1 Plate-and-frame free cooling Plate-and-frame heat exchangers are sometimes referred to as waterside economizers. One way to reduce the energy consumption of a chilled-water plant is to precool the water in the chilled-water loop before it enters the evaporator. This can be accomplished by piping a plate-and-frame heat exchanger into the chilled-water and condenser-water loops. Using the piping arrangement shown in Figure 3 9, free cooling and mechanical cooling occur simultaneously. (Plate-and-frame free cooling can be achieved with other piping arrangements, depending on the operating characteristics desired.) Figure 3 9 Chilled-water plant with plate-and-frame free cooling When the ambient wet-bulb temperature is low enough, the heat exchanger transfers heat from the chilled water returning to the evaporator to the condenser water returning from the cooling tower. Precooling the chilled water before it enters the evaporator lessens the cooling burden, reducing the energy that the chiller uses. Application considerations Adding a heat exchanger to provide free cooling increases the initial cost of the system. The additional pressure loss also raises pumping costs. The ambient wet-bulb temperature determines the free-cooling capacity of the heat exchanger cooling capacity diminishes as the ambient wet-bulb temperature rises. Free cooling is only Plate-and-frame free cooling 3 43
2 available when the ambient wet-bulb (AWB) temperature is less than the design return chilled-water (DRCW) temperature plus the heat exchanger approach (HEA) temperature, that is, AWB DRCW + HEA The cooling tower must be designed for winter operation. Water entering the condenser must be maintained within the temperature limits specified by the chiller manufacturer. Related reading Multiple-Chiller-System Design and Control Applications Engineering Manual (Trane literature number SYS-APM001-EN) Chilled Water Systems Air Conditioning Clinic, one of the systems series (Trane literature number TRG-TRC016-EN) A New Era of Free Cooling, Engineers Newsletter (volume 20, number 3) Sample scenario A chilled-water plant includes a three-stage centrifugal chiller and a plate-and-frame heat exchanger that has a 3 F approach. The following illustrations demonstrate how to model this plant. Cooling-equipment definitions in the TRACE 700 library include an approach temperature for a plate-andframe heat exchanger the default is 3 F. To model a different approach temperature, use the Library/ Template Editors program to copy and modify an existing piece of cooling equipment. Note: TRACE 700 assumes that the capacity of the heat exchanger equals the cooling capacity of the chiller to which it is assigned. then type the new approach temperature here. To change the approach temperature, choose a plateand-frame type here 3 44 TRACE 700 User s Manual CDS-PRM001-EN Plate-and-frame free cooling
3 To model a cooling plant that includes a plate-andframe heat exchanger: 1 Select the desired equipment type. For this example, pick one of the centrifugal chillers from the water-cooled chiller category. 2 Enter the full-load consumption for each pump. 3 Click Controls and choose one of the plate-and-frame options as the free cooling type. For a cooling plant with multiple chillers, be sure to specify the free-cooling option for each chiller. Plate & frame series uses the heat exchanger to supplement mechanical cooling. Plate & frame uses the heat exchanger instead of mechanical cooling, but only if ambient conditions permit. The heat exchanger only operates if it can satisfy the entire cooling load. Plate-and-frame free cooling 3 45
4 Refrigerant-migration free cooling As the name implies, refrigerant-migration free cooling is based on the principle that refrigerant migrates to the coldest point in a refrigeration circuit. Under favorable conditions, this energysaving option for centrifugal chillers can provide up to 40 percent of the design cooling capacity of the chiller. When condenser water returning from the cooling tower is colder than the water in the chilled-water loop, as depicted in Figure 3 10, the refrigerant pressure in the condenser is less than that in the evaporator. This difference in pressure drives refrigerant vapor from the evaporator to the condenser, where it liquefies. With the help of gravity, the liquid refrigerant flows back to the evaporator. The non-mechanical refrigeration cycle is sustained, providing free cooling, as long as the differential refrigerant pressure is sufficient to drive vapor from the evaporator to the condenser. Figure 3 10 Refrigerant-migration free cooling Application considerations Mechanical cooling and refrigerant-migration free cooling cannot occur simultaneously. This type of free cooling can only be used if the cooling capacity of the tower water is sufficient to meet the entire building load TRACE 700 User s Manual CDS-PRM001-EN Refrigerant-migration free cooling
5 Little, if any, free-cooling capacity is available when the ambient wet-bulb temperature exceeds 50 F. Unlike the compressor (which is off), accessories such as pumps and cooling-tower fans continue to operate in the conventional manner during the free-cooling mode. The cooling tower must be designed for winter operation. Related reading Chilled Water Systems Air Conditioning Clinic, one of the systems series (Trane literature number TRG-TRC016-EN) Sample scenario A water-cooled centrifugal chiller is equipped for refrigerantmigration free cooling. When ambient conditions permit, free cooling satisfies up to 40 percent of the design capacity of the chiller. To model a chiller with refrigerant-migration free cooling: 1 Add the appropriate equipment category to the cooling plant. For this example, select watercooled chiller. (This is equivalent to dragging an equipment icon to a plant on the Configuration tab.) 2 Replace the default equipment tag with a more descriptive name, if desired. 3 Select the desired equipment type and fullload consumption for each pump. 4 Click Controls and choose the appropriate option from the list of free cooling types (in this case, refrigerant migration). If refrigerant-migration free cooling cannot satisfy the entire load, then mechanical cooling is used instead. Refrigerant-migration free cooling 3 47
6 Strainer-cycle free cooling Like other methods of free cooling for chillers, strainer-cycle free cooling acts as a waterside economizer that reduces the amount of energy consumed to produce chilled water. In this case, the source of cooling is condenser water returning from the cooling tower. Figure 3 11 illustrates a typical strainer-cycle piping arrangement that provides free cooling. When the ambient wet-bulb temperature is cold enough, the tower water is valved around the chiller and directly into the chilled-water loop. A filter is positioned upstream of the valve to strain the condenser water before it enters the chilled-water loop, resulting in the name given to this method of free cooling. Figure 3 11 Piping arrangement for strainer-cycle free cooling Application considerations Pumping cooling-tower water throughout the entire chilled-water loop increases the risk of corrosion and fouling. Water treatment, though costly, can help mitigate this risk. Free cooling is only available if the leaving-tower water can satisfy the entire cooling load, limiting the effectiveness of this option. Ambient wet-bulb temperature determines the amount of freecooling capacity available from the strainer cycle cooling capacity diminishes as the ambient wet-bulb temperature rises TRACE 700 User s Manual CDS-PRM001-EN Strainer-cycle free cooling
7 The cooling tower must be designed for winter operation. Sample scenario A chilled-water plant, which includes a water-cooled centrifugal chiller, is piped to provide strainer-cycle free cooling. After adding a watercooled chiller to the cooling plant: 1 Choose the appropriate equipment type (a centrifugal chiller for this example). 2 Specify the full-load consumption for each pump. 3 Click Controls and choose strainer cycle from the list of free cooling types. Strainer-cycle free cooling occurs at the plant level. If the cooling plant includes multiple chillers, repeat this step for each chiller. If strainer-cycle free cooling cannot satisfy the entire load, then mechanical cooling is used instead. Strainer-cycle free cooling 3 49
Hello, my name is Sarah Hilden and I am a Marketing Engineer in the C.D.S. group at Trane.
Slide 1 TRACE 700 Waterside Economizers Hello, my name is Sarah Hilden and I am a Marketing Engineer in the C.D.S. group at Trane. Today, we will be going over how to model waterside economizers in TRACE
More informationSupply air temperature reset
is a control scheme that allows an airside system to modulate the supply air temperature based on outside air temperature, worst-case room demand, or a combination of the two. When enabled, the temperature
More informationDirect and indirect evaporative cooling
Using the evaporative process to precool the supply air stream can reduce the energy consumption of mechanical cooling equipment. Two methods of evaporative cooling exist: direct and indirect. The effectiveness
More informationterminal units only provide sensible cooling, a separate dehumidification system is usually needed.
providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can
More informationTRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE.
Slide 1 TRACE 700 Chiller Sequencing and Controls Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE. Today, we will be talking about the Plant Sequencing and Controls
More informationAir Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN
Air Conditioning Clinic Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Absorption Water Chillers One of the Equipment Series A publication of The Trane Company Worldwide Applied Systems
More informationChilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.
TRACE 700 incorporates two chilled beam strategies: passive and active. Passive chilled beams consist of a fin-and-tube cooling coil, contained in a housing (or casing), suspended from the ceiling. Chilled
More informationMethod to test HVAC equipment at part load conditions
IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking
More informationAC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT
AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT Central Chiller Plant (with Cooling Tower and Chilled Water distribution) The other AC configuration is called a Chilled Water or Larger Cooler system. It
More informationAir Conditioning Clinic
Air Conditioning Clinic Ice Storage Systems One of the Systems Series August 2012 TRG-TRC019-EN Ice Storage Systems One of the Systems Series A publication of Trane Preface Ice Storage Systems A Trane
More informationFor an administrative fee of $9.97, you can get an un-locked, printable version of this book.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of
More informationEnergy Recovery Ventilation
Published on Business Energy Advisor (https://oncor.bizenergyadvisor.com) Home > Energy Recovery Ventilation Energy Recovery Ventilation Proper ventilation is essential for maintaining good indoor-air
More informationSales Bulletin #VRV061
Sales Bulletin #VRV061 Date: April 1 st, 2013 To: Subject: Daikin AC Sales, Service, and Distribution VRV Libraries for Trane TRACE Modeling Daikin AC is pleased to announce the availability of custom
More informationDehumidifying with Dedicated Outdoor Air
Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,
More informationGeneral HVAC Recommendations
General HVAC Recommendations DESIGN GUIDELINES FOR ENERGY EFFICIENT HVAC SYSTEMS Thank you for your interest in energy efficiency! Energy efficient heating, ventilation, and air conditioning (HVAC) equipment
More informationBRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application
1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights
More informationNew Features. IES Virtual Environment 6.4
New Features IES Virtual Environment Contents New Features... 1 1 Tabular Room Data editing for thermal properties... 3 2 ApacheHVAC... 4 3 Alternate system schedules: enhancements... 17 4 BREEAM Navigator...
More informationDISTRIBUTION SYSTEMS. Water Piping and Pumps
DISTRIBUTION SYSTEMS Water Piping and Pumps Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are targeted
More informationMultiple-Chiller-System Design and Control
Applications Engineering Manual Multiple-Chiller-System Design and Control SYS-APM001-EN (March 2001) Multiple-Chiller-System Design and Control Mick Schwedler, applications engineer Ann Yates, information
More informationCONTENTS. B. System Design and Performance Requirements
15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationCascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:
Case-16 Cascade Refrigeration System for LPG Subcooling Copy Right By: Thomas T.S. Wan ( ) Mar. 28, 2003 All Rights Reserved Case Background: This is a case of using a cascade refrigeration system to subcool
More informationCold Weather Operation Of Cooling Towers
This article was published in ASHRAE Journal, March 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
More informationGEOTHERMAL DESIGN GUIDE
GEOTHERMAL DESIGN GUIDE BENEFITS OF THE BULLDOG SYSTEM CGC Version CGC Group of Companies Incorporated 2018 CONTENTS INTRODUCTION... 2 CHALLENGES FACING CONVENTIONAL GSHP SYSTEMS... 3 FACTORS WHICH IMPACTS
More informationA Career that will take you to heights you never imagined!
Air-Conditioning Automation systems Boiler systems Chilled water systems Commissioning Electrical Electronics Graphic design Green technologies Information technology Networking Programing Refrigeration
More informationSECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower
SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal
More informationMaintain. a TOWER of POWER. Part One How to. Don t let out of site, out of mind prevent you from keeping cooling towers running efficiently
Part One How to Maintain a TOWER of POWER Don t let out of site, out of mind prevent you from keeping cooling towers running efficiently BY GLENN A. BABCOCK The cooling tower is often the forgotten component
More informationApacheHVAC in VE 2012
ApacheHVAC in VE 2012 Cooling tower loop Condenser water loop Electric water cooled chiller Chilled water loop Open cooling tower Towb L T 1 T lct V c Compressor T let V e Cooling tower loop pump Water-to-water
More informationRSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs
Lesson 1 - Basic Heat Pump Theory (Part 1) Describe the basic operation of a heat pump. Explain the function of various heat pump controls. Interpret the wiring diagrams and performance data provided by
More informationSeries. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost
LL Chillers and Outdoor Mechanical Rooms Air-Cooled Features: Air-cooled condenser chillers with capacities from 35-345 tons Evaporative-cooled condenser chillers with capacities from 35-540 tons Variable
More informationNirvana Cycling Refrigerated Dryers
Nirvana Cycling Refrigerated Dryers Nirvana Cycling Refrigerated Dryers Ingersoll Rand s Nirvana Cycling Refrigerated Dryer provides reliability like no other dryer in its class: reliability that you can
More informationKawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto
Kawasaki centrifugal chiller using water as a refrigerant Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto Contents 1. Introduction of MiZTURBO 2. Study of CO 2 emissions
More informationIntroduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN
Introduction to HVAC Agenda Psychrometrics Human Comfort Heat Transfer Refrigeration Cycle HVAC Terminology HVAC Systems Introduction to HVAC Psychrometrics 2000 TRG-TRC002-EN Properties of Air Dry-bulb
More informationBASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)
BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION Business Name Site physical address (Street, Suburb, City) Nature of site / business operation Electricity Supplier Power factor
More informationBy Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE
By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE T he advent of the small scroll or screw chiller, capable of producing condenser water as high as 140
More informationHow about Savings in Time, Money, Energy and Longer Life?
Chapter 17: The Value of Maintaining Evaporative Cooling Equipment 97 The Value 17 of Maintaining Evaporative Cooling Equipment 1. Cooling Tower Maintenance and Upgrades... What s in it for You? How about
More informationRefrigeration System Overview. ASTI 32 Hour Managing Ammonia Course September 27 30, 2016
Refrigeration System Overview ASTI 32 Hour Managing Ammonia Course September 27 30, 2016 A refrigeration system is a mechanical heat transport system. The system absorbs heat energy from an area it is
More informationTechnical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:
Refrigeration Systems Theoretical hours: 2 Practical hours: 2 Units: 6 COOLING TOWERS First 10 minutes: review the last lecture. Then explain the new lecture, solve an example. Last 10 minutes review the
More informationBASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation
INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded
More informationHow to Cut Chiller Energy Costs by 30%
How to Cut Chiller Energy Costs by 30% Pre-packaged retrofit cuts centrifugal compressor chiller energy costs by 30% while reducing required maintenance and extending operating life at Duke Realty Corporation
More informationPartial Load Performance Of Refrigeration System
Chapter 11 Partial Load Performance Of Refrigeration System Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Hot Gas Bypass & Liquid Injection: When the compressor is under surge condition,
More informationClimate control precision in Hi-tech environments Jupiter and Mercury Close Control Units
Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units Precision control from the total provide Uncompromised precision More than ever data centers, server rooms, and
More informationIt:ill:~~~=~:~in~1 FIGURE 1 HOW AIR VOLUME IS RECOVERED BY AN ADAMS REHEAT SYSTEM
Compressed air is both hot and laden with moisture coming from the air compressor. It needs to be cooled and dried, and then reheated so it can be used in the manufacturing process. One traditional method
More informationAPS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017
APS Chiller Seminar Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017 Agenda for today Refrigeration Cycle Chiller Types and Refrigerants Compressor Styles Chilled Water Pumping Systems
More informationHVAC Clinic. Helical Rotary & Centrifugal Water Chillers
HVAC Clinic Helical Rotary & Centrifugal Water Chillers Table Of Contents Introduction... 3 Chiller Types... 3 Chiller Components... 4 Refrigeration Cycle... 15 Application Considerations... 19 Introduction
More informationThe Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.
The Refrigeration Cycle Jerry Cohen President Jacco & Assoc. Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative
More informationHVAC Water chiller selection and optimisation of operation
HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water
More informationTHERMOSYS 4.3. Getting Started Guide
THERMOSYS 4.3 Getting Started Guide February 2016 Table of Contents 1 Installation and File Organization... 3 2 THERMOSYS by Example... 4 2.1 THERMOSYS Component Descriptions... 5 2.1.1 Compressor... 6
More informationA. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.
15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional
More informationA. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.
15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional
More informationThe Book of AERMEC NRL Sequence of Operation
The Book of AERMEC NRL Sequence of Operation Heating and cooling operation. 2 Sequence of operation Aermec air to water chiller/heat pump use Hydronic s in conjunction with refrigerant to provide heating
More informationSECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller:
SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC). 3. 15711 - Induced Draft Cooling Tower. B.
More informationTC-5231 Series, TC-5232, & TC-5241 Series
TC-5231 Series, TC-5232, & TC-5241 Series Low Temperature Thermostats General Instructions Application The TC-5231, TC-5232, and TC-5241 low temperature thermostats are used to control temperature in air
More informationAppendix 13. Categories of Cooling and Heating systems
EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01
More informationWater-cooled chillers with High Speed Centrifugal Compressors
Water-cooled chillers with High Speed Centrifugal Compressors Refrigerant R134a 190-760 (395 to 2660 kw) Refrigerant R1234ze 135 G - 505 G (310 to 1820 kw) Table of Contents Introduction...3 Features and
More informationHVAC - Central System Thermal Storage
HVAC - Central System Thermal Storage General Thermal storage is a cost saving technique, and in some cases, energy saving technology. Commercial cooling can account for as much as 40% of peak demand on
More informationEnergy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters
Energy Efficiency Through Waste Heat Recovery Heat Recovery Centrifugal Chillers and Templifier Water Heaters Innovative Solutions for Saving Energy McQuay offers two innovative methods of saving energy
More informationGP SERIES Packaged Chillers
Material Handling Process Cooling Temperature Control Size Reduction Temperature Control Process Cooling Material Handling Size Reduction GP SERIES Packaged Chillers Precision Comprehensive Engineered
More informationEvaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study
www.amec.com Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study DISCUSSION TOPICS Brief Overview of Air-Cooled and Evaporative-Cooled Condenser Technologies Pros and Cons Scope and Results
More informationDescription of All Alternatives Considered-
Description of All Alternatives Considered- Energy efficiency is an area where the Tubman design can be improved. The design heating load is 1807.8 MBH and the design cooling load is 1702.2 MBH or 142
More informationWater-Cooled Dual Compressor Screw Chiller
Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,
More informationAIR CONDITIONER PERFORMANCE RATING
HPRATE V5.1 AIR CONDITIONER PERFORMANCE RATING by G.L. Morrison MechLab The University of New South Wales.EDU.AU September 2012 Version 5.1 HPRATE 5 Air Conditioner Performance Rating 1 HPRATE AIR CONDITIONER
More information100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION
100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationSECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower
SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B.
More informationPDHonline Course A127 (4 PDH) Evaporative Cooling. Instructor: George E. Thomas, PE. PDH Online PDH Center
PDHonline Course A127 (4 PDH) Evaporative Cooling Instructor: George E. Thomas, PE 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
More informationChilled Water system
Chilled Water system Introduction For large installations the Condenser, Evaporator, Compressor and Expansion device can be purchased as a package unit, known as a Chiller. The usual package consists of
More information60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES
60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,
More informationAPPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps
APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual Suggestions for the hydraulic integration of chillers and heat pumps Table of Contents From practical experience, for your practical needs...
More informationMicroTech Series 200 Centrifugal Chiller
Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History
More informationTrane CDQ Desiccant Dehumidification
Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features
More informationChiller Plant Design. Julian R. de Bullet President debullet Consulting
Chiller Plant Design Julian R. de Bullet President debullet Consulting 703-483-0179 julian@debullet.com This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer ASHRAE
More informationNEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80
NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80 Carrier Software Systems Carrier Corporation Syracuse, New York rev October 10, 2013 Copyright 2013 Carrier Corporation, All Rights Reserved Page
More informationPACKAGED AIR COOLED Product Data Catalog
PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES
More informationJune 2001 / BULLETIN Way Valves. The right solenoid valve for any job.
June 01 / BULLETIN - 3-Way Valves The right solenoid valve for any job. Page 2 / Bulletin - Advantages Sporlan 3-Way Valves 3-Way Pilot eliminates costly high- to low-side leaks. "B" reduces total installed
More informationEngineering Bulletin Rev B. Contents. Piping Arrangements for Heat Pump Water Heating Systems
Engineering Bulletin 940126-0003 Rev B Piping Arrangements for Heat Pump Water Heating Systems Contents 1. INTRODUCTION... 0 2. WATER PIPING... 0 3. HEAT PUMP WATER HEATER PIPING... 1 4. RINGMAIN (RECIRCULATING
More informationTechnical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1
Technical Training Associates Presents Commercial Refrigeration Equipment Servicing Part 1 By Jim Johnson A Practical Approach To The Fundamentals Of Walk-Ins, Reach-In and, Display Cases: Restaurant,
More informationREFRIGERATION CYCLES
REFRIGERATION CYCLES Carnot Cycle We start discussing the well-known Carnot cycle in its refrigeration mode. Figure 1: Carnot Cycle In this cycle we define the coefficient of performance as follows: COP
More informationREPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop
Energy-Savings Strategies for Rooftop VAV Systems Occupied set-point temperature Unoccupied set-point temperature Rooftop variable-air-volume (VAV) s are used to provide comfort in a wide range of building
More informationClosed Circuit Cooling Towers
Closed Circuit Cooling Towers Overview Closed circuit cooling towers provide evaporative cooling for many types of systems, and the specific application will largely determine which BAC Closed Circuit
More informationAppendix A. Glossary of Common Terms
Glossary of Common Terms Glossary of Common Terms Absorption chiller A refrigeration machine using heat as the power input to generate chilled water. Adjustable speed drive A means of changing the speed
More informationLife-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power
energy center Paper Report Summary 210-1 174-2 Fixed and Floating Head Pressure Comparison for Madison Ice Arena Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power July 1998 April,
More informationFORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST
FORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST AHRI CERTIFICATION PROGRAM FOR AIR-COOLED WATER-CHILLING PACKAGES USING THE VAPOR COMPRESSION CYCLE ACCL Participant: Date of Test: Witness Test
More informationMicroTech Series-200 Flooded Screw Chiller
Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D
More informationAE October 1965 Reformatted October Hot Gas Bypass Control Systems
Hot Gas Bypass Control Systems AE21-1160 AE21-1160 October 1965 Reformatted October 2010 On many refrigeration and air conditioning systems, the refrigeration load will vary over a wide range. This may
More informationModular Chiller Systems. Application Guide
Modular Chiller Systems Application Guide Table of Contents Introduction.... 1 References/Nomenclature Conventions... 2 Terms & Definitions.... 2 Module Size Selection...3 Water Source, Cooling Only and
More information(12) United States Patent
US008011 196B2 (12) United States Patent Eber et al. (54) REFRIGERANT CONTROL OF A HEATRECOVERY CHILLER (75) Inventors: Alan Hv Eber, La Crosse, WI (US); Steven J. Pitts, LaCrescent, MN (US); Brian T.
More informationFans and Pumps I. Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong
MEBS6008 Environmental Services II http://www.mech.hku.hk/bse/mebs6008/ Fans and Pumps I Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail: cmhui@hku.hk Sep 2012
More informationSERVICE ASSISTANT OVERVIEW FDSI Online Training
Author: Dale T. Rossi Online Editor: Zachary Williams SERVICE ASSISTANT OVERVIEW FDSI Online Training May 5, 2009 Table Service Assistant Description... 2 Installing the Main Unit... 3 Ambient Temperature...
More informationCase 13 Food Storage & Processing Center
Case 13 Food Storage & Processing Center Copy Right By: Thomas T.S. Wan ( ) Feb. 2, 2002 All Rights Reserved Case Background: The refrigeration system is for a food processing and storage facility. The
More informationSPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE
SPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE www.addison-hvac.com Creating a New Project 1. Open the ACE Interface within the web browser. ACE performs best using the Google Chrome browser. Do not use
More informationAPPA Institute for Facilities Management. Energy & Utilities Cooling Production (316) Purpose of Today s Presentation. Agenda
APPA Institute for Facilities Management Energy & Utilities Cooling Production (316) Mark St. Onge, EFP 1 Purpose of Today s Presentation To provide a broad understanding of central cooling production
More informationLenntech. Tel Fax
Lenntech info@lenntech.com Tel. +31-152-610-900 www.lenntech.com Fax. +31-152-616-289 MC Fluid Cooler Unmatched reliability Heavy-duty construction, high performance design and our five-year mechanical
More informationAIR TO AIR HEAT EXCHANGERS
AIR TO AIR HEAT EXCHANGERS HEAT PIPE TECHNOLOGY CLOSED LOOP DESIGN AVAILABLE IN 120, 230, 24VDC & 48VDC NEMA TYPE 12, 4 AND 4X UL LISTED FOR STANDARD AND HAZARDOUS LOCATIONS A2A SERIES AIR TO AIR HEAT
More informationAPOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller
Point Map Rev. 3, February, 2002 Systems Integration APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller Table 1. Series 200 Centrifugal Chiller. Point Type Range/Units 01
More informationTHERMOSTATIC EXPANSION VALVES Part 1
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 THERMOSTATIC EXPANSION VALVES Part 1 Revised by Loren Shuck, CMS INTRODUCTION The thermostatic expansion valve (frequently
More informationTHE PRODUCTS YOU NEED. THE QUALITY YOU WANT. THE INNOVATION YOU DESERVE.
THE PRODUCTS YOU NEED. THE QUALITY YOU WANT. THE INNOVATION YOU DESERVE. Central Chillers & Pump Tanks C E N T R A L C H I L L E R S 30RAP Series Central Chillers 10-60 Tons 30RAP Series air-cooled central
More informationAll Chiller Products. Water Cooled and Air Cooled Modular Chillers Available in 208, 230, 460 & 575 Volts Application Ranges from 30 to 1,000 Tons
All Chiller Products Water Cooled and Air Cooled Modular Chillers Available in 208, 230, 460 & 575 Volts Application Ranges from 30 to 1,000 Tons ClimaCool modular chillers. No compromises. They re not
More informationFeaturing Ozone-safe HFC134a. Hitachi Centrifugal Chillers. NEW GXG-S Series GSG-S Series Debut
Featuring Ozone-safe HFC134a Hitachi Centrifugal Chillers NEW GXG-S Series GSG-S Series Debut Centrifugal Chiller New GXG-S, GSG-S Series Debut High-efficiency New series Centrifugal Chillers that use
More informationNEW CHILLER SCHEDULE
TITLE: REPLACE CHILLER MACC MAXIMO # 4542690 PROJECT # 14M108CN MACC # 14-0459 ATTACHMENTS: 1. MAXIMO Equipment update form SCOPE OF WORK: The contractor shall provide all material, labor, equipment, and
More informationFeaturing Ozone-safe HFC134a. Hitachi Centrifugal Chillers NEW. GXG-S Series GSG-S Series. Debut
Featuring Ozone-safe HFC134a Hitachi Centrifugal Chillers NEW GXG-S Series GSG-S Series Debut Centrifugal Chiller New GXG-S, GSG-S Series Debut High-efficiency New series Centrifugal Chillers that use
More information