Experiment 7: Temperature Control of Heat Exchanger ( TBC 4/4/2009 )

Size: px
Start display at page:

Download "Experiment 7: Temperature Control of Heat Exchanger ( TBC 4/4/2009 )"

Transcription

1 Experiment 7: Temperature Control of Heat Exchanger ( TBC 4/4/2009 ) Objective: To implement a feedback temperature control of the hot water exiting a doublepipe heat exchanger. I. Introduction: Feedback Control Configuration The control configuration is similar to the configuration given in experiment 6. The signal is a voltage ranging from 0 to 5 volts. The actuator block includes both the voltage to pressure (E/P) transducer, compressed air supply and the steam control valve. The signal represents the amount of steam entering the heat exchanger. The signal is the temperature measured using an RTD sensor, while is the setpoint temperature. Figure 1. Feedback loop. For this experiment, we will implement a simple proportional-integral control law: PI Control: 1 (1) Because of the possibility of saturation in the control valves, integral windup need to be addressed if PI control were to be used, i.e. the integral term of the PI controller continues to unnecessarily grow during saturation. Strategies that try to solve the integral windup problem are known collectively as anti-reset windup approaches. Thus, instead of (1), we could implement an additional logic that shuts off the integral windup during saturation conditions such as: (2) (3) 0 if 0 or 1 otherwise (4) 1

2 II. Procedure/ Tasks: A. Build the data-aquistion/control setup (Figure 1) Figure 1. Control Setup. B. Create the RTD sub-vi ( refer to lab 6, modify to accept 5V from USB ) C. Create the Saturation Check sub-vi ( Figure 2. ). The Greater than or Equal block and the Or block can be found in the Functions pallete, [Programming] [Comparison] menu. Figure 2. Saturation Check sub-vi. D. Create the PI Controller sub-vi (See Figure 3). The Subtraction and Division block can be found in [Programming] [Numeric] menu. The Select block can be found in [Programming] [Comparison] menu. The Integral block can be found in [Mathematics] [Integ & Diff] menu, then select Time Domain Math. A properties window should pop-up, then select [Integral] and [Continuous] buttons then click [OK]. 2

3 Figure 3. PI Control Block. E. Create the Actuator sub-vi by renaming the Dimmer subvi of lab 6 and setting the minimum voltage to 0 volts and maximum to 5 volts. F. Combine the parts and create the Control System VI (see Figure 4). Note that the Feedback Node block will appear automatically after connect the Saturation Check subvi to the PI Controller subvi. Also, for the Write block, choose the [no header] and [one column only] buttons. Figure 4. Control System VI. 3

4 Figure 5. The Front Panel for Control System VI. G. Startup the heat exchanger system (See Appendix A) and select 20% mark on the rotameter. H. Connect the transducer to the controller unit and begin tests below. (For the items below, use the setpoint of 40.) I. Perform a step test and obtain an FOPTD model. (See Appendix C) J. Use the Cohen-Coon tuning rules and apply them to the system. Note your observations. K. Shut down the heat exchanger system (See Appendix B). 4

5 III. Observation: Cohen-Coon Tuning Method: 1. FOPTD model found: 2. Cohen Coon Tuning: Calculations: Kc : : 3. Response observation: Temperature Response: Control Signal Response: 5

6 Appendix A. Heat Exchanger Startup ( based on procedure for heat transfer coefficient experiment found in CM3215 developed by F. Morrison, revised for CM3310 by T. Co) Experimental Procedure CAUTION: Always wear insulated gloves when adjusting the steam valve, when touching uninsulated piping or when handling condensate. The equipment may be hot at the beginning of lab. If the TA has not done it yet, connect the transducer to the compressed air supply and to the steam valve. (see Figure A1.) + E/P Transducer - Figure A1. Connecting the transducer to the air supply and steam valve. Begin water flow in the loop as follows: 1. Start water flow through the ½ pipe as follows. Make sure that tank T-02 is empty and clean. Close the drain valve (DV-2). 2. Open water valve WV-10 and fill T-02 with water. Once the tank is filled, the water control float valve will shut-off water flow. The water control float valve keeps water level constant at a set point. 3. Make sure valves WV-1, WV-2, and WV-3 as well as the needle valve WV-5 are all closed. Turn on pump P Direct the water through the ½ pipe by opening valve WV-1. Turn three-way valve WV-4 knob to direct the water flow through rotameter FI-01. Make sure that valves WV- 6 and WV-7 are closed. Adjust three-way valve WV-8 to direct water to the heat exchanger E-01. Turn three-way valve WV-9 knob to direct water to T Fix the water flow rate to 20% on FI-01 by using needle valve WV-5. Begin flow of steam through the outer jacket of the heat exchanger as follows: 6. Position three-way valve SV-3 to direct flow through the Swagelok steam trap. 7. Open the main steam valve SV-1. Drain condensate from the line as follows: 6

7 8. Check with the TA to see if this step has been done; if not, using insulated gloves, position the black rubber drain hose located downstream of SV-2 in a Styrofoam bucket. One team member should stabilize the bucket and hose. 9. Using insulated gloves, open SV-2 slowly to drain all of the line condensate into the bucket. Close SV-2 when steam begins to come out of the hose. Dispose of the condensate in a floor drain do not use the sink drain. Clean up any water spills with paper towels. 10. Return the rubber hose to common drain. Start steam flow 11. Open DV-1. Turn three-way valve WV-9 knob to direct water to T-01. Verify that the pump is on and that water is circulating through the inside of the heat exchanger. Do not recirculate water back to tank T Open main air valve AV-1 and set the control valve FV-06 to 18 psig. Appendix B. Heat Exchanger ShutdownProcedure ( based on procedure for heat transfer coefficient experiment found in CM3215 developed by F. Morrison, revised for CM3310 by T. Co) 1. Set the air pressure regulator to 0 psig using the pressure regulator. 2. Close the main air valve AV Close main steam valve SV Return all drain hoses to the common drain. 5. Allow the cold water to circulate through the loop to cool the heat exchanger for at least 3 minutes. Stop when the piping at the cold-water exit of the heat exchanger is cool to the touch. 6. Close valves WV-1 and needle valve WV Turn off pump P Close main water valve WV Position three-way valve WV-9 to direct flow to Tank T Drain all tanks. 11. Dry off any wet surfaces with paper towels. Turn off all the electronic devices and properly store them. 12. (If you are in the last session of the day, detach the transducer from the compressed air line and the steam valve then reconnect air line directly to steam valve). 7

8 Appendix C. Obtaining an Empirical FOPTD Model 1. If it is not yet implemented in the Control System VI, include a [Write Meas File] block (which can found in [Express] [Output] menu. 2. Make sure that the temperature is initially at steady state. 3. Introduce a step change in controller output, then collect the data up to the point where the temperature settles to a new steady state. ( One simple way to manually introduce step change is to set 0 and then use to input a value between 0 and 1.) The FOPTD model has the solution given by the following: if (5) exp if 4. You can use Excel solver to find the model (see Figure C1) by minimizing RMS through changing of tdelay, tau, T_init and T_final. Note: you can find t0 from the point where had a step change. =SQRT(AVERAGE(F8:F2008)) =IF=(E8-C8)^2 =IF( B9<$B$1+$B$2, $B$4, $B$5 - ($B$5-$B$4)* EXP( -(B9-$B$1-$B$2) /$B$3) ) Figure C1. Spreadsheet for obtaining FOPTD. Note: process gain can be found as (6) 8

Experiment 4: Temperature Control of Heat Exchanger ( TBC 1/21/2012, 2/11/2017 )

Experiment 4: Temperature Control of Heat Exchanger ( TBC 1/21/2012, 2/11/2017 ) Experiment 4: Temperature Control of Heat Exchanger ( TBC 1/21/2012, 2/11/2017 ) Main Task: To implement a feedback temperature control of the hot water exiting a heat exchanger. I. Feedback Control Setup

More information

Overall Heat Transfer Coefficient for Double-Pipe Heat Exchanger

Overall Heat Transfer Coefficient for Double-Pipe Heat Exchanger Overall Heat Transfer Coefficient for Double-Pipe Heat Exchanger Pre-laboratory Assignment Review the following: concept of the double-pipe heat exchanger, the overall heat transfer coefficient, logarithmic

More information

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink 1 Asoka R.G, 2 Aishwarya N, 3 Rajasekar S and 4 Meyyappan N 1234 Department of Chemical Engineering Sri Venkateswara College of Engineering,

More information

2017 products.koer.com Page 1 of 14

2017 products.koer.com Page 1 of 14 VAV Parameters 2017 products.koer.com Page 1 of 14 INTRODUCTION Learn how to setup various VAV parameters and configurations, PID calculation elements, EC motor voltages, wall type etc. 2017 products.koer.com

More information

PumpLab TM Operator s Manual

PumpLab TM Operator s Manual PumpLab TM Operator s Manual PumpLab TM Centrifugal Flow/ Process Control System i PumpLab TM Main Features Clear View Flow Circuit Outlet Valve Data Display/Record Flow Meter Exit Pressure Sensor Computer

More information

Operating Instructions

Operating Instructions Operating Instructions 1. Preparation of Organic Feed. 1. To avoid flooding the columns during start-up, check that the main valves for water (VS1) and organic phase feed (VF2) on the 1 st floor are closed

More information

Exercise 8. Controlling a Batch Mixing Process EXERCISE OBJECTIVE

Exercise 8. Controlling a Batch Mixing Process EXERCISE OBJECTIVE Exercise 8 Controlling a Batch Mixing Process EXERCISE OBJECTIVE To create a ladder program for controlling a batch mixing process. To test program operation through the completion of verification steps.

More information

Experimental Procedure

Experimental Procedure 1 of 7 9/13/2018, 10:38 AM https://www.sciencebuddies.org/science-fair-projects/project-ideas/enveng_p036/environmental-engineering/can-nanotechnology-help-clean-up-ocean-oilspills (http://www.sciencebuddies.org/science-fair-projects/project-ideas/enveng_p036/environmental-engineering/can-nanotechnology-help-clean-up-ocean-oil-spills)

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems

Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems Lab 1b Cooling Tower Performance and Sensors for Thermal-Fluid Systems OBJECTIVES Warning: though the experiment has educational objectives (to learn about boiling heat transfer, etc.), these should not

More information

Temperature Control of Heat Exchanger Using Fuzzy Logic Controller

Temperature Control of Heat Exchanger Using Fuzzy Logic Controller Vo1ume 1, No. 04, December 2014 999 Temperature Control of Heat Exchanger Using Fuzzy Logic Controller Aravind R. Varma and Dr.V.O. Rejini Abstract--- Fuzzy logic controllers are useful in chemical processes

More information

Chapter 2.3: Steam System

Chapter 2.3: Steam System Part I: Objective type Questions and Answers Chapter 2.3: Steam System 1. For industrial process heating, the best quality of steam is: a) dry saturated steam b) superheated steam c) wet steam d) high

More information

Alarms Updated 03/26/2018

Alarms Updated 03/26/2018 Updated 03/26/2018 Table of Contents Alarms Alarms in OneView...1 Types of Alarms...1 Setting up Alarms...2 Alarm Configuration...4 Customize Alarm Parameters...5 List of Configured Alarms...7 Acknowledging

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Session 2633 Development of a Psychrometric Test Chamber Michael J. Swedish Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Acknowledgments The design of the Psychrometric

More information

Dacor Technical Service

Dacor Technical Service Attention: This manual is just a section from the complete Wall Oven Service Manual. If you find that you require the complete service manual, which includes exploded views and parts, use and care information

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

In order to be useful, many substances must be available in pure form.

In order to be useful, many substances must be available in pure form. DISTILLATION COLUMN INTRODUCTION In order to be useful, many substances must be available in pure form. In the real world substances are seldom found or produced pure, they are frequently found mixed together

More information

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application 2273 Application Note 140-1045 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

IJ3000 IJ3000 Flushing System N Revision B Installation Instructions Page 1 of 10

IJ3000 IJ3000 Flushing System N Revision B Installation Instructions Page 1 of 10 IJ3000 IJ3000 Flushing System 5760-029N Revision B Installation Instructions Page 1 of 10!! WARNING: Do not turn on until all plumbing and electrical connections have been made. WARNING: The flushing system

More information

QuadraTouch Pro Software Manual Dryer Control System

QuadraTouch Pro Software Manual Dryer Control System QuadraTouch Pro Software Manual Dryer Control System Software is constantly changing. Make sure you are up to date with Sukup s newest software. New software and manuals are available for download at:

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

Jet Compressors. Circulate Steam Boost Low-Pressure Steam Compress and Mix Gases in Desired Proportion

Jet Compressors. Circulate Steam Boost Low-Pressure Steam Compress and Mix Gases in Desired Proportion s Circulate Steam Boost Low- Steam Compress and Mix Gases in Desired Proportion S&K s are used in the process, paper, petroleum, power, gas, and other industries to circulate steam, boost low-pressure

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

Removal of Non-condensable Gases and Air Is Critical In A Steam System

Removal of Non-condensable Gases and Air Is Critical In A Steam System Removal of Non-condensable Gases and Air Is Critical In A Steam System Air and non-condensable gases are one of the major problems in a steam system. Both can cause production problems for a steam system

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL HYDROFILL Hydronic water treatment filling units Copyright 2016 Caleffi OPERATING AND MAINTENANCE MANUAL NA10439 www.caleffi.com NA5709 series Function HYDROFILL is a water treatment fi lling unit that

More information

Circuit SolverTM THERMOSTATIC RECIRCULATION VALVE FOR DOMESTIC HOT WATER SYSTEMS.

Circuit SolverTM THERMOSTATIC RECIRCULATION VALVE FOR DOMESTIC HOT WATER SYSTEMS. www.circuitsolver.com The Problem 1 Water flows to the path of least resistance. The Solution Install a Circuit Solver on each hot water supply branch line immediately downstream of the last runout to

More information

OPERATING MANUAL TORREY PINES SCIENTIFIC, INC. DIGITAL HPLC COLUMN HEATER MODEL CO20 DOCUMENT NUMBER CO20-00

OPERATING MANUAL TORREY PINES SCIENTIFIC, INC. DIGITAL HPLC COLUMN HEATER MODEL CO20 DOCUMENT NUMBER CO20-00 OPERATING MANUAL TORREY PINES SCIENTIFIC, INC. DIGITAL HPLC COLUMN HEATER MODEL CO20 DOCUMENT NUMBER CO20-00 Torrey Pines Scientific, Inc 2713 Loker Ave. West Carlsbad, CA 92010 Phone: 760-930-9400 Fax:

More information

OPERATIONAL PROCEDURES

OPERATIONAL PROCEDURES Mobile Nephelometer for Ambient PM 2.5 Monitoring OPERATIONAL PROCEDURES For use with the M903 Radiance Research Nephelometer and Garmin GPSMAP 60Cx Prepared by: Karla Poplawski, Eleanor Setton and Steeve

More information

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application 2023 Application Note 140-1052 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 6 Hardware Outputs...

More information

Helicoil and Shell-Tube Heat Exchanger. Abdullah AlThomairi, Ahmed Sajjad, and Faris AlShuaibi. October 25, 2014

Helicoil and Shell-Tube Heat Exchanger. Abdullah AlThomairi, Ahmed Sajjad, and Faris AlShuaibi. October 25, 2014 Helicoil and Shell-Tube Heat Exchanger Abdullah AlThomairi, Ahmed Sajjad, and Faris AlShuaibi October 25, 2014 Submitted to: NORTHEASTERN UNIVERSITY Department of Chemical Engineering CHME 3313 Transport

More information

Installation Instructions & Operating Manual

Installation Instructions & Operating Manual GUARANTEE Your Elecro heater is guaranteed for one year from the date of purchase against faulty workmanship and materials. ELECRO ENGINEERING LTD will replace or repair, at it s discretion, any faulty

More information

Safety Precautions As Related To Operating Slurry Slakers

Safety Precautions As Related To Operating Slurry Slakers Safety Precautions As Related To Operating Slurry Slakers By: Mohamad Hassibi Chemco Systems, L.P. 5-01-2007 Revision 1-2008 Slurry slakers produce very high quality lime slurry, however, if not operated

More information

OPERATING & SERVICE PARTS MANUAL 700ES ENERGY SMART WRAPPER SERIES C

OPERATING & SERVICE PARTS MANUAL 700ES ENERGY SMART WRAPPER SERIES C OPERATING & SERVICE PARTS MANUAL 700ES ENERGY SMART WRAPPER SERIES C READ ALL INSTRUCTIONS CAREFULLY BEFORE OPERATING EQUIPMENT TABLE OF CONTENTS Machine Components & Electrical Requirement... Preliminary

More information

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

Information Job Sheet 4. Closed-Loop Drainback Systems. Drainback tanks

Information Job Sheet 4. Closed-Loop Drainback Systems. Drainback tanks Information Job Sheet 4 Closed-Loop Drainback Systems Drainback systems can consist of two closed-loop circuits. Each loop contains an active pump to circulate the solar and storage fluids independently.

More information

Cascade Sequencer. Control Installation and Operation Instructions. Infinite Energy Boiler Manual. Also read and follow: CS-IOM-1

Cascade Sequencer. Control Installation and Operation Instructions. Infinite Energy Boiler Manual. Also read and follow: CS-IOM-1 CS-IOM-1 Cascade Sequencer Control Installation and Operation Instructions Also read and follow: Infinite Energy Boiler Manual Installer: Read the appliance Installation Manual, including this manual,

More information

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Instruction Manual Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Manual PCT-3000 Revision 9/2014 The PCT-3000 series control console incorporates

More information

Gen II Entree Bath - All Models

Gen II Entree Bath - All Models Gen II Entree Bath - All Models Installation Manual Important Safety Instructions Read & Follow All Instructions Thoroughly Important safety instructions. Read and follow all instructions thoroughly. CAUTION:

More information

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units... Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop

More information

Bench Top Cooling Tower H893

Bench Top Cooling Tower H893 Bench Top Cooling Tower H893 Figure 1: H893 Shown with Column B (fitted) and Optional Column E Demonstrates all processes found in a full scale forced draught cooling tower Rapid stabilisation allows experimental

More information

Shell and Tube Heat Exchanger User's Manual

Shell and Tube Heat Exchanger User's Manual Page 1 of 5 Shell and Tube Heat Exchanger User's Manual Brigham Young University Unit Operations Laboratory Revision 97.5 Introduction The Shell and Tube Heat Exchanger is a small model of a typical industrial

More information

Rev B, 9/2/2009. Kodiak Chiller Overview

Rev B, 9/2/2009. Kodiak Chiller Overview 930-0001 Rev B, 9/2/2009 Kodiak Chiller Overview Presentation Outline Phone: 781-933-7300 Lytron Technical Support Contact Information 3 Introduction 4 Part I: Unpacking 5 Part II: Installation 7 Part

More information

ACME DIAGNOSTICS STANDARD OPERATING PROCEDURE

ACME DIAGNOSTICS STANDARD OPERATING PROCEDURE ACME DIAGNOSTICS STANDARD OPERATING PROCEDURE Procedure Number: II.01.200a Effective Date: 09/14/99 Review and Update: 09/2003 TITLE: ADVIA 120 ROUTINE MAINTENANCE PURPOSE AND PRINCIPLE: The ADVIA 120

More information

- Data Brochure Mixing Control 360

- Data Brochure Mixing Control 360 - Data Brochure Mixing Control 360 D 360 03/09 The Mixing Control 360 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or setpoint operation. The

More information

Improved Dryer Control

Improved Dryer Control Improved Dryer Control Kenneth C. Hill President Kadant Johnson Systems Division David Vijh Senior Process Control Engineer Technical White Paper Series EXECUTIVE SUMMARY Significant improvements in dryer

More information

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV CyCLO User Guide Version 2.00 19 th December 2017 REV 2.00 1 Contents 1. Hardware... 3 1.1. Introduction... 3 1.2. Electrical Specification... 3 1.3. Board Overview... 4 1.4. Electrical Installation...

More information

Welcome to MultiSight TM Vision Sensor Hands-On Lab

Welcome to MultiSight TM Vision Sensor Hands-On Lab Welcome to MultiSight TM Vision Sensor Hands-On Lab About This Hands-On Lab Welcome to the MultiSight TM Vision Sensor Hands-On Lab! This session provides you with an opportunity to explore the functionality

More information

Specifications 3. Bladder 5. Chimney 12. Air Supply 12. Anti-Rollout Device and Ash Auger Tube 14. Timer 15

Specifications 3. Bladder 5. Chimney 12. Air Supply 12. Anti-Rollout Device and Ash Auger Tube 14. Timer 15 TABLE OF CONTENTS Page No. Specifications 3 Bladder 5 Fire Door 7 Chimney 12 Air Supply 12 Anti-Rollout Device and Ash Auger Tube 14 Timer 15 Supply Line and Return Line Threaded Connectors 15 Low Water

More information

TEMPERATURE CONTROLLER (STANDARD MODEL)

TEMPERATURE CONTROLLER (STANDARD MODEL) OPERATING MANUAL TEMPERATURE CONTROLLER (STANDARD MODEL) 689-0000 689-0005 Barnant Company 28W092 Commercial Avenue Barrington, Illinois U.S.A. 60010-2392 (847) 381-7050 (847) 381-7053 (Fax) 800-637-3739

More information

AIR CONDITIONER PERFORMANCE RATING

AIR CONDITIONER PERFORMANCE RATING HPRATE V5.1 AIR CONDITIONER PERFORMANCE RATING by G.L. Morrison MechLab The University of New South Wales.EDU.AU September 2012 Version 5.1 HPRATE 5 Air Conditioner Performance Rating 1 HPRATE AIR CONDITIONER

More information

SECTION AIR COMPRESSORS AND ACCESSORIES

SECTION AIR COMPRESSORS AND ACCESSORIES PART 1 GENERAL 1.01 WORK INCLUDED SECTION 11370 AIR COMPRESSORS AND ACCESSORIES A. This specification includes air compressors with air dryers. B. Furnish, install, start-up, and test air compressors and

More information

Commercial Noritz Water Heater Multi-System Application Sheet

Commercial Noritz Water Heater Multi-System Application Sheet Commercial Noritz water heaters can be used individually or in a Multi-System (2+ units) when used with either a Quick Connect Cord or a multi-unit. QC-1 (Quick Connect Cord) SC-1-6M SC-1-12M SC-1-24M

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

BMC OPERATION AUTOMATIC & MANUAL SYSTEMS

BMC OPERATION AUTOMATIC & MANUAL SYSTEMS BMC OPERATI AUTOMATIC & MANUAL SYSTEMS Automatic Control Manual Control PICTOGRAMS Each Signifier displayed here is specific to this User Manual. Menu Previous Advance Note Tip Example Run Sequence Seed

More information

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM BEST PRACTICE NO. 30 WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM Air and noncondensable gases are one of the major problems in a steam system that can cause production

More information

Sanitation Controls for Food Processing

Sanitation Controls for Food Processing PENN STATE FOOD SCIENCE TRAINING SUPPORT Sanitation Controls for Fd Processing Effective Employee Education Starting with a gd foundation of relevant facts and applications, this information can be effectively

More information

Eccotemp L5 and L10 Comprehensive Troubleshooting Guide

Eccotemp L5 and L10 Comprehensive Troubleshooting Guide http://waterheatertimer.org/tent-city-usa-water-heater.html Eccotemp L5 and L10 Comprehensive Listed below are some common questions and troubleshooting guidelines for our various models. Always remember

More information

PULSE OXIMETER PACKAGE

PULSE OXIMETER PACKAGE instrumentation and software for research PULSE OXIMETER PACKAGE CANL-425SV-A USER S MANUAL DOC-095 Rev. 1.6 Copyright 2012 All Rights Reserved Med Associates Inc. P.O. Box 319 St. Albans, Vermont 05478

More information

- Data Brochure Universal Reset Module 422

- Data Brochure Universal Reset Module 422 - Data Brochure Universal Reset Module 422 D 422 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

OPERATING AND MAINTENANCE MANUAL FOR INSTANTANEOUS STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL F

OPERATING AND MAINTENANCE MANUAL FOR INSTANTANEOUS STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL F OPERATING AND MAINTENANCE MANUAL FOR INSTANTANEOUS STEAM FIRED WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL F Edition 2013 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

Bench-Top Vacuum Oven with 28 segments programmable controller

Bench-Top Vacuum Oven with 28 segments programmable controller Bench-Top Vacuum Oven with 28 segments programmable controller DZF-6000F Series Vacuum Oven MTI Corporation www.mtixtl.com 1 Safety notes DZF Vacuum Oven Please read the following safety notes carefully

More information

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application 2050 Application Note 140-1136 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware Outputs...

More information

QIAcube HT Unpacking and Installation Instructions

QIAcube HT Unpacking and Installation Instructions QIAcube HT Unpacking and Installation Instructions Unpacking the QIAcube HT Important points before starting If you have any questions about the unpacking procedure, contact QIAGEN Technical Services or

More information

OPERATING & SERVICE PARTS MANUAL 700ES ENERGY SMART WRAPPER SERIES B

OPERATING & SERVICE PARTS MANUAL 700ES ENERGY SMART WRAPPER SERIES B OPERATING & SERVICE PARTS MANUAL 700ES ENERGY SMART WRAPPER SERIES B READ ALL INSTRUCTIONS CAREFULLY BEFORE OPERATING EQUIPMENT TABLE OF CONTENTS Machine Components & Electrical Requirement... 3 Preliminary

More information

CONTROLLING BOILER SWELL AND SHRINK

CONTROLLING BOILER SWELL AND SHRINK CONTROLLING BOILER SWELL AND SHRINK INTRODUCTION Steam drum level is one of the major contributors of boiler trips and downtime. Affected by a specific phenomenon (swell and shrink) it is difficult to

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

MacDonald Steel Limited

MacDonald Steel Limited DELUXE FILLER / CROWNER MODEL - DFC4 1 REV 00 CAUTION / WARNING READ MANUAL BEFORE OPERATING MACHINE DO NOT EXCEED 50 PSI ON Co2 OR BEER LINES DO NOT EXCEED 100 F (35 C) ON Co2 OR BEER LINES DO NOT HOSE

More information

Niles Steel Tank Hot Water Generator Installation and Operation Manual

Niles Steel Tank Hot Water Generator Installation and Operation Manual Niles Steel Tank Hot Water Generator Installation and Operation Manual Contents: Contents 1 Hazard definitions 1 1. General Information.... 2 Availability... 3 Optional Control Packages... 5 2. Installation....

More information

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE Satoru Ito 1, Keisuke Tsukada 1, Nobuyoshi Tsuzuki 2, Takao Ishizuka 3 and Hiroshige Kikura 3 1 Department of nuclear Engineering, Graduate

More information

MT Alliance Refrigeration Technician s Manual

MT Alliance Refrigeration Technician s Manual MICRO THERMO TECHNOLOGIES MT Alliance Refrigeration Technician s Manual Document No. 71-MTA-1007-R3.1 V4.1 No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL LV8 COMMERCIAL REFRIGERANT RECOVERY UNIT NATIONAL REFRIGERATION PRODUCTS 985 WHEELER WAY LANGHORNE, PA 19047 (215) 638-8909 FAX (215) 638-9270 A01001 7/11/96 NRP-OM-LV8 7/96

More information

EXTREME HP-1 Reverse Osmosis System

EXTREME HP-1 Reverse Osmosis System EXTREME HP-1 Reverse Osmosis System Leader Evaporator Co., Inc. 49 Jonergin Drive Swanton, VT 05488 Tel: 802-868-5444 www.leaderevaporator.com TABLE OF CONTENTS INTRODUCTION... 4 THEORY OF OPERATION...

More information

KRSCP Self-Contained Walk-In Unit Installation and Service Manual Addendum

KRSCP Self-Contained Walk-In Unit Installation and Service Manual Addendum KRSCP Self-Contained Walk-In Unit Installation and Service Manual Addendum P/N 1H52918001_B Version 1.1 May 2011 P/N_1H52918001_B P/N 1H52918001_B iii TABLE OF CONTENTS I. Overview.....................

More information

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold

INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold LOW VAC INSTRUCTION MANUAL 4-WAY BALL VALVE Digital Manifold REF HIGH SPECIAL FEATURES Low battery indicator Displays 63 refrigerants Displays corresponding saturation, dew or bubble point temperature

More information

P550W Series Air Dryers

P550W Series Air Dryers P550W Series Air Dryers User s Guide Models covered: P550W P550WH P550WLP P552W P552WH P552WLP 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P550W Series Air Dryer! We

More information

University of Minnesota Nano Fabrication Center Standard Operating Procedure

University of Minnesota Nano Fabrication Center Standard Operating Procedure Equipment Name: ALD Coral Name: ald Revision Number: 8 Model: Savannah Revisionist: T. Whipple Location: Bay 1 Date: 3/14/2017 1 Description The ALD, Atomic Layer Deposition system is a Savannah series

More information

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS

Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS English Instruction Manual DIGITAL MANIFOLD FOR HVAC/R SYSTEMS 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Instruction Manual

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 502C-902C SUGGESTED SPECIFICATIONS Catalog No.: 6000.601A Effective: 07-12-18 Replaces: 10-31-16 FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

Insty-Pac Steam Humidifiers

Insty-Pac Steam Humidifiers IP-1 Insty-Pac Steam umidifiers The PURE umidifier Co. Insty-Pac (patent no. 6,065,740) steam injection humidifier is jobengineered to assure highly efficient steam release into the air stream. Each humidifier

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

MOCCA CUBIC AUS/NZ. 08/53066/0 Issue 2

MOCCA CUBIC AUS/NZ. 08/53066/0 Issue 2 MOCCA CUBIC AUS/NZ 08/53066/0 Issue 2 The product complies with the European Safety Standards EN60335-2-30 and the European Standard Electromagnetic Compatibility (EMC) EN55014, EN60555-2 and EN60555-3

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

OPERATION & MAINTENANCE MANUAL TX600

OPERATION & MAINTENANCE MANUAL TX600 OPERATION & MAINTENANCE MANUAL TX600 RTI TECHNOLOGIES, INC. 4075 East Market Street York, PA 17402 Manual P/N 035-80118-00 (Rev B) ! TABLE OF CONTENTS! TX600 Before Using Page 2 Safety Precautions Page

More information

- Data Brochure Universal Reset Module 423

- Data Brochure Universal Reset Module 423 - Data Brochure Universal Reset Module 423 D 423 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

Manage Alarms. Before You Begin. NTP-E57 Document Existing Provisioning CHAPTER

Manage Alarms. Before You Begin. NTP-E57 Document Existing Provisioning CHAPTER CHAPTER 9 Manage Alarms This chapter provides procedures required to view and manage Cisco ONS 15600 alarms and conditions. Cisco Transport Controller (CTC) detects and reports SONET alarms generated by

More information

Manage Alarms. Before You Begin CHAPTER

Manage Alarms. Before You Begin CHAPTER CHAPTER 9 Manage Alarms This chapter provides procedures required to view and manage Cisco ONS 15600 alarms and conditions. Cisco Transport Controller (CTC) detects and reports SONET alarms generated by

More information

Spacing Average distance between seeds in a given row of planted seeds. Results are expressed in inches.

Spacing Average distance between seeds in a given row of planted seeds. Results are expressed in inches. Purpose: The purpose of the Field Seed Spacing Template is to provide a tool to gather information on seeds that have been planted. The results provide a numerical evaluation of the plant population and

More information

Oakton TEMP 9500 Advanced Multiparameter Controller

Oakton TEMP 9500 Advanced Multiparameter Controller Oakton TEMP 9500 Advanced Multiparameter Controller Models: 89800-03 & 89800-04 Oakton Instruments 625 E Bunker Ct. Vernon Hills, IL 60061, USA 1-888-4OAKTON (1-888-462-5866) info@4oakton.com Contents

More information

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs User Manual Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs Models 89800-03 and 89800-04 THE STANDARD IN PRECISION MEASUREMENT Table of Contents

More information

Chemistry Materials Separation Processes

Chemistry Materials Separation Processes Chemistry Materials Separation Processes You will be assigned to separate a mixture of several different materials. However, first you will need to learn about several techniques used for mixture separation.

More information

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application 2070 Application Note 140-1040 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware

More information

Pump-Up Controller MODEL 4062

Pump-Up Controller MODEL 4062 Pump-Up Controller 4-20mA Input/Scalable Output Seal Fail Monitoring Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters RS-485/Modbus Communications DESCRIPTION The Model 4062 Pump-Up

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

MODEL A18 SOLVENT RECOVERY SYSTEMS (EXPLOSION PROOF UNITS)

MODEL A18 SOLVENT RECOVERY SYSTEMS (EXPLOSION PROOF UNITS) MODEL A18 SOLVENT RECOVERY SYSTEMS (EXPLOSION PROOF UNITS) FOR PROPER AND SAFE USE OF THIS CHEMCHAMP EQUIPMENT, PLEASE FOLLOW THIS DOCUMENT AND LOCAL AUTHORITY. KEEP THIS DOCUMENT FOR FUTURE REFERENCE.

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

LineGuard 2300 Program User Manual (FloBoss 107)

LineGuard 2300 Program User Manual (FloBoss 107) Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual (FloBoss 107) Remote Automation Solutions Revision Tracking Sheet November 2012 This manual may be revised periodically

More information