1 GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 69 PRESIDENT SEPTEMBER 2014
2 Report for Department of Infrastructure Development Fire Services Preliminary Report: 69 President September 2014 Table of Contents 1. INTRODUCTION Design Criteria and Specifications Scope of the Services Scheme Report PROJECT SUMMARY FIRE SYSTEMS Fire Water System Details Sprinkler System Details Smoke Ventilation Details Means of Escape Details Structure and Compartmentation Details Fire Fighting Services Details Recommendation i P a g e
3 1. INTRODUCTION 69 President is located at cnr. President and Simmonds Streets, Johannesburg, Gauteng (see Locality Map). Figure 1: Locality Map The project brief, as issued by Gauteng Funding Agency (GFA), was to conduct an initial assessment of the building fire infrastructure and systems of 69 President, and to provide recommendations regarding the repairs and renovations of the building. 1.1 Design Criteria and Specifications This project will be implemented in compliance with all the requirements of the National Building Regulations and the new SANS10400, with specific focus on Part T of the regulations. The entire assessment shall be carried out in accordance with relevant SANS codes applicable for the facility: SANS T, The application of the National Building Regulations Part T: Fire Protection SANS D, The application of the National Building Regulations Part D: Public safety. SANS M, The application of the National Building Regulations Part M: Stairways. SANS W, The application of the national building regulations Part W: Fire Installation SANS 543, Fire Hose Reels SANS , Symbolic safety signs Part 1: Standard signs and General requirements 1
4 SANS , The use and control of fire-fighting equipment Part 1: Portable and wheeled (mobile) fire extinguishers. SANS 1910, Portable refillable fire extinguishers SANS 10287, Automatic sprinkler installations for fire-fighting purposes 1.2 Scope of the Services Scheme Report This report deals with the fire services to be implemented based on the existing systems and proposed architectural changes to the building, this is photo assessment only. 2. PROJECT SUMMARY 2.1 Project Description 69 President is an existing building and is comprised of a basement services level, ground floor with reception, two above ground parking levels, twenty seven (27) upper floors and an eleventh floor service level. The 69 President building is a total of 30,765m 2. The building is currently in a state of disrepair and appears to have been in the process of being refurbished. The majority of the services, Fire systems included, have been stripped, damaged or demolished. 3. FIRE SYSTEMS 3.1 Fire Water System Details The existing fire water system is non-operational due to non-completion theft and damage. Existing hose reels in the eastern staircase are damaged and not connected to the water supply and have missing hoses and valves, figure 1. New hose reels are on site for installation at the western staircase but the majority have not been installed, figure 2. Figure 1 - Existing Hose Reel Figure 2 New Fire Hose reels 2
5 The new hose reels that have been installed have not been connected to the fire water mains, figure 3. The last service on the fire water system was in 2007, figure 4. Figure 3 - New Hose Reel Installed Figure 4 - Last Service All portable fire extinguishers have been removed, figure 5. The existing fire water tank has had valves removed, figure 6. The fire water storage tank does not have adequate storage capacity for firefighting purposes. A new fire water supply tank and diesel pump will be required to supply a minimum of one hydrant and 2 hose reels for at least 120 minutes. Figure 5 - Missing Fire Extinguisher Figure 6 Existing Water Tanks The existing diesel fire water pump has been damaged and is not operational, figure 7. This pump will need to be replaced with a new diesel powered fire water pump suitable for supplying the hydrants at the highest point within the building as per current standards. The motor of the jockey pump has been removed, figure 8. Both the pump and motor require replacement to meet current standards. 3
6 Figure 7 - Fire Water pump motor Figure 8 - Fire Water Jockey Pump The pump control equipment has been damaged and all wiring has been stripped from the control panels, figures 9 and 10. All will need to be replaced along with the pumps themselves. Figure 9 Pump Controller Figure 10 - Pump control Equipment There are currently no fire hydrants installed on any levels of the building, figure 11. The current fire hydrant supply system is designed with a pressure reducing system every 10 floors. This system has been removed and will need to be reinstated to make the system active, figure 12. Alternatively the installation of a multi-stage pump will eliminate the need for this. Figure 11 - Hydrants Not Installed Figure 12 - Pressure reducing systems removed 4
7 There is no statutory fire signage installed indicating fire equipment. There is currently no means of fighting a fire should one occur in the building. 3.2 Sprinkler System There is an existing sprinkler system in the basement areas of the 69 President building. The main sprinkler control valve is situated within the fire pump room Details The entire basement sprinkler system is non-operational due to theft and damage. Sprinkler control valve is not operationa0l and has no pressure, figure 9. All sprinkler spares have been taken from the spares cabinet. The fire pump control panel has been stripped of all wiring, (figure 10). Figure 13 - Sprinkler ICV Figure 14 - Sprinkler Alarm Gong The basement sprinkler protection seems intact and could possibly be reused after pressure testing to confirm its status, figure 15, 16. Adjustments to the sprinkler layout will be required to suit the revised layouts with the basement to meet statutory requirements, figure 15, 16. Figure 15 - Missing Sprinkler Heads Figure 16 - Sprinkler Range Pipes The requirements of the current SANS Part T requires sprinkler protection in an office building over 30m in height with floors over 500 m 2. The existing floor area is over 700m 2 per level, hence requires sprinklers. However, separating the floors into areas of 500m 2 and less will comply with the regulations without sprinkler protection since it is an existing building. This can be done be places a class B fire door at the entrance to each floor at gridline 11 of the architects drawings. Alternatively a new sprinkler system can be installed throughout the building. 5
8 3.3 Smoke Ventilation Details The existing basement smoke ventilation system is not operational. HVAC engineer to comment and ensure operation. Ventilation of the parking levels is through open sections on all sides. These are in good condition and comply with regulation, figure 17. The exiting windows are not openable, figure 18. All floor areas are to be compartmented into areas of 500m 2 or less to meet the requirements of SANS for smoke ventilation. Alternatively mechanical smoke ventilation will be required. Figure 17 Parking Level Ventilation Figure 18 Office level Windows Staircase ventilation for the eastern staircases is done through large louvers at the top of the stairwells. These are in good condition but do not comply with regulations for a building over 30m in height, figure 19. A mechanical pressurization system is required to be installed in the staircase. Staircase ventilation for the western staircases is done through small louvers along the height of the stairwells. These do not comply with regulations for a building over 30m in height, figure 20. A mechanical pressurization system is required to be installed in the staircase. Figure 19 - Eastern Staircase Ventilation Figure 20 - Western Staircase Ventilation 6
9 3.4 Means of Escape The 69 President building is currently served by two enclosed fire escapes that link all floors of the building. The eastern stair discharges in the main building lobby, the western stair discharges into occupied space on ground level Details Hand railings in the staircases have been damaged and there are sections missing (figure 21). These require repairs or replacement. Hand railings are on a single side of the stairs only, current regulations require handrails on both sides. Surfaces of stair treads are damaged and not suitable for use (figure 22). Repairs are required. Figure 21 - Western Staircase Handrails Figure 22 - Western Staircase Treads The existing eastern steel staircase has not been maintained and the treads are sagging, figure 23. Structural engineer to confirm that they are safe for use. Access doors into the eastern stairwell are in process of being replaced with fire doors, the frames are installed but no doors, figure 24. The frames do not comply with the regulations for class B fire doors, the rebates are less than the requires 25mm. Figure 23 Eastern Steel Staircase Figure 24 Eastern Staircase Fire Door Frame 7
10 Access doors into the eastern stairwell are in process of being replaced with fire doors, the frames are not installed yet, figure 25. There are several security gates in both staircases, figure 26. These do not comply with regulations and must all be removed. Figure 25 - Western Staircase Fire Door Figure 26 - Security gates The number of escape routes are adequate for a population of a standard office building based on the time of construction. The eastern staircase requires direct access to outside the building without exiting into occupied office space. There is no statutory fire signage installed indicating escape routes. 3.5 Structure and Compartmentation The 69 President building is of concrete structure with brick internal structure. There are numerous vertical shafts and service penetrations between floors Details All HVAC vertical ducts have access doors on each floor, the existing doors do not comply with the requirements for fire separation between the ducts and floors, figure 27. All of these access doors need to have minimum rating of 120 minutes. All vertical electrical ducts require fire sealing, they are currently all open between floors, figure 28. Figure 27 HVAC Duct Access Doors Figure 28 - Vertical Slab Penetrations 8
11 HVAC dampers been installed where ducts enter the service shafts, figure 29. However all dampers are not mounted against the wall of the duct. All fire dampers are to be repositioned so that they are either built into the wall or are flush up against it. The external curtain wall runs continuously between floors with no separation between floors, figure 30. This is creating a flue between all floors that will result in rapid spread of fire between all floors. This space between the curtain wall and slab requires fire sealing both above and below the floor slab with an insulated panel in between the seals. This is a critical issue and needs to be addressed immediately. Figure 29 - Fire Dampers Figure 30 - Unsealed Curtain Wall 3.6 Fire Fighting Services It must be ensured that the fire department has safe access to a building for firefighting purposes Details It appear that the existing service lift is being enclosed behind fire doors, figure 31, indicating that it will be used as a fireman s lift. These fire doors are only installed on one floor and the installation has not been completed, no door closers and iron monger have been installed. Figure 31 - Fireman s Lobby Fire doors Figure 32 - Fireman s Lift Controller HVAC ducts that are entering into the kitchen area adjacent to the fire doors are not installed with fire dampers. To create the safe environment of a fireman s lobby, such dampers must be installed. 9
12 4 Recommendation The critical remedial work required to meet the minimum national fire standard is recommended and a high level budgetary cost for the remedial work is presented. Install new fire hose reels, fire hydrants and fire extinguishers as per SANS T/W. Install new diesel fire water booster pump and 160m 3 storage tank. Replace main Sprinkler control valve to current regulations. Revise and repair sprinkler installation to suit regulations, all piping to be painted and supported as per regulations. Reinstate sprinkler spares cabinet and replace missing spares. Pressure test existing mains pipework to ensure compliance with regulations. Install new sprinkler system throughout or compartment all office levels into compartments of 500m 2 or less. Reinstate basement smoke ventilation system. Install new statutory fire signage throughout. Repair/ replace existing handrails in stairwells. Remove all security gates in escape routes. Structural engineer to comment or structural integrity of eastern steel staircase. Install new pressurization systems in both stairwells. Install second hand rail within all stairwells as per SANS S. Repair damaged surfaces of all stairs. Complete installation of fire doors to all escape stairs. Eastern staircase requires direct exit to outside the building, layout to be revised to suite. All vertical penetrations through floor slab to be fire sealed All HVAC ducting to have fire dampers correctly installed at entry to vertical service ducts. Replace all HVAC service duct doors Enclose goods lift to be converted to fireman s lift within fireman s lobby with suitable class B fire doors and fire dampers. Fire seal curtain wall on all levels to ensure smoke barrier between floors. 10
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR LIBRARY HOTEL OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: Library
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 75 Fox Street Building OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report:
More informationGAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT
GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT VERTICAL TRANSPORT FOR ABSA BUILDING OCTOBER 2014 Report for Gauteng Department of Infrastructure Development Vertical Transport
More informationSCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY
SCHEDULE Essential s taken from Schedule 9 of the Building Regulations 2006 43 PART 1 BUILDING FIRE INTEGRITY 1 Building elements required to satisfy prescribed fire-resistance levels 2 Materials and assemblies
More informationBUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING
GAUTENG DEPARTMENT OF INFRASTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT ELECTRICAL SERVICES FOR 75 FOX STREET BUILDING September 2014 Contents 1. INTRODUCTION... 3 1.1. Design Criteria and Specification...
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS
FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber
More informationFIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY
UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)
FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE
FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT BEQ KNIT LTD. ZIRABO, ASHULIA, SAVAR, DHAKA Other Factories: Beq Sweaters Ltd., Tammam Design Ltd. April 22, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing
More informationFollowing are the systems proposed as per NBC & Local Fire Authority:
1. OBJECTIVES AND STRATEGIES OF THE FIRE PROTECTION DESIGN This report describes the design parameters, system requirements of fire protection system for mixed occupancy (Assembly + Business) building
More informationUCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES
Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments
More informationMAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006)
MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) 1. INTRODUCTION 1.1 Essential Safety Measures Defined Essential Safety Measures (previously called essential services) are
More informationEnclosure 4- RISK ASSESSMENT
Enclosure 4- RISK ASSESSMENT RISK ASSESSMENT Risk is a potential that a chosen action or activity will lead to a loss of human or property. Risk assessment is a step for Risk Management. Risk assessment
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT TOYO COMPOSITE KNIT GARMENTS LTD 1, SOUTH KAMALAPUR SARDER COMPLEX, DHAKA Other Factories: Pure Cotton Ltd, Knit and Knitwear Ltd June 7, 2014 Page 2 Fire Safety Inspection
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE
FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification
More informationPROJECT: NITESH PALO Bangalore FIRE SAFETY MEASURES
PROJECT: NITESH PALO ALTO @ Bangalore FIRE SAFETY MEASURES System Description 1 Firewater pumping system 2 Wet riser system and hose reel system. 3 Automatic sprinkler system 4 Yard hydrant system 5 Pressurization
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MULTIFABS LTD KASHIMPUR, NAYAPARA Other Factories: ne April 9, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was surveyed for fire safety on
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT M.S.ATTIRES LTD. ACCORD ID: 10887 A. RAHMAN PLAZA, SHANSHONGAON, FATULLAH, NARAYANGONJ OTHER FACTORIES: AISA FASHION LTD.; PRINT GARDEN LTD.; S.M. COLLECTION LTD. February
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT VINTAGE GARMENTS LTD EAST NARSHINGPUR, BURI PARA, ASHULIA, SAVAR Other Factories: ne June 1, 2014 Page 2 Fire Safety Inspection Report Introduction manufacturing complex was
More informationESCAPE WAYS IN RESIDENTIAL BUILDINGS
ESCAPE WAYS IN RESIDENTIAL BUILDINGS 1. Fire safety solution a) Division of buildings into fire compartments and determination of fire safety degree b) Comparison of standard and design requirements on
More informationSAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.
SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22
More informationCertification Assessment Instrument and Guidelines
Certification Instrument Full compliance with BCA 96 will ensure passing 19 for Section 1 Do not need 100 to pass 1 SECTION 1 SAFETY (25 POINTS) Residential Fire Sprinkler System Not required to pass Section
More informationINITIAL FIRE SAFETY ASSESSMENT - EXPANSION
INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Plot 47-52 & 68-73, KEPZ North Patenga Chittagong Chittagong 06 Mar 2017 The Alliance for Bangladesh Worker Safety Page 1/23 06 Mar 2017 Introduction
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed
More informationTechnical write-up on Fire safety services
1. General: Technical write-up on Fire safety services Nitesh Santa Clara, proposed development is a residential apartment with multiple blocks. Document briefs on fire safety systems envisaged for the
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationFire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan
Fire Risk Assessment Worksafe Solutions Consultancy Ltd 67 Flitwick Road Maulden Bedfordshire, MK45 2BJ Tel: 01525 406787 email enquiries@worksafesoultions.co.uk Index Part 1 Introduction Part 2 The Fire
More informationBUILDING FIRE STRATEGY (Operational & Fire Engineering Information)
Safety Services Fire Safety Fire Strategy for: 132 Hampstead Road (317) UNIVERSITY COLLEGE LONDON BUILDING FIRE STRATEGY (Operational & Fire Engineering Information) Regulatory Reform (Fire Safety) Order
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT
OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible
More informationINITIAL FIRE ASSESSMENT REPORT (FAR)
INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction
More informationSome Important Aspects of Fire Safety Regulations about High Rise Buildings
Some Important Aspects of Fire Safety Regulations about High Rise Buildings Tokyo University of Science Prof. Kyoichi Kobayashi (Dr. of Engineering) Many high rise buildings are being built with awful
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the
More informationBlue Whirl Building. General Fire Safety Checklist. conducted for. Location 1029 McLean Ave, Dallas, TX 75211, USA. Visit 20 Sep :08 PM
General Fire Safety Checklist conducted for Blue Whirl Building Location 1029 McLean Ave, Dallas, TX 75211, USA Visit 20 Sep 2018 03:08 PM Prepared by SafetyCulture Staff Completed on 20 Sep 2018 03:58
More informationTechnical Seminar on the Code of Practice for Fire Safety in Buildings 2011
Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 The Code of Practice for Fire Safety in Buildings 2011 The FS Code comprises 7 parts and 1 annex: Part A Introduction Part B
More informationCHAPTER 8: RISK ASSESSMENT & EMERGENCY PREPAREDNESS PLAN
CHAPTER 8: RISK ASSESSMENT & EMERGENCY PREPAREDNESS PLAN RISK ASSESSMENT The phases of an emergency includes: 1. Risk assessment 2. Mitigation 3. Preparedness 4. Response 5. Recovery Areas of Risk includes:
More informationUnit 2 Fire Safety (Zone 1)
IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 1) Examiner Report March 2018 Introduction 42% of candidates attained a Pass. Half of the candidates that attained a Pass secured
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed
More informationSection 7 - Fire Maintenance Checklist
Please work through these checklists as required. Where the answer to any question is NO this indicates a potential hazard through lack of maintenance controls. If unsure that a question relates to your
More informationFIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES
FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document
More informationFire protection documentation. CFPA-E Guideline No 13:2015 F
Fire protection documentation CFPA-E Guideline No 13:2015 F FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation in the
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More informationNirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection
Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of
More informationRISK ASSESSMENT & EMERGENCY PREPAREDNESS PLAN
RISK ASSESSMENT & EMERGENCY PREPAREDNESS PLAN RISK ASSESSMENT The phases of an emergency includes: 1. Risk assessment 2. Mitigation 3. Preparedness 4. Response 5. Recovery Areas of Risk includes: Naturally
More informationDesign Guidelines Fire Safety in New and Refurbished Buildings
Design Guidelines Fire Safety in New and Refurbished Buildings Introduction All major new or refurbishment projects must comply with the Technical Standards (Scotland) Regulations as a matter of course.
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Cha 72/1/C, Ground-4th FL, Progoti Swarani, Uttar Badda, Dhaka Dhaka The Alliance for Bangladesh Worker Safety Page 1/16 Introduction to the Report The following report contains
More informationPrescriptive Requirement for Smoke Control
HKIE CPD Training Course (II) 7July 2009 Organization by The Hong Kong Institution of Engineers Fire Division Co-organized by the Association of Registered Fire Services Installation contractors of Hong
More informationFIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH
FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH January 3, 2014 Redpoint Jackets Ltd. PAGE 1 SUMMARY The four story factory housing Redpoint Jackets Ltd. located in Dhaka Export Processing
More informationOur Ref: CD/FSSD/12/02/03/01 DID: FAX:
Our Ref: CD/FSSD/12/02/03/01 DID: 68481407 FAX: 68481493 14 Jan 2010 Registrar, Board of Architects (BOA) Registrar, Professional Engineers Board (PEB) President, Singapore Institute of Architects (SIA)
More informationFire. IMO fire control signs - according to IMO Resolution A.654 (16) (mm) 150x x200
IMO fire control signs - according to IMO Resolution A.654 (16) Safety and operating instructions for trained personnel (SIS) - As per ISO 24409, SIS signs are safety-related signs that replicate the symbols
More informationCase Study 1 Underground Car Park
Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building
More informationLYHA Fire Safety Policy
LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with
More informationAccreditation Program: Hospital
ccreditation Program: Hospital Life Safety 2008 The Joint ommission on ccreditation of Healthcare Organizations ccreditation Program: Hospital hapter: Life Safety Standard LS.0001 The [organization] designs
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker
More informationFIRE RISK ASSESSMENT
FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter
More informationEQUIVALENT INITIAL FIRE SAFETY ASSESSMENT
EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20
More informationIndependent Living Scheme Fire Risk Assessment. General needs residential sleeping accommodation
Sutton House 1 Forster Street Radford ttingham NG67 3DQ At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory fire
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationFire Risk Assessment
Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email
More informationSURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin
SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites
More informationThe Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex:
The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: Mr. Junkers Lam Senior Building Surveyor of Buildings Department (9 Sept 2013) Part A Introduction Part B Means
More information8.1. Fire and Heritage. The maintenance series. Information sheet. Guidelines on Fire Safety in Heritage Buildings
The maintenance series Information sheet 8.1 Fire and Heritage Destruction of the Prince of Wales Theatre by fire on 3 October 1860. It was situated at the corner of King and Castlereagh Streets, Sydney.
More informationMWL Consulting Company
MWL Consulting Company NFPA Member since1990 Fire Service Section Fire Marshal (retired) Newport Fire Department Michael W. Leber 17 Whitwell Avenue Newport, RI 02840 Mobile Phone 401-439-5322 mlebernpt@aol.com
More informationPLAN REVIEW SUBMITTAL GUIDE
PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT KAROONI KNIT COMPOSITE RATANPUR, SHAFIPUR KALIAKOIR OTHER FACTORIES: NONE April 5, 2014 Page 2 SUMMARY was surveyed for fire safety on 4/5/2014 by Hughes Associates, Inc.
More informationElement C3.5 Means of Escape
.5 Means of Escape RRFSO Article 14 Legal Factors Responsible person must ensure routes to emergency exits and exits themselves are kept clear at all times Exits must directly lead to place of safety Safe
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationIndependent Living Scheme Fire Risk Assessment. Independent living sheltered residential accommodation and public library
Independent Living Scheme Fire Risk Assessment Strelley Court Strelley Road Strelley ttingham NG8 3BJ At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly
More informationNYU RESIDENTIAL FIRE SAFETY PLAN PART I - BUILDING INFORMATION SECTION
BUILDING ADDRESS: BUILDING OWNER: Name: Address: Telephone : NYU RESIDENTIAL FIRE SAFETY PLAN PART I - BUILDING INFORMATION SECTION Greenberg Hall 545 First Avenue, NY, NY, 10016 New York University 70
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT GLOBAL OUTWEAR LTD. PLOT # M/1, ROAD # 7, SECTION # 7, MIRPUR, DHAKA March 3, 2014 Accord - Bangladesh RMG Fire Safety Inspection Global Outwear Ltd. Page 2 SUMMARY Global
More informationCommon Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive.
Common Fire Code Violation Checklist Listed are some of the most commonly found fire code violations and should not be considered as all inclusive. Exterior Features All fire access roads signed per TFD
More informationCURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES
CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES EMERGENCY MANAGEMENT DESIGN GUIDELINES 000331 Details of revisions Level Details Date Initial 1 Document created from 20150513NewBuildsAndRedevelopments.docx
More informationAS 2419 OVERVIEW OF PROPOSED CHANGES. Gary Nenadovich Director G N Consulting
AS 2419 OVERVIEW OF PROPOSED CHANGES Gary Nenadovich Director G N Consulting Disclaimer FPA Australia's policy is one of continuous improvement, details of products, procedures or methods described within
More informationIAAI/USFA Abandoned Building Project
IAAI/USFA Abandoned Building Project FD Operations in Vacant/Abandoned Buildings Presentation Outline Introduction This lesson is intended to introduce fire department personnel to the conditions that
More informationFire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /)
Fire resistance (A copy of this is available on www.routledge.com/books/details/ 9780415809696/).1 Fire resistance The overall aim of fire safety precautions is to ensure that: all corridor doors shall
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Name: Assessor: Anzir Apparels Limited, Unit-1 Karim supermarket, Baipal, Baipal, Savar Savar Dhaka Bangladesh Emkay Enterprises 30 Apr 2014 The Alliance for Bangladesh
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 107/112 Nazrul Market 1st & 2nd floor, Chawk Bazar, Chittagong Emkay Enterprises 09 Apr 2014 The Alliance for Bangladesh Worker Safety Page 1/28 Factory
More informationINITIAL FIRE ASSESSMENT REPORT (FAR)
INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh
More informationNEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS
Mandatory Fire Safety Instruction NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Reference A: Reference B: Approved Document B
More information150 Elgin - Office Tower and Grant House Renovations
APPLICATION OF THE ONTARIO BUILDING CODE 150 Elgin - Office Tower and Grant House Renovations 150 Elgin Street Ottawa, Ontario Presented to: Mr. Brandon Donnelly Morguard Investments Limited c/o Mr. Harry
More informationTYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)
TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May
More informationEmergency Evacuation Plan. Tiffany Tower Plot W2 Jumeirah Lakes Towers
Emergency Evacuation Plan Tiffany Tower Plot W2 Jumeirah Lakes Towers September 2017 TABLE OF CONTENTS 1.0 I N T R O D U C T I O N... 1 2.0 B U I L D I N G I N F O R M A T I O N... 1 3.0 F I R E S Y S
More informationLetter of Recognition
Letter of Recognition The on Fire and Building Safety () hereby recognizes that: KARIM TEXTILES LIMITED (9297) orbag, Kaliakoir, Gazipur Has successfully completed all remediation measures required from
More informationDesign of Fire safety in Multi Occupancy Residential Accommodation
Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability
More informationMeasures (ILSM) Process
Managing the Interim Life Safety Measures (ILSM) Process 1 A Program for The Texas Association of Healthcare Facility Management Monday, April 30, 2012 Robert H. Bartels, CHFM CHSP CHEP SASHE President,
More information22 BISHOPSGATE Lift Evacuation Strategy
June 28, 2018 22 BISHOPSGATE Lift Evacuation Strategy Romain Hourqueig, Head of UK Fire Engineering Neil Allardice, Senior Fire Engineer AGENDA The project Fire Safety Strategy Why lift evacuation? The
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT A-PLUS IND LTD PLOT # 28, MILK VITA ROAD, SECTION #07, MIRPUR, DHAKA - 1216, BANGLADESH March 10, 2014 Page 2 SUMMARY was surveyed for fire safety on 3/10/2014 by Hughes Associates,
More informationFirefighting operations on construction sites F5-12 GD
DESIGNER S GUIDE Firefighting operations on construction sites F5-12 GD Introduction When to use Scope The purpose of this chapter is to provide a consistent Fire and Emergency New Zealand position on
More informationFire Risk Assessment (FRA) Checklist
Fire Risk Assessment (FRA) Checklist Assessed by: Job Title: Department/Location: Date Document Downloaded: Date of Assessment: Duty Holder Name: FRA. Description / Comments FHRA. 1. MANAGEMENT, PLANNING
More informationSlight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk
Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action
More informationHealth, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service
Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in
More information