1 ASSE Standard # ASSE Board Approved: APRIL 28, 2008 ANSI Approval: DATE American Society of Sanitary Engineering Performance Requirements for Anti-Siphon Fill Valves for Water Closet Tanks An American National Standard
2
3 General Information Neither this standard, nor any portion thereof, may be reproduced without the written consent of the American Society of Sanitary Engineering. No product may be said to be ASSE approved unless the manufacturer has applied to the ASSE, has had his product tested according to the applicable ASSE Standards, and when the product has passed the test, displays the ASSE Seal on the product. Instructions for receiving the authorization to display the Seal are available from ASSE's International Office. Organizations wishing to adopt or list any ASSE Standard should print the ASSE Standard number on the cover page first and in equal or larger type to that of the adopting or listing organization. American Society of Sanitary Engineering Westlake, Ohio Copyright 2008, 1999, 1986, 1979, 1976 Anti-Siphon Fill Valves for Water Closet Tanks ASSE Standard # i
4 ii Anti-Siphon Fill Valves for Water Closet Tanks
5 Foreword This foreword shall not be considered a part of the standard, however, it is offered to provide background information. ASSE standards are developed in the interest of consumer safety. This standard outlines the performance requirements for Anti-siphon Fill Valves (Ballcocks) for Gravity Water Closet Flush Tanks, and describes those performance requirements in terms of methods of testing applicable to all such units, equivalent materials or methods of testing intended to demonstrate compliance with these requirements are also acceptable. Recognition is made of the time volunteered by members of the working group and of the support of the manufacturers who also participated in the meetings for this standard. This standard does not imply ASSE s endorsement of a product which conforms to these requirements. Compliance with this standard does not imply acceptance by any code body. It is recommended that these devices be installed consistent with local codes by qualified and trained professionals. This standard was promulgated in accordance with procedures developed by the American National Standards Institute (ANSI). Anti-Siphon Fill Valves for Water Closet Tanks iii
6 Product Standards Committee Edward Lyczko Product Standards Committee Chairman Cleveland Clinic Cleveland, Ohio Rand H. Ackroyd Rand Engineering Newburyport, Massachusetts Gunnar O. Collins Collins Backflow Specialists, Inc. Palatine, Illinois Judson W. Collins JULYCO Professionals Mannford, Oklahoma Shannon M. Corcoran ASSE Standards Coordinator Westlake, Ohio A. Richard Emmerson General Interest Buffalo Grove, Illinois Ron George Ron George Design & Consulting Newport, Michigan Charles Gross International Association of Plumbing and Mechanical Officials Walnut, California John F. Higdon, P.E. Apollo Valves/Conbraco Industries, Inc. Pageland, South Carolina Valentine Lehr, P.E. Lehr Associates New York, New York Chuck Lott Precision Plumbing Products, Inc. Portland, Oregon Peter Marzec United Association of Plumbers and Pipefitters Washington, D.C. Brad Noll Wilkins, A Division of Zurn Industries, Inc. Paso Robles, California Thomas C. Pitcherello State of New Jersey Bordentown, New Jersey Shabbir Rawalpindiwala Kohler Company Kohler, Wisconsin Tsan-Liang Su, Ph.D. Center for Environmental Systems Stevens Institute of Technology Hoboken, New Jersey Steven Hazzard ASSE Staff Engineer Westlake, Ohio iv Anti-Siphon Fill Valves for Water Closet Tanks
7 1002 Working Group Arturo Robles 1002 Working Group Chairman Fluidmaster, Inc. San Juan Capistrano, California Bruce Artunez Coast Foundry Pamona, California Steven Hazzard ASSE Staff Engineer Westlake, Ohio Larry Himmelblau Chicago Faucet Co. / Geberit Des Plaines, Illinois Sarah Morgan Oatey Company Cleveland, Ohio Norman M. Kummerlen Moen, Inc. North Olmsted, Ohio Sally Remedios Delta Faucet Co. Indianapolis, Indiana Steve Tokarz Brass Craft Novi, Michigan David Viola IAPMO Ontarioa, California John Watson Sloan Valve Company Franklin Park, Illinois Chip Way Lavelle Industries Burlington, Wisconsin Manfred Wolpert Chicago Faucet Co. / Geberit Des Plaines, Illinois Shabbir Rawalpindiwala Kohler Company Kohler, Wisconsin Anti-Siphon Fill Valves for Water Closet Tanks v
8 Table of Contents Section I General Application Scope... 1 Figure 1 - Shank, Locknut and Coupling Nut Dimensions Reference Standards... 2 Section II Test Specimens Samples Submitted for Test Samples Tested Drawings Rejection... 3 Section III Performance Requirements and Compliance Testing Elevated Pressure and Temperature Test Cycle Test Critical Level Marking and Backflow Prevention Test... 5 Figure 2 - Anti-Siphon Fill Valve Test Assembly Total Flow Test - Retrofit Devices Only Refill Capacity Test - Retrofit Devices Only... 6 Section IV Detailed Requirements Materials Identification and Markings Installation Instructions... 8 Section V Definitions... 9 Appendix A... 9 vi Anti-Siphon Fill Valves for Water Closet Tanks
9 Anti-Siphon Fill Valves for Water Closet Tanks Section I 1.0 General 1.1 Application This standard provides dimensional and minimum performance requirements for anti-siphon fill valves for water closet tanks (herein referred to as the device ), including protection of the potable water supply against back siphonage of water from the water closet tank. 1.2 Scope Description These devices are cold water supply valves that are installed within water closet tanks to provide tank refill and a trap reseal after flushing a water closet. They are equipped with backflow prevention devices or an air gap Working Pressure The device shall be designed to operate at a minimum pressure range of 20.0 psi to psi static (137.9 kpa to kpa) Capacity - Total Fill and Refill Original Equipment Manufacturer When the device is furnished as original equipment with a manufacturer s water closet, the total flow capacity shall be sufficient to assure proper operation of the fixture in accordance with the performance standard, ASME A The device shall deliver a fill rate through the refill orifice as required by the water closet manufacturer Retrofit Use When the device is furnished to retrofit water closets, the device shall deliver a minimum flow rate at 15.0 psig (103.4 kpa) flowing pressure of 1.5 GPM (5.7 L/min), and a minimum refill flow rate, through the refill orifice, of 20% of the total fill rate at 15.0 psi (103.4 kpa) flowing pressure Leakage and Spray Containment The device shall not spray or otherwise leak water to the outside of the water closet tank during operation Backflow Prevention The device shall be equipped with a means to prevent backflow due to back siphonage. Air inlet ports shall be protected in such a manner as to reduce the risk of the intake of foreign material into the device. Anti-Siphon Fill Valves for Water Closet Tanks 1
10 1.2.6 Refill Tube A means shall be provided to secure the refill tube in its installed position Dimensional Criteria for Fill Valve Components Dimensions for shanks, coupling nuts and locknuts shall be as shown in Figure 1. Thread dimensions shall be 15/16-14 UNS-1 per ASME/ANSI B1.1. See Appendix A. Figure 1 Shank, Locknut and Coupling Nut Dimensions < SHANK B COUPLING NUT Note 2 A < > H Note 3 < E > C >< > Note 1 < > D Note 4 G < > F A LOCKNUT (OR MOUNTING NUT) <> < B Note 2 A > A B C D E F G 15/16-14UNS-1 Thread 1.40 inches (35.56 mm) minimum diameter 1.37 inches (34.8 mm) minimum 1.62 inches (41.15 mm) minimum inches (15.88 mm mm) inside diameter 0.50 inches (12.70 mm) minimum effective thread depth 0.31 inches (7.87 mm) minimum H 0.5 inches (12.70 mm) minimum depth NOTE 1: 0.1 inches (2.5 mm) maximum chamfer permissible as shown in figures. NOTE 2: Thread lead-in chamfers shall be permitted NOTE 3: The shank bottom surface shall be smooth and suitable for sealing with flat washers. NOTE 4: 0.1 inch (2.5 mm) maximum lead in for thread shall be allowed. 1.3 Reference Standards Referenced industry standards shall mean the listed edition of the standard. ASME A Performance Requirements for Backflow Protection Devices and Systems in Plumbing Fixture Fittings ASME A Vitreous China Plumbing Fixtures and Hydraulic Requirements for Water Closets and Urinals ASME B Unified Inch Screw Threads 2 Anti-Siphon Fill Valves for Water Closet Tanks
11 Section II 2.0 Test Specimens 2.1 Samples Submitted for the Test Three (3) devices of each model shall be submitted by the manufacturer. 2.2 Samples Tested The testing agency shall select one (1) of each model for the full test. Tests shall be performed in the order listed on one (1) device of each model submitted. 2.3 Documentation Assembly drawings, installation instructions, and other information which are needed to enable a testing agency to determine compliance with this standard, shall accompany devices when submitted for examination and performance tests. 2.4 Rejection Failure of one (1) device shall be cause for rejection of that model. Anti-Siphon Fill Valves for Water Closet Tanks 3
12 Section III 3.0 Performance Requirements and Compliance Testing 3.1 Elevated Pressure and Temperature Test Purpose The purpose of this test is to evaluate the device s performance at elevated temperatures and pressures; and to ensure that the manufacturer has provided a means for securing the refill tube to the overflow tube and that it remains in place during the test Procedure The device shall be installed in a water closet tank or container per the manufacturer s instructions. The water shall be permitted to be displaced in the water closet tank or container. The water supply temperature for this test shall be maintained at F ± 5.0 F (48.9 C ± 2.8 C), with a static pressure of psi (861.9 kpa). Flush the water closet tank every five (5) minutes for a total of fifty (50) cycles using a flush volume tolerance of 1.4 to 2.0 gallons (5.3 to 7.6 liters). Following this test, and with the water closet tank filled with water maintained at F ± 5.0 F (48.9 C ± 2.8 C), the pressure in the device shall be raised to psig ( kpa) and maintained for five (5) minutes. The device shall be checked for leakage, distortion, or other indications of damage which would affect the device s performance Criteria Any indications of leakage, distortion, or other damage which affects the device s performance shall result in a rejection of the device. Failure of the refill tube to remain in place throughout this test shall result in a rejection of the device. 3.2 Cycle Test Purpose The purpose of this test is to demonstrate the device s long-term operational performance Procedure Install the device per the manufacturer s instructions in a water closet tank or container. The device shall be operated a total of seventy-five thousand (75,000) cycles at a minimum of 90.0 psi (620.6 kpa) static pressure and 70.0 psig (482.7 kpa) minimum flowing pressure using ambient temperature [65.0 F F (18.3 C to 26.7 C)] water. For each cycle, the tank shall be filled and the cycle shall have a maximum cycle time of one (1) minute. The water shall be permitted to be displaced in the tank to accelerate this test. Following this test, maintain a static pressure of psig ( kpa) for five (5) minutes, and observe for leakage, distortion, or other indications of damage which would affect the device s performance Criteria Any indications of leakage, distortion, or other damage which affects the device s performance shall result in a rejection of the device. Failure of the refill tube to remain in place throughout this test shall result in a rejection of the device. 4 Anti-Siphon Fill Valves for Water Closet Tanks
13 3.3 Critical Level Marking and Backflow Prevention Test Purpose The purpose of this test is to verify the Critical Level (CL) marking, and ensure that the backflow prevention feature functions as intended Procedure Install the device in accordance with Figure 2. Foul all of the check valves, seats and checking members with a inches (0.8 mm) diameter wire. The fouling wire shall be placed at a single point on each seating area. Figure 2 Anti-Siphon Fill Valve Test Assembly Antisiphon Fill Valve Bowl Refill Tube AA BB Test Tank Tank Fill Tube Colored Water Lock Nut Sight Glass Pressure Gauge Quick Opening Valve Slow Opening Valve To Vacuum Tank Water Collecting Drain A sight glass shall be assembled to the shank assembly as shown in Figure 2. Start with the tank water level inches (3.2 mm) below the vacuum breaker air port(s) or water discharge openings (air gaps type). As the water level is lowered, the device shall be subjected to an instantaneous vacuum of 25 inches of mercury (84.7 kpa) until there is no water in the sight glass. Next, apply an intermittent vacuum of 5 inches of mercury (16.9 kpa) for five (5) seconds on and five (5) seconds off until there is no water in the sight glass. Repeat the intermittent vacuum test Anti-Siphon Fill Valves for Water Closet Tanks 5
14 at 10, 15, 20, and 25 inches of mercury (33.9 kpa, 50.8 kpa, 67.8 kpa, and 84.7 kpa) until there is no water in the sight glass. This determines line BB, the elevation at which back-siphonage ceases as the test tank water level is lowered. To determine line AA, the elevation at which back-siphonage begins as the level is raised, set the water level one (1) inch (25.4 mm) below line BB. The device shall be subjected to an instantaneous vacuum of 25 inches of mercury (84.7 kpa). Increase the water level by increments of inch (3.2 mm) until water appears in the sight glass. At each inch (3.2 mm) increment, apply an intermittent vacuum of 5 inches of mercury (16.9 kpa) for five (5) seconds on and five (5) seconds off until water appears in the sight glass. Repeat the intermittent vacuum test at 10, 15, 20, and 25 inches of mercury (33.9 kpa, 50.8 kpa, 67.8 kpa, and 84.7 kpa) until water appears in the sight glass. While lines AA and BB may coincide, the lower of the two (2) lines shall be determined to be the Critical Level (CL) of the device Criteria a) If the Critical Level (CL) mark on the device is at or below the Critical Level (CL) determined in Section 3.3.2, proceed to Section 3.5. b) If water fails to appear in the sight glass, the device shall be tested to Section c) If the Critical Level (CL) mark on the device is above the Critical Level (CL) determined in Section 3.3.2, this shall result in a rejection of the device Procedure to Determine if There are Hidden Checks Install the device in accordance with Figure 2. Hold all of the check valves, seats and checking members fully open. Seal off the air inlet ports. A sight glass shall be assembled to the shank assembly as shown in Figure 2. Submerge the device completely under the water in the water closet tank, and subject the device to a vacuum of 25 inches of mercury (84.7 kpa). Check for water in the sight glass. Failure of water to appear in the sight glass shall indicate the presence of a hidden check valve. Repeat the procedure in Section with the check valve(s) fully open until water appears in the sight glass. Retest to Section Total Flow Test - Retrofit Devices Only Purpose The purpose of this test is to verify that the retrofit device meets minimum flow rates Procedure The device shall be set to run fully open with a flowing pressure of 15.0 psi (103.4 kpa) measured at the inlet to the device. Measure the flow rate for a minimum of one (1) minute Criteria Failure of the device to flow a minimum of 1.5 GPM (5.7 L/min) at 15.0 psi (103.4 kpa) flowing pressure shall result in a rejection of the device. 3.5 Refill Capacity Test - Retrofit Devices Only Purpose The purpose of the test is to verify that the device meets minimum refill requirements. 6 Anti-Siphon Fill Valves for Water Closet Tanks
15 3.5.2 Procedure The device shall be set to run fully open with a flowing pressure of 15.0 psi (103.4 kpa) measured at the inlet of the device. The refill flow rate shall be measured for a minimum of one (1) minute Criteria Failure of the device to flow a minimum of 20% of the flow rate measured in Section through the refill tube at 15.0 psi (103.4 kpa) flowing pressure shall result in a rejection of the device. Anti-Siphon Fill Valves for Water Closet Tanks 7
16 Section IV 4.0 Detailed Requirements 4.1 Materials Solder and fluxes containing lead in excess of 0.2% shall not be used in contact with potable water. Metal alloys in contact with potable water shall not exceed 8% lead. 4.2 Identification and Markings Each device shall be permanently marked with the following information in such a manner that the device can be readily identified after installation. a) Manufacturer s name or trademark; b) Model name or number, or part number; c) Critical Level marking for device with air inlet ports. 4.3 Installation Instructions When devices are furnished to retrofit water closets, installation instructions shall be provided with the final packaged product. 8 Anti-Siphon Fill Valves for Water Closet Tanks
17 Section V 5.0 Definitions Definitions not found in this Section are located in the Plumbing Dictionary, Sixth Edition, published by the ASSE. Anti-Siphon Fill Valve Anti-siphon fill valves are cold water supply valves that are installed within water closet tanks to provide tank refill and a trap reseal after flushing a water closet. They are equipped with backflow prevention devices or an air gap. Critical Level The lowest water level in a fitting at which backsiphonage will not occur 1. Appendix A This Appendix shall not be considered a part of the standard. It is provided for informational purposes only. Thread Dimensions (For Reference Only) The information in this appendix is the result of a series of calculations which are specified in reference standard ASME/ANSI B1.1. Fill Valve Shanks Nominal Shank Size 15/16 inch (23.81 mm) External Thread Designation 15/16-14UNS- 1A Major Diameter of Thread Pitch Diameter of Thread Maximum Minimum Maximum Minimum inch (23.77 mm) inch (23.37 mm) inch (22.50 mm) inch (22.39 mm) Fill Valve Locknuts and Coupling Nuts Nominal Size 15/16 inch (23.81 mm) Internal Thread Designation 15/16-14UNS- 1B Minor Diameter of Thread Pitch Diameter of Thread Maximum Minimum Maximum Minimum inch (22.05 mm) inch (21.85 mm) inch (22.90 mm) inch (22.63 mm) 1. Excerpt from the ASME A /CSA B125.1). Anti-Siphon Fill Valves for Water Closet Tanks 9
18 American Society of Sanitary Engineering FOR PLUMBING AND SANITARY RESEARCH 901 Canterbury Road, Suite A Westlake, Ohio USA TEL: (440) FAX: (440) general.info@asse-plumbing.org Web:
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS MATERIAL AND PROPERTY STANDARD FOR
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS MATERIAL AND PROPERTY STANDARD FOR EARLY-CLOSURE REPLACEMENT FLAPPERS OR EARLY-CLOSURE REPLACEMENT FLAPPER WITH MECHANICAL ASSEMBLIES IAPMO
More informationBy Authority Of THE UNITED STATES OF AMERICA Legally Binding Document
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has
More informationBy Authority Of THE UNITED STATES OF AMERICA Legally Binding Document
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has
More informationPublic Comment Draft 19Nov18
ASSE Standard #1084 2018 ASSE Board Approved: xxxx ANSI Approval: xxxx ASSE International Performance Requirements for Water Heaters with Temperature Limiting Capacity Public Comment Draft 19Nov18 General
More informationSECTION DOMESTIC WATER PIPING SPECIALTIES
SECTION 22 11 19 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationSummary of Substantive Changes between the 2012 and 2018 editions of ASME A /CSA B125.1 Plumbing Supply Fittings
Summary of Substantive Changes between the 2012 and 2018 editions of ASME A112.18.1/CSA B125.1 Plumbing Supply Fittings Presented to the IAPMO Standards Review Committee on May 6, 2013 General: The changes
More informationB. Shop Drawings: Include diagrams for power, signal, and control wiring.
SECTION 224213.13 - COMMERCIAL WATER CLOSETS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationB. Shop Drawings: Include diagrams for power, signal, and control wiring.
SECTION224213.13 -COMMERCIAL WATERCLOSETS PART 1- GENERAL 1.1 SUMMARY Section Includes: 1. Water closets. 2. Flushometer valves. 3. Toilet seats. 1.2 ACTION SUBMITTALS Product Data: For each type of product.
More informationUnion County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Faucets for lavatories, bathtubs, bathtub/showers, showers and sinks. 2. Flushometers. 3. Toilet
More informationA. Section Joint Sealants: Seal fixtures to walls and floors.
SECTION 224000 - PLUMBING FIXTURES PART 1 GENERAL 1.1 SECTION INCLUDES A. Water closets. B. Urinals. C. Lavatories. D. Sinks. E. Service sinks. F. Showers. G. Wash fountains. H. Eye wash fountains. 1.2
More informationCombined Hand-Washing Systems
IAPMO IGC 127-20142018 PUBLIC REVIEW DRAFT Combined Hand-Washing Systems IAPMO Standard IAPMO IGC 127 20142018 Published: January 2014 Previous Editions: January 2014, July 2013, April 2013, April 2009,
More informationDUKE UNIVERSITY CONSTRUCTION STANDARDS
1 22 40 00 Plumbing Fixtures 1. General A. Definitions 1. Section includes a. Water closets and urinals b. Lavatories, sinks, and service sinks c. Electric water coolers, drinking fountains, d. Showers
More informationAPPENDIX L ALTERNATE PLUMBING SYSTEMS
ALTERNATE PLUMBING SYSTEMS L 1.0 General. L 1.1 Applicability. The intent of this appendix is to provide clarification of procedures for the design and approval of engineered plumbing systems, alternate
More informationDESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.
PART 1 - GENERAL 1.1 Toilet rooms and utility rooms to have floor drains at lowest point. 1.2 Utilize Exposed Flushometers. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.
More informationBARRINGTON PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET K-4327
BARRINGTON PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET K-4327 BEFORE YOU BEGIN INSTALLER HAZARD NOTIFICATION WARNING: Risk of injury or water damage. Contents of vessel under pressure can cause severe
More informationDESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES
2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.
More informationLasco # Description Picture Lasco # Description Picture
TOILET REPAIR 02-1755 2 Pack, White Toilet Seat Hinge 663353 Washer, 02-3133 664625 3-1/16 O.D. x 2-1/8 I.D. x 3/16, Close Coupled Sponge Gasket, Toilet Tank To Bowl Gasket, Sponge Rubber Tank To Bowl
More informationA. This Section includes the following domestic water piping specialties:
SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationSAN RAPHAEL PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET
SAN RAPHAEL PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials,
More informationINSPECTION OF COMMERCIAL KITCHEN PLUMBING
INSPECTION OF COMMERCIAL KITCHEN PLUMBING 801.1 SCOPE Food-handling establishments 2 - by John Williams, Jr. Plumbing Control Supervisor Onondaga County Water Environment Protection Commercial Kitchens
More informationMatrix of changes for the National Standard Plumbing Code July 2013
Matrix of changes for the National Standard Plumbing Code July 2013 Item # Section Number Person Submitting Change Committee Action 10-77 10.20.8 and Table 3.1.3 XI Certification 10-82 12.16 Size and Lengths
More informationDESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point.
PART 1 - GENERAL 1.01 Toilet rooms and utility rooms to have floor drains at lowest point. 1.02 Utilize Exposed Flushometers. 1.03 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.
More informationTRUMAN STATE UNIVERSITY PRESIDENT S RESIDENCE RENOVATION
SECTION 224100 - RESIDENTIAL PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationPALARRE, ROCHELLE WATER-GUARD VITREOUS CHINA SIPHON JET TOILET
PALARRE, ROCHELLE WATER-GUARD VITREOUS CHINA SIPHON JET TOILET BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials,
More informationAPPENDIX A. A 3.2 Determine the elevation of the highest. A 3.3 Subtract the sum of loss in static pressure
APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS St. George / Wyatt / Seagram One-Piece Toilets St. George 1.28 gpf / 4.8 Lpf - Model# D22000C101 Wyatt 1.28 gpf / 4.8 Lpf - Model# D22005C101 Seagram 1.28 gpf / 4.8 Lpf - Model#
More informationUBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6
Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section
More informationMEMOIRS VITREOUS CHINA TOILETS
MEMOIRS VITREOUS CHINA TOILETS BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials, and installation sequences.
More informationWELLWORTH WATERGUARD VITREOUS CHINA SIPHON JET TOILET
WELLWORTH WATERGUARD VITREOUS CHINA SIPHON JET TOILET 1. BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials,
More informationCALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM 1 2 1/AC AC SS SS/CC
CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Adopting Agency BSC SFM HCD DSA OSHPD CSA DPH AGR DWR CA 1 2 1/AC AC SS SS/CC 1 2 3 4 Adopt
More informationUniversity of Rochester October 17, 2008 Brooks Landing Business Center
SECTION 224200 COMMERCIAL PLUMBING FIXTURES PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, equipment and services to perform operations required for the complete installation and related
More informationFrequently Asked Questions
Frequently Asked Questions 1. What is back-siphonage? Back-siphonage is the reversal of normal flow in a system caused by a negative pressure (vacuum or partial vacuum) in the supply piping. 2. What factors
More information2. All necessary storm and sanitary pumps shall be tied into emergency power, and sump levels shall be monitored electronically through the B.A.S.
DIVISION 22 00 00 22 30 00 EQUIPMENT Page 1 of 10 22 30 00 EQUIPMENT 22 01 01 GENERAL REQUIREMENTS General 1. All plumbing shall comply with the B.C. Plumbing Code. 1. Avoid the use of storm pumps and
More informationInternal Use Only INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR ELECTRICAL OR HIGH-DENSITY MAGNETIC ANTI-SCALE OR WATER CONDITIONING APPLIANCE IGC 91-2009 1. PURPOSE 1.1 The purpose
More informationDOMESTIC WATER PACKAGED BOOSTER PUMPS
DIVISION 22 PLUMBING 22 11 16 DOMESTIC WATER PIPING 22 11 19 DOMESTIC WATER PIPING SPECIALTIES 1. To facilitate landscape and other maintenance operations, exterior hose bibs shall be provided at 150 foot
More informationDIMENSIONAL STANDARD FOR M22 THREAD CONNECT COUPLER RECEPTACLES AND PLUG COLLARS FOR PORTABLE PRESSURE WASHERS
PWMA PW203-2014 PWMA Standard DIMENSIONAL STANDARD FOR M22 THREAD CONNECT COUPLER RECEPTACLES AND PLUG COLLARS FOR PORTABLE PRESSURE WASHERS Pressure Washer Manufacturers Association Sponsor: 1300 Sumner
More informationSECTION PLUMBING
SECTION 22 10 00 PLUMBING PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish all labor, material and equipment necessary for the complete installation of the sanitary sewer system (including soil and vent piping),
More informationDESIGN GUIDELINES AND TECHNICAL STANDARDS
DESIGN GUIDELINES AND TECHNICAL STANDARDS Date of Issuance: January 1, 2014 DIVISION 22 PLUMBING SECTION 22 1118 DOMESTIC WATER DISTRIBUTION SYSTEM 1. General: This section outlines general requirements
More informationPORTRAIT LITE VITREOUS CHINA REVERSE TRAP TOILET
PORTRAIT LITE VITREOUS CHINA REVERSE TRAP TOILET BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials, and
More informationLaboratory Evaluation Report for: Barrier Type Floor Drain Trap Seal Protection Devices
American Society of Sanitary Engineering Seal (Certification) Program Laboratory Evaluation Report for: Barrier Type Floor Drain Trap Seal Protection Devices Tested under ASSE Standard 1072 Issued: September,
More informationLAV FCO WCO NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS.
ELECTRIC WATER HEATER SCHEDULE DESIGNATION MODEL MANUFACTURER STORAGE RECOVERY TEMPERATURE LEAVING ELECTRICAL CHARACTERISTICS REMARKS/SPECIAL INSTRUCTIONS NUMBER GALLONS RATE RISE WATER K.W. VOLTAGE PHASE
More informationGENERAL PLUMBING REQUIREMENTS
22 00 00 GENERAL PLUMBING REQUIRMENTS i. 00 00 07 Design Professional Design Process Requirements ii. 00 00 08 Design Professional Documentation Requirements and Deliverables iii. 01 81 00 Facility Performance
More informationMONTECITO FIRE PROTECTION DISTRICT
Section 5a MONTECITO FIRE PROTECTION DISTRICT FIRE PROTECTION PLAN Residential Automatic Fire Sprinkler System Installations I Automatic Fire Sprinkler System Standards 1. Definition and Standard: An automatic
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Fitzgerald 1.28 gpf / 4.8 Lpf 2-Piece Toilet Elongated with Seat - Model# D2205CA101 Round Front with Seat - Model# D2205DA101 Thank you for selecting. To ensure this product
More informationThis Product MasterSpec Section is licensed by AVITRU, LLC to Haws Corporation ("Licensee").
Copyright 2017 by The American Institute of Architects (AIA) Exclusively published and distributed by AVITRU, LLC for the AIA This Product MasterSpec Section is licensed by AVITRU, LLC to Haws Corporation
More informationModels: FM FM WARNING
Installation Stainless Steel Blowout Urinal Models: 923-8000 923-8001 923-8002FM 923-8003FM Table of Contents Overview...2 Pre-Installation Information...3 Installation Instructions...4-7 Cleaning Instructions...7
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS ARCHIVE 1.6 gpf/6 Lpf One-Piece Toilet Model 97920-60 ARCHIVE 1.28 gpf/4.8 Lpf One-Piece Toilet Model 97920-28 CHAPEAU 1.6 gpf / 6 Lpf One-Piece Toilet Model 97820-60 CHAPEAU
More informationSECTION PLUMBING FIXTURES
CSUEB Pioneer Heights Phase r 15410 Page 1 SECTION 15410 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More information1. Division 22 Section "Emergency Plumbing Fixtures." 2. Division 22 Section "Drinking Fountains and Water Coolers."
Page 224000-1 SECTION 224000 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSTROGER HOSPITAL 4 th FLOOR RENOVATIONS
CONTRACT WORK RFP NO. STROGER HOSPITAL 4 th FLOOR RENOVATIONS JOHN H. STROGER, JR. HOSPITAL OF COOK COUNTY 1901 WEST HARRISON STREET CHICAGO, ILLINOIS 60612 VOLUME 3 OF 3 MECHANICAL, PLUMBING, ELECTRICAL
More information2). Crane Co. 4). Kohler Co. 5). Universal-Rundle Corp. Revised September 29, 2017 Commercial Plumbing Fixtures
PART 1: GENERAL A. This Section provides design standards for plumbing fixtures and trim. Certification of compliance with specified ANSI, UL, and ASHRAE Standards will be required, as appropriate, for
More informationFREEDOM RESIDENTIAL CONCEALED PENDENT LEAD FREE SPRINKLER VK4570 (K4.9) TECHNICAL DATA
Page 1 of 5 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Lead Free* Sprinkler VK450 is a small high-sensitivity solder link and lever residential sprinkler designed for installation on concealed
More informationCOUTURE ECO-LITE VITREOUS CHINA REVERSE TRAP TOILETS
COUTURE ECO-LITE VITREOUS CHINA REVERSE TRAP TOILETS BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials,
More informationWELLWORTH /HIGHLINE WITH PEACEKEEPER VITREOUS CHINA TOILET
WELLWORTH /HIGHLINE WITH PEACEKEEPER VITREOUS CHINA TOILET BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials,
More informationPLUMBING FIXTURES CHAPTER 27
CHAPTER 27 PLUMBING FIXTURES SECTION P2701 FIXTURES, FAUCETS AND FIXTURE FITTINGS P2701.1 Quality of fixtures. Plumbing fixtures, faucets and fixture fittings shall be constructed of approved materials,
More informationSECTION FUEL-FIRED DOMESTIC WATER HEATERS
SECTION 22 34 00 FUEL-FIRED DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not
More informationDESIGN STANDARDS SECTION Toilet rooms and utility rooms to have floor drains at lowest point.
PART 1 - GENERAL 1.01 Toilet rooms and utility rooms to have floor drains at lowest point. 1.02 Utilize Exposed Flushometers. 1.03 Utilize wall hung toilet room fixtures. Urinals for handicapped may be
More informationMATERIALS Traps TRAPS. No. IPC IRC Description
MATERIALS Traps TRAPS MAX " MAX 0" No. IPC IRC Description 00. P0.6 00. P0.6 00. P0. 00. () P0.6 Exc. Vertical distance from fixture to the trap weir can not exceed ". Horizontal distance from the fixture
More informationPERSUADETM ORDERING INFORMATION NOTES T01-D INSTALLATION INSTRUCTIONS 3/4.8L TWO-PIECE TOILET 3/4.8L K-3654T-W/K-3654T-CW
PERSUADE TM INSTALLATION INSTRUCTIONS 3/4.8L TWO-PIECE TOILET 3/4.8L K-3654T-W/K-3654T-CW Please read these instructions carefully to familiarize yourself with the required tools, materials, and installation
More informationCRAFTSMAN EXAMINATION, JUNE 2007 PLUMBING ANSWER SCHEDULE
No. 9195 CRAFTSMAN EXAMINATION, JUNE 2007 PLUMBING ANSWER SCHEDULE Plumbers, Gasfitters and Drainlayers Board, 2007. All rights reserved. No part of this publication may be reproduced by any means without
More informationSECTION PLUMBING FIXTURES AND TRIM. A. Types of plumbing fixtures required for the project include the following:
SECTION 15440 PART I - GENERAL 1.01 WORK INCLUDED A. Types of plumbing fixtures required for the project include the following: 1. Water Closets 2. Urinals 3. Lavatories 4. Mop Sink 5. Sinks 6. Electric
More informationA. General: comply with appropriate standards. 1. International Association of Plumbing and Mechanical Officials: IAPMO. 2. California State AB 1953.
SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Water closets. 2. Urinals. 3. Lavatories. 4. Sinks. 5. Service sinks. 6. Electric water coolers. 7. Wash fountains.
More informationSECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS
SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from
More informationREVIVAL LITE VITREOUS CHINA REVERSE TRAP TOILET
REVIVAL LITE VITREOUS CHINA REVERSE TRAP TOILET BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials, and installation
More informationLABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS
SECTION 22 20 00 LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",
More informationFREEDOM RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER VK480 TECHNICAL DATA
Page 1 of 6 1. DESCRIPTION Viking Freedom Residential Concealed Horizontal Sidewall Sprinkler VK480 is a small high-sensitivity solder link and lever residential sprinkler designed for installation on
More informationSpecial Requirements For Health Care Facilities
Chapter 14 Special Requirements For Health Care Facilities 14.1 GENERAL This Chapter applies to special fixtures and systems that occur in health care facilities and to the special plumbing requirements
More informationfreedom residential concealed pendent lead free sprinkler
Page 1 of 6 Telephone: 269-95-9501 Technical Services: 77--56 Fax: 269-1-0 Email: techsvcs@vikingcorp.com 1. DESCRIPTION Viking Freedom Residential Concealed Pendent Lead Free* Sprinkler VK70 is a small
More informationEVALUATION SUBJECT: CAST IRON SOIL PIPE AND FITTINGS EXTRA HEAVY OR SERVICE
ICC-ES Report PMG-1083 Reissued 05/2017 This report is subject to renewal 05/2018 EVALUATION SUBJECT: CAST IRON SOIL PIPE AND FITTINGS EXTRA HEAVY OR SERVICE DIVISION: 22 00 00 PLUMBING SECTION: 22 13
More informationKaress ORDERING INFORMATION NOTES T01-A INSTALLATION INSTRUCTIONS
Karess INSTALLATION INSTRUCTIONS VITREOUS CHINA TWO-PIECE TOILET S-TRAP 305mm K-5331T-S S-TRAP 400mm K-5471T-S Please read these instructions carefully to familiarize yourself with the required tools,
More informationCentral Brass C O M P A N Y. A Division of Pioneer Industries, Inc. Installation Guide
Central Brass C O M P A N Y A Division of Pioneer Industries, Inc. Installation Guide Slow-Close Two Handle Widespread Lavatory Faucet: 3127-AN1 3127-AVN1 3127-DAN1 3127-DAVN1 This product meets the following
More informationICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.
ICP Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A 1 inch diameter faucet, where the inside edge of the spout opening is 2.5 inches away
More informationIPC CODE AND COMMENTARY
2012 IPC CODE AND COMMENTARY 2012 International Plumbing Code Commentary First Printing: March 2012 ISBN: 978-1-60983-070-0 (soft-cover) COPYRIGHT 2012 by INTERNATIONAL CODE COUNCIL, INC. ALL RIGHTS RESERVED.
More informationReview of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings
Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings Reprinted with permission from NFPA 13D Installation of Sprinkler Systems in One- and two-family Dwellings and Manufactured
More informationHWC NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS.
ELECTRIC WATER HEATER SCHEDULE DESIGNATION MODEL MANUFACTURER STORAGE RECOVERY TEMPERATURE LEAVING ELECTRICAL CHARACTERISTICS REMARKS/SPECIAL INSTRUCTIONS NUMBER GALLONS RATE RISE WATER K.W. VOLTAGE PHASE
More informationGENERAL PLUMBING REQUIREMENTS
22 00 00 GENERAL PLUMBING REQUIRMENTS 1. GENERAL A. Related sections: i. 00 00 07 Design Professional Design Process Requirements ii. 00 00 08 Design Professional Documentation Requirements and Deliverables
More informationICC 902/ APSP 902/ SRCC Solar Pool and Spa Heating System Standard
ICC 902/ APSP 902/ SRCC 400-2017 Solar Pool and Spa Heating System Standard American National Standard International Code Council 500 New Jersey Avenue, NW, 6 th Floor Washington, D.C. 20001 Approved October
More informationDIMENSIONAL STANDARD FOR 1/4" QUICK CONNECT COUPLER PLUGS AND SOCKETS FOR PORTABLE PRESSURE WASHERS
PWMA PW201-2014 PWMA Standard DIMENSIONAL STANDARD FOR 1/4" QUICK CONNECT COUPLER PLUGS AND SOCKETS FOR PORTABLE PRESSURE WASHERS Pressure Washer Manufacturers Association Sponsor: 1300 Sumner Avenue Cleveland,
More informationPLUMBING FIXTURES Reserved
CHAPTER 27 PLUMBING FIXTURES Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 395R This page left intentionally blank. 396R 2003 INTERNATIONAL RESIDENTIAL CODE SECTION P2708 SHOWERS P2708.1 General. Shower
More information3/4.8 AERODYNE 3/4.8L CLASS FIVE+
3/4.8 AERODYNE 3/4.8L CLASS FIVE+ INSTALLATION INSTRUCTIONS VITREOUS CHINA SKIRTED TRAPWAY ONE-PIECE TOILET S-TRAP 305mm K-3869T/K-3869T-S S-TRAP 400mm K-4165T/K-4165T-S Please read these instructions
More informationC. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.
SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this
More informationPLUMBING REQUIREMENTS
PLUMBING REQUIREMENTS This handout is a compilation of the standard requirements based on the State Plumbing Code and City Ordinance for projects of this type. This information sheet does not contain all
More informationSECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD
PART 1: GENERAL 1.01 Codes and Standards: A. Plumbing Code Compliance: Comply with applicable portions of National Standard Plumbing Code pertaining to selection and installation of Plumbing materials
More informationSeries 20 Dual Check Backflow Preventers
Series 20 Dual Check Backflow Preventers Excellence Matters Specify It! A Division of Watts Regulator Company 427 North Market Blvd Suite #9 Sacramento, CA 9584 Phone: 96-928-02 Fax: 96-928-9 www.amesfirewater.com
More information8707T Includes seat. 8745T Includes Bowl
PRESQU ILE INSTALLATION INSTRUCTIONS P/S- VITREOUS CHINA P/S-TRAP TOILET S-TRAP 200mm / P-TRAP 180mm K-8707T/K-8707T-S BEFORE YOU BEGIN Please read these instructions carefully to familiarize yourself
More informationARCHERTM ORDERING INFORMATION NOTES T01-C INSTALLATION INSTRUCTIONS VITREOUS CHINA ONE-PIECE TOILET K-3639T/K-3639T-C
ARCHER TM INSTALLATION INSTRUCTIONS VITREOUS CHINA ONE-PIECE TOILET K-3639T/K-3639T-C Please read these instructions carefully to familiarize yourself with the required tools, materials, and installation
More informationINSTANT-FLOW C-MICRO WATER HEATER
WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS (LOW ACTIVATION MODELS) TABLE OF CONTENTS Technical Information..................................... 2 Dimensional Data........................................
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Plumbing Standards
Date Description of Change Pages / Sections Modified ID 8/5/17 Entire document - mgl PART 1 - INTRODUCTION 1.1 This section applies to Plumbing for campus institutional facilities. A. Purpose: Yale University
More informationPage 1 of 7. Replaces Form No. F_ Rev 16.3 (Added 16X22 and 18X20 coverage areas)
Page 1 of 7 1. DESCRIPTION Viking Freedom Residential Concealed Horizontal Sidewall Sprinkler VK490 is a small high-sensitivity solder link and lever residential sprinkler designed for installation on
More informationINSTALLATION INSTRUCTIONS CARE AND MAINTENANCE
INSTALLATION INSTRUCTIONS CARE AND MAINTENANCE Heritage VorMax Right Height Elongated 2-piece Toilet Model 205AA104 Thank you for selecting American Standard - the benchmark of fine quality for over 100
More informationInstallation Instructions
Instructions for Topload Washers Original Instructions Keep These Instructions for Future Reference. CAUTION: Read the instructions before using the machine. (If this machine changes ownership, this manual
More informationCRAFTSMAN EXAMINATION, JUNE 2007 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours
Affix label with Candidate Code Number here. If no label, enter candidate Number if known No. 995 CRAFTSMAN EXAMINATION, JUNE 007 PLUMBING INSTRUCTIONS QUESTION AND ANSWER BOOKLET Time allowed THREE hours
More informationAdvantage Series Bathing System Specifications
Advantage Series Bathing System Specifications 6000 Series 6300 Series 450 Main Street, Somerset, WI 54025 Phone: 715.247.5625 Fax: 715.247.3424 http://www.apollobath.com The information in this manual
More informationCHAPTER 10 TRAPS AND INTERCEPTORS
CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
More informationPort of St Helens SIA Aircraft Hanger Scappoose, OR
Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance
More informationSECTION WET-PIPE SPRINKLER SYSTEMS
SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationFREELANCE ORDERING INFORMATION NOTES T01-D
FREELANCE INSTALLATION INSTRUCTINS P/S VITREOUS CHINA P/S TRAP TOILET S-TRAP 305mm/400mm/P-TRAP 80mm K-7509T/K-7509T-S BEFORE YOU BEGIN Please read these instructions carefully to familiarize yourself
More informationVANTAGE. Installation Manual. Release Date: April 16, 2003 Publication Number: INS Revision Date: January 22, 2015 Revision: E
VANTAGE Installation Manual Release Date: April 16, 2003 Publication Number: 3120031005INS Revision Date: January 22, 2015 Revision: E Visit the Cornelius web site at www.cornelius.com for all your Literature
More informationGARCIA GALUSKA DESOUSA Consulting Engineers
L#58619/Page 1/November 1, 2017 PLUMBING Executive Summary: Presently, the Plumbing Systems serving the building are cold water, hot water, sanitary, waste and vent system, storm drain piping, and natural
More informationCRAFTSMAN EXAMINATION, NOVEMBER 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours
Affix label with Candidate Code Number here. If no label, enter candidate Number if known No. 9195 CRAFTSMAN EXAMINATION, NOVEMBER 2009 PLUMBING INSTRUCTIONS QUESTION AND ANSWER BOOKLET Time allowed THREE
More information