Motor control and protection unit M10x parameter description

Size: px
Start display at page:

Download "Motor control and protection unit M10x parameter description"

Transcription

1 Motor control and protection unit M10x parameter description

2 The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. In no event shall ABB be liable for direct, indirect, special, incidental, or consequential damages of any nature or kind arising from the use of this document, nor shall ABB be liable for incidental or consequential damages arising from use of any software or hardware described in this document. This document and parts thereof must not be reproduced or copied without ABB s written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. The software described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. All rights reserved. Copyright 2016 ABB 2 Motor control and protection unit M10x parameter discription

3 Table of contents General Target group Use of warning, caution, information and tip icon Terminology Related documentation Related system version Document revision history New features available in enchanced products Document overview Motor Information Motor ID Motor type System supply voltage(m102 only) System frequency Motor power rating Motor nominal current (N1) Motor nominal current (N2) Motor control Starter ID (M10x-M only) Starter type Startup time Startup time (N2) (M102 only) Changeover time (M102 only) Ramp up time (M102 only) Ramp down time (M102 only) Earth fault primary Internal CT primary Communication failure delay Failsafe mode Feedback Feedback timeout External CT used External CT1 primary External CT2 primary External CT secondary COMMS. Modbus communication PROFIBUS DP communication Control authority Motor control mode Motor grouping enable, disable Group start direction Group ID (M10x-M only) Group number Group start delay Group stop delay M10x Parameter description Motor control and protection unit 3

4 Digital inputs Contact type Operation delay Operation Digital outputs Start/stop delay Operation principle Thermal overload protection (TOL) enable, disable Thermal mode Trip class (T6) Trip class (Te) Ia/In TOL alarm level TOL trip level TOL reset level Trip reset mode TOL bypass enable/disable Cooling coefficient (Mt6) Ambient temperature Staff protection enable, disable Trip level Trip delay Trip reset mode Phase failure protection enable, disable Alarm level Trip level Trip delay Trip reset mode Unbalance protection enable, disable Alarm level Trip level Trip delay Trip reset mode Underload protection enable, disable Alarm level Trip level Trip delay Trip reset mode Noload protection enable, disable Alarm level Trip level Trip delay Trip reset mode Motor control and protection unit M10x parameter discription

5 Earth fault protection enable, disable Enable earth fault protection during motor startup Alarm level Trip level Trip delay Trip reset mode PTC protection (M102 only) enable, disable PTC alarm level PTC trip level PTC trip delay PTC reset level PTC short circuit alarm level PTC trip reset mode Undervoltage protection (M102 only) enable, disable Alarm level Trip level Trip delay Reset level Trip reset mode Autorestart function (M102 only) enable/disable Maximum autoreclose time Maximum power downtime Staggered start delay Start limitation protection enable, disable Time interval Number of starts Long start protection enable, disable Locked rotor level Locked rotor delay Phase sequence protection Maintenance Running time alam level Start number alarm level Diagnosis information (M10x-P) only) User definable map (M10-M only) User definable data (M10x-P only) MD LED Color MD21 display option M10x Parameter description Motor control and protection unit 5

6 General Target group This manual provides information on the internal parameters of M10x for the purpose of understanding, engineering, testing, system integration or commissioning of the product. Each chapter consists of brief explanations of the functions, the relevant parameters and the parameter descriptions, along with ranges. Default values of all parameters are listed in appendix Factory settings for M10x. Examples and further explanations are provided for user reference in parameterization. Use of warning, caution, information and tip icon This publication includes Warning, Caution, and Information icons where appropriate to point out safety related or other important information. It also includes Tip icons to point out useful hints to the reader. The corresponding symbols should be interpreted as follows The electrical warning icon indicates the presence of a hazard that could result in electrical shock. The warning icon indicates the presence of a hazard that could result in personal injury. The caution icon indicates important information or warnings related to the concept discussed in the text. It might indicate the presence of hazard that could result on corruption of software or damage to equipment/property. The information icon alerts the reader to pertinent facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function Although Warning notices are related to personal injury, and Caution notices are associated with equipment or property damage, it should be understood that the operation of damaged equipment could, under certain operational conditions, result in impaired process performance leading to personal injury or death. It is, therefore, imperative that you comply fully with all Warning and Caution notices. 6 Motor control and protection unit M10x parameter discription

7 Terminology List of terms, acronyms, abbreviations and definitions used in the document Abbreviation Term Alarm Alarm is defined as status transition from any state to abnormal state. Status transition to abnormal state can be data crossing over the pre-defined alarm limit. DCS Distributed control system High level distributed control system Hardware hardwiring A control access term describing that the M10x accepts its commands from the hardwired inputs when the local control authority is enabled. PCS Process control system High level process control system PROFIBUS-DP Modbus Modbus RTU PROFIBUS-DP/V1 Fieldbus communication protocol with cyclic data transfer (V0) Fieldbus communication protocol Fieldbus communication protocol Fieldbus communication protocol, extension of PROFIBUS-DP allowing acyclic data transfer and multi master (V1) PTC Positive temperature coefficient PTC thermistors are semiconductor elements with a very high positive temperature coefficient. RCU Remote control unit Local control unit with pushbutton and indicator to operate a device (eg, motor) from field level. Remote fieldbus A control access term describing that the M10x accepts its commands from the fieldbus inputs when the remote control authority is enabled. RS485 Communication interface standard from EIA (Electronics Industries Association, USA), operating on voltages between 0V and +5V. RS-485 is more noise resistant than RS- 232C, handles data transmission over longer distances, and can drive more receivers. STP Shielded twisted pair A type of cable commonly used for signal transmission. TOL Thermal overload Protection against overheated caused by overload Trip A consequence of an alarm activated or an external trip command from another device to stop the motor or trip the circuit breaker. MCC Motor control center Common term for a switchgear used for motor control and protection. SOE Sequence of events A record of events with time stamp. M10x Parameter description Motor control and protection unit 7

8 Related documentation 1TNC M10x User Guide 1TNC M10x-P PROFIBUS Protocol Implementation 1TNC M10x-M Modbus Protocol Implementation 1TNC MCUSetup User Guide Related System Version The content of this document is related to M10x products with the following hardware and firmware version release HW FW M10x-M 24VDC M10x-M 110VAC M10x-M 240VAC M10x-P 24VDC M10x-P 110VAC M10x-P 240VAC MD MD Until further notice, this document is also applicable for future firmware versions. The described functions are designed but may not be fully implemented in all details. Please refer to the release notes regarding possible restrictions. Document revision history Revision of change Date M0201 Initial Edition 10/2003 M0202 Change Earth Fault Setting; Revise the Terminology of Control Authority; Revise DI 04/2008 M0203 Template Changed as per BU Guideline 10/2010 M0204 Released for M10x products with new hardware, suitable for both M10x-M and M10x-P 01/2013 M0205 Add feedback timeout and DO function 07/2013 M0206 Add in Phase sequence protection and more DO functions, main switch supervision function. 09/ Motor control and protection unit M10x parameter discription

9 New features available in enhanced products In comparison with previous firmware and hardware revisions General features 1 One single type of integrated CT ranging from 0.24~63A replaces all 6 types of CTs in previous products. 2 Products with options for 110VAC or 240VAC power supply and DI types are available in addition to 24VDC option. 3 Additional SOE function in M102 provides event recorder data up to 256 events with time stamp. 4 Products in the same categories are made with the same features and functionalities and are only different in power supply and communication interface from each type. For example, M101's range of products has identical functionalities regardless of different types of power supply and interfaces, such as M101-M 24VDC, M101-P 240VAC, etc. Physical dimension 1 Main unit dimension remains the same as previous revision. MDx panel is slightly larger in width and length (both 3mm extra) while cutout dimension remains the same. Control features 1 Contactor feeder and contactor feeder/rcu are added into starter types. 2 Two separate start types are available for two-speed starters. NR_2N is for two-speed motor with separate windings while NR_2N Dahlander is for Dahlander connection motor. 3 Control logic in NR_softstarter and REV_softstarter are modified slightly. 4 Control authority feature in M10x-M has been revised to be identical to M10x-P. Digital inputs and outputs 1 All DIs in M10x are configurable and also selectable with NO or NC. 2 E-stop, Limit 1, Limit 2, External trip input control definition has been revised. 3 More features are added to DOs. Protection 1 Long start protection is available to provide stall protection during motor startup. 2 Options are provided to enable or disable TOL protection during motor startup. 3 PTC short circuit protection and PTC open circuit protection are available. Communication 1 Additional communication speeds are available for MODBUS bps and bps. Measuring and monitoring 1 Additional running data are monitored, such as current phase unbalance, thermistor resistor, time to TOL trip, time to TOL reset, startup time, DI status. 2 Phase-to-phase instead of phase-to-neutral voltage is directly measured. Maintenance 1 More maintenance features are implemented, including providing number of trips, SOE with time stamp, etc. Operator panel MDx 1 MDx is provided as IP54. 2 Color and function of LEDs are selectable. 3 Messages on MD21 are selectable. 4 Two languages are supported, ie, English and Chinese. 5 Parameter setting via MD21 is available. 6 Parameter setting port on MDx is mini USB connector in lieu of USB connector. M10x Parameter description Motor control and protection unit 9

10 Document overview M10x parameterization can be done from a several laptop/workstation with MCUSetup software, or via operation panel MD21. The motor related parameters and the protection function are set based on the motor manufacturer s data sheet. M10x parameterization is mainly classified into the following functions Motor information Motor control COMMS (communication) Control authority Motor grouping Digital inputs Digital outputs TOL protection Stall protection Phase failure protection Unbalance protection Underload protection Noload protection Earth fault protection PTC protection (M102 Only) Undervoltage protection & sutorestart (M102 only) Start limitation protection Long start protection Maintenance Diagnosis information (M10x-P only) User defined map (M10x-M only) User defined data (M10x-P only) MD LED MD Display option (MD21 only) s are further subdivided into parameters, to be set individually. Above functions and their related parameters are covered in each of the subsequent chapters. 10 Motor control and protection unit M10x parameter discription

11 Motor information Motor information consists of parameters that mainly reflect the motor ratings. Parameters involved with the motor Information are as below Motor ID Motor type System supply voltage (only for M102) System frequency Motor power rating Motor nominal current Motor nominal current (N2) (only for M102) Motor ID Motor information space! # $ % & ( ) +, ; A Z[ ] ^ _ a z { } ~ MOTOR1 -- A maximum length of 20 characters (ASCII) can be assigned to an identifier to describe the location or function of the motor. M10x-P supports only maximum 4 characters (ASCII). Motor Type Motor information 1 = Single phase, 3 = Three phases 3 = Three phases Motor control/starter type Phase failure protection/function Unbalance protection / function M10x can handle a single- or three-phase AC motor. Based on the number of phases of the motor, single or three can be selected. For single-phase motors, the motor current lead or the CT secondary lead (for > 63 A) is passed through L1 phase window of the M10x internal current transformer. Single phase application is practicable with NR-DOL starter type. Neither the phase failure protection nor the unbalance protection is available for the application. M10x Parameter description Motor control and protection unit 11

12 System supply voltage (M102 Only) Motor information 110(1)690V 380V -- This parameter is to be selected per system supply design value. System frequency Motor information 50/60Hz 50Hz -- System frequency is a measured parameter when voltage is measured by M10x, for example a M102 with voltage inputs wired. It is a fixed value when voltage is not measured, e.g M101. It is for reference only and does not affect operation of the M10x. Motor power rating Motor information 0.01(0.01)1000kW 1.5kW Motor information/motor nominal current Motor information/motor nominal current (N2) This is the reference data at rated voltage and frequency. The value is given on the motor rating plate and does not affect operation of the M10x. Motor nominal current (N1) Motor information 0.08(0.01)63.0A or Iprim or Iprim 4A Motor information/motor power rating Motor control/external CT parameters This is the rated current In of the motor, at rated load, at rated voltage and frequency. The value is given on the motor rating plate. The rated current can be set within this range. 12 Motor control and protection unit M10x parameter discription

13 N1 setting is related to External CT primary and External CT secondary settings under Motor control. Setting range without selecting external CT option is from A. If external CT is selected, the range is dependent on the primary and secondary of external CT, ie, If External CT secondary is set to 1, the range varies from 0.5 to 1.0 of CT nominal primary current. If External CT secondary is set to 5, the range varies from 0.1 to 1.0 of CT nominal primary current. Example In the case of an external current transformer primary of 100A, the range varies from 50 to 100A when external CT secondary is selected as 1. The range can also be from A if secondary of 5A is selected. Motor nominal current (N2) Motor information 0.08(0.01)63.0A or Iprim or Iprim 4A Motor information/motor power rating Motor control/internal CT primary, external CT parameters This is the rated current In of the motor, at rated load, at rated voltage and frequency. The value is given on the motor rating plate. The rated current can be set within this range. N2 setting is related to External CT primary and External CT secondary settings under Motor control. This setting is available for two-speed motors where the second set of CT is required. The setting range and reading is the same as for N1. Applicable to both N1&N2In cases of small current measurement (<0.5A) it is highly recommended to increase the primary wiring turns through internal CT in order to avoid nuisance current measurement. Refer to relevant parameter 'Internal CT primary winding'. M10x Parameter description Motor control and protection unit 13

14 Motor control Motor control function consists of parameters which reflect the configuration of the motor feeder. For example, the ratings for external current transformers and contactor feedback supervision are included. Parameters involved with the starter configuration function are Starter ID Starter type Startup time Startup time (N2) (M102 Only) Changeover time (M102 Only) Ramp up time (M102 Only) Ramp down time (M102 Only) Earth fault primary Internal CT primary Communication failure delay Failsafe mode Feedback Feedback timeout Soft test switch External CT used External CT1 primary External CT2 primary (M102 Only) External CT secondary Starter ID (M10x-M Only) Motor information space! # $ % & ( ) +, ; A Z[ ] ^ _ a z { } ~ A1 -- The user can name each motor starter to simplify addressing and handling. A maximum of 20 characters (ASCII) can be assigned. 14 Motor control and protection unit M10x parameter discription

15 Starter type Motor control M101 NR-DOL, NR-DOL/RCU, REV-DOL, REV-DOL/RCU, Feeder, Contactor feeder, Contactor feeder/rcu M102 NR-DOL, NR-DOL/RCU, REV-DOL, REV-DOL/RCU, Actuator, NR-S/D, NR-2N, NR_2N Dahlander, Autotransformer, NR_softstarter, REV_softstarter, Feeder, Contactor feeder, Contactor feeder/rcu NR-DOL Motor control/failsafe mode Motor control/n2 parameters (NR-2N, NR_2N Dahlander) Motor control/s/d parameters (NR-S/D) Motor control/autotransformer parameters Motor control/ramp up/downtime M10x supports different kinds of motor connections. This parameter needs to be set according to the type of motor control desired. More details of M10x starter types are described in the M10x user guide. NR-DOL Non reversing direct on line. NR - Non reversing means the motor runs in only one direction. When M10x accepts start command, internal relay CCA is closed and remains closed until stop command is accepted or protection function is active. Internal relay CCB and CCC has no functions in this application. Internal relay CCB and CCC has no functions in this application. NR-DOL/RCU Non reversing direct on line RCU starter RCU stands for, remote control unit. This is a starter type where contactors can be directly hardwired controlled by a control device located near the motor in parallel with M10x control. In other word, this starter allows motor control by remote control device even if M10x is not in operation. When M10x accepts Start CW command, internal relay CCA is closed and remains for one second only. When Stop command is accepted or protection is active, CCC relay is closed to cut the contactor coil circuit and remains for one second only. The wiring of the self-auxiliary contact across the start command latches the contactor. M10x Parameter description Motor control and protection unit 15

16 REV-DOL Reversing direct on line REV- Reversing starter supports the motor running in both directions (clockwise CW, counter clockwise CCW). When M10x accepts start 1 command, internal relay CCA is closed to start motor running in one direction and remains closed until stop command is accepted or protection function is active. Same operation is followed the opposite direction after accepting start 2 command. Possible changing direction sequence is as follows Start 1- Stop-Start2 Start 2- Stop-Start1 REV-DOL/RCU Reversing direct on line RCU starter In addition to NR-DOL/RCU, this starter supports the motor running in both directions. Actuator (M102 only) Actuator starter is for controlling valves, dampers and actuators by using limit switches. The limit switch stops the motor when activated, after the motor is running in one direction. The activated limit switch message is then read in M10x and only Start 2 command for reserve direction is allowed. In case of an actuator starter with torque sensor, the torque switch associated with the sensor is used to stop the motor. The limit switch limits starting to the respective direction and indicates the respective stop position. One of the digital inputs can be used as input for the torque sensor. If the torque activates before the limit switch, the motor is tripped with a message DI trip. NR-S/D (M102 only ) Reduced voltage starts in star and runs the motor in delta after transition conditions are met. Star-delta starters are used mainly to restrict the starting current of a motor due to supply limitations. The motor is started with the winding connected in star and transferred to delta after the changeover time. Starting at a lower voltage also reduces shocks on the motor coupling, belts and gear mechanisms. Starting current and the torque are reduced to 1/3 of the DOL value. However, it must be determined whether the reduced motor torque is sufficient to accelerate the load over the whole speed range. 16 Motor control and protection unit M10x parameter discription

17 The changeover is based on time, the star-to-delta transition takes place after the parameterized changeover time. The star-to-delta switchover is done with a maximum transition time to ensure quenching of the arc in star operation before it changes over to delta to prevent short-circuit. During the contactor transitions, the M102 waits until the previous sequence is successfully completed. In case of any contactor failure, the feedback supervision trip will open all the contactors. NR-2N (M102 only) Non-reversible two-speed motor separate winding Two-speed drives are used for applications requiring dual motor outputs. NR-2N is the starter designed for two separate winding motors. Please refer to the user guide for more details on function description. Current measurement for NR-2N utilizes two sets of external CTs, measuring current from main supply. External CTs can be selected separately for both motor windings. NR-2N Dahlander (M102 only) Non-reversible two-speed motor Dahlander connection Two-speed drives are used for applications requiring dual motor outputs. NR-2N Dahlander is the starter type designed for motors with Dahlander connection. Please refer to the User Guide for more details on function description. Autotransformer (M102 only) Non-reversible motor starter based on reduced voltage via auto-transformer Autotransformer starter supports motor starting with reduced voltage, providing reduced motor startup current. As a result, the starting torque is reduced accordingly. M10x Parameter description Motor control and protection unit 17

18 NR_softstarter (M102 only) Non-reversible softstarter control Softstarter applications are for controlling motor accessory softstarter devices. M10x gives start and stop commands to the softstarter unit. The softstarter is set for adjusting motor voltage with its own parameters. More information about softstarter can be found in the softstarter manual. Please refer to the User Guide for more details on function description. Rev_softstarter (M102 only) Reversible softstarter control ality of this starter type is according to NR-softstarter with support for reversing motor direction. Please refer to the User Guide for more details on function description. Feeder The feeder application is regarded as a specific starter type in M10x. For feeder mode, the dedicated motor protections are either auto-inhibited or prohibited via parameter setting. The circuit breaker trip signal is detected by M10x via specified inputs before an alarm sounded. All measurement and control functions are activated for this application. Note The internal relays CCA and CCB are electrically interlocked for all starter types. Contactor feeder Feeder control by contactor When a start command is given, the internal relay CCA remains closed until a stop command is given. The internal relay CCB and CCC has no function here. Contactor feeder/rcu Feeder control by contactor on line (remote control of the contactor, bypassing the M10x). The start CW command closes the internal relay CCA for 1sec respectively. The stop command will close relay CCC for 1 sec. The wiring of the self-auxiliary contact across the start command latches the contactor. Removing the M10x from the starter will not prevent RCU operation depending however which the connection (external relay and/or switch) is used for start and stop). The stop pulse issued by the M10x will override the RCU-switch start position. 18 Motor control and protection unit M10x parameter discription

19 Startup time Motor control 1 (1) 250 s 5s Motor control/starter type (all) Motor control/changeover time TOL protection/tol alarm Stall protection/ enable, disable Phase failure protection/ enable, disable Unbalance protection/ enable, disable Earth fault protection/ enable, disable Underload protection/ enable, disable Noload protection/ enable, disable Motor startup time parameter is used to define the maximum startup time for the motor. It is the time that is required for the motor to complete its starting sequence. The starting sequence is said to be complete when the startup current reaches 1.25 times the nominal current. This parameter defines the length of time for the startup phase of the motor during which most of the protection functions and alarm messages are deliberately suppressed. Protection type TOL protection Stall protection Long start protection Phase failure protection Unbalance protection Underload protection Noload protection Earth fault protection PTC protection Undervoltage protection Start limitation Phase sequence Suppressed during motor startup Selectable during motor startup M10x Parameter description Motor control and protection unit 19

20 Startup time (N2) (M102 Only) Motor control 1 (1) 250 sec 5sec Motor control/motor startup time (N1) Motor control/starter type (NR-2N, NR-2N Dahlander) This parameter has the same definition as the previous parameter, Motor startup time, except it is dedicated for speed N2. Changeover Time (M102 Only) Motor control 1 (1) 250 sec 5sec Motor control/starter type (NR-SD, NR-2N, NR-2N Dahlander, Autotransformer) Underload protection/enabled, disabled Noload protection/enabled, disabled This parameter is applied to both NR-SD starter, Autotransformer starter, NR-2N starter and NR-2N Dahlander starter. In the case of autotransformer starter, the parameter defines the time that the motor is running with reduced voltage. The motor changes to line voltage connection when the defined time has elapsed. For SD starter, the start-to-delta transition is executed after the defined time. For NR- 2N starter and NR-2N Dahlander starter, speed 2 will transfer to speed 1 after the defined time has elapsed. Ramp up time (M102 Only) Motor control 1 (1) 250 sec 10sec Motor control/starter type (NR-softstarter, REVsoftstarter) Phase failure protection Unbalance protection Underload protection Noload protection 20 Motor control and protection unit M10x parameter discription

21 Softstarter is a separate unit to motors smoothly by limiting inrush current. The ramp up time is the parameter of the softstarter set to start up the motor. During this delay, the following protection functions are deactivated - Stall, Phase failure, Unbalance, Underload, Noload, Undervoltage. M102 controls the motor by giving start/stop commands to the softstarter. The motor protection is done by the softstarter during startup. The accuracy of the current measurement in M10x may be compromised if no prevention measures are taken to reduce the harmonics caused by the soft starters! Ramp downtime (M102 Only) Motor control 1 (1) 250 sec 10sec Motor control/starter type (NR-DOL, REV-DOL) Phase failure protection Unbalance protection Underload protection Noload protection Softstarter unit has a parameter which is used to select the stop ramp time of the motor. M102 is adapted to this stop time by setting the ramp downtime not less than the selected stop ramp time of the motor. Earth fault primary Motor control 1A or 5A 1A Earth fault protection/ Earth fault protection/alarm level Earth fault protection/trip level The parameter defines the maximum primary current of the RCT. If 1A RCT is selected, the setting range of earth fault protection is 100mA~3A; If 5A is selected, the range is 500mA ~15A. M10x Parameter description Motor control and protection unit 21

22 Internal CT primary winding Motor control 1-5T 1T Motor information/nominal current Motor information/nominal current (N2) The parameter defines the windings of internal CT primary. When the nominal current is less than 0.5A (0.08<In<0.5), it is highly recommended to increase the primary winding to 2~5 turns and set this parameter as '2" or "5" accordingly. Refer to relevant parameters 'motor nominal current N1' and 'motor nominal current N2' Communication failure delay Motor control 1(1)25sec or 255sec 255sec Motor control/failsafe mode This parameter is to defines the maximum permitted period after M10x detects a communication interruption. After the permitted time delay elapses, M10x considers loss of communication and activates failsafe function. Meanwhile the message of communication failure will be sent and shown on operator panel MDx. If the the value is set at 255 sec, the communication failure function will not respond. Failsafe mode Motor control NOP/Start1(CW)/Start2(CCW)/Trip NOP Communication/Communication failure delay If a loss of communications is detected, the failsafe function is activated. M10x will then operate under failsafe mode, ie No operation Start motor direction 1 Start motor direction 2 Trip out motor When the failsafe function is activated, M10x control access authority is assigned to the local and MDx operator panel until communication is restored, regardless of which control access group had authority prior to communication loss. 22 Motor control and protection unit M10x parameter discription

23 Feedback Motor control Enabled/Disabled Enabled Motor control/starter type Motor control/feedback timeout M10x provides feedback supervision that monitors the status of motor and contactor after control command is given by M10x. Status is checked by using feedback signals (C_Fa,C_Fb, C_Fc) wired from contactor auxiliary contacts or by current measurement. Feedback function is fixed to enabled under most of the starter types where status of motor and contactor are checked through contactor auxiliary contacts. However, under starters NR-DOL and Contactor feeder, this function can also be set to disabled and status of contactor is checked through current measurement when feedback is set to disabled. Soft test switch Motor control Disabled, enabled Disabled Digital input//test switch Soft test switch parameter determines if M10x is under test mode. Alternatively the test mode can be enabled through the digital input test switch (hardwiring). When test mode is enabled, it is allowed to stimulate all control functions but ignores current based protection functions if zero current is measured. If current (>5% Ie) is detected under test mode, the protection functions are switched back on automatically. External CT used Motor control Disabled, enabled Disabled Motor control/nominal current Motor control/nominal current (N2) Motor control/external CT1 primary Motor control/external CT2 primary Motor control/external CT secondary When motor rating exceeds 63A, external intermediate CT is used. In case of NR-2N, external CTs may be selected for both windings and the secondary output rating of both external CTs remains the same. M10x Parameter description Motor control and protection unit 23

24 External CT1 primary Motor information 1(1) 6300 A 100A Motor control/nominal current Motor control/external CT used This parameter can only be set when external CT installed is enabled. Secondary output of external CT shall match with internal CT primary. For example, if external CT primary is selected as 2.5-5A, only CTs with 5A secondary are used for external CTs. External CT2 primary Motor information 1(1) 6300 A 100A Motor control/nominal current(n2) Motor control/starter type Motor control/external CT used Motor control/internal CT primary Motor control/external CT secondary This parameter is designed for the second sets of CTs under NR-2N starter. Example NR-DOL Motor rating 45kW, 86A, External CT 100/5, the settings are as follows Motor control/nominal current Motor control/nominal current(n2) Motor control/external CT used Motor control/internal CT primary Motor control/external CT1 primary Motor control/external CT2 primary Motor control/external CT secondary 86A Not active Enabled 0.24~63A 100A Not active 5A 24 Motor control and protection unit M10x parameter discription

25 External CT secondary Motor information 1, 5 1 Motor control/nominal current Motor control/nominal current(n2) Motor control/starter type Motor control/external CT used Motor control/internal CT primary Motor control/external CT secondary This parameter is designed for the secondary of external CT. M10x Parameter description Motor control and protection unit 25

26 COMMS. Modbus communication The communication function provided by M10x-M is based on Modbus RTU. The fieldbus interface is RS485. There are two identical RS485 interfaces, for redundant design. Parameterization, remote control, data acquisition and transmission etc., are implemented via the communication function. For more information on M10x-M communication, please refer to M10x User Guide and Modbus Protocol Implementation for M10x-M. The parameters involved with the protection function are Device address Parity check Redundancy Modbus baud rate Device address COMMS Each M10x-M on the same serial communication network must have a unique address in the range of 1 to 127. Computer software driving the serial network must be configured to recognize each separate address. M10x parity check COMMS Odd/Even/None None - This parameter determines what type of parity checking is used when communicating with the M10x-M. 26 Motor control and protection unit M10x parameter discription

27 Redundancy COMMS Enabled/disabled Disabled - There are two identical RS485 interfaces of Modbus RTU protocol in M10x-M for redundant design. When redundant communication is required, this parameter must be set as enabled to activate the standby communication port. Modbus baud rate COMMS 1200/2400/4800/9600/19200/38400/57600 bps 9600 bps - This parameter is to define the data transmission rate between M10x-M and an upper control system (such as DCS) or a workstation. M10x Parameter description Motor control and protection unit 27

28 PROFIBUS DP communication Relevant parameters to set up PROFIBUS DP communication interface are as follows Device address Operating mode Block DP Device address COMMS Each M10x-P on the same serial communication network must have a unique address in the range of 0 to 126. Computer software driving the serial network must be configured to recognize each separate address. Operating mode COMMS DPV1 DPV1 - For PROFIBUS DPV1, it allows cyclic and acyclic data exchange between master and slave station. Block DP COMMS Enabled/disabled Enabled - The block DP function determines whether M10x will update the parameters when receiving the initialization command from the upward system. If it is disabled, the parameters in M10x will be overwritten by the data transmitted from master station during startup of the DP master. If the selection is enabled, the updating command from master DP during startup will be ignored. Parameter setting will be allowed through MCUSetup software only. 28 Motor control and protection unit M10x parameter discription

29 Control authority M10x control authority is the term describing the privileges for allowing motor control operation through M10x. It is also a setting parameter in M10x to define which control access group has privilege to operate the motor via M10x. For detailed descriptions on control access in M10x, please refer to 1TNC D0205 M10x User Guide. PROFIBUS Option (Only in M10x-P) Control Authority PROFIBUS Auto Mode Active Enabled/ PROFIBUS Auto Mode Active Disabled Default Setting PROFIBUS Auto Mode Active Disabled Related Parameters Digital Inputs/Loc/R/Control Authority/Soft Local/ Remote Control Authority/MD Control When PROFIBUS auto mode active is enabled, M10x accepts the command from fieldbus to select the control access. Soft Local/Remote Control Authority Local Hardwiring / Remote Fieldbus Default Setting -- Related Parameters Digital inputs/loc/r /Control authority/profibus option When Local hardwiring is enabled, M10x accepts its commands from the hardwired inputs. When Remote Fieldbus is enabled, M10x accepts its commands from the hardwired inputs. MD Control Control authority MD (Operation panel)/md enable in Local/ MD enabled in Remote/ MD enabled when Auto Mode set 0 /MD enabled when Auto Mode set 1 Default Setting -- Related Parameters Digital inputs/loc/r/md control Control authority/profibus option When MD (Operator panel) is enabled, M10x accepts the command from operator panel MD Control authority M10x Parameter. M10x Parameter description Motor control and protection unit 29

30 Motor grouping In the case of conventional switchgear, the operator can start or stop a process by sequentially starting or stopping of the motors. The required delay between the motors is introduced either manually or with the help of a timer and serial interlocks. This increases the operators time, cabling and the initial cost of the starter. With the help of an intelligent system, the operator can start or stop the process with a single group command. The start and stop delay can be set for individual motors. The serial communication with logical connections between devices reduces the cabling, process interlocks and the hardware. In case of an abnormality in any motor of the group, a group tripping would follow. In this context, a motor group means a collection of motors, which are operated by an individual group start or stop command. The successful start of the motor group is indicated. Individual start/stop command from fieldbus can also be given to the devices located in the group as well as via the switches connected to the device I/O in the local mode. Motor grouping function is only available for PROFIBUS-DPV1. The parameters under motor grouping function are as below enable/disable Group start direction Group ID Group number Group start delay Group stop delay enable/disable Motor grouping Enabled/disabled Disabled Motor grouping/parameters Motor grouping function can be disabled with the help of this parameter. When disabled, motor group function does not have any functionality in the M10x and all other parameters of the function (group ID, group number, group start direction, group start/stop delay) are inactivated in the MCUSetup software. 30 Motor control and protection unit M10x parameter discription

31 Group start direction Motor grouping Start1/Start2 Start1 Motor grouping/parameters Motor control/starter type This parameter defines the direction of rotation of the motor when started by a group command. The rotating direction of the motor depends on the starter type parameter value. Group ID (M10x-M only) Motor grouping 16 characters GROUP1 Motor grouping/group number Group name is the name of the group to which the motors (M10x) belong. This name is used only for identity and has no impact on motor operation. Group number Motor grouping 1 (1) 9 1 Motor grouping/group identifier Each motor group is assigned with unique number. Group start Delay Motor grouping 0 (1) 300 sec 0sec Motor grouping/group start direction Motor control/startup time Motor grouping/group number This is the delay for motor start after receipt of the group start command. Group stop delay Motor grouping 0 (1) 300 sec 0sec - This is the delay for motor start after receipt of the group start command. M10x Parameter description Motor control and protection unit 31

32 Digital inputs The M10x has either 13 sets of 24VDC programmable digital inputs or 9 sets of 110VAC/240VAC programmable digital inputs for motor control and supervision. Each input can be configured with various functions according to the predefined list. These functions (Limit1, Limit2, PLC control1, PLC control2, F_CA, F_CB, F_CC, Loc/R, Main switch status, External trip) can only be assigned for one time at the same parameterization file. For each input, specific characteristic, such as Contact type, Delay etc., can be defined to different purposes. The parameters under digital inputs are as below Contact type Operation delay Operation Digital input NOP, Start1, Start2, Stop (edge trigger), Stop (level trigger), Limit1, Limit2, Process interlock1, Process interlock2, Test switch, Emergency stop, PLC control1, PLC control2, Trip reset, Torque switch, F_CA, F_CB, F_ CC, Loc/R, Main switch status, External trip, MD control, TOL Bypass. The power supply of DI is 24VDC M10x Digital inputs DI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10 DI11 DI12 Default function NOP NOP START1 START2 STOP NOP F_CA NOP NOP NOP NOP NOP NOP 32 Motor control and protection unit M10x parameter discription

33 The power supply of DI is 110V or 240VAC M10x Digital inputs DI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 Default function NOP NOP START1 START2 STOP NOP F_CA NOP NOP NOP Control authority/control mode Each digital input can be assigned to a specific function according to different purposes. The description of individual digital input function is available in '1TNC M10x User Guide', digital inputs section. M10x Parameter description Motor control and protection unit 33

34 Contact type Digital input NO/NC NO Digital input/ This parameter is used to define the normal state of the input, normally open or normally closed. Digital inputs have many functions for selection, and different functions have different characters as shown in the table below. Trigger mode Contactor type Start1 Edge triggering NO, NC Start2 Stop* Trip reset PLC control1 If the input status is different the the setting, the function will be active PLC control2 If the input status is the same Process interlock1 as the setting, the function will be active Emergency stop Level triggering NO, NC Torque switch Process interlock2 MD control External trip If the input status is different than the setting the function will be active Test switch Stop* TOL Bypass NOP Detects the input status only * Stop input can be edge trigger type or level trigger type 1. When motor starter type is Actuator, one of the digital inputs may be defined as torque switch input if needed. For wiring details, please refer to the User Guide. 2. When one of the digital inputs is defined as process interlock1, the input is regarded as unhealthy if the high/low is detected as the same type as the preset contact. For example, if the contact typed is set as NO type, a low input is regarded as unhealthy. With operation delay set to zero, motor start is prohibited when this unhealthy contact is detected. 3. When one of the digital inputs is defined as emergency stop, torque switch or external trip, the input is considered unhealthy if the high/low is different from the setting contact type. For example, if the contact type set is NO, a high input is considered unhealthy. 34 Motor control and protection unit M10x parameter discription

35 Operation delay Digital input s 0s Digital input//start1, start2, stop, process interlock1, process interlock2 For Start1, Start2, this parameter sets the amount of time that CCA,CCB,CCC can remain open during a motor start. For Stop, this parameter sets the amount of time that CCA,CCB,CCC can remain closed during of a motor stop. Process interlock1 sets the amount of time that the process interlock switch can remain open on the occurrence of a motor start. If the switch remains unhealthy for longer than this time, a trip/stop will occur. If this parameter is set to 0, the process interlock switch must be healthy in order for M10x to allow the motor to start. Process interlock2, sets the amount of time that the process interlock switch can be unhealthy during normal operation. If the switch remains unhealthy for longer than this time, a trip/stop will occur. Operation Digital input Stop/trip only/ alarm only/ trip and alarm Stop /process interlock1, process interlock2, Emergency stop This parameter determines whether DI feature is a trip (reset required in order to restart the motor) or a stop (no reset required) or an alarm (whenever the process interlock switch is unhealthy). M10x Parameter description Motor control and protection unit 35

36 Digital outputs The M101 range of products is equipped with one set of programmable digital outputs while two sets are equipped in the M102 range of products. The parameters under programmable outputs are Start/Stop delay Operation principle Digital outputs Energize on start delay, De-energize on stop delay, DIx status*, Trips, Specific Trip function (TOL, Earth fault trip, Stalled rotor trip, Phase failure trip.phase unbalance trip, Under-load trip, No-load trip,ptc trip,under-voltage trip, Start limitation trip, Long start trip,phase sequence trip), Alarms, Specific alarm function ( TOL, Earth fault alarm,overload alarm,phase failure alarm.phase unbalance alarm, Under-load alarm, No-load alarm,ptc alarm, PTC short circuit alarm, PTC open circuit alarm,under-voltage alarm, Start limitation alarm, Under-voltage alarm, Autoreclose alarm), Watchdog, Communication Failure, RCU mode, Local_remote output, Contactor welded, Ready to start. Fieldbus control Digital outputs/start/stop delay The description of individual function is available in document 1TNC M10x User Guide, Digital Outputs section. * DIx status in case of 24VDC M10x, DIx=DI9, DI10 &DI11; In case of M10x AC type, DIx=DI0,DI1 &DI2. 36 Motor control and protection unit M10x parameter discription

37 Start/stop delay Digital outputs 0 (0) 125sec Digital outputs//energize on motor start delay Digital outputs//de-energize on motor stop delay Only use for the function Energize on motor start delay and the function De-energize on motor stop delay. Trip delay Digital outputs 0.1 (0.1) 12.5sec Digital outputs/earth fault trip Only use for the function earth fault trip. If the parameter is set, digital output relay trip contactor after the setting delay time. Operation principle Programmable output Open circuit, Close circuit Open circuit (watchdog output) Close circuit (Trips, Specific trip, Alarms, Specific alarm, TOL, Communication Failure, Contactor welded) Programmable output//(trips, Specific trip, Alarms, Specific alarm, TOL, Communication Failure, Contactor welded) This parameter is to set the operation principle of digital output. If open circuit is selected, digital output relay will remain de-energized if the selected function does not occur; and digital relay will remain energized if selected function occurs. If close circuit is selected, digital output relay will remain energized if the selected function does not occur; and digital relay will remain de-energized if selected function occurs. M10x Parameter description Motor control and protection unit 37

38 Thermal overload protection (TOL) M10x protects the motor by calculating the thermal image of the motor during both run and stop. This image is used to allow optimal performance of the motor with calculated time to trip. The thermal image is calculated based on the highest of the three measured phase currents and depends on the parameterized data such as trip class (t6), motor ambient temperature (T AMB ), cool down time factor (M t6 ). Motor ambient temperature is taken into account for thermal image calculation by means of a device internal parameter TFLC, where TFLC is the highest of the measured three phase currents related to motor ambient temperature. When the thermal capacity level reaches the setting of trip level (eg,100%), the thermal overload trip will occur. The TOL trip can be reset after the thermal image goes below the motor reset level. The motor can be restarted only after TOL trip is reset. When the motor is being stopped, the thermal image calculation continues by using the background heat level and cooling down time factor until thermal capacity level decreases to zero. The thermal capacity decreases at a constant rate until it reaches the background heat level, after which it depends on the parameter s trip class and cool down time factor, thus simulating cooling down of the stator winding and the iron body of the motor. During power failure, the thermal capacity level of the motor is stored in the memory and the cooling down calculation starts from this level after resumption of power. TOL Protection conforms to IEC , ie, with a motor current 1.05xTFLC running for 2 hrs will not cause TOL-trip and subsequent rise in current to 1.2xTFLC will cause trip within 2 hrs. In case of an unbalance situation, the fictitious negative sequence current in remaining phases is taken into TOL calculation to trip early. 38 Motor control and protection unit M10x parameter discription

39 Parameters involved in TOL protection are disabled, enabled Thermal model Trip class t6 (standard model) Trip class te Time (EEx e model) Ia/In ratio (EEx e model) TOL alarm level Trip reset mode TOL bypass command (standard model) Cool coefficient Ambient temperature Co oling o f hots po ts in the w inding s depending on background heat level t =100 % A Cooling of m otor iron depending on the cooldown time factor s TOL alarm message 2. TOL trip and alarm 3. TOL trip reset rip level Alarm level R= Reset level t Fig. 1. Illustration of motor thermal simulation behavior enable/disable TOL protection Enabled/Disabled/Disabled during motor startup Enabled TOL protection/parameters Motor control/motor startup time Motor control/motor startup time N2 TOL protection function is recommended to be switched on all through motor starting, running stop period. If set as enabled, function is carried through motor starting, running and stopped stage. M10x Parameter description Motor control and protection unit 39

40 If set as disabled, function is switched off through all motor operating stages. All relevant parameters of the TOL function (trip reset mode, thermal model, TOL bypass, trip level, trip delay, T6, Te, cool coefficient, Ia/In and temperature) do not have any functionality in the motor control unit. If set as disabled during motor startup, this function is disabled only through motor starting stage. Disabled during motor startup TOL protection is inactivated during motor startup time Enabled/disabled Disabled TOL protection TOL protection function can be enabled or disabled during motor startup time via this parameter. Thermal mode TOL protection Standard/EEx e Standard TOL protection/parameters PTC protection/trip level/reset level TOL protection/motor ambient temperature The thermal model can be selected as either standard or EEx e. The standard model makes use of trip class, startup I ratio and motor startup time in TOL calculation. Parameter trip class definition defines the trip time for 6x motor nominal current (In) and it must be less than defined cold state maximum value for the motor. The protection of explosion-proof three-phase induction motors with type of protection increased safety EEx e is done with two special parameters, the stall/ nominal current ratio (Ia/In ratio) and te time. The tripping time of the TOL protection from the cold state motor must be less than the te time rated for the motor. For EEx e thermal model a set of parameters have fixed values or are not available in order to simplify parametering instructions and parametering process while providing a secured protection functionality. This should be carefully considered by the user since the given parameter values do not affect functionality in this case. The following parameters are not available when EEx e mode is selected TOL Protection/Motor ambient temperature Fixed 40 C TOL Protection/TOL bypass command Disabled 40 Motor control and protection unit M10x parameter discription

41 Trip class (T6) TOL protection 3 (1) 40 sec 6sec TOL protection/thermal model (standard) Motor information/nominal current (In) Motor information/motor ambient temperature Parameter trip class (t6) is the basic setting of the thermal protection function. This allows the user to set the thermal model characteristic according to motor startup requirements and characteristics. The trip class parameter allows the user to define the time that protection permits current of 6x ln from cold condition for motor protection. Motor startup is the most common reason for short overload situations. Normally, two starts from cold condition and one start from a hot condition are permitted. The Trip class (t6) value can be set for one cold start, which allows easy setting of protection. The trip class (t6) time for protection is defined based on the motor maximum start time, provided by the manufacturer. Initial information required for trip class (t6) definition Motor startup current ratio (rated motor data, Is/In), see parameter Startup I ratio Maximum start time permitted for cold motor Maximum start time permitted for warm motor Motor ambient temperature, see parameter Motor ambient temperature. Example 1. A thermal protection is set for a motor M2BA315SMC, 110 kw. Motor startup current ratio (Is/In) 7,5 Maximum start time for cold motor 30 sec Maximum start time for warm motor 15 sec Motor ambient temperature 40 C With the initial information, the protection characteristic can be defined by the following procedure First, the motor start current is calculated according to the ambient temperature. Practically, with 40 C about ambient temperature, the following calculation for start current can be passed. For more information about ambient temperature coefficient, see table of maximum permitted current in the chapter Ambient temperature. Temperature coefficient is derived with the following routine Since the motor ambient temperature in the example is 40 C, the TFLC is 1.00 x In. M10x Parameter description Motor control and protection unit 41

42 Motor startup current ratio is 7.5, thus motor rated start current (Is) is Is = Is/In x In The effect of ambient temperature is derived when Is and TFLC are known Is/TFLC = 7.5 x In/1.00 x In = 7.5 The calculated start current ratio (7.5) and motor maximum start time (30 sec) are placed on the cold condition time/current characteristic diagram. Start current ratio is located on the horizontal axis, while the maximum permitted time for cold motor start is set on the vertical axis. The cross point of these constraints shows the maximum setting for trip class (t6). The received setting is the absolute maximum value without further considerations and a lower value can be selected. A longer start is not protected by thermal protection and additional protection against stalled rotor is necessary. In case of thermal protection trip at start, with the setting of maximum Trip class (t6) value, checking the motor size for extreme start requirement is recommended. The 40 sec setting is limited by the range of parameter. Value for trip class (t6) is derived from the cold condition time/current diagram, (see Fig. 2). This setting allows start time up to approx. 26 sec for cold motor, before a thermal protection trip occurs. The start time for a warm motor with this parameter setting can be read from the hot condition time/current diagram accordingly. The check routine is shown in Fig. 3. The warm condition start must be within motor ratings. In this case, the start time for a warm motor is approximated from the latter diagram and must be shorter than 12 sec, as read from the diagram. In practice, starts lasting longer than 12 sec will lead to trip from the thermal protection. 42 Motor control and protection unit M10x parameter discription

43 Fig. 2. Trip class (t6) definition from cold condition time/current diagram. Diagram presented in 40 C motor ambient temperature Fig. 3. Start time vs. trip class (t6) definition from hot condition time/current diagram. Diagram presented in 40 C motor ambient temperature M10x Parameter description Motor control and protection unit 43

44 A more optimized setting of the thermal protection is needed in case one start for warm motor is required. In this case, the trip class (t6) parameter is derived from the warm condition time/current diagram according to actual duration of motor start and motor startup current. The derived trip class (t6) value is verified from the cold condition time/current diagram to ensure that thermal protection trip time is less than maximum allowed start time for a cold motor, ie, the protection is well defined. Separate protection is needed for unsuccessful start, ie, stalled rotor, if the thermal protection characteristic allows longer start before trip than is allowed for the motor. In this case, stall protection is utilized for a cold motor start supervision. By defining the operation of Startup time and stall protection trip delay, the trip must be set before motor maximum start time is exceeded, in case of unsuccessful start. Trip class (Te) TOL protection 5 (5) 40 sec 5sec TOL protection/thermal model (EEx e) TOL protection/ia/in ratio Motor information/motor ambient temperature The safe locked rotor te time of a particular induction motor is the time necessary for the winding temperature to rise from its final operational value to a fixed maximum value determined by the corresponding temperature class of the motor during locked rotor. It is of particular significance when the overload protection is specified for motors destined for use in hazardous locations. The te time is for EEx e motors to withstand Ia/In current. The parameter value for trip class te time is as rated for EEx e motor in the data book which represents the maximum value. Parameterized value for trip class te time can be equal or less than motor rated te time. For a faster trip, value less than rated is selected. With Ia/In ratio, this parameter makes it possible for M10x unit to calculate the trip time of the motor according to the load. M10x calculates the trip time for EEx e motor automatically, but the trip time for a certain current for further investigation can be defined as presented in this chapter. 44 Motor control and protection unit M10x parameter discription

45 Trip time can be defined with the help of the following cold condition time/current diagram. The diagram represents TOL standard model cold condition. Initial information, as parameterized, is required Ia/In ratio for EEx e motor te time for EEx e motor When Ia/In ratio is placed on the current (Is/TFLC) axis and te time is placed on the time (t) axis, the coordinate on which the lines drawn through these points cross each other is located on the t6 curve. According to defined t6 curve, trip time vs. motor current are available from cold condition time/current diagram. The same t6 curve can be also used for defining the trip time from a hot condition time/current diagram, as well. For example Ia/In ratio for EEx e motor is 7 and parameter te time value is 7 sec. By using the following cold condition time/current diagram, t6 curve can be found. When t6 curve is defined, other trip times vs motor current are available. Motor ambient temperature is not observed because it does not have an affect in TOL EEx e module usage, thus Ia/In can directly be used (see parameter Ambient temperature). The readout is t6 curve which is either existing in the diagram or is an estimation below the defined point. In this case Trip class (t6) = 9 sec is estimated from the diagram below. Trip time for current 3xIn is estimated approximately 40 sec. Fig. 4. Trip class definition for TOL/EEx e model from cold condition with time/current diagram. Diagram presented in 40 C motor ambient temperature. M10x Parameter description Motor control and protection unit 45

46 Ia/In TOL protection 1.2 (0.1) 8 5 TOL protection/thermal model (EEx e) TOL protection/trip class te time This is the ratio of stall current to the nominal current for EEx e application. The motor will withstand this current for the duration trip class te time. This information is rated for EEx e motor and available in motor data sheet. TOL alarm Level TOL protection 60 (1) 100% 90% -- When the motor thermal level reaches thermal capacity level set by this parameter, the M10x sends a warning TOL alarm. The TOL alarm is automatically reset when the thermal capacity reaches the parameterized TOL alarm level again. An overload alarm is reported when the motor current exceeds 1.14 x In. TOL trip Level TOL protection 60 (1) 100% 100% -- When the motor thermal level reaches thermal capacity level set by this parameter, M10x issues a trip command to stop motor with a message TOL trip. TOL reset level TOL protection 10 (1) 60% 50% -- Following a TOL trip, the thermal capacity of the motor is decreasing. Until the motor thermal level reaches thermal capacity level set by this parameter, TOL trip cannot be reset. THe motor cannot be restarted before resetting. 46 Motor control and protection unit M10x parameter discription

47 Trip reset mode TOL protection Auto/Remote/Local/Remote and local Remote and local Programmable inputs/ TOL trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the fault as desired by parameterization. Auto reset Reset the relay automatically. Reset is not possible before the calculated thermal capacity reaches the reset level. Remote reset Reset through fieldbus. Reset is not possible before the calculated thermal capacity reaches the reset level. Local reset Reset the relay through local hardwiring or MD panel. Reset is not possible before the calculated thermal capacity reaches the reset level. TOL bypass enable/disable TOL protection Enabled/Disabled Disabled TOL protection / Thermal model (standard)/ DI -TOL Bypass This parameter is part of TOL bypass function which raise the TOL tripping level up to 200% temporarily when it is activated. When TOL bypass function is activated, a motor is allowed to continue running until thermal capacity level reaches 200% without tripping on TOL and a motor tripped on TOL is allowed to be restarted immediately in case of emergency regardless the thermal level. To activate TOL bypass function, the parameter "TOL bypass is required to be enabled. The operation of TOL bypass function is from a special "TOL Bypass " command either through local control signals (via digital input hard-wiring) or given by fieldbus. If the command comes from local control DIs, depending on the DI setting, a continuous "0" or "1" activate the TOL bypass function. A reserve signal de-activate the function. If the command comes from PROFIBUS, a continuous "1" from PROFIBUS activate the function until a "0" is received. If the command comes from MODBUS, an " activate TOL bypass" command activate the function. An 'de-activate TOL bypass' command deactivate the function. More description of TOL bypass function is available in the document 1TNC M10x User Guide, TOL bypass function. M10x Parameter description Motor control and protection unit 47

48 Cooling coefficient (Mt6) TOL protection 1 (1) For an accurate thermal image of the motor, M10x needs to know the characteristics of the motor to be controlled. Different motors in different environments need different time periods to warm up and to cooling down. The cooling down period for a stopped motor is usually about four times longer than the warm up period and it certainly differs within the motor, eg, in certain hot spots of the windings from the iron core. But this value can be different depending on dirt or other material covering the motor, motor body size, weight installation place, etc. The normal value for the parameter is between 4 8 describing the slower cooling for a stopped motor [curve 1 and 2] than cooling of a running motor [curve 3]. In practice, this has been discovered as the normal rule for motors covering various applications. However, if the motor manufacturer gives recommendation for another value, it may be set to the protection. For example External cooling system is installed for improving the cooling down of a stopped motor. According to the motor manufacturer, cooling time constants for a running and stopped motor are equal. Thus, the parameter can be set below recommended value 4 [curve 1]. Fig. 5. Cooling coefficient (Mt6) parameter influence on stopped motor cooling (principle diagram) 48 Motor control and protection unit M10x parameter discription

49 Ambient temperature Motor information 0 (5) + 80 C 40 C TOL protection/thermal model Motor information/nominal current TOL protection/trip class TOL protection/trip class te time TOL protection/tol, and O/L alarm Motors of basic design are intended for operation in a maximum ambient temperature of 40 C. If a motor is to be operated in higher ambient temperature, it should normally be derated and should not be loaded to the same thermal capacity. Normally this reduction of output power is done automatically by M10x, but it is also possible to do it manually, as will be shown later in this chapter. To calculate the thermal image of the motor being protected, the M10x needs to know the temperature of the environment in which the motor is running. Especially in industries where the motors are located near the heat source, the maximum thermal capacity level of the motor is reduced based on the increased surrounding temperature. Motors designed for EEx e applications are always rated and certified for a certain maximum ambient temperature, most commonly 40 C. If EEx e motor is designed for other temperatures, the manufacturer will supply the motor rated data. Because of the nature of EEx e motor, the output power ratings are not reduced automatically according to ambient temperature by M10x. Instead of using ambient temperature parameter, M10x uses fixed value 40 C, thus the multiplier is one (1) when TOL EEx e model is selected. The M10x reduces the maximum permitted current by the multiplier as indicated in the table below (TOL standard model) Ambient temperature C Permitted current = In x Ambient temperature C Permitted output, % of rated output M10x Parameter description Motor control and protection unit 49

50 Example The thermal capacity level of the motor reduces from 100% at 40 C to 85% at 50 C. Therefore, the motor can be loaded maximum to 92% of its rated load at 50 C. Manual reduction may be needed if other reduction multipliers than presented in the table above are required. Output power reduction is done by setting the value 40 C to parameter motor ambient temperature and calculating the temperature reduction directly to nominal current. When the multiplier is calculated this way it must be applied to trip class time as well (Is/TFLC). Example Motor data sheet specifies that at 60 C motor can be loaded maximum of 75% of the nominal. Thus motor ambient temperature is set to 40 C and when setting the nominal current the rated motor current is derated nominal current=0.75xin When nominal current is derated, trip class parameter is defined with the same factor. It should also be considered that other parameters, ie, protection function trip and alarm levels, referring to nominal current are affected relatively. 50 Motor control and protection unit M10x parameter discription

51 Stall protection Stall protection is used to protect the driven mechanical system from jams and excessive overloads. Under such conditions, the motors have to be switched off in good time and reported to avoid undue mechanical and thermal stress on the motor and the installation. This protection function is active only after the motor has successfully started or after parameterized motor startup time has elapsed, and will cause relay activation in case of a motor stall while it is running. The parameter can be set to a higher value for applications experiencing overload as part of normal operation. Large low-voltage motors and those devices (eg, mixers, crushers, saw cutters, etc.) having short admissible stalling time less than the startup time are not protected by this function. Stall protection function consists of the following parameters enable, disable Trip level Trip delay Trip reset mode I Lmax Startup current Trip Level Trip Delay I N Startup Fig. 6. Stall protection function activated Trip t M10x Parameter description Motor control and protection unit 51

52 enable/disable Stall protection Enabled/Disabled Disabled Stall protection /parameters Motor control/motor startup time Motor control/motor startup time N2 Stall protection function can be disabled with the help of this parameter. When selecting disabled, all parameters under stall protection are deactivated. Stall protection activates after motor startup when either of the following criteria are met a) Motor running current has recovered around 1,25 x In after starting b) Startup time (setting value) has elapsed Trip level Stall protection 120 (10) 800% 400% Stall protection/ enable/disable Stall protection/trip delay When the highest of the measured phase currents remains above the set value for a trip delay time, the M10x will perform a trip with a message Stall trip. If normal conditions are restored before the trip delay elapses, the M10x will go back to normal operation. The trip level referenced to In is set based on the motor technical data sheet supplied by the manufacturer and the requirements/restrictions of the application. 52 Motor control and protection unit M10x parameter discription

53 Trip delay Stall protection 0.0 (0.1) 25.0 sec 0.5sec Stall protection/ enable, disable Stall protection/trip level When the condition for a stall trip is present, the M10x will startcount down for the time specified in trip delay parameter. The trip is followed with a message Stall Trip. The trip delay is set based on the requirements/restrictions of the application. Trip reset mode Stall protection Remote/Local/Remote and local Remote and local Stall protection/ enable, disable Programmable inputs/ Stall trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the trip as desired by parameterization. Remote reset Reset through fieldbus. Local reset Reset through operator panel MD or local hardwiring M10x Parameter description Motor control and protection unit 53

54 Phase failure protection Phase failure in motor phase currents is a common phenomenon in industrial environments. It generally occurs because of pitted contacts in the contactor or SCPD, imbalance in the mains supply, loose connections, blown fuse, and faults within the motor. It is an extreme situation where a complete loss of phase occurs. This can be caused by a utility supply problem or by a blown fuse in one phase. Unbalanced phase currents are a major cause of motor thermal damage due to the nature of the current. The negative sequence current induced in the rotor is double the power supply frequency and produces a counter torque to the desired motor output. For small unbalances, the overall output torque will remain same as the motor develops a large positive sequence torque to overcome the negative sequence torque. This opposing torque and the high negative sequence current lead to an increased temperature rise in the rotor and stator. Reasons for the phase failure are neither temporary nor self-covering. Although TOL protection performs an accelerated trip during phase failure and unbalance over 20%, there are no good reasons to wait for the trip to occur through TOL protection. By the use of phase failure protection a motor can be tripped without waiting for thermal calculation. Indeed, phase failure protection should be parameterized to trip in less time than TOL. Parameters involved in phase failure protection are enabled/disable Alarm level Trip level Trip delay Trip reset mode (ILMIN / ILMAX) Alarm level Trip level Trip delay t 1. Alarm message 2. Trip delay active 3. Trip delay cleared 4. Trip delay active 5. Contactor trip and trip message 6. Reset according to reset mode Fig. 7. Phase failure protection 54 Motor control and protection unit M10x parameter discription

55 enable/disable Phase failure protection Enabled/Disabled/Alarm only Phase failure protection/parameters Motor control/startup time Motor control/startup time N2 Motor control/ramp time Motor control/motor type Phase failure protection function can be disabled with the help of this parameter. When disabled, protection function does not have any functionality in the M10x. Alarm only is an option of function disable/enable. When Alarm only is active, an alarm occurs only if the measured value is more than the set alarm level. This function is disabled automatically in the case of single-phase motor and during the motor startup period. Alarm level Phase failure protection 10 (1) 90% 80% Phase failure protection/ enable/disable To avoid motor failure by phase failure, the M10x calculates the ratio between the lowest phase current to the highest phase current (I LMIN / I LMAX ) from the measured currents of all three phases. If the condition set by this parameter is true, there will be a phase failure alarm warning message. The phase failure alarm clears automatically on restoration of normal condition. Trip level Phase failure protection 5 (1) 90% 70% Phase failure protection/ enable/disable Phase failure protection/trip delay When the ratio I LMIN / I LMAX corresponds to the value set on trip level, the M10x will trip after the elapse of trip delay time with a message Phase failure trip. If normal conditions are restored before the trip, the M10x will go back to normal operation. M10x Parameter description Motor control and protection unit 55

56 Trip delay Phase failure protection 0 (1) 60 sec 10sec Phase failure protection/ enable/disable Phase failure protection/trip delay After trip level condition is reached, the M10x will delay the trip for the time defined by pre-parameterized trip delay. A message Phase failure trip is generated. With this delay, a short phase current loss can be filtered. The M10x can be reset according to the trip reset mode parameter. Trip reset mode Phase failure protection Remote, Local, Remote and local Remote and local Phase failure protection/ enable/disable Phase failure trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the trip as desired by suitable parameterization. Remote reset Reset through fieldbus. Local reset Reset through operator panel MD or local hardwiring. 56 Motor control and protection unit M10x parameter discription

57 Unbalance protection Unbalance protection function protects the motor against a small degree of unbalance in the motor phases. The function monitors the ratio between IL MIN /IL MAX. The calculation of the motor thermal capacity takes into account the unbalance for early tripping to prevent motor damage due to negative sequence currents. For more information, refer to phase failure protection. Parameters involved in unbalance protection are as below enable/disable Alarm level Trip level Trip delay Trip reset mode (I LMIN / I LMAX ) Alarm level Trip level Trip delay t 1. alarm 2. start trip delay 3. clear trip delay 4. start trip delay 5. trip 6. trip reset Fig. 8. Unbalance protection enable/disable Unbalance protection Enabled/Disabled/Alarm only Disabled Unbalance protection/parameters Motor information/number of phases (3 phase applications) Motor control/motor startup time Motor control/motor startup time N2 The unbalance protection function can be disabled with the help of this parameter. When disabled, the protection function does not have any functionality in the M10x. Alarm only is an option of disable/enable. When Alarm only is active, an alarm occurs only if the measured value is more than the set alarm level. This function is disabled automatically in the case of single-phase motor and during the motor startup period. M10x Parameter description Motor control and protection unit 57

58 Alarm level Unbalance protection 50 (1) 90% 90% Unbalance/ enable/disable/alarm only To avoid a motor failure by phase unbalance, the M10x calculates a ratio between the lowest phase current to the highest phase current (I LMIN /I LMAX ) from the measured currents of all three phases. If the condition set by this parameter is true, there will be an Unbalance alarm warning message. The unbalance alarm clears automatically after normal status is attained. Trip level Unbalance protection 50 (1) 90% 85% Unbalance/ enable/disable/alarm only Unbalance/Trip delay When the ratio I LMIN /I LMAX corresponds to the value set for this parameter, M10x will start a countdown set by trip delay parameter after which a trip occurs with an unbalance trip message. If normal conditions are restored before the trip, the M10x will go back to normal operation. Trip delay Unbalance protection 0 (1) 60 sec 10sec Unbalance/ enable/disable/alarm only Unbalance/Trip level After the trip level is reached, the M10x will delay the trip for the time set by this parameter. After the set trip delay, the M10x will trip the motor and give an unbalance trip message. With this delay, short phase unbalances can be filtered. The M10x can later be reset according to the trip reset mode parameter. 58 Motor control and protection unit M10x parameter discription

59 Trip reset mode Unbalance protection Remote/Local/Remote and local Remote and local Unbalance/ enable/disable/alarm only A phase unbalance trip can be reset in multiple ways. Depending on the control philosophy, it is possible to reset the trip as desired by suitable parameterization. Remote reset Reset through fieldbus. Local reset Reset through operator panel MD or local hardwiring. M10x Parameter description Motor control and protection unit 59

60 Underload protection Underload protection function monitors the process against loss or decrease in motor load. This protection function is current-based protection. It is especially useful for indication of loss of suction for pumps, broken belt for conveyors, loss of airflow for fans, broken tools for machines, etc. Such states do not harm the motor but early diagnosis helps to minimize the extent of damage to the mechanical installation and subsequent loss of production. The motors on underload draw mainly the magnetizing current and a small load current to overcome frictional losses. Therefore, the other reason to isolate the motors on underload is to reduce the reactive load on the power system network. Underload protection function is based on the highest measured phase current. Underload protection is active only after the motor has successfully started, ie, when current is detected. Parameters involved in underload protection are enable/disable Alarm level Trip level Trip delay Trip reset mode (I LMAX / I n) Alarm level Trip level Trip delay Alarm message 2. Trip delay active 3. Trip delay cleared 4. Trip delay active Contactor trip and trip message 6. Reset according to reset mode t Fig. 9. Underload protection 60 Motor control and protection unit M10x parameter discription

61 enable/disable Unload protection Enabled/Disabled/Alarm only Disabled Motor control/ramp-up time Motor control/ramp-down time Motor control/startup time (Autotrafo) Underload protection function can be disabled with the help of this parameter. When disabled, protection function does not have any functionality in the M10x. Alarm only is an option of function disable/enable. When alarm only is active, an alarm occurs only if the measured value is more than the set alarm level. In the startup time of softstarter/autotransformer, underload protection is suppressed. Alarm level Unload protection 20 (1) 90% 30% Underload protection/ If the highest phase current (I LMAX ) of the measured three phase currents is detected below the alarm level, then an underload alarm warning message is created to inform the operator of the underload condition. Underload alarm clears automatically on restoration of normal condition. Trip level Unload protection 5 (1) 90% 20% Underload protection/ Underload protection/trip delay When current I LMAX reaches the trip level, the M10x trips the motor after elapse of trip delay time. An underload trip message is generated after the trip. If normal conditions are restored before the trip, the M10x will go back to normal operation. M10x Parameter description Motor control and protection unit 61

62 Trip delay Unload protection 0 (1) 1800 sec 10sec Underload protection/ Underload protection/trip level The trip is delayed by the time set by this parameter. If underload condition is not back to normal before the elapse of trip delay time, a trip is generated with a message. With this delay, short underload situations can be filtered. Trip reset mode Unload protection Remote/Local/Remote and local Remote and local Underload protection/ Underload protection/trip level Underload trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the trip as desired by suitable parameterization. Remote reset Reset through fieldbus. Local reset Reset through operator panel MD or local hardwiring. 62 Motor control and protection unit M10x parameter discription

63 Noload protection The noload protection function protects the process against sudden loss of load. This condition does not harm the motor, but requires a switchoff to safeguard the process. The no load current is of the order of 0.2 to 0.6 In depending on the size and speed of the motor. The no load current of slow-speed motors is high and that of large motors is low. The noload protection function is based on the highest phase current measured by the current measurement unit. The noload protection function detects missing current with respect to the contactor and the main switch ON feedback, and executes actions as parameterized. Noload protection is active only after the motor has successfully started, ie, when current is detected. Parameters involved in noload protection are enabled/disable Alarm level Trip level Trip delay Trip reset mode (I LMAX / I n) Alarm level Trip level Trip delay Alarm message 2. Trip delay active 3. Trip delay cleared 4. Trip delay active Contactor trip and trip message 6. Reset according to reset mode t Fig. 10. Noload protection M10x Parameter description Motor control and protection unit 63

64 enable/disable Noload protection Enabled/Disabled/Alarm only Disabled Noload/Parameters Noload protection function can be disabled with the help of this parameter. When disabled, protection function does not have any functionality in the M10x. Alarm only is an option of function disable/enable. When alarm only is active, an alarm occurs only if the measured value is more than the set alarm level. This function is disabled automatically during the motor startup period. Alarm level Noload protection 5 (1) 50% 20% Noload protection/ If the highest phase current (I LMAX ) of the measured three phase currents is detected below the alarm level, a noload alarm warning message is created to inform the operator of the no load condition. Noload alarm clears automatically on restoration of normal condition. Trip level Noload protection 5 (1) 50% 15% Noload protection/ Noload protection/trip delay If the highest phase current (I LMAX ) of the measured three phase currents falls below the trip level for longer than the time period set by the trip delay, the M10x trips the motor with a noload trip message. 64 Motor control and protection unit M10x parameter discription

65 Trip delay Noload protection 0 (1) 1800 sec 5sec Noload protection/ Noload protection/trip level When the current ILMAX reach the noload trip level, the M10x trips the motor after elapse of trip delay time. A noload trip message is generated after the trip. If normal conditions are restored before the trip, the M10x will go back to normal operation. With this delay, short noload situations can be filtered. Trip reset mode Noload protection Remote/Local/Remote and local Remote and local Noload protection/ The noload trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the trip as desired by suitable parameterization. Remote reset Noload trip reset is possible via the fieldbus. Local reset Noload trip reset is only possible via digital input which is assigned for reset (or via operator panel MD). M10x Parameter description Motor control and protection unit 65

66 Earth fault protection The earth fault protection function protects the motor and the network against ground current flow. During earth fault, the motors can reach a dangerous potential above the ground level thus posing a safety hazard to personnel. The earth faults are mainly caused due to aging of the insulation, deterioration of insulation due to sustained or cyclic overloading, moisture or conductive dust. Most insulation faults result in leakage to the frame of the motor. Earth fault protection in M10x device provides the protection for fatal isolation damages. The function is by default suppressed by parameters Motor startup time and Softstart ramp time to avoid nuisance tripping due to harmonics caused by saturation of the current transformers. In some cases, it may need to be switched on during startup in specific project requirements. M10x relay is NOT a residual current protection device. This protection is neither intended to be used for pre-emptive isolation supervision nor for personnel protection against electrical shock. For these applications, ABB recommends the usage of external protection devices (PRCDs/RCDs). Parameters involved in the earth fault protection are as below enable/disable (Earth fault protection is activated during motor startup time). Alarm level Trip level Trip delay Trip reset mode I0 Trip delay Trip level Alarm level t 1. Motor startup time 2. Normal operation (Earth fault protection active) 3. Alarm message 4. Trip delay active 5. Trip delay cleared 6. Trip delay active 7. Contactor trip and trip message 8. Reset according to reset mode Fig. 11. Earth fault protection 66 Motor control and protection unit M10x parameter discription

67 enable/disable Earth fault protection Enabled/Disabled/Alarm only Disabled Earth fault protection/parameters Motor control/motor startup time Motor information/number of phases (3 phase applications) Earth fault protection function can be disabled with the help of this parameter. When disabled, the protection function does not have any functionality in the M10x. Alarm only is an option of function disable/enable. When alarm only is active, an alarm occurs only if the measured value is more than the set alarm level. Enable earth fault protection during motor startup Earth fault protection is activated during motor startup time Enabled/Disabled Disabled Earth fault protection Earth fault protection function can be enabled or disabled during motor startup time via this parameter. Alarm level Earth fault protection 100(100)3000mA(Earth fault primary 1A) or 500(100)15000mA(Earth fault primary 5A) 500mA Earth fault/ When the earth fault current exceeds the pre-set level, an earth fault alarm is generated. The earth fault alarm is automatically reset when the current falls below the alarm level. This function can be bypassed during the startup of a motor by parameterization of a trip delay. M10x Parameter description Motor control and protection unit 67

68 Trip level Earth fault protection 100(100)3000mA(Earth fault primary 1A) or 500(100)15000mA(Earth fault primary 5A) 800mA Earth fault protection/ Earth fault protection/trip delay When the earth fault current remains above the trip level for a preset trip delay time, the M10x will generate a trip command with an earth fault trip message. If normal conditions are restored before the trip delay time elapses, the M10x will go back to normal operation. Trip delay Earth fault protection 0.1(0.1) 60sec 0.1sec Earth fault protection/ Earth fault protection/trip level When the earth fault current rises above the trip level, the M10x will execute a trip command after elapse of the time specified in the trip delay parameter. The trip is followed with an earth fault trip message. The countdown is reset if the earth fault current goes below the trip level before the pre-set trip delay. The trip is reset depending on the parameterization of the trip reset mode. Trip reset mode Earth fault protection Remote/Local/Remote and local Remote and local Earth fault protection/ An earth fault trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the trip as desired by parameterization. Remote reset Reset through fieldbus. Local reset Reset through operator panel MD or local hardwiring. 68 Motor control and protection unit M10x parameter discription

69 PTC protection (M102 only) PTC thermistors are semiconductor elements with a very high positive temperature coefficient. PTC temperature detectors are used extensively in the protection of motors against excessive temperature rise. They are embedded directly between the phase windings on the overhang of the stator winding normally during manufacture. In contrast to the trip class (t6) and TOL protection that responds to the load current, the PTC protection responds to the change in thermistor resistance due to temperature rise in the windings. The PTC protection is also sensitive to fall in temperature in order to make it possible to reset the trip. The thermistors are selected to have a rated operating temperature (TNF) to correspond with the insulation class, type and construction of the motor. Its resistance increases sharply in the range of its rated operating temperature (TNF). Use a type A temperature sensor with a characteristic curve according to IEC The M102 senses this abrupt change in the resistance to execute a trip command. A trip will follow when trip level is detected by the measurement and reset is allowed when resistance is under reset level. Parameters involved in PTC protection are enable/disable PTC alarm level PTC trip level PTC trip delay PTC reset level PTC short circuit alarm level Trip reset mode ( H ) Trip delay PTC trip Trip reset Trip Trip Level Level Alarm Level Reset Level PTC Temperature alarm Alarm clear t Fig. 12. PTC protection M10x Parameter description Motor control and protection unit 69

70 enable/disable PTC protection Enabled/Disabled/Alarm only Disabled PTC protection/parameters The PTC protection function can be disabled with the help of this parameter. When disabled, the protection function does not have any functionality in the M102. Alarm only is an option of function disable/enable. When alarm only is active, an alarm occurs only if the measured value is more than the set alarm level. PTC alarm level PTC protection 100 (1) 10,000 ohms 1,600 ohms PTC protection/ enable, disable This parameter defines the alarm level for the PTC protection function. The limit causes a PTC temperature alarm message to be issued when the measured temperature is higher than the alarm level. The temperature is measured via the PTC thermistors. Usually, three PTC thermistors in series are built into the overhang of the stator winding at the coolant air exhaust end of the motor. The thermistors are selected to have a rated operating temperature (TNF) to correspond with the insulation class, type and construction of the motor. If the resistance corresponding to the high temperature at one or more of the thermistors exceeds this value, an PTC temperature alarm will be generated. The PTC temperature alarm clears automatically on reaching the normal condition, ie, resistance restores below alarm level. PTC trip level PTC protection 100 (1) 10,000 ohms 3,600 PTC protection/ When PTC resistance remains above the trip level for a preset trip delay time, the M102 will generate a trip command with a PTC trip message. If normal conditions are restored before the trip delay time elapses, the M102 will go back to normal operation. 70 Motor control and protection unit M10x parameter discription

71 PTC trip delay PTC protection 1 (1) 1800 sec 1sec PTC protection/ PTC Protection/PTC trip level When the PTC resistance rises above the trip level, the M102 will execute a trip command after elapse of the time specified in the trip delay parameter. The trip is followed with PTC trip message. The countdown is reset if PTC resistance goes below the trip level before the pre-set trip delay. The trip is reset depending on the parameterization of the trip reset mode. PTC reset level PTC protection 100 (1) 10,000 ohms 1,600 ohms PTC protection/ Following a PTC trip, the resistance of PTC is decreasing. Until the resistance reaches the level set by this parameter, PTC trip cannot be reset. The motor cannot be restarted before reset. PTC short circuit alarm level PTC protection 0 (1) 250 ohms 10 ohms PTC protection/ This parameter defines the alarm level for the PTC short circuit protection function. The limit causes a message PTC short circuit alarm to be issued when the measured temperature is lower than the alarm level. M10x Parameter description Motor control and protection unit 71

72 PTC trip reset mode PTC protection Auto / Remote / Local / Remote & Local Remote & Local PTC protection/ A PTC trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the trip as desired by parameterization. Auto reset The PTC temperature trip resets automatically after the sensor loop resistance goes below the threshold set for the trip-reset level. Remote reset Reset through fieldbus. Local reset Reset through operator panel MD or local hardwiring. 72 Motor control and protection unit M10x parameter discription

73 Undervoltage protection (M102 only) The undervoltage protection function protects the motor against overload during voltage dips. During a mains undervoltage, the electrical energy required to drive the rotor remains the same for some period, owing to its inertia. According to the energy conservation law Mechanical energy = Electrical energy VL * IL * cos Φ Equation 1 Where VL is the motor line voltage, IL is the motor line current and Cosphi is the power factor. From Equation 1, the motor draws more current during voltage dips to deliver the same mechanical energy. The motors switched off during voltage dip or power failure can be restarted on power resumption sequentially to prevent simultaneous switch-on of the motors and thus prevent another mains failure on the network. The tripping of motors due to undervoltage of short duration can be bypassed. The feature also helps to restart the process on power resumption by sequentially starting the motors (staggered start). The undervoltage protection also prevents startup of the motor if the voltage is not high enough and indicates phase loss before switching on the motor. Parameters involved in undervoltage protection are enable/disable Alarm level Trip level Trip delay Reset level Trip reset mode 3 Fig. 13. Undervoltage protection M10x Parameter description Motor control and protection unit 73

74 enable/disable Undervoltage protection Enabled/Disabled/Alarm only Disabled Undervoltage protection/parameters Autorestart/ The undervoltage protection function can be disabled with the help of this parameter. When disabled, the protection function does not have any functionality in the M102. Because the function of autorestart is associated with the undervoltage protection, if the undervoltage protection is disabled, the function of autorestart can not be enabled. Alarm only is an option of function disable/enable. When alarm only is active, an alarm occurs only if the measured value is more than the set alarm level. This function is disabled automatically during the motor startup period. Alarm level PTC protection 50 (1) 100% 80% Undervoltage protection/ This parameter defines the voltage level for an undervoltage alarm. The undervoltage protection is based on the lowest of the measured phase-phase voltages. An undervoltage alarm is generated when the lowest of the measured voltages is below the parameterized alarm level. Trip level Undervoltage protection 30 (1) 100% 65% Undervoltage protection/ Undervoltage protection/trip delay Autorestart/parameters This parameter defines the trip level for the undervoltage protection function. When the lowest of the measured phase-phase voltages goes below the trip level, the M102 will start counting a trip delay or go into the autorestart process. 74 Motor control and protection unit M10x parameter discription

75 Trip delay Undervoltage protection 0.2 (0.1) 5 sec 1sec Autorestart/Maximum powerdown time This parameter defines the time from the undervoltage trip level to the execution of the trip command. When the lowest of the measured phase-phase voltages goes below the trip level for a time specified in the trip delay, the M102 will open the contactor. Reset level Undervoltage protection 50 (1) 100% 90% Undervoltage/Trip delay Autorestart/Maximum autoreclose time Autorestart/Maximum powerdown time Autorestart/Staggered start time The reset voltage level is a voltage limit for restarting the motor after an undervoltage trip. The motor will start immediately or after a delay depending on the time during which the reset voltage level is reached (refer to Fig. 13). Trip reset mode Undervoltage protection Remote/Local/Remote and local Remote and local Undervoltage protection/ A undervoltage trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the trip as desired by parameterization. Auto reset Undervoltage trip resets automatically after the voltage goes above the reset voltage level Remote reset Reset through fieldbus. Local reset Reset through operator panel MD or local hardwiring. M10x Parameter description Motor control and protection unit 75

76 Autorestart function (M102 only) The phase A phase C (Uac) voltage is supervised continuously. It is possible to automatically restart the motor after momentary power loss. Two alternative models of autorestart function are provided in M102 standard and enhanced. In standard mode, the reaction of the auto restart function depends on the length of the voltage dip. The following cases show the different reactions of M102 in different voltage dip situations. Case 1 Voltage dip< autoreclose time Fig. 14. Voltage dip< autoreclose time If voltage is restored within the autoreclose time, the motor will be restarted immediately. Case 2 autoreclose time<voltage dip< Max. power down time Fig. 15. autoreclose time<voltage dip< Max. power down time 76 Motor control and protection unit M10x parameter discription

77 If the supply is restored after the autoreclose time but before the maximum power down time, the motor will be restarted after the staggered start time. Case 3 Voltage dip> Maximum power down time Fig. 16. Voltage dip> Maximum power down time If the supply remains below the restore level after maximum power down time, no automatic restart is triggered, even if voltage restores later. If voltage dip impact is more of a concern, enhanced autorestart function can be introduced. In the enhanced mode, the reaction of the autorestart function not only depends on the length of the voltage dip, but also the number of voltage dips within a certain time. The following cases show the different reactions of M102 in different voltage dip situations. Case1 Voltage dip< autoreclose time Identical to Standard mode Case1 Case2 autoreclose time<voltage dip< Maximum power downtime Identical to Standard mode Case2 Case3 Voltage dip> Maximum power downtime Identical to Standard mode Case3 Case4 2xdip<200ms within 1s M10x Parameter description Motor control and protection unit 77

78 Fig xdip<200ms within 1s If the interval between two voltage dips (which length less than 200ms) is less than 1 second, automatic delay restart is triggered after second voltage restore. Parameters involved in autorestart function are enable/disable mode Maximum autoreclose time Maximum powerdown time Staggered start delay enable/disable Autorestart Enabled/Disabled/Alarm only Disabled Autorestart/Parameters Undervoltage/Parameters The Autorestart function can be disabled with the help of this parameter. When disabled, the autorestart does not have any functionality in the M102. Because the function of autorestart is associated with the undervoltage protection, if the the function is to be enabled, the undervoltage protection will be enable automatically. 78 Motor control and protection unit M10x parameter discription

79 Maximum autoreclose time Autorestart 0 (100) 5000 msec 200msec Autorestart/ Undervoltage/Trip reset mode Undervoltage/Reset level Undervoltage/Maximum power down time Maximum autoreclose time is the time during which the motor immediately restarts on restoration of voltage above the reset voltage level. Maximum power downtime Autorestart 0 (0.1) 1200 sec 5sec Autorestart/ Undervoltage/Trip reset mode Undervoltage/Trip voltage delay Undervoltage/Maximum power downtime Undervoltage/Staggered start time The maximum powerdown time starts after the trip delay time has elapsed. It is the maximum waiting time of the M102 for the power resumption. The motor will restart after staggered start delay on voltage restoration above the reset voltage level between end of maximum autoreclose time and maximum power down time. The M102 issues an undervoltage trip message if the voltage recovers above the reset voltage level after the maximum powerdown time. The trip can be reset based on the parameterization of the trip reset mode. Staggered start delay Autorestart 0.6 (0.1) 1200 sec 5sec Autorestart/ Undervoltage/Trip reset mode Undervoltage/Trip delay Undervoltage/Reset voltage level Autorestart/Maximum autoreclose time Autorestart/Maximum powerdown time This parameter defines the time from the voltage rise above the reset voltage level to the time when the start command is executed. It is applicable to the motors if the voltage restores above the reset voltage level between the delay. This parameter can be used to start the motors sequentially after resumption of power to prevent voltage dip caused by simultaneous starting of several motors. M10x Parameter description Motor control and protection unit 79

80 Start limitation protection Start limitation helps to protect the motor and also the process against excess number of starts in a given interval. When the number of starts is reached and the motor is switched off, a new start is prevented. The time interval starts from the first start. After the elapse of the time interval the counter is reset to the preset value. The permissible motor starts per hour can be obtained from the manufacturer s motor and apparatus data sheet. However, the minimum waiting time between two starts must be observed. The parameterization of the protection function can be the number of starts per time interval or the time between two consecutive starts. In the first case, the user must wait after the trip for the reset to take place before making a start. The time to reset after start limitation trip is provided to the fieldbus. Independent of this function, the motor is protected by TOL function and a start is possible only if the thermal capacity is below the startup inhibit level. If motor data specifies the number of starts during a certain time span, this protection function has the added advantage of supervising the number of starts. In other cases, a process may require the number of motor starts this protection can provide. ality is presented in the following example. Fig. 18 shows the start limitation protection with three starts allowed. i) Normal situation, after stop command motor can be started normally, Start 2. Every start activates an internal timer for the time defined by time interval parameter. The number of active timers are reviewed after every stop command and compared to value of number of starts parameter. Stop command can be implemented during active or elapsed timer. ii) Two timers are still active, thus stop command generates a start limitation alarm message and one more start is allowed, Start 3. iii) The third start has been executed. A contactor trip and trip message Start Limitation Trip alarm will follow when motor is stopped while there are two active timers, here starting from Start 1. When start limitation trip is active the time to reset is provided to the fieldbus. iv) Trip can be reset when the first timer from Start 1 is finished. Motor start is possible when all pending trips are reset. Supervision continues with a new timer from Start Motor control and protection unit M10x parameter discription

81 Fig. 18. Start limitation alarm The parameters involved with the protection function are enable/disable Time interval Number of starts enable/disable Start limitation protection Enabled/Disabled Disabled Start limitation/parameters The start limitation protection function can be disabled with the help of this parameter. When disabled, the protection function does not have any functionality in the M10x. Time interval Start limitation protection 1 (1) 600 min 1min Start limitation/number of starts During this time interval the number of starts is limited by setting the parameter number of starts. Number of starts Start limitation protection 1 (1) Start limitation/time interval This parameter defines the number of allowed starts during a predefined time window set by the parameter time interval. If this value is set to one, the parameterized time interval will define the time between two consecutive starts. M10x Parameter description Motor control and protection unit 81

82 Long start protection The long start protection function protects motors against lock or stall in start state and signals a fault when current continuously exceeds a separately set threshold after a start command for the same period of time. This protection function is active only during the parameterized motor startup time. If motor startup time has elapsed it will cause relay activation in case of a motor stall, but not long start protection. Long start protection function is based on the highest measured phase current. The parameters involved with the protection function are enable/disable Locked rotor level Locked rotor delay Trip reset mode Fig. 19. Long start protection 82 Motor control and protection unit M10x parameter discription

83 enable/disable Long start protection Enabled/Disabled/Alarm only Disabled Long start protection/parameters Motor information/motor startup time Motor information/motor startup time N2 The long start protection function can be disabled with the help of this parameter. When disabled, the protection function does not have any functionality in the M10x. Locked rotor level Long start protection 120 (10) 800 % 120 Long start protection/ enable/disable Long start protection/locked rotor delay After a start signal, when the measured phase currents remain above the set value for a locked rotor delay time during the startup time, M10x will will perform a trip with a long start trip message. If normal conditions are restored before the trip delay elapses, or parameterized motor startup time has elapsed, the M10x will go back to normal operation. The trip level referenced to In is set based on the motor technical data sheet supplied by the manufacturer and the requirements/restrictions of the application. Locked rotor delay Long start protection 0 (1) 250 sec 10sec Long start protection/ enable/disable Long start protection/locked rotor level When measured current above the set value of locked rotor level during the startup time, the M10x will start countdown for the time specified in locked rotor delay parameter. The trip is followed with a ong start trip message. The trip delay is set based on the requirements/restrictions of the application. M10x Parameter description Motor control and protection unit 83

84 Phase sequence Protection M10x protects the motor against connection in wrong phase sequence. Before motor startup, M10x detects the phase sequence of voltage continuously and after startup M10x will detect the phase sequence of current. The definition of correct phase sequence Voltage L1, L2, L3 Current Ia, Ib, Ic If enable phase sequence protection, when M10x detects the voltage or current is different fromthe definition, M10x will release a phase sequence trip signal. Enable/Disable Phase sequence protection Enabled/Disabled Disabled Phase sequence protection/parameters A phase sequence trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the trip as desired by parameterization. Trip Reset Mode Phase sequence protection Remote/Local/Remote & Local Remote & Local Phase sequence protection/ A phase sequence trip can be reset in multiple ways depending on the control philosophy. It is possible to reset the trip as desired by parameterization. Remote Reset Reset through fieldbus. Local Reset Reset through operator panel MD or local hardwiring 84 Motor control and protection unit M10x parameter discription

85 Maintenance Preventive maintenance is the best way to have long service life for any equipment. Maintenance function can be configured suitably as a reminder for preventive maintenance. The user reaps high benefits in terms of reduced process downtime and loss of production. Maintenance function indicates the operation of the motor in terms of hours run and the usage of starter in the form of operating cycles. Number of hours run helps to assess the bearing life and its lubrication or replacement, whereas the number of operating cycles help in deciding replacement of worn-out power contacts or the contactor itself. Maintenance alarm can be activated after lapse of the set counter. The counters can be set after maintenance according to two different principles depending, of course, on normal routine of the user. Parameters of the maintenance function are Running time alarm level Start number alarm level Running time alarm level Maintenance 0 (1) 65,535 h 65535(Disabled) -- The user can set a period after which preventive maintenance is desired. When the running timer exceeds the preset running time alarm level, a running time alarm message is generated for the corresponding M10x. This helps to lubricate and maintain the bearings of the motor within the correct service interval. When the parameter is set to 65535, the running time alarm is disabled. Start number alarm level Maintenance 0 (1) 65, (Disabled) -- This parameter reflects the control cycles of contactors. Users can set this parameter in line with the electrical life of a contactor. When start counter has run through the set value of cycles in preset start number alarm level, the corresponding M10x generates a start number alarm message. This helps in carrying out preventive maintenance of power contacts. When the parameter is set to 65535, the start number alarm is disabled. M10x Parameter description Motor control and protection unit 85

86 Diagnosis information (M10x-P only) M10x, as a slave station, gives diagnosis information to master stations on the basis of the following three groups of information Group 1 Alarm information for selection TOL, Overload, Phase failure, Phase unbalance, Underload, Noload, Earth fault, PTC, Undervoltage, Autoreclose, Contactor feedback, Welded contactor, PTC short circuit, PTC open circuit, Start limitation, Ready to trip reset, Running time, Start number, Serial communication, DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9, DI10, DI11, DI12 Group 2 Trip information for selection TOL, Stalled failure, Phase failure, Phase unbalance, Underload, Noload, Earth fault, PTC, Undervoltage, Contactor feedback, Serial communication, Start limitation, Feeder, Long start, Emergency stop, External trip, DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9, DI10, DI11, DI12 Group 3 Other information for selection Signal (input from terminal X1) DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9, DI10, DI11, DI12 Trigger resource Field(RCU), MD, Fieldbus, DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9, DI10, DI11, DI12 Other Information Block DP, Discrepancy in parameter settings, Hardware fault, Parameter status, Watchdog alarm, Current of last TOL trip By tipping the ticket in front of each message, users can define which message needs to be sent. DI9~DI12 are available only for the DC24V power of DIs. 86 Motor control and protection unit M10x parameter discription

87 User definable map (M10x-M only) The M10x-M contains a user definable area in the memory map. This area allows re-mapping of the addresses of any actual values or setpoints registers. The user definable area has two sections 1. A register index area (memory map addresses 1100H-1114FH) that contains 80 actual values or parameter register addresses. 2. A register area (memory map addresses 0050H-009FH) that contains the data at the addresses in the register index. Register data that is separated in the rest of the memory map may be re-mapped to adjacent register addresses in the user definable registers area. This is accomplished by writing to register addresses in the user definable register index area. This allows for improved throughput of data and can eliminate the need for multiple read command sequences. The user definable register index is stored as a parameter and therefore it is remembered even when the power is removed. For example, if the values of phase L1 current (register address 0028H) and motor status (register address 0019H) are required to be read from a M10x-M, their addresses may be re-mapped as follows Write 0028H to address 1100H (User definable register index 0000) using function code 06H or 10H. Write 0019H to address 1101H (User definable tegister Index 0001) using function code 06H or 10H. It is now possible to read these two data registers with one read, at addresses 0050H, 0051H. Address 0050H will contain Phase L1 current and address 0051H will contain Motor state. M10x Parameter description Motor control and protection unit 87

88 User definable data (M10x-P only) The M10x contains a user definable data area in the memory map. Three data structures are available for user to define in different applications. Up to 12 bytes data can be sent out to PROFIBUS master station with three options of 4 bytes, 8 bytes, 12bytes. The functions for selection are as below Type1 4 bytes in and 2 bytes out No bytes are mappable. But, in the Configurable area byte1 bit4-7 can be defined for DIs (DI0~DI12) by user. Type2 8 bytes in and 2 bytes out 3 bytes in are mappable by master station. Data assignable for byte4&5 ( two bytes value only) includes I L1 /In, I L2 /In, I L3 / In, U L1L2, U L2L3, U L3L1, Power factor, Earth fault current, Power, Thermistor value, Running time, Start number, Frequency, Time to TOL trip, Time to TOL reset, Actual startup time. Data assignable for byte6 Thermal capacity, Current unbalance And 12 bits can be defined to DIs(DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9, DI10, DI11, DI12) by user 4 bits come from Configurable area byte1 bit bits come from User definable area byte 7 bit0-7 U L1L2, U L2L3, U L3L1, Power factor, Power, Thermistor value and Frequency are only available for M102 byte4 & byte5. Type3 12 bytes in and 2 bytes out 7 bytes in are mappable by master station. Data assignable for byte4&5 ( two bytes value only) includes I L1 /In, I L2 /In, I L3 / In, U L1L2, U L2L3, U L3L1, Power factor, Earth fault current, Power, Thermistor value, Running time, Start number, Frequency, Time to TOL trip, Time to TOL reset, Actual startup time. Data assignable for byte6&7 ( two bytes value only) includes I L1 /In, I L2 /In, I L3 / In, U L1L2, U L2L3, U L3L1, Power factor, Earth fault current, Power, Thermistor value, Running time, Start number, Frequency, Time to TOL trip, Time to TOL reset, Actual startup time. 88 Motor control and protection unit M10x parameter discription

89 Data assignable for byte8&9 ( two bytes value only) includes I L1 /In, I L2 /In, I L3 / In, U L1L2, U L2L3, U L3L1, Power factor, Earth fault current, Power, Thermistor value, Running time, Start number, Frequency, Time to TOL trip, Time to TOL reset, Actual startup time. Data assignable for byte10 Thermal capacity, Current unbalance And 12 bits can be defined to DIs(DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9, DI10, DI11, DI12) by user. 4 bits come from Configurable area byte1 bit bits come from User definable area byte 11 bit0-7 U L1L2, U L2L3, U L3L1, Power factor, Power, Thermistor value and Frequency are only available for M102 byte4~byte9. i) Only the PROFIBUS master station can decide which of the cyclical data type (Type1, Type2 and Type3) will be mapped to the M10x. ii) MCUSetup software can be used to set the certain function for each configurable type or bit. iii) DI9~DI12 are only available for the DC24V power of DIs. For more details, please refer to M10x-P PROFIBUS DP Implementation for M10x. M10x Parameter description Motor control and protection unit 89

90 MD LED The MD(operation panel) has 4 LED indicators. Each LED can be configured with various color and function. As shown in Fig. 20 and 21, from top to the bottom, the LED is called LED1, LED2, LED3 and LED4. Fig.20. View of MD21 Fig.21. View of MD31 The parameters under MD LED for LED1~4 are Color Color MD LED Green(LED1), Green/Red(LED2 LED3), Red/Yellow(LED4) Green(LED1), Red(LED2), Red(LED3), Yellow(LED4) MD LED/ The parameter defines the color of each LED which is used to indicate the selected function. MD LED Ready, Start1, Start2, Running, Stop, Ready to start, Fault, DI0, DI1,DI2, DI3, DI4, DI5, DI6, DI7, DI8, DI9 1, DI10 1, DI11 1, DI12 1 Ready (LED1), Start1(LED2), Stop(LED3), Fault(LED4) MD LED/ The parameter defines the function of each LED. If motor is in the selected situation, the LED will be on. The definition of each function is listed below. 90 Motor control and protection unit M10x parameter discription

91 LED functions Ready Start1 Start2 Running Stop Ready to start Fault DIx 1 Meaning of the function M10x unit is powered up and ready for operation Motor is running CW/N1 Motor is running CCW/N2 Motor is running CW/N1 or CCW/N2 or feeder is closed Motor is stopping or feeder is open Motor ready to start, i.e. there is no active internal or external trip, motor is not under emergency stop state (if defined) & Main Switch is ON (if defined) Motor is at fault The status of DIx 1) DI9~DI12 are only active for M10x 24VDC type. M10x Parameter description Motor control and protection unit 91

MNS Motor Management INSUM P. MCU User s Guide Version 3.0d ABB

MNS Motor Management INSUM P. MCU User s Guide Version 3.0d ABB MNS Motor Management INSUM P MCU User s Guide Version 3.0d ABB Software revision 2.1 ABB INSUM Software Version 3.0d 1 ABB INSUM Software revision 3.0d NOTICE The information in this document is subject

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

Soft Start Series MP700 Solid State, Reduced Voltage

Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controls and Accessories Soft Start Series MP700 Solid State, Reduced Voltage Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

TraceNet ECM Series Control System

TraceNet ECM Series Control System TraceNet ECM Series Control System ECM Operating Guide Thermon Manufacturing Company TraceNet is a registered trademark of Thermon Manufacturing Company. ECM Operating Guide 2014, 2015 Thermon Manufacturing

More information

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs)

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs) MRS752348-MUM Issued: 0/997 Version: F/23.6.2005 Data subject to change without notice COCB_ Circuit Breaker (2 state inputs/ 2 control inputs) Contents. Introduction... 3. Features... 3.2 Application...

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

Series Temperature Controller Instruction Sheet

Series Temperature Controller Instruction Sheet Series Temperature Controller Instruction Sheet Thank you very much for purchasing DELTA A Series. Please read this instruction sheet before using your A series to ensure proper operation and please keep

More information

725B Configuration Software Manual

725B Configuration Software Manual 725B Configuration Software Manual REV DATED DESCRIPTION AUTHOR APPROVED 0 09-03-10 First Issue P.Cartmell Page 1 of 80 SECTION 1 - SOFTWARE INSTALLATION... 5 725B ConfigurationSoftware Installation...

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

PTE0705 Electric Fence Monitor

PTE0705 Electric Fence Monitor PTE0705 Electric Fence Monitor The JVA logo is a registered trademark of JVA Technologies. JVA Technologies. TABLE OF CONTENTS DESCRIPTION... 2 QUICK START GUIDE... 3 FEATURES... 4 EXPLANATION OF TERMS...

More information

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE isocket Smart Relay is a complex Smart House system which is installed in the fuse cabinet (electric cabinet) in the house. We therefore assume that

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

Refrigerated air dryers

Refrigerated air dryers Refrigerated air dryers OPERATING AND MAINTENANCE MANUAL Original instructions 38178800319 OPERATING AND MAINTENANCE MANUAL - Contents 1 CONTENTS CONTENTS... 1 Chapter 1 IDRY ELECTRONIC CONTROLLER...

More information

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS.  A4741 / Rev.1 DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS User Manual and Menu Map A4741 / Rev.1 www.entes.com.tr ATTENTION -Disconnect all power before connecting the device. -Don t remove

More information

Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e

Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e C C1 C2 AL1 AL2 AL3 Micro-controller X Model: PXR4/5/9 PXR SEL Operation Manual ECNO:46e Table of Contents Part Names and Functions... 6 Operations... 7 2-1 Parameter list... 7 2-2 Basic operations...

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS Firmware versions up to V2.0.X INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGCUIT2Protocol-IM-H57880 06/15 1/32 Contents Section I Introduction

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

Applications and Examples

Applications and Examples Applications and Examples Comat AG Bernstrasse 4 CH-3076 Worb Tel. +41 (0)31 838 55 77 www.comat.ch info@comat.ch Fax +41 (0)31 838 55 99 Contents General remarks to the examples... 3 Applications, Examples

More information

OWNER S OPERATION MANUAL

OWNER S OPERATION MANUAL DUTY P P STDBY Run 1 2 Run STDBY P P FAULT Run 3 4 OK: Change mode PUMPCONTROL OWNER S OPERATION MANUAL Advanced Multi Pump Controller Installation and Operating Instructions MODEL: FPC-15607-S AUTO: RUNNING

More information

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU with Automatic Power Transfer Switch Contents: NOTE: The drawings included in this package are for controllers covered under our standard

More information

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

La Marche Manufacturing Company   Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual La Marche Manufacturing Company www.lamarchemfg.com Option 46 Series Digital Combined Accessory Package Installation and Operation Manual This manual is subject to change without notice. You may obtain

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1 NGC-40 Bridge Overview Raychem-AR-H58862-NGC40BridgeOV-EN-1805 nvent.com 1 Table of Contents 1. NGC-40 Overview... 9 1.1 Example NGC-40 System... 10 2. Legal stuff... 11 3. Protocols... 12 3.1 Data es...

More information

CLEANROOM MONITOR CR3A Network - Installation Instructions

CLEANROOM MONITOR CR3A Network - Installation Instructions CLEANROOM MONITOR CR3A Network - Installation Instructions INTRODUCTION The CR3 Series Cleanroom Monitor, was developed specifically to allow for monitoring of confined spaces with accuracy and reliability.

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1- DPR-45 User Manual V-2.0 (2..206) DPR-45 TEMPERATURE PROTECTION RELAY PT00 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT 9-50VDC SUPPLY DESCRIPTION DPR-45 is a precision unit designed for the temperature

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual Instruction manual MTL process alarm equipment October 2016 CSM 725B rev 2 MTL RTK 725B Configuration Software Manual SECTION 1 - INTRODUCTION... 5 Basic Requirements... 5 SECTION 2 - SOFTWARE INSTALLATION...

More information

Safety Function: Single-beam Area Access Control (AAC)

Safety Function: Single-beam Area Access Control (AAC) Application Technique Safety Function: Single-beam Area Access Control (AAC) Products: Guardmaster Dual-input Safety Relay, Single-beam Area Access Control Sensors with E-stop Safety Rating: CAT. 4, PLe

More information

FPS MANUAL FEEDER PROTECTION SYSTEM

FPS MANUAL FEEDER PROTECTION SYSTEM 3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols FPS MANUAL FEEDER PROTECTION SYSTEM Revision 1-C-031615 MAIN MENU Metering Ñ ²Messages

More information

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440) Safety Temperature Limiter STL 50 Certified to DIN EN 14597 (replaces DIN 3440) Features M For use as: STB Protection - temperature limiter ASTB Exhaust gas - protection - temperature limiter STW Protection

More information

Ethernet General Purpose

Ethernet General Purpose Ethernet General Purpose Technical Manual Revision 1.03 8 November 2013 Pakton Technologies IO PAE224 Ethernet GPIO Manual.docx Page 1 of 22 Revision 1.03 Last updated 8/11/2013 Table of Contents INTRODUCTION...3

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

Installer Manual KNX Touchscreen Thermostat

Installer Manual KNX Touchscreen Thermostat Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY

More information

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual Revision 1.03 8 November 2013 JVA Technologies Ethernet General Purpose IO Technical Manual www.jva-fence.com.au Table of Contents INTRODUCTION...3 Scope and Purpose...3 Glossary...3 SPECIFICATIONS...4

More information

RS485 MODBUS Module 8AI

RS485 MODBUS Module 8AI Version 1.4 15/04/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

FlameGard 5 MSIR HART

FlameGard 5 MSIR HART FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

User Guide

User Guide ABS control panel CP 112 212 ON ON ON ON ON ON User Guide www.absgroup.com ii ABS CONTROL PANEL CP 112 212, USER GUIDE Copyright 2008 ABS Group. All rights reserved. This manual, as well as the software

More information

SACE PR021/K SIGNALLING UNIT

SACE PR021/K SIGNALLING UNIT SACE PR021/K SIGNALLING UNIT 1SDH000559R0002 L3016 1/52 EN CONTENTS 1. GENERAL INFORMATION...4 1.1. FOREWORD...4 1.2. APPLICABLE SCENARIOS...5 2. TECHNICAL SPECIFICATIONS...6 2.1. ELECTRICAL CHARACTERISTICS...6

More information

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47) DIESEL ENGINE CONTROL UNIT DCU 205 - USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) 64 84 52 00 Fax: (+47) 64 84 52 12 office@auto-maskin.no - 1 - TABLE OF CONTENTS 1. INTRODUCTION TO THE DCU 205...4

More information

MR3CCUHV Temperature/Defrost Control

MR3CCUHV Temperature/Defrost Control Master Catalog 125 Temperature Controls Section A Product/Technical Bulletin Issue Date 0401 MR3CCUHV Temperature/Defrost Control The MR3CCUHV Temperature/Defrost Control is designed to control the temperature

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

Series Digital Controller Instruction Sheet

Series Digital Controller Instruction Sheet 216/3/11 Series Digital Controller Instruction Sheet Thank you very much for purchasing DELTA DTC Series Temperature Controller. Please read this instruction sheet before using your DTC series to ensure

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

PowerLogic ION Setup Meter Configuration Software Configuration Guide

PowerLogic ION Setup Meter Configuration Software Configuration Guide PowerLogic ION Setup Meter Configuration Software Configuration Guide 70002-0293-03 12/2010 Conventions Used in this Manual This section describes the symbols and terminology used in this guide. Symbols

More information

OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL

OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL ap15_2manual04/22/13 Page 1 4/22/2013 1 Serial Number : Option: OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL Micro Seven, Inc. 1095-K N.E. 25th Hillsboro, OR 97124 U.S.A. phone: 503-693-6982

More information

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option Description of options Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M 4189340401D SW 1.4X.X Description of option Functional description DEIF A/S Parameter list DEIF A/S,

More information

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12 AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual RST-5000 Series Web Enabled Input Module Rev. A2, 1/12 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com RST-5000

More information

Engine Control Unit, ECU 100 Functional description Additional functions Parameter list

Engine Control Unit, ECU 100 Functional description Additional functions Parameter list DESIGNER'S REFERENCE HANDBOOK Engine Control Unit, ECU 100 Functional description Parameter list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

Installation Manual Tracker 221

Installation Manual Tracker 221 Installation Manual Tracker 221 KSR KUEBLER AG Im Kohlstatterfeld 17 D-69439 Zwingenberg / Germany www.ksr-kuebler.com Contents About this Installation Manual...4 Description Tracker 220-series...4 Installing

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER FCS-23A

INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER FCS-23A INSTRUCTION MANUAL FOR MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER Thank you for your purchase of our Microcomputer based Temperature Indicating Controller. This manual contains instructions

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number Innovation In and Out of Parlour Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual Version - 1.0 Date - June 2016 Part Number - 39-0038 Index Manual Version... 3 About the Remote Vacuum

More information

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel Manual# 1006494 User s Manual 200E Series DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel User's Manual Rev. 1.0 Marine Pro 200E Series ~~~ DCU 210E Diesel Engine Control Unit DCU 208E Diesel

More information

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B PRODUCT BULLETIN SB 8001B Type 8001 ALARM ANNUNCIATOR TYPE8001 FEATURES 16 or 32 alarm points per flush mount enclosure Displays are backlit with long life LEDs and engraved to suit Dimmer controls built

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

IndigoVision Alarm Panel. User Guide

IndigoVision Alarm Panel. User Guide IndigoVision Alarm Panel User Guide THIS MANUAL WAS CREATED ON 2/21/2017. DOCUMENT ID: IU-AP-MAN002-4 Legal considerations LAWS THAT CAN VARY FROM COUNTRY TO COUNTRY MAY PROHIBIT CAMERA SURVEILLANCE. PLEASE

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH CONTROL PANEL INTERFACE USING THE AUTO/OFF/MANUAL SWITCH With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting occurs when utility power source

More information

Trinity Tft/Lx Model #s: Tft60-399/Lx Version Date:

Trinity Tft/Lx Model #s: Tft60-399/Lx Version Date: Trinity Tft/Lx Model #s: Tft60-399/Lx150-800 Version Date: 2013-07-26 NEW FEATURES Second Central Heat Input Internal Lead-Lag Control System Sensor Modulation Sensor Alternatives Warm Weather Shutdown

More information

Independent Zone Control (I.Z.C.)

Independent Zone Control (I.Z.C.) Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics

More information

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification SCC Inc. LMV51 Control Product Description February 7, 2017 The LMV51 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft

More information

Safety Instructions MS 10B ALARM UNIT MS 10B ALARM UNIT. Used symbols. Always observe this information to prevent damage to the device

Safety Instructions MS 10B ALARM UNIT MS 10B ALARM UNIT. Used symbols. Always observe this information to prevent damage to the device Safety Instructions Used symbols Important Comments Before starting with installation of the MS 10B Alarm Unit, we recommend you to read the important information beneath. Qualification The installation

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS XXXXXXX-0 EN 1904 READ AND SAVE THESE INSTRUCTIONS BASIC-PLC CONTROLLER MANUAL For all Condair desiccant dryer with equipped with Basic- PLC valid from version: PLC-35/PLC-45 18.04.03 Dehumidification

More information

SCAN200E USER S MANUAL

SCAN200E USER S MANUAL SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We

More information

General Purpose IO Technical Manual

General Purpose IO Technical Manual General Purpose IO Technical Manual Revision 1.06 8 November 2013 Pakton Technologies PAE222 GPIO Manual.docx Page 1 of 21 Revision 1.06 Last updated 8/11/2013 Table of Contents INTRODUCTION...3 Scope

More information

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System. The Fireye EP260, EP270 (early spark termination), or EP265 (pilot stabilization) programmer modules are used with the FLAME-MONITOR Burner Management Control System (P/N E110). Several operational characteristics

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011 October 2011 PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412 The PACSystems * Thermocouple Input module IC695ALG412 provides twelve isolated differential thermocouple input channels.

More information

Gas Controller Module GC-06

Gas Controller Module GC-06 Page 1 Oct. 2015/2 Measuring, warning and controlling module for toxic, combustible and refrigerant gases and vapours. The gas controller series GC-06 is designed in accordance with the standard EN 50545-1.

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller Mounting and Operating Instructions Electronics from SAMSON EB 5610 EN Firmware version 1.40 Edition December 2014 Controller

More information

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com FL500 Modbus Communication Operating Manual Order No.: 10193214/00 MSAsafety.com 1000 Cranberry Woods Drive Cranberry Township, PA 16066 A Phone 1-800-MSA-2222 Fax 1-800-967-0398 For your local MSA contacts

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Manual# 1100334 User s Manual 200 Series DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel Rev. March 2012 User's Manual for the Marine Pro 200 Series ~~~ DCU 210 Diesel Engine Control Unit DCU

More information

Table of Contents SECTION PAGE

Table of Contents SECTION PAGE Table of Contents SECTION PAGE SECTION 1 INTRODUCTION................... 1.1 Description.............................. 1.2 Features................................ 1.3 Models.................................

More information

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert)

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert) Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert) P.N. 7876C (export) February 12, 2015 For Spas equipped with BP2100, BP6013 controllers and Spa Touch panel. Spa

More information

TE809-Ats Instructions Manual

TE809-Ats Instructions Manual TE809-Ats Instructions Manual Project: v2.0 PREFACE Thanking you for preference, TECNOELETTRA SRL hopes that the use of this equipment could be a reason of satisfaction. This manual is designed to put

More information

Module Features are-configurable, no module jumpers to set

Module Features are-configurable, no module jumpers to set December 2011 PACSystems* RX3i Isolated Thermocouple Input Module, 6 Channels, IC695ALG306 Isolated Thermocouple Input Module, 12 Channels, IC695ALG312 Isolated Thermocouple Input module IC695ALG306 provides

More information

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D ASCO 5350 The ASCO 5350 ATS Remote Annunciator is listed under the Underwriter s Laboratories Standard UL-1008 for Automatic Transfer Switch accessories. This stand-alone device provides individual status

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV CyCLO User Guide Version 2.00 19 th December 2017 REV 2.00 1 Contents 1. Hardware... 3 1.1. Introduction... 3 1.2. Electrical Specification... 3 1.3. Board Overview... 4 1.4. Electrical Installation...

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

RTO. User guide 05/

RTO. User guide 05/ RTO User guide Version: RT0 M&S (master & slave) Characteristics: Constant lighting, temperature regulation with a low inertia heating system. Building opening hour scheduler and presence detection. 05/2013

More information