Test Report: ICL/CR15/11/087

Size: px
Start display at page:

Download "Test Report: ICL/CR15/11/087"

Transcription

1 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) Fax.: +44 (0) firetesting@intersciencecomms.co.uk Test Report: ICL/CR15/11/087 BS EN :2007 +A1:2009 Fire classification of construction products and building elements Part 1: Classification using data from reaction to fire tests Sponsored By Unience Co Ltd Namchon-ri Oksan-myeon Cheonwon-gun Chungbuk-do Korea Registered Office: West Yard House, Guildford Grove, Greenwich, London SE10 8JT, UK firetesting@intersciencecomms.co.uk; Web: intersciencecomms.co.uk Company Registration VAT No. GB Page 1 of 5

2 Test Report: ICL/CR15/11/087 BS EN :2007 +A1:2009 Fire classification of construction products and building elements Part 1: Classification using data from reaction to fire tests 1 Introduction Sponsored By Unience Co Ltd Namchon-ri Oksan-myeon Cheonwon-gun Chungbuk-do Korea This classification report defines the classification assigned to the product tested in accordance with the procedures called up in EN :2007 +A1:2009 for construction products, excluding floorings and linear pipe thermal insulation products to determine classification B through to E. 2 Description of Test Specimens The description of the specimens given below has been prepared from information provided by the sponsor of the test. All values quoted are nominal, unless tolerances are given. Parameter Trade Name Suppliers reference Description Details Alfrex FR aluminium composite Alfrex Aluminium Composite Panel (Alfrex). Composition: Aluminium skin, 0.5 mm Non-combustible Mineral Filled Core, 3.0 mm Aluminium Skin, 0.5 mm Classification Report : ICL/CR15/11/087 Page 2 of 5

3 Parameter Description of the sample as received. Details An aluminium composite panel consisting of: An off-white core material. Two coated aluminium facings. The exterior face was matt light grey; the interior face was silver grey. The interior face was protected by a light grey film with dark grey and red markings. The following text was visible on the film: Alfrex Non combustible ACP Qualified ISO 9001/14001 Install only in this direction The following code was printed at intervals over the exterior face of the test specimens: E/S - S/2 AM(2) ALFREX FR ALUMINIUM COMPOSITE PANEL KS F 4737 KSA C/N , Y2015 MO9D01H17M31UNIENCE.CO.KR / MADE IN KOREA Test sponsor s product data Generic type of product Aluminum composite panel Nominal thickness (mm) 4 Nominal density (kgs/m 3 ) Note 1 Nominal mass per unit area 7.35 (g/m 2 ) Colour Interior face: Silver grey Exterior face: Grey Core: off white This classification report consists of five pages and may only be used or reproduced in its entirety. 3 Reports and results in support of this classification 3.1 Reports Test method Name of Laboratory Name of sponsor Report ref. no. Interscience Fire Laboratory Unience Co Ltd ICL/H15/5222 ISO Interscience Fire Laboratory Unience Co Ltd ICL/H15/5223 EN Classification Report : ICL/CR15/11/087 Page 3 of 5

4 3.2 Results ICL/H15/5222 ISO Test result: Pass. No ignition of the paper ICL/H15/5223 EN : Summary of results: Run No. Data Mean Run Number FIGRA 0.2MJ (W/s) FIGRA 0.4MJ (W/s) SMOGRA (m²/s²) THR 600s (MJ) TSP 600s (m²) Flaming droplets/particles No No No Flaming droplets/particles > 10 s No No No LFS reaches edge of specimen No No No 4 Classification The product, Alfrex FR aluminium composite 4mm thick, in relation to its reaction to fire behaviour, is classified as B-S1, d0. Prepared by Approved by C. B. Chong S. Kumar Fire Scientist Technical Manager Date: 20 th November Classification Report : ICL/CR15/11/087 Page 4 of 5

5 CLASSES OF REACTION-TO-FIRE PERFORMANCE FOR CONSTRUCTION PRODUCTS EXCLUDING FLOORINGS, LINEAR PIPE THERMAL INSULATION PRODUCTS, AND ELECTRIC CABLES Class Test method (s) Classification criteria Additional classification A1 A2 EN ISO 1182 a and EN ISO 1716 EN ISO 1182 a or EN ISO 1716 and EN T 30 C; and m 50 %; and t f = 0 (i.e. no sustained flaming) PCS 2,0 MJ/kg a and PCS 2,0 MJ/kg b and PCS 1,4 MJ/m 2 c and PCS 2,0 MJ/kg d T 50 C; and m 50 %; and t f 20 s PCS 3,0 MJ/kg a and PCS 4,0 MJ/m 2 b and PCS 4,0 MJ/m 2 c and PCS 3,0 MJ/kg d FIGRA 120 W/s and LFS < edge of specimen and THR600s 7,5 MJ B EN FIGRA 120 W/s and LFS < edge of specimen and EN ISO i Exposure = 30 s THR600s 7,5 MJ Fs d 150 mm within 60 s C EN FIGRA 250 W/s and LFS < edge of specimen and EN ISO i: Exposure = 30 s THR600s 15 MJ Fs 150 mm within 60 s Smoke production f and Flaming droplets/particles g Smoke production f and Flaming droplets/particles g Smoke production f and Flaming droplets/particles g D EN FIGRA 750 W/s Smoke production f and EN ISO i: Exposure = 30 s E EN ISO i: Exposure = 30 s F Fs 150 mm within 60 s Fs 150 mm within 60 s No performance determined Flaming droplets/particles g Flaming droplets/particles h a For homogeneous products and substantial components of non-homogeneous products. b For any external non-substantial component of non-homogeneous products. c Alternatively, any external non-substantial component having a PCS 2,0 MJ/m2, provided that the product satisfies the following criteria of EN 13823: FIGRA 20 W/s, and LFS < edge of specimen, and THR600s 4,0 MJ, and s1, and d0. d For any internal non-substantial component of non-homogeneous products. e For the product as a whole. f In the last phase of the development of the test procedure, modifications of the smoke measurement system have been introduced, the effect of which needs further investigation. This may result in a modification of the limit values and/or parameters for the evaluation of the smoke production. s1 = SMOGRA 30m 2 /s2 and TSP600s 50m 2 ; s2 = SMOGRA 180m 2 /s 2 and TSP600s 200m2; s3 = not s1 or s2 g d0 = No flaming droplets/ particles in EN within 600 s; d1 = no flaming droplets/ particles persisting longer than 10 s in EN within 600 s; d2 = not d0 or d1. Ignition of the paper in EN ISO results in a d2 classification. h Pass = no ignition of the paper (no classification); Fail = ignition of the paper (d2 classification). I Under conditions of surface flame attack and, if appropriate to the end use application of the product, edge flame attack. Classification Report : ICL/CR15/11/087 Page 5 of 5

6 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) Fax.: +44 (0) firetesting@intersciencecomms.co.uk Test Report: ICL/H15/5222 ISO : 2010 Reaction to fire tests- Ignitability of products subjected to Direct impingement of flame- Part 2- Single- flame source test Sponsored By Unience Co Ltd Namchon-ri Oksan-myeon Cheonwon-gun Chungbuk-do Korea Registered Office: West Yard House, Guildford Grove, Greenwich, London SE10 8JT, UK Page 1 of 4 firetesting@intersciencecomms.co.uk; Web: intersciencecomms.co.uk Company Registration VAT No. GB

7 1 Purpose of Test Test Report: ICL/H15/5222 ISO : 2010 Reaction to fire tests- Ignitability of products subjected to Direct impingement of flame- Part 2- Single- flame source test Sponsored By Unience Co Ltd Namchon-ri Oksan-myeon Cheonwon-gun Chungbuk-do Korea To assess the performance of specimens of a composite when tested in accordance with the procedure specified in ISO : 2010 Reaction to fire tests- Ignitability of products subjected to Direct impingement of flame- Part 2- Single- flame source test 15 second edge application. 2 Description of Test Specimens The description of the specimens given below has been prepared from information provided by the sponsor of the test. All values quoted are nominal, unless tolerances are given. The sponsor of the test did not supply further details relating to the composition of the material tested. Parameter Trade Name Suppliers reference Description Details Alfres FR aluminium composite Alfrex Aluminium Composite Panel (Alfrex). Composition: Aluminium skin, 0.5 mm Non-combustible Mineral Filled Core, 3.0 mm Aluminium Skin, 0.5 mm ICL Report No: ICL/H15/5222 Page 2 of 4

8 Parameter Details Description of the sample as An aluminium composite panel consisting of: received. An off-white core material. Two coated aluminium facings. The exterior face was matt light grey; the interior face was silver grey. The interior face was protected by a light grey film with dark grey and red markings. The following text was visible on the film: Alfrex Non combustible ACP Qualified ISO 9001/14001 Install only in this direction The following code was printed at intervals over the exterior face of the test specimens: E/S - S/2 AM(2) ALFREX FR ALUMINIUM COMPOSITE PANEL KS F 4737 KSA C/N , Y2015 MO9D01H17M31UNIENCE.CO.KR / MADE IN KOREA Test sponsor s product data Generic type of product Aluminum composite panel Nominal thickness (mm) 4 Nominal density (kgs/m 3 ) Note 1 Nominal mass per unit area 7.35 (g/m 2 ) Colour Interior face: Silver grey Exterior face: Grey Core: off white 3 Conditioning of Specimens The specimens were received on 7 th September The specimens were conditioned for a minimum period of 48 hours prior to testing at 23 ± 2 C and 50 ± 5% RH, and until constant mass was achieved. 4 Date of Test The test was performed on 3 rd November ICL Report No: ICL/H15/5222 Page 3 of 4

9 5 Test Procedure The test was performed in accordance with the procedures specified in ISO Reaction to fire tests- Ignitability of products subjected to Direct impingement of flame- Part 2- Single- flame source test and this report should be read in conjunction with this standard. Ignition source was applied for 30 seconds. 6 Test Results The test results relate only to the behavior of the specimens of the product under the particular conditions of test; they are not intended to the sole criterion for assessing the hazard of the product in use. The test results relate only to the specimens of the product in the form in which they were tested. Small differences in the composition or thickness of the product may significantly affect the performance during the test and will therefore invalidate the test results. The results of tests are as follows Face application Specimen No Ignition (yes/no) Ignition ceases (sec) Flame reached 150mm(yes/no) Time to reach 150mm (sec) Flame spread (mm) Ignition of filter Paper (yes/no) 1 No N/A No N/A 0 No 2 No N/A No N/A 0 No 3 No N/A No N/A 0 No Specimen No Ignition (yes/no) Edge Application Ignition Flame reached ceases 150mm(yes/no) (sec) Time to reach 150mm (sec) Flame spread (mm) Ignition of filter Paper (yes/no) 1 No N/A No N/A 0 No 2 No N/A No N/A 0 No 3 No N/A No N/A 0 No Note: After each test the specimen was visually examined to determine the flame spread value. The criterion used was to see if there is visible charring on the surface.. Prepared by Approved by C. B. Chong S. Kumar Fire Scientist Technical Manager Date of Issue: 20 th November ICL Report No: ICL/H15/5222 Page 4 of 4

10 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) Fax.: +44 (0) firetesting@intersciencecomms.co.uk Test Report: ICL/H15/5223 EN Single Burning Item (SBI) test on Alfrex FR aluminium composite pane Sponsored By Unience Co Ltd Namchon-ri Oksan-myeon Cheonwon-gun Chungbuk-do Korea Registered Office: West Yard House, Guildford Grove, Greenwich, London SE10 8JT, UK Page 1 of 14 firetesting@intersciencecomms.co.uk; Web: intersciencecomms.co.uk Company Registration VAT No. GB

11 Test Report: ICL/H15/5223 EN Single Burning Item (SBI) test on Alfrex FR aluminium composite pane Sponsored By Unience Co Ltd Namchon-ri Oksan-myeon Cheonwon-gun Chungbuk-do Korea 1 Objective To assess the performance of the sample described in Section 2 of this report when subjected to the tests specified in EN 13823: A1: Description of Test Specimens The description of the specimens given below has been prepared from information provided by the sponsor of the test. All values quoted are nominal, unless tolerances are given. The sponsor of the test did not supply further details relating to the composition of the material tested. Parameter Trade Nome Suppliers reference Description details Alfres FR aluminium composite Alfrex Aluminium Composite Panel (Alfrex). Composition: Aluminium skin, 0.5 mm Non-combustible Mineral Filled Core, 3.0 mm Aluminium Skin, 0.5 mm ICL Report No: ICL/H15/5223 Page 2 of 14

12 Description of the sample as received. An aluminium composite panel consisting of: An off-white core material. Two coated aluminium facings. The exterior face was matt light grey; the interior face was silver grey. The interior face was protected by a light grey film with dark grey and red markings. The following text was visible on the film: Alfrex Non combustible ACP Qualified ISO 9001/14001 Install only in this direction The following code was printed at intervals over the exterior face of the test specimens: E/S - S/2 AM(2) ALFREX FR ALUMINIUM COMPOSITE PANEL KS F 4737 KSA C/N , Y2015 MO9D01H17M31 UNIENCE.CO.KR / MADE IN KOREA Test sponsor s product data Generic type of product Aluminum composite panel Nominal thickness (mm) 4 Nominal density (kgs/m 3 ) Note 1 Nominal mass per unit area (g/m 2 ) 7.35 Colour Interior face: Silver grey Exterior face: Grey Core: off white Substrate and ventilation conditions Generic type of product Calcium silicate Thickness (mm) 12.5 Density (kgs/m 3 ) 870 European reaction to fire A2-s1,do classification Type of air gap None Position of the air gap Not applicable Measured Sample data Mean sample density (kgs/m 3 ) Mean sample thickness (mm) 4.05 Mean sample mass (kgs/m 2 ) 7.18 ICL Report No: ICL/H15/5223 Page 3 of 14

13 Test information Face to be tested Orientation aspect Sample identification Interior face Installation direction is indicated on the panel E/S - S/2 AM(2) ALFREX FR ALUMINIUM COMPOSITE PANEL KS F 4737 KSA C/N , Y2015 MO9D01H17M31 UNIENCE.CO.KR / MADE IN KOREA Sample receipt date 7 th September 2015 Date of the test 2 nd November 2015 Note1: This information was not supplied by the sponsor of the test, 2.1 Description of substrate 12.5 mm-thick, 870 kg/m³ calcium silicate, classified A2-s1, d0 to EN Jointing details The specimen was tested with the following joints: A vertical joint on the short wing. The centre line of the joint was positioned a distance of 447 mm from the finished corner, measured when the wings were mounted ready for testing. Adjacent panels were butt-jointed. The vertical joint on the short wing and the corner joint were open / unprotected, i.e. they were not covered by a sealant or joint cover 2.3 Mounting The wings of the test specimen were loose laid against12.5 mm-thick, 870 kg/m³ calcium silicate board. 3 Conditioning of Specimens The specimens were conditioned as required by the test standard. 4 Date of Test The test was performed on 2 nd November ICL Report No: ICL/H15/5223 Page 4 of 14

14 5 Test Results Tabulated data Table 1 Data Run No Mean FIGRA0.2MJ (W/s) FIGRA0.2MJ (W/s) FIGRA0.4MJ (W/s) THR600s (MJ) TSP600s (m²) Flaming droplets/particles No No No Flaming droplets/particles No No No LFS reaches edge of specimen No No No Table 2 Event Occurrence of Event (Yes/No) Run No Occurrence of a surface flash No No No Smoke from the specimen not entering the hood during test Falling of parts of the specimen No No No Development of a gap in the corner (mutual fixing of No No No backing board fails) Occurrence of one or more conditions which justify an No No No early termination of the test 1560 Yes(1) Yes(1) Yes(1) Test duration (s) Any other event See observations It should be noted that: Specimens with an average rate of smoke production value, RSPav, of not more than 0.1m²/s during the total test period or a total smoke production value of not more than 6m² over the total test period have a SMOGRA value of zero. The fire growth rate indices are calculated only for that part of the exposure period in which the threshold levels for RHRav(t) and THR have been exceeded. If one or both threshold values are not exceeded during the exposure period, FIGRA is equal to zero. The threshold value used for RHRav(t) is 3kW. Two different THR threshold values are used, resulting in FIGRA 0.2MJ and FIGRA 0.4MJ. Values of THR600s and TSP600s refer to a time of 600s after the flame has been applied to the specimen. This is 300s after the start of the test, and therefore represents a time of 900s in the graphs presented below. The results of a test are not valid for classification purposes when an early termination of the test has occurred. ICL Report No: ICL/H15/5223 Page 5 of 14

15 Observations. Run Comments s: Smoke started to issue from the vertical joint in the short wing s : Smoke started to issue from the vertical joint in the short wing Smoke production ceased s : Smoke started to issue from the vertical joint in the short wing Smoke production ceased. 1-3 The test specimen burnt over the corner joint approximately 30 second after burner was extinguished. Prepared by Approved by C. B. Chong S. Kumar Fire Scientist Technical Manager Date of Issue: 20 th November ICL Report No: ICL/H15/5223 Page 6 of 14

16 Appendix 1 Test Run 1: ICL Report No: ICL/H15/5223 Page 7 of 14

17 ICL Report No: ICL/H15/5223 Page 8 of 14

18 Test Run 2: ICL Report No: ICL/H15/5223 Page 9 of 14

19 ICL Report No: ICL/H15/5223 Page 10 of 14

20 Test Run 3: ICL Report No: ICL/H15/5223 Page 11 of 14

21 ICL Report No: ICL/H15/5223 Page 12 of 14

22 Appendix 2 ICL Report No: ICL/H15/5223 Page 13 of 14

23 ICL Report No: ICL/H15/5223 Page 14 of 14

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com CLASSIFICATION CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE

More information

Test Report: ICL/H18/9039 Rev 1

Test Report: ICL/H18/9039 Rev 1 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification no.

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification

More information

Test Report No: ICL/H17/7967

Test Report No: ICL/H17/7967 2294 Notified Body No 2700 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Sponsor Prepared by P.O. Box 118 NL-2394 ZG HAZERSWOUDE Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Sponsor Prepared by P.O. Box 70 NL-5750 AB DEURNE Efectis Nederland BV Lange Kleiweg 5 P.O. Box 1090 NL-2280 CB

More information

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests

More information

New European Fire Testing Classification for Construction Products

New European Fire Testing Classification for Construction Products New European Fire Testing Classification for Construction Products THE BENCHMARK IN FIRE TESTING EU Construction Products Directive The EU Construction Products Directive (CPD), is the basis of construction

More information

Classification report

Classification report - Restricted Classification report Reaction to fire classification report of product Fibo-Trespo Bathroompanels / Respatex Bathroompanels Author Gunn Hofstad SINTEF NBL as Reaction to fire 2012-07-04 Table

More information

Contact person Date Reference Page Richard Johansson P (2) Fire Research

Contact person Date Reference Page Richard Johansson P (2) Fire Research issued by an Accredited Testing Laboratory Contact person Richard Johansson 215-8-13 5P4413 1 (2) Fire Research +46 1 516 56 75 richard.johansson@sp.se 12 ISO/IEC 1725 Sklejka-Pisz Paged S.A Ul. kwiatowa

More information

CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation

CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation Speaker: Dr. L. K. Sze, Lipmann Technical Director of Date: 23 January, 2018 Disclaimer:

More information

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests

More information

CLASSIFICATION REPORT

CLASSIFICATION REPORT CLASSIFICATION REPORT NUMBER 251.C.1804.020.EN.01 Work sheet: 21801003 DATE OF ISSUE April 10 th, 2018 NOTIFIED BODY PAGE TEST SPECIMEN CONCERNING TO APPLICANT DATE/S OF TEST AUTORIZED SIGNATORIES Notified

More information

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for: Classification of reaction to fire performance in accordance with EN 13501-1: 2007 +A1: 2009 on Superfoil SFNC Prepared for: Boulder Developments Ltd Black Horse Farm Main Street Norwell Nottinghamshire

More information

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50. Classification of reaction to fire performance in accordance with BS EN 13501-1: 2007 +A1: 2009 on Sandwich Panel, WP 50 Prepared for: Sandwich Panel Factory Jeddah Saudi Arabia 13 July 2011 0578 Page

More information

BS EN ISO : 2010

BS EN ISO : 2010 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination

More information

Reaction to fire testing of Vescom vinyl wall covering with a Fibre Structure, a total weight of 550 g/m 2 according to EN 13823:2002

Reaction to fire testing of Vescom vinyl wall covering with a Fibre Structure, a total weight of 550 g/m 2 according to EN 13823:2002 Efectis Nederland BV Efectis Nederland report 2008-Efectis-R0431[Rev.1](E) Reaction to fire testing of Vescom vinyl wall covering with a Fibre Structure, a total weight of 550 g/m 2 according to EN 13823:2002

More information

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013 SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT No. RA140063 ACCORDING TO THE EUROPEAN STANDARD NF EN 135011+A1:2013 Notification by the French Government

More information

Additional Reaction to Fire Classification Report

Additional Reaction to Fire Classification Report Additional Reaction to Fire Classification Report MDF Plate Client: Teknos A/S File no.: PCA10461Aad Date: 2018-01-09 Pages: 5 Encl.: 3 Ref: MPA / JAG Notified Body No. 0845 Danish Institute of Fire and

More information

Centrum stavebního inženýrství a.s.

Centrum stavebního inženýrství a.s. Centrum stavebního inženýrství a.s. Fire Technical Laboratory AUTHORIZED NOTIFIED BODY No. 22 BODY No. 9 CLASSIFICATION OF REACTION TO FIRE IN ACCORDANCE WITH EN 5-:27+A:29 Applicant: Příhoda s.r.o. Za

More information

BCTC CARPET TECHNICAL CENTRE

BCTC CARPET TECHNICAL CENTRE Wira House West Park Ring Road Leeds, LS16 6QL Tel: +44 (0)113 259 1999 Fax: +44 (0)113 278 0306 Web: http://www.bttg.co.uk/bctc Email: CSLeeds@bttg.co.uk 7 September 2010 Page 1 of 7 Client: Rectory Farm

More information

BS EN ISO : 2010

BS EN ISO : 2010 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Fire Tests For Determination Of The Burning

More information

BS EN ISO : 2010

BS EN ISO : 2010 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination

More information

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 1716: 2010 Determination Of The

More information

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877. Return address: P.O. box 337, 7500 AH Enschede, TNO Centre for Textile Research Ariënsplein 3 7511 JX ENSCHEDE Forbo Flooring Attn. Mr. A. Tijhof Postbus 13 1560 AA Krommenie Report Sponsor : Contractor,

More information

REACTION TO FIRE TESTS FOR BUILDING PRODUCTS DETERMINATION OF THE HEAT OF COMBUSTION ACCORDING TO STN EN ISO 1716: 2003

REACTION TO FIRE TESTS FOR BUILDING PRODUCTS DETERMINATION OF THE HEAT OF COMBUSTION ACCORDING TO STN EN ISO 1716: 2003 mgr. Dušan BERNÁT Fire and Research Institute Ministry of Interior of the Slovak Republic REACTION TO FIRE TESTS FOR BUILDING PRODUCTS DETERMINATION OF THE HEAT OF COMBUSTION ACCORDING TO STN EN ISO 1716:

More information

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2002 Fire Tests For

More information

SBI. Single Burning Item - EN THE BENCHMARK IN FIRE TESTING

SBI. Single Burning Item - EN THE BENCHMARK IN FIRE TESTING SBI Single Burning Item - EN 13823 THE BENCHMARK IN FIRE TESTING FTT Single Burning Item (SBI) The importance of the SBI The European Construction Products Directive requires that all European Member states

More information

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft. T F

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft.   T F ederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / etherlands Organisation for Applied Scientific Research TO report Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box 49

More information

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009 P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN 13501-1:2007+A1:2009 Classification

More information

BS EN : 2001 & IEC :2000

BS EN : 2001 & IEC :2000 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 60695-2-11: 2001 & IEC 60695-2-11:2000

More information

Reaction to fire classification report No C-rev.1

Reaction to fire classification report No C-rev.1 Reaction to fire classification report. 17241C-rev.1 Owner of the classification report Distributor: Vescom bv Churchilllaan 10 Sint Jozefstraat 20 5705 BK Helmond 5750 AB Deurne The Netherlands The Netherlands

More information

Additional reaction to fire classification report No H

Additional reaction to fire classification report No H Additional reaction to fire classification report. 12700H Owner of the additional classification report Antalis International 8 Rue de Seine 92517 Boulogne Billancourt Cedex France Introduction This additional

More information

Reaction to fire classification report No C

Reaction to fire classification report No C Reaction to fire classification report. 17911C Owner of the classification report Tapetex B.V. Distributor: Vescom bv Churchilllaan 10 Sint Jozefstraat 20 5705 BK Helmond 5750 AB Deurne The Netherlands

More information

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation

More information

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation

More information

IMO Resolution MSC 61(67): Annex 1: Part 2

IMO Resolution MSC 61(67): Annex 1: Part 2 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IMO Resolution MSC 61(67): Annex 1: Part

More information

Centrum stavebního inženýrství a.s.

Centrum stavebního inženýrství a.s. Centrum stavebního inženýrství a.s. Fire Technical Laboratory AUTHORIZED NOTIFIED BODY No. 22 BODY No. 90 CLASSIFICATION OF REACTION TO FIRE IN ACCORDANCE WITH ČSN EN 50-+A:200 Applicant: Příhoda s.r.o.

More information

Form: KSD-100:10 Page 1 of 3

Form: KSD-100:10 Page 1 of 3 /Translation from the Lithuanian language/ Form: KSD-100:10 Page 1 of 3 /Logo: GTC; DBS/ REACTION TO FIRE TESTING DIVISION FIRE REASEARCH CENTRE FIRE AND RESCUE DEPARTMENT UNDER THE MINISTRY OF THE INTERIOR

More information

TFI Report Classification

TFI Report Classification TFI Report Classification of the Reaction to Fire according to EN 13501-1:2010 Customer Unilin bvba, Division Flooring Ooigemstraat 3 8710 Wielsbeke BELGIUM Product wall covering Wall covering This report

More information

Classification Report

Classification Report Classification Report BASEC Client Report No. Hubbell Inc. (Delaware) L1CPRT801-1 Classification Number of pages in this Report: 6 Issue Date 3 January 2018 Items Tested 1 sample of Copper Communication

More information

NF X : Parts 1, 2, 3, 4 & 5

NF X : Parts 1, 2, 3, 4 & 5 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com NF X 10-702: Parts 1, 2, 3, 4 & 5 Fire test

More information

DELTA Classification Report

DELTA Classification Report DELTA Classification Report TEST Reg. no. 19 Reaction to fire classification report for electric cables: Cat 6A U/FTP 500 MHz FRNC Performed for Caleb Cable Industrial Ltd. no.: Page 1 of 9 19 December

More information

PUBLIC SUMMARY REPORT OF THE EGOLF EN 13823

PUBLIC SUMMARY REPORT OF THE EGOLF EN 13823 PUBLIC SUMMARY REPORT OF THE EGOLF EN 13823 ROUND ROBIN 2015-2016 Authors: Anne Steen-Hansen, RISE Fire Research Nick Neumann, MFPA Leipzig Richard Johansson, RISE Safety Marina Andersson, RISE Safety

More information

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor: IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2 Smoke & Toxicity Test WF Report Number: 166040 Date: 13 th August 2007 Test Sponsor: Fiba Tech Industries Ltd. 0249 Page 2 of 13 Bodycote warringtonfire

More information

Not all insulation is the same! from fire testing to real fires.

Not all insulation is the same! from fire testing to real fires. Not all insulation is the same! from fire testing to real fires. Introduction fire performance is not a simple science > two most important aspects of fire certification for insulation products are: >

More information

New European Cable Testing and Classification

New European Cable Testing and Classification New European Cable Testing and Classification THE BENCHMARK IN FIRE TESTING New European Cable Testing and Classification Cables will be tested using 5 test methods, and classified by extending the provisions

More information

Analysis Report

Analysis Report Prestige Carpets bvba Dhr. Dirk Santens Klein Frankrijk 38 9600 RONSE Your notice of Your reference Date 19-06-2013 24-07-2013 Required tests : Identification number T1309624 Information given by the client

More information

CERTIFICATE OF APPROVAL No ME 5085

CERTIFICATE OF APPROVAL No ME 5085 CERTIFICATE OF APPROVAL No ME 5085 1 Suite No. 52, 5 th Floor, Martin Burn Building, 1 RN Mukherjee Road, Kolkata- 700001 (West Bengal), India Tel: +91 33 40276600 Have been assessed against the requirements

More information

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in INFRASTRUCTURE TECHNOLOGIES Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in accordance with AS/NZS 3837:1998 Fire Testing Report Author: Heherson Alarde Report Number:

More information

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor: BS EN 61034-2: 2005 Measurements Of Smoke Density Of Electric Cables WF Report Number 177599 Date: 17 th November 2008 Test Sponsor: FTC Fabbrica Trentina Conduttori Srl 0249 Page 2 of 13 Bodycote warringtonfire

More information

Review Fire Test Report

Review Fire Test Report Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Review Fire Test Report Determination of

More information

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 153420 Date: 28 th April 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 153420 BS 476: Part

More information

REVIEW ON TWO PERFORMANCE-BASED TESTS FOR ASSESSING FLAME SPREAD IN HONG KONG

REVIEW ON TWO PERFORMANCE-BASED TESTS FOR ASSESSING FLAME SPREAD IN HONG KONG , Volume 5, Number 3, p.69-81, 2003 REVIEW ON TWO PERFORMANCE-BASED TESTS FOR ASSESSING FLAME SPREAD IN HONG KONG C.W. Leung Department of Building Services Engineering, The Hong Kong Polytechnic University,

More information

BS 476: Part 6: 1989+A1:2009

BS 476: Part 6: 1989+A1:2009 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 6: 1989+A1:2009 Method Of Test

More information

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? Marcelo M. Hirschler GBH International, USA ABSTRACT The results of three

More information

Information Data Sheet. Fire behavior of decorative high pressure laminates (HPL)

Information Data Sheet. Fire behavior of decorative high pressure laminates (HPL) Information Data Sheet Fire behavior of decorative high pressure laminates (HPL) November 2009 1 Introduction Decorative laminate (HPL = High-pressure laminate) can look back on a long tradition of use

More information

CLASSIFICATION IN REGARD OF REACTION TO FIRE according to EN :2007

CLASSIFICATION IN REGARD OF REACTION TO FIRE according to EN :2007 SWORN TRANSLATOR & INTERPRETER OF THE ENGLISH LANGUAGE Provincial Court Gdansk, Poland EWA KOCIK 7/9 Czubinskiego Street 80-215 Gdansk tel. (48) 58 345 50 76, (48) 509 209 454 logo : Certified translation

More information

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy BS 476: Part 7: 1997 on K-Flex IN Clad Foil Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, 36 20877 RONCELLO (MB) Italy 30 th October 2012 0578 Page 1 of 6 Prepared on behalf of BRE Global

More information

CPR: EUROCLASSIFICATION & TESTS FOR CABLES

CPR: EUROCLASSIFICATION & TESTS FOR CABLES Séance d information «Câbles dans la construction, quoi de neuf?» / Informatiesessie Kabels in de bouw, wat voor nieuws is er? CPR: EUROCLASSIFICATION & TESTS FOR CABLES ervé Breulet CPR & Cables June

More information

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC)

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) P. Van Hees and J. Axelsson, SP Sweden, S. J. Grayson and A. M. Green, Interscience Communications UK, H Breulet, ISSeP Belgium and U Vercellotti,

More information

Fire Test Reports for Interpon D Powder Coatings

Fire Test Reports for Interpon D Powder Coatings Akzo Nobel Powder Coatings Ltd. Specification Fire Test Reports for Interpon D Powder Coatings Explanations and collations of key reports and approvals for the UK market. July 2017 Russell Deane Powder

More information

Harmonisation and equivalence of reaction-to-fire performance classification in Europe: a small-scale desk-based study

Harmonisation and equivalence of reaction-to-fire performance classification in Europe: a small-scale desk-based study Harmonisation equivalence of reaction-to-fire performance classification in Europe: a small-scale desk-based study Prepared for: ADCAS 2 Waltham Court, Milley Lane, Hare Hatch, Reading, Berkshire RG10

More information

Test report. NanoPhos coating system EPR and EEN. Name of client: NanoPhos SA. Date: Pages: 5 Encl.: 1 Ref: BP / KTO

Test report. NanoPhos coating system EPR and EEN. Name of client: NanoPhos SA. Date: Pages: 5 Encl.: 1 Ref: BP / KTO Test report NanoPhos coating system EPR and EEN Name of client: NanoPhos SA File no.: PFB10173A Date: 2015-10-14 Pages: 5 Encl.: 1 Ref: BP / KTO Danish Institute of Fire and Security Technology Jernholmen

More information

BS 476: Part 6: 1989+A1:2009

BS 476: Part 6: 1989+A1:2009 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 6: 1989+A1:2009 Method Of Test

More information

SUBJECT: ASSESSMENT FOR INTERNAL SURFACE FINISHES OF LIGHTBETON PANEL FOR COMPLIANCE WITH THE NEW ZEALAND BUILDING CODE(NZBC)

SUBJECT: ASSESSMENT FOR INTERNAL SURFACE FINISHES OF LIGHTBETON PANEL FOR COMPLIANCE WITH THE NEW ZEALAND BUILDING CODE(NZBC) 07 th May 2018 Ref: /jobs/18039 Light Beton Panel compliance.doc Plytech International Ltd 23 Business Parade North Highbrook Auckland 2013 Email: craig.f@plytech.co.nz Attention: Craig Floyd SUBJECT:

More information

Analysis Report

Analysis Report Forbo Flooring Coral nv Dhr. Jan van Galen Postbus 17 1560 AA KROMMENIE Nederland Your notice of Your reference Date 08-02-2016 23-02-2016 Analysis Report 16.00634.08 Required tests : Identification number

More information

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Page 1 of 27 Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Test Sponsor Saveguard (UK) Limited Warrington Fire Research Centre Ltd.,

More information

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 158117 Date: 13 th October 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 158117 BS 476:

More information

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013 SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT ACCORDING TO THE EUROPEAN STANDARD NF EN 13501-1+A1:2013 Notification by the French Government to the European

More information

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com EN 45545-2: 2013 Summary Test Report Requirement

More information

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: Page 1 of 10 TEST REPORT REPORT NUMBER: 102317918SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112

More information

TFI Report Reaction to fire test

TFI Report Reaction to fire test TFI Report 450740-07 Reaction to fire test For the classification according to EN 13501-1:2010 Customer GÜLSEVEN HALI GÜLSEVEN TEKSTIL KIMYA GIDA SAN. TIC. LTD. STI Ahi Evran Sanayi Sitesi Istiklal Caddesi

More information

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013 SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE CLASSIFICATION REPORT ACCORDING TO THE EUROPEAN STANDARD NF EN 13501-1+A1:2013 Notification by the French Government to the European

More information

Report VNLF Test Report

Report VNLF Test Report Report VNLF 081158.1 Test Report Applicant KLEEN-TEX Industries in Europa GmbH Münchner Straße 21 6330-Kufstein Austria Reference Mrs. Antje Schlegel Application Determination ofthe burning behaviour according

More information

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA

More information

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IEC 60331-11-21 Method of test defined in

More information

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6 Test Report No. AJD201302471 Date: JUN.09, 2013 Page 1 of 6 WALER PRECISION MFG. SDN. BHD. NO.2, JALAN CANGGIH 1, TAMAN PERINDUSTRIAN CEMERALNG, 81800 ULU TIRAM, JOHOR, MALAYSIA. The following sample(s)

More information

Construction Products Directive

Construction Products Directive Construction Products Directive Evaluation of conformity of Heat soaked thermally toughened soda lime silicate safety glass to he N 14179-2 ( September 2006) G E P V P, T H E E U R O P E A N A S S O C

More information

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions. BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions WF Report Number: 147709 Test Sponsor: FTC - Fabbrica Trentina Conduttori

More information

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection

Passive fire protection. 6 Passive fire protection. 6.1 Fire compartmentation. Passive fire protection 6 Inside buildings there are two types of fire protection systems: Active Fire Protection and Passive Fire Protection. Both systems should actively work together in the event of a fire. 6.1.1 The four

More information

MFPA Leipzig GmbH Prüf-, Überwachungs- und Zertifizierungsstelle für Baustoffe, Bauprodukte und Bausysteme

MFPA Leipzig GmbH Prüf-, Überwachungs- und Zertifizierungsstelle für Baustoffe, Bauprodukte und Bausysteme Prüf-, Überwachungs- und Zertifizierungsstelle für Baustoffe, Bauprodukte und Bausysteme Geschäftsbereich III - Dr.-lng. Peter ause Arbeitsgruppe 3.1 - Brandverhalten von Bauprodukten Mathias Claus Telefon

More information

FAÇADE FIRE TESTS Towards a new European standard method

FAÇADE FIRE TESTS Towards a new European standard method FAÇADE FIRE TESTS Towards a new European standard method Lars Boström November 22, 2017 RISE Research Institutes of Sweden Safety Content Current state in Europe regarding façade fire tests History on

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings

More information

TFI Report Classification

TFI Report Classification TFI Report Classification of the Reaction to Fire according to EN 13501-1:2010 Customer Stuttgarter Straße 75 74321 Bietigheim-Bissingen GERMANY Product resilient floor covering Product 1: Scala 55 Connect

More information

C-01 FIRE DECKS AND BULKHEADS

C-01 FIRE DECKS AND BULKHEADS Guideline No.: C-01(201510) C-01 FIRE DECKS AND BULKHEADS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information UL 2360 Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction General Information UL 2360 - Test Methods for Determining the Combustibility

More information

Facts about insulation and fires 29 October 2014

Facts about insulation and fires 29 October 2014 Facts about insulation and fires 29 October 2014 Not all insulation is the same Real fire case studies involving Insurer approved PIR sandwich panels and insulation boards. Roy Weghorst Head of regulatory

More information

Classification of Fire Performance of Wall and Ceiling Lining Materials

Classification of Fire Performance of Wall and Ceiling Lining Materials Classification of Fire Performance of Wall and Ceiling Lining Materials Using the Method of Kokkala, Thomas and Karlsson Reference: Kokkala, M.A. Thomas, P.H. and Karlsson, B. Rate of Heat Release and

More information

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E. Benefiting Government, Industry and the Public Through Innovative Science and Technology Barry L. Badders, Jr. P.E. 7 December 2011 Part 1 Non-Combustibility Test Part 3 Test for A, B,, and F Class Divisions

More information

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls Journal of Mechanics Engineering and Automation 5 (2015) 465-471 doi: 10.17265/2159-5275/2015.08.007 D DAVID PUBLISHING Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

More information

Guidance Note. 3. Fire Propagation and flame Flame Spread in in Powder Coatings. Abrasion Resistance of Fluoropolymer and polyester Coatings

Guidance Note. 3. Fire Propagation and flame Flame Spread in in Powder Coatings. Abrasion Resistance of Fluoropolymer and polyester Coatings Guidance Note 3. Fire Propagation and flame Flame Spread in in Powder Coatings Abrasion Resistance of Fluoropolymer and polyester Coatings British Standards British Standard 476 refers to fire tests on

More information

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota Architectural Testing TEST REPORT Report No.: D7913.05-121-24 Rendered to: 3M COMPANY St. Paul, Minnesota PRODUCT TYPE: Window Film SERIES/MODEL: 3M Scotchshield Ultra 800 TEST METHOD: ASTM E 84-11a, Standard

More information

ASSOCIATION POUR LA CERTIFICATION DES MATERIAUX ISOLANTS

ASSOCIATION POUR LA CERTIFICATION DES MATERIAUX ISOLANTS Revision index Effective date C 15/02/2015 ASSOCIATION POUR LA CERTIFICATION DES MATERIAUX ISOLANTS 4, avenue du Recteur-Poincaré, 75782 Paris Cedex 16 Tel. 33 (0)1.64.68.84.97 Fax. 33 (0)1.64.68.83.45

More information

Method of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions.

Method of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions. Method of test defined in IEC 60331-21 for determining the circuit integrity performance of a cable under fire conditions. WF Report Number: 148371 Test Sponsor: FTC - Fabbrica Trentina Conduttori Srl

More information

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria TEST REPORT Report No.: E6736.01-121-24 Test Date: May 6, 2015 Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria PRODUCT TYPE: Max Exterior F-Quality SERIES/MODEL: Décor. 0085 TEST METHOD:

More information