Public Services Building 155 N First Avenue Hillsboro, OR March 2012

Size: px
Start display at page:

Download "Public Services Building 155 N First Avenue Hillsboro, OR March 2012"

Transcription

1 Public Services Building 155 N First Avenue Hillsboro, OR March 2012 Tests and report done by: Joel Klobas Emerging Energy Solutions Technical Director joelk@eeswest.com

2 Contents Introduction... 3 Description of Equipment... 3 Flow Chart of the System and Readings... 4 March 2012 Test... 5 The post measurement test show:... 6 Sub-Cooling... 6 Pre-test Pre-test Post-test... 7 Condenser performance... 8 Pre-test Pre-test Post-test Comparison chiller dt condensing - cooling water Compressor performance Pre-test Post-test Comparison table Nominal Data Rating condition comparison: Conclusions P a g e

3 Introduction The purpose of this chiller analysis is to compare test data from before and after repairs that were made to the system. The first test was performed in May of 2011 indicating the system was low on refrigerant and may have some type of non-condensable (air or nitrogen) mixed with the refrigerant. Between May of 2011 and September 2011 when we conducted our second test the condenser tubes were cleaned on the water side and the filter drier was replaced. During our second test it was evident that the problem of non-condensables remained. March of 2012 repairs were again performed to address the non-condensable issues. The repairs to the system included: Removal of all contaminated refrigerant. Remove old filter driers and installation of new ones. Remove old compressor oil and install new oil. Repair leaks. Evacuation of the system to 40 microns. Charge the system with new R-22 refrigerant to the factory recommendation of 60lbs. While the technician was recovering the old refrigerant it was noted that only 30lbs of refrigerant was removed from the system. The manufacturer s recommended charge of this system is 60lbs. The recovered refrigerant was not sent out to be tested for non-condensables. After all the above repairs were concluded, ClimaCheck was hooked up to the system to verify all recommended changes had been completed correctly. Additionally the final test would indicate the actual savings that were achieved by doing the repairs. The ClimaCheck PA Pro performance analyzer is a data logger that uses a multitude of temperature sensors, pressure transducers, and electrical analyzing equipment which all take readings and measurements that are then converted to data. This data is then collected and imported into a software program. The software then uses thermodynamic laws which make calculations similar to the types of calculations used in a research and development labs. All readings were taken with the ClimaCheck Pa Pro. All conclusions were made by inspection and research of this data using some nominal data supplied by the manufacturer. Description of Equipment The Equipment is a McQuay water cooled chiller built in This chiller is refrigerating a Glycol loop providing cooling to a server room. This system has two refrigerant circuits, one compressor on each circuit, a desuperheater on each circuit, a condenser for each circuit, and a common evaporator cooled by both circuits. The two desuperheaters provide heat for a heating loop in the building and preheating for a potable hot water heater. Water provided to the condensers comes from an evaporative condenser outside controlled by a fan cycle control. Normally the 3 P a g e

4 water inlet temperature is controlled at 74 F; however the sensor was not working during the final test causing the fan on the evaporative condenser to run continuously. Only circuit 1 was tested. There are three test dates noted in this report, May 18 th, October 2011, and March The data collected for these tests was taken on circuit one at full load with the desuperheater loop on. Compressor two never ran during the test, it was forced off. Flow Chart of the System and Readings Single Compressor Flow Chart The above diagram is a flow chart representative of the system tested. The yellow triangles represent where ClimaCheck temperature probes were attached. The blue circle is the low Pressure and the red circle is the high pressure. Pressure transducers were connected to each point. There also was a power meter attached to record voltage and Amperage. 4 P a g e

5 March 2012 Test There should only be a 10 difference between the two Saturated Condensing Temperature Exiting Water Temperature Sub-Cool 18.7 F Adding refrigerant to system System is stable and showing good readings This graph shows the start-up and charging of the system. The last 20 minutes shows very stable operation at full charge. All abnormal unstable data shown indicates times when refrigerant was being added to the system. It is important to point out that the difference between saturated condensing temperature and leaving water temperature of the condenser stayed about the same throughout the charging of the system. This indicates poor heat transfer between the refrigerant and the cooling water in the condenser. 5 P a g e

6 The post measurement test show: Sub-Cooling - During the latest repairs the system was charged to manufacturer s specification of 60 lbs. The system is now operating at a sub-cool of 18.7 F, (shown above). This sub-cool would be expected to be at the high end range of most chillers. No significant increase of dt between water and condensing temperature was shown during charging of the system (graph above). Pre-test 1 Pre-test 1 showed a sub-cool ranging from 13 F to 0 F averaging about 6 F. 6 P a g e

7 Pre-test 2 Pre-test 2 showed a 4.5 F sub-cool averaging almost 4 F. For the entire test the liquid line sight glass was flashing rapidly. You cannot have higher than 0 F sub-cool with a flashing sight glass. This fluctuation is a strong indication of non-condensables in the system. Post-test Post-test showing 19.2 F to 18.6 F of sub-cool. This reading is a little higher than would be expected. This high sub-cool is an indication of poor heat transfer between the refrigerant and the cooling water in the condenser. 7 P a g e

8 Condenser performance - The condenser has a low performance with almost 20 F difference between exiting water and condensing. However the condenser is operating better with the correct refrigerant charge. There is no longer any indication of non-condensables in the refrigeration circuit. 8 P a g e

9 Pre-test 1 dt condensing - cooling water. This is the difference of the saturated condensing temperature and the leaving condenser water (cooling water). There is an 18.6 F average. Pre-test 2 dt condensing - cooling water. This is the difference of the saturated condensing temperature and the leaving condenser water (cooling water). There is a 19.5 F average. 9 P a g e

10 Post-test dt condensing - cooling water. This is the difference of the saturated condensing temperature and the leaving condenser water (cooling water). There is a 19.6 F average. Notice the stability in this graph is much different than the two prior, this is due to the evaporative condenser fan never shutting off due to the bad sensor mentioned earlier. All three graphs show a large difference indicating very poor heat transfer in the condenser. Comparison chiller dt condensing - cooling water Here we see a test done on a very similar chiller the dt condensing - cooling water ranged from 7 F to 10 F. This would be an expected operating range. 10 P a g e

11 Compressor performance - Compressor Isentropic Efficiency of 65-67% is in line with what is expected of a good semi-hermetic compressor (typical range 64-72%) at similar operating condition. Pre-test 2 The isentropic efficiency of the compressor during the pretest is showing 87 96% effeciency. This is immpossible for a reciprocating compresors which is expected to run between 64-72% efficiency. It is clear that noncondensables are present. Post-test 11 P a g e

12 Now the non-condensables have been removed from the system and the isentropic efficeincy is right where you would expect from this 24 year old compressor 65-68%. Comparison table Parameter Pre-test 1 Pre-test 2 Post-test Difference May 18 Sept 9 March 9 Pre-test 2 and post Chilled water in F Chilled water out F Chilled water dt F (12.5%) Evaporation F dt chilled water evaporation F Cooled water in Cooled water out Cooled water dt F (+17%) Condensing F dt condensing - cooling water Power input KW (-4%) The following can be noted as improvements: There are some differences in operation between Pre-test 2 and Post-test: A. Post-test has a lower chilled water inlet temperature of 1.2 F B. Post-test has a lower chilled water exiting temperature of 1.9 F (difference is caused by higher capacity) C. Post-test has lower cooling water of 6.1 F D. Post-test has lower cooling water out temperature of 4.1 F (difference is caused by higher capacity) The above table indicates that the chiller has increased in performance significantly with the non-condensables removed and new refrigerant added to the correct manufacturer specifications. Compared to the first two tests and last test, the condenser performance has increased its performance slightly but is still significantly below where it should be. 12 P a g e

13 Nominal Data WHR040D Selection guidelines (page 15) 1. Ratings may be interpolated for any chilled water temperature between 42 F and 50 F but cannot be extrapolated. 2. Chilled water quantities - Ratings are based on a 10 degree chilled water range and are applicable from a minimum of 8 F to a maximum of 12 F differential between entering and leaving chilled water temperature. 3. Condenser water quantities - Ratings are based on a 10 F rise in condenser water temperature and are applicable from 1 ½ to 4 gpm/ton (20 F to 7.5 F rise) except as limited by pressure drop in Chart 2. Capacity data note that data is given in first table at entering water and in second at exiting water temp with a dt of 10 F e.g. the two first two columns are equivalent and given for a 5 F higher exiting water temperature than listed. The flow is lower than nominal but within range. A lower flow than table will be beneficial for performance when rating tables are based on existing water. 13 P a g e

14 Rating condition comparison: Operating conditions (temperature and flow) is within the given range of the chiller but with lower water temperature than tabulated. Exiting water temp is approx. 5 F below tabled data. Based on extrapolation of table At 5 F higher exiting water temperature the rated EER is 17.6 whereas ClimaCheck measured the EER at 14.5 which is an increased energy consumption of 18%. Extrapolation of table always include an increased uncertainty but it can be noted that 5 F lower exiting water condensing has an estimated impact of an additional 5% increased EER. Conclusions The McQuay Chiller performance improved significantly when the non-condensable gases were recovered and the system was charged with new refrigerant. The capacity has increased % There is a decrease in power consumption of a 4 % This equates to a 15 to 25% performance improvement. However there is still room for improvement in the system. If the condenser was brought to manufacturers specifications there is a possibility of an additional savings of 20%. No data on evaporation or condensing temperatures versus water temperatures was found in manufacturers manual which makes it impossible to - with certainty specify cause of decreased performance to condenser. There are a number of possibilities that could cause pour performance of this condenser: A leak on the condenser water gasket allowing flow to occur between inlet and outlet water before passing through the condenser tubes, (a shortcut). Cavitation of the water circulation pump that is circulating cooled water from the evaporative condenser, (water tower). This is a likely problem due to the design of the water system but is very easily detected as when cavitation occurs you can hear the bubbles being produced in the pump. There was no indication of cavitation while the tests were performed. Air in the water side of the condenser that is trapped. This is unlikely since the water side of the condenser barrel is tubes and the refrigerant is in the barrel. Poor original design. After reading the design specifications of this chiller this is very unlikely A build-up of scale on the inside of the condenser tubes that has not been able to be removed during cleaning causing poor heat transfer between refrigerant and cooling water. 14 P a g e

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Executive Summary. Number of Low Number of High Number of Faults , Number of OK Unit Lower limit Upper limit Air on Model no evap. F Air off evap. F dt air evap. F Executive Summary Evapo. F This is a summary chart for quick reference and view of all the systems tested. Red boxes

More information

Refrigeration System Report March 2017

Refrigeration System Report March 2017 New Seasons Market 7703 SW Nyberg Street Tualatin, OR 97062 Refrigeration System Report March 2017 Commissioning done by: N/A Manufacturer: Contractor: Report published by: Roupen Ohannessian, ClimaCheck

More information

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled

More information

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT EarthLinked TXV Kit Installation Manual for Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT CONTENTS PAGE Pre-Installation 3 Hydronic Water Module Conversion

More information

MASS. MARITIME ACADEMY

MASS. MARITIME ACADEMY MASS. MARITIME ACADEMY REFRIGERATION LAB OUTLINE Rev.3 Fall 2015 Table of Content Page Lab #1: Introduction to refrigeration system components, tools and procedures 1 Lab #2: Familiarization, operation,

More information

Part IV: Flow Side Components Flow Diagram

Part IV: Flow Side Components Flow Diagram Part IV: Flow Side Components Flow Diagram Supply The supply is the outlet of the chiller. This is where cooled coolant exits. The return is the inlet of the chiller. This is where the warm liquid enters.

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou Condensers ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM A. Hadawey, Y. T. Ge, S. A. Tassou 4 7 8 5 3 2 6 1 Produced by: The Centre for Energy and Built Environment

More information

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters Energy Efficiency Through Waste Heat Recovery Heat Recovery Centrifugal Chillers and Templifier Water Heaters Innovative Solutions for Saving Energy McQuay offers two innovative methods of saving energy

More information

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor K.Harshavardhan Reddy, M. Rama Narasimha Reddy, A.VENKATASWAMI, Dr M.YOHAN Abstract: - At first glance, calculating the of any type of compression

More information

Rev B, 9/2/2009. Kodiak Chiller Overview

Rev B, 9/2/2009. Kodiak Chiller Overview 930-0001 Rev B, 9/2/2009 Kodiak Chiller Overview Presentation Outline Phone: 781-933-7300 Lytron Technical Support Contact Information 3 Introduction 4 Part I: Unpacking 5 Part II: Installation 7 Part

More information

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant EarthLinked TXV Kit Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant CONTENTS PAGE Pre-Installation 3 Cased Coil Conversion 4 System Start-Up 17 TXV CCS-410-KIT

More information

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988 Product Improvements for 2017 Todays Objectives Job Site Information Sheets Low Ambient

More information

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd Abstract This paper presents the design approach adopted for the expansion of a large existing

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

Refrigeration/Troubleshooting Manual

Refrigeration/Troubleshooting Manual Refrigeration/Troubleshooting Manual P.O. Box 245 Syracuse, NY 13211 www.roth-america.com 888-266-7684 P/N: 2300100910 Table of Contents: Section 1: Geothermal Refrigeration Circuits Overview... 2 Water-to-Air

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

(Refer Slide Time: 00:00:40 min)

(Refer Slide Time: 00:00:40 min) Refrigeration and Air Conditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 10 Vapour Compression Refrigeration Systems (Refer Slide

More information

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant EarthLinked TXV Kit Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant CONTENTS PAGE Pre-Installation 3 Air Handler Conversion 4 System

More information

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F Temperature Control Units Water & Oil - F Portable Chillers Air & Water-Cooled - 7 F Central Chillers Air & Water-Cooled Packages & Modules - 7 F Pump Tank Stations Chilled or Tower Water - gallons Cooling

More information

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS David Grassl PE Mechanical Engineer Principal Similar to traditional boiler systems, condensing boiler systems have many designs they can operate

More information

Adsorption Chillers Energysmart Green Cooling

Adsorption Chillers Energysmart Green Cooling Adsorption Chillers Energysmart Green Cooling New Partners in innovation Leaders in Dehumidification... Worldwide Power Partner Inc USA www.bryair.com Recover Low Grade Process Waste Heat For Energy Smart

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Refrigerant Mass and Oil Migration During Start-up Transient

Refrigerant Mass and Oil Migration During Start-up Transient Refrigerant Mass and Oil Migration During Start-up Transient Steffen Peuker, Predrag Hrnjak* Department of Mechanical and Industrial Engineering University of Illinois at Urbana-Champaign 1206 West Green

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

Daikin Blueprint: Delivering Hot Water with a Chiller

Daikin Blueprint: Delivering Hot Water with a Chiller Daikin Blueprint: Delivering Hot Water with a Chiller Analyzing the design of heat recovery on air-cooled chillers and the effect it has on building energy consumption By Paul Crisman Daikin Chiller Applications

More information

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved. GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

PL Series Premier Indoor Plenum Coils

PL Series Premier Indoor Plenum Coils IM-PLC-0667392-04 April 2016 PL Series Premier Indoor Plenum Coils Installation Instructions GENERAL ADP evaporator coils are designed for use with condensing units or heat pump units. These instructions

More information

SCA 620C AIR COOLED SCREW CHILLER

SCA 620C AIR COOLED SCREW CHILLER DUNNAIR I N T E R N A T I O N A L L I M I T E D SCA 620C AIR COOLED SCREW CHILLER MV6 CONTROL Refrigerant: R22 Standard NOMINAL CAPACITY 620 kw(r) DUNNAIR INTERNATIONAL LIMITED Subject to change without

More information

VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS. Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign

VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS. Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign Dept of Mechanical & Industrial Engineering 1206 WGreen St Urbana,

More information

ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS

ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS Per the EPA: Retail food refrigeration, or commercial refrigeration, includes equipment designed to store and display chilled

More information

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Material Handling Process Cooling Temperature Control Size Reduction Temperature Control Process Cooling Material Handling Size Reduction GP SERIES Packaged Chillers Precision Comprehensive Engineered

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL RLV-700 REFRIGERANT RECOVERY / RECYCLING UNIT (PATENTED) NATIONAL REFRIGERATION PRODUCTS 985 Wheeler Way Langhorne, PA 19047 (215) 638-8909 FAX (215) 638-9270 REVISED 03-21-2018

More information

Often fellow technicians, co-workers and field personnel CHARGE REFRIGERANT DETERMINING PROPER SYSTEM

Often fellow technicians, co-workers and field personnel CHARGE REFRIGERANT DETERMINING PROPER SYSTEM Image courtesy of Mastercool. DETERMINING PROPER SYSTEM REFRIGERANT CHARGE Troubleshooting refrigerant system issues is one of the toughest jobs HVACR technicians will ever face. BY RICH PERROTTA A wireless

More information

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES The experimental system established in the present study to investigate the transient flow boiling heat transfer and associated bubble characteristics of

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

Energy consumption storage facilities examined in ICE-E

Energy consumption storage facilities examined in ICE-E Energy consumption storage facilities examined in ICE-E August 2012 Edited by Lars Reinholdt Danish Technological Institute = ICE-E Audit report 1 Contents EXECUTIVE SUMMARY 3 INTRODUCTION 4 THE ISSUES

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

Parilla Thermal Storage Project Case Study. May Page 1 of 11

Parilla Thermal Storage Project Case Study. May Page 1 of 11 Parilla Thermal Storage Project Case Study May 2014 Page 1 of 11 BACKGROUND Parilla Premium Potatoes is a large refrigerated storage facility (Figure 1) located in South Australia; the facility consists

More information

Refrigerated Air Dryers

Refrigerated Air Dryers Refrigerated Air Dryers Dual Control and Demand Manager Series 600-3000 scfm Energy Saving Refrigerated Dryers A Choice of Two Because compressed air demand fluctuates in some applications and is relatively

More information

THERMAL ICE STORAGE: Application & Design Guide

THERMAL ICE STORAGE: Application & Design Guide THERMAL ICE STORAGE: Application & Design Guide Table of Contents: 1. Introduction A. History of Thermal Energy Storage B. Operating and Cost Benefits 2. Applications A Fundamental System B. HVAC Cooling

More information

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit

More information

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power energy center Paper Report Summary 210-1 174-2 Fixed and Floating Head Pressure Comparison for Madison Ice Arena Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power July 1998 April,

More information

Comparative Performance of HFO Blends in a Condenser

Comparative Performance of HFO Blends in a Condenser The knowledge hub for refrigeration, air conditioning and heat pumps Nick Atkins MInstR Simon Jones MInstR Gary Bell Comparative Performance of HFO Blends in a Condenser Paper 2 research laboratory tests

More information

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017 Zeta Rev LN HP 10.2 Configured unit accessories 1PS - One user-side pump with tank LN - Low noise RG - Condensation control with fan speed regulator CSP - Set point compensation depending on external air

More information

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Marco Alexandre Onofre Dias This paper presents a model that was implemented

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City) BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION Business Name Site physical address (Street, Suburb, City) Nature of site / business operation Electricity Supplier Power factor

More information

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler Author: Volodymyr Voloshchuk Vl.volodya@gmail.com Introduction In

More information

EarthLinked SCW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked SCW Series Compressor Unit R-410A Quik-Start Instructions EarthLinked SCW Series Compressor Unit R-410A Quik-Start Instructions CONTENTS PAGE Pre-Installation 3 Placement & Mechanical Information 6 System Application Options 12 Antifreeze Protection 13 Electrical

More information

MODEL URS-1: FACTORY RETROFIT PROGRAM

MODEL URS-1: FACTORY RETROFIT PROGRAM MODEL URS-1: FACTORY RETROFIT PROGRAM The USR-1 unit has gone through extensive testing in order to attain maximum performance. It has been determined that in order to set the unit for all weather operation,

More information

A/C Cooling Load calculation and measurement

A/C Cooling Load calculation and measurement Testo Inc. 40 White Lake Rd. Sparta NJ 07871 (800) 227-0729 A/C Cooling Load calculation and measurement When we talk about sizing an air conditioning appliance (tons of cooling, BTU/h or KW), we are specifying

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Chiller units and air-water heat pumps RANGE OPERATING LIMITS

Chiller units and air-water heat pumps RANGE OPERATING LIMITS Chiller units and air-water heat pumps Cooling capacity: Heating capacity: 6, to 6,6 kw 8, to 69,4 kw ENVIRONMENTALLY FRIENDLY HFC R407C PROTECTION DE L'ENVIRONNEMENT Silent and compact design Air-conditioning

More information

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)

More information

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

terminal units only provide sensible cooling, a separate dehumidification system is usually needed. providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can

More information

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET

More information

HEAT EXCHANGERS Maximize Thermal Efficiency with LaZerWeld Plate Heat Exchangers. For Industrial Refrigeration

HEAT EXCHANGERS Maximize Thermal Efficiency with LaZerWeld Plate Heat Exchangers. For Industrial Refrigeration HEAT EXCHANGERS Maximize Thermal Efficiency with LaZerWeld Plate Heat Exchangers For Industrial Refrigeration HEAT EXCHANGERS Frick Quality Heat Exchanger Solutions Proven Technology LaZerWeld Plate Heat

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Installation, and Maintenance Manual IMM WGZ-2 Group: Chiller Part Number: 331374401 Effective: October 2005 Supercedes: IOMM WGZ-1 Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 120AW, Packaged

More information

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS ENERGY CONSUMPTION HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS Introduction Those in charge of specifying and purchasing equipment for industrial compressed air systems have many

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

Refrigerated & Desiccant Compressed Air Dryer Product Selector

Refrigerated & Desiccant Compressed Air Dryer Product Selector Refrigerated & Desiccant Compressed Air Dryer Product Selector ASD and HTD Series Refrigerated Dryer Units DD Series Desiccant Dryer Units Service Parts For faster service and to avoid errors, please use

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

Refrigerant changeover guidelines

Refrigerant changeover guidelines Refrigerant changeover guidelines HCFC R-22 to HFC R-407A/F, R-448A or R-449A for medium and low temperature applications HCFC R-22 to HFC R-407C for high, medium and low temperature applications HCFC

More information

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS ORTEC Compressed Air, Gas & Fluid Technologies HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS Energy Lean Planet Green Cycling and Non-Cycling Design Energy Efficient s Fluctuating and Intermittent Loads Capacity,0

More information

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO 06-10616. File name: URS-1 Service Manual up to 06-10616 Last revised: Jan. 30th 2009 TROUBLESHOOTING AND SERVICE GUIDE: The following is intended as

More information

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc. The Refrigeration Cycle Jerry Cohen President Jacco & Assoc. Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful Harnessing Energy Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful Vapor Power Cycle The vast majority of electrical generating plants are variations of vapor power

More information

Closing the Loop What s best for your system?

Closing the Loop What s best for your system? What s best for your system? Heat Rejection System Design Choices Consulting Engineers have two choices when designing a heat rejection system whether the cooling loop is open to the atmosphere or a closed

More information

ARV.

ARV. ARV www.coldinnovation.it 1 INDEX Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R134a...pag. 5 Semi-hermetic screw compressor...pag.

More information

Refrigerant Type Heat Recovery Unit for Temperature & Humidity Control Room

Refrigerant Type Heat Recovery Unit for Temperature & Humidity Control Room Legend of quality Energy saving products. Refrigerant Type Heat Recovery Unit for Temperature & Humidity Control Room ENERCOV, The best solution to create room environment controls such as humidity, temperature,

More information

Liebert CRV Warranty Inspection Check Sheet

Liebert CRV Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Date of Installation

More information

Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM. 13 th May 2017

Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM. 13 th May 2017 Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM 13 th May 2017 0 1 Portion of Inverter Residential Air Conditioners Worldwide (2015) and in Vietnam (Mar 2017) What is "Inverter"?

More information

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration

More information

USING THE P-T CARD AS A SERVICE TOOL

USING THE P-T CARD AS A SERVICE TOOL Service Application Manual SAM Chapter 620-115 Section 2 USING THE P-T CARD AS A SERVICE TOOL Reprinted with permission from Sporlan Division, Parker Hannifin Corporation INTRODUCTION Manufacturers of

More information

SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION

SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION UNIT OBJECTIVES After studying this unit, the reader should be able to Describe a standing pressure test. Choose a leak detector

More information

<<Date>> <<Recipient>> <<Address>>

<<Date>> <<Recipient>> <<Address>> Dear : M&V Plan for Frank s Market Our Measurement and Verification (M&V) plan for the second Refrigeration System Redesign of Frank s Market is attached

More information

DIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.)

DIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.) : new refrigerant replacement for R-22 with low Global Warming Potential (GWP). Performance comparison with six existing refrigerants. CARRIED OUT BY DIRA S.L. (Desenvolupament, Investigació i Recerca

More information

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions CONTENTS PAGE Pre-Installation 3 Placement & Mechanical Information 4 System Application Options 10 Antifreeze Protection 14 Electrical

More information

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s) Electrical Problems Fuse(s) blow or circuit breaker trips Does the unit use circuit breakers or fuses? Fuse(s) Circuit breakers Are the fuses dual element time delay? Is the circuit breaker HACR rated?

More information

RDT Refrigeration Book

RDT Refrigeration Book RDT Refrigeration Book Indoor / Outdoor Air-Cooled Systems Indoor Air-Cooled Systems 1. Shorter line runs. 2. Systems located off roof or dock space. 3. Weather covers are not required (saves cost). 4.

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

WXC R134a. Nominal Cooling Capacity from 224 to 692kW

WXC R134a. Nominal Cooling Capacity from 224 to 692kW WXC R134a Nominal Cooling Capacity from 224 to 692kW FEATURES AND BENEFITS Range of 12 models. Higher capacity and higher EER from the same compressor. High EER, low sound power level and high reliability.

More information

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A

More information

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore

More information

Modelling the Performance of a Diffusion Absorption Refrigeration System

Modelling the Performance of a Diffusion Absorption Refrigeration System Modelling the Performance of a Diffusion Absorption Refrigeration System Noman Yousuf 1, Etienne Biteau 2, Timothy Anderson 1, Michael Gschwendtner 1 and Roy Nates 1 1 School of Engineering, Auckland University

More information

A Treatise on Liquid Subcooling

A Treatise on Liquid Subcooling A Treatise on Liquid Subcooling While the subject of this article is Liquid Refrigerant Subcooling, its affect on the operation of the thermostatic expansion valve (TEV), and ultimately on system performance

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Low Global Warming Refrigerants For Commercial Refrigeration Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel

More information

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

HYDROCIAT LW R407C. Water cooled chillers USE RANGE Screw compressors CIAT dry direct expansion shell and tubes evaporator HPS equipment (High Power System) cooling or heating Heat recovery ENVIRONMENTALLY HFC R407C PROTECTION DE FRIENDLY L'ENVIRONNEMENT

More information