivered by the compressor. It does this by varying the amount of rotor length that can be used for compression (figure 35) by exposing the chamber that would otherwise be trapped by the refrigerant vapor. By changing the position of the slide valve, the compressor is able to load and unload. Some manufacturers utilize a variable position slide valve which can precisely match the system load. Other manufacturers use a stepped position slide valve. The stepped position slide valve operates much like the scroll staging example discussed earlier. Figure 35. Helical Rotary Slide Valve A more efficient method of controlling helical rotary compressors is to utilize a variable frequency drive to modulate compressor speed. A variable frequency drive, while more expensive than a slide valve, greatly increases compressor part load efficiency. In addition, as discussed earlier, the variable frequency drive can double as a soft starter for the compressor. Helical rotary machines, which utilize variable frequency drives, do not require a slide WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 18 of 25

19 valve. Eliminating the slide valve removes its associated inefficiencies and further decreases the number of moving parts by 50%. Application Considerations Single Versus Multiple Circuits Both helical rotary and centrifugal water chillers are available as single circuit machines or multiple circuit machines. Often, designers are lured by the appeal offered by multiple circuited machines. Multiple circuits offer redundancy. Each circuit contains its own compressor, expansion device and dedicated portions of the evaporator and condenser (figure 36). Figure 36. Multiple Circuits However, multiple circuited machines do not offer 100% redundancy. Multiple circuited machines share a single control system. Should the controls fail, the entire machine will fail. In addition, multiple circuited machines, which contain twice the number of moving parts, present double the potential for equipment failure. Equipment failure is directly related to the number of moving parts in a system. If we double the number of moving parts, we double the potential for failure. Finally, multiple circuited machines offer reduced part load efficiency. Consider a machine that operates with a single circuit compared to a machine that operates with dual circuits of the same capacity. A single circuited machine operating at 50% load utilizes 100% of its heat exchange surface area in the evaporator and condenser. A dual circuited machine, with one circuit off, operates at 50% load with 50% of its heat exchange surface area available for heat transfer. This decrease in heat transfer at lower loads equates to a significant drop in part load efficiency. If a designer requires redundancy, it is often better to design a plant with multiple chillers in lieu of a single chiller plant with multiple circuits. However, in applications where multiple machines exceed the design budget, multiple circuited machines may be a viable option. Variable Primary Flow Throughout the 21 st century, chillers were considered constant flow evaporator devices. However, the flow would always change slightly due to systems effects. These effects include the interaction of the pump with the system curve and variations of flow as chillers are enabled and disabled along with their associated pumps. Modern chilled water systems commonly employ variable flow through the evaporator. This further enables designers to achieve valuable pump energy savings and a somewhat simplified Hydronic design. WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 19 of 25

20 Figure 37. Variable Primary Chiller A variable primary chilled water system design often allows the designer to reduce the number of pumps required to operate the system (figure 38). Rather than utilizing dedicated primary and secondary pumps, a variable primary pumping system eliminates the need for secondary pumps. Figure 38. Variable Primary System In a variable primary system, the primary pumps are supplied with variable frequency drives. The secondary pumps are eliminated. As the system flow modulates with demand, the primary pumps modulate in order to satisfy the system demand. The flow through the chiller is allowed to modulate. As the system modulates below the minimum setpoint for the given chiller (generally around 30-40% of design flow), a two way valve located in a bypass pipe allows flow to bypass the system and satisfy the minimum flow required by the chillers. While variable primary pumping systems offer both energy savings and an opportunity for a simplified Hydronic design, several considerations must be taken into account when controlling the system. Those considerations are: Maintain minimum system flow (usually around 30-40% of design flow) Maintain maximum rate of change of flow (usually around 10% - 30% maximum change in flow per minute). Accurately control two way valve in bypass to maintain minimum chiller flow. WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 20 of 25

21 o Generally controlled with a flow sensor in return of production loop Condenser Water Temperature Control In virtually all design climates, chilled water plant energy savings can be realized by unloading the cooling tower as the ambient wet bulb temperature is depressed (for water cooled plants). The energy savings realized with condenser relief can be further amplified in drier climates. Furthermore, many chilled water systems are designed with plate and frame heat exchangers in order to provide a means of energy recovery at lower ambient wet bulbs. However, running a helical rotary or centrifugal chiller at lower condenser water temperatures can adversely affect the operation of the chiller. Virtually all helical rotary chillers and some centrifugal chillers rely on the pressure difference between the condenser and evaporator to transport oil. Without this pressure difference, the machine may be starved of much needed oil. In these instances, the system should be designed with some type of condenser head pressure control in order to maintain an adequate pressure differential within the machine. For water cooled systems with a cooling tower, three methods of condenser capacity control are recommended. The first method is to use a throttling valve at the condenser outlet. The throttling valve reduces the condenser water flow through the condenser (figure 39). The throttling method has the advantage of being simple and relatively inexpensive. In addition, the throttling method will save some pump energy. The system can be designed to either run on the pump curve or the pump can be controlled by a variable frequency drive. However, the throttling method has the potential to run into pump surge and may run below the tower minimum flow rate at low flows. Figure 39. Condenser Two Way Valve Control The second method of capacity control for water cooled systems is cooling tower bypass. Tower bypass mixes warm leaving condenser water with cool entering condenser water. Flow to the condenser is constant while flow to the cooling tower is variable (figure 40). The advantage to this system is that the flow through the condenser is constant. The disadvantage is that this system does not allow the system to start under low load conditions (such as coming out of plate and frame free cooling) and you may still run below the tower minimum flow. Figure 40. Condenser Three Way Mixing Valve WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 21 of 25

22 The third method of capacity control for water cooled system is chiller condenser bypass. Chiller condenser bypass varies the flow through the condenser by bypassing condenser water around the chiller condenser (figure 4`). The advantage to this system is that the pump and tower experience constant flow at all load conditions. The downside to this system is that we do not see any energy savings by unloading the pump. Figure 41. Condenser Three Way Diverting Valve In cold climates, either condenser throttling or condenser bypass are preferred. Both of these systems allow the chiller to start under low load, low ambient conditions or in the event of a system coming out of free cooling. Being that the condenser water flow is decreased with both methods; provisions need to be made to bypass the flow switch at low flow conditions. Often, a simple time delay switch may be used to prevent the chiller from disabling while attempting to start under cold condenser water conditions (i.e. coming out of plate & frame cooling). Heat Recovery Chillers Systems with simultaneous heating and cooling demands or that require domestic hot water can benefit from utilzing chillers with heat recovery. Heat recovery chillers utilze the heat energy produced by the condenser to produce warm/hot water. Two types of heat recovery chillers exist, those with Auxilary heat recovery condensers Heat pump chillers Auxilary heat recovery chillers utilize a second heat heat exchanger bundle (figure 42) in order create hot water. The auxiliary heat exchanger is preferentially loaded, receiving the hot gas directly discharged from the compressor, maximizing the hot water generation capability. After the hot, high pressure gas discharging the compressor generates hot water, the slightly cooler condenser refrigerant vapor is routed to the primary condenser. There is is condensed to a high pressure liquid and the refigeration cycle completes. Figure 42. Heat Recovery Chiller The chiller is controlled based on leaving chillled water temperature. The heat capacity generated from the auxiliary heat exchanger is not controlled. The heat generated to the auxiliary condenser is directly related to the chilled water capacity generated by the chiller. Auxilary heat recovery chillers are able to produce hot water in the rage of 95 o F to 115 o F. A heat pump chiller, like an auxilary heat recovery chiller, is capable of generating hot water. Unlike an auxilary heat recovery chiller, a heat pump chiller does not utilize a separate secondary heat exchagner in order to generate heat. WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 22 of 25

23 A heat pump chiller is optimized to generate high levels of compressor lift, utilzing its condenser bundle to produce heat. Heat pump chillers utilize 100% of the heat energy that would otherwise be rejected at the cooling tower, utilzing that heat to meet the building heating demand (figure 43). Heat pumnp chillers are able to produce hot water in the rage of 120 o F to 170 o F. However, the total lift generate by the compressor is generally limited to 65 o F to 100 o F. Thus, at higher hot water temperatures, the chilled water temperature produced by the chiller is limited. Figure 43. Heat Pump Chiller Heat pump chillers are controlled to maintain the hot water load. The chilled water capacity is not controlled. Being that the cooling load is the dependent variable, the chilled water capacity is directly related to the heating capacity required. Thus, a heat pump chiller is commonly one of multiple chillers in the plant. The heat pump chiller is base loaded. Any additional chilled water demand would be satisified by one or multiple dedicated cooling only chilers. If the heat pump chiller cannot maintain the heating load, a supplemental boiller may be installed to meet any additional heating demand. In order to determine the overall efficiency benefit of a heat pump chiller compared to a conventional chiller plus boiler plant, figure 44 depicts the efficiencies that could realistically be expected operating a heat pump chiller. Figure 44. Heat Pump System Example The conversion of COP to chiller kw/ton is: kw/ton = 3.516/COP WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 23 of 25

24 If a chiller has an efficiency of 1.0 kw/ton, the COP would be 3.5. Thus, assuming chiller with an efficiency in heat pump mode of 1.2 kw/ton, the cooling COP is 2.9. That equates to.35 units of input work to 1 unit of output cooling. A typical R-134 heat pump chiller can produce 150 o F to 180 o F hot water. In this example, assume 150 o F hot water and 44 o F chilled water with a cooling COP of 2.9 (1.2 kw/ton) and a heating COP of 3.8. For the purposes this example, this is a very conservative figure. Most modern R-134a heat pump chillers can operate at an efficiency greater than 1.2 kw/ton. Recall that COP is a unitless value relating output capacity to input work. The heat pump chiller will generate about 25-45% more to account for the heat of compression. In this example, we will assume the heat of compression is accounts for 35% of the heat generated by the chiller. That is to say for every 1.35 units of heating energy produced, the chiller will produce 1 unit of cooling energy. This give us a heating COP of 3.8. This results in a combined COP of the plant of 6.7 ( ). A similar chiller plus boiler system may incorporate a chiller with a COP of 6.1 (0.57 kw/ton where k/w/ton = 3.516/COP) and a boiler operating at similar conditions at a.85 COP (85% efficient condensing boiler). The overall COP for this plant would be: Comparing the two systems (figure 45): Figure 45. Heat Pump COP System Efficiency the heat pump system uses 5 times less energy than the chiller plus boiler system (6.7 COP / 1.48 COP). Upon further anlysis of the two systems, it becomes readily apparent why heat pump systems can offer designers an opportunity to attain tremendous energy savings. In order to realize the energy savings potential afforded by a heat pump chiller, the system must have simultaneous heating and cooling loads. For example, larger buildings with a higher percentage of interior zones would generally create simultaneous loads. The ASHRAE 2008 Handbook reads: WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 24 of 25

25 Another common example of such a system would be a variable air volume operating during the warmer spring, summer and fall months. VAV systems are typically designed with some type of reheat at the air terminal units. These reheat terminal require some form of heat energy, even during the warmest months of the year. Figure 46. VAV Reheat The ratio of heat energy to cooling energy produced by a heat pump chiller is typically very close to 1.35 to 1. The difference in heating energy to cooling energy is a product of the heat produced by the refrigeration cycle (heat of compression). However, rarley will the building load profile follow the ratio of heating to cooling energy produced by the chiller. Thus, heat pump chillers are generally run in conjunction with supplemental boilers and chillers. WN Mechanical Systems Helical Rotary & Centrifugal Chillers Page 25 of 25

APS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017

APS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017 APS Chiller Seminar Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017 Agenda for today Refrigeration Cycle Chiller Types and Refrigerants Compressor Styles Chilled Water Pumping Systems

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7

More information

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Air Conditioning Clinic Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Absorption Water Chillers One of the Equipment Series A publication of The Trane Company Worldwide Applied Systems

More information

CVGF. Water Cooled Centrifugal Chillers

CVGF. Water Cooled Centrifugal Chillers CVGF Water Cooled Centrifugal Chillers January 2010 CVGF Key Features 2 stage centrifugal compressor Semi-hermetic compressor R134a refrigerant Falling film evaporator Economizer cycle NEW Tracer Adaptiview

More information

Midea VFD Centrifugal Chiller Technology

Midea VFD Centrifugal Chiller Technology Midea VFD Centrifugal Chiller Technology Content Why VFD VFD centrifugal chiller technology Solution 2 HVAC major issues Energy conservation Global warming reduction 3 Why VFD No Compressor A/C Lower GWP

More information

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components: Pumps DOE-HDBK-1018/1-93 CENTRIFUGAL PUMPS CENTRIFUGAL PUMPS Centrifugal pumps are the most common type of pumps found in DOE facilities. Centrifugal pumps enjoy widespread application partly due to their

More information

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT Central Chiller Plant (with Cooling Tower and Chilled Water distribution) The other AC configuration is called a Chilled Water or Larger Cooler system. It

More information

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South 3/5/2018 1 Update Dedicated Heat Recovery Chiller Technology Don Frye Gulf South Good design is an intentional act Begin with the end in mind Basic Bldg Tenants IAQ (low VOC & CO 2 ) Controlled Temp &

More information

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING Sample Questions and Answers CHAPTER 5 EVAPORATORS 1. What is Evaporator? Classify the various types of evaporator. Evaporator

More information

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

Refrigeration Systems and Accessories

Refrigeration Systems and Accessories As with the Chapter Review Tests and the Final Exam, the tests your understanding of the materials underlying the learning objectives. After you ve reviewed your answers to the Chapter Review Tests, try

More information

Magnetic Bearing Technology: Achievements in Higher Efficiency

Magnetic Bearing Technology: Achievements in Higher Efficiency Magnetic Bearing Technology: Achievements in Higher Efficiency Magnetic Bearing Compressor 100% Oil Freeeliminates oil system maintenance costs. R134a Refrigerantmeets Montreal protocol and is not subject

More information

How to Cut Chiller Energy Costs by 30%

How to Cut Chiller Energy Costs by 30% How to Cut Chiller Energy Costs by 30% Pre-packaged retrofit cuts centrifugal compressor chiller energy costs by 30% while reducing required maintenance and extending operating life at Duke Realty Corporation

More information

2. CURRICULUM. Sl. No.

2. CURRICULUM. Sl. No. . CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years. TURBOCOR COMPRESOR CHILLERS General Description Microprocessor controlled, water chiller using HFC 134a refrigerant, two stage centrifugal oil free variable speed compressor's and electronic expansion

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012 SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

terminal units only provide sensible cooling, a separate dehumidification system is usually needed. providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can

More information

Alfa Laval Wet Surface Air Coolers (WSAC ) FAQs

Alfa Laval Wet Surface Air Coolers (WSAC ) FAQs Alfa Laval Wet Surface Air Coolers (WSAC ) FAQs Q: How is the WSAC a closed-loop cooling system? A: The WSAC is a closed-loop cooling system because the process loop being cooled is inside the tube bundles

More information

PREVIEW COPY. Compressors. Table of Contents. Introduction to Compressors...3. Lesson Two Reciprocating Compressors...21

PREVIEW COPY. Compressors. Table of Contents. Introduction to Compressors...3. Lesson Two Reciprocating Compressors...21 Compressors Table of Contents Lesson One Introduction to Compressors...3 Lesson Two Reciprocating Compressors...21 Lesson Three Rotary, Helical, and Scroll Compressors...37 Lesson Four Centrifugal Compressors...51

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a Air-Cooled Variable Speed Drive Screw Chillers Super Efficient Super Quiet Cooling Capacity Range 540-1405 kw R134a World s first low sound Air-Cooled variable speed drive screw chiller The recognition

More information

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation Form 30-217 / January 2007 Heat Reclaim Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation While the vapor-compression cycle has

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS David Grassl PE Mechanical Engineer Principal Similar to traditional boiler systems, condensing boiler systems have many designs they can operate

More information

Daikin Blueprint: Delivering Hot Water with a Chiller

Daikin Blueprint: Delivering Hot Water with a Chiller Daikin Blueprint: Delivering Hot Water with a Chiller Analyzing the design of heat recovery on air-cooled chillers and the effect it has on building energy consumption By Paul Crisman Daikin Chiller Applications

More information

Fans and Pumps I. Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong

Fans and Pumps I. Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong MEBS6008 Environmental Services II http://www.mech.hku.hk/bse/mebs6008/ Fans and Pumps I Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail: cmhui@hku.hk Sep 2012

More information

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE T he advent of the small scroll or screw chiller, capable of producing condenser water as high as 140

More information

College of Technological Studies Department of Power & Refrigeration Technology. Course Contents

College of Technological Studies Department of Power & Refrigeration Technology. Course Contents College of Technological Studies Department of Power & Refrigeration Technology Course Contents Course Designation: Air Conditioning Control systems Course No. : 272 0463 Credit Hrs.: 3 Lecture Hrs.: 2

More information

MLC Air Cooled Chillers MLC-FC Free Cooling Chillers MLC-AD Adiabatic Chillers

MLC Air Cooled Chillers MLC-FC Free Cooling Chillers MLC-AD Adiabatic Chillers MLC Air Cooled Chillers MLC-FC Free Cooling Chillers MLC-AD Adiabatic Chillers 60-500 Tons n Mission Critical Cooling n Central Plant Process Cooling n Specialized HVAC Cooling Systems COOLING SOLUTIONS

More information

Innovation for a Better & Greener Future

Innovation for a Better & Greener Future Innovation for a Better & Greener Future Comprehensive range of Water Cooled Variable Speed Centrifugal Chillers with Magnetic Bearing Compressors Kirloskar Chillers, a future-focused organisation, has

More information

A Treatise on Liquid Subcooling

A Treatise on Liquid Subcooling A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance

More information

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Water-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Water-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.

More information

Rotodynamic Pumps INTRODUCTION:

Rotodynamic Pumps INTRODUCTION: Rotodynamic Pumps INTRODUCTION: Liquids have to be moved from one location to another and one level to another in domestic, agricultural and industrial spheres. The liquid is more often water in the domestic

More information

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012 HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager INTRODUCTION The science of creating vacuum is often misunderstood and when the desired vacuum condition is not being achieved in a manufacturing setting this usually means production comes to a halt and

More information

Chiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off

Chiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off Application Guide AG 31-003-1 Chiller Plant Design 51.5F Return Water To Chiller Two 400 Ton Chillers Each At 300 Tons (Balanced Load) 51.5F 480 gpm Flow Through Decoupler 44F 54F Building Load 600 Tons

More information

Method to test HVAC equipment at part load conditions

Method to test HVAC equipment at part load conditions IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking

More information

THERMAL ICE STORAGE: Application & Design Guide

THERMAL ICE STORAGE: Application & Design Guide THERMAL ICE STORAGE: Application & Design Guide Table of Contents: 1. Introduction A. History of Thermal Energy Storage B. Operating and Cost Benefits 2. Applications A Fundamental System B. HVAC Cooling

More information

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer Technical Development Program PRESENTED BY: COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems Ray Chow Sales Engineer TDP Updates Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Ice Storage Systems One of the Systems Series August 2012 TRG-TRC019-EN Ice Storage Systems One of the Systems Series A publication of Trane Preface Ice Storage Systems A Trane

More information

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost LL Chillers and Outdoor Mechanical Rooms Air-Cooled Features: Air-cooled condenser chillers with capacities from 35-345 tons Evaporative-cooled condenser chillers with capacities from 35-540 tons Variable

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information

TECHNICAL BULLETIN SELECTING A COMPRESSED AIR DRYER INTRODUCTION

TECHNICAL BULLETIN SELECTING A COMPRESSED AIR DRYER INTRODUCTION TECHNICAL BULLETIN SELECTING A COMPRESSED AIR DRYER INTRODUCTION Having an understanding of why water forms in your compressed air piping system will help you in evaluating the type of air drying system

More information

Midwest Industrial Initiative Webinar: Industrial Refrigeration

Midwest Industrial Initiative Webinar: Industrial Refrigeration Midwest Industrial Initiative Webinar: Industrial Refrigeration Opportunities for Energy Efficiency and Cost Savings Thursday, June 6, 2013 www.kw-engineering.com Bryan Hackett, PE kw Engineering What

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Air-Cooling Evaporators

Air-Cooling Evaporators Air-Cooling Evaporators Types of construction Circuit Configurations Methods of Refrigerant Feed Methods of Air Circulation Methods of Defrost Type of Construction Bare tube Finned Tube Plate-surface Bare

More information

KE2 EvaporatorEfficiency Theory of Operation

KE2 EvaporatorEfficiency Theory of Operation Theory T.1.1 June 011 TM thermsolutions ENTER BACK KE Therm Solutions, Advanced Energy Saving Technology for Commercial Refrigeration and AC Systems Page Table of Contents Basic Refrigeration System Evaporator

More information

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features: RZ PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS Features: Air-cooled condenser, water-cooled condenser, or evaporative-cooled condenser packaged rooftop units from 55-240 tons Water-source

More information

CTI Sponsored Educational Program

CTI Sponsored Educational Program Presented By: Kent Martens SPX Cooling Technologies, Inc. Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for

More information

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs Lesson 1 - Basic Heat Pump Theory (Part 1) Describe the basic operation of a heat pump. Explain the function of various heat pump controls. Interpret the wiring diagrams and performance data provided by

More information

Evaporative Condenser Engineering Manual

Evaporative Condenser Engineering Manual TECHNICAL RESOURCES Evaporative Condenser Engineering Manual Introduction The objective of a mechanical refrigeration system is to remove heat from a space or product, and to reject that heat to the environment

More information

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated.

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated. NOMENCLATURE INTRODUCTION The HTT HWDX water-cooled chillers range is the latest addition to HTT s growing family of commercial products, featuring the most current technologies advances. The HWDX main

More information

MECHANICAL SCIENCE Module 2 Heat Exchangers

MECHANICAL SCIENCE Module 2 Heat Exchangers Department of Energy Fundamentals Handbook MECHANICAL SCIENCE Module 2 Heat Exchangers Heat Exchangers DOE-HDBK-1018/1-93 TABLE OF CONTENTS TABLE OF CONTENTS LIST OF FIGURES... ii LIST OF TABLES... iii

More information

Presented By: John Dolan, P.E.

Presented By: John Dolan, P.E. Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience jdolan@thermohvac.com

More information

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During

More information

Heat Recovery Units. Heat Recovery 1

Heat Recovery Units. Heat Recovery 1 Heat Recovery Units Heat Recovery 1 Heat Recovery Unit Why? A heat recovery unit (HRU) can help make mechanical ventilation more cost effective by reclaiming energy from exhaust airflows. HRUs use air-to-air

More information

Bulletin , March Electric Hot Gas Bypass Valves

Bulletin , March Electric Hot Gas Bypass Valves Bulletin 100-60, March 2018 Electric Hot Gas Bypass Valves PAGE 2 / Bulletin 100-60 10 FEATURES AND BENEFITS SDR-4 Direct temperature control Tight shutoff when closed Can be interfaced with direct digital

More information

Form No: USS0408A-60Hz tons Air Cooled Rotary. 203 through 522 Tons. 60Hz. Products That Perform...By People Who Care

Form No: USS0408A-60Hz tons Air Cooled Rotary. 203 through 522 Tons. 60Hz. Products That Perform...By People Who Care Form No: USS0408A-60Hz - 203-522 tons Air Cooled Rotary Screw Flooded Chillers 203 through 522 Tons 60Hz R Products That Perform...By People Who Care TABLE OF CONTENT Introduction... 2 Nomenclature...

More information

Copy Right By: Thomas T.S. Wan

Copy Right By: Thomas T.S. Wan Chapter 23 Motor and Starter Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Electric Motors All the motors are to be designed and constructed in accordance with NEMA code. Electric

More information

Use this Construction/HVAC Glossary to answer the questions below.

Use this Construction/HVAC Glossary to answer the questions below. www.garyklinka.com Page 1 of 21 Instructions: 1. Print these pages. 2. Circle the correct answers and transfer to the answer sheet on the second last page. 3. Page down to the last page for the verification

More information

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance Jong Min Choi, W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building

More information

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs Abstract Fan and coil evaporators as used in the industrial refrigeration industry can be certified for performance per ANSI/AHRI Standard 420-2008, Performance Rating of Forced-Circulation Free-Delivery

More information

Multiple-Chiller-System Design and Control

Multiple-Chiller-System Design and Control Applications Engineering Manual Multiple-Chiller-System Design and Control SYS-APM001-EN (March 2001) Multiple-Chiller-System Design and Control Mick Schwedler, applications engineer Ann Yates, information

More information

Refrigeration Systems

Refrigeration Systems Refrigeration Systems COP COP = coefficient of performance Air conditioners, refrigerators: COP=QL/Wnet Heat pumps: COP=QH/Wnet Energy balance: Wnet+QL=QH From Cengel, Thermodynamics: An Engineering Approach,

More information

System Design, Commissioning, Operation

System Design, Commissioning, Operation PART 3: CO 2 as a Refrigerant System Design, Commissioning, Operation Service This series continues with the introduction of transcritical, cascade and secondary systems; how each system works; and compares

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

Torad Rotary Spool Compressor

Torad Rotary Spool Compressor Torad Rotary Spool Compressor Communication White Paper By: Torad Engineering, LLC Cumming, Georgia USA Torad Rotary Spool Compressor Introduction: The rotary spool compressor shares various attributes

More information

Chapter 9. Refrigeration and Liquefaction

Chapter 9. Refrigeration and Liquefaction Chapter 9 Refrigeration and Liquefaction Refrigeration is best known for its use in the air conditioning of buildings and in the treatment, transportation, and preservation of foods and beverages. It also

More information

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system

More information

energydesignresources

energydesignresources energydesignresources design brief Energy building Efficiency design Practices in Industrial Refrigeration Summary Energy costs are a significant expense for facilities that operate industrial refrigeration

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional

More information

Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans

Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans Varofoil Controllable Pitch in Motion Fans Compared to Variable Frequency Controlled Fans A look at two accepted technologies.. System Characteristics In general, the pressure developed by a fan is a function

More information

Agenda and Objectives

Agenda and Objectives Agenda and Objectives Trane Engineers Newsletter Live Series Variable-Speed Drives (VSDs) and Their Effect On HVAC System Components Variable-speed drives (VSDs) can save energy, but the savings may not

More information

How about Savings in Time, Money, Energy and Longer Life?

How about Savings in Time, Money, Energy and Longer Life? Chapter 17: The Value of Maintaining Evaporative Cooling Equipment 97 The Value 17 of Maintaining Evaporative Cooling Equipment 1. Cooling Tower Maintenance and Upgrades... What s in it for You? How about

More information

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad- 500 043 B.Tech (III II SEM) MECHANICAL ENGINEERING REFRIGERATION AND AIR CONDITIONING Prepared by, Dr. CH V K N S N Moorthy, Professor

More information

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd Abstract This paper presents the design approach adopted for the expansion of a large existing

More information

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters Energy Efficiency Through Waste Heat Recovery Heat Recovery Centrifugal Chillers and Templifier Water Heaters Innovative Solutions for Saving Energy McQuay offers two innovative methods of saving energy

More information

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES November 2006 / BULLETIN -60 ELECTRIC DISCHARGE BYPASS VALVES PAGE 2 / Bulletin -60 10 FEATURES AND BENEFITS Direct temperature control Tight shutoff when closed Can be interfaced with direct digital controls

More information

Appendix A. Glossary of Common Terms

Appendix A. Glossary of Common Terms Glossary of Common Terms Glossary of Common Terms Absorption chiller A refrigeration machine using heat as the power input to generate chilled water. Adjustable speed drive A means of changing the speed

More information

GENERAL TABLE OF CONTENTS NOMENCLATURE DCLC D V

GENERAL TABLE OF CONTENTS NOMENCLATURE DCLC D V GENERAL From the beginning of 20 th Century, DB has been providing innovative solutions for the heating, air conditioning and refrigeration needs of its customers. Today s global company has a proud heritage

More information

1. Know your process. The following guidelines will help you navigate what can be a challenging and time consuming task.

1. Know your process. The following guidelines will help you navigate what can be a challenging and time consuming task. Many processes today require an indirect method of heating, which implies the use of a heat transfer medium, instead of circulating the process directly into a heater. Thermal oil, water, glycol mixtures,

More information

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things

More information

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview As in residential buildings the purpose of mechanical conditioning and ventilation is to maintain air quality and thermal comfort in buildings, with

More information

Smardt Oil-Free Chillers

Smardt Oil-Free Chillers Smardt Oil-Free Chillers Company History in Brief Turbocor compressor invented in Australia in 1993 Turbocor was relocated to Montreal in 1999 Danfoss forms 50/50 partnership in 2004 Smardt was founded

More information

Partial Load Performance Of Refrigeration System

Partial Load Performance Of Refrigeration System Chapter 11 Partial Load Performance Of Refrigeration System Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Hot Gas Bypass & Liquid Injection: When the compressor is under surge condition,

More information

Heat pump and energy recovery systems

Heat pump and energy recovery systems SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

$42,000. Danfoss Turbocor Compressors Give INTERTECH PLASTICS A RESHORING ADVANTAGE. saved annually

$42,000. Danfoss Turbocor Compressors Give INTERTECH PLASTICS A RESHORING ADVANTAGE. saved annually CASE STUDY TWO $42,000 saved annually Intertech s new variable speed cooling system is precise, reliable, and efficient slashing cooling costs by approximately $42,000 annually. Danfoss Turbocor Compressors

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features: RL Packaged Rooftop Units, heat pumps and Outdoor air handling Units Features: Air-cooled condenser, water-cooled condenser, or patented AAON evaporative-cooled condenser, with capacities from 45-240 tons

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic VAV Systems One of the Systems Series July 2012 TRG-TRC014-EN VAV Systems One of the Systems Series A publication of Trane Preface VAV Systems A Trane Air Conditioning Clinic Figure

More information

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 SAE Alternate Refrigerant Cooperative Research Program Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 To: Alternate Refrigerant Task Force Members From: Ward Atkinson

More information

Leadership, Innovation, Advanced Technology Synergise Here!

Leadership, Innovation, Advanced Technology Synergise Here! Cooling Synergies Leadership, Innovation, Advanced Technology Synergise Here! 125 years of Engineering Innovation Kirloskar Chillers is proud to be a part of 125 years old Kirloskar Group. The diversified

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information