Fire protection of cantilevered external steel balconies in multistorey flats - a case study.
|
|
- Merry Young
- 5 years ago
- Views:
Transcription
1
2 Fire protection of cantilevered external steel balconies in multistorey flats - a case study. A presentation prepared for April 2015 meeting of the `Steel in Fire Forum, Institution of Structural Engineers, London. Gordon Cooke BSc PhD CEng MICE FIFireE Chartered Civil Engineer and Fire Safety Consultant gordon@cookeonfire.com (Formerly Visiting Professor, School of Engineering and Mathematical Sciences, City University, London)
3
4 The problem Fire enforcement notice served Client trying to resolve two issues: 1. if external balcony steelwork needs fire protecting 2. does timber cladding of top storey need coating to reduce flame spread
5 Plan of building showing location of flats, balconies and stairs. Location of balconies in open air and positions of staircases at ends of accommodation meant that means of escape were good, although there were a few locations where the flats were in dead ends. Key Stair Balcony Flat
6 There a Typical layout of a flat
7 Fire scenario
8 Structural Consulting Engineers calculations In a 2 page report the Consulting engineers interpreted the regs to require 60 min fire resistance for the balcony steelwork. My experience suggested the unprotected steelwork had less than 30 min They decided they would use BS 5950 Part 8 to calculate Limiting temp and Design temp for different times of exposure (30, 45, and 60min).
9 Engineers calculation results Acceptable if limiting temperature > design temperature
10 Engineers conclusions It is clear from the above calculations that the balconies perform well enough (not including the decking) to be safe for use as a fire escape for a period in excess of 30 min but not likely 60 minutes. However, it is possible that the building was designed in such a way that the balconies are not necessarily included as part of the overall escape strategy and that they may only require 30 minutes fire resistance or even none at all. We are not familiar enough with this building to make that determination and suggest that a fire consultant be approached to advise further.
11 Typical balcony cantilever.
12 Balcony continuity
13 Timber-slatted balcony walkway
14 My approach I considered it unreasonably onerous to assume the steel was exposed to ISO 834 conditions. If any calculation method should be employed it should use the classic jetting flames method of Law and O Brien. The Law work showed that if the external steel was spaced away from the facade by at least 2/3rd of the window height then the steel would not reach approximately 550 degc, the commonly accepted failure temperature criterion for structural steel.
15 My approach (cont d) If a balcony collapsed in a fire it would not affect the stability of the building. Severe fire would create catenary effect in balcony. Occupant safety OK Some property damage, fire-fighting and FDA considerations.
16 Fire safety strategy There did not appear to be a fire safety strategy for the building and I recommended that one be prepared and submitted to the LFB for comment and approval. It seemed that a stay-in-place strategy might have been adopted as the fire alarm was said to be disabled. Strategy and fire protection is mutually dependent.
17 Cost savings The client mentioned that the savings gained by not having to use intumescent or other passive fire protection for the balcony steelwork was in excess of 300,000. However the implications of a stay-in-place strategy were that local fire detection and alarm would be needed in some areas where there was an unavoidable dead end condition
18 The timber cladding issue. Was Class 4 surface spread of flame acceptable? I considered it was as there were no storeys above the cladding and lateral flame spread is minimal. If anything it was a property loss issue.
19 Unprotected steel columns in the undercroft car park. I deemed it unnecessary to fire protect these owing to the open-sided environment.
20
21
Paper presented at the International Symposium on Protection of Cultural Heritage Buildings from Fire, Kyoto, Japan, April 6 7, 2003
Paper presented at the International Symposium on Protection of Cultural Heritage Buildings from Fire, Kyoto, Japan, April 6 7, 2003 UPGRADING THE FIRE RESISTANCE OF FLOORS AND DOORS IN HERITAGE BUILDINGS
More informationUnit 2 Fire Safety (Zone 1)
IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 1) Examiner Report March 2018 Introduction 42% of candidates attained a Pass. Half of the candidates that attained a Pass secured
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More informationLoss Prevention Standards
Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building
More informationDesign of Fire safety in Multi Occupancy Residential Accommodation
Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability
More informationFire precautions in dwellings
NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types
More informationDesign Guidelines Fire Safety in New and Refurbished Buildings
Design Guidelines Fire Safety in New and Refurbished Buildings Introduction All major new or refurbishment projects must comply with the Technical Standards (Scotland) Regulations as a matter of course.
More informationBRE: Stay-put or Evacuate? Carl Sherwood BRE Fire Safety Group 22 nd July Part of the BRE Trust
BRE: Stay-put or Evacuate? Carl Sherwood BRE Fire Safety Group 22 nd July 2016 Part of the BRE Trust Introduction New buildings: Building Regulations 2010 Existing buildings: Regulatory Reform (Fire Safety)
More informationCladding Screening Test Result
Cladding Screening Test Result Submitting body Building address L&Q, One Kings Hall Mews, SE13 5JQ Flats 1-18, Burnell House, E20 1GY Organisation type: Contact details for test result Location of where
More informationFIRE RISK ASSESSMENT
FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter
More informationfire risk assessment For use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
More informationAre we using the wrong design fires for tall building fire strategies, in light of recent full height fires?
Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires? Tall Building Fire Safety Network meeting & seminar FIREX, London, 22 nd June 2016 Eoin O Loughlin
More informationCopy of article submitted to Fire Safety Engineering for publication January/February 2009
Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Metal faced sandwich panels with plastic foam cores - a challenge to fire safety by Gordon Cooke Confusion, misleading
More informationIDD 033C - Fire door sets
IDD 033C - Fire door sets Why are fire door sets important? Fire doors are one of the most important features of a building s fire precautions and have two key functions: To protect escape routes from
More informationFire Risk Assessment Guide
Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are
More informationApplication of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia
Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia A Challenging Application for the New Italian Fire Code
More informationIFE Level 4 Certificate in Fire Science and Fire Safety
Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the application of fire safety measures in complex premises and environments. Complex premises and environments include
More informationGrenfell Tower fire safety investigation: The fire protection measures in place on the night of the fire, and conclusions as to:
BLAR00000017_0001 Grenfell Tower fire safety investigation: The fire protection measures in place on the night of the fire, and conclusions as to: the extent to which they failed to control the spread
More informationMEDIUM-DENSITY HOUSING # 7. Fire safety
BRANZ FACTS MEDIUM-DENSITY HOUSING # 7 Fire safety Moving from low-density to medium-density housing (MDH) involves people living in closer proximity. This has a number of implications for fire safety
More informationFire safety and high rise student accommodation
Fire safety and high rise student accommodation This practical leaflet aims to explain the following: the Grenfell Tower fire the potential implications for students living in highrise halls what students
More informationPrincess Court Cornbrook Park Road Old Trafford Manchester M15 4FE
Princess Court Cornbrook Park Road Old Trafford Manchester M15 4FE Prepared by: Peter Golding Tech IOSH and Mark Alderson BSc Hons IEng MIFireE (IFE 0002248) Safety Management (UK) Ltd Holme Suite Clawthorpe
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE
FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification
More informationKensington Aldridge Academy, London W10
Kensington Aldridge Academy, London W10 Fire Safety Review Job Number: 1103 June 2018 FIRE SAFETY REVIEW CONTENTS EXECUTIVE SUMMARY 1.0 INTRODUCTION 2.0 FIRE SAFETY REQUIREMENTS 3.0 EXTERNAL WALL SPECIFICATION
More informationCase Study 1 Underground Car Park
Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the
More informationFire Risk Assessment Guide
Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are
More informationFire Safety Risk Assessment for Treowen, Wonastow, Monmouth, NP25 4DL
Fire Safety Risk Assessment for Treowen, Wonastow, Monmouth, NP25 4DL Record of significant findings Scope of Risk Assessment This fire safety risk assessment covers the use of Treowen as a venue for Civil
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE
FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification
More informationThe Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex:
The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: Mr. Junkers Lam Senior Building Surveyor of Buildings Department (9 Sept 2013) Part A Introduction Part B Means
More informationRESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:
RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: Manitoba Regulation 221/2015 and Manitoba Regulation 222/2015 DATE: MARCH 17, 2016 1. INTRODUCTION On April 1, 2016, new building and
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS
FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber
More information22 BISHOPSGATE Lift Evacuation Strategy
June 28, 2018 22 BISHOPSGATE Lift Evacuation Strategy Romain Hourqueig, Head of UK Fire Engineering Neil Allardice, Senior Fire Engineer AGENDA The project Fire Safety Strategy Why lift evacuation? The
More informationFIRE SAFETY SEMINAR 2009 WORKSHOP DISCUSSION
FIRE SAFETY SEMINAR 2009 WORKSHOP DISCUSSION BREAKOUT GROUPS DISCUSSIONS Approval of plans Building owner is making renovations to few units and asks FSM for advice? Please enlighten owner. FSM should
More informationFIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA
93 FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA INTRODUCTION 94 Legal requirements for the protection of firefighters Requirements of Building Act Fire Prevention Act Technical Guidelines OIB
More informationDispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth
Determination 2016/058 Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth Summary This determination considers whether signage is required between
More informationThe Association for Specialist Fire Protection
The Association for Specialist Fire Protection Passive Fire Protection Understanding the Risks! Wilf Butcher Chief Executive Officer Association for Specialist Fire Protection How does the dictionary define
More informationFire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan
Fire Risk Assessment Worksafe Solutions Consultancy Ltd 67 Flitwick Road Maulden Bedfordshire, MK45 2BJ Tel: 01525 406787 email enquiries@worksafesoultions.co.uk Index Part 1 Introduction Part 2 The Fire
More informationQ) What should I do if the fire alarm sounds in the building? Q) What do I do if I discover a fire?
ITEM 7(a)(i) Information from Milton Keynes Council and Buckinghamshire and Milton Keynes Fire and Rescue Service Dear resident You may have questions regarding fire safety at Stephenson House, especially
More informationWORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS
1 WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS TABLE 4.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF ASSEMBLIES Construction
More informationFire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /)
Fire resistance (A copy of this is available on www.routledge.com/books/details/ 9780415809696/).1 Fire resistance The overall aim of fire safety precautions is to ensure that: all corridor doors shall
More informationChallenges of Fire Fighting in Fire Engineered Built Environment
Available online at www.sciencedirect.com Procedia Engineering 11 (2011) 583 592 The 5 th Conference on Performance-based Fire and Fire Protection Engineering Challenges of Fire Fighting in Fire Engineered
More informationFINAL VERSION. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN
FINAL VERSION Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN August 2017 Responsible Person (e.g. employer) or person having control of
More informationFire Resistance of Timber Structures
Fire Resistance of Timber Structures Dr. Andrea Frangi ETH Zurich, Institute of Structural Engineering (IBK), Switzerland Presentation at ENEM09 Coimbra, October 29, 2009 Datum Use of timber as building
More informationPassive Fire Protection Guidance. Niall Rowan Technical Officer Association for Specialist Fire Protection
Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)
FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building
More informationLessons Learned from the FaçadeFiasco. Dr. Jonathan Barnett Technical Director, RED Fire Engineers
Lessons Learned from the FaçadeFiasco Dr. Jonathan Barnett Technical Director, RED Fire Engineers How did we arrive at the fac ade compliance problem and who is responsible? Who should cover rectification
More informationEmergency Evacuation Procedures
Emergency Evacuation Procedures Preparing for an Evacuation Know your building or classroom s floor plan. Know where the doors, windows, stairs, and fire extinguishers are. Determine in advance the nearest
More informationGeneral Principles of Smoke Control
AMCA International General Principles of Smoke Control Patrick Janssens, Sales Manager Colt International www.coltinco.co.uk or www.coltinfo.be Air System Engineering & Technology (ASET) Conference Europe
More informationSEPTEMBER-NEWSLETTER-ELEVATOR DANGERS
SEPTEMBER-NEWSLETTER-ELEVATOR DANGERS Each year, firefighters are brought up to fire floors in high-rise buildings by elevator and are forced to run for their lives through a gauntlet of flame, heat and
More informationPassive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection
Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking
More informationGENERAL FIRE SAFETY TERMS & DEFINITIONS
UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:
More informationREVISED. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN
REVISED Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN July 2017 Responsible Person (e.g. employer) or person having control of the
More informationEMERGENCY EVACUATION PLAN
UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s)
More informationBristol City Council Private Rented Sector Fire Safety Standards
Bristol City Council Private Rented Sector Fire Safety Standards Introduction The purpose of this document is to provide a basic guide to the fire precautions that are required in privately rented properties
More informationTURNING CONCEPTS INTO REALITY
TURNING CONCEPTS INTO REALITY AMRON ASSOCIATES An Introduction Amron Associates is part of the Wire Belt Group, which has been manufacturing metal mesh for over 50 years. Amron Associates is the special
More informationFIRE SAFETY POLICY. Adequate fire alarm systems that are tested at the required intervals
FIRE SAFETY POLICY Densholme Care Farm provides for groups of service users of all ages with differing physical, learning, mental health, emotional, social and behavioural difficulties, as well as school/college
More informationFire Risk Assessment
Fire Risk Assessment George Wright House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General
More informationPractice Advisory 18: Fire safety design for tall buildings
Practice Advisory 18: Fire safety design for tall buildings It s important that reliable and resilient fire design features are used in the design of tall buildings. This advisory highlights the specific
More informationHughes Downey Architects Tel.: Rideau Street. Kingston, ON K7K 3A4 Fax:
Date: May 30th, 2018 To: Alex Rowse-Thompson From: Bruce Downey Re: Response to Proposed Development for 81 King St Kingston specifically related to the proposed garage extension structure Company: Heritage
More informationFire Risk Management Post Grenfell
Fire Risk Management Post Grenfell Martin Arnold Ltd 4 Gunnery Terrace The Royal Arsenal London SE18 6SW T: 020 8317 7557 F: 020 8317 7741 E: general@martinarnold.co.uk W: martinarnold.co.uk Introduction
More informationPASSIVE FIRE PROTECTION FTI-MARNEROS LTD
PASSIVE FIRE PROTECTION FTI-MARNEROS LTD the art of passive fire protection since 1989 ABOUT FTI - MARNEROS is the joining of the fire department of Chr. Marneros & Co Ltd and Fire and Thermal Installations
More informationUNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:
Bldg Name: Rockefeller & Medical School (201 & 374) UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s)
More informationFire Engineering in High Rise 15 November 2013
Fire Engineering in High Rise 15 November 2013 Neal Butterworth Arup UK www.arup.com Neal.Butterworth@arup.com Contents How do we protect against fire? How do we know this works? Why evacuate? What assumptions
More informationUNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:
UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying Department(s) / School(s) / Institute(s): Medical Sciences
More information2012 B.C. Building Code Compliance Review (Division B Part 3)
Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting
More information1. What s so good about loft conversions? 2. What s new? - Legislation. 3. Key design options. 4. What Type of Roof? 5. Complying with Fire
1. What s so good about loft conversions? 2. What s new? - Legislation 3. Key design options 4. What Type of Roof? 5. Complying with Fire 6. Loft stairs 7. Designing the new structure 8. Loft windows 9.
More informationGuide to Gate Safety Legislation & the Machinery Directive
Guide to Gate Safety Legislation & the Machinery Directive Guide to Gate Safety Legislation & Machinery Directive Gate Safety in the UK market In June 2010 the tragic deaths of 2 young children in separate
More informationFire Severity for Structural Design
Fire Severity for Structural Design A UK Perspective Susan Deeny, PhD 2 Broadgate Phase 8 3 5 Shaping a better world Experience of working in Abu Dhabi 6 UAE 7 Fire Severity for Structural Analysis Building
More informationFire Risk Assessment
Fire Risk Assessment Carried out on behalf of EF international School On the 30 Aug 2017 By Matt Pate Copyright FCS Live Ltd 2017 Page 1 of 30 CONTENTS 1. Risk Summary 2. Risk Assessment 01 Persons at
More informationCenter for Life Safety Education
Center for Life Safety Education Fire Sprinklers 101 Introduction, Building Codes, and Water Supplies Reprinted with permission from NFPA 13, Installation of Sprinkler Systems, Copyright 2007, National
More informationPERFORMANCE OF PASSIVE FIRE PROTECTION IN JET FIRES
PERFORMANCE OF PASSIVE FIRE PROTECTION IN JET FIRES L. C. Shirvill Shell Research Ltd., Thornton Research Centre, P.O. Box 1, Chester CHI 3SH Emergency Shutdown Valves on offshore oil and gas risers must
More informationCPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation
CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation Speaker: Dr. L. K. Sze, Lipmann Technical Director of Date: 23 January, 2018 Disclaimer:
More informationExova Warringtonfire - Expert Witness Directory 2018
Exova Warringtonfire Holmesfield Road Warrington Cheshire WA1 2DS United Kingdom T : +44 (0) 1925 655116 E : warrington@exova.com W: www.exova.com Exova Warringtonfire - Expert Witness Directory 2018 Please
More informationGuide to Gate Safety Legislation & the Machinery Directive. In Association with:
Guide to Gate Safety Legislation & the Machinery Directive In Association with: Tel: 0845 054 5070 asosafety@egduk.com Guide to Gate Safety Legislation & Machinery Directive Gate Safety in the UK market
More informationFive London Hospital Fires: Report by Philip Gibbs, LFB. For internal training use only.
Introduction This report is a summary of the findings from a study conducted into the Five London Hospital Fires by Philip Gibbs of London Fire Brigade. The purpose of this report is to: Highlight fire
More informationFire Risk Assessment
Fire Risk Assessment Address of Property Assessed: Person Undertaking the Assessment - Name: Position: Date of Assessment: The Lodge, 1 Hunt Street, Swindon, Wiltshire SN1 3HW Anna-Marie Dutton Manager
More informationSURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG
SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG E.C.L. Pang and W.K. Chow Research Centre for Fire Engineering, Area of Strength: Fire Safety Engineering The Hong Kong Polytechnic
More informationINDOOR AIR QUALITY IN ENGLISH HOMES - NITROGEN DIOXIDE
INDOOR AIR QUALITY IN ENGLISH HOMES - NITROGEN DIOXIDE SKD Coward, GJ Raw, JW Llewellyn and DI Ross BRE, Watford WD25 9XX, UK ABSTRACT BRE has conducted a national survey of air pollutants in 876 homes
More informationFire Risk Assessment Guide
Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are
More informationHandout Notes Major changes in BS : 2016
Handout Notes Major changes in BS 5266-1: 2016 The contents section now includes Introduction 1 Scope 2 Normative references 3 Terms and definitions 4 Consultation and records 5 Illumination for emergency
More informationThe Singapore Fire Safety Engineering Guidelines. Nicholas Lee, Senior Consultant Fire Safety & Shelter Department Singapore Civil Defence Force
The Singapore Fire Safety Engineering Guidelines Nicholas Lee, Senior Consultant Fire Safety & Shelter Department Singapore Civil Defence Force Singapore Civil Defence Force The Singapore Civil Defence
More informationLondon Borough of Hammersmith & Fulham
Assessment Details: Property Assessed Flora Gardens 186-197, FLORA GARDENS, LONDON Assessment Date 19/12/2017 Assessment Valid Until 04/12/2020 Assessor Details Mark Richards LBHF Fire Risk Assessor QA
More informationSaving lives with coatings
Saving lives with coatings The essentials of passive fire protection. Paul Mather. Passive fire protection by means of intumescent, cementitious or ceramifying coatings or layers has gained importance
More informationSHEVTEC Extended Travel Distance. System for Chettles Yard, Nottingham
Case Study SHEVTEC Extended Travel Distance System for Chettles Yard, Nottingham Name: Chettles Yard, Nottingham Background: Chettles Yard student accommodation is a typical example of modern high specification
More informationDESIGN REVIEW PANEL PROCEDURES AND PROTOCOL
Meeting Schedule DESIGN REVIEW PANEL PROCEDURES AND PROTOCOL (a) The Design Review Panel is scheduled to meet the last Thursday of every month on the dates shown in the attached Schedule of Meetings, the
More information161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures
161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means
More informationFire Risk Assessment. ABC Car Workshop. Prepared for. Redacted
Fire Risk Assessment Prepared for ABC Car Workshop Assessor: (Assessor s Name) Date of Assessment: 24/07/17 Date of Next Assessment Review: Upon occupation Introduction and Scope This Fire Risk Assessment
More informationRequirements for ships carrying hydrogen and compressed natural gas vehicles
Lloyd's Register briefing IMO FP 55 Summary report for clients Overview The 55 th session of the IMO Fire Protection Sub Committee (FP) was held from 25 th to 29 th July 2011, at the IMO headquarters in
More informationLondon Borough of Hammersmith & Fulham
London Borough of Hammersmith & Fulham Assessment Details: Property Assessed Flora Gardens 161-185, FLORA GARDENS, LONDON Assessment Date 16/01/2018 Assessment Valid Until 23/08/2018 Assessor Details Gary
More informationNEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS
Mandatory Fire Safety Instruction NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Reference A: Reference B: Approved Document B
More informationFIA Guidance on Manual Call Point - Protection - False Alarm Mitigation
Guidance Note FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation FIA Guidance on Manual Call Point - Protection False Alarm Mitigation 1. INTRODUCTION... 3 2. BS 5839-1 RECOMMENDATIONS...
More informationThe Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE
The Protection of Machinery Spaces by means of the Local Application of Water Mist Dr. Tim R. Nichols CPhys FIFireE 2017 Johnson Controls. All rights reserved. Tyco Fire Products LP is a subsidiary of
More informationSHOPPING MALL UNITS - TO LET GREEN STREET, LONDON E7 8LE
DESCRIPTION East Shopping Centre, a new development intergrated within the heart of Green Street. The development which is aimed for completion in September 2014, shall provide 27 two storey units, anchored
More informationFIRES IN BUILDING & CONSTRUCTIONS
FIRES IN BUILDING & CONSTRUCTIONS By: ZEESHAN BARI AIM OF THE PRESENTATION inform how FIRE spreads in p onstructions and Buildings. OBJECTIVES After this Presentation you should be able to: Understand
More informationFire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1
Billy Hanafin H & S and Operations Officer Version 1.0 October 2013 Page 1 1. General The Trust is a responsible employer that takes its Fire Safety duties seriously. For that reason, this policy has been
More informationHow to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?
Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through
More informationPolicy for Safe Evacuation of Persons with Disabilities
Policy for Safe Evacuation of Persons with Disabilities 1. Policy Statement The London School of Economics is committed to promoting access for people who have a disability or long-term medical condition.
More informationDECLARATORY STATEMENT. THIS CAUSE came on for consideration upon the Petition for Declaratory
TOM GALLAGHER CHIEF FINANCIAL OFFICER STATE FIRE MARSHAL STATE OF FLORIDA In re the Matter of Rocky Sneed, Petitioner. Case No.: 80599-05-FM Petition for Declaratory Statement to the Florida Department
More informationFire protection documentation. CFPA-E Guideline No 13:2015 F
Fire protection documentation CFPA-E Guideline No 13:2015 F FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation in the
More informationBRE & LPCB Ruth Tucker -Passive Fire Protection
www.bregroup.com BRE & LPCB Ruth Tucker -Passive Fire Protection Building a better world together After 1666 Great Fire of London each insurer set up a Fire Office to look after fire risk 1868 - The Fire
More information